HomeMy WebLinkAboutGENERAC PAPERWORK11:
GENE RAC®
16/20/22 W RECEIVED GUARDIAN° SERIES
JAN 0 7 'C 019 Residential Standby Generators
ST. L-deie Gounty, Permitting Air -Cooled Gas Engine
INCLUDES:
• True Power" Electrical Technology
• Two Line LCD Multilingual Digital
Evolution"4 Controller (English/Spanish/
French/Portuguese)
• Two Transfer Switch Options Available:
100 Amp, 16 Circuit Switch or
200 Amp Service Rated Smart Switch.
See Page 4 for Details.
• Electronic Governor
Standby Power Rating
Models G007036-0, 0007037-0 (Aluminum - Bisque) -16 kW 60 Hz
Model G007035-0 (Aluminum - Bisque) -16 MN 60 Flz
Models G007039-0, G007038-0 (Aluminum
Models G007043-1, G007042-1 (Aluminum
ST.LUCIE COUNTY
PLAN REVIEW
• System Status & Maintenance Interval LED
Indicators
BLDG:
DATE:
• Sound Attenuated Enclosure
• Flexible Fuel Line Connector
EL
DATE:/'�
• Direct -To -Dirt Composite Mounting Pad
PLUMB:
• Natural Gas or LP Gas Operation
DATE:
• 5 Year Limited Warranty
MECH:
• Capability to be installed within 18" (457 mm)
of a building*
FEATURES
O INNOVATIVE ENGINE DESIGN& RIGOROUS TESTING are at the heart of Generac's O
success in providing the most reliable generators possible. Generac's G-Force engine
lineup offers added peace of mind and reliability for when you need It the most. The
G-Force series engines are purpose built and designed to handle the rigors of
extended run times In high temperatures and extreme operating conditions.
O TRUE POWER- ELECTRICAL TECHNOLOGY: Superior harmonics and sine wave O
form produce less than 5%Total Harmonic Dislodion for utility quality power. This allows
confident operation of sensitive electronic equipment and micro -chip based appliances,
such as variable speed HVAC systems.
Bisque) - 20 kW 60 Flz
Bisque) - 22 kW 60 Hz
SCANNED
BY
'Lbde County
GENERAC'
C(S)Vs Q PISLT-EST.
�[' [_.
LISTED IJI��LJ�.
Note: CUL certimcatisn Only applies to unbundled units and units packaged with
limited circuit switches. Units packaged with the Smad Switch are UL cadged in
the USA only.
"Ony If located away from doors, windows and fresh air intakes,
end unless otherwise directed by local codes.
SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION:
This state-of-the-art power maximizing regulation system is standard an
all Garofalo models. It provides optimized FAST RESPONSE to changing
load conditions and MAXIMUM MOTOR STARTING CAPABILITY by
electronically torque-malching the surge loads to the engine. Digital
voltage regulation at ±1%.
SINGLE SOURCE SERVICE RESPONSE from Generec's extensive dealer
network provides parts and service know-how for the entire unit, from the
engine ki the smallest electronic component.
O TEST CRITERIA: O GENERAC TRANSFER SWITCHES: Long life and reliability are
V PROTOTYPE TESTED If NEMA MG1.22 EVALUATION synonymous with GENERAC POWER SYSTEMS. One reason for this
V SYSTEM TORSIONAL TESTED V MOTOR STARTING ABILITY confidence Is that the GENERAC product line Includes its own transfer
systems and controls for total system compatibility.
w GENERAC atT3 ��ry.
PROMISE y0: Mobib ry
"o ay Link
�PN[P P" �HPP
•bull/P Iev UG uvNp lawn!/vvnf/anlpn pnN.
16/20/22 kW
GENERAC°
features and benefits
Engine
• GeneracG-Force design
Maximizes engine "breathing" for increased fuel efficiency. Plateau honed cyllnderwallsandplasma molyringshelps theengine
run cooler, reducing oil consumption resulting in longer engine life.
• "Spiny-lok" cast iron cylinder walls
Rigid construction and added durability provide long engine life.
