HomeMy WebLinkAboutTRUSS PAPERWORKA-1 ROOF
TRUSSES
A FLORIDA CORPORATION
Lumber design values are in accordance with ANSI/TPI 1-2007 section 6.3
These truss designs rely on lumber values established by others.
SCANNED
RE: Job 74190 St Lucie County
Site Information:
Customer Info: JM BUILDING SUPPLY Project Name: MONROE RESIDENCE
Lot/Block: 3 Model: MONROE RESIDENCE
Address: LOT 3 MULLER RD, FT PIERCE, FL Subdivision:
City: County: St Lucie St.
Name Address and License # of Structural Engineer of Record, If there is one, for the built
Name: License #:
Address:
City:
General Truss Engineering criteria Design Loads (Individual Truss Design Drawings Show Special
Conditions):
Design Code: RF_Standard_40_160_ Design Program: Alpine Engineered Produ
Wind Code: ASCE 7-10 Wind Speed: 160
Roof Load: 40.0 psf Floor Load: 0.0 psf
This package includes 103 individual, dated Truss Design Drawings and 16 Additional Drawings.
With my seal affixed to this sheet, I hereby certify that I am the Truss Design Engineer and this index sheet
conforms to 61G15-31.003,section 5 of the Florida Board of Professional Engineers Rules.
n
UN
c�
VJ
OLL
Ur�
La
2ro
<W
No.
Seq #
Truss Name
Date
No.
Seq #
Truss Name
Date
No.
Seq #
Truss Name
Date
1
2790
A01
11/12/18
13
2721
A13
11/12/18
25
2731
B03
11/12/18
2
2713
A02
11/12/18
14
2722
A14
11112/18
26
2732
B04
11/12/18
3
2714
A03
11/12/18
15
2723
A15
11/12/18
27
2733
B05
11/12/18
4
2818
A04
11112/18
16
2833
A16
11/12/18
28
2734
B06
11/12/18
5
2821
A05
11/12/18
17
2836
A17
11/12/18
29
2735
B07
11/12/18
6
2824
A06
11/12/18
18
2839
A18
11112/18
30
2860
B08
11/12118
7
2718
A07
11/12/18
19
12842
1 A19
11/12/18
31
2737
B09
11/12/18
8
2719
A08
11112/18
11/12/18
32
2801
B10
1IVI2118
9
2907
A09
11/12/18
11112/18
33
2855
Ell
11/12/18
10
2913
A10
11/12/18
H24dt
11/12/18
34
2802
B12
11/12/18
11
2916
All _
11/12/18
11/12/18
35
2863
B13
11/12/18
12
2720
Al2
11/12/18
11/12118
j 36
2922 C01
111112118
Thetruss drawing(s) referenced have beer) prepared byAlpfne Engineemd Products, Inc. under mydnectsupmisim based on dle parameters provided byA-1 Roof
Truss Design Engineer's Name: Anthony Tombo III
My license renewal dale for the state of Florida is February 28,2019.
NO E.Thesealonthese drawingsindicateacceptvrceof professionalengineering
respo nsibiGty solelyforthe truss components shown.
The su'nabiliy and use of components for my padkularbuflding isthe responsibility ofthe building
designer, perANSlrrPI-1 Sec. 2
The Truss Design Drawmg(s)(TDD[s]) referenced have been prepared based on the construction
documents (also referred to attin nes as'Stmctural Engineering Documental provided by the Building
Designermdirating the nature and chamrterofthe worlL
The design criteria therein have been transferred to AnthonyTombo m PE by [At Roof Trusses orspe 'relic
location]. These TDDs (also referred to attunes as'Strucbral Delegated
Engineering Dom moral are specaltysbuctural component designs and may be part of the projects
deferred or phased submittals. As a Truss Design Engkmerfw,Spe®ity Anthony T.
Engineer), the seal hem and on the Too represents an acceptance of professional engineering
responsibility for the design of the single Truss depicted on thaTDD only. The Building Designers
responsible forand shall coordinate and review the TODs for
mmpaublitywith theirwriben engineering requirements. Please review all TDDs and al related notes.
SERIAL iF :
/ D rii 4d36b989999e20a51 b6cde8e
Page 1 of FILE COPY
�= A-1 ROOF
TRUSSES
A FLORIDA CORPORATION
RE: Job 74190
Lumber design values are in accordance with ANSI/TPI 1-2007 section 6.3
These truss designs rely on lumber values established by others.
No.
Seq #
Truss Name
Date
No.
Seq #
Truss Name
Date
No.
Seq #
me
Date
37
2740
CO2
11/12/18
75
2812
J10G
11/12118
113
STDL10
AIL
11/12118
38
2741
CO3
11/12/18
76
2872
J1OP
11112/18
114
STDL11
AIL
11/12/18
39
2742
C04
11/12/18
77
2765
J2
11/12/18
115
STDL12
WSTD.DETAIL
AIL
11/12/18
40
2743
C05
11/12/18
78
2766
J2A
11112/18
116
STDL13
AIL
11/12/18
41
2804
C06
11/12/18
79
2767
J5
11/12118
117
STDL14
AIL
11/12/18
42
2744
CJ1
11/12118
80
2768
J6
11/12/18
118
STDL15
AIL
11112/18
43
2745
CJ1E
11/12118
81
2769
J7
11/12118
119
STDL16
AIL
11/12118
44
2746
WIT
11112/18
82
2770
RC
11/12/18
_
_
-
45
2747
CJ3
11/12/18
83 12771
VE
11/12/18
46
2748
CJ3A
11/12/18
84
2772
J7P
11/12/18
47
2749
CJ3C
11/12/18
85
2773
PBO1
11/12/18
48
12750
CJ3E
11112/18
86
2774
PB02
11/12/18
49
2751
CJ3P
11112118
87
2798 -
13803
11/12/18
50
2752
CJ5
11/12118
88
2775
PB04
11/12/18
51
2753
CJ5A
11112/18
89
2809
T01
11/12/18
52
2754
CJ5C
11/12/18
90
2776
V10
11/12118
53
2755
CJ5E
11112/18
91
2777
V4
11/12/18
54
2756
CJ5P
11/12118
92
12778
V8
11/12/18
55
2869
D01
11/12/18
93
2779
VH4
11/12118
56
2757
D02
11/12/18
94
2780
VM10
11/12118
57
2758
D03
11/12/18
95
2781
VM12
11/12/18
58
2759
D04
11/12118
96
2782
VM14
11/12118
59
2811
D05
11/12/18
97
2783
VM16
11/12118
60
2760
006
11/12/18
98
2465
VM18
11112/18
61
2761
D07
11112/18
99
2785
VM2
11/12118
62
2805
D08
11112/18
100
2786
VM4
11/12/18
63
2806
D09
11/12/18
101
2787
VM5
11/12/18
64
2807
D10
11/12/18
102
2788
VM6
11/12118
65
2762
E01
11112118
103
2789
VM8
11/12/18
66
2763
E02
11/12118
104
STDL01
STD. DETAIL
11/12118
67
2808
E03
11/12/18
105
STDL02
STD. DETAIL
11/12118
68
12791
HJ1
11/121181
106
STDL03
STD. DETAIL
11112/18
69
2792
HJ2
11/12/18
107
STDL04
STD. DETAIL
11/12/18
70
2793
HJ5
11112/18
108
STDL05
TO. DETAIL
11/12/18
71
2794
HJ7
11/12/18
109
STDL06
STD. DETAIL
11112/18
72
2795
HJ7C
11/12118
110
STDL07
STD. DETAIL
11/12/18
73
2796
HHE
11/12118
Ill
STDL08
STD. DETAIL
11/12/18
74
2797
HRP
11112118
112
STDL09
STD. DETAIL
11/12118
Page 2 of 2
Job Truss Truss Type City Ply 11109/2018
74190 A01 FLAT 1 1 2790
148# 14M tint#+ 148# 14811 148# 1;1:4 1481 148# 148#+ 148#+ 148#y 148#+
2'0'12-y—T—I-2'—t—Z 2' - —2'- 1 1-1--2' 2' f—Y-1-2'—y-2'.--1--2'.—t-2'1
29
=5XB =3X8 =3X4=4X4 I12X4 =3X8 =5XB
A B C D E F G
T
in
N M L K J
1113X10 =6X8 =3X8 =H0510
=5xI0
29'
H
=sxa In3X10
104# i
" 104# 104#
loin# i 104# i104# + 1o4A i
104# 104# 109# 104#
104# + 101
104#
Loading Criteria (psf) Wind Criteria
Code / Misc Criteria
Defl/C51 Criteria
♦ Maximum Reactions
(Ibs)
TCLL: 20.00 Wind Sld: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in Inc Udell U#
Gravity
Non -Gravity
TCDL: 10.00 Speed: 160 mph
TPI Std: 2014
VERT(LL): 0.277 E 999 360
Loc R+ / R- / Rh
/ Rw / U / RL
BCLL: 0.00 Enclosure: Closed
Rep Factors Used: Varies by
46ML): 0.553 E 628 240
N 2339 /- /-
/- /781 179
BCDL: 10.00 Risk Category: II
FT/RT:10(0)/10(10)
HORZ(LL): 0.057 A - -
H 2338 /- /-
/- 1773 /-
EXP: C KzD NA
Plate Typri
HORZ(TL): 0.113 A - -
Wind reactions based on
MWFRS
Des Ld: 40.00 Mean Height: 15.00 it
WAVE, HS
Creep Factor: 2.0
N Br Width =-
9
Min Pact -
NCBCLL: 10.00 TCDL: 5.0 sf
P
Maz TC CSI: 0.665
H Big Width =-
Min Req = -
Load Duration: 1.25 BCDL: 5.0 psf
Max BC CSI: 0.982
Maximum Top Chord Forces Per Ply (Ibs)
Spacing: 24.0 " MWFRS Parallel Dist: 0 toh/2
Max Web CSI: 0.838
Chords Tens.Corl
Chords Tens. Comp.
CS.0 Dist a: 3.00If
Loc. from endwall: not in 9.00 tt
Wgt: 193.2 Ibs
A- B 1382 -4182
D - E 2106 -6327
GCpi: 0.18
B-C 2086-6305
E-F 2106 -6327
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
C-D 2106-6327
F-G- 1406 -4186
Lumber
Deflection
Top chord 2x6 SP #2
Max JT VERT DEFL LL: 0.28"
DL: 0.28". See
Maximum Bot Chord Forces Per Ply (Ibs)
Bot chord 2x6 SP 2400111
standard detail package for
camber
Chords Tens.Comp.
Chords Tens. Comp.
Webs 2x4 SP#3 :W22x4 SP M-30:
recommendations. Provide
for adequate drainage of
N-M 74 0
K-J 6368 -204B
Special Loads
roof.
M - L 4356 -1382
J - 1 4358 -1405
L-K 6368 -2048
I-H 34 0
—(Lumber Dur.Fac=1.25/Plate Dur.Fac=1.25)
TC: From 30 pit at 0.00 to 30 plf at 29.00
BC: From 10 pit at 0.00 to 10 pit at 29.00
Maximum Web Farces
Per Ply (Ibs)
TC: 14B It Conc. Load at 2.06. 4,06, 6.06, 8.06
Webs Tens.Comp.
Webs Tens. Comp.
10.06,12.06,13.97,14.94,16.94,18.94,20.9422.94
A - N 795 -2226
E - J 381 -587
24.94,26.94
BC: 104 lb Conc. Load at 2.06, 4.06, 6.06, 8.06
A - M 4637 -1532
J - F 2201 - -696
10.06,12.06,13.97,14.94,16.94,18.94,20.94,22.94
M - B 755 -1670
F - I 744 -1658
24.94,26.94 -
B - L 2190 -703
I - G 4641 -1515
L-C 394 -613
G-H 788 -2227
Purling
C-J 23 -46
In lieu of structural panels or rigid ceiling use puriins
to laterally brace chords as follows:
-
Chord Spacing(in oc) Startitt) End(tt)
BC 84 0.00 29.00
-
Apply puffins to any chords above or below fillers
at 24" OC unless shown otherwise above.
The TC of this truss shall be braced with attached
spans at 24" oc in lieu of structural sheathing.
_
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads and reactions based on MWFRS.
End verticals exposed to wind pressure. Deflection
-
meets U360.
Additional Notes
Truss must be installed as shown with top chord up
"WARNING^ Please thoroughly review Me"A-1 ROOF TRUSSES("SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER ("BUYER") ACKNOWLEDGMENr form.
Verify design pammeters and read notes on this Truss Design Drawblg(MD) and the AnMorry T. Tomes 111, P.E Refereno Sneer, before usa.Dnless oNervnse statetl an Me TDD. onty Alpin
rme=rplatesshagbeusedforthe TDDtobe lM. As a Truss Design Engineering (i.e.Specully Engineer), Me seal on any Too represents an exeplanra of Me professional engineedn
responsibility for Me design of the single Truss depidetl on the Too only, under TPI-I. The design assumptions, leading oondi6ons, salability and use of this Truss for any Building Is Me
Building is the resonablity of the Owner. theOwnefs authoraed agent or Me Building Designer, in Me carried Of Me IRC, Me IBC. local building ode and TPI-1. Theappenilof Me
or Me ng Me rin M. Oanhud of Me Hai the
resuse of
of the tling instoosion Contra we Affoonal tessatoutIn Ue TDoanamepaxlasand
Anthony T. Tombo III, P.E.
and bracint
haandg,storage,ers
MellTons.indsizllll be reslbaslbility ofthe Building Delsignerr and
T..
#80083
guidelines of Me Building Component Safety lnfom,adon(BSCB Published by TPI and SECA am referenced for general guidance. TPIA definesNe muWasibli4es and does ofthe
Designer, Truss Design Engineer and Truss Manufacturer, unless othemise defined by a Contract agreed upon in worn, by all parties M,way. The Truss Design Engineer is NOT Me Behor
g 4451 St. Lade Blvd.
Designer or Truss System Engineer of any building. MOspitali aournsamasdeffirma cl-1.
(apyn#nB'1016 M1Rwl Trusses-PrWony T. TamWIII.PE timseurion ofirsdcamerkitanyturn. rsp,MtieE wJMur Newnren permiuicn offrt mrfTxsues-Arno T.TomW III, RE
Fort Pierce, FL 34946 _
Job Tress Tress Type Cry Ply 11/122018 2713
7.4190 A02 FLAT 1 1
=4X6
A
- - 29, - -- - ------ -
=3X4 -3X4 011.5X4 =3X4
B C D E
(a) (a)
L K G
10
3Xfi 103X6
=4X6
F
=3X8
Loading Criteria (psl) Wind Criteria
TCLL: 20.00 Wind Sld: ASCE 7-10
TCDL: 10.00 Speed: 160 mph
BCLL: 0.00 Enclosure: Closed
BCDL: 10.00 Risk Category: II
EXP: C Kzb NA
Des Ld: 40.00 Mean Height: 15.00 it
NCBCLL: 10.00 TCDL: 5.0 psf
Load Duration: 1.25 BCDL: 5.0 psf
Spacing: 24.0MWFRS Parallel Dist: h2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top chord 2x4 SP #2
But chord 2x4 SP #2
Webs 2x4 SP #3
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Purlins
In lieu of structural panels or dgid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 76 0.00 29.00
Apply pudins to any chords above or below Fillers
at 24' OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
End verticals exposed to wind pressure. Deflection
meets U360.
Additional Notes
Truss must be installed as shown with top chord up.
J I H
=3X8 �3X4 �3X8
29'
Code / Misc Criteria
De01CSl Criteria
♦ Maximum Reactions (Ibs)
Code:FBC 2017 RES
PP Deflection in loc Udefl U#
Gravity Non -Gravity
TPI Sid: 2014
VERT(LL): 0.128 D 999 360
Loc R+ ! R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.255 D 999 240
L 1160 /- /- 1618 1503 230
FT/RT:10(0)I10(10)
HORZ(LL): 0.033 A - -
G 1160 P /- /618 1503 /-
Plate Type(s):
HORZ(TL): 0.066 A - -
Wind reactions based on MWFRS
WAVE
Creep Factor. 2.0
L Erg Width =- Min Req - -
Max TC CSI: 0.734
G Brg Width = - Min Req = -
Max BC CSI: 0.972
Maximum Top Chord Forces Per Ply (Ibs)
Max Web CSI: 0.948
Chords Tens.Comp. Chords Tens. Comp.
Wgt: 156.8 lbs
A-e 937 -1667 D-E 1157 -2191
B-C 1157-2191 E-F 938 -1667
VIEW Ver: 18.02.00.1016.21
C-D 1157-2191
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.,
L-K 340 -347 1-H 1722 -1049
K-J 1722-1146 H-G 123 -130
J-1 1722 -1049
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
A - L 687 -1098 J - E 538 -320
A - K 1882 -1038 E - H 588 -753
K - B 588 -754 H - F 1882 -1038
B-J 538 -319 F -G, 687 -1098
D-J 329 -387
-WARNING- Please flomughly review to 'A-1 ROOF TRUSSESCSEU_M"). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER') ACKNOWLEDGMENT' f«m.
p
Verify design pmemdars and read notes an Otis Trees Design crowing (TDD)and Me Antony T. Tomes ill, P.E. Reference Sheetb.fore use. Unless oMmoise slated on the TDD, ony Alpin
_
ceanecWpLatess"I be us8df«teTODto bavalid. Me Tress Design En,muerug(i.e. Speaaly Eninuu), to sealm airy TDD represents an arcepfmae Drte pmfesvwW angineam
�'i
�A-.ROOF
.pansbJiry Wane design oft. single Truss depicted antes TDD only.mder V41. The design assunpWas.Imong conddons,evaus Gty and use ofirls Truss for my Burns,
iRD55B
ngater vm teRC.MeIO.1=1 tA.IBC,tcelbd Tea ml of to
to Owner, te0amerarn
..m��o•
Me ceanyof
On-1.TOO
resporgiDdry or Me Amer, to Own.lS autor�d agml«Ne&nWmg Oesign«.in to mnteslat telRC, to IBC,Iwal euiwng cede and TPl-1. Tee aDpmval al t. TDO erN my field
M,Medagent.rt.BWdage dunned
Anthony. Tombo ill, P.E.
y
usealta Tri¢s,NtlW'vg haMfmg, sb29e, h�stllatm end emtig shaA Ee to responvhiGry of tAe BuNmg Oesignerend Conbap«. Nl ants set wttto TDD aM to practices aM
Truss
gWelines oftlre BUWeg Canganent5afery lNama4on(BSCI)puUfshed ey TPl artl SBCAare rekrencM f«gerc2l gtndance. TKldefirestemsponeakMEaM duliesorte
Deslgref.Tas Designorigins«and aeru,ea bye Cmo-aa agrees won in»iieng qau paNss twvea meTrass Dssign E«gmesr is NDT m. BWu
St.Lud
g451 St. LurJe Blvd.
ybMJdMwfacwer.uNae,ana«%e
Deenmr«Tress symmErg.eam�«,ylwld.g. Agraraea tmn are a+der asml-1yMM.��q 6.eM �_a,,,�..,.._.n�_ ee
Fort Pierce, FL 34946
Jab
74190
Truss Trusts; Type Oty Ply 11112f2018
A03 FLAT 1 1 271a
f 29'
=4X4 .3X4 =3X4 1111.5X4 =3X4 =4X4
A B C D E F
y.
(a)
W1
(a)
K J I
=4X4 =3X8 =3X4
29'
H
=4X4
N1
fl
In
G
DI3X6
Loading Criteria (psq Wind Criteria
Code / Misc Criteria
Def lCS1 Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00 Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udell U#
Gravity
Non -Gravity
TCDL: 10.00 Speed: 160 mph
TPI Sld: 2014
VERT(LL): 0.091 D 999 360
Loc R+ / R- / Rh
/ Rw / U / RL
BCLL: 0.00 Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.182 D 999 240
L 1160 /- /-
/627 1520 /293
BCOL: 10.00 Risk Category: II
FT1RT:10(0)/10(10)
HORZ(LL): 0.026 A - -
G 1160 /- /-
/627 1520 A
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.053 A - -
Wind reactions based on
MWFRS
Des Ld: 40.00 Mean Height 15.34 fit
WAVE
Creep Factor. 2.904
L B Width =-
Min Re
NCBCLL: 10.00 TCDL: 5.0 psf
Max TC CSI: 0
G Brg Width =-
Min Reel — -
Load Duration: 1.25 BCDL: 5.0 psf
Max BC CSI: 0.976
Maximum Top Chord Forces Per Ply (Ibs)
Spacing: 24.0MWFRS Parallel Dist: h/2 to In
Max Web CSI: 0.912
Chords Tens.Comp.
Chords Tens. Comp.
C&C Dist a: 3.00 fit
Loc. from endwall: not in 9.00 it
Wgt: 169.4 Ibs
A - B 793 -1336
D - E 941 -1748
GCpi: 0.18
B-C 941 -1748
E-F 794 -1336
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
C-D 941-1748
Lumber
Top chord 2x4 SP #2
Maximum Bot Chord Forces Per Ply (Ibs)
got chord 2x4 SP #2
Chords Tens.Comp.
Chords Tens. Comp.
Webs 2x4 SP#3:W12x4 SP #2:
L-K 448 -435
I-H 1381 -913
Bracing
K-J 1381 -1041
H-G 170 -157
J - I 1381 -913
-
(a) Continuous lateral restraint equally spaced on
member.
Maximum Web Forces
Per Ply (Ibs)
Purlins
Webs Tens.Comp.
Webs Tens. Comp.
In lieu of structural panels or rigid ceiling use punins
A - L 711 -1103
J - E 450 -300
to laterally brace chords as follows:
A - K 1624 -935
E - H 615 -761
Chord Spacing(in oc) Start(fl) End(ft)
K-B 615 -761
H-F 1624 -934
BC 81 0.00 29.00
Apply purlins to any chords above or below fillers
B-J 450 -299
F-G 710 -1103
at 24' OC unless shown otherwise above.
D - J 325 -381
Hangers I Ties
_
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
End verticals exposed to wind pressure. Deflection
meets U360.
Additional Notes
Truss must be installed as shown with top chord up.
"WARNING— Please Noreughly rerl. the -A-1 ROOF TRUSSES("SELLER, GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMENT' form.
A
Veiny design parameters and read notes on Nis Those; Design Drawvg (TOD) and the MNmy T. Tombo III, P.E. Reference Sheet before use. Unless otherwise stated on the TOD, may Alpin
connedmpl %sshanb wedfx Ma TODfobov d. As a Truss Design Engamerbg(Le. Spatially Engineer)"seal on am' TOD represents an acceptance of the laafess®nal engineenn
he
A-1 seal
�ia11556
responsibility for Me design of the single Truss depided onthe Too only, under TP4l.me desgn assumptions, bading conditions, salability and uze of N¢ Tmse fofany Balding the
Budding 6 Me responsibility of the Owner, Me owners aehan¢ed agent Wthe Budd'ug Deep.,,, in the content of the IRC, the IBC, 1.1 building dtle eat TPM. meapprmaleflhe
responsgirdy of Na Owner. du Ovmeh autlw¢ed agent orthe BuiM'ug Designer. in Necmtertaf the lRC. Na IBC, brat WJd'ug mde and TPl-l-meapWe TDDaMon
Anthony•Tombo ill, P.E.
y
MDY,a
and
gegner andante. bn Nlrgtes emsp McTtD ldOp ofce Ta
use of NeTruss,BulWinghaMNg,sSagyInfordadan(BSCl)ngslad be the aadSQAax,flMeucfordud es ofda Truss
TPIaMSBCAare referencedeaf
Me Bedding Component Tram lannufaEonr.
#80063
un"Ifi byan se se lmobooeshereesDesignEnin
unlepubrnnedey
Designer. cussf ManuGCWm. uNess odnerMse dafa Ebro Conh-ad agreed upon rtwnNg by ad paNez mvtivN. The Times Design Engineer is NOT toes-
4451 St. Lucie Blvd.
Me nerorT Se WFJgmeera a"
Designerar T^R. syswm rvgimermam bolding. Ag moiwaaa la,m+araa, d.ruwd mTPl-t.
Fort Pierce,FL34946
GgfegM03018M1 RaITwva-AmMrf T.Temlam.P£RepM,ctLvi oleo dvartmtFaw/lam.hpdutded�lpnn amwnTen pwmuvmaral PoalTn¢uf-NWvryT. Twnto ill, P.E
Job
Truss
Truss Type
City
Ply
11/12/2018
2818
74190
A04
FLAT
1
1
29'
=4X4 =3X4 =3X4 011.5X4
=3X4
=4X4
A B C D
E•
F
do
TI
I
m
t
L K J I
H
G
013X6 =4X4 =3X8 =3X4
=4X4
013X6
29'
J
Loading Criteria (psf) Wind Criteria Code! Misc Criteria DegICSI Criteria ♦ Maximum Reactions
(Ibs)
TCLL: 20.00 Wind Std: ASCE 7-10 Code: FBC 2017 RES PP Deflection in loc Udell LJ#
Gravity
Non -Gravity
TCDL: 10.00 Speed: 160 mph TPI Sid: 2014 VERT(LL): 0.073 D 999 360 Loc R+ / R- / Rh
/ Rw / U / RL
SCLL: 0.00 Enclosure: Closed Rep Factors Used: Yes VERT(CL): 0.145 D 999 240 L 1160 !- /-
/603 1518 /-
BCDL: 10.00 Risk Category: II FT/RT:10(0)/10(10) HORZ(LL): 0.022 A - - G 1160 /- /-
1603 /518 /-
EXP: C Kzt NA Plate Type(s): HORZ(TL): 0.044 A - Wind reactions based on MWFRS
Des Ld: 40.00 Mean Height: 16.34 ft WAVE L B Width =-
Creep Factor. 2.0 r9
Min Re q = -
NCBCLL: 10.00 TCDL: 5.0 psf
Max TC CSI: 0.874 G Erg Width =-
Min Req = -
Load Duration: 1.25 BCDL: 5.0 psf
Max BC CSI: 0.987 Maximum Top Chord Forces Per Ply (Ibs)
Spacing: 24.0MWFRS Parallel Dist h/2 to h
Max Web CSI: 0.766 Chords Tens.Comp.
Chords Tens. Comp.
C&C Dist a: 3.00 it
Loc. from endwall: not in 9.00 ft Wgt: 176.4 lbs A - B 594 -1113 -
D - E T73 -1455
GCpi: 0.18 B-C 773-1455
E--F 594 -1113
Wind Duration: 1.60 VIEW Ver: 18.02.00.1016.21 C - D 773 -1455
-
Lumber
Top chord 2x4 SP #2 Maximum got Chord Forces Per Ply (Ibs)
Bot chord 2x4 SP #2 Chords Tens.Comp.
Chords Tens. Comp.
Webs 2x4 SP#3 L-K 0 0
I-H 1160 -M
Bracing K-J 1150 -622
H-G 0 0
J-1
1150 -622
(a) Continuous lateral restraint equally spaced on
member.
Maximum Web Forces
Per Ply (Ibs)
Purling Webs Tens.Comp.
Webs Tens. Comp.
In lieu of structural panels or rigid ceiling use purling A- L 675 -1103
J - E 401 -205
to laterally brace chords as follows: A-K 1446 -772
E-H 577 -761
Chord Spacing(in oc) Start(ft) End(ft) K-B 577 -761
H-F 1446 -772
BC 99 0.00 29.00
B - J -205
F - G 675 -1103
Apply pudins to any chords above or below fillers
at 24' OC unless shown otherwise above. D - J 329 29 -381
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
End verticals not exposed to wind pressure.
Additional Notes
Truss must be installed as shown with top chord up. .
-WARNING- Please Nomugldy review Me'A-1 ROOF TRUSSES MEUER"), GENERAL TERMS and CONDITIONS CUSTOMER CBUYEW) ACKNOWLEDGMENT form.
Verlfydeaign parsonetenend read notason Nis Truss Design Dranng(TDO)wd teA ony T.Tombo Ill. P.EReference sneetbeforeuss. Unoescaerwieestaled ongn TDDonly Arpin
Zneedn
tonne platesshaYbeusedfn Ne TDDlobevalid. As a Truss Design Engineeibg(i.e. Specially Engbnar), Me seal onany TOO represensanacceptance of Me
p cfessinal
is Me
�a A4 ROOF
�TRLL556
resposaddaysor Ne design of me single Tnrss depicted on Me TOO only. under TPIA. The design assuorMions. Wool conditions, sebbifty andas of Bile Truss foram, Building
Buud'ugk Ne resllonsbilily of Ne Ownv, Ne Owrefa eulMrRed agent or Ne auld'ug Desgner,inNe contetl of Ne IRC. Na IBC, loot bolding rode and TPN. Tba applmal of Na
..��oaa
mspons�Lry or Ne Owner.Neownels euNwaN agem or Ne Bmla'vg Designer. in Ne �tavtot NeIRC, NeIBC,lool buudv,g rode and DeDa
bdin
Anthony
TTombo ill, P.E.
ctiisMaiMeld
,es tTtha T4pDOaNe
b9oaimnncpdeofurneme,nq ct oSlaaBCiCbASadaWyre fGnNiwgnneNarl Tre
ugOoleusdNSTarnufegslsey , bebe NTePrevInubdiydCaandllmnpba. artdiess."unA
NSuN
#BOD83
CbeIre)sspchlogbNfrssehMrMaddsnT
MraeMsgp
P4ldreNeaposaWdu.
oO4medic.
'yaelWreNeras,TTWrrel¢Nbse DBireausiuiudgd'mn'mgEg CnMaudauuonr9NmWaacgtlWoonnm+a(Br, ydaoakegrerBeunecelddu'ud p,gfoanDr geInrsmgeg
TMTssDesErgievisNOTth
4451 $L Lucie Blvd.
Desi�arar Tusa gyslem Erpvreerof anY bwldmg. Ag egiilar¢ed temp an a9 defined Y,TPpt.
LoppgNOalfeMl WdT,uisee-MdmyT.TmmEp O,P.E Repv4vmd0iadmvrml.baMlmRbPMINIede9lait PewMm{emrssm olMl RealTruxa-MdmyT. Tvnh, N, P.E
Fort Pierce, FL 34946.
Job Truss - Truss Type Ory I Ply 11/12J2ula
74190 A05 HIPM 1 1 2a21
— - - 24V7 } 411 9 --{
12
=3X4 �3X4 1111.5X4 =SX8 6
TO,A_.... B C D E Q
I
E
I
a) (a)
FI
3 6 r
I
H v36rg
=4X4
Loading Criteria (ps0 Wind Criteria
TCLL: 20.00 Wind Std: ASCE 7-10
TCDL: 10.00 Speed: 160 mph
BCLL: 0.00 Enclosure: Closed
BCDL: 10.00 Risk Category: II
EXP: C Kzt NA
Des Ld: 40.00 Mean Height: 16.10 it
NCBCLL: 10.00 TCDL: 5.0 psf
Load Duration: 1.25 BCDL: &0 psf
Spacing: 24.0MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 it
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top chord 2x4 SP #2 :T1 2x4 SP M-30:
Sot chord 2x4 SP #2
Webs 2x4 SP #3
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Purlins
In lieu of structural panels or rigid ceiling use puffins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(@)
TC 24 0.00 24.04
BC 112 0.00 29.00
Apply puffins to any chords above or below fillers
at 24' OC unless shown otherwise above.
Hangers I Tres
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
End verticals not exposed to wind pressure.
sa3X4 =3X8
EE3X4
13X4(R)
29'
Code / Mist; Criteria
Defi/CSI Criteria
♦ Maximum Reactions (Ibs)
Code:FBC 2017 RES
PP Deflection in loc L/defl L/#
Gravity Non -Gravity
TPI Std: 2014
VERT(LL): 0.056 D 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.112 D 999 240
L 1160 /- /- /620 /525 /132
FT/RT:10(0y10(10)
HORZ(LL): 0.015 A - -
G 1160 /- /- 1674 /454 !-
Plate Type(s):
HORZ(TL): 0.029 A - -
Wind reactions based on MWFRS
WAVE
Creep Factor. 2.0
L Brg Width =- Min Req = -
Max TC CSI: 0.672
G Big Width = - Min Req = -
Max BC CSI: 0.977
Maximum Top Chord Forces Per Ply (Ibs)
Max Web CSI: 0.678
Chords Tens.Comp. Chords Tens. Comp.
-Wgt: 193.2 lbs
A-B 588-1022 D-E 757 -1254
B - C 757 -1253 E - F 491 -866
VIEW Ver. 18.02.00.1016.21
C-D 757-1253
_
-
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
L-K 173 -48 I-H 733 -356
K-J 1052 -441 H-G 0 0
J-1 1052 -441
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp, Webs Tens. Comp.
