Loading...
HomeMy WebLinkAboutEVALUATION REPORTSProduct Evaluation Report S GULF COAST SUPPLY & MANUFACTURING, LLC. CgIN, St 4e yoEO UCi 26 Ga. SV Crimp Roof Panel over 15132" Plywood Unty Florida Product Approval #11651.13 R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 —D Category: Roofing Subcategory: Metal Roofing Compliance Method: 61G20-3.005(1)(d) NON HVHZ Product Manufacturer: Gulf Coast Supply & Manufacturing, 14429 SW 2nd Place, Suite G30 Newberry, FL 32669 Engineer Evaluator: Dan Kuhn, P.E. #75519 Florida Evaluation ANE ID: 10743 Validator: Locke Bowden, P.E. #49704 9450 Alysbury Place Montgomery, AL 36117 Contents: Evaluation Report Pages 1 — 5 LLC. N1EL Si"'�', -0 51� A = STATE'OF Q: %IFS+ .�OR10P S ""i I I I L Ei t' 10/05/2017 Compliance Statement: The product as described in this report has demonstrated compliance with the Florida Building Code 2017, Sections 1504.3.2. Product Description: 5V Crimp Roof Panel, 26 Ga. Steel, 24" Coverage, through fastened roof panel with fasteners in the panel flat over minimum 15/n" plywood decking. Non Structural application. Panel Material/Standards: Material: Minimum 26 Ga. Steel, ASTM A792 or ASTM A653 G90 conforming to Florida Building Code 2017 Section 1507.4.3. Paint Finish Optional Yield Strength: 80.0 ksi Corrosion Resistance: Panel Material shall comply with Florida Building Code 2017, Section 1507.4.3. Panel Dimension(s): Thickness: 0.018" Minimum Width: 24" Coverage Rib Height: 3/s" Major Rib Panel Fastener: #9-15x1.5" with sealing washing in the flat of the panel or approved equal, 1/4" minimum penetration through plywood. , Corrosion Resistance: Per Florida Building Code 2017, Section 1506.6, 1507.4.4 Substrate Description: Design Uplift Pressures: Minimum 15A2" thick, APA Rated plywood over supports at maximum 24" O.C. Design of plywood and plywood supports are outside the scope of this evaluation. Must be designed in accordance w/ Florida Building Code 2017. Table "A" Fastener Pattern p12"-12" MON Design Pressure includes a Safety Factor = 2.0. Code Compliance: The product described herein has demonstrated compliance with the Florida Building Code 2017, Sections 1504.3.2. Evaluation Report Scope: The product evaluation is limited to compliance with the structural wind load requirements of the Florida Building Code 2017, as relates to Rule 61 G20-3. Performance Standards: The product described herein has demonstrated compliance with: • UL 580-06 - Test for Uplift Resistance of Roof Assemblies • UL 1897-12 - Uplift Test for Roof Covering Systems. Reference Data: 1. UL 580-94 / 1897-98 Uplift Test .Force Engineering & Testing, Inc. (FBC Organization # TST-5328) Report No. 117-0053T-05 & 117-0331T-08 2. Certificate of Independence By Dan Kuhn, P.E. (FL# 75519) @ Kuhn Engineering, LLC (FBC Organization # ANE ID: 10743) Test Standard Equivalence: 1. The UL 580-94 test standard is equivalent to the UL 580-06 test standard 2. The UL 1897-98 test standard is equivalent to the UL 1897-12 test standard. Quality Assurance Entity: The manufacturer has established compliance of roof panel products in accordance with the Florida Building Code and Rule 61 G20-3.005(3) for manufacturing under a quality assurance program audited by an approved quality assurance entity. Minimum Slope Range: Minimum Slope shall comply with Florida Building Code 2017, including Section 1507.4.2 and in accordance with Manufacturers recommendations. For slopes less than 3:12, lap sealant must be used in the panel side laps. Installation: Install per Manufacturer's recommended details. Underlayment: Shall comply with Florida Building Code 2017 section 1507.1.1. Roof Panel Fire Classification: Fire classification is not part of this acceptance. Shear Diaphragm: Shear Diaphragm values are outside the scope of this report. Design Procedure: For roofs within the parameters listed on the load table, fastening pattern must at a minimum meet those listed for the applicable wind zone. For all roofs outside the parameters listed on the load table, design wind loads shall be determined for each project in accordance with FBC 2017 Section 1609 or ASCE 7-10 using allowable stress design. The maximum fastener spacing listed herein shall not be exceeded. This evaluation report is not applicable in High Velocity Hurricane Zone. Refer to current NOA or HVHZ evaluation report for use of this product in High Velocity Hurricane Zone. a ENGINEER LOAD TABLE: 26 Ga. 5VCrimp Roof Panel over 15/32" Plywood .!