• Electronic Ignition/spark advance
These features combine to assure smooth, quick starting every time.
• Full pressure lubrication system
Pressurized lubrication to all vital bearings means better performance, less maintenance and longer engine life. Now featur-
ing up to a 2 year/200 hour oil change interval.
• Low oil pressure shutdown system
Shutdown protection prevents catastrophic engine damage due to low oil.
• High temperature shutdown
Prevents damage due to overheating.
Generator
• Revolving field
Allows for a smaller, light weight unit that operates 25% more efficiently than a revolving armature generator.
• Skewed stator
Produces a smooth output wavelorm for compatibility with electronic equipment.
• Displaced phase excitation
Maximizes motor starling capability.
• Automatic voltage regulation
Regulates the output voltage to ±1 % prevents damaging voltage spikes.
• UL2200listed
For your safety.
Transfer Switch (if applicable)
•
Fully automatic
Transfers your vital electrical loads to the energized source of power.
•
NEMA3R
Can be installed inside or outside for maximum flexibility.
•
Remote mounting
Mounts near your existing distribution panel for simple, low-cost installation.
Evolution'" Controls
•
Auto/Manual/Off illuminated buttons
Selects the operating mode and provides easy, at -a -glance status Indication in any condition.
•
Two-line LCD multilingual display
Provides homeowners easily visible logs of history, maintenance and events up to 50 occurrences.
•
Sealed, raised buttons
Smooth, weather -resistant user interface for programming and operations.
•
Utility voltage sensing
Constantly monitors utility voltage, setpoints 65%dropout, 80%pick-up, of standard voltage.
•
Generator voltage sensing
Constantly monitors generator voltage to ensure the cleanest power delivered to the home.
•
Utility interrupt delay
Prevents nuisance start-ups of the engine, adjustable 2-1500 seconds from the factory default selling of 5 seconds b a
qualified dealer. y
• Engine warm-up
Ensures engine is ready to assume the load, selpoint approximately 5 seconds.
• Engine cool -down
Allows engine to cool prior to shutdown, selpoint approximately 1 minute.
• Programmable exercise
Operates engine to prevent oil seal drying and damage between power outages by running the generator for 5 minutes every
other week Also offers a selectable selling for weekly or monthly operation providing flexibility and potentially lower fuel
costs to the owner.
• Smart battery charger
Delivers charge to the battery only when needed at varying rates depending on outdoor air temperature.
Compatible with lead acid and AGM -style batteries.
• Main line circuit breaker
Protects generator from overload.
• Electronic governor
Maintains constant 60 Hz frequency.
Unit
• SAE weather protective enclosure Sound attenuated enclosures ensure quiet operation and protection against mother nature, withstanding winds up to 150
mph. Hinged key locking roof panel for security. Lifl-out front for easy access to all routine maintenance Items. Electrostat-
ically applied textured epoxy paint for added durability.
• Enclosed critical grade muffler Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
• Small, compact, attractive Makes for an easy, eye appealing Installation, as close as 18" away from a building.
Installation System
• 1 it (305 mm) flexible fuel line connector Absorbs any generator vibration when connected to rigid pipe.
• Direct -to -din composite mounting pad Complex lattice design prevents settling or sinking of the generator system.