A-L 715-1097 D-1 410 -470
A-K 1361 -783 E-H 393 -512
K - B 608 -721 H - F 986 -479
B-1 270 -199 F-G 651 -1128
I- E 687 -307
-WARNING' Please thoroughly review the -A-1 ROOF TRUSSES ('SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER ("BUYER") ACBNOVILEDGMEN form.
s
V.* design pammete s and read notes on this Truss Deaign Drawing (TDD) and the Anmany T. Tombo Ill. P.E. Reference Shout berore use. Unless otherwise stated an the D. only Xpin
wnneaorplada 0.0 bo med for the TDD to bevalid. Aa a Trout Design Englneerhg 0.e.5peculty Engheer), the seal on any Too represems an a�pta. of Ne ea fessbnal engine.
is
A-r ROOF
�iRU$5E5
onaonvLJdy far the design of this single Truss depicted on the Too only, under TPW. The design essumpton; loading condiOons. suilapGH and use of the Truss for any Bull in me
of thelMneGthe Otualagnt.1theII agent ortheBugdvg. of The
Jelin,
.combo Iv
coundofMe RC.tet C.1.1 xf.didugwde ppsuva. Too adlnflo
rgnmsimibof the Owner, the Owners autha'vitl agent ar the Buld'vgOezf9ner,lothe mote#afthe lRC. the IBC.local builo'ug mtle and! TPaiietaeiatfuaDantheandarry field
anpoinlaltyof Me Ostan.
M1IlOD T. Tombo lll, P.E.
%r80083
haM essetwtin Ne TODaM de
useoftheditB (BS bI)Wb agby BugdvgrgemerWdC f the Trvss
pSBv
#
.apd ideAhr
ofresantl
entt fety.inste0a
reagre for TPI-t eefires the aM
a Besigng Component Safety lalormemn 1. se r¢Iud Cy Wia a mfe
ignn ldbg
ntfl
ePl bsaCAare
Du n wnUg byance.
rhuse Design ee
Designer,Tmss Design ErgineeraM Truss Manufacwrer, unless oNerreassirmedbwl-1. tlagreed upon in wrMgby av paNes mvtl N. maTrusa Dezlpr Engineer is florets Build
. Tm o u
4451 St. Lucie Blvd.
. Lucia
Designerar Tnusa System Fsgmemolarry NNGng. P➢oPtaGzed tempas�tafinednTPN
- _ - .. ..-_. ...._......n,...,un...w.,.�....a,,,R.,.,we_, a,..r,,.�,_.,,,,,s,.r rd„m nl.Pe
Fort Pierce, F134946
Job Truss Truss Type Oty I Ply 11/1212018
74190 A06 HIPM 1 1 2824
_ 22'0*7 I s•ng I
=3X4 a3X4 =6X8 - 12
4 R C D E C R
i
i
FI
L a4Ae K J I H
M4X4 =3X4 as3X8 =3X4
Loading Criteria (ps0
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0 °
Lumber
Top chord 2x4 SP #2
Bol chord 2x4 SP #2
Webs 2x4 SP #3
Wind Criteria
Wind Std: ASCE7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.60 ft
TCDL: 5.0 pet
BCDL: 5.0 psf
MWFRS Parallel Dist: IT to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 It
GCpi: 0.18
Wind Duration: 1.60
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Purling,
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 0.00 22.04
BC 120 0.00 29.00
Apply pudins to any chords above or below fillers
at 24' OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional CSC
member design.
End verticals not exposed to wind pressure.
13X4(R)
Code Misc Criteria
De0/CSI Criteria
♦ Maximum Reactions (Ibs)
Code:FBC 2017 RES
PP Deflection in loc Udell L/#
Gravity Non -Gravity
TPI Std: 2014
VERT(LL): 0.050 D 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.101 D 999 240
L 1160 /- - /- /632 1540 1138
FT/RT:10(0)/10(10)
HORZ(LL): 0.013 A - -
G 1160 A /- 1697 1377 /-
PlateType(s):
HORZ(TL): 0.026 A - -
Wind reactions based on MWFRS
WAVE
Creep Factor. 2.0
L Brg Width =- Min Req = -
Max TC CSI: 0.896
G Brg Width = - Min Req = -
Max BC CSI: 0.699
Maximum Top Chord Forces Per Ply (Ibs)
Max Web CSI: 0.929
Chords Tens.Comp. Chords Tens. Comp.
Wgt: 198.8 Ibs
A- B 503 -839 D - E 689 -1095
B -C 689-1095 E-F 542 -994
VIEW Ver. 18.02.00.1016.21
C-D 689 -1095
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
L-K 231 -68 I-H 821 -375
K-J 866 -296 H-G 0 0
J-I 866 -296
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
A-L 737-1102 I-E 401 -201
A-K 1246 -747 E-H 321 -364
K-B 636 -756 H-F 975 -445
B-I 343 -251 F-G 641 -1105
D-I 3S7 -410
-WARNING" Please ltomugbly review Me'A-1ROOF TRUSSES("SELLER'). GENERAL TERMS and CONDITIONS CUSTOMER (BUYER') ACKNOWLEDGMENT` fmm.
d
Varily design parameters and read notes on Nis Tress Design Drawing QOD) and tie Mowry T. Tombo 111. P.EReferenm Sheetbefomuw.UnlessoNe�sestaledw Ne TDD,only NP"
cvmeclorpblesshaflbeusedfor Oe TDDWWh lid. As a Tmss Design Enginea ig(i.e.Spedelty Engineer). Me seal on any TDD reprssome an acceptmge of the pmfessbrat er,mmerb
A.t ROOF
responsWRyfor Me design of Me single Truss depitled on tie TOD a*. under TPpl.Teedesign assumption, bating conditions, suilabiGly and use of he Truss foraM Bwldng efen
�TRU55F5
evatlug is the responsbiliry of Pa Owner, Ne Qmeh aulhorceU agenlor the BudGrg Oesigner, in tie wntartol NalRC, tha lBC, btal guiding mdeaM TP1-1. rmapp0mildr m
.�.m.�
uwcfseryW,MWO er,Ne ng,sh uN-imdl genrorbeciM Dasigneninm bltycf BuWhd sign Ipal Wgdvgmde and TP41.TMepptm' Doo TODaoideal
use al Na Tmss,hrJutlug hadgng, itprage.intaibtim aM Cradn9 slug be the respwwbLry of the Bugling oesgnereM Contrapm.Nlroteslh.nesnWTODerd Mepramas and
AnthonyTombo Ill, P.E.
%r
adfu Mwr gbya'a TPNelvad the rend DnilOeEnMduues ollhe Tnas
guE Jinea oftie Denton Component 5aferybMmadan(.Sips Niemen, TPIaM50Contat agreed
Ded,oarrT.sS,VxEngineer. old Truss Manu(acMrer. unless oNemisa defy LbyaControl agreed uponNwhtb9 by a0 paNes inwrred. the Truss Oeshpt FiginrerrsNOT Me BuOG
4451 St. LUCIe Blvd.
#.Luca
Oes�erarTmss System Fig'meer ofaMbwd'mg.Mapi. ed bme areazdefeied In TPI-1.
.�...__"..e=e��_.�.�__..____..........,.M..._,......-..�._.......,,a._r n,.,rn.n..._a.m..,r.rmm nL P.E
Fort Pierce, FL 34946
Job Truss Tmss Type City Ply 11/122018
2718
74190 A07 HIPM 1 1
l 290.7 _ I e'11.9
I1I.5x4zs3x4 03X4
1
I
29'
In.SX4
Loading Criteria (ps0 Wind Criteria
Code / Mist; Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: .20.00 Wind Std: ASCE 7-10
Code:FBC 2017 RES
PP Deflection in loc Udell U#
Gravity
Non -Gravity
TCDL: 10.00 Speed: 160 mph
TPI Sid: 2014
VERT(LL): 0.036 D 999 360
Loc R+ / R- / Rh
/ Rw l U / RL
BCLL: 0.00 Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.072 D 999 240
M 1160 /- /-
/682 1606 1579
BCDL: 10.00 Risk Category: II
FT/RT:10(Oy10(10)
HORZ(LL): 0.013 H - -
H 1160 /- A
/682 1298 /-
EXP: C KzL NA
Plate Type(s):
HORZ(TL): 0.026 H - -
Wind reactions based on
MWFRS
Des Ld: 40.00 Mean Height: 17.10 ft
WAVE
Creep Factor. 2.0
M Brg Width = -
Min Req = -
NCBCLL: 10.00 TCDL 5.0 psf
689
Max TC CSI: 0.94
H Big Width =-
Min Reg = -
Load Duration: 1.25 BCDL 5.0 psf
Max BC CSI: 0.994
Maximum Top Chord Forces Per Ply (Ihs)
Spacing: 24.0' MWFRS Parallel Dist: It to 2h
Max Web CSI: 0.749
Chords Tens.Comp.
Chords Tens. Comp.
C&C Dist a: 3.00 ft
Lac. from endwall: not in 9.00 it
Wgt: 224.7 lbs
A - B 659 -717
D - E 764 -9S7 _
GCpi: 0.18
B-C 659 _-717
E-F 669 -992
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
C-D 659 -717
F-G 239 -148
Lumber
Top chord 2x4 SP #2
Maximum Bot Chord Forces Per Ply (Ibs)
But chord 2x4 SP #2 :132 2x4 SP M-30:
Chords Tens.Comp.
Chords Tens. Comp.
Webs 2x4 SP 9301 2x6 SP 2400f-2.0E:
M - L 786 -352
J - I 836 -564
L-K 959 -679
I-H 648 -517
Bracing
K-J 836 -%4
(a) Continuous lateral restraint equally spaced on
member.
-
Maximum Web Forces Per Ply (Ibs)
Purling
Webs Tens.Comp.
Webs Tens. Comp.
In lieu of structural panels or rigid ceiling use putting
A _ M 841 -1106
K - E 250 -197
to laterally brace chords as follows:
A - L 1182 -842
E - I 194 -90
Chord Spacing(in oc) Start(ft) End(ft)
B-L 404 -443
I-F 334 -121
TC 24 0.00 2
L-D 423 -417
F-H 756 -1173
Bt0.00 29.04.00
Apply puffins to any chords above orbelow fillers
-
D-K 213 -109
G-H 175 -127
at 24' OC unless shown otherwise above.
Hangers/Ties -
-
(J) Hanger Support Required, by others
Wind
Wind.loads based on MWFRS with additional C&C _
member design.
'
End verticals exposed to wind pressure. Deflection
meets U360.
^WARNING^ Please, Naroughly review the 'Al ROOF TRUSSES('SELLER'). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMENT' tam.
Venty design premetelsand read rotes on Pis Tmu Design DrW (TOD)and" Anthoh T. Tombo H. P.E.Reference gives before use. Unless othennise stated on the MD. on! Arpin
co =p%tess"Ubeused/ware TDDbber4. As a Truss Design Engmeeing li.e. Specialty Engineer), the seal on any Too represents an accepts. ofee prefessiowl enginea
A_1 ROOF
responsibi of Na singleTruss depicted onthe TODONy, under TPFl. The design assumpdons, trading condhlorw. swtabigry eM ua of Nis Truss faT1,0 B,ulding is Me
�T111158E5
usereMed11hot
BWdug"s use respmseiWy of end Purer, the Owrers auNvzad egantm Me Bui&g Designer, in tNe conted of the lRC, the IBC, Was bugling mdaand TPl-1. TheaDandlnyfi
•.�m.v.a
mspof andotess The, she andany find
oonitofNunset,nIs;gmdaof
Owners auNonzedagenLalMcing
Anthony Tombo Ill, P.E.
1/
conngcode
the Tha.hunw,,an
irt09 D the
use of the Truss, hxdWup haMlin9.sbrege, insWla4onaM Crermg shag be tlw responvtaLydme Buddmg DesigroraM Contraen. All roles set wtin Oe TDO and the praclices and
shelf
Tr,as
80083
p.Luci
Compolent Safely lnromatlon (BSCessothhedby TPledbyra are referencedangeneral gu'daroe. TPpt tlefila¢Iheresporuibgigangmeries OT
gudeWasgrtlre Design
Des9ller. Truss Design EngineereM Truss ManWacWm.uNea oNemiza defused bye, ColNacl agreed upon NwnNg by all paNes invvlvM The Truss Design Empneer is NOT Me -
4451 $t. Lucie Blvd.
DairylermTura Sysbm Engineer olWnybugling. MT` &edleansaurastle(u,edm TP41
.. .,. .__ ._ � __..._........�....,_.,...M_.._._.......,.re_,a.........._.T....,,Mnrve_
FortPierce. FL 34946
Job Truss Truss Type City I Ply 11/12/2018
7'4190 A08 I HIPM 1 1 2719
i
i
Loading Criteria (psO
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
FRCP: C Kzt NA
Mean Height: 17.60 It
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.001t
Loc. from endwall: not in 9.00 It
GCpi: 0.18
Wind Duration: 1.60
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3:W1 2x6 SP 24001-2.0E:
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Purlins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 0.00 18.04
BC 113 0.00 29.00
Apply purling to any chords above or below fillers
at 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
End verticals exposed to wind pressure. Deflection
meets U360.
13x4(R)
Code / Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions libel
Code: FBC 2017 RES
PP Deflection in loc Udell U#
Gravity Non -Gravity
TPI Std: 2014
VERT(LL): 0.034 L 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.068 L 999, 240
N 1160 1- 1- 1706 /631 /653
FT/RT:10(Ou10(10)
HORZ(LL): 0.012 A - -
H 1160 /- /- 1694 /262 A
Plate Type(s):
HORZ(TL): 0.023 1 - -
Wind reactions based on MWFRS
WAVE
Creep Factor: 2.0
N Brg Width =- Min Req = -
Max TIC CSI: 0.547
H Brg Width =- Min Req = -
Max BC CSI: 0.982
Maximum Top Chord Forces Per Ply (Ibs)
Max Web CSI: 0.835
Chords Tens.Comp. Chords Tens. Comp.
Wgt: 212.2 lb,
A-B 631 -595 D-E 740 -841
B-C 631 -595 E-F 722 -981
VIEW Ver: 18.02.00.1016.21
C-D 631 -595 F-G 508 -917
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
r
N-M SEE -379 K-J 811 -546
M - L 839 -595 J - 1 774 -557
L-K 811 -546 I-H 157 -144
Maximum Web Forces Per Ply (Ibs) -
Webs Tens.Comp. Webs Tens. Comp
A-N
878 -1110
E-J
194
-123
A-M
1129 -847
J-F
210
-128
B - M
369 -398
F - I
404
-461
M - D
485 -490
I - G
959
-561
D-L
196 -123
G-H
719
-1112
L-E
217 -135
—WARNING— Please thoroughly review the-A-1 ROOF TRUSSES('SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER CBUYER") ACM0WLeotiMhv l"corm.
A
Verify design parameters and read notes on Nis Tmss Design DmwBg(TDD) and the AnNmyT. Tomb, ill, P.E. Reference Sheet before usa. Unless otherwise stated on the MD, oNy Npin
11
mrmeoWpbresshagbeusedfor Ne TDDbbeY id. MaTmss Design E� ineerhig(i.e.apeoaltyEngineer),Nesealanany TDDrepresenbanaomphanceof Nepmfessionalengineerm
A-1 ROOF
resmnsidgy br the design of the surgeTmss depicted as the MD only, under TeM.Thedeugn assumptions, boding mndiuons. suihiNfity and use ofthb Trans turner Bulotng is Me
9TTRD556
Bugdi�g bNe responabifityal Ne Owner, Ne Ownefs audeReaagentur Ne Bugdug Designer,NNe m�tedol Ne IRG, NeIBC.lural bugding sodeeM TP41. TheaDDrosah of the
.m�wa
responsgifity of Ne Owner, the OwmlSauNodretl agents the Bugd'ug Desgner,bNe meted of the lRC. the IBC, IomIWNug mtleaM Tp4l. TheapproralNthe T00 aM atM fietl
Anthony•Tombo ill, P.E.
y
use atga Tmss,iMW'vg handling, shurage, iteWlatim atd bmcvg slugfe Ne responsibSty orNe auWug DasgneraM Cbntraahar. Mnolessctwtintha TODaMNepraotimsand
guidelines ofW sodding Component safety lnfomation(MCI) published by TPI and MCA are referenced rer gMaml guidance. TP4ld5sNemspmbai saMdullesofp Tmss
#80083
Designerjeema Desgn Engineer and! TmssfAanWadurer. unless overwoe d¢fd¢d bra Cmimctagreed uponinwiaing brag panes awoNad. Thermos Design Engneeris NOTthe Susan g
4451 St. Lucie Blvd.
Designer or Texas spasm Engineer of a,buTdNa M mptarem tame are as a,fnedhTPI-I. .,,,M,,,T •..,,m 111 er.
Fart Pierce. FL 34946
Job Truss Truss Type City Ply 11/12/2018
74190 A09 HIPM 1 1 zsm
Loading Criteria (psf)
TCLL: 20.00
TCDL: 10,00
BCLL: 0.00
SCOL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 18.10 ft
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 It
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top chord 2x6 SP #2:T3 2x4 SP #2:
Bot chord 2x4 SP #2
Webs 2x4 SP #3 :W1 2x6 SP #2:
:W2, W4 2x4 SP #2:
Bracing -
(a) Continuous lateral restraint equally spaced on
member.
Special Loads
—(Lumber Dur.Fac=1.25I Plate Dur.Fac =1.25)
TC: From 60 plf at 0.00 to 60 off at 29.00
BC: From 20 plf at 0.00 to 20 plf at 29.00
TC: 140 lb Conic. Load at 2.58, 6.08
Puffins
In lieu of structural panels or dgid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in cc) Start(ft) End(ft)
TC 24 0.00 16.04
BC 110 0.00 29.00
Apply pudins to any chords above or below fillers
at 24' CC unless shown otherwise above.
Hangers I Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional CSC
member design.
End verticals not exposed to wind pressure.
Additional Notes
The maximum horizontal reaction is 740#
uTra
Code 1 Miss: Criteria
Deb/CSI Criteria
♦ Maximum Reactions (Ibs)
Code:FBC 2017 RES
PP Deflection in loc Udell U#
Gravity Non -Gravity
TPI Slid: 2014
VERT(LL): 0.034 B 999 360
Loc R+ / R- I Rh / Rw 1 U / RL
Rep Factors Used: No
VERT(CL): 0.077 B 999 240
L 1398 /- /- 1911 1585 1452
FT/RT:10(0)/10(10)
HORZ(LL). 0.013 E - -
G 1202 /- /- /746 /558 A
Plate Type(s):
HORZ(TL): 0.020 H - -
Wind reactions based on MWFRS
WAVE
Creep Factor. 2.0
L Brg Width = - Min Req = -
Max TC CSI: 0.797
G Brg Width = - Min Req = -
Max BC CSI: 0.998
Maximum Top Chord Forces Per Ply ([be)
Max Web CSI: 0.829
Chords Tens.Comp. Chords Tens. Comp.
Wg1: 241.51bs
A-B 459 -769 D-E 573 -1025
B-C 460 -771 E-F 479 -993
VIEW Ver: 18.02.00.1016.21
C-D 460 -770
-
Maximum Bot Chord Forces Per Ply (Ibs)
_
Chords Tens.Comp. Chords Tens. Comp.
L - K 496 -137 I - H 839 -386
K-J 831 -366 H-G 0 0
J-1 331 -366
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Camp
A-L
817-1335
I-E
196
-118
A - K
1288 -768
E - H
335
-444
B-K
515 -760
H-F
1010
-460
K-D
353 -209
F-G
583
-1150
D-1
266 -86
"WARNING- Pleas.tivo,hly review Me'A-I ROOF TRUSSES("SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER('8ln'ER') ACMNOVILEDGMENr' to=.
Verifydead, pinaet.isantl read notes.. this Truss Design Oravang(mD) and ele AMhony T. To Ins III,P.E Roference Sheet betas use. Unbu otherwise Naletl onrue TOD, an Alpin
con pletessMnbeusedbree TODrobevalid. M a Truss Design Engineervgli.e.Specialty Eaginear). Na seal on any TDD represents en acceptance of Na professional e,gineam
A-r ROOF
responslblLry form design ofthe single T. depioled on Its TDD a*. under TPM.Thes deafgn assurrpgons. baring conditions, suitability and use of N's Truss fa any guiding ude
®TRu55E5
BUNug bNe respmsbuiry of Ne Owner, Me Ownefs aulledred agenla Na gUgdug Designer. in tlfe conle#of Me IRC, NeIBC, Ioml WJdug wtle artl TPM. Tneepprevalol Ne
responsbiliry althe Ovmer,en Owcers auNorvntl agontatne Bwbhg Designer,bNe mnte tot gra lRC, McIBC, brat Wldu19 wde antl TPM. true approval al Pa TDD erb a,ry fieb
Anthony T. Tombo Ill, P.E.
use oftM Trr¢s,htludug Aa�y,storage. Ylyalladpn and ba2u19 aha0 be dra rezponvD'Irry of Na Bugd'ag DesgnaaMCantrada. Ao robs set outig Na TDD aM Me prxtices antl
Tress
#8Luci
guNUne. Tree Deign Canponad Safety lnforma.ontgSDgpubr¢hedtry TPlertl -
TPM derales NeTrussDAsfEngineer
CAararererred
nMduEes NOTt
Engnea and Truss ManWacWrer,uN cogemise dafeed bye Contralagreed uponbwrkrg by ell parties involved. The Truss Design F�r#neerb NOT the
a upon b mnailg byMP
Devgner,rn¢as
44$1 $I. Lucia Blvd.
Spas
r0m ,fieM,Flet amrtuE ws�efdniM,vanyr Ten'n9N� Inn PEde
Fart Pierce 349.
Job Truss Truss Type City 41y 11/09/2018 2913
74190 • A10 I HIPM 1 1 1 1
Loading Criteria (psf)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
I'm
Wind Criteria
Wind Sid: ASCE7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: It
EXP: C Kzt NA
Mean Height: 15.00 it
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: It to 2h
CB.0 Dist a: 3.00 it
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Top chord 2x6 SP #2 :T3 2x4 SP #2:
Bot chord 2x4 SP M-30 :B2 2x4 SP #2:
Webs 2x4 SP #3:W1 2x6 SP #2:
02, W4 2x4 SP #2:
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Special Loads
—(Lumber Dur.Fac =1.25/ Plate Dur.Fac =1.25)
TC: From 40 pit at 0.00 to 40 plf at 29.00
TC: From 20 plf at 0.00 to 20 plf at 29.00
BC: From 20 pit at 0.00 to 20 pit at 29.00
TC: 140 lb Conc. Load at 2.58. 6.08
Pudins
In lieu of structural panels or rigid ceiling use puffins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 0.00 16.64
BC 120 0.00 29.00
Apply purling to any chords above or below fillers
at 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
End verticals not exposed to wind pressure.
Additional Notes
The maximum horizontal reaction is 376#
Code / Miss: Criteria
DeO/CSI Criteria
♦ Maximum Reactions (Ibs)
Code:FBC 2017 RES
PP Deflection in loc Udefl LI#
Gravity Non -Gravity
TPI Sld: 2014
VERT(LL): -0.037 B 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: No
VERT(CL): 0.078 B 999 240
L 1398 /- /- /920 1271 1241
FT/RT:10(0)/10(10)
HORZ(LL): 0.011 E - -
G 1202 /- /- 1789 /228 P
Plate Type(s):
HORZ(TL): 0.019 H - -
Wind reactions based on MWFRS
WAVE
Creep Factor. 2.0
L Brg Width = - Min Req = -
Max TC CSI: 0.815
G Brg Width =- Min Req = -
Max BC CSI: 0.968
Maximum Top Chord Forces Per Ply (Ibs)
Max Web CSI: 0.654
Chords Tens.Comp. Chords Tens. Comp.
Wgt 238.7 lbs
A-B 518 -810 D-E 586 -1033
B-C _ 519 -811 E-F 439 -972
VIEW Ver: 18,02.00.1016.21
C-D 519 -811
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
L-K 376 -122 I-H 824 -318
_
K-J 844 -240 H-G 0 0
J-1 844 -240 -
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
A-L 919-1332 I-E 188 -82
A - K 1302 -833 E - H 295 -470
K-D 296 -97 H-F 1007 -385
B - K 627 -780 F - G 521 -1152
D-1 240 -79
"WARNING' Please thoroughly review Me "A-1 ROOF TRUSSES(SELLER'). GENERAL TERMS and CONDITIONS CUSTOMER(6UVER°) ACKNOWLEOGMENT'fcrm.
stay design parameters and read notes on this Tross Design Drawing TDD)and de Antony T. Twnbo IN. P.E.ReferenceSheet before Ise. Unless omemiss stated onto MD. only All
.w.. ..ne .. ..w rn.rnn morn bvalnl sea Tv Gneion Ennineenna I e. SnadalN Eminent). vie seal on any TOO ramesents an aa,Mi ofthe pronseedlul engender
e contest ofele IRC. the RIC.1=1 bWdbg code and TPIA. no approval m me l uu am anynen Anthony. Tombo ill, P.E.
ubTdyeld¢OuiW'vg DesgneraM Conbagpr. Kinedesset Min UeMDalldthe prxtpes and y
eCAarereferenoedfor,haniguidaroe. TP4ldevast.haporreib,1W.andduties erne Truss #80083
a Contain agreed upon In yacr, by all Parties bhaNed.The Truss Deskpl Lrlgineer is NOT Ite9' 4451 St. Lucie Blvd.
M4%,,,.eoWTM1edwavANe aMen oemivsimMA-I I1mr„aaa-anavrvr.Ta,wn la. P.a Fort Pierce, FL 34946
Job Truss Truss Type Ory Ply 11/0912018
2916
74190 A11 I HIPM 1 1
Loading Criteria (psf)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
1e" f40a
1—zr'—(-- as. —1 22714
Wind Criteria
Code / Misc Criteria
Wind Std: ASCE 7-10
Code: FBC 2017 RES
Speed: 160 mph
TPI Sid: 2014
Enclosure: Closed
Rep Factors Used: No
Risk Category: 11
FT/RT:10(Oy10(10)
EXP: C Kzb NA
Plate Type(s):
Mean Height: 18.11 it
WAVE
TCDL: 5.0 psf
BCDL: 5.0 Pat
MWFRS Parallel Dist:0 to h/2
C&C Dist a: 3.00 it
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Top chord 2x6 SP #2 :T3 2x4 SP #2:
But chord 2x4 SP #2
Webs 2x4 SP #3:W1 2x6 SP 42:
:W2, W4 2x4 SP #2:
:Rt Bearing Leg 2x8 SP 2400f-1.8E:
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Special Loads
-(Lumber Dur.Fac=1.25/Plate Dur.Fac=1.25)
TC: From 60 pit at 0.00 to 60 plf at 28.93
BC: From 20 plf at 0.00 to 20 plf at 28.32
TC: 140 lb Cone. Load at 2.58, 6.08
Purlins
In lieu of structural panels or rigid ceiling use purling
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 0.00 16.04
BC 112 0.00 28.32
Apply purlins to any chords above or below filers
at 24' OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
End verticals not exposed to wind pressure.
Additional Notes
The maximum horizontal reaction is 406#
P)4
'I
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
PP Defection in loc Udell L/#
Gravity Non -Gravity
VERT(LL):.0.037 B 999 360
Loc R+ / R- / Rh / Rw / U / RL
VERT(CL): 0.073 B 999 240
M 1376 /- /- 1911 1670 1384
HORZ(LL): 0.013 E - -
G 1206 /- I- R86 1572 1-
HORZ(TL): 0.019 H -
Wind reactions based on MWFRS
Creep Factor. 2.0
M Big Width =- Min Req = -
Max TC CSI: 0.762
G Big Width = 7.6 Min Req = 7.6
Max BC CSI: 0.979
Bearing G is a rigid surface.
Bearing G requires a seal plate.
Max Web CSI: 0.681
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 249.91bs
Chords Tens.COmp. Chords Tens. Comp.
VIEW Ver: 18.02.00.1016.21
A-B 513 -753 D-E 589 -979
B-C 514 -754 E-F 454 -933
C-D 514 -754
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens -Comp. Chords Tens. Comp.
M - L 406 -123 J -1 778 -355
L-K 799 -352 I-H 66 -52
K-J 799 -352
Maximum Web Forces Per Ply (Ibs)
Webs
Tens.Comp.
Webs
Tens.
Comp.
A-M
956-1312
J-E
195
-97
A-L
1260 -859
E-I
312
-437
B - L
633 -760
1- F
896
-393
L-D
324 -191
G-H
103
0
D-J
236 -89
F-G
901
-1382
"WARNING— Please lh,roughly review ihe'A-1 ROOF TRUSSES(SELLER'). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER') ACKNOWLEDGMENT" ram.
arty threaten barometers and read notes on his Tmss Design Mowing MD) and thsAnthony T. TomEo III. P.E. Reference Sheet barons use. Unless oNemeise stated on the MD. only At
the IRC. the IBC. b
IbRiN or the Bull
Camas agrees
Igner and Contract,
wrguidance. V
iting by an bodies
o am me parececdares a�a Anthony T. Tombo ill, P.E.
es ma duties alma Tmss #80083
Engineer is NOT the MR 4451 St. Lucie -Blvd.
Tanta III. RE Fort Pierce, FL 34946
Job Truss Truss Type City Ply 1111211
2720
7`4190 Al2 HIPM 1 1
18'(y7 I 10'10'11 2' �
Loading Criteria last)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0 "
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: It
EXP: C Kzt: NA
Mean Height: 17.61 it
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 it
Loc. from endwall: not in 4.50 it
GCpi: 0.18
Wind Duration: 1.60
Top chard 2x4 SP #2
Bot chord 2x4 SP #2 :82 2x4 SP 2400f-2.0E:
Webs 2x4 SP #3:W1 2x6 SP 24001
:Rt Bearing Leg 2x8 SP 24001
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Purlins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 0.00 18.04
BC 120 0.00 28.32
Apply pudins to any chords above or below fillers
at 24" CC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
End verticals exposed to wind pressure. Deflection
meets L/360.
T
T 1
1
SEAT PLATE REQ.
Code f Misc Criteria
Defl/C51 Criteria
♦ Maximum Reactions (Ibs)
Code: FBC 2017 RES
PP Deflection in loc L/defl L/#
Gravity Non -Gravity
TPI Sid: 2014
VERT(LL): 0.033 K 999 360
Loc R+ / R- / Rh / Rw / U f RL
Rep Factors Used: Yes
VERT(CL): 0.065 K 999 240
M 1139 /- /- 1690 /624 1627
FT/RT:10(0)/10(10)
HORZ(LL): 0.013 G - -
H 1164 /- /- 1693 11 /-
PlateType(s):
HORZ(TL): 0.026 G - .
Wind reactions based on MWFRS
WAVE
Creep Factor: 2.0
M Brig Width =- Min Req = -
Max TC CSI: 0.549
H Brg Width = 7.6 Min Req = 7.6
Max BC CSI: 0.926
Bearing H is a rigid surface.
Bearing H requires a seat plate.
Max Web CSI: 0.900
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 242.2 lbs
Chords Tens.Comp. Chords Tens. Comp.
VIEW Ver: 18.02.00.1016.21
A-B 613 -582 D-E 705 -811
B-C . 613 -582 E-F 643 -951
C-D 613 -582 F-G 482 -216
Maximum Bet Chord Forces Per Ply (Ibs)
'
Chords Tens.Comp. Chords Tens. Comp.
