EVALUATION REPORT
TRI-BUILT Materials. Group, LLC
PO Box 70
Rutherford,, NJ 07070
(800)516-1485
EXTERIOR RESEARCH & DESIGN, U.C.
Certificate of Authorization #9503
353 CHRISTIAN STREET, UNIT#13
OXFORD, CT 06478
(203)262-9245
Evaluation Report
FL16048-R6
Date of Issuance:,10/25/2012
Revision 6: 09/25/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 6v' Edition (2017) Florida Building Code
sections noted herein. SCANNED
DESCRIPTION: TRI-BUILT Roof Underlayments BY
LABELING: labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency InotegUNtir
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinityl ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words 'TrinityI ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
Its distributors and shall be available for inspection at the job site at the request of the Building Official
This Evaluation Report consists of pages 1 through 6.
Prepared by:
_
+,uss!nfr��,n
:ii ceas aM1t•'''
Robert J.M. Nieminen P.E.
Florida Registration No. 59166, Florida DC4ANE1983
ayn•n,�pno^s Thefaaim0eseal apsearin6wasauthorixed by M4rtNiem4.en,
P.r.onwns/eon. med«.em>e Uanela was 1ps;ened
d.wn L
CERTIFICATION OF INDEPENDENCE:
1. TrinitylERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any Company manufacturing or
distributing products it evaluates.
2. Trinityl ERD is not owned, operated or controlled.by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not havenor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
\( � RININ ERD
ROOFING COMPONENT EVALUATION:
I. SCOPE:
Product Category: Roofing
Sub -Category: Underlayment
Compliance Statement: TRI-BUILT Roof Underlayments, as produced by TRI-BUILT Materials_ Group, LLC, have
demonstrated compliance with the following sections of the 6t6 Edition (2017) Florida Building Code through testing
in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations /
Conditions of Use set forth herein.
2. STANDARDS:
Section
Property
Standard
Year
1504.3.1
Wind Resistance
FM4474
2011
1504.3.1
Wind Uplift
UL1897
2012
1504.6
Accelerated Weathering
ASTM G155
2005
1507.2A / 1507.1.1,1507.2.9.2
Physical Properties
ASTM D1970
2015
1507.3.3
Physical Properties
FRSA/TRI April 2012.(04-12)
2012
3. REFERENCES:
4.
S.
Enti
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD (TST6049)
ERD(TST6049)
ERD (TST6049)
UL, I.I.C. (QUA9625)
UL, LLC.(QUA9625)
Examination
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
,Physical Properties
Physical Properties
Physical Properties
Physical Properties
Physical Properties
Accelerated Weathering
Wind Resistance
Quality Control
Quality Control
Reference
540540.02.13-1
S40540.11.13
S40540.03.14
S44870.04.14-2
S44870.04.14-3
S44870.04.14-1
S44870.04.14-4
S43530.02.14-1-R1
S43530.05.14
S40540.10.14
SC7645.02.15
SC8520.04.15
SC14045.05.17-R1
Multiple -Listing R16814
Service Confirmation
Date
02/19/2013
11/19/2013
03/26/2014
04/02/2014
04/02/2014
04/10/2014
04/10/2014
05/14/2014
05/28/2014
10/31/2014
02/13/2015
05/27/2015
06/07/2017
12/10/2015
Exp. 07/18/2020
PRODUCT DESCRIPTION:
4.1 Tri-Built Sand-R SA Shingle Underlayment is a self -adhering, glass -mat reinforced, sand -surfaced, SBS
modified bitumenroof underlayment, with 36-inch sheet width; meets ASTM D1970.
4.2 Tri-Built S/A HT TU Underlayment is a self -adhering, non -woven polyester fabric surfaced, SBS modified
bitumen roof underlayment; meets ASTM D1970 and FRSA/LRI April 2012.