0 Integral sediment trap Prevents panicles and moisture from entering the fuel regulator and engine, prolonging engine life
GENERACa
16/20/22 kW specifications
Generator
Mode]
G007035-0, G007036.0,
G007038.0, G007039.0
6007042.1. G007043.1
Rated Maximum Continuous Power Capacity (LP)
G007037.0 (16 kW)
(20 kW)
(22 kW)
Rated Maximum Continuous Power Capacity (NO)
16,000 Watts'
20.000 Watts'
22,000
Rated Voltage
16,000 Watts"
18,000 Wafts'
19,500
Rated Maximum Continuous Load Current— 240 Volts(IP/NG)
240
66.6/66.6
240
240
Total Harmonic Distortion
83.3175
91.6/81,3
Circuit Breaker
Less than 5%
Less than 5%
Less than 5%
PMainLine
70 Amp
lag Amp
100Amp
Number of Rotor Pales
1
1
12
Rated AC Frequency
fi0
0 Hz
2
0
60 Hz
2
OH
6 2
Power Factor
Battery Requirement (not included)
1.0
UimensinsWeight (LXW
12 Volts, Group 26B 540 CCA Minimum or Group 35AGM 650 C_ CA Minimum
H)tNmm
4061186
448/203
466/211
Sound output
tix B(
Sound output in tlB(A)al23 il(7m)whh generator at normal load'
48 x 25 x 29/1218 x 638 x 732
Sound output in dB(A) at 23 it (7 m) with generator In Quiet -Test" lbw -speed exercise made* •
66
58
66
67
Exercise duration
56
58
Engine
5 min
Smin
5min
Type of ine
of
NumberofCylinders
Cylinders
GENERAC G-Force 10DO Series
CylindDisplaer Bloc
Cylinder Block
2
999 cc
2
999 cc
2
999 cc
Aluminum w/ Casl Iron Sleeve
IgnValven System
System
Overhead Valve
Overhead Valve
Overhead Valve
Goveon
System
Solid-state w/Magneto
Solid-state w/Magneto
Solid -stale w/Magneto
Compression
Compression Ratio
Electronic
Electronic
Electronic
Starter
95•1
951
Oil Capacity Including Filler
12 Vdc
12Vdc
12 Vdc
Operating rpm
Approx 1.9 gV1.8 L
Approx. 1.9 gV1.8 L
Approx. 1.9 gVi,8 L
Fuel Consumption
3,600
3,600
3,600
Natural Gas fla/hr (ma/nr)
1/2 Load
Full Load
218 (6.17)
204 (5.78)
228 (6.46)
Liquid Proone a
0 If /hr (gavhr) Who
309 (8.75)
301 (8.52)
327 9 26
(• )
1/2 Load
Full Load
91.6 (2.52) (9.53)
86 (2.37) (8.991
92 (2.53)19.671
106.8 (2.94).111.111 129.6 (3.56) [13.481 142 (3.90)114.771
Note: Fuel pipe must be sized for full load. Required fuel pressure to generator fuel inlet at all load ranges-3.5-7'weler column (7-13 mm mercury) for natural gas, 10-12'inler column (19-22 mm mercury)
for LP gas. For Btu canteru multiply 11 /hex 2500 (LP) or Ils/hrx 1000 (NG). For Meoaiaule content. mummy mach, v an ac n or ,,, ma...„— ... ,.,
2-Line Plain Text Multilingual LCD Display
Made Bultons:Auto
Manual
OR
Ready to Run/Mainlenance Messages
Engine Run Hours Indlcatlon
Programmable start delay between 2-1600 seconds
Utility Voltage Loss/fielum 10 Utility Adjustable (Brownout Setting)
Future Set Capable Exerciser/Exercise Set Error Warning
RurvAlamVMalmenance Logs
Engine Stan Sequence
Starter Cock -out
Smart Battery Charger
Charger FaulVMlssing AC Warning
Low Satiety/Battery Problem Protection and Battery Condition Indication
Automatic Voltage Regulation with Over and Under Voltage Protection
Under-Frequency/Overload/stepper Overcurrenl Protection
Safety Fused/Fuse Problem Protection
Automatic Low Oil Pressure/High Oil Temperature Shutdown
OvercrarrWOverspeed ((Q 72 Hz)/rpm Sense Loss Shutdown
High Engine Temperature Shutdown
Internal FaulVlncomect Wi u g Protection
Common External Fault Capability
Field [Intractable Firmware
Simple user interface lot ease of operation.
Automatic Start on Ulllity failure. 7 day exerciser..
Start with starlet control, mall slays on. II Oil lily falls, transfer to load lakes place.
Slaps unit. Power Is removed. Control and charger still operate.
Standard
Standard
Standard (programmable by deafer only)
From 140-171 V/190-216V
Standard
50 Events Each
Cyclic cranking: 16 sec On, 7 rest (90 Sec maximum duration).
Shaer cannot re-engage until 5 sec alter engine has slopped.