M-L' 970 -337 K-J788 -558
L-K 810 -631 J-1 658 -535
Maximum Web Forces Per Ply (Ibs)
Webs 'Tens.Comp. Webs Tens. Comp
A-M
895-1090
E-J
193 -97
A - L
1106 -867
J - F
296 -71
B-L
371 -399
F-I
742 -1050
L - D
507 -467
H - 1
954 -570
D-K
177 -145
G-H
1757 -1852
K-E
217 -155
—WARNING— Please thoroughly review the°A-1 ROOF TRUSSES('SELIER'). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER') ACKNOWLEDGMENT" form. A
Verify design parameters and read notes on this Truss Design brown, (Too) and McAolose T: Tombs in, P.E.Retemnm Sheefbefomuse.Un@sso erxisesWa on Ne TDD,ony Npin N
connector plates stlall ba used tw Me TDD to be val'ld. As a Truss Design Engummiring(i.e. specofty Eagineen, the seal on any TDD represents an acceptance of the professional engineerin ii ROOF
responsibility for Me design of Me single Truss deplaed on Me TDD only, under TPI-I. The design assumptions, land, conditions, suitability and use of this Truss for airy Building is Me �aTRUSSE9
Building re Me responsibility of Me Ovnec the O,osi authorized agent or Me Buildup Designer, in the content of Me IRO, the IBC, 1=1 building code and TPI-1. The approl of Me
reva
sponsLlhyth &M.Owns, e Owner's auwd lho-a gent or Me Building Designer, in Me cantiod of the IRC. theIBC, local bultlitg code and TPI-I. Theopprovalofthe TI)Dandanyfield AnthonyT. Tombo Ill, P.E.
use of the Truss, ixluding handling, storage. installation and trading shall be Me responsibility of Me Budding Designer and Costs". All rotes set out in the TDD aM lle practices antl
guidelines of Me Building Component Safety lhformauon(BSCI) published by TPI antl SECA are referenced far general guidance. TPI-t doges Me responsibJiues and dudes orme Truss If80083
Designer, Truss Doi Engineer and Truss Manufadure. unless otmovisa defines by by a Contract agreed upon in salby all parties involved. The Truss Design Engineer is NOT Me Buflai 4451 St. Lucia Blvd.
Oesigneror Truss Syzlem Etglneer of any buAtling.Mcapi-----terms are as tlegned MTPI-1. _ "w" p ice. Ten ai T. Tmnno Is PE Fort Pierce, FL 34946
Job Truss Truss Type City Ply 11/12/2018 2721 t
74190 A13 SPEC 4 1
Loading Criteria (psf)
Wind Criteria
TCLL: 20.00
Wind Std: ASCE 7-10
TCDL: 10.00
Speed: 160 mph
BCLL: 0.00
Enclosure: Closed
BCDL: 10.00
Risk Category: 11
EXP: C Kzt.' NA
Des Ld: 40.00
Mean Height: 15.24 It
NCBCLL: 10.00
TCDL: 5.0 psf
Load Duration: 1.25 _
BCDL: 5.0 psf
Spacing: 24.0"
MWFRS Parallel Dist:0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Top chord 2x4 SP #2
Bat chard 2x4 SP #2 :B2 2x4 SP 24001-2.0E:
Webs 2x4 SP #3
:Rt Bearing Leg 2x8 SP 2400f-1.8E:
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Purling
In lieu of structural panels or rigid ceiling use puffins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(fl)
BC 74 0.13 28.32
Apply puffins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Loading
Truss passed check for 20 psf additional bottom
chord live load in areas with 42"-high x 24"-wide
clearance.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical exposed to wind pressure.
Deflection meets U360.
1B9'13
Code / Misc Criteria
Defl/CSI Criteria
Code: FBC 2017 RES
PP Deflection in loc Udell U#
TPI Std: 2014
VERT(LL): 0.070 L 999 360
Rep Factors Used: Yes
VERT(CL): 0.141 L 999 240
FT/RT:10(0)/10(10)
HORZ(LL): 0.024 1 - -
Plate Type(s):
HORZ(TL): 0.047 1 - -
WAVE
Creep Factor: 2.0
Max TC CSI: 0.499
Max BC CSI: 0.972
Max Web CSI: 0.748
Wgt. 173.6 Ibs
VIEW Val 18.02.00.1016.21
11yrs aja
SEAT PUITE RED.
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ / R- / Rh / Rw / U / RL
A 1144 /- /- f732 /460 1433
H 1166 /- /- 1602 /492 1-
Wind reactions based on MWFRS
A Brg Width =- Min Req= -
H Brg Width = 7.6 Min Rail = 7.6
Bearing H is a rigid surface.
Bearing H requires a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chards Tens. Camp.
A - B 982 -1972 D - E 659 -972
B - C 916 -1724 E - F 646 -949
C - D 925 -1610 F - G 262 -176
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Camp.
A -L 1689 -1023 K - J 1251 -736
L - K 1251 -736 J - 1 634 -389
Maximum Web Forces Per Ply (Ibs)
Webs
Tens.Comp.
Webs
Tens. Comp.
B - L
354 -336
J - F
353 -126
L-D
516 -195
F-I
578 -1054
D -J
480 -666
H-1
994 -446
E-J
530 -278
G-H
1758 -1700
^WARNING^ Please thoroughly revlew Me'Ml ROOF TRUSSES(SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMENP form.
Verify design pa2meters and read pates on this Tmss Design Orin ing (TOO) and me Anthony T. Tombo III, P.E. Reference Sheet before use. Unless Mhehxise staled onto TOD, only Nero
wnne=r plates shal b used for Pe TDD rn be va d. As a Those Design Engineering (i.e. Spatially Engineer), Pe seal on any TOO represents an acceptance of the professional engineerin f Aq MOO
responsbility for the design areas single Tmss danded on the TDOonly, under l 1-1. The design assumptions, kaing conditions, sufabiutyanduseaf Pis Tines forary Building is Ne �TAU55E5
Belding is the responsibility of the Owner, the owners burnoose agent or the Building Designer, in the Conted ofthe IRC, the IBC, local building code and TPI-1. Theappmvalof Pe
respopeteliryof Pe Owner, Pe Owners authorized agent orthe Buildng Designer, in the mn[edof me IRC, theIBC,1.1 building[ode antl Toll Theapprovalof Pe TDDandanyfied Anthony. Tombo ill, P.E.
use afthe Tmss,assuding handling, storage, installation and braang slug be the responsiblgty bill Building Designer and Conbadis, All notes setoulin the TDDanldie pradoesand y
guidelines of the Building Component Safety lnfomladon(BSCI) published by TPl and SECA are referemzd for general guidance. TPI-1 defines the marorrsiblities anddutiesof Pe Tmss #80083
Designer. Tress Design Engineer and Tress Manufacturer, unless otherwise defured by a Canoed agreed upon in wrlfing by all parties involved. The Tmss Design Engineer is NOT Pe Buldl 4451 St. Lucie Blvd.
Designer erT peg System Engineer of any building. M mpip bred tiros ,m as defined a TIRM. Fort Pierce, FL 34946
_.m. ....e.i ..noon row m.mnnr m"nv M1vm.ta"mnhtN xMo,nNe writlen cermictlon of A-1 Rw(Truss®—AMnmY T. TmnMIII. P.E
Job Truss Truss Type City I Ply 11/12/2018 2722
74190 A14 SPEC 1 1
18.9.13
T
T 1
11
SEAT PLATE RED. SEAT PLATE RED.
Loading Criteria (ps0 Wind Criteria
Code / Misc Criteria
Def1lCSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00 Wind Sid: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc L/defl L/#
Gravity Non -Gravity
TCDL: 10.00 Speed: 160 mph
TPI Std: 2014
VERT(LL): 0.072 L 999 360
Loc R+ / R- / Rh / Rw / U / RL
BCLL: 0.00 Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.143 L 999 240
A 1144 /- /- 1733 /460 1433
BCDL: 10.00 Risk Category: ll
FT/RTA0(0)/10(10)
HORZ(LL): 0.0251 - -
H 1158 /- /- /602 1492 /-
EXP: C KzL NA
Plate Typri
HORZ(TL): 0.050 1 - -
Wind reactions based on MWFRS
Des Ld: 40.00 Mean Height: 15.24 8
WAVE
Creep Factor: 2.0
A Br Width = 7.6 Min Re 1.5
9 q =
NCBCLL: 10.00 TCDL: 5.0 psf
Max TC CSI: 0.499
H Big Width = 7.6 Min Req = 7.6
Load Duration: 1.25 BCDL: 5.0 psf
Max BC CSI: 0.972
Bearings A & H are a rigid surface.
Spacing: 24.0 ° MWFRS Parallel Dist: 0 to h/2
Bearings A & H require a seat plate.
C&C Dist a: 3.00 itMax
Web CSI: 0.741
Maximum Top Chord Forces Per Ply (Ibs)
Loc. from endwall: not in 4.50 ft
Wgt: 173.6 Ibs
Chords Tens.Comp. Chords Tens. Comp.
GCpi: 0.18
_
Wind Duration: 1.60
VIEW Ver: 18.02.00A016.21
A-B 978-1966 D-E 659 -969
B-C 913-1719 E-F 646 -942
Lumber
C - D 922 -1605 F - G 262 -177
Top chord 2x4 SP #2
Bot chord 2x4 SP #2 :B2 2x4 SP M-30:
Maximum Bot Chord Forces Per Ply (Ibs)
Webs 2x4 SP #3
:Rt Beading Leg 2x8 SP 2400f-1.8E:
Chords Tens.Comp. Chords Tens. Comp.
A-L 1684-1020 K-J 1249 -735
Bracing
L - K 1249 -735 J - 1 633 -388
(a) Continuous lateral restraint equally spaced on
-
member.
Maximum Web Forces Per Ply (Ibs)
Putting
Webs Tens.Comp. Webs Tens. Comp.
In lieu of structural panels or rigid ceiling use purling
B - L 352 -333 J - F 353 -126
to laterally brace chords as follows:
L - D 513 -193 F - I 578 -1052
Chord Spacing(in oc) Start(ft) Erl
D-J 479 -664 H-I 960 -446
BC 74 0.15 28.32
Apply pudins to any chords above or below fillers
E -J 497 -277 G - H 1723 -1701
at 24' OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical exposed to wind pressure.
Deflection meets 1_/360.
-WARNING" Please thoroughly review Me-A-1 ROOF TRUSSESCSELLEW). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER-) ACKNOWLEDGMENT- form. a
Vetily design pammeters and re ad notes on this Toss Design Drawmg(TDD)and the Anthony T. Tombo Ill.P.E. Reference Sheet before use. Unless othemse staled on Me TDD, only Albin I
mrmepor plates shed be used for Me TOD to be valid Asa Truss Design Engineenrg gi Spedaly Engineer), the seal on any TDD represent an acceptance of Me professional engineedn �A-r ROBF
responsibidy for Me design of the single Toss decided on the TDD My. under TPI-1. The design assumptions, easing conditions, suitability and use ofthis Truss for any Building is Me -' —TRUSSES
Building b Meresponsibifty of the owner, Me owners authorized agent or the Building Designer. in Me cone#Of Me IRC. Me IBC, 1.1 budding uses and TPI-1. Thsappowlof Me
responsgll,y ofthe owner, the 01 authmexid agent orthe Bulding Designer, in 0e centeMof Me IRC, Me IBC, local building Code and TPI-1. Theappmvalof Me TIDDandany Geld Anthony. TombD II,.P.E.
use ofthe Truss, indutling handling, storage. installatlon and bracing shall be Me responsibiliy ofthe Building Designer and turnover. Allnotessetout iuthe TDDandtheprecticusantl y
guidelines ofthe BuiMing Component Safety Information(BSCQ published by TPI and SECA are he nereedforgenemiguidarms. TPI-1 defies Me respinebditles and duties Of Me Toss #80083
Designer, Tmw Dmgn Engineerand Toss Manufacturer, unlessutheremi, named! bya ColtraCagreed upon inwriGng byall padlasinvolmu.. The Truss Design Sheri NOTMe Buildfir g 4451 St. Lucie Blvd.
-,-- - _ y as tlefinetlbTPl-1. enm•.w T. Twee ln. PE Fort Pierce, FL 34946
Designer or Truss System Engineer of any building. ABmpitt edlermsare _ _ W _.v ,..w-, map M.we.r o..0 T.�a.._
Job Tmss Tmss Type Dry Ply 11/12r2018
74190 A15 I SPEC 3 1 2723
Loading Criteria (ps0
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
rrs_ 44
whTn ,Ea s..TEREO.
Wind Criteria
Wind Std:' ASCE 7-10
Speed: 160 mph
Enclosure: Closed.
Risk Category: II
EXP: C Kzt NA
Mean Height: 15.24 it
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist:0 to IV2
CSC Dist a: 3.00 ft
Loc. from endwall: not in 4.50 it
GCpi: 0.18
Wind Duration: 1.60
Lumber
Tap chord 2x4 SP #2 -
Bot chord 2x4 SP M-30
Webs 2x4 SP #3
:Rt Bearing Leg 2x8 SP 2400f-1.8E:
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Purlins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 98 0.15 25.32
Apply puriins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading
Tmss passed check for 20 psf additional bottom
chord live load in areas with 42'-high x 24' wide
clearance.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical exposed to wind pressure.
Deflection meets 1_/360.
Code / Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
Code:FBC 2017 RES
PP Defection in loc Udell L/#
Gravity Non -Gravity
TPI Std: 2014
VERT(LL): 0.052 K 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.104 K 999 240
A 1024 1- 1- 1668 1406 1478
FT/RT:10(0)110(10)
HORZ(LL): 0.015 H - -
G 1038 /- /- 1597 1447 /-
Plate Type(s):
HORZ(TL): 0.031 H - -
Wind reactions based on MWFRS
WAVE
Creep Factor: 2.0
A Big Width = 7.6 Min Req = 1.5
Max TC CSI: 0.478
G Big Width = 7.6 Min Req = 7.6
Max BC CSI: 0.999
Bearings A 8 G are a rigid surface.
Bearings A 8 G require a seat plate.
Max Web CSI: 0.841
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 1S9.6 lbs
Chords Tens.Comp. Chords Tens. Comp.
VIEWVer. 18.02.00.1016.21
A-B 868-1719 D-E 549 -702
B-C 800-1470 E-F 522 -703
C-D 810 -1356
Maximum Bet Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-K 1465-1004 J-1 1015 -711
K-J 1015 -711 I-H . 63 -124
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
B - K 359 -342 I - F 698 -385
K-D 542 -194 G-H 94 0
D - I 463 -665 F - G 995 -1272
E-I 293 -132
^WARNING^ Please Uomughy review One -A-1 ROOF TRUSSES('SELLER'). GENERAL TERMS and CONDMONS CUSTOMER ('BUYER') ACKNOWLEDGMENT' form.
A
VaRy&e gnpa etemaMmdnotmmNis Tmss Design D2 g(MD)wd Ne AnUl T.Tomholll, P.EReference 5lreet behre Use. Unless othennse stated on Ne TOD, ony Npin
"�
cermetlm plates char Wused forme TDDb Wvalor. Asa Tmss Deign Engine (e.Spedaly EngL er),atesealonany TDDrepresenmanacceptanceofheprotessiormlempneedn
is he
�RA-1RDRF
responahilAylcrlhadevgnofthesingle Tmss dep2fik onheTDDONy, tinder TP4l. Tlm designassumptions. loading sandinons.suilatiOtyand useMhb Trunda Wa,Budding
pTRU55E5
Buadvg's he rescensYi4y of he Owner, he Gwrets auhorhed egentordw Bugdvg Designer, in Ne wntert of Ne lRC, Ne 1BC,bml Wading mde aM TPI-1. Thaapptm'slor Ne
.n®+m.wov
responsargy alma Owner, he Owmeds auhor¢ed agenta Ure Building Designer,whe wnlart of halRC, heIBC, locel WiMitRJ code aM TPpl. The eppmal oltln TDD aM arry field
Anthony. Tombo Ill, P.E.
y
usa INtha Truss,vWding haMfing.storage.imUAadw atd blaring sta0 be he respo�bSy Nhe BudSuxJ Designer end Lonbapor.ide sxtoutin the
0083
#8Luci
oD amde MoftT
oftla Component lydormadon(Ba TPleMBa dery she vDaitln alxnxins ofT
n�s adl4cdby
CaUbnd anseddon9erwnelg by
Deskynes
pastes vsU; B
Desipw. Truss Design Engineer and Truce Manufa[Wrer.uNesa ohemasa darned bya Cm�had agreed upon in wrabg by all paNes'viwNetl. TM Tmv Design Fsgineer is NOTHreB'
Design Tnnss
44$1 St. Lucie Blvd.
TPI-DevgR a Tmss So�em ErprieeraN�anvbwd ar ��tmreer.,�a n..m,,..l.vmmtua.miwan.mmr nm:.smotA-t rmrTe�-
_ Anvonr.rmmul, P.E.
Fort Pierce, FL 34946
Job Truss Truss Type City Ply 11/12/2018 2833
74190 A16 I SPEC 1 1
195.13 — r
in
A
i
Loading Criteria (ps0
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL 10.00
Des Ld: 40.00
NCBCLL 10.00
Load Duration: 1.25
Spacing: 24.0'
SEAT RATE Peg.
Wind Criteria
Wind Sid: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: It
EXP: C Kzt: NA
Mean Height: 1524 ft
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 it
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top chord 2x4 SP #2
Bot chord 2x4 SP M-30:B2 2x4 SP #2:
Webs 2x4 SP #3
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Purling
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 113 0.15 26.00
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Hangers I Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Code / Misc Criteria
Code: FBC 2017 RES
TPI Std: 2014
Rep Factors Used: Yes
FT/RT:10(0U10(10)
Plate Type(s):
WAVE
DefilC51 Criteria -
PP Deflection in loc L/defl L/#
VERT(LL): 0.056 J 999 360
VERT(CL): 0.112 J 999 240
HORZ(LL): 0.017 H - -
HORZ(TL): 0.034 H - -
Creep Factor. 2.0
Max TC CSI: 0.794
Max BC CSI: 0.985
Max Web CSI: 0.711
Wgt: 144.2 Ibs
VIEW Ver. 18.02.00.1016.21
♦ Maximum Reactions (Ibs)
Gravity Nan -Gravity
Loc R+ IR- /Rh /Rw /U /RL
A 1046 /- /- /688 /175 /366
G 1034 /- /- 1590 1195 1-
Wind reactions based on MWFRS
A Brg Width = T6 Min Req = 1.5
G Brg Width = - Min Req = -
Bearing A is a rigid surface.
Bearing A requires a seat plate.
Maximum Tap Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A - B 797 -1766 D - E 480 -752
B-C 728-1515 E-F 466 -755
C-D 738-1402
Maximum Bet Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Camp.
A-J 1507 -908 I-H 1054 -6D3
J -1 1054 -603 H- G 0. 0
Maximum Web Forces Per Ply (Ibs)
Webs
Tens.Comp.
Webs Tens.
Camp.
B-J
364 -345,
E-H 307
-37
J-D
540 -19B
H-F 785
-381
D-H
446 -618
F-G 619
-982
-WARNING- Please Nnreughly miew Me-A-1ROOF TRUSSES (SELLER'). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOw4.EDGMENI- 1p .
Verify design painmeters and need notes on Nis Tmss Design DraWetg(TDD)and Ne AnNon, T.Tomba III, P.ERe%mnm Shcelbeforeuse.Unlezz WN M'I5esNIMan NeMD, oNy Alpi
sannsoor plates shall be assdfor Me Me N be valid. M a Truss Design Engineer, fa. Spetlally Egieer).Meeast on any Too repiesenb an amisplarce of Me pro(ezYwW engineenn
g6A-1 RWF
nesponsisiJIylor Ns design M Me angle Truss depiCed on Via TOO only, under TPl-1.The design assumpduu, loading Ondidone. indaMGty antl use of B4s Truss been, Balding aNre
Bufiditg oNe neSponsibiRy of Ne Owner,Ne Owrers euNorizM agent or Ue BWd'vg Designer.N Ne WnNa oINe IRC,iM IBC.bal bugdNg mde and TPl-1. The apptwal oftlne
®iRll$$6
..�,m.ma
responsgYgyolNa Ovmer, ea Ow is euNa'ecdagenlmWBwaitq Designer.NNe wn[eaof NaIRC. Ne IBC, tool bugdin9 mtle aM TPI-1. The eDprm2l olNe TDO eM atry flea
Anthony. Tombo Ill, P.E.
y
o/Ne Buddin9lhsigner era Canl2tlor.Mroles aotMln Ne TDp aM Ne prances aM
ge.imYaDagon(MbraWgshaa betln fax
wzeefda Truss.hdu?ucine,smot
80083
#.Luca
Sal SSMLH
guaefinasofss oodgin nsese nt Safely lNprtvBm(BStq pubfamd byTPIaM SBCAare releremzd forgeneml guidalip T, envoyed. hares Design d,issordmT�
Oes9^er, Truss Oesgn Etgineerand Trus Manurac4ner, unlessoNemise Mfuled b)ar:mtraG agreeduponNwr2tg by afi parM1n d�wNcd. Tln Truss Deign Fagineer is NOT NeB
4451 St. Lurie Blvd.
OesiJ�crorMmsssetem 6gmearsi^Nuldmg. ado PmraodlmmNmas defmaln TPp1
.. _ _ mm ., M•��.� ee,d,�m.e.m,wan..rerc>,rams=mma.l Romr�aa-Am�wnr.rmmui. 1E.
Fort Pierce. FL 34946
Job Truss Truss Type City Ply 11/09/2018 2836
74190 A17 I HIPS 1 1
Loading Criteria (psi)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
Lumber
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
SEATP TE RED.
Wind Criteria
Wind Std: ASCE 7-'10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 it
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Purlins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 17.00 20.64
BC 84 0.15. 26.00
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Hangers I Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional CSC
member design.
Right end vertical not exposed to wind pressure.
—WARNING— Please Moroghly review Me-A-1
'Mily desian aNdmelars and read net.. Mis Tn as D
Code / Misc Criteria
Def]ICSI Criteria .
A Maximum Reactions (Ibs)
Code:FBC 2017 RES
PP Defection in loc Udell L/#
Gravity Non -Gravity
TPI Std:,2014
VERT(LL): 0.056 K 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.112 K 999 240
A 1046 /- /- 1699 1201 /330
FT/RT:10(Oy10(10)
HORZ(LL): 0.020 H - -
G 1034 /- /- 1583 1234 !-
Plate Type(s):
HORZ(TL): 0.040 H - -
Wind reactions based. on MWFRS
WAVE
Creep Factor. 2.0
A Brg Width = 7.6 Min Req = 1.5
Max TC CSI: 0.826
G Brill Width = - Min Req = -
Max BC CSI: 0.984
Bearing A is a rigid surface.
Bearing A requires a seat plate.
Max Web CSI: 0.714
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 158.2 lbs
Chords Tens.Comp. Chords Tens. Comp.
'
VIEW Ver. 18.02.00.1016.21
A-B 753-1710 D-E 473 -535
B-C 507 -942 E-F 438 -661
C-D 538 -890
Maximum Bet Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A - K 1436 -862 I - H 733 -415
K-J 1432 -863 H-G 0 0
J-1 1432 -863
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
K-B 364 0H-E 164 -99
B-1 523 -798 H-F 78B -431
D-1 526 -184 F-G 651 -987
D-H 330 -529
GENERAL TERMS and CONDITIONS CUSTOMER (•BUYER-) ACKNOWIEDGMENt" farm.
,ony T.Tombolll.SouP.E. Refarenm SheefUebre use. Unless oNe�wisa ¢fated on Ne T[ID. oNy Alf
d nnannnan aswEmodma. loading randNms.sudaanessoft an WLN and use al Ws Trussnonce ifor a any Bullding u Ne ¢ri
y"ro Anthony T. Tombo III, P.E.
e imss #80083
Me Sony 4451 St. Lucie Blvd.
Fort Pierce, FL 34946
Job Truss Truss Type Qty I PI
74190 A18 I HIPS 1 1
15 F 77'11�3'a'5----
2839
n
b
1 --
F zrto—I
F-1
1zs•rT
tT—I
Loading Criteria (psf) Wind Criteria
Code / Misc Criteria
De81CS1 Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00 Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflecfion in loc L/defl LI#
Gravity Non -Gravity
TCDL: 10.00 Speed: 160 mph
TPI Std: 2014
VERT(LL): 0.248 O 999 360
Loc R+ I R- / Rh / Rw / U I RL
BCLL: 0.00 Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.491 O 632 240
B 1107 /- A l775 1248 /306
BCDL: 10.00 Risk Category: ll
FT/RTAO(Oy10(10)
HORZ(LL): 0.096 J - -
1 1033 /- /- 1581 1300 P
EXP: C Kzb NA
Plate Type(s):
HORZ(TL): 0.190 J - -
Wind reactions based on MWFRS
Des Ld: 40.00 Mean Height 15.00 it
WAVE
Creep Factor. 2.0
B Bing Width = 7.6 Min Req = 1.5
NCBCLL: 10.00 TCDL: 5.0 psf
Max TC CSI: O'992
1 Brg Width = - Min Req = -
Load Duration: 1.25 BCDL: 5.0 psf
Max BC CSI: 0.885
Bearing 8 is a rigid surface.
Spacing: 24.0' MWFRS Parallel Dist: h to 2h
Bearing B requires a seat plate.
C&C Dist a: 3.00 fl
Max Web CSI: 0.885
Maximum Top Chord Forces Per Ply (Ibs)
Loc. from endwall: not in 9.00 ft
Wgt: 168.0 Ibs
Chords Tens.Comp. Chords Tens. Comp.
GCpi: 0.18
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
A-B 27 0 E-F 700 -1160
B-C 676-1334 F-G 710 -970
Lumber
C-D 940 -1950 G-H 340 -517
Top chord 2x4 SP #2 :T1 2x4 SP 24001-2.0E:
D - E 674 -1179
Bot chord 2z4 SP #2:82 2x4 SP 24001-2.0E:
Webs 2x4 SP #3
Maximum Bo[ Chord Forces Per Ply (Ihs)
Plating Notes
Chords Tens.Comp. Chords Tens. Comp.
All plates are 3X4 except as noted.
B - O 1002 -835 M - L 0 0
C-P 1772-1108 L-J 60 -23
Purlins
P-N 1677 -1027 J-I 0 0
In lieu of structural panels or rigid ceiling use puriins
N - K 1672 -1028
to laterally brace chords as follows:
,
Chord Spacing(in oc) Slart(ft) End(ft)
Maximum Web Forces Per Ply (Ibs)
TC 24 15.00 22.64
BC 24 0.15 1.99
-
Webs Tens.Comp. Webs Tens. Comp.
BC 119 1.99 15.15
C-O 1643 --515 K-J -225
BC 120 15.15 26.00
Apply pudins to any chords above or below fillers
7243T7
P-O 643 -515 K-G 724 =456
at 24" OC unless shown otherwise above.
N - D 396 0 J - G 536 -659
D-K 519 -826 J-H 882 -508
Hangers/Ties
F-K 245 0 H-1 646 -1023
(J) Hanger Support Required, by others
K-L -149 0
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
-WARNING— Please Moreughy review Me W ROOF TRUSSES('SELLER'). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER-) ACKNOWLEDGMENT' form.
E
Verify design pammeteraand read eases on this Truss Design Dravig(TDD)andMai Anthom T. TMW ill. P.E. Reference Street Were use. Unless othervnse stated on the TOO. only Alpin
'®
maeuser Issues slay be used for Me TDD fo DB valid. As a Truss Design Engineering (i.e. 5peaalty Engineer). tie seal on any TDD represents an ameplance of the professional engine.'
sA-s ROOF
�iQr1$$6
respor.bliyf.rMedesignafthe single Truss depined on tie TDD only, under TPI-1.Thedaugn assumptions, baling serrations, suilamGyaM useol is Trusafor any Belong sthe
BW?ug oNe respon53ilRyd Me Owner, Ihs Owrers auNodeetl agent or NaBldug Designer,Ntln mnfa#aINe IRC, Ne1BC.bml Owldim]cotleeM TPL1. The apDnrvalNMe
•.®mews
TDDeolgoeeand
nesponvbiliy WNa pvner, die owreds aumorved agent arere euik'eg Designer, in Ilia mole#of be IRC. tla IBC,loml Wldug ruse and TPI-1.Tlneapole
Anthony. Tombo ill, P.E.
y
TIDllhe
Afine Ne TDD aMNeprdctice
vie of me Truss,'undWgg harWMg, sto rigs. instagagon entl bating soar be Va resporaibiNy oltla Bu vg oesigreraM CanhacWn
#.Luca
lde M ms Tm
guidelines altie Bwldig Component Safety lN.mab.n(BBCI)publsatd WTPIaN SBCAare refs smdtor gerval guNance. TPFl defuces NarespanvTBilies artl duGesddre Truss
Desgrm, Truss Deign Grgmeer and Trusa MmuAcauet,ususlusaareedefined Ma Cplhatl agreed uponNwrigtg byM paNe3 mvoNed Tae True Deign Enyneer¢NDT tie Ba
4451 $t. LUCIe Blvd.
oasgner arr�a system Erpineaolamblfd g. An mplatoad uma�aa dernadtlTPM. r—_a,,....,r.T,.,�.em. rF
Fort Pierce. FL 34946
Job Truss Truss Type Oty I Ply 11/12/2018 2842
74190 A19 I HIPS 1 1
r
13' )— 11T11 i—
` 83X4 �dXd
r
1�
Loading Criteria (ps0
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
SEATFLATERED.
)-Tl't0-I
F-1
Wind Criteria
Wind Std: ASCE7-10
Speed: 160 mph
Enclosure:.Closed
Risk Category: II
EXP: C Kzt NA
Mean Height 15.00 ft
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: h/2 to It
C&C Dist a: 3.00 8
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Top chord 2x4 SP 42 :T1 2x4 SP 2400f-2.0E:
Bot chard 2x4 SP #2 :B2 2x4 SP M-30:
Webs 2x4 SP #3
Plating Notes
All plates are 1.5X4 except as noted.
Purlins
In lieu of structural panels or rigid ceiling use puriins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 13.00 24.64
BC 24 0.15 1.99
BC 82 1.99 14.78
BC 120 14.78 26.00
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional CSC
member design.
Right end vertical not exposed to wind pressure.
Code 1 Misc Criteria
DeflfCSI Criteria
♦ Maximum Reactions liking)
Code: FBC 2017 RES
PP Deflection in loc Udell U#
Gravity Non -Gravity
TPI Std: 2014
VERT(LL): 0.191 O 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.379 O 819 240
B 1107 P 1- 1772 1422 1334
FT/RT:10(0y10(10)
HORZ(LL): 0.080 J - -
J 1033 /- !- 1587 1461 /-
Plate Type(s):
HORZ(TL): 0.160 J - -
Wind reactions based on MWFRS
WAVE
Creep Factor. 2.0
B Big Width = 7.6 Min Req = 1.5
Max TC CSI: 0.570
J Big Width = - Min Req = -
Max BC CSI: 0.971
Bearing B is a rigid surface.
Bearing B requires a seal plate.
Max Web CSI: 0.831
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 176.4 Ibs
Chords Tens.Comp. Chords Tens. Comp.
VIEW Ver: 18.02.00.1016.21
A-B 27 0 E-F 734 -1130'
B-C 489-1184 F-G 732 -1126
C-D 1046-2137 G-H 503 -774
D-E 1250-215B H-1 30 -18
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
B - O 831 -644 N - L 1139 -725
C-P 1951 -1238 M-K 33 -37
P-N 1877-1180 K-J 192 -123
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp
C-0
819-1056
L-G
533
-344
P - O
535 -395
L - K
768
-434
D-N
457 -483
G-K
583
-764
N-E
1028 -618
K-H
969
-549
E-L
147 -101
H-J
613
-960
F-L
154 -158
I-J
53
-40
L-M
67 0
••WARNING^ Please thoroughly review the WI ROOF TRUSSES (•SELLER"). GENERAL TERMS and CONDITIONS CUSTOMER(•BUYER") ACKNOWLEDGMENT' form.
'
Veny design parameters are read notes on N's Truss Design D mvirp (MD) and ex Amnany T. Tombo III, P.E. Reference Sheet before use. UNess otherwise staled on the MD. ody Alen
_
mmeserplamosimlo.uwdforlhe T00mhevarb. Ase T..Design Engineemgf.e.Spe ity Engineer),Oewelonany TDDrepresentsana=planmor NepmksswnalergineeM
aA-1 MOF
respon;thility for Una design of the single Truss deplond on the MD a*. under TPl-1. The design assurnfions. loading mndNons. enlabifity and ew often; Toss for arry Bolded is the
�nR1155r3
Bu �gbthe responsibary of the Owner, the Orrtiers autMdrM agent or the Buidug Designer,etha conleq of NelRC, the lBC.bcelbuJtl'ug mdeaM TPN. Tnaapprov u'o
..00.m.swo
respowDmy of rim Owner, om Owneya authovaa agwlwthe 9uJdug Dezignor,in Ne center olthe lRC, on IBC, Ipral building cede aM TPpl. Tire approvaldNa TODaM arrygem
Anthony. Tombo ell, P.E.