4.3 Tri-Built Smooth HT S/A Underlayment is a self -adhering, glass -mat reinforced, film -surfaced, SBS
modified bitumen roof underlayment; meets ASTM D1970.
LIMITATIONS:
5.1 This is a building code evaluation. Neither TrinitylERD nor Robert Nieminen, P.E. are, in any way,. the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZjurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials
Directory for fire ratings of this product.
Exterior Research and Design, U.C. TM Evaluation Report A42960:30.12-R6
CeMflcvte of Authorization 119503 6 EDITION(2017)FBC NON-HVHZ EVALUATION FL16048-R6
TRI-BUILT Roof Underlayments; (800) 516.1485 Revision 6:09/25/2017
Page 2 of 6
\J I RINITY ERD
5.4 TRI-BUILT Roof Underlayments may be used with any prepared roof cover where the product is
specifically referenced within FBC approval documents. If not listed, a request may be made to the
Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the
prepared roof covering.
5.5 Allowable Roof Covers:
TABLE 1: ROOF COVER OP IONS
Underlayment
Asphalt
Shingles
Nail -On Tile
Foam -On Tile
Metal
Wood Shakes
Slate
&Shingles
Tri-Built Sand-R SA Shingle
Underlayment
Yea
No
No
No
Yes
yes
Tri-Built S/A HT TU
Yes
Underlayment
Yes
Yes
See 5.5.1
Yes
Yes
Yes
d7i Built Smooth HTS/Ai
r-�.
,Underlayment_y
.Yeses
No
No
[Yes1
Yes
L.YesJ
5.5.1 "Foam -On Tile is limited to use of the following Approved tile adhesives / unrlprlavmpnr rnmhina«;
_ .. — •-.... ._...... .. _...................
-TABLE 1A:.ALLOWABLE TILE ADHESIVE / UNDE_RLAYMENT COMBINATIONSr
Adhesive
FloddaProductApproval
Underlayments
ICP Adhesives Polyset® AH-160
FL6332
Tri-Built S/A HT TU Underlayment
Dow TileBond-
FL22525
Tri-Built S/A HT TU Underlayment
5.6 Allowable Substrates:
5.6.1 Direct -Bond to Deck:
Tri-Built Sand -RSA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
➢ Plywood; ASTM D41 primed plywood; OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41
primed Southern Yellow Pine; ASTM D41 primed structural concrete.
While not required over plywood, OSB or Southern Yellow Pine substrates, TRI-BUILT Materials Group, LLC
recommends priming the deck if the final roof cover is not slated for installation within 24 hours. Note:
TRI-BUILT Materials Group,. LLC requires tongue -and -groove board decking be covered with plywood or
OSB prior to installation of the self -adhering underlayment.
5.6.2 Bond -to -Insulation:
Tri-Built Sand=R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
➢ Dens Deck Prime; SECUROCK Gypsum -Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per
minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations
under foam -on tile systems (Tri-Built S/A HT TU Underlayment only), insulation attachment shall be
designed by qualified design professional and installed based on testing of the insulation/underlayment
system in accordance with FM 4474, Appendix D or TAS 114, Appendix 1.
Refer to Tile Manufacturers orAdhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance
Exterior Research and Design, LLC Evaluation Report A429fi0.10.12-R6
Cerliflcute ofAuthorkation 09503 6'"EDITION (2017)F13C NON-HVH2 EVALUATION FL36048-R6
TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6: 09/25/2017
Page 3 of 6
5.6.3 Bond to Mechanically AttachedBase Laver: \I TR1N1-rY ERD
Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Bulk Smooth HT S/A
Underlayment applied to:
➢ ASTM D226, Type I or II felt.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per
minimum codified requirements. For installations under foam -on tile systems (Tri-Built S/A HT TU
Underlayment only), base layer shall be attached per minimum, requirements of FRSA/TRI April 2012 (04-
12).