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
GENERAC`
16/20/22 kW switch options
Limited Circuits Switch Features
• 16 space, 24 circuit, breakers not Included,
• Electrically operated, mechanlcally-held contacts for fast, positive
connections
• Rated for all classes of load,100% equipment rated, both inductive and
resistive.
• 2-pole, 250 VAC contactors.
• 30 millisecond transfer time.
• Dual coil design.
• Rated for both copper and aluminum conductors.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
• NEMANL 311 aluminum outdoor enclosure allows for indoor or outdoor
mounting flexibility.
• Multi listed (or use with 1"standard, tandem, GFCI and AFCI breakers from
Siemens, Murray, Eaton and Square D for the most flexible and cost effec-
tive Install.
Dimensions
JMM679.4
M7643
th
W2
Depth
13.5
6.91
343.0
175.4
Wire Ranges
Conductor Lug Neutral Lug Ground Lug
1/0-#14 2/0-#14 2/0-#14
Service Rated Smart Switch Features
• Includes Digital Power Management Technology standard (DPM).
• Intelligently manages up to four air conditioner loads with no additional
hardware.
• Up to four more large (240 VAC) loads can be managed when used in
conjunction with Small Management Modules (SMMs).
• Electrically operated, mechanically -held contacts for fast, clean connections.
• Rated for all classes of load,100% equipment rated, both inductive and resis-
five.
• 2-pole, 250 VAC contactors.
• Service equipment rated, dual coil design.
• Rated for both aluminum and copper conductors.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
• NEMA/UL 311 aluminum outdoor enclosure allows for Indoor or outdoor mount-
ing flexibility.
Dimensions
200 Amps 1201240, 1e
netgnt I Width
Hf H2 I W1 W2 Depth
26.75 30.1 10.5 13.5 6.91
679.4 764 3 1 9997 1 9.19 n I
Model
G007035.0 (16kM
No. or Poles
2
Current Rating (Amps)
100
Voltage Raling (VAC)
120/240,10
Ulgly Voltage Monitor (Fixed)-
-Pick-up
80%
-Dmpouf
65%
Return to Uglily-
approx 15 sec
Exercises bi-weekiy for 5 minutes't
Standard
U. Listed
Standard
Total Circuits Available
24
Tandem Breaker Capabllfties
8tandems
Circuit Breaker Protected
Available INS Symmetrical
Fault Current @ 250 Volts
10,000
*Function of Evolution Controller
Exercise can be set to weekly or monthly
Model G007037.0 (16 kW)/G007039-0 (20 kW)/
G007043-0 (22 kW)
No. of Pales
2
Current Rating (Amps)
200
Voltage Rating (VAC)
120/240,10
Utility Voltage Mention (Fixed)'
-Pick -op
-Dropout
80%
Return to Utility-
65%
approx 13 sec
Exercises bf-weekly for 5 minutes'
Standard
UL Listed
Standard
Enclosure Type
NEMA/UL 311
Circuit Breaker Protected
22,000
Lug Range
250 MGM- #6
*Functon of Evolution Controller
Exercise can be set to weekly or monthly
16/20/22 kW
GENERAC
available accessories
Model # Product Description
The Wi-FI enabled LP fuel level monitor provides constant monitoring of the connected LP fuel tank. Mon.
G007005-0 Wi-FI LP Fuel Level Monitor itoring the LP tank's fuel IDvel Is an Important step in making sure your generator is ready to ran during an
unexpected power failure. Status alerts are available through a free application to notify when your LP tank
is in need of a refill.
G006463.4
Generac's Mobile Link allows you to check the status of your generator from anywhere that you have ac-
Mobile Link"
cess to an Internet connection from a PC or with any smart device. You will even be notified via e-mail or
text message when a change In the generator's status occurs. Available in the U.S. only.
6005819-0 26R Wet Cell Battery
Every standby generator requires a battery to start the system. Generac offers the recommended 26R wet
cell battery for use with all air-cooled standby product (excluding PowerPact®).
G007101-0 Battery Pad Warmer
The pad warmer rests under the battery. Recommended for use if the temperature regularly falls below 01F.