Y
use ofthe Truss. bvfudug hMli ang,swin age, andiaton and bracing shall be theres4o Lsryame Buildup Designer and contractor. Ag rgtes wtoulN the TDD aM theluatli�aM
#
1
m,moNemhadefinedbya
De�gs.T Design Figi�n MT. Manufarmun Carhactagreedup inwnvgbYagpartu'm .The Tn Design er EngineNOTft
uri
4451 St..Lucie Blvd.
m�wQNr�msyas .Figuaaa mb�nlc ao �arw lema ereaa mrgeat,TPu.
_ . erea,em�.w.nha�..sva.ewmmesa wmr.am. woven oemucsmmwlRmTmssea-dMgnyT.Twnba m.PE
Fort Pierce, FL 34946
Job Truss Truss Type Cry Ply 11112121118 2845
74190 A20 HIPM 1 1
I T
Loadinh Criteria (mo
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
ua= a4X8
SEAT PLATE RED.
H
Wind Criteria
Wind Std: ASCE7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzb NA
Mean Height: 15.00 ft
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: h/2 to In
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00It
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top Chord 2x4 SP M-30 :T2 2x4 SP #2:
Bat chord 2x4 SP #2:B2 2x4 SP M-30:
Webs 2x4 SP #3
Plating Notes
All plates are 1.5X4 except as noted.
Purling
In lieu of structural panels or rigid ceiling use paring
to laterally brace chords as follows:
Chord Spacing(In DO) Starl(ft) End(ft)
TC 24 1..00 26.00
BC 24 0.15 1.99
BC 81 1.99 14.78
- BC 120 14.78 26.00
Apply pudins to any chords above or below fillers
at 24' OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Code / Misc Criteria
Defi1CS1 Criteria
♦ Maximum Reactions (Ibs)
Code: FBC 2017 RES
PP Deflection in loc L/defl L/#
Gravity Non -Gravity
TPI Sid: 2014
VERT(LL): 0.176 O 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.349 O 888 240
B 1107 A A 1761 1428 1315
FT/RTAO(0)f10(10)
HORZ(LL): 0.079 J - -
I 1033 A A 1589 1463 /-
Plate Type(s):
HORZ(TL): 0.156 J - -
Wind reactions based an MWFRS
WAVE
Creep Factor, 2.0
B Brg Width = 7.6 Min Real = 1.5
Max TC CSI: 0.567
1 Brg Width = - Min Req = -
Max BC CSI: 0.999
Bearing B is a rigid surface.
Bearing B requires a seal plate.
Max Web CSI: 0.825
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 166.6 IDS
Chords Tens.Comp. Chords Tens. Comp.
VIEW Ver: 18.02.00.1016.21
A-B 27 0 E-F 828 -1370
B - C 553 -1261 F - G 824 -1363
C-D 1132 -2215 G-H 497 -858
D - E t754 -1541
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
B-O 920 -711 M-K 1311 -825
C - P 2032 -1322 L - J 52 -27
P- N 1948 -1257 J -1 0 0
N - M 1940 -1254
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Camp
C-O
904-1171
K-L
86
0
P-O
588 -436
K-G
654
-419
N-D
348 -76
K-J
836
-493
D-M
510 -748
G-J
634
-834
E-M
394 -162
J-H
1205
-698
E-K
110 -121
H-1
634
-987
F - K
237 -261
"WARNING•' Please thoroughly review Me -A-1 ROOF TRUSSES(SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER CBUYEW) ACKNOWLEDGMENT form.
verilydesignpa enotersantl mad notes on dus Tmas Design Drawing(MD)antl es Ant!"T.TOmbo III,P.EReferenw gM1eetbefae use. UNeas aNerwise atatetl on the TDD,o sy Alpin
wml pWtnOalbousedforthe TDDlobevalld. Aa a Tmss Design Engineering (i.e. Specially Engineer), she seal on any TDD representsan accaptaxe ofthe gofessimW engineerm
A-s RDYF
mspo iilityforthedesignof Ma Nngle Trussdepictedw"MDWy,under TP4l.Tlredesignaswmptiom.betlingmndW.S.suit Utyamu ofB Tmmfam Btntdug hMe
aTBr155B
Bugtl'ug 6Ne responsiDilityol Ne Owner, Na Oxrlela eu8a2ed agents Ne Buad'eg Devgner, in tlm mntetlalthe lRC, the lB4loml bolding mtleeM TP41. Tie appmvel of iMe
.nm�o
responsLilityol the Owner, da Owneh auMMvedageniwNa BuiM'agDesyner,mNe maeat of NaMRC. tlm IBD,Ipal Wld'eg mde vtl TPl-1. Tha aDDmvaIWMe TDD ertl airy field
Anthony. Tombo Ill, P.E.
y
use of lM1 dadgg M1aMfg,sbrfetylutagatio Canhatlor. /W rotes set wtN Na TODaMNe p2ctices aM
byMnaponv'hTamWeBul Desim
(a I)pga
of ft lg
Dines rays Basign Groper andSafely MNomutm(BSCI)pmr¢hedby TPIaMSBrAaredarenoetlbr g antra, yaa Fa es defire The responsibiOesaM duties NOT 11TrM¢s
Desig�c, Tn65 Design Engineer and Trans ManulM Wessnmareederuretlhyaaanbaa agreetl uponNwdNq by el potties vlwNetl. TheTrm OaNgtr Engineer is NOT the
SL Lucie
g451 SL Lutle Blvd.
caps
Ofa�r",.e sy�m Ero:w«mem luJtluq. mmpaarv4a Memo are aaaermeabrnpt.
e Th,avi•_Au1mrT T,min la Pa n�m,els.me.,me„�umen.t,.w.bwwao�.mmm..imm x,�smawtRmT�.n-snamvtToiwenl. P.e
Fort Pierce. FL 34946
Job Truss Truss Type City Ply 11/12/2018 2729
7-4190 A21 I HIPM 1 1
1
f- 9'
01.5X4
SEAT PLATE REO.
17'
=4X8
71'10 ; 12'6'
H
11'46
1
Loading Criteria (psf) Wind Criteria Code! Misc Criteria DefllCS1 Criteria
♦ Maximum Reactions
(Ibs) -
TCLL: 20.00 Wind Std: ASCE 7-10 Code: FBC 2017 RES PP Deflection in loc Udell U#
Gravity
Non -Gravity
TCDL: 10.00 Speed: 160 mph TPI Sld: 2014 VERT(LL): 0.148 P 999 360
Loc R+ / R- / Rh
/ Rw / U / RL
BCLL: 0.00 Enclosure: Closed Rep Factors Used: Yes VERT(CL): 0.294 P 999 240
B 1107 !- /-
1736 1456 /314
BCOL 10.00 Risk Category: It FT/RT:10(0)/10(10) HORZ(LL): 0.073 K - -
J 1033 1- /-
1576 l437 1-
EXP: C Kzb NA Plate Type(s): HORZ(TL): 0.145 K - -
Wind reactions based on MWFRS
Des Ld: 40.00 Mean Height: 15.00 ft WAVE
Creep Factor. 20.
B B Width = 7.6
Min Re = 1.5
NCBCLL: 10.00 TCDL: 5.0 psf
813
Max TC CSI: 0.975
J Brg Width =-
Min Req = -
Load Duration: 1.25 BCDL: 5.0 psf
Bearing B is a rigid
Spacing: 24.0' MWFRS Parallel Dist: h/2 to h Max BC CSI: 0.975
Bearing B requires a seal
Seat
plate.
plate.
C&C Dist a: 3.00 it Max Web CSI: 0.902
Maximum Top Chord Forces Per Pie (Ibs)
Loc. from endwall: not in 9.00 it W9t: 156.81bs
Chords Tens.Comp.
Chords Tens. Comp.
GCpi: 0.18
Wind Duration: 1.60 VIEW Ver: 18.02.00.1016.21
A-B 27 0
E-F 1030 -1740
B-C 745-1316
F-G 1025 -1728
Lumber
C - D 1304 -2378
G - H 1025 -1728
Top chord 2x4 SP #2
D - E 982 -1771
H - 1 699 -1060
Sot chord 2x4 SP #2 :B2 2x4 SP M-30:
Webs 2x4 SP 93
Maximum Bat Chord Forces Per Ply (Ibs).
Plating Notes
Chords Tens.Comp.
Chords Tens. Camp.
All plates are 3X4 except as noted.
B - P 984 -823
N - L 15W -1140
C-0 2198-1655
M-K 65 -46
Purling
Q-0 2105-1578
K-J 159 -146
In lieu of structural panels or rigid ceiling use pudins
O - N 2094 -1573
to laterally brace chords as follows:
Chard Spacing(In oc) Start(ft) End(ft)
TC 24 9.00 26.00
Maximum Web Forces
Per Ply (Ibs)
BC 24 0.15 1.99
Webs Tens.Comp.
Webs Tens. Comp.
BC - 84 1.99 14.78
BC 120 14.78 26.00
C - P 1049 -1256
L - M 81 0
Apply pudins to any chords above or below fillers
Q-P 626 -507
L-H 799 -551
at 24' OC unless shown otherwise above.
O - D 311 -146
L - K 1034 -706
D-N 508 -653
H-K 659 -658
Hangers/Ties
E-N 411 -142
K-1 1350 -791
(J) Hanger Support Required, by others
E - L 246 -199
I - J 640 -985
F-L 285 -321
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical exposed to wind pressure.
'
Deflection meets 1-1360.
"IVARNING- Please tomughly review to WI ROOF TRUSSES(•SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER-) ACKNOWLEDGMENT" form.
g
Vedfydesignp.lem andread notes a a this Truss Design Oraw'ulg(matend MCAMhony T. Twnpp In. P.E.Refemnw SM1eetberore use. Unless oNerwise staled on Ne TOD..*Alpin
mnecnrp�ansshe0 tie usedforte TDD bbe valid. Asa Tress Cosign Entnixein,i.e.Spe:airy Engineer), No said on any TOD represents an atteplanca ofthe
nafe onalemyneenn
A-1 ROOF
�iftll$56
responnaliy far No design of to single Toa, deeded on ltre Too may, under TPl-1.The design isssumpgons, being madams, suilabLry and use ofthis Truss for my Building is to
BuiSuigbte reapmvbilgy of to Owner,NeOvmers aullnn2eC agenimta au�igDesigier, of to donned of to lRC, tln IBC.Ioml WJdbig mde mid TP41.
TheaPprpvaldte
.,onv'bYity of to Owner, the Oaae. naaoneel agent., to avildhy Designer.in terddetl of to IRC. to ISC, oval wad'vig mde and TPl-1. ran, appm2l of to TDD and any flab
Anthony. Tombo ill, P.E.
y
use of to Tress,IMWing haMGng,storage. mslaAadm ant Wamig shill he tin resmnsiGLyolte Bugling DasgiereM Contradm.Aflnonsseloutbte TODaidtepTdcdcosand
duties to Tress
#B0083
gtidelines oils auldbig Component Safety lydmmadm (BBG)pubosRd by TPIaM SHCA are reform Mbrgercrel gubarcn. TPpt defnes to respmnibilidea ant of
Desgnm,T. Design Erigbean and T.Mmubcbum, untess uenwdsedefned by a Contrail agreed upm In writing by ag paNes inWved. no T. Design Engineer is NOT to B.Ilds
4451 St. Lucie Blvd.
DesknwTmu System Ef4y dare'bug g.Mmpaafzdtanna areaadef dnTP41.
rmM taxaaA.lsaai, fu-mamwr Taamm_Pa In. RE
Fort Pierce, FL 34946
Job Truss Truss Type City I Ply 11/12/2018 2799
724190 A22 I HIPM 1 2
I:a
210 19 187# taTa1 1870 107# 167# Lela1 187# 10)
I TO'6�Y0'6 �2'TYt2'.-1-2�2'�Y-1-Yt Y�1.4{
is
e3M nano
SEAT PUTE `Ea.
1-71-10 1
H
125'
r 2U'12-1
5179 12 12U
11-4T
13J
1 13w 130a 13M 130p 130a
LoadingCriteria (psf) Wind Criteria
Code! Misc Criteria
DeFl/CSI Criteria
♦ Maximum Reactions Ibs
TCLL: 20.00 Wind Std: ASCE 7-10
Code: FED 2017 RES
PP Deflection in loc Udell U#
Gravity
Non -Gravity
TCDL: 10.00 Speed: 160 mph
TPI Sid: 2014
VERT(LL): 0.182 P 999 360
Loc R+ ( R- / Rh
/ Rw
/ U / RL
BCLL: 0.00 Enclosure: Closed
Rep Factors Used: No
VERT(CQ: 0.363 P 855 240
B 2341 /- A
/-
11125 1114
BCDL: 10.00 Risk Category: II
FT/RT:10(0)/10(10)
HORZ(LL): 0.093 J - -
J 2605 1- 1-
!-
/1246 A
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): OA85 J - -
Wind reactions based on
MWFRS
Des Ld: 40.00 Mean Height 15.00 it
WAVE
Creep Factor. 2.0
B Brg Width = 7.6
Min Req = 1.5
NCBCLL: 0.00 TCDL: 5.0 psf
Max TC CSI: 0.676
J Brg Width =-
Min Req = -
Load Duration: 1.25 BCDL: 5.0 psf
Bearing B is a rigid surface.
Spacing: 24.0' MWFRS Parallel Dist: 0 to h/2
Max BC CSI: 0.897
Bearing B requires a seat plate.
CSC Dist a: 3.00 ft
Max Web CSI: 0.741
Maximum Top Chord Forces Per
Ply (Ibs)
Loc. from endwall: not in 9.00 it
Wgt: 299.61bs
Chords Tens.Comp.
Chords
Tens. Comp.
GCpi: 0.18
Wind Duration: 1.60
VIEW Ver. IS 02.00.1016.21
A-B 13 .10
E-F
1435 -2951
B-C 713-1363
F-G
1420 -2919
Lumber
Puffins
C - D 1328 -2769
G - H
2919
180542D -1638
Top chord 2x4 SP #2 :T1 2x4 SP 2400f-2.OE:
In lieu of structural panels or rigid ceiling use puffins
D - E 1328 -2769
H - I
805 -1638
Bat chord 2x4 SP 92 :82 2x4 SP 24001-2.0E:
to laterally brace chords as
follows:
Webs 2x4 SP #3
Chord Spacing(in oc)
Start(t1) End(0)
TC 24
7.00 26.00
Maximum Sot Chord Forces Per
Ply (Ibs)
Nailnote
BC 24
0.15 1.99
Chords Tens.Comp.
Chords
Tens. Comp.
Nail Schedule:0.131"x3", min. nails
BC 120 1.99 26.00
Apply purlins to any chords above or below fillers
B - P 976 -477
N - L
2802 -1295
Top Chord: 1 Row @12.00" o.c.
at 24" OC unless shown otherwise
above.
C - Q 248E -1125
M - K
151 -65
Bat Chord: 1 Row @12.00" D.C.
Q-O 2393 -1080
K-J
22 0
Webs : i Row @ 4"o.c.
Use equal spacing between rows and stagger nails
Wind
O - N 2420 -1087
in each row to avoid splitting.
Wind loads and reactions based on MWFRS.
Right end vertical exposed
to wind pressure.
Maximum Web Forces
Per Ply (Ibs)
Special Loads
Deflection meets Ll360.
Webs Tens.Comp.
Webs
Tens. Comp.
-(Lumber Dur.Fac =1.25 / Plate Dur.Fac =1.25)
C - P 609 -1246
L - M
112 0
TC: From 60 pif at -1.00 to 60 plf at 7.00
Q - P 621 -293
L - H
1395 -663
TC: From 30 plf at 7.00 to 30 plf at 26.00
BC: From 20 plf at 0.00 to 20 plf at 7.06
D - O 535 -155
L - K
1544 -716
BC: From 10 plf at 7.06 to 10 plf at 26.00
D - N 446 -232
H - K
646 -1041
TC: 214 lb Conc. Load at 7.03
N - E 241 -312
K -1
1945 -922
TIC 1871b Conc. Load at 9.06.11.06.13.06,15.06
E - L 194 -107
I - J
632 -1216
17.06.19.06,21.06,23.06,25.06
F- L 232 -274
BC: 517lb Conc. Load at 7.00
BC: 123 lb Conc. Load at 9.06,11.06,13.06
BC: 130 lb Conc. Load at 15.06,17.06,19.06,21.06
23.06,25.06
Plating Notes
All plates are 1.5X4 except as noted.
Hangers I Ties
(J) Hanger Support Required, by others
-WARNING- Please thoroughly review Me'A.1 ROOF TRUSSES('SELLER"), GENERAL TERMS and COMMONS CUSTOMER ('BUYER") ACKNOWLEDGMENT" torn.
J
V.* design pweve. .nd read notes on Pis Tress Design Drawbg(TDD) and to Anthony T. Jumbo ld P.E. Reference Sheet before wa. Unless otherwise slated on Pe MO. only Npin
mmerfor plates span be used for Pe TDD W be valid As a Truss Design E bleerrfga.Speonalty Engineer). Pe seal on any TDD repmeanW an woopmece of the pefessional engineenn
A-1 HOUF
responsSihrytar to design of Me single Truss depicted on Pe TDD only, under TP41. The design assumptions, twel conditions, sueaMDy and use of this Truss for any building is the
®TNtl55[3
BundWgk Peresponsbaityol Pe Owner.MO esautgtl agenimt Bu6ding Deagner,WPeaanteriof PDIRC,W lBC,l�buddingmdeand TPI-1. Theapple,nuotthe
responsll.lily of PeOwner, to OwmYa aNhor¢ed agent or Pe buitl'aq D¢signer, in Pe mntertof NeIRC. PaIBC.loml bundug codeaM TP41. Mappreval altln TDD and airy fieM
Anthony. Tomb0111, P.E.
y
useal the vWudingharoamout Safety inormaton enddaagshed be tle raspo tulle Bosed! Designer aMCdntrdcW
0083
#SLuci
of Me TPI-tdef Pe responsibnitlesaM duUesoftheeltss
CA. -Idefle MemsWthe MtDa dWp of�e TM
tenderness; ruma eengn Component Safety Information (MCI)publishedTPIaN SBCAare refere dMgenadng loyal
Oeigner, Truss Desgn Elgineerarf Trva ManuAs WgessgNendise dha agreed upon Nwri4ng byall paNes vwMed Tlla Trvv DeSlgn Ellgneer iz NOT Pa Buld
QQ51 $L LUQB Blvd.
oet turned 1.
oeserarTrvss syum Enyeeraonly dadi�. As vl: wed a and a: der M'nNTP41, a�bleexumnm.wmzn mmtsmmwtlam Tua,e-
. _ _ - n.. nn.�m.n urvmm Mavry T.Tdm.'s.P.E_
Fort Pierce, FL 34946
Job I Truss Truss Type Ory I Ply 11/12/2018
74190 B01 I COMN 1 2 2919
Loading Criteria (par)
TCLL 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
\6%&R) a5y8
G H
Y139P 1160n ITEM 11fietl 1160P 11Wtl I160P 116M 13W 1398% 137
Gl 1139tl 11MP IIi4tl It4M 11MD
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height 15.00 ft
TCOL 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist:0 to h/2
C&C Dist a: 3.73 It
Loc. from endwall: not in 9.00 It
GCpi: 0.18
Wind Duration: 1.60
Top chord 2x4 SP #2 :T1 2x8 SP 24001-1.8E:
:T2 2x6 SP #2:
Bot chord 2x8 SP 2400F1.8E :B3 2x6 SP
2400f-2.OE:
Webs 2x4 SP #3:W5, W7, W8, W10. W19 2x4 SP 92:
:W9, W13, W16, W18 2x4 SP M-30:
:W20 2x8 SP 2400f-1.8E:
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Nailnote
Nail Schedule:0.131"x3", min. nails
Top Chord: 1 Row @12.00' o.c.
Bot Chord: 2 Rows @ 5.50' o.c. (Each Row)
Webs :1 Row @ 4' o.c.
Use equal spacing between rows and stagger nails
in each row to avoid splitting.
(1)112" bolts may be used for
(2) 0.131'x3', min. nails on
The Bottom Chord Only.
Special Loads
--(Lumber Dur.Fac =1.25 / Plate Dur.Fac =1.25)
TC: From 60 plf at 0.34 to 60 plf at 37.27
BC: From 60 plf at 0.00 to 60 plf at 0.34
BC: From 20 plf at 0.00 to 20 plf at 37.27
BC: 2339lb Cone. Load at 5.67
BC: 1160 lb Cone. Load at 7.67. 9.67,11.67,13.67
15.67.17.67.19.67
BC: 1398 Ib Conc. Load at 21.67,23.67
BC: 1376 lb Conc. Load at 25.67
BC: 1139 Ib Conc. Load at 27.67
BC: 1144 lb Conc. Load at 29.67,31.67,33.27.35.27
T
1
Code / Misc Criteria DeflICSI Criteria
♦ Maximum Reactions (Ibs)
Code: FBC 2017 RES PP Deflection in loc Udell U#
Gravity Non -Gravity
TPI Std: 2014 VERT(LL): 0.338 S 999 360
Loc R+ / R- / Rh / Rw
/ U / FIL
Rep Factors Used: Varies b Q: 0.676 S 659 240
W 11067 /- /- /-
/4446 P
F URTAO(Ou10(10) HORZ(LL): 0.105 C - -
X M59 /- /- /-
15083 /-
Plate Type(s): HORZ(TL): 0.211 C - -
Wind reactions based on MWFRS
WAVE, HS Creep Factor: 2.0
W Brg Width = 7.6 Min Req = 4.6
Max TC CSI: 0.754
X Brg Width = 6.9 Min Rent = 5.1
Max BC CSI: 0.981
Bearings W & X are a rigid surface.
Bearings W & X require a seat plate.
Max Web CSI: 0.999
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 784.0 lbs
Chords Tens.Comp. Chords
Tens. Comp.
VIEW Ver. 18.02.00.1016.21
A -B 4939-12230 F-G
2647 -6429
B - C 4585-11215 G - H
1976 -4795
Purling
C - D 395-9581 H - I
2-
In lieu of structural panels or rigid ceiling use purlins
D - E 3952 -9567 - J
2041 41 -897 4897
to laterally brace chords as follows:
E-F 3295-7927 J-K
152D -3651
Chord Spacing(in oc) Stad(ft) End(ft)
TC 24 21.00 26.33
BC 95 0.00 37.27
Maximum Bot Chord Forces Per Ply (Ibs)
Apply puffins to any chords above or below fillers
Chords Tens.Comp. Chords
Tens. Comp.
at 24' OC unless shown otherwise above.
A - V 10929 -4406 O - P
S722 -2356
Wind
V-U 10924-4404 P-0
5702 -2350
Wind loads and reactions based on MWFRS.
U - T 9987 -4083 O - N
4375 -1816
T - S 9987 -4083 N - M
3314 -1374
Right end vertical not exposed to wind pressure.
S- R 8401 -3472 M- L
0 0
R- Q 6987 -2904
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp
V - B
1203 -382
G - O
838 -2042
B - U
397 -1171
O - H
2283 -943
U - C
1985 -765
0-1
1140 -435
C - S
835 -2170
I - N
545 -1344
S - E
2866 -1151
N - J
2420 -1006
E - R
1011 -2531
J - M
1243 -2888
R - F
3243 -1411
M - K
5324 -2207
F-Q
1301 -3009
K-L
2458 -5892
G - Q
4547 -1877
-WARNING- Please thoroughly review Me 'A-1 ROOF TRUSSES(•SELLER'). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER') ACKNOWLEDGMENT" form.
A
Ve,iy design parametem and read mres on this Truss Design Drawin,(TOD)and Out Anthony T. Tombo Ill. P.E.Refemnwgmtbeforeuss.UnlessoNetwisesNtedonthe MoD.ony Alpin
g
wt e=platesshallbeusadfw Ne TDDtobevalN. Ate a Truss Design Engineering (i.e. Specialty Engineer), Me seal on any TOO represents an aaeptance of the professional engineenn
�0A-r ROOF
responstlgry firths design of the angle Truss depicted on Me Too only. under TPI-1.The design assumptions, bating sonditions, suitabtgy and use of tha Truss army Building is Me
NTRUSSE5
Budditg's the responsibility of the C.ner, Me Owner's authorised agent Mthe Building Designer, in the contaM.f Me IRC, Me IBC, blot budding mtle and TPI-1. Tlteapptoval oftim
rspof or r.inthecontea rareArtl TPL The the TDDaMeny fink
Owner, the Owm(sage.
Anthony. Tombo III, P.E.
y
Monsager taBuilding beta in Me Too(
andante. orkld t set ounMeTooand lhepradiossantl
MeT ,fr htsNlW4on aM breagshea be Ne atheBMi,Ne Designerconnector.
Neosed
use of the Truss, htsedr, Trua
oom
#SLuci
CratdMg.storage.
TPI-1 dmd. NeTrusa iEB
TPI d!Sm Aar re for g Memsp
Campenent Safety lMomalim (Bornm
Wererues
erititerarl EatgdWesartre
byallp
Englnee+eMTruss Manu(ac9ud, unlessoNemise deft MEya CanbaGa,geed upon in writlttg by all paNes'vrvoNed. The True OeSyn Er�neer¢NOT NeB"
Designer. Design umnedbyafredbyaCAarerererencedfof meriting
DasgrercrTrus
44j18t. LOGYB Blvd.
Sfas
ce,.s...n r45-1adSo�.reai�neerNa-tryT 1-11 raPta�1�`„temu are as 4NVJ rut TPF1.
_ M ...� i are,aem�n:,a,,.raai.aaaumitafwwon wwdwt wiwsatotA-tlmfrna>e-Aimmvr.TMao nI, P.E
Fort Pierce, FL 34946
Job
Truss
Truss Type
Qty
Ply
11/09/2018
2730
T4190
B02
COMN
3
1
`
. -".
F-- 21'0'1 l 5-3.141 21'O'l
05XB
ae5x6
F
G
TII
H S3X6
12 y3X4E
6 p
(a)
(a) I m1.5X4
y 3X6D
JS3Xfi
-
�1.5X4 C (a)
(a)
K`3X4
' =3X6(BI)B
A
L=33X6(B1)
II
T 5 R
P sa5 O N
U
a3X4 =4X6 a3%4
=aXB =4X6 81.5X4
SEAT PLATE RED.
SEAT PLATE RED.
SEAT PLATE REQ.
3TO'3
- - 10713
�
F.1 4T4'
Loading Criteria (list)
Wind Criteria
Code I Misc Criteria
DoB1CSl Criteria
♦ Maximum Reactions
(Ibs)
TCLL: 20.00
Wind Sld: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc L/defl Ll#
Gravity
Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Sid: 2014
VERT(LL): 0.118 T 999 360
Loc R+ / R- / Rh
/ Rw / U / RL
B 1468 P /-
/1029 1600 1481
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.234 T 999 240
BCDL: 10.00
Risk Category: II
FT/RT:10(0y10(10)
HORZ(LL): 0.043 O - -
O 2246 1- I-
/1395 /877 f-
EXP: C Kzt NA
Plate Type(s):
HORZ(TL): 0.085 0 -
U 192 /- A
1492 /177 /-
Des Ld: 40.00
Mean Height 16.00 ft
WAVE
Creep Factor. 2.0
Wind reactions based on MWFRS
NCBCLL: 0.00
TCDL: 5.0 pat
Max TC CSI: 0.9
B Brg Width = 7.6
Min Req = 1.7
Load Duration: 1.25
BCDL: 5.0 psf
O Brg Width = 7.6
Min Req = 2.7
Spacing: 24.0'
MWFRS Parallel Dist: 0 to h2
Max BC CSI: 0.965
U Brg Width = 7.6
Min Req = 1.5
C&C Dist a: 4.73 A
Max Web CSI: 0.910
Bearings B, O, & L are a
rigid surface.
Loc. from endwall: Any
Wgt: 278.6 Ibs
Bearings B, 0, & L require
a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21 1
Chords Tens.Comp.
Chords Tens. Comp.
Lumber
A-B 27 0
G-H 1189 -1065
Top chord 2x4 SP #2
B - C 2027 -2489
H - I 637 -162
Bot chord 2x4 SP#2
C-D 1842-2187
I-J 610 -327
Webs 2x4 SP #3
D-E 1864 -2114
J-K 564 -340
Bracing
E-F 1385-1357
K-L 349 -422
F-G 1208 -887
L-M 27 0
(a) Continuous lateral restraint equally spaced on
member.
Maximum Bot Chord Forces Per Ply (Ibs)
Purling
Chards Tens.Comp.
. Chords Tens. Camp.
In lieu of structural panels or rigid ceiling use pudins
B - T 2142 -1532
Q- P 534 -155
to laterally brace chords as follows:
T - S 1652 -1036
P - 0 534 .155
Chord Spacing(in oc) Stert(ft) End(ft)
S-R 1652-1036
O-N 328 -243
TC 24 21.00 26.33
BC 72 0.15 47.19
R-Q 1124 -424
N-L 336 -242
Apply puffins to any chords above or below fillers
,
at 24' OC unless shown otherwise above.
Maximum Web Forces
Per Ply (Ibs)
Webs Tens.Comp.
Webs Tens. Comp.
Wind
Wind loads based.on MWFRS with additional C&C
C -T 608 -374
Q - H 619 -248
member design.
T-E 523 -340
H-O 1466 -1857
E - R 879 -757
0-1 353 -271
Right bottom chord exposed to wind.
F-R 687 -568
O-K 804 -518
Additional Notes
F-Q 593 -550
K-N 352 -354
G 199 240
WARNING: Furnish a copy of this DWG to the
installation contractor. Special care must be taken
during handling, shipping and installation of trusses.
See'WARNING' note below. -
"WARNING- Please thoroughly review Me'A-1 ROOF TRUSSESCSEL1ER'). GENERAL TERMS and CONDITIONS CUSTOMER(•BUYER") ACKNOWLEDGMENT' foml.
Verity design parameters and read notes on distress Design Drawers(IOD) and tha Anlhmy T. Tombo ill, P.E. Raferenoe Sheet before use. Unless otherwise stated on Me Too, onlyAlen
mmedor planes shall be used for the TOO W W ralW. As a Truss Design Engineering (i.e. Speaaby Engineer), de said on any TOD represents an accoplonce of the professional engineers
museasibIty for Me design of the angle Truss depitled an Me TOD a*. under TPl-1. The design assumptions, baring
sunbeam. witaleDy and use of this Truss br any Bandbg is de
Bugdirgb Ue resppnsiNliry o/the Owner, the Owne(s auumriretl agenlwthe BugP gDesigner,mUe motetl of Ue
IRC, UeIBC.balb ldug rode and TPF1. Theeppurralof Ua
Seeking eMairesponsI ame euu¢i
Nyu�dmagel �n and eeiaang
of rulft TooPell--aa
Mmhsset
Anthony T. Tombo III, P.E.
se of Me,Tnusr wage. irsnundaation brat bbDDasigneraiftadC
Dame Mindy -TOLD
Truss
#80083
rupimllelUes of Ue Buldbg Compmmmt Sakryldomutrm(BBCII puboshed by TPlam secAare rererercsd forgererw guidari¢. TPN dermas gn respmeibyties and aulres o(Irre
Oesgnes. Truss Design Emineerand Truss ManufacLuer. artless oNemise dermed by a CmOaG agreed upon In wraing by all Forties mwNed. The Truss Design Ety/neerb NOT Me Barrels
3
4451 St. Lucie Blvd.
DesgnerwTeuss Spam Etgineeraf airy ouldmg. M vCIMf¢ed lerma ereaatlefiredbTPFt.
c<PngluemleatRmrniuef-w��aw�yT.rarmamPa Reprmav�maa:ae�sar,+.inamrmnlsl�N*bdwelm v.wmm� punaasan of u"tRmrnmea-aw4rrr.ramm In. P.E.
Fart Pierce, FL 34946
Job
Truss
Truss Type
City
Ply
11/12/2018
2731
74190
B03
COMN
1
1
f - 21' 5'4' I
- 21'
aa5X6
F_- r G
TI H 43X6
T4
12 ,3X4E
6
(a)
81.5X4
- 03X6D
��3X6
'
fkLSX4C (a) (a)
Ku3X4
s 3X6(B1)B
A
Lsa IX6(81)
U T B2 B R O B3 P
aq O N
a3%4 =H0308 =3X4 E4X6aa3X8 sv4Xb
01.5X4
SEATPLATEREO. SEAT PIATE REQ.
SEAT PLATE REG.