5.6.4 Wind Resistance. for Underlayment Systems in Foam On Tile Applications: FRSA/TRI April 2012 (04-12)
does not address wind uplift resistance of all underlayment systems beneath foam -on the systems, where
the underlayment forms part of the load -path. The following wind uplift limitations apply to direct -deck
underlayment systems that arenotaddressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile
applications. Maximum Design Pressure is the result of testing for wind load resistance based on
allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety
per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-12), Appendix A, Table 1A or
FBC 1609 for determination of design wind pressures.
#1 Maximum Design Pressure =-45 0 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Primer: (Optional) ASTM D41 or RESISTO EXTERIOR PRIMER
Underlayment: Trl-Built S/A HT TU Underlayment, self -adhered.
#2 Maximum Design Pressure =-67.5 psf:
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Primer: Soprema Elastocol 600c
Underlayment: Tr66ulltS/A HT TU Underlayment, self -adhered.
#3 Maximum Design Pressure =-150 0 psf:
Deck: Min. 15/32-inch APA-rated BCX plywood (may be installed C-side up) to meet project
requirements to satisfaction of Authority Having Jurisdiction.
Deck Preparation: Plywood shall be thoroughly cleaned to remove dust and debris that may inhibit
adhesion. All sheathing fasteners shall be driven flush with the surface. All sharp
splinters and wood projections shall be removed/sanded.
Primer: (Optional) RESISTO EXTERIOR PRIMER
Underlayment: Tri-Bullt S/A HT TU Underlayment, self -adhered, shall be thoroughly roll using hand
roller and/or weighted roller to ensure there are no voids, and ensure there are no
voids/bridging at side and end -laps.
#4 Maximum Design Pressure=-600psf:
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Base Sheet: Soprema Sopra-G or Modified Sopra-G mechanically attached with nails (FBC 1517.5.1)
and tin caps (FBC 1517.5.2) spaced 6-inch o.c. at the 4-inch laps and 6-inch D.C. in three,
equally spaced rows in the center of the sheet.
Underlayment: Tri-Built S/A HTTU Underlayment, self -adhered.
Exterior Research and Design, LLC. Evaluation Report A42960.30.12-R6
Certificate of Authorization g9503 6TM EDITION(2017) FBC NON-HVHZ EVALUATION FL36048-116
TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6:09/25/2017
Page 4 of 6
\i TRINITY ERD
5.6.4.1 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly sh I II meet
or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table IA.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1
design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an
attachment density designed by a qualified design professional to resist the elevated pressure criteria.
Commonly used methods are ANSI/SPRI WD3, FM Loss Prevention Data Sheet 1-29 and Roofing
Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in
Section 2.2.10.1-of FM Loss Prevention Data Sheet 1-29 (January 2616) for Zone 2/3 enhancements,
5.7 ExoosureLimitations:
Tr) -Built Sand-R SA Shingle Underlayment or Tri-Built Smooth HT S/A Underlayment shall not be left
exposed for langer than 30-days after installation
Tri-Built S/A HT TU Underlayment shall not be left exposed for longer than 180-days after installation.
5.8 Tile Slippage Limitations (TAS 103 Per FRSA/TRI April 2012 (04 12)),
When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall
be as follows. These slope limitations can only be exceeded by using battens during loading of the roof
tiles.
'TABLE 2: TILE SUPPAGELIMITATIONSFOR DIRECT-DECHTILE INSTALLATIONS
Underlayment
Tile Profile
Staging Method
Maximum
Slope
Flat
Max. 10-tile stack
6:12
Lugged
Max. 10-tile stack
5:12
Max. 10-tile stack (bottom 2-tile stack
shall be inverted, followed by 8 tiles high 6:12
on slope, as shown below)
�''Y1:__'•
Tri-Built S/A HT TU
Underlayment
_,�y
Lugged
Exterior Research and Design, I.I.C. Evaluation Report A42960.10.12-R6
Certi/Icole oJAuthorlratign H9503 a EDITION (2017) FBC NON-HVHZ EVALUATION FL16048-R6
TRI-BUILT Roof Uhderlayments: (800).S16-1485 Revision 6: 09/ZS/2017
Page 5 of 6
S. INSTALLATION: PJNIN ERD
6.1 TRI-BUILT Roof Underlayments shall be installed in accordance with TRI-BUILT Materials Group, LLC
published installation requirements subject to the Limitations set forth in Section 5 herein and the
specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly
to remove any dust and debris prior to application, and prime the substrate (if applicable).