(Not necessary for use with AGM -style batteries).
G007102-0 Oil Wanner
Oil warmer slips directly over the oil filter. Recommended for use if the temperature regularly falls below
0°F.
G005621.0 Auxiliary Transfer Switch
The auxiliary transfer switch contact kit allows the transfer switch to lock out a single large electrical load
Contact Kit
you may not need. Not compatible with 50 amp pre -wired switches.
G007027-0-Bisque Fascia Base Wrap Kit
The fascia base wrap snaps together around the bottom of the new air cooled generators. This offers a
(Standard on 22 kW)
sleek, contoured appearance as well as offering protection from rodents and insects by covering the lifting
holes located in the base.
G005703-0 - Bisque Paint Kit
If the generator enclosure is scratched or damaged, it is important to touch-up the paint to protect from
future corrosion. The paint kit Includes the necessary paint to properly maintain or touch-up
a generator
enclosure.
6006486.0 Scheduled Maintenance Kit
Generac's scheduled maintenance kits provide all the hardware necessary to perform complete routine
maintenance on.a General; automatic standby generator,
G006873-0 Smart Management Module
I Smart Management Modules are used in conjunction with the Automatic Transfer Switch to Increase its
(50Amps)
power management capabilities. It provides additional power management flexibility not found in any other
power management system.
cer•TsiDeviex
dimensions & Uns
Dimensions shown are approximate. peter la installation manual lot exact dimensions. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.
FROWM W
GENE RAC Generac Power Systems, Inc, • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
02017 Genew Power systems, Inc. NI nights reserved. Ag speci0ca0ens are subject to change wnhom notice. Pan No. 10000000194•F 513117
Smart Management
Modules (SMM)
GENERAC® ACCESSORIES
Model Goo6673.0
G&
I ICTrn
mr-ati rflur If tl6l m
GeRerSmart
Ma Smart Management
Modules
Management System Is designed to optlmize the performance of a standby generator. The system can consist of up to 8lndlvldual
Smart Management Modular sly. Unlike other load management systems that depend on another control device, the 6MM modules are actually self -
aware and operate autonomously.
thFrequency is the true measure of generator engine performance and does not need to factor In Increased ambient temperatures, elevation changes or
reshold, he module wilModules
automatically follow a power management algorithm tof the power being o ensure tharoduced t the generator generators
oaded.nd if it falls below a certain
The modules can be set to a load priority between 1-8 or be sot In a IOck out Only mode for was 111111 just Slfnply do not need to fun In an oufage, therefore
reducing the necessary sine of the generator for a more cost effective solution.
SMM SPECIFICATIONS
Powers
Support
Conlaeh
Coll VA i
Coll VA i
pales....,
ReSlauve
FA.Induc
.ocked R1
if so......
240 VAC (from Une Input
...240 VA(
..........................240 VAC
• ......- ......................... 3 a
................................. 6.5
.............I..............,„ „2
I...... ...................... 50
.. 40
............. I ..... 240@240V
....I .......................... Yes
•..•...................NEMA 311
Smart
Modules
Dimensions and UPC
0 0
8MM C®ntruls (located behind the cover of the module)
B C
LED ON -LOAD OONNEGTED
PRIORITY LGOKOUr
LEDFLASBdS-LOADSNED
E LOAD ON
LED FLASH 39. 30 MIN LOOKOUT
° T GENERATOR
LEDFLAeNESd GENLDAULWKGUr
/I O
P1 T0°
LED OFF NO MODULE PDVM
LOOKOUT
TEST
DISABLED
PdodtyDiel W—
Sets andule priority.
IocWStAMI(B)—
Prsventsl0adfromoperalingvrhensyslemisoperating under generatorpowar.
Test ButIon (D)—
DIMI)I a contactor OUTPUT for a specilled Ome.
LED(D) —
Provides module slEluawith easy Nerving through the Odmal viewing window
located In Tha upper flow corner of the modulo.