3T0'3
- 1OW13
F7 4T4'
1'I
Loading Criteria (ps0
Wind Criteria
Code! Misc Criteria
Deft/CSI Criteria
♦ Maximum Reactions
(Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udell L/#
Gravity
Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Sid: 2014
VERT(LL): 0.112 U 999 360
Loc R+ / R- / Rh
/ Rw / U / RL
B 1478 /- /-
11033 /273 1483
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.224 U 999 240
BCDL: 10.00
Risk Category: II
FT/RT:10(0y10(10)
HORZ(LL): 0.037. O - -
O 2226 /- /-
11392 /406 /-
EXP: C Kzb NA
Plate Type(s):
HORZ(TL): 0.074 O - -
V 330 /-24 !-
1494 /178 /-
Des Ld: 40.00
Mean Height: 15.53It
WAVE, HS
Creep Factor. 2.0
Wind reactions based on
MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.600
B Brg Width = 7.6
Min Req = 1.7
Load Duration: 1.25
BCDL: 5.0 psf
O Big Width = 7.6
Min Req = 2.6
Spacing: 24.0'
MWFRS Parallel Dist: h to 2h
Max BC CSI: 0.839
V Big Width = 7.6
Min Req = 1.5
C&C Dist a: 4.73 It
Max Web CSI: 0.898
Bearings B, O, 8 L are a
rigid surface.
Loc. tram endwall: not in 13.00 R
Wgt: 278.6 Ibs
Bearings B, O, & L require a seat plate.
GCpi: 0.18
Maximum Tap Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver. 18.02.00.1016.21
Chords Tens.Comp.
Chords Tens. Comp.
Lumber -
A-8 27 0
G-H 816 -1091
Top chord 2z4 SP#2
B-C 1298-2510
H-1 603 -132
Bat chord 2x4 SP M-3032 2x4 SP #2:
C - O 1181 -2135
- J 530 -254
:B3 2x4 SP 2400f-2.OE:
O-E 1944203 -1379
J-K
-417
Webs 2x4 SP#3
E-F 944 -1379
379
K-L 379 -417
Bracing
F-G 820 -910
L-M 27 0
(a) Continuous lateral restraint equally spaced on
member.
Maximum Bat Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
Chords Tens. Comp.
Puffins
B U 3
Q P 572 86
ins
In lieu of structural panels or rigid ceiling use purling
U-T 671 -623
P-O 572 -86
to laterally brace chords as follows:
T-S 1671 -623
O-N 323 -282
Chord Spacing(in oc) Start(ft) End(tt)
S - R 1143 -252
N - L 331 -280
TC 24 21.00 26.33
BC 75 0.16 47.19
R-Q 1143 -252
Apply pudins to any chards above or below fillers
-
at 24' OC unless shown otherwise above.
Maximum Web Forces
Per Ply (Ibs)
Webs Tens.Comp.
Webs Tens. Comp.
Wind
Wind loads based on MWFRS with additional C&C
C - U 400 -375
Q - H 607 -180
member design. -
U-E 597 -176
H-O 974 -1832
Right bottom chord exposed to wind.
E-S 550 -757
0-1 254 -272
F-S 688 -332
O-K 728 -519
Additional Notes
F-Q 370 -54B
K-N 357 -478
WARNING: Furnish a copy of this DWG to the
Q - Ca 244 -95
installation contractor. Special care must be taken
during handling, shipping and installation of trusses.
See'JARNING' note below.
^WARNING^ Pleas. BlorcughlyreNew Ne'A-1 ROOF TRUSSES('SELLER'), GENERAL TERMSand CONDITIONS CUSTOMER CBUYER')ACXNOvAEDOMENP foml.
Verify design paramders and read nates an Nis Tress Design o2wmg (MD)and tle Anthony T. Tombo 111, P.E. Reference sheet before use. Unless oNemise staled
onthe TOD, oNy Alpin
conneMrplatea ehdd beusedbr Ne TOO lob.valid. Asa Tmss Design Engmeerig(i.e.5pedaly Engheor),the seal on any Too represents an acrsptarce of Me prokzsiofal eigineedn
13 q_1 ROOF
responsbiliyfor the design of the single Truse depicted on be Too oNy, under WP1. Tim design assumption.., boding oondigons sulab9y and use of Nis Trues for airy Bulding is Me
aTRD556
Bultliig SNe msponsbily of lbeOmer, Ne Ownefs autgdzM agentw Ne BulPmg Designer,b Ne come#oI NeIRC. NeiBC. tarot bulMdug code antl.TP41.
Thaapprova10M.
..w.o..auw
oNa cwvaa�areM
se�aenw
Anthony
T. Tombo lit. P.E.
c of ubiym�fuvrJOuEmq l,antlang,�worege. bataaatiw aM bm['vg s�M1albeNerrespor vb=iLrya Buld'ug OezigMeIBCrel 0b foss eacmmdiaiooandi
ffioap
Tmw
#80083
giddemesd Na Bdwbv ompmntSfetylm bw(nCgpublisrodby TPlam SBGammfeme f«genemlguidanw. TPl-ldet sNerespauiblmesamdudesoftre
Devgnw,TussD ign Engi.e .WT. Wnufecbaer,unlessoNervbsedefinedbya Conbadnmre upoAMn bNbyagp6eshvoNed.TheTrussDesignElg[neerisNOTMeBOnj
4451 St. Lucie Blvd.
Desgrsrw Tmss System Ergme eaMb mg. Ag bVdr¢ad temc ere as definedb TP41.
C �nyNOa118 M1PMTrua�a-MNmry T.Tombola,P£RePo]uYmdaasGevme+l'nary Nm.6pd titedwM1MtW�rOm Rnma�ef.-1PmfT�iea-NYmyT. Tvrito ill, P.E
Fort Pierce, FL 34946
Job
Truss
Truss Type
Qty
Ply
11/122018
2732
74190 -
B04
COMN
1
1
9'4'
a5X6 �13X4 ix6X6
F G H
T 72 03X4E
TI
6 �
114X6
a
03X6D (a)()>(a)
3X6
en
N 1.SX4C (a)
K33X4
�3X6(B10A•R)B
1
LaMfi(81)
1
=
B1 T S R O P
O N
=3X4 =4Xfi �3X8 a08 =4X6
=4X6 mt.5X4
SEAT PLATE RED.
SEATPtATEREO.
SEAT PLATE RED.
3T0'3
- - 10713�
('1 47`4'
Loading Criteria (ins)
Wind Criteria
Code / Misc Criteria
Def ICS1 Criteria
♦Maximum Reactions (Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udefl U#
Gravity
Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Std: 2014
VERT(LL): 0.116 E 999 360
Loc R+ / R- / Rh
/ Rw / U I RL
B 1484 P !-
11034 280 1440
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CQ: 0.230 E 999 240
BCDL: 10.00
Risk Category: 11
FT/RT:10(0y10(10)
HORZ(LL): 0.037 Q - -
U 2228 P A
11375 /404 /-
EXP: C Kzb NA
Plate Type(s):
HORZ(TL): 0.073 Q -
V 323 /-32 /-
/496 1179 /-
Des Ld: 40.00
Mean Height: 15.03 R
WAVE
Creep Factor. 2.0
Wind reactions based on
MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.883
B Brg Width = 7.6
Min Req = 1.8
tio Load Duran: 1.25
BCDL: $.0 psf
U Brg Width = 7.6
Min Req = 2.6
Spacing: 24.0'
MWFRS Parallel Dist: h to 2h
Max BC CSI: 0.977
V Brg Width = 7.6
Min Req = 1.5
C&C Dist a: 4.73 it
Max Web CSI: 0.556
Bearings B, U, & L are a
rigid surface.
Loc. from endwall: not in 13.00 it
Wgt: 273.0 Ibs
Bearings B. U. & L require a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp.
Chords Tens. Comp.
Lumber
A- B 27 0
G- H 803 -880
Top chord 2x4 SP #2
B - C 1372 -2586
H - 1 745 -1101
Bot chord 2x4 SP#2:B12x4 SP M-30:
C-D 1202-2Z75
I-J 589 -170
Webs 2x4 SP #3 -
D-E 1217 -2161
J-K 534 -182
Bracing
E-F 1015-1550
K-L 394 -429
F - G 1001 -1306
L - M V0
(a) Continuous lateral restraint equally spaced on
member.
Maximum Bot Chord Forces Per Ply (Ibs)
Puriins
Chords Tens.Comp.
Chords Tens. Comp.
In lieu of structural panels or rigid ceiling use purling
B - T 2244 -1066
Q - P 4Z7 -380
to laterally brace chords as follows:
T - S 1783 -727
P - O 427 -3BO
Chord Spacing(in Do) Start(ft) End(ft)
S-R 13 -2
O-N 341 -30
TC 24 19.00 28.33
BC 75 0.15 47.19
R-Q 114143 -323
N-L 341 -301
Apply pudins to any chords above or below fillers
at 24' OC unless shown otherxise above.
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp.
Webs Tens. Comp.
Wind
Wind loads based on MWFRS with additional C&C
C -T 388 -350
Q - H 182 -72
member design.
T-E 496 -110
Q-1 1458 -638
E - R 513 -685
1- O 1063 -1857
Right bottom chard exposed to wind.
F-R 3S9 -156
O-K 648 -483
Additional Notes
R-G 438 -193
K-N 370 -45B
G - Q 400 -6Z7
WARNING: Fumish a copy of this DWG to the -
_
installation contractor. Special care must be taken
during handling, shipping and installation of trusses.
See "WARNING" note below.
-
^WARNING'- Please NpreugNyrenew ore -A-1 ROOFTRUSSES(5E11ER-). GENERALTERMS and CONDITIONS CUSTOMER tli Y ) ACMOWLEDGMENT- farm
Vasty design parameters and read asses an gre Truss Design Dmad ] (Too) and Isla And"T_ Tpmba III, P.E. Refwenee SMe1 before use. UNese othendim stated
on Me MD. omyN
ooryecMrpbesa Obeusedfor Me TDDh We M.Asa Tmss Design Engmeemg(.e.5pe ity Ewhm r).ftwalonany TDDmpresenban acmplaneddrun, pofess. eng'er
Ll.f
9A-1 ROOF
respmsAJityfwdre design of me aingte Trues depend on Me Too only. under TPFl. Tee design aswmdons. batingw Mekns, sulfab'Gty and N's Truss foran, Sa➢dirga Me
dO ETRus5
BUJdug's Ne reaponsmitity of Ua Owrer, are Ownefs autladzed agentwtle BUN6rg Designer,bge mote#o1Ne IRC, pa I6C. beW bWtlmg mdeeM TP41.
Theappmml of de
.nmeaio
aarre:pnwemtyaula eu nag
mdualrlg'na�narN srio eve wla�oau�nerwid
aamosend
Anthony
T. Tombo III, P.E.
o�se minarrtyrnzaa b�dry siao°e oesais erartl Cano�aa�n�AnexasutoxinMeeMDanem
Truss
#80083
guidermesof de Bmldmg Coreonentsawy lMomadon(MCI) osbUsned by TPl ardMCAare refarenmd br gercrzlguitlarlca. ToOdefinnmeresponaI ilitiesarMdudesof
Ma
Ossignen Tmss Design EngincereM Truss ManufaMrer.unlev eMerxise tlef NdyaConeaG agreed uponNwrmrlg by all panne inwNed. Tee Truss Deaign ErlryneerfoNOTMe BUJ'
4451 St. Lucie Blvd.
Oesymrw Truss ayslem ErgbeerolarrybuMmg.Mmpie enxo dNare, ddefneedn TPFI.
r�febNOa119 A-IaNTruvef-MPbry T. TamM111,PE RMMu:Ibn'a EmrmmM1Er arryfwm.sPdvtilfdnldlandmv.'rlEan Mrmlfsb^^f M1 RmfTuvroa-Maury T. TdnM II1, P.E
Fort Pierce, FL 34946
Job
Truss,
TRUSS Type
City
Ply
1111212018
2733
74190
B05
COMN
1
I
1
m5X8 131.5X4 =6X6
E F G
12
6 ��0
H s4X6N
3X6
T
Ja%3X4
fall
=3Xfi(A7)
K= 3X6(Bi)
1 32
T S P O
N M
01.5X4-4X6=3X4 es3X10 =4X4 ss4X6
=4X6 41.5X4
SEAT PLATE RED. SEAT PLATE RED.
SEAT PLATE RED.
3T0'3
-- 10'3'13�
F7. 474'
Loading Criteria (psf)
Wind Criteria
Code / Misc Criteria
Deft/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL 20.00
Wind Sid: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udell L/#
Gravity
Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Sld: 2014
_
VERT(LQ: 0.106 R 999 360
Loc R+ / R- / Rh
/ Rw / U / RL
B 1487 /- /-
/1035 J292 1398
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.210 R 999 240
BCDL: 10.00
Risk Category: It
FT/RT:10(0y10(10)
HORZ(LL): 0.040 P - -
U 2214 /- 1-
11390 1394 /-
EXP: C Kzt NA
Plate Type(s):
HORZ(TL): 0.081 P - -
V 323 /-21 1-
/470 1182 /-
Des Ld: 40.00
Mean Height: 15.00 it
WAVE
Creep Factor. 2.0
Wind -reactions based on
MWFRS
NCSCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.696
B Brg Width = 7.6
Min Req = 1.8
Load Duration: 1.25
BCDL: 5.0 pat
U Brg Width = 7.6
Min Req = 2.6
Spacing: 24.0'
MWFRS Parallel Dist: It to 2h
Max BC CSI: 0.951
V Brg Width = 7.6
Min Req = 1.5
C&C Dist a: 4.73 it
Max Web CSI: 0.982
Bearings B, U. & K are a
rigid surface.
Loc. from endwall: not in 13.00 it
Will: 270.2 Its
Bearings B, U. & K require
a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21 1
Chords Tens.Comp.
Chards Tens. Comp.
Lumber
A-B 27 0
G-H 56 -927
TOP chord 2x4 SP #2 :Tt 2z4 SP M-30:
B - C 1276 -2478
H - I 566 -141
Bat chord 2x4 SP #2
C-D 108-17
I-J -1
Webs 2x4 SP 113
D - E 1087 -1749 49
J - K 410 410 -38381
Bracing
E-F lW4-1316
K-L 27 0
F- G 1004 -1316
(a) Continuous lateral restraint equally spaced on
member.
Maximum Bat Chord Forces Per Ply (Ibs)
Purlins
Chords Tens.Comp.
Chords Tens. Comp.
In lieu of structural panels or rigid ceiling use pur ins
B -T 2112 -947
P - O 417 -393
to laterally brace chords as follows:
T - S 2109 .949
O - N 417 -393
Chord Spacing(in OC) Starl(ft) End(ft)
S - R 2109 -949
N - M 290 -273
. TC 24 17.00 30.33
BC 75 0.15 47.19
R-Q 1476 -511
M-K 298 -270
Apply pudins to any chords above or below fillers
Q - p 753 -182
at 24' OC unless shown otherwise above.
-.
Web Forces
Per Ply (Ibs)
Wind
Webs Tens.Comp.
Webs
Webs Tens. Comp.
Wind loads based on MWFRS with additional C&C
member design.
T - C 347 0
G - P 489 -770
C - R 509 -737
P - H 1450 -654
Right bottom chord exposed to wind.
E-R 571 -189
H-N 1012 -1842
Additional Notes
E-Q 169 -336
N-J 680 -529
F- Q 348 -398
J - M 383 -447
WARNING: Furnish a copy of this DWG to the
Q - G 929 -518
installation.contmetor. Special care must be taken
during handling, shipping and installation of trusses.
See 'WARNING* note below.
"WARNING- Please thoroughly review the'Ml ROOF TRUSSES ('SELLER"). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMENT" form.
Verity design pearradem and mad notes on Ws Truss Design Coaxing (Too) and the Amboy T. Tpmbo III, P.E. Refemnm Sheet betore use. Unless otherwise statetl on the MO. only Alpin
COMedar plates ahaA big used laden TDO to De valid. Asa Tress Callen Entire¢r'vg(i.e. 5peotm, Elgmeer), No seal many Too represents an accaptanixt of the profestiaulenginemn
-A.r ROOF
meponvbi4Hbrthe da ix%.fthesingle Truss t,pideddnthe T00 only, under TP4l.The design assanpdma, bating mntligoM1e,dmaGfiry antl uyedthis Tiat forany BudEingisdm
�lAr cccc
BugGug's be responsbiury of Ne Owner,NeO.vrefs auparhed agents Na euiSrag Designer, in den rmteat of Ne IRC. Ne18C.bwlbuiting rate aM TP4t.
Thaappmvald Ne
..�.�v
resparsbiliryol Nepvner, the Qnels eugidrrziN a9entatle BuiW'ug Designer.n Na mimgd Ne IRC,tM iBC.loW gnWug rate aM TP41. T1xiapPmm1 flha
TDDmdm,fietl
Anthony. TDmbo III, P.E.
y
¢seelimn.f Infannalion(MCI) pngslu0 be tla iNlitmWeenced Designer aMeanhagor. Mnoles setMNlhe TOD UM Me pracEces and
80083
#.Luca
theTruss.LdW'vgampme,sfafaty aTPI ndSBCA
s Tafanss m
Oger,Tuss Design Engme�er and Manufa�, unhhot aftlw#eemrned by a Cmtrad egrect upm vmb by 0 patine involved. TM Tmai Design Eo inerr Is NOT the Bu�
4451 Lute
aesignera TwssywmFiQeerday Imw'ag. Ae redmruea tame aimCdemd bTPpt.
fgmgfitOIDte FIRMTussea-MCmrf T.Tmib Y4 PE flry rbnMdeiaEmnenlFary(mn,epd,msl wMon PavrSa, rem�'+e WAtRmlTuva-NNmrT.TmiEo el, P.E
er
Fort Pierce, FL 34946
3494
Job •
Truss
Truss Type
.Qty
Ply
111121211E
2734
T4190
B06
COMN
1
1
I
ITV I
is
-1 - - - -
=5%8 N1.5X4=4X6 =5X8
E F G H
T 12
-4X6
T
6 m3X60
a 3X6
03X40 (a) (a) (e)
J K33X4
[n
EZ3X6IA7)B
L Mfi(B1) I
1 s�
U T S R O P
V O N
11
W
UI1.5%4 sa3X4=4X6 =4XB m4X6tA4X4
=4X6 1111.5X4
SEAT PLATE RED. SEAT PLATE RED.
SEAT PLATE REG.
3TG'3
- - - 109'13
).1 4T4'
11.1
Loading Criteria led)
Wind Criteria
Code / Misc Criteria
DefUCSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Sid: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udell U#
Gravity
Non -Gravity
TCOL: 10.00
Speed: 160 mph
TPI Sid: 2014
VERT(LL): 0.121 T 999 360
Loc R+ / R- / Rh
/ Rw / U / RL
B 1469 /- /-
11016 1293 1356
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.241 T 999 240
BCDL: 10.00
Risk Category: II
FT/RT:10(0)/10(10)
HORZ(LL): 0.041 P - -
V 2295 A /-
11417 1431 /-
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.082 P - -
W 292 1-85 /-
1459 1184 /-
Des Ld: 40.00
Mean Height: 15.00 it
WAVE
Creep Factor: 2.0
Wind reactions based on
MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.905
B Brg Width = 7.6
Min Req = 1.7
Load Duration: 1.25
BCDL: 5.0 psf
V Brg Width = 7.6
Min Req = 2.7
Spacing: 24.0 °
MWFRS Parallel Dist: h to 2h
Max BC CSI: 0.943
W Brg Width = 7.6
Min Req = 1.5
C&C Dist a: 4.73 it
Max Web CSI: 0.718
Bearings B, V. & L are a
rigid surface.
Loc. from endwall: not in 13.00 it
Wgl: 9.0 25lbs
Bearings B, V. & L require
a seat plate.
GCpi: 0.18 _
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp.
Chords Tens. Comp.
Lumber
A-B 27 0
G-H 1053 -1471
_
Top chord 2x4 SP #2
B - C 1300 -2480
H - 1 530 -604
Sot chord 2x4 SP#2
C-0. 1108-1888
I-J 738 -232
Webs 2x4 SP #3
-
D-E 1134 -1841
J-K 648 -237
E-F 1053 -1471
K-L 456 -392
Bracing
F- G 1052 -1470
L- M 27 0
(a) Continuous lateral restraint equally spaced on
member.
Maximum Sot Chord Forces Per Ply (Ibs)
Purlins
Chords Tens.Comp.
Chords Tens. Comp.
In lieu of structural panels or rigid ceiling use puffins
B - U 2124 -985
Q - P 501 -68
to laterally brace chords as follows:
U -T 2121 -9B7
P - O 505 -537
Chord Spacmg(In oc) Stan(ft) End(ft)
T-S 1604 -610
O-N 300 -381
TC 24 15.00 32.33
S-R 1604 -610
N-L 309 -377
BC 75 0.15 47.19
Apply pudins to any chords above or below fillers
R-Q 501 -68
at 24' OC unless shown otherwise above.
Maximum Web Forces
Per Ply (Ibs)
Wind
Webs Tens.Comp.
Webs Tens. Comp.
Wind loads based on MWFRS with additional C&C
U - C 281 0
H - P 645 -1033
member design.
C-T 436 -597
P-1 1557 -743
Right bottom chord exposed to wind.
E - T 540 -144
1-0 1040 -1934
E-R 152 -2T7
O-K 709 -568
Additional Notes
-
F - R 490 -558
K - N 394 -439
WARNING: Furnish a copy of this DWG to the
R- H 13DO -714
installation contractor. Special care must be taken
during handling, shipping and installation of trusses.
See 'WARNING* note below.
^WARNING' Please foreuglYy review Me'MI ROOF TRUSSES(SELIER-). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER') ACKNOwLEDGMENI' frnM.
'�
ve*&sgnpaameWmaWmdwmw Ma Tmss Design Drredg(rDD)andfe Mfony T.T=Wtll.P.E Relerenm Steel oefae use. UNev ogawnse staled onfe TDD.oMy Plpi
mnrremw plates stall be used for the TDD M W w1d. As a Trans Design Encynadigire. Sperdafty agmeer).Me wad on a" Me represanb an a�ptance Of Me gotessual engineeAl
fs"
A-t ROOF
�Tn1155E5
resporezlmTyroetne desgnorgle single Trussdepicmdon Mo TDDony, under TP4l. The design aswmpeom. badug mtlitions, wiWaly andese of MS Truss fwalry
scolding
BuatlMg6MeresponsSttyoffe Owar,tbe Owarssutnoradagenlmfeaundlg Desgner.mmewnletlof Me IRC,MeIBC.bretbddhg WaaMTP t-
Tile applvval of Me
•�ao.�a
Off&IRC, aMTPN.TMapprnvalmfeTDDaMessand
facing dgn
Anthony Tombo 111, P.E.
%r
uepof McTens.ineraingtMD.vnehauNu¢eaaednan admer,mfeanleat
an conceder. alessemsnMe TDD
off�ancedfr gSgner and contender.
useoffe nGW'ug fon,crg,sterzge. hibernation arWD2 be me Designer
ate Mepsof ate
Truss
#.Luca
xbimoan
WI -I
of Me and SBAa TPIrnmef sferesps
of Me Smeylandectons.,empubrsnere by TPIaM Sa CAaesdagred!u for general by
Danign Engindutiesolfe
esignlgngederent
T. MonufacWrer, umessofervdw defineabya COnaamagreea upon in coding by all plNes invoNetl. Tie Tevu Design Engineer is NOT Me BugC
Desgner,Truss DesignE 61 probes
Designer.
4451 Blvd.
gineeald
carrion Designer or tons svamm Engineer menu bmlala. An mplaluad eamo alo as aerlaa In rPt-1.
Lepyd9MO:Lte Mt amlTnueb-MNmY T. TanW In, P.E RepvlwM Ntivsammmlb anY ram. b pW Wledv+Nat Ne rrti0en petmbsbn raft PmlTrvsava-AnamyT. Tanto III, P E
Fort Pierce, FL 34946
Pierce, FL
Job
Truss
Truss Type
City
Ply
11/12/2018
2735
74190
B07
COMN
1
1
=6X6 m3X4 m4XG 111.5X4 a5X8
D E F G H
a5X6
TT
j
c
T 6p
I
03X4C (a) (a)
J33X4
(a)
(a)
=3X6(Bt)B
A
K=LX6(B7)
11
33
U T S R Q P O
N M
111.5X4 =3X4 -4X6 a3X4 =4X10 ea06 II4X4(R) =4X6 ®1.SX4
SEAT PIATE REQ. BEAT PIATE REQ.
SEAT PLATE REG.
37'0'3 -
1OW13
�1 4T4'
Loading Criteria fibs()
Wind Criteria
Code / Misc Criteria
Def11CSl Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in Ice Udell L/#
Gravity
Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Still: 2014
VERT(LL): 0.130 T 999 360
Lac R+ / R- / Rh
I Rw / U / RL
B 1452 /- /-
/992 /606 /314
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CQ: 0.258 T 999 240
BCDL: 10.00
Risk Category: ll
FT/RT:10(0y10(10)
HORZ(LL): 0.044 O - -
N 2372 /- P
11438 1907 /-
EXP: C Kzb NA
Plate Type(s):
HORZ(TL): 0.088 0 - .
V - 265 /-146 /-
1449 1196 /-
Des Ld: 40.00
Mean Height: 15.00 ft
WAVE
Creep Factor. 2.0
Wind reactions based on
MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.643
B Brg Width = 7.6
Min Req = 1.7
Load Duration: 1.25
BCDL: 5.0 psf
N Brg Width = 7.6
Min Req = 2.8
Spacing: 24.0
MWFRS Parallel Dist: h/2 to h
Max BC CSI: 0.927
V Brg Width = 7.6
Min Req = 1.5
C&C Dist a: 4.73 ft -
Max Web CSI: 0.826
Bearings B, N. & K are a
rigid surface.
Loc. from endwall: not in 13.00 It
Wgt: 267.4 Ibs
Bearings B, N, & K require a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver. 18.02.00.1016.21
Chords Tens.Comp.
Chords Tens. Camp.
Lumber
A-B 270
G-H 898 -1262
Top chord 2x4 SP#2
B-C 1320-2481
H-1 271 -137
_
Bat chord 2x4 SP#2
C-D 1183 -1997
1-J 867 -318
Webs 2x4 SP #3
D - E 11-197
J - K 879 -400
Bracing
E-F 898-1261
K-L 27 0
(a) Continuous lateral restraint equally spaced on
F - G 898 -1261
member.
Mazimum Bat Chord Forces Per Ply (Ibs)
Purlins
Chords Tens.Comp.
Chords Tens. Comp.
In lieu of structural panels or rigid ceiling use puriins
B _ U 2133 -1020
Q - P 224 -67
to laterally brace chords as follows:
U - T 2131 -1022
P - O 224 -67
Chord Spacing(in oc) Start(ft) End(ft)
T-S 1713 -698.
O-N 580 -651
TC 24 13.00 34.33
BC 75 0.15 47.19
S-R 1713 -731
N-M 316 -486
Apply pudins to any chords above or below fillers
R - Q 1779 -731
M - K 316 -48
at 24" OC unless shown otherwise above.
Maximum Web Forces_
Per Ply (Ibs)
Wind
Webs Tens.Comp.
Webs Tens. Comp.
Wind loads based on MWFRS with additional C&C
U - C 230 0
Q - H 1602 -878
member design.
C - T 370 -479
H - O 812 -1375
Right bottom chord exposed to wind.
D-T 451 -121
0-1 1646 -813
Additional Notes
D-R 168 -139
I-N 1081 -2020
R-E 236 -Z7
N-J 716 -581
WARNING: Famish a copy of this DWG to the
E - Q 397 -727
J - M 395 -435
installation contractor. Special care must be taken
G- Q 3' -436
during handling, shipping and installatton of trusses.
See °WARNING° note below.
-WARNING- Please tthorouglay review Me'A-1 ROOF TRUSSES(5ELLER). GENERAL TERMS and CONDITIONS CUSTONHUZSWER') ACKNOWLEDGNII P War.
Va* design parameterseM read notes on ros Truss Design Dsmss tg (mD)and gig AnNwry T. Torso III, P.E Reference Sheetbe(ore use. Unless oNervnse abtad on Ne TDD, anNAlpn
I
wnn phhsshagbeusedfaftMDto WnIW. As a Truss Design Eigineerug(to. Specialty Engineer), ere seal on any TOD represenerin aanplarce of the professional enyne
q-g ROOF
gty and e of Nh Truss Wang Building Mlle
regainsibJiry farfg design of Me single Truss depicted th on e Too only, under TPM. The design assurn,tims, loading conditions. suitaNuse
`�
�TRT155OF
BWdbg 6 me responsibility of the owner. Me Cvmefs aumwhed agent or Me BattlMco Sarong Designer. In e cannot sighs IRC. to (Be. WalbWdig code and TPl-1.
Theawn,miofee
a.m.a>aov
code and! SsetoutnptheeM�
*a Me casnandof Me Me. Me ISO and
or Me xing
Truss, vexla�'ma
nethepraaicensyx�a
Anthony
T. Tombs Ill, P.E.
Whiling sla2ge. imunlauun and boent
u rU stalll bethemoscav'bllty of Me Building Designs Contrbuffdaiactor. ninccla
Truss
#80083
guidelines of Pe Building component Safety infoonabon(iSM) published by TPI am SBCA are referenced for geneol guidance. TPI-1 dayms Me responsibilities and Mattes of the
Designer. Than Design Engineer and Truss Manufacmrey untessoNervnsa defined by a Contract agreed upon to writing by at parties invohreo. The Truss Design Engineer is NOT Me ballots
1
,
4451 St. Lucie Blvd.
Designer ortmu snwm Engineer ofany building An al+talired temp areas darmoe InTPp1'
Co,scNO 2018 A-1 Rmt Tuaees-AMwny T. TamWIII,P.E RePodutlly,dNsd=sent hanytwm,hpMWb]Mtlwt the wneen porn on of M1 PmlTussea-MNwyT. TamW III, P.E.
Fort Pierce, FL 34946
Job
Truss
Truss Typo
Dry
111122018
2860
74190
B08
COMN
1
[pill
254'
55X8 O =4X6 101.SX4
sa5X6
D E_.jX4 F G
H
72
6
T —
T
r �3X40 (a) (a)
143X4
(a)
ESX6(BA7) B
1
Jm K 6(B1)
3
S R D P O N
=q M L
11
07.5X4 =3%4 =4X6 =3X4 =—SX70 =4%6
OI1.SX4
SEATPLATEREQ. SEAT PLATE RED.
SEAT PLATE RED.
3TW3
- - 10-3.13-� -
F,t 4T4'
�•(
Loading Criteria (psq
Wind Criteria
Code / Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in too Udell L/#
Gravity
Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Std: 2014
VERT(LL): 0.143 P 999 360
Loc R+ / R-- / Rh
/ Rw / U / RL
B 1408 /- 1-
/950 1588 /271
SCLU 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.285 P 999 240
BCDL: 10.00
Risk Category: It
FT/RT:10(OY10(10)
HORZ(LL): 0.046 O - -
M 2553 /- 1-
/1518 1988 /-
EXP: C Kzb NA
Plate Type(s):
HORZ(TL): 0.091 O - =
T 194 /-275 A
/429 1247 /-
Des Ld: 40.00
Mean Height: 15.00 it
WAVE
Creep Factor, 2.0
Wind reactions based on
MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0,977
B Brg Width = 7.6
Min Req = 1.7
Load Duration: 1.25
BCDL: 5.0 psf
M Brg Width = 7.6
Min Req = 3.0
Spacing: 24.0'
MWFRS Parallel Dist: h2 to h
Max BC CSI: 0.998
T Brg Width = 7.6
Min Req,= 1.5
C&C Dist a: 4.73 it
Max Web CSI: 0.873
Bearings B, M, 8 J are a
dgid surface.
Loc. from endwall: not in 6.50 it
Wgt: 243.fi Ibs
Bearings B, M, 8 J require
a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp.
Chords Tens. Comp.
Lumber
A-e. 27 0
F-G 801 -1176
Top chord 2x4 SP #2 :T2 2x4 SP M-30:
B - C 1289 -2392
G - H 802 -1176
Bot chord 2x4 SP #2
C - D 1196 -2053
H - I 1177 -528
Webs 2x4 SP #3
D-E 1234 -1990
I-J 833 -398
E-F 801 -1176
J-K 27 0
Bracing
1
(a) Continuous lateral restraint equally spaced on
Maximum Bot Chard Forces Per Ply (Ibs)
member.
Chords Tens.Comp.
Chords %Tens. Comp.