6.3 Tri-Built Sand-R SA Shingle Underlavment Tri-Built S/A HT TU Underlavment or Tri Built Smooth HT S/A
Underlavment:
6.3.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
6.3.2 Non -Tile applications:
While priming is optional, TRI-BUILT Materials Group, LLC recommends priming the deck if the final roof
cover is not slated for installation within 24 hours.
Apply sheet parallel to the roof edge. Roll out approximately 10 ft of membrane and peel back the first 3
ft of release film.
Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible.
Once the entire length of membrane is in place, peel -off the release film diagonally while holding the
membrane tight. Firmly roll, broom or hand -press the membrane into place to achieve a bond.
Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6-
inches and staggered not less than 2-ft from vertical seams in the course below, sealed:inaccordance with
TRI-BUILT Materials Group,. LLC requirements.
When installing at slopes above 8:12, TRI-BUILT Materials Group, LLC recommends back -nailing in the
overlap area at the top of the sheet at 12-inch o.c.
For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet
over valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge in
each direction. For valleys, apply the sheet starting at the lowest point and work upward.
6.3.3 Tile Applications (Tri-BuiltS/A HTTU Underlavment only):
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the
instructions noted above as a guideline.
For foam -on tile applications, reference is made to Section 5.6.4 herein for wind resistance limitations:that
fall outside the scope of FRSA/TRI April 2012-,(04-12).
Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the
underlayment. See Table 2 herein, and TRI-BUILT Materials Group, LLC published requirements for tile
staging.
BUILDING PERMIT.REQUIRErAENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
B. MANUFACTURING PLANTS:
Gulfport, MS
9. QUALITY ASSURANCE ENTITY:
UL, LLC —QUA9625; (314) 578-3406; k.chancellor@us.ul.com
-END OF EVALUATION REPORT -
Exterior Research and Design, U.C. Evaluation Report A42960.10.12-R6
Certificate of Auth arization #9503 6TM EDITION 12017)F8C NON-HVHZ EVALUATION FL16048-R6
TRI-BUILT Roof Underlayments: 1800) 516-1485 Revision 6: 09/25/2017
Page 6 of 6
EVALUATION REPORT OF
METAL SALES MANUFACTURING CORPORATION
`26 GA. IMAGE H PANEL'
FLORIDA BUILDING CODE 6TH EDITION (2017)
FLORIDA PRODUCT APPROVAL
FL 11560A-R3
ROOFING
METAL ROOFING
Prepared For:
Metal Sales Manufacturing Corporation
545 South 311 Street, Suite 200
Louisville, KY 40202
Telephone: (502) 855-4300
Fax: (502) 855-4200
Prepared By:
Bala Sockalingam, Ph.D., P.E.
Florida Professional Engineer #62240
1216 N Lansing Ave., Suite C
Tulsa, OK 74106
Telephone: (918) 492-5992
FAX: (866) 366-1543
This report consists of
Evaluation Report (3 Pages including cover)
Installation Details (I Page)
Report No. C2181-4
Date: 9.8.2017
SCANNED
at. LucBY
County
`,t`��.isO..Kq
No 62240
ik• A :itV.
0: STATE OF 'Q
's,<,%-4 0 R 4Q P caN�.'�
FL 11560.4-R3
C2181-4
9.8.2017
Page 2 of 3
Manufacturer: Metal Sales Manufacturing Corporation
Product Name: Image II
Panel Description: Max. 16" wide coverage with i" high ribs
Materials: Min. 26 ga., 50 ksi steel. Galvanized coated steel (ASTM A653) or
Galvalume coated steel (ASTM A792) or painted steel (ASTM A755).