®��n���a, Generac Power Systems, Inc. G 845 W29290 HWY. 59, Waukesha, WI 58189 o generac.cam
eB��II 11��+7 02016GeneracpowerSystems,Ina. An CONS resented. ADspeciAcaionsare Subject toChange without none& euaeGnOLlsom 03110rye
12
Site Selection and Preparation
Install the generator set, in Its protective enclosure,
outdoors where adequate cooling and ventilating air e— The generator must be installed on a level sur-
is
always available (Fiq;;ra z7.1). Consider these factors: face. The generator must be level within a o.5 in
° The installation of the generator must comply(73 mm) all around,
ictiY with ICC IFGC, NFPA 37, NFPA 54, NFPA — The generator. is typically placed on pea gravel,
str
58, and NFPA 70 standards, compacted soil, crushed stone, or a concrete
° Install the unit where air inlet and outlet openings pad. Check local codes to see what type Is
will not become obstructed by leaves, grass, snow, required. 1{ a concrete pad is required, all appli-
etc. If prevailing winds will cause blowing or cable codas should be followed,
drifting, consider using a windbreak to protect the Installation Guidelines for Stationary unit. Generators Air`Cooled
° Install the generator on high ground where water NFPA 37 is the The National Fire Protection
levels will not rise and endanger it. This unit should Association's standard for the installation and use of
not operate in or be subjected to standing water. stationary combustion engines. Its requirements limit the
° Allow sufficient room on all sides of the generator spacing of an enclosed generator set from a structure or
for maintenance and servicing. This unit must be wall (Ffgur: s-,),
Installed in accordance with any local, state, or NFPA 37, Section 4.1.4, Engines Located OUtd00r5:
national codes for minimum distances from other Engines, and their weatherproof housings if provided,
structures. that are Installed outdoors shall be located at least 5 ft
° Clearance from the ends and front of the generator (1.52 m
must be 3 ) from openings in walls and at least 5 ft (1.52 m
bushes, and trees. OleM). Thisce includes the back of the from structures having combustible walls. A minimum generator must be a minimum of 18 in (457 mm Separation shall not be required where the following
Clearance at the to s conditions exist:
(1,52 p houlu to a minimum of 5 1 • The adjacent wail of the structure has a fire
m) from any structureoverhang, or resistants
projections from the wall, rating of at feast one hour.
° DO NOT Install under wooden decks or structures 2. The weatherproof enclosure is constructed of
unless there is at least 5 ft 1.52 noncombustible materials and it has above the generator. ( m) of clearance demonstrated that a fire within the enclosure been
° Install the unit where rain gutter do not ignite combustible materials outside the
run-off, landscape irrigation, waterwspnnkiersroor enclosure.
sump pump discharge does not flood the unit or AnnexA Expfahato spray the enclosure, including any air inlet or outlet A4.1.4 2 ry Material
openings. () Means or demonstrating comp lance are by
means of full scale fire test or by calculation procedures.
° Install the unit where services will not be afrected
or obstructed, including concealed, underground, Because of the limited spaces that are frequently
or covered services such as electrical, fuel, phone available for Installation, It has become apparent that
air conditioning, or irrigation. This could afrQ exception er would be beneficial for many residential
and commercial Installs or
With that in mind, the
wnlYcoverage. manufacturer contracted with an Independent
° stlng
Where strong prevailing winds blow from one enclosulaboratory to
re will run full
ignite scale
fire
tests
etmateu9toutsitdhe
direction, face the generator air inlet openings to the enclosure,
the prevailing winds.
° Install the generator as close as possible to the fuel
NOTE; Southwest Research Institute testing approves
sTHAT LAWS OR CODES upply to reduce the length of piping, REMEMBER 18 In (a57 min) installation minimum from s
re
DISTANCE AND LOCATION. in absence oEGULATE P nation(ng� r recognized
Southwest Research Institute fsua
local codes regarding agencyily, recognized third .party testing and listing
recommend folgiowing these guideiines:earance, we The criteria was to determine the worst case fire scenario
install the generator as close as possible to the within the generator and to determine the ignitabflity of
transfer switch, REMEMBER THAT LAWS OR items outside the engine enclosure at various distances.