£+ �L�J s.. 120 .:}.� ^, rv•Y 130 ;ia � �f1"e'F' 140 "J. n 150 2� 160 ...M'1�i .�4'.£1k 170 11�..�Am`�.}{'N; 180 WIIND FASTENER (MIN.enetratiodon) SUBSTRATE SPEED P 1 (MIN. 15/32" ON CENTER SPACING ON CENTER SPACING ON CENTER SPACING ON CENTER SPACING ON CENTER SPACING ON CENTER SPACING ON CENTER SPACING '4 -a Y YL - - pT.' �yxy �'rf.'{i' 'ia�' a 'e`iFr ; -TA§5" ' P . ZONE 2 #9-15x1.5" Plywood 16" TYPE 1 16" TYPE 1 16" TYPE 1 16" TYPEA 16" TYPE 1 16" TYPE 1 16" TYPE 1 ,� '� "Uk' 'Y4 Yvrn .#r ri.YSJ+%St N k P �33CM1W 1.) PANEL DESCRIPTION: 5V CRIMP, MIN. 26 GA., GRADE 80, 24"COVERAGE. 2.) PANEL FASTENER: #9-15X1.5" HWH WITH SEALING WASHER W/ MIN. A" PENETRATION. 3.) MAXIMUM ALLOWABLE PANEL UPLIFT PRESSURE: -94.25 PSF® 16" O.C. FASTENER SPACING TYPE 1 FASTENER PATTERN, -131.0 PSF @16" O.C. FASTENER SPACING TYPE 2 FASTENER PATTERN BASED ON TAS 125, UL 580/UL 1897 TESTING. 4.) PLYWOOD DECKING: MIN. 15/32" THICK PLYWOOD MUST BE DESIGNED IN ACCORDANCE WITH FLORIDA BUILDING CODE 2017. 5.) ROOF SLOPE: ON ROOF SLOPES LESS THAN 3:12, LAP SEALANT MUST BE USED IN PANEL SIDE LAPS. 6.) LOAD TABLE BASED ON WIND PRESSURES CALCULATED PER ASCE 7-10 (KD = 0.85) MULTIPLIED BY 0.6 PER FLORIDA BUILDING CODE 2017. ZONE ZONE3 is l' r i �j \� RIDGE i� ,�/I I i ZONE 1 i__________________-- _.EAVE ZONE 2 GABLE ROOF a I Note: Dimension (a) is defined as 10% of the minimum width of the building or a 40% of the mean height of the roof, whichever is smaller, however, (a) cannot be less than either 4% of the minimum width of the building or 3 feet. --- --------------� a ZONE i I I --------------------- TYPE1 FASTENER PATTERN F 112111-1/2f HWH w/121'In Washer At Panel Lap=/- � TYPE 2 FASTENER PATTERN (1) #9-15 x 1-1/2" HWH w/Sealing Washer CREEK �l i� Certificate of Authorization bur 29824 f1��1 IK 17520 Edinburgh Drive Tampa, FL 33647 TECHNICAL SERVICES, LLC (813) 480-3421 EVALUATION REPORT FLORIDA BUILDING CODE, 6'" EDITION (2017) Manufacturer: OWENS CORNING ROOFING AND ASPHALT LLC Issued October 11, 2017 1 Owens Corning Parkway Toledo, OH 43657 (800)438-7465 www.owenscorning.com Manufacturing Location: Brentwood, NH SCANNED Houston, TX BY St. Lucie County Quality Assurance: UL LLC (QUA9625) SCOPE Category: Roofing Subcategory: Underlayments Code Sections: 1504.3.1. 1507.1.1 Properties: Physical properties REFERENCES Enti Report No. Standard Year PRI Construction Materials Technologies (TST5878) NEI-039-02-01 ASTM D 1970 2015 PRI Construction Materials Technologies (TST5878) NEI-042-02-01REV2 ASTM D 1970 2015 PRI Construction Materials Technologies (TST5878) NEI-045-02-01 TAS 103 1995 PRI Construction Materials Technologies (TST5878) NEI-045-02-01 ASTM G 155 2005a PRI Construction Materials Technologies (TST5878) NEI-053-02-01 TAS 103 1995 PRI Construction Materials Technologies (TST5878) NEI-053-02-01 ASTM G 155 2005a PRI Construction Materials Technologies (TST5878) NEI-093-02-02 ASTM D 1970 2015 PRI Construction Materials Technologies (TST5878) OCF-213-02-01 ASTM D 1623 2009 PRI Construction Materials Technologies (TST5878) OCF-237-02-01 UL 1897 2012 PRI Construction Materials Technologies (TST5878) OCF-252-02-01 ASTM D 4798 2001 PRI Construction Materials Technologies (TST5878) OCF-252-02-01 ASTM D 1970 2015 PRI Construction Matedals Technologies (TST5878) OCF-253-02-02 ASTM D 1970 2015 PRI Construction Materials Technologies (TST5878) OCF-272-02-01 TAS 103 1995 PRI Construction Materials Technologies (TST5878) OCF-296-02-02 ICC-ES AC 188' 2012 PRI Construction Materials Technologies (TST5878) OCF-297-02-01.1 ICC-ES AC 48 ASTM D 1970 2012 2015 PRI Construction Materials Technologies (TST5878) OCF-318-02-01 ASTM D 1970 2015 PRI Construction Materials Technologies (TST5878) OCF-320-02-01 TAS 103 1995 PRI Construction Matedals Technologies (TST5878) OCF-320-02-01 ASTM G 155 2005a PRI Construction Matedals Technologies (TST5878) OCF-321-02-01 ASTM D 1623 2009 PRI Construction Materials Technologies (TST5878) OGF-322-02-01 UL 1897 2012 PRI Construction Materials Technologies (TST5878) 'Determined OCF-355-02-01. UL 1897 2012 to be equivalent to ASTM D 226-09, Type I and II _ _....