Purlins
B - S 2050 -1001
O - N 667 -752
In lieu of structural panels or rigid ceiling use pudins
S - R 2057 -1003
N - M 667 -762
to laterally brace chords as follows:
R - Q 1787 -757
M - L 396 -713
Chord Spacing(in oc) Start(ft) End(ft)
Q-P 1787 -7,57
L-J 399 -710
TC 24 11.00 36.33
P-O 1988 -856
BC 75 0.15 47.19
Apply pudins to any chords above or below fillers
at 24' OC unless shown otherwise above.
Maximum Web Forces
Per Ply (Ibs)
Webs Tens.Comp.
Webs Tens. Comp.
Wind
Wind loads based on MWFRS with additional C&C
S - C 157 0
G - O 495 -551
member design.
C-R 286 -325
O-H 2292 -1252
D - R 417 -84
H - M 1232 -2125
Right bottom chord exposed to wind.
D - P 243 -180
M -1 789 -610
P - E 246 -2
I - L 373 -455
Additional Notes
E - O 548 -995
Negative reaction(s) of -275# MAX. from a non -wind _
load case requires uplift connection. See Maximum
Reactions.
WARNING: Fumish a Copy of this DWG to the
installation contractor. Special pre must be taken
during handling, shipping and installation of trusses. -
See •WARNING' note below.
-WARNING- Please thoroughly ravine, the'A-1 ROOF TRUSSES PSELLEW), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMENT form.
-4
-M
Velgy deep paremebrs and read notes on this Truss Design Draxvg(mD) and Me Anthony T. Tdnba Ill. P.EReMmnw SWetWbmu .UntemoNomiaestatedan Oe TDD,ordYAlPin
mmledar pbtea stleg De used fwthe TpO bEa vagd. Asa Truss Design Etgineervp im.specary Engineer), the seal an any Too represents an acceptance olthe professional engineedn
A-1 WOF
aTRu5eTl3
respwysLyliry brthe design oltheangte Trussdeplcted on eye Too only, under TPl-1.The design assumptions, leading auditions, sMaNUyseduseafthb Truss Warty Bugding*the
augGlg sure rssporrstitiry Pl the Owner, the Ovmeh euthor¢ed agentm the Bugdug Designa,Nthe codetl of the lRC. the IBC, local Nylding mde and TPL1.
Theappreral Prtha
.nmm.wov
zed haavuyg�s�naoDEeiaspmsiEol Na eudRdug 01DasgnetaM ksPset
the
Anthony T. Tombo ill, P.E.
,�¢e o�INe inasthlam�WLgMM'mg,�storage vm¢Smllaum Conhee� wlNNe TOD
and przc4ms arW
Truss
#60DB3
guidelines olelesutli,g eomponentsarery idormaene(BSCII PUtASIgO MTPIaM SBCAare rebren¢tlforgeneml guider®. 1D1-t defirea therespm4Dgitiesaetl du4es olden
Deal Truss Design ENneur and Truss Manuramrn.uNses oNemias derued%a centred agreed upon In vei4ng Meg Parl uiMvee. The Truss Design E�neers, NOT me Bu'
4451 St. Lude Blvd.
cat ovTie MSTdanY bold F Pig aaWNrded tam6 areda deruvdmTPF1,
MNmy i. Twnln N. P£ PepMutThn W Ma dm�nlhm/Mm, ePdyyTWd Wlnamewr0a, aNmSv,NA-1 FmfTry¢aea-MIvry T. Tanbr III, P£
Fort Pierce, FL 34946
Job Truss Truss Type Qty Ply 1111MU16 2737
7.4190 B09 I HIPM 1 1
Loading Criteria (ps0
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL 10.00
Des Ld: 40.00
NCBCLL• 10.00
Load Duration: 1.25
Spacing: 24.0'
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
14
SEAT PLATE RED.
F 1'-�
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: It
EXP: C Kzt: NA
Mean Height 15.00 R
TCDL- 5.0 pelf
BCDL: 5.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 R
Loc. from endwall: not in 9.00 R
GCpi: 0.18
Wind Duration: 1.60
Puffins
In lieu of structural panels or rigid ceiling use purlins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(R) End(R)
TC 24 9.00 15.27
BC 100 0.15 15.27
Apply purling to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical exposed to wind pressure.
Deflection meets LI360.
111.5x4
SEAT PIATE RECI.
Code I Misc Criteria
DetIICSI Criteria
♦ Maximum Reactions (Ibs)
Code: FBC 2017 RES
PP Deflection in loc Udell L/#
Gravity Non -Gravity -
TPI Std: 2014
VERT(LL): 0.019 C 999 360
Lee R+ / R- / Rh / Rw ! U / RL
Rep Factors Used: Yes
VERT(CL): 0.038 C 999 240
B 679 /- !- /486 1274 /314
FTIRT:10(Oy10(10)
HORZ(LL): 0.008 F - -
H 602 /- !- /381 /258 /-
Plate Type(s):
HORZ(TL): 0.015 F - -
Wind reactions based on MWFRS
WAVE
Creep Factor: 2.0
B Brg Width = 7.6 Min Req = 1.5
Max TC CSI: 0.736
H Brg Width = 6.9 Min Req = 1.5
Bearings B & H are a rigid surface.
Max BC CSI: 0.981
Bearings B & H require a seat plate.
Max Web CSI: 0.789
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 81.21bs
Chords Tens.Comp. Chords Tens. Comp.
VIEW Ver: 18.02.00.1016.21
A-B 27 0 C-D 380 -629
B - C 535 -929 D - E 159 -146
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
B - G 783 -773 G - F 499 -471
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
C - G 344 -323 D - F 460 -621
D-G 417 -67 E-F 197 -188
—WARNING— Please thoroughly review Me'A-1 ROOF TRUSSES ( -SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER(•BUYER") ACKNOWLEDGMENT' form.
Veriy design paramelsn antl read nouns on this Tress Design Crewing (TDD) end Me Antlwny T. Tombo III, P.E. Reference Shestlrefore use. Unless otherwise stated on the Too, ony Arpin
mnreprphtessMflbeusedfor Me TDDtobavalid. As a Truss Design Engineering(i.e.Specialty Enginaar).Mesea!on any Too represents an aaepuase, of the professional engino sn Nq-r ROOF
respm,sidury for the design ofthe single Truss depicted on the Too only, under TPI-t.nodesgn assumptions, loading mndidone. sudabiliy and use oftais Tmse W any Binding is Me .1fRMS301i
Bugding OemsironsWiyof Ne Owner. eD rsauN dagentw Ne Binding Designer,inihecmM1sato(NeiRC,N IBC.bmlbuadingmdeend TPL1. Theeppmwalof Ne ••uow++e
responsDrliryof Ue D,vner, the PmefsauNor'Ired agent or Ne BuiW'ug Designer. in lbe mntector NalRC. tla IBC,Ipal bu�tlmg rode and TPN. The eppmval of Ne TOD aM arry fiep Anthony T. Tombo Ill, P.E.
use of the Truss. intlud'vg landGng, slorege,'vag0atanand bmdrg atiaO Ee the responvDi4ry o/fM BuWug DesignerarM Conaatlor. All roles utautlo Ne TOD aM Ne prx4ces and
guideger.oflbe Building Component safety lNomation(BSlesso0SRMby TPlartly a CAarerefgeed.,on In varal guidance. es in defines rice rest Desl Engineer
allies of the Tress #BODB3
Desigrar. Truss Design Eng'mmreM Truss ManulaCwer, unless odamise defuredbya Dormaa agreed uponNwrNrg by all names involved. The Truss Design Ergitleer is NOT the BuilC a 4451 St. Lucie Blvd.
Desimreror Toss Slem.Eginee.manr anmlog. Ar repirar ea mono areaadarmadmTPu. „pe Fort Pierce, FL 34946
Job Truss Truss Type Oty Ply 11/1212018 2801
74190 B10 I HIPM 1 1
Loading Criteria (psf)
TCLL: 20.00
TCDL 10.00
BCLL: 0.00
BCDL 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0
I
i r
3531, 1B7#` 167#p-9
-4-Y0'8ta 7__I _Z 1e 3'�II
ea4�
.TRATEREa. SEAT RATE REQ.
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt NA
Mean Height: 15.00 It
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 it
Loc. from endwall: not in 9.00 R
GCpi: 0.18
Wind Duration: 1.60
Lumber
Tap chord 2x4 SP #2
Bet chord 2x4 SP 2400f-2.OE
Webs 2x4 SP #3
Special Loads
-(Lumber Dur.Fac =1.25 / Plate Dur.Fac.=1.25)
TC: From 60 plf at -1.00 to 60 plf at 7.00
TC: From 30 plf at 7.00 to 30 plf at 15.27
BC: From 20 pit at 0.00 to 20 plf at 7.03
BC: From 10 plf at 7.03 to 10 plf at 15.27
TC: 253lb Cone. Load at 7.03
TC: 187lb Cone. Load at 9.06,11.06,13.06.15.06
BC: 501 Ib Conc. Load at 7.03
BC: 1301b Conc. Load at 9.06,11.06,13.06,15.06
Purlins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 7.00 15.27
BC 103 0.15 15.27
Apply purling to any chords above or below fillers
at 24' OC unless shown otherwise above.
Wind
Wind loads and reactions based on MWFRS.
Right end verfical not exposed to wind pressure.
163.1
5010 1304 1� 1J0 1300
Code / Misc Criteria
De0/CSI Criteria
A Maximum Reactions (Ibs)
Code: FBC 2017 RES
PP Deflection in loc L/de0 L/#
Gravity Non -Gravity
TPI Std: 2014
VERT(LL): 0.045 G 999 360
Loc R+ / R- / Rh . / Rw / U / RL
B 1269 /- /- /- 1592 /-
Rep Factors Used: Vanes b
L): 0.089 G 999 240
FT/RT:10(0)/10(10)
HORZ(LL): 0.015 F - -
H 1705 /- /- !- 1808 /-
Plate Type(s):
HORZ(TL): 0.029 F - -
Wind reactions based on MWFRS
WAVE
Creep Factor: 2.0
B Brig Width = 7.6 Min Req = 1.5
Max TCCSI: 0.678
H Big Width =6.9 Min Req=1.5
Max BC CSI: 0.974
Bearings B & H are a rigid surface.
Bearings B & H require a seat plate.
Max Web CSI: 0.954
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 77.01bs
Chords Tens.Comp. Chords Tens. Comp.
VIEW Ver: 18.02.00.1016.21
A-B 27 -20 C-D 798 -1839
B-C 969-2127 D-E 3 -24
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
Chords Tens. Comp.
13-G 1812 -805
G-F 1267 -675
Maximum Web Forces
Per Ply (Ibs)
Webs Tens.Comp.
Webs Tens. Comp.
C- G 327 0
D- F 897 -1659
G - D 788 -169
E - F 249 -289
-WARNING- Please thoroughly review Me'A-t ROOF TRUSSES('SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER (BUYER') ACNNOMEDGMENP form.
Verily design immersion and read notes on this TmsS Design Drunung (TOD) and Me AnMony T. Tombo 113. P.E. Reference sheet before use. UNass otnervose staled on Me TDD, ony Alpin
sha0 be used far Me Too bbe valid. Asa Truss Design EngmeerFg(i.e. Ssaxily Segment), Me seal on any Too mpmsenh an acceptance a Me professional enginecon
A-1 RnDF
connector plates
Me TOD TPl-1. The design assumpllona, loading conditions, sudabiliy and use of Mis Trusts for any Building is the
®TRUSSES
respow'biliyror Me design of Me single Trues deplored on are, under
Buddug uMafaponsSier. Me Owsau, Oxne Oe Building Devnn Mecenm,dof IBC, locelbuddingmde entl TPl-1. The approval of Me
..m�.1v
C,IMIthe
entw Uhedagenlw
Of Me IBC treat and TP4l.TentImva
OwrelsauMmvN abonan Mesu Designer, in Msbuty
Anthony. TOmbO III, P.E.
y
atonMelRe.
contracetle
santl
Me TfOe.hxludug haM broom,bs be MeraponsibirM1y atone Canhacb Dandth.pro omand
use Me TrofNeO.Mgmin
0083
#.
Vs li Bwltiag CemponentaarerylMomadon(eaCl)pum, IryTPl nufDes'gmlV l dotes MemsnMe MOD doWsd
guide ent fetyiusNde (OS OU NOMeeBui
aafiresmerespoDeig
.ortha bSBCAamfeagre urorne tgbyaUe.Th
Engirt
Oaimwl, Tmss Desgn Ergineerantl Tmss Marruh,ana,rWess omerwoe riot Mbya Coneariagreetl upon in wnEng by au paths mMVN. 1Te Truza Oeslgn Erynee+o NOT Me Build
Lucie
4451 St. LUtie Blvd.
oayr,aror„nRa sysawwm Ergthaar prime rmm�. Ar p.ptarvaa maser tlthTPI-1
... _ _, .... �,a .,,�. mwhmeewd�4maw,mm awrre::immA-1 RwrTr�n-Awmvr.raam lu. P.E
Fort Pierce FL 34946
.
Job Truss Truss Type Oty Ply 111122018 2855
74190 B11 I HIPM 1 1
Loading Criteria (psf)
TCLL 20.00
TCDL 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL 10.00
Load Duration: 1.25
Spacing: 24.0"
Lumber
Top chord 2x4 SP #2
Bat chord 2x4 SP #2
Webs 2x4 SP #3
1'T10 --�
bz3X3
12
6 � a1.5X4C
_
a2X4(A1) B
A
N3%fi
p
SEAT PLATE RED.
Wind Criteria
Wind Stoll: ASCE 7-'10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 it
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: h/2 to IT
C&C Dist a: 3.00 it
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Purlins
In lieu of structural panels or rigid ceiling use puffins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 9.00 10.64
BC 43 0.15 10.64
Apply purlins to any chords above or below fillers
at 24" OC unless shown ctherwise above.
Hangers 1 Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical exposed to wind pressure.
Deflection meets U360.
Left bottom chord exposed to wind.
Code / Mise Criteria
Code: FBC 2017 RES
TPI Sid: 2014
Rep Factors Used: Yes
FT/RT:10(0)/10(10)
Plate Type(s):
WAVE
1OT10 i
DeflICSI Criteria
PP Deflection in loc Udell U#
VERT(LL): 0.014 G 999 360
VERT(CL): 0.013 G 999 240
HORZ(LL): 0.010 G - -
HORZ(iL): 0.013 G - -
Creep Factor. 2.0
Max TC CSI: 0.324
Max BC CSI: 0.967
Max Web CSI: 0.969
Wgt: 64.4 Ibs
VIEW Ver: 18.02.00.1016.21
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ / R- / Rh ! Rw / U / RL
B 495 /- /- /509 1215 1314
F 416 /- !- 1456 1188 /-
Wind reactions based on MWFRS
B Big Width = 7.6 Min Req = 1.5
F Big Width= - Min Req=-
Beaming B is a rigid surface.
Bearing B requires a seal plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-B 27 0 C-D 392 -Z37
B - C 604 -545 D - E 395 -174
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
B - G 493 -503 G - F 159 -146
Maximum Web Forces Per Ply (Ibs)
Webs
Tens.Comp.
Webs Tens.
Comp.
C - G
399 -330
G - E 748
-853
D-G
338 -123
E-F 852
-715
-WARMING- Please thoroughly reviewMe'XI ROOF TRUSSESCSELLER'7, GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER') ACKNOWLEOGMEM"folm. A
Venly design Parumeters and read notes on thus Truss Design D2wing(mD) and the Anthony T. Tanbo in, P.E. Reference about before use. Unless otherwise slated on the MD. only Net
wmedorpPWss Hbeusdforthe TDDWbevdid. Asa True Design Enginerkq(Le.SPe ityEngmeer).Ooualonany TDDmpresen%anattpl of Nepmfessbmiengineetul �MA-IROOF
respmsititity for the ensign of Pe single Truss depicted on Pe Too aYy, under TPM. The design assumah padts. leading condits, suitability and use of Pis Truss for arty Bunting is the STRUSSE5
Buldrg in Pe responsibibty d Pa Owns, Me Owners authorized.gent or Pe RWdrg DesigneePthe Contetld Pe lRC, theIBC, btal buJtling rode eM TPI-1. Theappmrelof Pa •.00�a
mspa ityofPe Owneeto Ownersadhoraedagentorao BuiWmg Desgner.mMe.nW4.fth.IRC,to IBC,loral WgE'ugwtleaM 1-1. Theapprorelof Me TeDand.MfiaW Anthony. Torl Ill, P.E.
use of the Truss,IMWrig hantlrug,storage, PsWaam antl bmc'vg shaA be the responsiblydthe BuiW'ug DesgneraM Contrxta. Mrotessetoutin Pe TODardthepeacs.and y
80083
Uues,nar. Trusts Design Erlgmn hoard Tams Marrnufam t. indeed odindessss darranldbby a a Da,o-aa agreealwon in mmtg by pardesruenkee. The TnmsDedign Ergnoars NOT Me sister #.Luca
Designer orTruss system Er,hoe" f aM tuddgy M repter ed tans ere se domed isTPI-1. 4451 SL Lurie Blvd.
('m*bNOX1180.1flul Tnssea-NNmvT. TanEo IO. P.E Retto]efu,M,eium atanyfivm.bpMOXedwRnM1Te wMma�ofA-I RmlTxuea-M T. TanM 111. P.E. Fort Pierce. FL 34946
Job Truss Truss Type Oty I Ply 11/12/2018 - 2802
T4190 1 B12 I HIPM 1 1
Loading Criteria (psf)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
it
sEPTRA oaod.
F 1,-1
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt NA
Mean Height 15.00 It
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist:0 to h/2
C&C Dist a: 3.00 It
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Special Loads
-(Lumber Dur.Fac =1.25 / Plate
Dur.Fac=1.25)
TC: From 60 plf at -1.00 to
60 pit at
7.00
TC: From 30 pit at 7.00 to
30 pit at
10.64
BC: From 20 plf at 0.00 to
20 plf at
7.03
BC: From 10 plf at 7.03 to
10 plf at
10.64
TC: 253 Ib Conc. Load at 7.03
TC: 187 lb Conc. Load at 9.06
BC: 501 lb Conc. Load at 7.03
BC: 130 Ib Conc. Load at 9.06-
Pudins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 7.00 10.64
BC 75 0.15 10.64
Apply pudins to any chords above or below fillers
at 24' OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads and reactions based on MWFRS.
Right end vertical not exposed to wind pressure.
Left bottom chord exposed to wind.
Code / Misc Criteria
Code: FBC 2017 RES
TPI Sld: 2014
Rep Factors Used: Varies
FT/RT:10(OU10(10)
Plate Type(s):
WAVE
1
--
° ,sef
wig
Defl/CSI Criteria
PP Deflection in toe L/defl L/#
VERT(LL): -0.021 C 999 360
alitkORtQ: 0.028 C 999 240
HORZ(LL):-0.007 E - -
HORZ(TL): 0.010 F - -
Creep Factor. 2.0
Max TC CSI: 0'531
Max BC CSI: 0.715
Max Web CSI: 0.470
Wgt 54.6 lbs
VIEW Ver: 18.02.00.1016.21
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ / R- / Rh / Rw / U / RL
B 776 /- /- /- /480 /-
E 1060 /- /- /- 7783 /-
Wind reactions based on MWFRS
B Big Width = 7.6 Min Req = 1.5
E Brg Width =- Min Req = -
Bearing B is a rigid surface.
Bearing B requires a seat plate.
Maximum Tap Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A - B 27 -20 C - D 589 -837
B-C 743 -1043
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
B-F 853 -604 F-E 5 -5
Maximum Web Forces Per Ply (Ibs_)
Webs Tens.Comp. Webs Tens. Comp.
C-F 195 -215 D-E 740 -1023
F - D 1233 -865
"WARNING' Please Nomu,hly review Me -A-1 ROOF TRUSSES(•SELLER•), GENERAL TERMS and CONDITIONS CUSTOMER(•BUYER") ACMOMEDGMETIT" roam.
-4
Verify design pamoesmand mad notes on Nis Truss Design Drowns (TDD)omJNe AMboay T.Tome, Ill. P.E. Refemna sleet before usa. Unless omerwise styled on Ne TpD, ody Alpin
shag be used for Ne TDO Nbe raltl. As a Truss Design Engineaningne. Specialty ragNeen, No seal an any Too represents an amapranca of Me professioeal englm.ng
A-1R I F
�i2imusnes
�nnednr platys
lesponsiul"r Na desgn of Ne single Tmse dapped on Me TOO only, under TPLl. The design assumMom, badog candake, suitability and use of dus Tmss Mr any Budding is tye
BuddugoNe rcsponsAgRy of Ne Owner. Ne Qvne(s autbonzed agenlor Na Buddig Designer.Ntl'm anfetl of Ne IRC. Ne IBC.loal beld"ug mile arb TPl-1. Tbeappmvalof Na
.am�wna
�ponsbigy of Ne Owner, Ibe Qma(sauNaved agenly Ne Bdd'mg Dedgner,NNamnNd of NelRC. tle IBC, loaf building code and TPN. TIn aDPmrdl of NelDD aM any field
Anthony Tombo 111, P.E.
%r
use of ea Truss. agol handling. slorege. insfallaldn and brzrxg area be Me rexntuary aftle Baddug begiVar and Coatmctor. M roles set out in Me MD and Me p2dias and
#.Luca
DDeesigner, TrussfMeDesign Enigmas aMentT. MananNa�, unless ohmcie deNad W a Coneadagmed upon N vniWgg b/afl Fames Fnvdved. The Tness DDealM Engineers NOT Ne Su111i
4451 St. Lucie Blvd.
oavg,w,^nTruv,seem Engmeeeanr brag. ampoarcdlmaaareea Fml-1
_ _ nem sn a bYeEwPone tlwwrivm mm¢'v,arM PcafTnrsin-AnamYT. Tanta lq P.E
Fort Pierce, FL 34946
fob Truss Truss Type Dty Ply 11/12/2018 2863
74190 B13 I MONO 1 1
Loading Criteria (ps0
TCLL: 20.00
TCDL: 10.00
SCLL: 0.00
BCDL 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0
Lumber
Top chord Zx4 SP #2
Bot chord 2x4 SP 92
Webs 2x4 SP N3
0
r
SEAT PLATE REQ. SEAT,FLATE REQ.
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height 15.00 It
TCDL: 5.0 pat
BCDL: 5.0 psf
MWFRS Parallel Dist: IT to 2h
C&C Dist a: 3.00 fit
Loc. from endwsll: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Pudins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
8C 120 0.15 10.57
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Left bottom chord exposed to wind.
••WARNING" Please lbomugNy review fbe'A-1 ROOF TRUSSES
Veydesign pamandars and read rates on N'¢ Tmss Design Drawbg (Tot
tlnr oldies shall be used for Me MD In be valid. As a Train Design E
10'6"14
11
Code / Misc Criteria
Deb/CSI. Criteria
♦ Maximum Reactions (Ibs)
Code: FBC 2017 RES
PP Deflection in loc Udeft U#
Gravity Non -Gravity
TPI SIC: 2014
VERT(LL): 0.007 E 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.009 E 999 240
A 429 /- /- /466 1151 1206
FTIRT:10(Oy10(10)
HORZ(LL): 0.005 E - -
F 417 /- A /471 /174 1-
Plate Type(s):
HORZ(TL): 0.007 E - -
Wind reactions based on MWFRS
WAVE
Creep Factor. 2.0
A Brg Width = 7.6 Min Req = 1.5
Max TCCSI: 0.443
F Brg Width =6.9 Min Req=1.5
Bearings A & F are a dgid surface.
Max BC CSI: 0.584
Bearings A & F require a seat plate.
Max Web CSI: 0.316
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 53.21bs
Chords Tens.Comp. Chords Tens. Comp.
VIEW Ver. 18.02.00.1016.21
A-e 502 -528 B-C 40 -110
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-E 479 -621 E-D 471 -613
Maximum Web Forces Per Ply (Ibs) -
Webs Tens.Comp. Webs Tens. Comp.
E - B 421 -460 C - D 163 -89
B-D 761 -586
GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMENT" foim.
wrn'T.Tombelll. P.ERefemnw$s tEe mum.UnWe oNenv ..aledon N¢TDD,anly All
SceGaN EMN¢¢r1. 1110 Sedl on dnV TDD 2Ne3enL3 an afG¢ylalltOOltlle pfM¢SSgnd ¢IIBN¢¢n
a Conbad
Me
�
//�A-I ROOF
TnM55E5
Anthony T•Tombo III, P.E.
# 80083
4451 St. Lucie Blvd.
Fort Pierce, FL 34946
Job Truss Truss Type Oty Ply 11/12/2018 2922
74190 ' I C01 SPEC 1 2
Loading Criteria (lest)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 0.00
Load Duration: 1.25
Spacing: 24.0'
T
f-' 1
I se• 4 1160#-r-r-�z-' 1161y-1-z-d-z-0 12020
t}±BB 116atl ItEOC 11EOA 11606 116W 1160Y 11EOtl 1303p 12U3Y
Wind Criteria
Code / Misc Criteria
Wind Std: ASCE 7-10
Code: FBC 2017 RES
Speed: 160 mph
TPI Sid: 2014
Enclosure: Closed
Rep Factors Used: No
Risk Category: 11
FURTAO(Ou10(10)
EXP: C Kzt: NA
Plate Type(s):
Mean Height: 15.00 It
WAVE, HS
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist:0 to h/2
CBC Dist a: 3.00 It
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top chord 2x4 SP #2 :T1 2x4 SP M-30:
Bot chord 2x6 SP 2400f-2.OE
Webs 2x4 SP #3 :W5 2x4 SP #2:
:W9 2x4 SP M-30:
:W10 2x8 SP 24001-1.13E:
Nailnote
Nail Schedule:0.131"x3', min. nails
Top Chord: 1 Row @12.00' o.c.
Bat Chord: 2 Rows @ 6,00" o.c. (Each Raw)
Webs :1 Row @ 4"o.c.
Use equal spacing between rows and stagger nails
in each row to avoid splitting.
(1) 112" bolts may be used for
(2) 0.131'x3', min. nails on
The Bottom Chord Only.
Special Loads
-(Lumber Dur.Fac. 1.25I Plate Dur.Fac. 1.25)
TC: From 60 pIf at -1.00 to 60 pit at 5.67
TC: From 30 pIf at 5.67 to 30 plf at 12.50
TC: From 60 pIf at 12.50 to 60 pIf at 24.36
BC: From 20 pIf at 0.00 to 20 pit at 5.67
BC: From 10 pIf at 5.67 to 10 pIf at 24.36
BC: 2338 lb Conc. Load at 5.67
BC: 1160 lb Conc. Load at 7.67. 9.67.11.67,13.67
15.67,17.67.19.67
BC: 1202 Ili Conc. Load at 21.67,23.67
Hangers I Ties
(J) Hanger Support Required, by others
Wind
Wind loads and reactions based on MWFRS.
Right end vertical not exposed to wind pressure.
DeflICSI Criteria
PP Deflection in too Udell U#
VERT(LL): 0.171 N 999 360
VERT(CL): 0.338 N 859 240
HORZ(LL): 0.044 C - -
HORZ(TL): 0.087 C - -
Creep Factor. 2.0
Max TC CSI: 0.579
Max BC CSI: 0.855
Max Web CSI: 0.982
Wgt 351.4 lbs
VIEW Ver: 18.02.00.1016.21
Puffins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(fit) End(ft)
TC 24 16.62 24.36
BC 120 0.15 24.36
Apply puffins to any chords above or below fillers
at 24' OC unless shown otherwise above.
♦ Maximum Reactions (Ibs)
Gravity Nan -Gravity
Loc R+ / R- / Rh l Rw / U / RL
B 6401 1- I- /- 12477 /-
1 8078 /- I- I- /2839 !-
Wind reactions based on MWFRS
B Big Width =7.6 Min Fact =2.7
1 Brg Width = - Min Req = -
Bearing B is a rigid surface.
Bearing B requires a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chards Tens. Comp.
A-B 13 -10 E-F 1666 -4293
B-C 2459-6400 F-G 1164 -3197
C-D 2123-5439 G-H 1164 -3197,
D - E 1653 -4276
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp
B-0 5675-2170 L-K 48M -1803
O-N 5646 -2161 K-J 4899 -1812
N- M 4770 -1856 J- 1 0 0
M - L 4863 -1803 -
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp
O-C
1084 -330
F-K
1027 -Z71
C-N
367-1070
F-J
9B5 -2588
N - D
1801 -713
J - H
4655 -1696
D-M
650-1617
G-J
96 -132
E - M
3682 -1381
H -1
1269 -3437
M - F
.469 -1491
-WARNING- Please Moau,M, review Me"A4 ROOF TRUSSES("SEUER"). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER-) ACKNOWLEDGMENP form.
Verydesignpa2meters and food noteson Mis Truss Design Dewing(rDD)and MeA yT.Tmdo In. P.E.Retanm Sheetbeforeuse.UnlessoMe�isestaredon Ma TOD. only Alpi
mnmcmr plates shag tie used for Me TDDbbe valid Asa Truss Design Engineering (i.e. Speualty Engineer), Me seal on any TDD represent an acmptanm WMe professional engineered 6A-1murderRdr
responsieitity for Me desk, of Me singe T.depieded on Me TDD only. under TPI-1.The design assumptions, baling mndners. swtWrty and van of Mt Truss for my Binding is Me ®TRUSSES
Buglingt Me respmsibiGty of Me ownen Me Petals eugMzed ageMm Me Bolding Designer,reed¢[Doted of Me IRC, NeIBC.bml butlding redo end TPM. Theappmvalof Me
respms'bMty of thePaner, Me PnvlsanMa¢ed agent of On BUWug Designer. in Me rented of McIRC. Me IBC, Ioml Wdding rode a,M TIN-1. The apannal of Me TDD and any fied Anthony TOmbO III, P.E.
use f theTmss. t�edlg heedg. hinstorage. 'i
ge.aolMeon and mach, shag be Me samnstSty of the Buddhg Designer a animas. Nl rotes set net InMe Too and Me paedicm and%r
guidelines of" Studies Component safety lnformatim(MCI)mbrslad bYr,I and MCI, are afeanmd lorgenm'idg numon. TPpl defines Me resprnsibdiees and duties aftla buss #80083
Designer. Truss Design ErgMeer and Tuts Manufacturer. urdess othelarim derives! by a amended agreed upm M wdtig by on pvees inwlved. The Trim Design Engineer is NOT Me Saudi 4451 St. Lurie Blvd.
Desgan,orTea Sysbm Engrregafanyeinaaw. Ab moron edmeta maasdemimmTPpv nol Fort Pierce. FL 34946
Jab. Truss Truss Type Qty Ply 11112/2018 2740
74190 CO2 SPEC 4 1
F- 12'W - 117.6
Da4X4 TII
2
e �;;- C EiL5X4
A1.SX6 33
FS3X4(EB) 1
G 3Xa(E3)
a3 Ad(A1) B 1
J H
SEAT PIATE R
H
Loading Criteria (psf)
Wind Criteria
TCLL: 20.00
Wind Std: ASCE 7-10
TCDL: 10.00
Speed: 160 mph
BCLL: 0.00
Enclosure: Closed
BCDL: 10.00
Risk Category: II
EXP: C Kzt NA
Des Ld: 40.00
Mean Height 15.00 ft
NCBCLL: 10.00
TCDL: 5.0 psf
Load Duration: 1.25
BCDL: 5.0 psf
Spacing: 24.0
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc. firm endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Top chord 2x4 SP #2
Bol chord 2X4 SP #2
Webs 2x4 SP #3
:Rt Slider 2x6 SP #2: BLOCK LENGTH = 1.500'
Purlins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 114 0.15 24.11
Apply pudins to any chords above or below fillers
at 24' OC unless shown otherwise above.
Hangers I Ties
(J) Hanger Support Required, by others
Loading
Truss passed check for 20 psf additional bottom
chord live load in areas with 42'-high x 24'-wide
clearance.
Wind
Wind loads based on MWFRS with additional CSC
member design.
=3X4 se =3X4
24'1-B
Code / Misc Criteria
Deb/CSI Criteria
Code: FBC 2017 RES
PP Deflection in roc Udefl U#
TPI Sid: 2014
VERT(LL): 0.062 J 999 360
Rep Factors Used: Yes
VERT(CL): 0.120 J 999 240
FT/RT:10(0y10(10)
HORZ(LL): 0.028 F - -
Plate Type(s):
HORZ(TL): 0.059 F - -
WAVE
Creep Factor.. 2.0
Max TC CSI: 0.392
Max BC CSI: 0.992
Max Web CSI: 0.266
Wgt 116.2 lbs
VIEW Ver. 18.02.00AO16.21
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ / R- I Rh / Rw / U / RL
B 1032 /- /- /655 1176 1256
G 957 /- /- /562 1155 /-
Wind reactions based on MWFRS
B Bag Width =7.6 Min Req=1.5
G Brg Width=- Min Req= -
Bearing B is a rigid surface.