CODES MAY REGULATE THE DISTANCE AND The enclosure is constructed of
, and the results and conclusions
LOCATION, materialsfrom the
nindepen&nt testing lab Indicated that any fire within the
Installaton Guidelines For BD NzAir-Coiled Generators
generator enclosure would not pose any Ignition risk to
nearby combustibles or structures, with or without fire
service personnel response.
_® MM 2 p0 CHpm H
NOTE 3 0 GtAR. Yey°
WM 4 0 grAFL W
Wis 6 00 rgrARu. °O
a M sysr
Figure 3-2. Southwest Research Institute Marking
Based on this testing and the requirements of iVFPA 37,
Sec 4.1.4, the guidelines for installation of the generators
m) from the
listed above are changed to 18 in (457 m
back side of the generator to a stationary wall orbuilding he
rom
(C). For adequate maintenance and airflow clearance,
the area above the generator should be at least 5 ff (1.52
m) with a minimum of 3 it (0.91 m) at the front and ends
Of the enclosure. This Includes trees, shn comliano. ra and
clearance parameters couldes, Vegetation not iobstructair flow in addition, these
exhaust fumes from the generator could inhibit plant
growth. See ,cigu: a 3-Y and the installation drawing
within the owner's manual for details.
o
Automatic start-up. Disconnect utility
ower
render unit inoperable before Working on unit and
Failure to do so will result In death or serious injury.
(OOo191)
Asphyxiation, Running engines produce
carbon monoxide, a colorless, odorless,
poisonous Aas. Carbon monoxide if
C
Site Selection and Preparation
elite Preparation
° Locate the mounting area as close as possible to
the transfer switch and fuel supply.
° Leave adequate room around the area for service
access (check local code), and place high enough
to keep rising water from reaching the generator.
° choose an open space that will provide adequate
and unobstructed airflow.
Place the unit so air vents won't become clogged
with leaves, grass, snow, or debris. Verify that
exhaust fumes will not enter any building through
eaves, windows, ventilation fans, or other air
intakes (see Sff•� 8er;�
° Select the type of base, such as —but not limited
to —compacted soli, gravel, or concrete, as desired
or as required by local laws or codes, Verify your
local requirements before selecting.
Material Sufficient for Level installation
° Prepare a rectangular area approximately 5 In (127
mm) deep (A) and approximately 6 In (162 mm)
longer and wider (B) than the footprint of the
generator. Verify that the surface where the
generator will be mounted is compacted, leveled,
and will not erode over time. A concrete pad can be
Poured if desired or required.
Figure 3-3. Compacted Soft or Grave/ pad
avoided, w:l result In death or serious In 0u (NOTE: If a concrete pad Is required, follow all
(o0i 3) federal, state, or local codes. applicable
NOTE: If the generator is not set to OFF, It can crank and
start as soon as the battery cables are connected. If the
Utility power supply is not turned off, sparking can occur
at the battery posts and cause an explosion.
Installation Guidelines For 60 H AAlr-Cooled Genera
13
Site Selection and Preparation
t e&Wbn 3: Site SeleetiOn and Preparation
Site Selection
6ft(1.52m)
Figure a - .I. Insfallatfon Clearances;
iD Description
A Top 019enerator Comments
9 Front and end clearance Minimum Q clear distencas cannot Include shrubs, bushes, or ham
Rear clearance
1a M (qg] cm) minimum clearance
dictate othenNse, per r`1PPq tesdna iebedn9 and ilsdn9, unress stato or r0oat Codes
Windows and openings No operable windows, doors, or openings In the watt are permitted vdthin 5 ft 1.62 m from a
the 9eneretor. ( )
e =sung watt any point of
One -hour fire rate; watts allow closer placement of the generator set. Con
P Removable fence fum before Installation.
Removable fence panels for setvici
o Overhead clearance n9 cannot be placed less than 3 ft (0.91 m) In front of the
6 ft (1.52 m) minimum distance from any structure, overhang, orpro)eclions from the watt, generator.
DO NOT Insist' underwooden decks or structures unless this distance is fromtmaintained.
-1zb�- -
For 60 Hz Air -Cool-- d—'rators
11