Deck Description: Min. 15/32" thick plywood or min.'/4" thick wood plank (min SG of
0.42) for new and existing constructions. Designed and installed as
per FBC 2017.
Deck Attachment: 8d x 2.5" long ring shank nails or #8 x 2" long wood screws @ 6" o.c.
(Minimum) in the field and @ 4" o.c. at edges. Designed as per FBC 2017.
New Underlayment: Minimum underlayment as per FBC 2017 Section 1507.4.5.1.
Existing Underlayment: One layer of asphalt shingles over one layer of #30 felt. For reroofing
(Optional) construction only.
Slope: 1/2:12 or greater in accordance with FBC 2017 Section 1507.4.2.
Requires applied lap sealant for roof slopes less than 3:12.
Design Uplift Pressure: 84.25 psf @ fastener spacing of 24" o.c.
(Factor of Safety = 2)
Fastener Pattern: #10-12 pancake head screws along panel seam. Fastener shall be of
sufficient length to penetrate through the deck a minimum of 1/4".
Test Standards: Roof assembly tested in accordance with TAS 125-03 `Standard
Requirements for MetalRoofing Systems'.
Code Compliance: The product described herein has demonstrated compliance with FBC
2017 Section 1507.4.
Product Limitations: Design wind loads shall be determined for each project in accordance
with FBC 2017 Section 1609 or ASCE 7-10 using allowable stress
design. The maximum fastener spacing listed herein shall not be
exceeded. This evaluation report is not applicable in High Velocity
Hurricane Zone. Fire classification is not within scope of this
Evaluation Report. Refer to FBC 2017 Section 1505 and current
approved roofing materials directory or ASTM EI08/UL790 report
from an accredited laboratory for fire ratings of this product.
FL 11560.4-R3
C2181-4
9.8.2017
Page 3 of 3
Supporting Documents: TAS 125 Test Reports
Hurricane Test Laboratory, LLC
HTL Report #: 0103-0714-09, Reporting Date 9/1/09
NEW UNDERLAYMENT
ROOF PANEL SEE DETAIL 1 EXISTING SHINGLES IF'� MAX.
R � (OPTIONAL)
n
EXISTING UNDERIAYMENT MINIMUM ATTACHMENT:
(OPTIONAL) Bd x 2.5" LONG RING. SHANK N411L
-MIN. 2X_ WOOD RAFTER/JOIST/ OR #8 x..2" LONG WOOD SCREWS
TRUSS AT MAX. 24" O.C. SPACED 0 6' O.C. IN THE FIELD
& 0 4 D.C. AT PLYWOOD EDGES
TYPICAL PANEL INSTALLATION X-SECTION
MIN 26 GA
NEWS UNDERLAYNENT
EXISTING SHINGLES 010 PANCAKE SCREWS
(OPTIONAL)
EXISTING UNDERLAYMEM
(OPRONAL)
PLYWOOD
DETAIL 1 15/32" THICK (MIN.)
GENERAL NOTES:
1. ARCHITECTURAL
FLORIDA BUILDIN
2.. ROOF PANELSA
PANEL = 16".
3. THE ROOF PANE
SPECIFIED ON TI
4. REQUIRED DESIG
6.
(MIN.)
ALLOWABLE UPLIFT PRESSURE
FASTENER
PRESSURE
SPACING
(PSG
(IN)
24
1 84.25
)F PANEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE
ODE (FBC).
SHALL BE. MIN. 26 GA MAX. EFFECTIVE COVERING WIDTH. OF
SHALL BE INSTALLED OVER SHEATHING & STRUCTURE AS
DRAWING.
AND LOADS. SHALL BE DETERMINED FOR EACH PROJECT. TM
AND
3I55 1