--_.__ roman r-K 11 Page 1 of 4 This evaluation report is provided for Stale of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, Installation, recommended use, or other product attributes that are not specifically addressed herein. GREET{ TECHNICAL SERVICES, LLC PRODUCT DESCRIPTION AND LIMITS OF USE OWENS CORNING ROOFING AND ASPHALT LLC WeatherLock® Self -Sealing Ice & Water Barriers WeatherLock® G WeatherLock® G is an ASTM D 1970 self-adhesive underlayment constructed from SBS (Brentwood, NH) modified asphalt, a fiberglass mat reinforcement and surfaced with granules. The product is supplied in 2-sq, rolls with nominal dimensions of 3-ft x 66.7-ft. WeatherLock® G is permitted to be used as prescribed in FBC Section 1507.1.1 for mechanically attached roofing coverings. Exposure on the roof deck shall be limited to a maximum 30 days. WeatherLock® Mat WeatherLock® Mat is an ASTM D 1970 self-adhesive underlayment constructed from (Brentwood, NH or SBS modified asphalt with a fiberglass mat reinforcement. The product is supplied in 1- Houston, 7X) sq. rolls with nominal dimensions of 3-ft x 33.3-ft and 2 sq. rolls with nominal dimensions of 3-ft x 66.7-ft. WeatherLock® Mat is permitted to be used as prescribed in FBC Section 1507.1.1 for mechanically attached roof coverings. Exposure on the roof deck shall be limited to a maximum 30 days. WeatherLock® Metal WeatherLock® Metal is an ASTM D 1970 self-adhesive underlayment constructed from (Brentwood, NH) SBS modified asphalt with a fiberglass mat reinforcement and plastic film surface. The product is supplied in 2.0 sq. rolls with nominal dimensions of 3-ft x'66.7-ft. WeatherLock® Metal is permitted to be used as prescribed in FBC Section 1507.1.1 for mechanically attached roof coverings. Exposure on the roof deck shall be limited to a maximum 90 days. DT>Q WeatherLock® Specialty Tile & Metal is an ASTM D 1970 self-adhesive underlayment l constructed from SBS modified asphalt and surfaced with a non -woven polyester fabric. The product is supplied in 2.14 sq. rolls with nominal dimensions of 3-ft x 71.3-ft. WeatherLock® Specialty Tile & Metal is permitted to be used as prescribed in FBC Section 1507.1.1. WeatherLock® Specialty Tile & Metal is permitted to be used with adhered clay or concrete tile roofing using either ICP Adhesives Polyset AH-160 (ICP Adhesives and Sealants, Inc.) or TILE BONDT" Roof Tile Adhesive (The Dow Chemical Company). Exposure on the roof deck shall be limited to a maximum 90 days. The maximum roof slope shall be 6:12 when used with clay or concrete tile installations without battens. Tile shall be stored on battens for roof slopes greater than 6:12. Tiles shall not be stacked greater 10 tiles per stack. WeatherLock® G (High WeatherLock® G (High Tear) is a self -adhered, underlayment used as an alternative to Tear) ASTM D 226, Type I or Type II roofing felt and ASTM D 1970 self -adhering polymer (Houston, 7)0 modified bitumen underlayment. The underlayment is composed of SBS modified asphalt with a fiberglass mat internal reinforcement and is surfaced with granules. The product is supplied with a nominal thickness of 50 mils in 1.95-sq rolls with nominal dimensions of 3-ft x 65-ft. WeatherLock® G (High Tear) is permitted to be used as prescribed in FBC Section 1507.1.1 for mechanically attached roof coverings. Exposure on the roof deck shall be limited to a maximum 30 days. FL9777-R11 2 of 1 1 - uvalueuun report is prowaea Tor State or Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. ;x CREEK TECHNICAL SERVICES, LLC PRODUCT APPLICATION OWENS CORNING ROOFING AND ASPHALT LLC WeatherLock@ Self -Sealing Ice & Water Barriers Min. Roof Slope: 2:12 in accordance with the FBC Application: All underiayments shall be installed in accordance with the FBC. Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck shall be checked for protrusion and corrected prior to underlayment application. Prior to beginning installation, the underlayment shall be unrolled and allowed to relax for a minimum of 3-5 minutes. The underlayment shall be installed with the release backer removed and pressed finely into place to ensure complete contact with the deck. The underlayment shall be installed with the roll length parallel to the eave, ,starting at the eave, and with minimum 3" side laps and minimum 6" end laps staggered min. 6-ft.from preceding course. Additionally, if applying WeatherLock® Specialty Tile & Metal, end laps shall be primed with ASTM D 41 primer or sealed with asphalt roof cement a minimum of 34 inches across the width of the lap. It is permissible to back nail the underlayment 12-inches on -center as needed (nails shall be installed perpendicular to deck with the nail heads flush to the top surface of the underlayment). Additionally, WeatherLock® Specialty Tile & Metal shall be back nailed when installed on roof slopes greater than 3:12. Min. Application 40"F; Contact the manufacturer when installing at temperatures below the minimum Temperature: application temperature. WIND RESISTANCE The Maximum Design Pressures shown below were calculated using a 2:1 margin of safety per FBC Section 1504.9 Underlavment System No 1 — WeatherLock Specialty Tile & Metal Only Roof Deck: Min. 15/32-inch COX plywood attached to wood supports spaced a maximum 24" o.c. Underlayment: WeatherLock® Specialty Tile & Metal shall be applied in accordance with manufacturer's installation instructions to the fastened deck and backnailed along the selvage with minimum 12ga., 1-1/4-inch galvanized ring shank roofing nails through optionally primed, 32ga. x 1-5/8-inch 0 tin caps spaced 12" o.c. The applied underlayment shall be rolled with a minimum 751b steel roller immediately following application. Maximum Design -142.5 psf Pressure: 11.1 , ,-rc a Page 3 of 4 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report invalid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. 11,V CREEK TECHNICAL SERVICES, LLC OWENS CORNING ROOFING AND ASPHALT LLC WeatherLockO Self -Sealing Ice & Water Barriers GENERAL LIMITATIONS 1) This evaluation report is not use in the HVHZ. 2) Fire Classification is not within the scope of this evaluation. 3) Installation of the evaluated product shall comply with this report, the FBC, and the manufacturers published application instructions. Where discrepancies exist between these sources, the more restrictive and FBC compliant installation detail shall prevail. 4) The roof deck shall be constructed of closely fitted plywood sheathing for new or existing construction. 5) The space under the deck area shall be properly ventilated in accordance with the FBC requirements. 6) All side lap seams shall be installed to shed water from the deck. 7) The underlayment may be used as described in other current FBC product approval documents. 8) Design wind load pressures shall be determined for components and cladding in accordance with FBC 1609. 9) The roof deck shall be designed by others in accordance with FBC requirements to resist the design wind load pressures for components and cladding. 10) Maximum Design Pressures for a given underlayment shall meet or exceed the design wind loads determined for the roof assembly. 11) All products listed in this report shall be manufactured under a quality assurance program in compliance with Rule 61 G20-3. COMPLIANCE STATEMENT The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building Code 6'" Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer. OP,,PFY IRup4F ee E ni 2017.10. No 74021 = 09:06:29 ��. STATE OF tt�` _041001 •�,p'. c p : ���` Zachary R. Priest, P.E. ,,,e &%9/ NALE��`�,,` Organization FloridNo.lANE9641 on No. 2111111111 CERTIFICATION OF INDEPENDENCE CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing products under this evaluation. CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under this evaluation. Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products under this evaluation. Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. END OF REPORT FL9777-Rll 4 of This evaluation report is provided for Stale of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, Installation, recommended use, or other product attributes that are not specifically addressed herein.