Bearing B requires a seat plate. -
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A- B 27 0 D- E 792 -1342
B - C 794 -1609 E - F 788 -1483
C-D 791 -1413 F-G 798 -1574
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Camp. Chords Tens. Comp.
B-J 1365 -633 I-H 913 -320
J-1 913 -320 H-G 1252 -588
Maximum Web Forces Per Ply (Ibs)
Webs
Tens.Comp.
Webs Tens.
Comp.
C-J
346 -327
D-H 419
-198
J - D
521 -239
H - E 303
-243
-WARNING- Please thoroughly review Me'A-1 ROOF TRUSSES('SEU-EW). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER-)ACKNOWLEDGMF form.
Verily design parameters and react notes on this, Tmss Design Drawing (TDD) and the Mthwy T. Tambo III. P.E. Reference Sheet before use. Unless otherwise stated on the MD, c' Arpin
issues lW. nnector isss shall be used Iw the TDD to W vaM a Truss Design Engineering (i.e. Specialty Engineer), the seal on any TDD represents an acceptance of the professional angineeM—A-1
RDOR
responsLilWinthe design ifthesing]. Truss depiclMontM TDDonl underWl-1.Thededgn assure,Lions, loading conditions, suha01nyaM useofthis Truss luxury, Building tithe"Am
Tr(ussEs
BuddingbNe responaibJiy of Ne Owner the Owrreta euthor¢ed egentwthe augGy Designor,mthapMletl al Ne lRC, the IBC.Iwal Dugtling mtleaM TPI-1. Theapprovalofthe
..®�•v
respons]tilitycfthe Owner.Ne DwnersauNwrsed wtwthe BWdig Des]gner,hOomneAoltheiRC,Ne IBC,IwalbuiKMu eaMTP1-1. Theappmvaloflhe TDDandarryfield
Anthony. Tombo 111, P.E.
y
use off Truss.urduding haMlmg. storage, undershirt aid brecig shad be the MWOMN 011the Biuhh, Designer and contractor. All role55etaNN Ne TDD aM Ne paCiesard
lten information
-
#80063
Designer.Tuidelines
nasDesgnErg ourraMxisent Truss Manufasouer. uNeuwoNemisetallusedl rh Mbya CmtraCagreed upon s urnntlrg tryst partles'mMveE. TheTrvssDesgn Engineris Norse Bu'
St. Lucie
Ding..xTnr..s'AmmEgmeero(arybuilding. AllapirarimElemearessnfiredin TPl-1.
CopyngNOa118 MIRwITwsea-NWcay T. TomMN.PEPRCMtAMIXdtlaEsvmaM1vr vryfmM1bPWItMwMraeduxrOm RrmetvrofAl Rvt Truvvf-MdaryT. TgnM ItI. P.E
3494
Fort Pierce. FL 34946
Fort
Jab Truss Truss Type Oty I Ply .j.11/12(.018 2741
74190 CO3 I COMN- 1 1
—12'6'
1
SEATPWTERED.
=3x4 aax4 =.L19
SEAT PLATE RED.
pi -I
H
Loading Criteria (psq Wind Criteria
Code! Misc Criteria
DegICSI Criteria
♦ Maximum Reactions (Ibs) .
TCLL: 20.00 Wind Sid: ASCE 7-10
Code:FBC 2017 RES
PP Deflection in Ice Udell L/#
Gravity Non -Gravity
TCDL: 10.00 Speed: 160 mph
TPI Sid: 2014
VERT(LL): 0.067 J 999 360
Lee R+ ! R- / Rh / Rw / U / RL
SCLL 0.00 Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.131 J 999 240
B 1060 /- /- /668 /435 1279
BCDL: 10.00 Risk Category: II
FT/RT:10(Oy10(10)
HORZ(LL): 0.026 H - -
K 1060 A I- /668 /435 /-
EXP: C Kzh NA
Plate Type(s):
HORZ(TL): 0.052 H - -
Wind reactions based on MWFRS
Des Ld: 40.00 Mean Height: 15.00 ft
WAVE
Creep Factor. 2.0
B Big Width = 7.6 Min Req = 1.5
NCBCLL: 10.00 TCDL: 5.0 psf
Max TC CSI: 0.405
K Big Width = 7.6 Min Req = 1.5
Load Duration: 1.25 BCDL: 5.0 psf
Bearings B & F are a rigid surface.
Spacing: 24.0' MWFRS Parallel Dist: h/2 to h
Max BC CSI: 0.991
Bearings B & F require a seat plate.
C&C Dist a: 3.00 ft
Max Web CSI: 0.270
Maximum Top Chord Forces Per Ply (Ibs)
Loc. from endwall: net in 9.00 ft
Wgt: 114.81bs
Chords Tens.Comp. Chords Tens. Comp.
Wind Duration: 1.60
VIEW Ver. 18.02.00.1016.21
A-B 27 0 D-E 821 -1472
B-C 821 -1668 E-F 822 -1668
Lumber
-
C- D 820 -1472 F- G 27 0
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Maximum Chord Forces Per Ply
Webs 2x4 SP #3
Chords Tens.Comp. Chords Tens.Comp.
Purlins
B-J 1418 -572 I-H 965 -281
In lieu of structural panels or rigid ceiling use puriins
J -1 965 -281 H - F 1417 -596
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 90 0.15 24.85
. t
Maximum Web Forces Per Ply (Ibs)
Apply putting to any chords above or below fillers
Webs Tens.Comp. Webs Tens. Camp.
at 24' OC unless shown otherwise above.
C-J 347 -328 D-H 518 -243
Wind
J-D 518 -243 H-E 347 -328
Wind loads based on MWFRS with additional C&C
member design.
—WARNING" Please thoroughly review Me 'AA ROOF TRUSSES(°SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER') ACKNOWLECGMENT' fmm.
Verify design paremeteni and read sense on this Tmss Design Dining (00) and Ne AmAolry T. Tom x, III, P.E. Reference Street before use. Unless othervnse elated on die MD. only No
m =pbtasabalbeussdfwme TDDbbavalid. As a Truss Design Engineering i.e- Specialty Elgbeef), No seal on any Too represents an asseptance of the voleadonal engineenn
A-r RDGF
responsbuy fords design ofthe single Truss deplenno an Jae Too only. under TPpt. Us design asurap6Dns,usual sadigons, suilaairty and use Dl0da Truss for my Budding is the
aTRLr55E5
Budd'ug lSthofeens IBC,loral mdaaM TPI-1. TheaDpnrvai of the
vgemnteAdMe
the Ownar, the OwrefsatwM
.�m.��a
Bagentsggner, RC.b IRC.l I.Na Wua
responsibtity of the Owner, die Qmeh euNor¢ed agentatle BuiM'vgDeigner,bNa mote#mthelRC. gm IBC,bul Wdtlilg code aM TPpt. The approval olWT00 aM alry fieb
er.
Anthon T. Tombo ill, P.E.
Y
useofma Truss, bdWdg taMWg.sth29e.i 4aAe4m eM E2titg sbap be lM1a rasWnSDiGty of the BUNug Designer ens Lonbapor. An rrotes utwtln the TDD aM Me practises and
lNarma4on(Ii5nI WbrrsKEby TPl and SBCAate Meie�Ekrgere2lguidance. TPI-t�Nces Perespanesigi
gwdeex.Trsd Bu,En
80083
#.Luca
Edin.uisNOTeeBad
ErgmseraM Tr�Manufachapiumevpes.adefned by a Cmeatl agreedupon'urwriEng try all paNes mvdvN. ThaTrusa Design Erg'uleer is NOT Na Bader
Desgrer,T tt giene.niT.
44t Blvd.
Snue
GN,�,a 1... e�:E^am,e:plTanv bead Ago Pp mna Saar a�—a
., _ _ . _ n,. ��w ,,,. _wmrinm..ewaasionmrt roof ra„ze- Anthony r.rawalg.PF.
Pier FL
Fort Pierce. FL 34946
Job Truss Truss Type Cry Ply 11/122018 2742
74190 C04 HIPS 1 1
11' 3'
=4X4
M3x4=4x4 �3xa
SEAT PLATE RED. SEAT RATE RED-
Loading Criteria (psf) Wind Criteria
Code / Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00 Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udefl Uf!
Gravity Non -Gravity
TCDL: 10.00 Speed: 160 mph
TPI Std: 2014
VERT(LL): 0.054 K 999 360
Loc R+ / R- / Rh / Rw / U / RL
BCLL: 0.00 Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.105 K 999 240
B 1060 /- /- /675 /437 1250
BCDU 10.00 Risk Category: II
FT/RT:10(0)/10(10)
HORZ(LL): 0.019 1 - -
L 1060 /- /- /675 /437 /-
EXP: C Kzt NA
Plate Type(s):
HORZ(TL): 0.037 1 - -
Wind reactions based on MWFRS
Des Ld: 40.00 Mean Height: 15.00 R
WAVE
Creep Factor: 2
B 8 Width = 7.6 Min Reg = 1.5
L: NCBCLL: 10.00 TCD5.0 psf
Max TC CSI: 0nJ .427
L erg = 7.6 Min Reg = 1.5
rg Width
Load Duration: 1.25 BCOL: 5.0 psf
Max BC CSI: 0.949
B & G are a rigid surface.
Spacing: 24.0' MWFRS Parallel Dist: h2 to h
Bearings B & G require a seat plate.
C&C Dist a: 3.00 it
Max Web CSI: 0.276
Maximum Top Chord Forces Per Ply (Ibs)
Loc. from endwall: not in 9.00 it
Wgt: 121.8 Ibs
Chords Tens.Comp. Chords Tens. Comp.
GCpi: 0.18
Wind Duration: 1.60
VIEW Ver: 18,02.00.1016.21
A-B 27 0 E-F 738 -1296
B-C . 915-1652 F-G 915 -1651
Lumber
C-D 741 -1301 G-H 27 0
Top chord 2x4 SP #2
D - E 741 -1097
Bot chord 2x4 SP 24001-2.0E
Webs 2x4 SP #3
Maximum Bot Chord Farces Per Ply (Ibs)
Purling
Chords Tens.Comp. Chords Tens. Comp.
In lieu of structural panels or rigid ceiling use pudins
B - K 1414 -670 J -1 1094 -355
to laterally brace chords as follows:
K -J 1094 -355 I - G 1413 -694
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 11.00 14.00
BC 120 0.15 24.85
Maximum Web Forces Per Ply (Ibs)
Apply purling to any chords above or below fillers
Webs Tens.Comp. Webs Tens. Comp.
at 24" OC unless shown otherwise above.
C - K 365 -367 I - E 354 -132
Wind
D-K 347 -104 I-F 366 -369
Wind loads based on MWFRS with additional C&C
D -1 156 -147
member design.
-WARNING- Please Nomughy review the WI ROOF TRUSSES("SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER(•BUYER") ACKNOWLEDGMENT' form.
9
Vent' design parameters and read notes on NisTmzs Design Drawing(TDD) and NeA Mot,,T. Tambo III, P.E. Reference Sheetbefore use. Unless othemise statedon Memo. ony Alpin
TDDWWvalid. As a Truss Design Engineering (i.e. Specialty Engineer), Nosed on any TDD tepresenrs an acceptance of to professional engineenn
�q.I ROOF
�L'TH1L556
wnneCwplatessMgbeusedfwda
responsSitity far to design of Me single Truss depirded on Me TOO ony, under WIM. The design assumptions. bading conditions, suitability wW we of Nis Truss for any adding is Ns
Sutidug's Nereseonzmiptyof Ne O+sa Ne OwnefsntwMedagentw Nener.h DceignegNNecC. WNe IBC.Ne1BC, IOWbuddngcedeaMT The epDav of the
.Tombo..10
resD l
n(MCI)P'vgsedbestgta atM Ne
Anthony P.E.
responvOTdyafoNa BURTtlmg De49ner ConbaSfw ide- sMereusm aM
ru atrtyius.Nled�mB haMrne sue, toffety
800830111,
bIIWe of�Ta
D ignmerr..Tr DesgBuildn Eng�maMTa Manufacb r.unlles)zoNe�ry dePrinedbya C� dogr uuponmwUW Ipmties�mlvo+ea�. The Trus,Desgn Engineer rs NOTme emldi
Lucie
4451 S. Lucie
Desgn«arTnss Sy WmEngNeerafw bmldmg. Ao vdraraea reran are asaermean TPLI.
C©yhyuOT'11aM1 PVITw.veS-Mmmry T. Tmnlna.P£Rrym1,v'm Waif devmere.Narrylvm.bpM➢itedwNva NawrlVm Pamnal'IIWA-1 PmlTnraw-A�amyT. TamW lll, P.E
3494
Fort Pierce, FL 34946
er
Job _ Truss Truss Type City Ply 11/122018
74190 C05 HIPS I 1 1 2743
r 9'
SEAT PLATE RED.
r } s�
e4x6
=3X4 =3X4 =3X8
25'
SEAT PLATE RED.
pi-i
i
1
Loading Criteria (psf) Wind Criteria -
Code/ Misc Criteria
Defl/CSI Criteria
♦Maximum Reactions (Ibs)
TCLL: 20.00 Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in Loc Udell U#
Gravity Non -Gravity
TCOL: 10.00 Speed: 160 mph
TPI Std: 2014
VERT(LL): 0.067 K 999 360
Loc R+ / R- / Rh / Rw / U / RL
BCLL: 0.00 Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.132 K 999 240
B 1060 /- /- /677 /439 1212
SCDL: 10.00 Risk Category: It
FT/RT:10(Oy10(10)
HORZ(LL): 0.030 1 - -
L 1060 A /- /677 /439 A
EXP: C Kzb NA
Plate Type(s):
HORZ(TL): 0.059 1 - -
Wind reactions based on MWFRS
Des Lit: 40.00 Mean Height: 15.00 it
WAVE
Creep Factor. 2.0
B Brg Width = 7.6 Min Req = 1.5
NCBCLL: 10.00 TCDL: 5.0 psf
Max TC CSI: 0.970
L Big Width = 7.6 Min Req = 1.5
Load Duration: 1.25 BCOL: 5.0 psf
Bearings B & G are a rigid surface.
Spacing: 24.0' MWFRS Parallel Dist: h2 to h
Max BC CSI: 0.174
Bearings B & G require a seat plate.
C&C Dist a: 3.00 ft
Max Web CSI: 0.174
Maximum Top Chord Forces Per Ply (Ibs)
Loc. from Crowell: not in 9.00 it
Wgt: 119.0 Ibs
Chords Tens.Comp. Chords Tens. Comp.
GCpi: 0.18
Wind Duration: 1.60
VIEW Ver. 18.02.00.1016.21
A-B 27 0 E-F 825 -1445
B-C 950-1690 F-G 950 -1689
Lumber
C- D 829 -1450 G- H 27 0
Top chord 2x45P#2 -
D-E 824-1259
Bot chord 2x4 SP #2
Webs 2x4 SP #3
Maximum Bot Chord Forces Per Ply (Ibs)
Puffins
Chords Tens.Comp. Chords Tens. Comp.
In lieu of structural panels or rigid ceiling use puriins
B - K 1448 -712 J -1 1255 -492
to laterally brace chords as follows:
K - J 1255 -492 I - G 1447 -736
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 9.00 16.00
BC 88 0.15 24.85
Maximum Web Forces Per Ply (Ibs)
Apply puffins to any chords above or below fillers
Webs Tens.Comp. Webs Tens. Comp.
at 24' OC unless shown otherwise above.
C-K 250 -219 I-E 356 -36
Wind
D-K 354 -32 I-F 251 -222
Wind loads based on MWFRS with additional C&C
D - I 145 -139
member design.
••WARNING^ Pleas. NwougNy review Me W1 ROOF TRUSSES(•SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER CBUYEW) ACKNOWLEDGMENP' to.
Verify design parameters and read notes on this Tress Design Drawing (TDO) and Me AMbaay T. Tomas III, P.E. Reference Sheet before use. Unless otherwise staled an Me TOO, only Alpm
mmeCor shot W used fw the Too to be valid. As A Toes Design Engineering (i.e. Specialty Engineer). reer). Me son any Too represents an acceptance of the profissbnal enryneenn
A-r ROOF
plates
respmslaliNfor Me design of Me single Truss depicted on Me Too only. under TP4l.The design assumptions, loading condi0ons, watefity and use of this Trued for any Building is the
®iR.1556
Bm1Grg omsponsibRyof N.Owner,9eQ rsautWriaedagentwNe BvMgDesigner.m NeoontedofthelRC,Mo IBC,Iwalb&ldhrg .and TPLt. Thaappravalof Ne
r.po+tvTibry of Me O er,eeO..pY.af,madd.,.M to Me Bwldim, odsignm.in Me meted of UeIRC. Me IBC, foal Wtdug code srd TPM. The approval of pre TDD and Wfietl
Anthony Tomb0 Ill, P.E.
%f
use of the Team.mciudvg max,eg.storage. insbfia9m Mad D,xh, slut W Me rtsportsiWM of Me Baking Desyner and Canbactw. All ant. set out m Be TDD aMe phao ices and
980083
quddin.oftlm Buidvg Component Safety lNwmadm(BSCq pubfisMd by lPlaM SBCA are refererxsd for 9erersl guidance. TP4l tlefiro Nis rcspmsiTtiti. and Outles �Ae Truss
ne Desigr. Tress Design Ergmew andm TnManu6cturer, defmcd by a Camad agreed upon in Writhes by all Farbee Mashnd.Us Trued Design Engineer is NOT Me Better
g 4451 St. Lucie Blvd.
Devgerw Tess System Engtnew afaay bu'dn9. AD mPta6xed fern. are.defurN mTP41.
GpyngAtOa118 h1 Bend Trwec-MNmrT. TvnbeL P£PeprmWiNPlfdmmaRmmry M1am,upN,iWeEMVa6pewMmr pandav,dMl RoolTusae>-MuvryT. TanCO I11, E.
Fort Pierce, FL 34946
,Job Truss Truss Type City, Ply 11/12/2018 2804
74190 C06 HIPS 1 1
25U 1870 lend 1 ]# 187# 187N 253#/
�2'0,6-1-Z t V 4115 / 2'.�2'D'B,_ I
am ll Bfixe
C D E
T 2
6 2
a4X81gtOR Fs4%BIB10R)
11 A G
K J I H
INX4 a3X10 aHOUB IM4
H
Loading Criteria (psf)
Wind Criteria
TCLL: 20.00
Wind Std: ASCE 7-10
TCDL: 10.00
Speed: 160 mph
BCLL: 0.00
Enclosure: Closed
BCDL: 10.00
Risk Category: II
EXP: C Kzt NA
Des Ld: 40.00
Mean Height: 15.00 ft
NCBCLL: 10.00
TCDL: 5.0 psf
Load Duration: 1.25
BCDL: 5.0 psf
Spacing: 24.0
MWFRS Parallel Dist:0 to h2
C&C Dist a: 3.00 It
Loc. from endwall: not in 9.00 It
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top chord 2x4 SP M-30
Bot chord 2x4 SP 2400f-2.OE
Webs 2x4 SP #3
Special Loads
-(Lumber Dur.Fac =1.251 Plate Dur.Fac=1.25)
TC: From 60 pit at -1.00 to 60 pit at 7.00
TC: From 30 pit at 7.00 to 30 plf at 18.00
TC: From 60 plf at 18.00 to 60 pif at 26.00
BC: From 20 pif at 0.00 to 20 plf at 7.03
BC: From 10 plf at 7.03 to - 10 plf at 17.97
BC: From 20 pif at 17.97 to 20 pif at 25.00
TC: 253 lb Conc. Load at 7.03,17.97
TC: 18711D Conc. Load at 9.06,11.06,12.50,13.94
15.94
BC: 501 Ib Conc. Load at 7.03,17.97
BC: 1301b Conc: Load at 9.06,11.06,12.50.13.94
15.94
Purlins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC. 24 7.00 18.00
BC 69 OAS 24.85
Apply puffins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads and reactions based on MWFRS.
Sale 13off 130# 130n 130#
Code 1 Misc Criteria
Code: FBC 2017 RES
TPI Std: 2014
Rep Factors Used: Varies
FT/RT:10(Ou10(10)
Plate Type(s):
WAVE, HS
i 4
13N 501#
Defl/CSI Criteria
PP Deflection in Inc Udell L/#
VERT(LL): 0.202 D 999 360
l>➢CL): 0.400 D 740 240
HORZ(LL): 0.069 H - -
HORZ(TL): 0.136 H - -
Creep Factor. 2.0
Max TC CSI: 0.726
Max BC CSI: 0.985
Max Web CSI: 0.487
Wgt: 117.6 Ibs
VIEW Ver: 18.02.00.1016.21
3EATPIATEREQ
W
T
1
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ / R- / Rh / Rw 1 U / RL
B 2387 1- 1- 1- 11118 1-
L 2387 1- I- 1- /1118 1-
Wind reactions based on MWFRS
B erg Width = T6 Min Req = 2.0
L Brg Width = 7.6 Min Req = 2.0
Bearings B & F are a rigid surface.
Bearings B & F require a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-B 27 -20 D-E 2313 -4905
B-C 2077-4410 E-F 20T7 -4410
C-D 2313-4905 F-G Z7 -20
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp
B - K 3843 -1790 I - H 386E -1791
K - J 3867 -1791 H - F 3843 -1790
J-1 38M -1791
Maximum Web Forces Per Ply (Ibs)
Webs
Tens.Comp.
Webs
Tens. Comp.
C-K
615 -14
J-E
1244 -625
C-J
1244 -625
H-E
615 -14
D-J
718 -833
-WARNING- Please thoroughly review the' A-1 ROOF TRUSSES("SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER rBUYER') ACKNOWLEDGMENT` form.
Verify design parameters and read notes on this Tmss Design Don,"(TOmand do ArMon, T. Tombo lll, P.EReference Sheet before use. Unless oNendsa sorted on Me Too, only, Arpin
bo for Me TDD to bevalid. As a Tmss Design Engineering n e. Specialty Engineon, toe seal on any TDD represent an acceptance of the professional engineenn
"IAa RDDF
mnnectorplates shall usod
responablity fortoe design of Me single Tmss depicted on Ole TDD only, under TPI-i.The design assumpbone, loading conditions, suitability and use of Pt Trusts for any Budding is toe
91TRI31i
Busdugethe respansl#Lly of lne Owner, Me Ovmah autlmn¢ed ayentwNa Bud6ng Designer, in Me canteN al NaIRC, toe 10G local EUJdug cede aM TPI-1. Theappmvelef Me
•r���+R
respvs3itiyol Ne Owner, do Omlers aumaaed agent or Ne BUJdug Designer,lo Ne metal of Ne lRC. tlb IBC, Iacel0ulQng cede aM Tpl-1. Theappmyalof Ore TDDaManyfield
Anthony. Tombo III, P.E.
y
Ise oftoe Truss, intruding handling. storage. insulation and baCng sezne Ol be no aasidlity&Me Bu"Designer and Contractor. Mrotessetwtia Ole TDDaMNepracticesand
glmelinesofthe BoldingComponent5aferyhdomatun(MCI) pubtstad by not and, 50CA are referennvd brgeneral guidance. TPbtdef sueresponsibFYie dutlesafMOTmss
11180083
Des'ipae.Tma Design Engineer and Truss Manufacturer, MiJesa uOlervise defined by a Cantrell agreed upon lnwndrg by m parries mrdvN. The Truss Design Engineer is NOT lore Buirdir 1
4451 St. Lucie Blvd.
Designer or T. system Engmaer ofanybwmny.M-Instated temu are as&fered'M TPI-;. e�µM. �
_ _ - .. n n.�....�.r ........ a mmmcsm NAlPwtTn¢ves-MemYT. TanM III. P.E
Fort Pierce, FL 34946
Job
Truss
Truss Type
Qty
Ply
11/12r2018 2744
74190
CJ1
JACK
16
1
12
T
2X4(A1) B
TT
r
5'' A 1 M
D
SEAT PLATE REQ.
Loading Criteria (ps0
Wind Criteria
Code / Misc Criteria
Deb/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loci Udell U#
Gravity Non -Gravity
TCDL 10.00
Speed: 160 mph
TPI Std: 2014
VERT(LL): NA
Lac R+ / R- / Rh / Rw I U / RL
B 153 1- 1- 1154 f70 146
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCDL: 10.00
Risk Category: It
FTIRT:10(0y10(10)
HORZ(LL):-0.000 D - -
D 13 to /- Ill /6 /-
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.000 D - -
C - /-14 /- 130 135 A
Des Ld: 40.00
Mean Height 15.00 it
WAVE
Creep Factor. 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDU 5.0 psf
Max TC CSI: 0.185
B Big Width = 7.6 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0.023
D Brg Width = 1.5 Min Req = -
Spacing: 24.0'
MWFRS Parallel Dist: 0 to h/2
C Erg Width = 1.5 Min Req = -
C&C Dist a: 3.00 ft
Max Web CSI: 0.000
Bearing B is a rigid surface.
Loc. from endwall: Any
Wgt: 5.61bs
Bearing B requires a seat plate.
- GCpi: 0.18
t
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21 1
Chords Tens.Comp. Chords Tens. Comp.
Lumber
A-B 27 0 "B-C 29 -25
Top chord 2x4 SP 92
Bol chord 2x4 SP #2'
Maximum Bot Chard Farces Per Ply (Ibs)
Puffins Chords Tens.Comp.
In lieu of structural panels or rigid ceiling use pudins B - D 0 0
to laterally brace chords as follows: -
Chord Spacing(in cc) Start(ft) End(ft)
BC 10 0.15 0.97
Apply puffins to any chords above or below fillers
at 24' OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design:
"WARNING- Please Nomughly review, the'A.1 ROOF TRUSSES ('SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER (BUYER') ACRNOWLEDGMEN toms.
very design pammetere and read notes on this Truss Design Dr 'tg(Too) and em Anthony T. Tombo Ill, P.E. Relerenca sheMbebre use. Unleu pNemiso staled on Ne TDD, only Alpin
wnnec pWtes shag be usO W ffie TOD to be 1U. M a Truss Design EgNeemg (i.e. Specialty Egmeer), the and on any TOO represents an acceptance of me Fwasmanal a gins&
Building isme
�_A-r ROOF
IamO55E5
respmvbiliyfw Madesign of Ne single Truss depicandonti TDD ory, underT!pl.Tlre deslgn assumptions, baling mndidpns, euitatiNtyand usegfthis Tmsnforanry
Buddn9oda responsiGWy of the Owner. theOmrers auNodzad agentm Na Buibhg Dgigner, NthefMteOr Ne lRF da IBC, trial Wadvg mots end TPN. The apporW of Ne
..®.m.o.,a
respmvUililyWNe Owner, Ne Owners eugomnd agentm Ne Bwb'ugDesigner,NOe®dmd of Na lRC. the lBC, tarot buiNing mdeam TPl-1. TAe aDWaral of the TOD aM anyfieM
Anthony. Tombo Ill, P.E.
y
oflhe Truss. Notating landting.storage. iretagaten aM brace, shag W dre respon.and, of rite Building Design, and CoMaMr. All totes srset M in Ne TOO and the pZ. and
83
#.Luca
dagreedupon9bw�imbyeyao Pmesl meT Dmignsginmr oN ahee
o *g .,Trn6Di knn EngMe aw Tam2nu(aa�veiBUNeu�oere�nnsadePru bbyae�m soap
St. Lucie
Desgrtr or Tmss system Engi. of arty mdbN¢. All mpitar¢ed 1�,tre are as defined In T 1.
coygnaeat' aal Rmfreset, -AN LTd m.PF. laomooln 0m dee,mea. Nant, tnt,. is p,mmmdw ne,vrmm wtt�nm 0h1 nmfrwma-ArNaayT.Tamm tn. PE
3494
Fort Pierce, FL 34946
Fort
Job
Trusts
Trusts Type
Qty
Ply
11/1212018 2745
74190
CJ1E
JACK
4
1
12
6 F7- C
T
2M(A1) B
57 A 1
D
SEAT PLATE REQ.
1r
Loading Criteria (psf)
Wind Criteria
Code / Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udefl U#
Gravity Non -Gravity
TCDL: 10,00
Speed: 160 mph
TPI Std: 2014
VERT(LL): NA -
Loc R+ ! R- / Rh / Rw / U / RL
B 153 !- /- 1167 184 146
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCDL: 10.00
Risk Category: ll
FT/RT:10(Ou10(10)
HORZ(LL): -0.000 D - -
D 13 10 /- 116 /8 !-
EXP: C Kzt NA
Plate Type(s):
HORZ(TL): 0.000 D -
C - /-14 A /28 135 /-
Des Ld: 40.00
Mean Height 15.00 ft
WAVE
Creep Factor: 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL 5.0 psf
Max TC CSI: 0.185
g Big Width = 8.0 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
D Brg Width =1.5 Min Req = -
Spacing: 24.0'
MWFRS Parallel Dist: 0 to N2
Max BC CSI: 0.021
C Brg Width = 1.5 Min Req = -
C&C Dist a: 3.00 ft
Max Web CSI: 0.000
Bearing B is a rigid surface.
Loc. from endwall: Any
Wgt: 5.6 IDS
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver, 18.02.00.1016.21
Chords Tens.Comp.. Chords Tens. Comp.
Lumber A-e 27 0 B-C 29 -25
Top chord 2x4 SP #2
Bol chord 2x4 SP #2
Maximum eot Chard Forces Per Ply (Ibs)
Purlins Chords Tens.Comp.
In lieu of structural panels or rigid ceiling use pudins B - D 0 0
to laterally brace chords as follows: '
Chord Spacing(in oc) Stan(ft) End(ft)
BC 10 0.15 0.97
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Left bottom chord exposed to wind.
-WARNING— Please thoroughly review Me 'A-1 ROOF TRUSSES(°SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMENP' form.
d
Verify design peannouns and read notes on this Truss Design Dramng(Too) and the Anthony T. Taman III, P.E. Reference Sheetbefore use. Unless otherwise slated onthe TDD, only Atpin
wnn.tl pUtesshagbeuse Wb oTDDto We W. Ae a Tmss Design Engineered (i.e. speandly Engineer). lee seal on any Too represents an acceptance of the professional engineerin
pcI ROOF
HTRycccc
responsibility for ft design of fine single Tivssdepctedon OeMDonly. under TPM.TMdesign assumpllons, badingwnditiws,aultxWGy and ussoflhh Truss Wany Budding athe
Budding bathe resgnsLiliyofthe Cwner. Ne Owneh wtMtlzed agentsdu ankles,Designer,in MecvnteawthelRC, that IBC, bcalboall, wdeand TPI-1. The ap,.W of the
respwvbdiry of Ne Owner, Vw Owmch auNorbed agentw Ne Building Designer, in Ne mntetl of Me IRC, MaIBC.lowl Wdtl'ug cede artl lPhl. TMeppravelofthe TDDandatryfield
Anthony•Tombo Ill, P.E.
y
ar Ma Trusv,iMWby haMGng,storage, instailationaM btacvg shay be de rezpwsibSrydtee Buddvg OesigneraM ConRastw. Altnotessetwtihtea TDDandthepmclirxsand
Truss
#80083
guideli�pitlm Buimvg Campwent Safety ltdpmagw(BBCI)pubgshM by TPIaM SBCAata referenced Tar general guidance. TPFt defims die respdtsibliE¢saes dul¢s of me
Designer.Truss Design Ergi zWTrossWmtf mr.mii oNe��bya Cr dagreeduponowr,byallpaNesvlwlved.The Truss Design Elgineer¢NOTNe BuJdi
4451 St. Lucie Blvd.
Designer aTmse system Er4nes,of anYbwldmg.
CapPghtOLNa Mr Rml Truvef-Mdmny T. TemLs1Y,PE Repe]u'.fM dtlif dmmw+a.ln arylam. ePduFtied'�IegitVm v.+0n MmisinarMl ROS Trmef-Mem/T. Tvnb III. PE
Fort Pierce, FL 34946
Job
Truss
Truss Type
Oty
Ply
11/12/2018 2746
74190
CJ1T
JACK
10
1
12
6 F7- C - -
T T
2X4(A1) B
T
T—
1 A
D
SEAT PLATE REQ.
Loading Criteria (ps0
Wind Criteria
Code! Misc Criteria
Defill Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udell U#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Slid: 2014
VERT(LL): NA
Loc R+ / R- / Rh / Rw / U / RL
B 153 /- /- 1167 184 146
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCDL: 10.00
Risk Category: ll
FT/RT:10(0)/10(10)
HORZ(LL):.0.000 D - -
D 13 /0 /- 116 /8 /-
EXP: C Kzt NA
Plate Type(s):
HORZ(TL): 0.000 D - -
C - /-14 /- 128 /35 /-
Des Ld: 40.00
Mean Height: 15.00 it
WAVE
Creep Factor: 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.185
B Brg Width = 7.6 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0psf
Max BC CSI: 0.021
D Brg Width = 1.5 Min Req = -
Spacing: 24.0 "
Mill Parallel Dist: 0 to h/2
C Brg Width = 1.5 Min Req = -
C&C Dist a: 3.00 it
Max Web CSI: 0.000
Bearing B is a rigid surface.
Loc. from endwall: Any
Wgt: 5.61bs
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber A-B 27 0 B-C 29 -25
Top chord 2x4 SP #2
Bat chord 2x4 SP #2
Maximum Bot Chord Forces Per Ply (Ibs)
Purlins Chords Tens.Comp.
In lieu of structural panels or rigid ceiling use puffins B - D 0 0
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 10 0.15 0.97 -
Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Left bottom chord exposed to wind.
••WARNING' Please Moroughly review the•A-1 ROOF TRUSSES("SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMENT- torn.
'
verily design parameters and read notes on this Thuss Design Dndwitg(l and the Anthony T. Tombo 111, P.E References sheet behind van. Unless otherwise stated on the TOD. only Alpin
'
connector plates shall be used forum TOD M be valid Asa These Del Engineering (i.e. Specialty Engineer).Medeal onany Too represents an acceptance of the preressional engineedn
late
aA-1 ROOF '
responsibilivatrum design ofthesingle Tmss deaded oa Me TDD ONy,underTPl-1.The design assumptions, loading oonditions, suitabifty add uaeoithis Trussforany Building
�TRUS5
Building is Me responsibility of the Diener. the owners authoraed agentor Me Building Designer, in Me conteMof the IRC, Me IBC.local building rode and TPI-1. The apprevel of m,
••m�•�a
respcn ebrily orthe Owner, Me Owners authorized agent or Ma Dal Dain the conteftof Me IRC, Me IBC, most building code end TPI-L The approval of Ma TDD and any red!
Anthony . Tombo III, P.E.
y
use of Me Trues, including handling. storage. installation and bracing shall be Me responsibility of Me BuiIEMg Designer and Centrador. All notes set out in Me Too and Me practices and
Tmss
#80083
guidelines of Me Building Component safety information(BSCI) published by TPI and SBCA are referenced for general guidance. TPI-0tlefnes Me responsibliYesend dNles of the
Designer. Truss Design Engineer and Trues Manufacturer, unless offervdss banned by a Contract agreed upon in sitting by all parties involved. The Those Design Engneer is NOT Me Buildi
g 4451 St. Lucie Blvd.
oesigneror Trusssyatem Ergineerotanybwldmg. AuraNmaedternsamasder elo rPl-t. -
capynguic M19,Yt Pont Tnszes-MNony T.Tomto III, P.E.Repe]uNon of Mis Emmenl,N any rmm, b pMigt Nxitlmut Ne wrNm Ix,mtsslw of A�1 Root Trvssee-MI1n,ry T. TgnW In, P.E
Fort Pierce, FL 34946
Job
Truss
Truss Type
Cry
Ply
11/12/2018 2747
74190
CJ3
JACK
10
1
C
12 - -
6[�7-
T-T
C"!
4(A1) B N
1
57
A
D
SEAT PLATE REC.
1' -I( 2'11"11 -{
Loading Criteria (par)
Wind Criteria
Code / Misc Criteria
DeFl/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in too L/deft L/#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Std: 2014
VERT(LL): NA
Loc R+ / R- / Rh / Rw / U ! RL
B 199 !- /- 1169 /65 /100
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCOL: 10.00
Risk Category: ll
FT/RT:10(0)/10(10)
HORZ(LL):-0.001 D - -
D 53• /- /- 128 /- /-
EXP: C Kzt NA
Plate Type(s):
HORZ(TL): 0.001 D - -
C 70 /- /- /50 167 /-
Des Ld: 40.00
Mean Height: 15.00 ft
WAVE
Creep Factor: 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.0
0 Brg Width = 7.6 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0.086 86
D Big Width = 1.5 Min Req = -
Spacing: 24.0"
MWFRS Parallel Dist: 0 to h/2
C Big Width = 1.5 Min Req = -
C&C Dist a: 3.00 ft
Max Web CSI: 0.000
Bearing B is arigid surface.
Loc, from endwall: Any
Wgt: 11.21Its
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber
A-B 27 0 B-C 31 -116
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Maximum Bot Chord Farces Per Ply (Ibs)
Purlins
Chords Tens.Comp.
In lieu of structural panels or rigid ceiling use putting
B - D 0 0
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 34 0.15 2.97
Apply purling to any chords above or below fillers
,
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
^WARNING^ Fluxes thoroughly review, Me 'A-1 ROOF TRUSSES ("SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMENl'i Mae.
Verly design parameters and read notes on this Truss Design Drawing (m0) and Me Anthony T. Tombo Ill, P.E. Refemnce Sheet before use. unless o resets. slated on the TDD, onlyArpin
sonrector plains shall be used hi TDD to ire valid As a Tross Design Engineervlg(i.e. Specially Engineer).theseal on any TDD represents an acceptance of the professional engines lbl
m—A-r ROOF `
responsibili to, Medesign of the single Truss depicted on the TDD only, under TPI-1. The design assumptions. loading conditions, suitability and use of this Truss for any Building is Me
TTRUSSES
Building in Me responsibility afthe Barren, the Owrers authorized agent or the Building Designer, in Me context of the IRC, the IBC, local building code and TPN.
Theappro,miethe
..�.o+w•e
responsibility of Me Owner, the Owners authorized agent or the Building Designer, in the contest of the IRC, the ISO. Most building door, and TPI-1. Theappmralofthe
TDDdadanytield
Anthony T. Tombo Ill, P.E.
oaf the Truss, including handling, stamge,installation and bral stroll bound responsibilinidthe Building Besignerand Confined,, Ali maxi.etow in theTDDandthe
pmtlicesand
980083
guidelines of the Building Component Safety lnfmmatlon(8SQ published by TPI and SBCA are referenced for general guidance. TPI-1 defines Vie responsibilities
and duties&Me These
Designer, Tmss Design Engineer and Thror Manufacture, unless otheerse decimal by a Contrail agreed upon in writing by all parties Involved. The Trues Design Engineer is NOT Me Buidir
4451 St. Lucie Blvd.
Designer or TNea system Engineer of any building. NI mpitalized temis am seder ed hT 1-1.
C dgM020l6Alnmf Tresses-MU,T.Ta WIII,P.E Repron.r offtermurn hoary Min, is pMvdl¢d elar.lne wnEen cernovibal A.1 RmfTnmms-Mtr T. TmAa III. RE
Fort Pierce. FL 34946
Job Tress Truss Type QTy I Ply 11/12/2018 2748
74190 CJ3A I JACK 2 1
Loading Criteria lost)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0"
Lumber
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
1
Wind Criteria
Wind Sid: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 it
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 it
Loc. from Birdwell: Any
GCpi: 0.18
Wind Duration: 1.60
Purling,
In lieu of structural panels or rigid ceiling use pudins
to laterally, brace chords as follows:
Chord Spacing(in cc) Stad(ft) End(ft)
BC 34 0.15 2.97
Apply putting to any chords above or below fillers
at 24" CC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Left bottom chord exposed to wind.
12 B
2X4(A1
SEAT PLATE REQ.
i2'11"11 �{
Code! Misc Criteria
Defl/CSI Criteria
Code: FBC 2017 RES
PP Deflection in [cc tldefl L/#
TPI Sid: 2014
VERT(LL): NA
Rep Factors Used: Yes
VERT(CL): NA
FT/RT:10(0)/10(10)
HORZ(LL): 0.001 C - -
Plate Type(s):
HORZ(TL): 0.002 C - -
WAVE
Creep Factor: 2.0
Max TC CSI: 0.279
Max BC CSI: 0.137
Max Web CSI: 0.000
Wgt: 9.8 Ibs
VIEW Ver: 18.02.00.1016.21
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ / R- 1 Rh / Rw / U / RL
A 125 /- /- 1131 /39 178
C 54 /- /- 192 150 /-
B 79 1- l- 164 172 1-
Wind reactions based on MWFRS
A Big Width = 7.6 Min Req = 1.5
C Brg Width = 1.5 Min Req = -
B Brg Width = 1.5 Min Req = -
Bearing A is a rigid surface.
Bearing A requires a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
A-B 35 -129
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
A-C 0 0
'M/ARNING' Please thoroughly review We -A-1 ROOF TRUSSESCSIELEIT), GENERAL TERMS and CONDITIONS CUSTOMER (BUYER-) ACKNOWLEDGMENT" font. e
Verity design parameters and read notes on this Truss Design creating (TDDI and the Anthony T. Tombs Itl, P.E. Reference Sheet before use. Unless otherwise stated on the MD,
onN Alpin
connector plates shall be used for the TDD to be valid. As a Truss Design Engineervig(i.e.Specialty Engineer), the seal on any TDD represents an acceptance of the professional engineerin �pq ROOF
responabilityfor the design of the single Truss deplored on be TDD aNy, under TPt-1. The design assumptions, leading conditions, suitability and use of this Truss for any Building is Me �5TRU15
Building is the resi'ronsbilt, of the Owner, Me Owner's authoraed agent or the Building Designer, in Me conte#ofMelRC, the Inc. atel building code and TPpt. Theapprovdofthe
responsibility ofthe Owner. ti Cori authorized agent orthe Building Design, a Me contextaf the IRC. the IBC. 1.1Wilding code and TPl-1. Theappmvalofthe TOOandanyfetd Anthony. Tombs Ill, P.E.
se of the Tress, including handling, storage, installation and bracing shall be the responsibilityof the Building Designer and Contractor. All notes set out In Ue TDD aM the practices and y
guitlelines of Meadlding Component Sa(ety lnbrmation(BSCI)Wblistied Dy TPIaM SBCAare referenced for generalguidance. TPI-1 der the responsibilities and duties ofthe Truss #80083
Designer, Truss Design Engineer and Truss Manufacture, unless o0endse defirv:d by a Contract agreed upon in writing by all press invoked. no Truss Design Engineer is NOT the Saudis 4451 St. Lucia Blvd.
DosignarorTresssydem Engineerdanyewding. Alrapiwuadtemwareasdaenedin Tlet-1. en_ Fort Pierce, FL 34946
Job
Truss
Truss Type
City
Ply
11/12/2018 2749
74190
CJ3C
JACK
2
1
D
12 - -
-- -
6
T
T
`.
N
_ V
_ N
=2X4(A1) e
_
r HB 0"1
A
GF
SEAT PLATE REQ.
10-1
�}-- 2'1"10 '1 -'
�- 2'11"11 --�
Loading Criteria (psf)
Wind Criteria
Code I Misc Criteria
DefI1CSl Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc L/defl L/#
Gravity Non -Gravity
TCLL: 10.00
Speed: 160 mph
TPI Sid: 2014
VERT 0 005 G 999 360
( ) LL -
Loc R+ / R- / Rh / Rw / U / RL
g igg /- /- /169 /65 /100
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.009 G 999 240
BCDL: 10.00
Risk Category: ll
FT/RT:10(0)/10(10)
HORZ(LL):.0.004 G - -
E 45 /- /- l25 /- /-
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.006 G - -
D 7.1 /- /- 152 162 /-
Des Ld: 40.00
Mean Height: 15.00 ft
WAVE
Creep Factor. 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.
B Big Width = 7.6 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0.05052
E Brg Width = 1.5 Min Req = -
Spacing: 24.0 "
MWFRS Parallel Dist: 0 to h/2
D Erg Width = 1.5 Min Req = -
C&C Dist a: 3.00 fl
Max Web CSI: 0.089
Bearing B is a rigid surface.
Loc. from endwall: Any
Wgt: 15.4 lbs
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber
A-B 27 0 C-D 32 -104
Top chord 2x4 SP#2
B-C 4 -81
Bot chord 2x4 SP #2
Webs 2x4 SP #3
Maximum Bot Chord Forces Per Ply (Ibs)
Plating Notes
Chords Tens.Comp. Chords Tens. Comp.
All plates are 1.5X4 except as noted.
B - F 9 -41 G - E 0 0
C-G 43 -7
Purling
-.
In lieu of structural panels or rigid ceiling use purling
Maximum Web Forces Per Ply (Ibs)
to laterally brace chords as follows:
Webs Tens.Comp.
Chord Spacing(in cc) Start(ft) End(ft)
BC 24 0.15 1.99
G-F 39 -4
BC 20 1.99 2.97
Apply During to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
"WARNING" Please thomul review Me'A-i ROOF TRUSSES('SELLER"). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMENTYom.
—
Verily, design pammeWm and read notes on this Toss Design Donar,(rDD) and Me Anthony T. Tombo Ill. P.E. Reference sheet tubes use. Unless otherwise stated on Me TDD, ony As,
son MrptatesshallbeusMfw MBTDOtobevalid. As a Tmss Design Engineering (Le, Specially Engineer). da seal on any TDD represents an acceptance ofthe professional engineerin
for Me design of Me single Truss decided on Me TDD only, under TPI-1. This design assumptions. leading omditions. suitability and use of this Tmss for any Building is Me
®A-r ROOF
�miRU55E5
maponsual
Building is Me responsibility of Me owner, Me Cannes augamed agent or Me Burning Designer, in Me nantextof Me IRC, Me IBC, Iwal building code and TPI-1.
Thiamsavolofine
maparectiy of Me cerep the Ovmees authorized agent or Me Building Designer,inMecontest of the IRC,MeIBC, local building code and TPI-1. The impotent of
Me TDD and any field
Anthony. Tombo Ill, P.E.
y
use of the Truss, iivludire handling, storage, installation and trial, stall has Me responsibihtyef Me Building Designeranmm d Conuir. All notessetoutin Me TDD and Me anedlres and
guidelines of Me Building Component Safety Informal (MCI) published by TPI ant SIBCA are referenced for general guidance. TPI-1 defines Me responsibJiOes atM tluties of Rile Tmss
#80083
Designer, Tmss Design Engineer and Tmss Manufacturer, unless direness dented by a Connect agreed upon in wdfing by all panics involvd e. The Tmss Design Engineer is NOT Me Burldir
1 4451 St. Lucie Blvd.
Designer or Teas system Engbear or any building. an caphosta ea teres ate ae der ei in TPln.
CupYd9ht031116 A-1 ReATmums-Mvur, .Tomta III. P.E. Repmdunbn W Ctis Cd-umeM,F a,ryfmm.'e OMiMedwYNaut MexnMn certnLssicn NMI Roof Tusses-Arose, T. Ton. III, P E
Fort Pierce. FL 34946
Job
Truss
Truss Type
City
Ply
11/12/2018 2750
74190
CJ3E
JACK
2
1
I
C
12
6
N
2X4(A1) B N
57 A -
1
D
-SEAT PLATE REQ.
+ 211t'11 -{
Loading Criteria (psf)
Wind Criteria
Code/ Misc Criteria
Ded/CSI Criteria
♦Maximum Reactions (Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FSC 2017 RES
PP Deflection in too L/defl L/#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Sld: 2014
VERT(LL): NA
Loc R+ / R- / Rh / Rw / U / RL
B 199 /- /- /216 /90 /72
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCDL: 10.00
Risk Category: II
FT/RT:10(0)/10(10)
HORZ(LL): 0.001 D - -
D 53 /- /- /86 146 /-
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.001 D - -
C 70 /- I- 153 145 /-
Des Ld: 40.00
Mean Height: 15.00 ft
WAVE
Creep Factor: 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL 5.0 psf
Max TC CSI: 0.1
B Big Width= 8.0 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0.127
D Brg Width = 1.5 Min Reg = -
Spacing: 24.0'
MWFRS Parallel Dist: h to 2h
C Big Width = 1.5 Min Req = -
C&C Dist a: 3.00 it
Max Web CSI: 0.000
Bearing B is a rigid surface.
Loc. from endwall: not in 9.00 it
Wgl: 11.21bs
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs) -
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber
A-B 27 0 B-C 31 -88
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Maximum dot Chord Forces Per Ply (Ibs)
Purling
Chords Tens.Comp.
In lieu of structural panels or rigid ceiling use purling
B - D 0 0
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 34 0.15 2.97
Apply purling to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
-
member design.
Left bottom chord exposed to wind.
^WARNING^ Please thoroughly review the -A-1 ROOF TRUSSES CSELLER'1, GENERAL TERMS and CONDITIONS CUSTOMER CSWEFR') ACHNOWLEDGMENT' form,
6
Verify design patemeters and read notes on this Truss Design branding (rDD)and Me Anthony T. Tombs Ill. RE Reference Sheet before use. Unless oluninso stated on Ne TDD, only Me"
g
mnnectorplatesshanbeusedfmlhe TDDlobevalid. As a ThoseDesign Engineering (i.e. Sinai Engineer). Me seal on any TDD represents an acceplands of the professional engirr in
for" design of Me single Trend depicted on the Too only. under TPM. The design assumco pbons, loading nditions, suitability and use M anis Truss for ally Buildingis Me
q-pppF
�ad TRUSSES
responsibility
Building's Me lesmns3ilily club O.vneA the O e. authorized agent., the Builds, Designer, land contingelha IRC. Ne 18C, lost building code antl TPI-1.
Tha approval of Pe
.�uwm.awv
Me me or too r. in me context ofthe IRO, Me building
notes lset me Too
Too
Anthony T. TOmbo III, P.E.
and Me peafthe
and of Me us, inclfirryof recind ous and and
uding handi ling, storage. installatated ion and trading sht all be Me resmsibility brand Building Delssiignerad Contractor. All outn
guidernesofthe Binding component Safety Internal(BSCD published th TPl and SBCAare referenced lurgdneralgoidance. TPI-1 defines Me respbnslilidesand dutiesoftne Tmss
#80083
Designer. Tmss Design Engineerand Truss Manufacturer,unless otterved, defined by a Contract agreed upon in orris, by all pulses involved. The Truss Design Engineer is NOT Me Builds
g 4451 St. Lucie Blvd.
Designer or Truce system Engineer of any building. Ab wpilalized letms are as der etl m TPF1.
CWyMtGN116Lla TMs s-Mthmy T.Tomb.III,P.E ReprMbgm ants @amen[h anylpm,hp,Mti idlvn uut Nexntten Cemm1 us4NA-Mof Tddds-Memny T.Tdrei III, FE.
Fort Pierce, FL 34946
Jab
Truss
Truss Type
Qty
Ply
11/12/2018 2751
74190°
CJ3P
JACK
2
1
C
12
_T
6�
T
� N
2X4(A1) B N
1
A
D
SEAT PLATE REQ.
1' 2r11"11 �{
Loading Criteria (psf)
Wind Criteria
Code / Misc Criteria
Defl/C51 Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Sid: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udell L/#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Sld: 2014
VERT(LL): NA
Loc R+ / R- / Rh / Rw / U / RL
B 199 /- /- /216 190 /100
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCDL: 10.00
Risk Category: ll
FTIRT:10(0)/10(10)
HORZ(LL):.0.001 D - -
D 53 /- /- /86 146 /-
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.001 D -
C 70 /- /- /53 /66 /-
Des Ld: 40.00
Mean Height: 15.00 it
WAVE
Creep Factor: 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL 5.0 psf
Max TC CSI: 0.
B Brig Width = 7.6 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0.105 105
D Brg Width = 1.5 Min Req = -
Spacing: 24.0 °
MWFRS Parallel Dist: 0 to N2
C Brig Width = 1.5 Min Req = -
C&C Dist a: 3.00 ft
Max Web CSI: 0.000
Bearing B is a rigid surface.
Loc. from endwall: Any
Wgt: 11.2 lbs
Bearing B requires a seat plate.
GCpi: 0.19
Maximum Top Chard Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver. 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber A-B 27 0 B-C 31 -123
Top chord 2x4 SP #2
But chord 2x4 SP #2
Maximum Bot Chard Forces Per Ply (Ibs)
Puffins Chords Tens.Comp.
In lieu of structural panels or rigid ceiling use puffins B - D 0 0
to laterally brace chords as follows:
Chord Spacing(in oc) Stad(ft) End(ft)
BC 34 0.15 2.97
Apply puffins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C _
member design.
Left bottom chord exposed to wind.
"WARNING^ Please thoroughly reviewthe'A-i ROOF TRUSSES('SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER') ACKNOWLEDGMENT'form,
e
Verify design pamraters and read notes on his Tmss Design Drawug(DO)and IN Anthony T. Tonto 111, P.E Rearenco Shnotbefore use. Unless otherwise stated on the TOD, only Npin
�
ell
wmlestor plates shall be used for the TDD to be valid. As a Tress Design Engineering (i.e. Specialty Engineer), the seal an any TDD represents an sweetened of the professional engineeM
Trussdeplcied TODony,under-PPI4.Thedesgn assumptions. leading consul swtabilityand ussofthis Tressforany Building lathe
ROOF
�2TRr155E5
responsibibyhorthedesign of the single onthe
Still is Ondo.,asibilitypftheQmen the Owners authorised agent orthe BudWrg Designer, in Me Conlon ofthe IRC, the IBC. Io®I building code and TPl-1. Theappmval ofthe
.nm�wuu
Anthony T. Tombo 111, P.E.
MandthelTreoss urJudmg handling,tooge, instanatonand trading shut be Neriespostiltytfthe Building Designaand contractor. mnoessetoutnpMe TGDand the pmnicesind
guidelines ofthe Building Component Safety Information(BSCI) published by Wit and SBCA are referenced for generalguidance. TPI-t,def sPe respamibJifies and dudes of the Tress
#80083
Designer, Tress Design Engineer and Tmss Manufacturer, unless othewse defined by a eonbaa agreed upon in writing by all padies imelved. The Tress Design Engineer is NOT the Buildir
9 4451 St. Lucie Blvd.
Designer or Truss System Eegmeerof am bantling. m capita@ed terms are asdeflima n TPI-1.
copyng WitiA1RmfTrusses-NMorryT.tom[oIV. Pi RmMudlon ofNistlommenUnanytmm.'s Orydnit¢tl w�thoutthenr0en permlssbnnMl RoMTrusses-MthwryT.Tamtolll,PE
Fort Pierce, FL 34946
Job
Tmss
Truss Type
'Oty
Ply
11/1212018 2752
74190
CJ5
JACK
6
1
C12
T
6
v
N
(V th
=2X4(A1) B
_L A
D
SEAT PLATE REQ.
�--- 1' 411"11
Loading Criteria (psf)
Wind Criteria
Code / Misc Criteria
DefI1CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Defection in too Udell Ll#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Std: 2014
VERT(LL): NA
Loc R+ / R- / Rh / Rw / U / RL
B 273 1- A /217 181 1154
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCDL: 10.00
Risk Category: ll
FT/RTAO(OU10(10)
HORZ(LL): -0.005 D - -
D 92 I- A /52 A 1-
EXP: C Kzt NA
Plate Type(s):
HORZ(TL): 0.008 D -
C 130 1- 1- 197 1118 /-
Des Ld: 40.00
Mean Height 15.00 ft
WAVE
Creep Factor. 2.0
Wind reactions based on MWFRS
NCBCLL: %00
TCDL 5.0 Pat
Max TIC CSI: 0.
B Brg Width = 7.6 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 ps(
-
Max BC CSI: 0.259 259
D Brg Width = 1.5 Min Req = -
Spacing: 24.0'
MWFRS Parallel Dist:0 to h/2
C Brg Width = 1.5 Min Req = -
C&C Dist a: 3.00 it
Max Web CSI: 0.000
Bearing B is a rigid surface.
Loc. from endwail: not in 4.50 fl
Wgt: 16.8 lbs
Bearing B requires a seat plate.
GCph 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00,1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber A-B 27 0 B-C 58 -134
Top chord 2x4 SP #2
Bol chord 2x4 SP #2
Maximum Bot Chord Forces Per Ply (Ibs)
Purlins Chords Tens -Comp.
In lieu of structural panels or rigid ceiling use puffins B - D 0 0
to laterally brace chords as follows:
Chord Spacing(in oc) Staff(ft) End(ft)
BC 58 0.15 4.97
Apply puffins to any chords above or below fillers
at 24' OC unless shown otherxise above.
Wind
Wind loads based on MWFRS with additional C&C
member design. '
"WARNING^ Please thamughly review the -A-1 ROOF TRUSSES('SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACI(NOWLEDGMENT'form.
a
Verify design pmarhelers and read notes on Nis Truss Design Dreavg(TOO) and the Anthony T. Tombo lit. P.E. Reference Sheet before use. Unless omerwise staled an the TDD. only Alpin
wmector POWs Mal be used for the TDD to be did. As a Truss Oesgn Engineering (i.e. Spo6alty EngNser), the seal many TDD represents an acceptance of Ne Professional engineerin
is dre
p-1 ROOF
�TRLL55g
respensibitiybr the design 0 the single Truss depleted on the TDD aNy.tnder TP41.1thedesign assumptions. Ong conditions. suitereaty and use of ago Thew fw any Bulding
BulQug aria responslblfity al Ne Owner. Ne Ovncts authodmdagent or Na Buldmg Desgnw,m Na m�le#MNeIRC, Ne IBC.bcel butlding code and TPl-1. Theapprowl of Ne
..��.�
responsSi4y al Na Owner, lire Owrers auNwiud agentwNe BUItlNg Desgner,thNe m�te#of Ne IRC. NaIBC,Iwal bnlSug cede aM TP41. TheapprevoloftheTDDandamfielE
useofthe Truss.W w gh g,sbrage,bL:h tmaMb ecgsha ftmspanw3Mlyof Ne BuW gDesgneraMC n"=. Mmtesset Min NBTDDand Nepre ceems!
Anthony.Tmbo III, P.E.
y i>
gDuetle�finaTl DBuldbg Component Safey lNwmatlon(BSCI)pubfisMd by TPIaM BBCA are referencedfw general guMance. TPFtdefi sNemsponvbiTNesaMdutle do Truss
¢sign Eg'mewaMTr Wnufaa w,uNessoNernicedefinWbyaConbadag up WwriNgbyadpaNesmvoyed. The Truss Design Eemeerts NOTNa Su
#80083
4451 St. Lucie Blvd.
oedywrorneae Symwn Fsgreserof am buffshl u mpitaraea tame era a+daro a thTPr-1.
GgrgmO AI8 MI ROI Tuvn-Mercny T. TmiEo Il. P£ RewWclMn daiaam�M1 ham Mn.ISGmNbleE xidim806 nrmb� PerMss'v�af0.1 Rv/Tnrsxa-MPmyT. Tor4o III, P.E
Fort Pierce, FL 34946
Job Truss Tmss Type Oly Ply 11/12/2018 2753
74190 CJ5A JACK 2 1
2X4(A1
J7
SEAT PLATE REQ.
i 4'11"11
Loading Criteria (ps0 Wind Criteria
TCLL: 20.00 Wind Std: ASCE 7-10
TCDL: 10.00 Speed: 160 mph
BCLL: 0.00 Enclosure: Closed
BCDL: 10.00 Risk Category: II
EXP: C KZL NA
Des Ld: 40.00 Mean Height 15.00 it
NCBCLL: 10.00 TCDL: 5.0 psf
Load Duration: 1.25 BCDL: 5.0 psf
Spacing: 24.0MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 It
Loc. from endwall: not in 4.50 it
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top chord 2x4 SP #Z
Bol chord 2x4 SP #2
Puriins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Stad(ft) End(ft)
BC 58 0.15 4.97
Apply pudins to any chords above or below fillers
at 24' OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Left bottom chord exposed to wind.
Code 1 Misc Criteria
Doff/CSI Criteria
♦ Maximum Reactions (Ibs)
Code: FBC 2017 RES
PP Deflection in loc Udell L1#
Gravity > Non -Gravity
TPI Std: 2014
VERT(LL): NA
Loc R+ I R- / Rh / Rw / U , I RL
Rep Factors Used: Yes
VERT(CQ: NA
A 205 f- /- /219 /69 1132
FT/RT:10(Oy10(10)
HORZ(LL): 0.006 C - -
C 93 /- /- 1156 183 P
Plate Type(s):
HORZ(TL): 0.010 C - -
B 135 . !- /- 1109 1119 P
WAVE
Creep Factor. 2.0
Wind reactions based on MWFRS
Max TC CSI: 0.522
A Brg Width = 7.6 Min Req = 1.5
Max BC CSI: 0.444
C Brg Width = 1.5 Min Req = -
B Brg Widih =1.5 Min Req = -
Max Web CSI: 0.000
Bearing A is a rigid surface.
Wgt: 15.4 Ibs
Bearing A requires a seal plate.
Maximum Top Chord Forces Per Ply (Ibs)
VIEW Ver. 18.02.00.1016.21
Chords Tens.Comp.
A-B 60 -146
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
A-C 0 0
-WARNING" Please lhomughlyrevlaw Me-A-1 ROOF TRUSSES('SEU.ER").GENERAL TERMS and CONDITIONS CUSTOMER CBUYEW)ACKNOWLEDGMENi-Mon,
A
Verify design pameneem and read notes on this Truss Design Dall(TDD)end Ns Anemay T. Tents, In. P.E Ralemnce Slleat before use. Unless oNerwise acted on Ma TDD. only Alpin
m ep plaesabalbeusMd Me TDDMbaselid. Aa a Tress Design Engmeedig(i.e.0petlalty Engner). eMe seal on any Too represents an aceptal of Me peafessunal entneedn
nesponsiblNyfor Medeaignol Me single Trussdepi[tedon Me TDD only,uMerTPM.TMtlesign assumptions. keeling conditions. suitability anessa ofMts Trussforany Building alone
�gq_I memo
plimus56
BuiPagbMe respmsaiNy of Ma Cwner.BmO+meys audm¢ed agent orWBuidgg Devgner,MMe cone tof McIRC, Me10C.lpal bu0dug wdeeM TPI-1. TbaaPliel lof Me
,
of Me eIsignerndea,ess. andoes Tba al of Me TDD mMany geld
resp.1
Anthony. Tombo 111, P.E.
y
to am
derip .intands,MeO.,, storage.seadagenlmWsing anrlse,nene my,Meialest
Min, s Ma MID and!
or Me Trl [,iasile, lwndruiesSolelymsellaton(M and bn2gs1u0 be Buildup Designer gMance. r
T
0083
#BLuci
emsin de oice
and BCAamfMe
TPI ide
"' P.esbemsell es.Designartl tlulies OTmTruss
gutlelines of McBsign Companies lMomu4an(Beiv.onerveCI) Nblianixi byolveby. CAaretligned seel en in general by
solved by a agreetl upon in wnNg by aO paNesMwNN. TNe Truss Design Elypneerts NOT Ma Butld
Designer,T.rT. Design Engineer e�k Tress Mng. ore
4451 St. Lucie Blvd.
All apitkead Anse I-1.
Oaz'grrerg i...—En_ deny bml 11mpeOaatl emmNem—as�e TN a arvFle—a.W tluvrNer,®mmese, NMl mwT.-Memo T. TonWIq P.E
ForFPierce, FL 34946
Job
Truss
Truss Type
City
Ply
11/12/2018 2754
'74190
CJ5C
JACK
2
1
D
12
T T
6 p
N_
[7
-2X4(A1) B
HB 2'10 1 E
I
m L A
GF
SEAT PLATE RED.
f --- 1' --f --= 2'1*10 2'10"l -�
4'11"1'1 i
Loading Criteria (psf)
Wind Criteria
Code / Misc Criteria
Deft/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Sld: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in too Udell L/#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Sld: 2014
VERT(LL): 0.037 F 999 360
Loc R+ / R- / Rh / Rw l U 1 RL
B 273 /- /- 1217 181 1154
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.071 F 818 240
BCDL: 10.00
Risk Category: ll
FT/RT:10(0y10(10)
HORZ(LL):-0.020 G -
E 84 /- !- /50 /- /-
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.035 G - -
D 130 1- /- /98 1112 1-
Des Ld: 40.00
Mean Height 15.00 It
WAVE
Creep Factor. 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.416
B Big Width = 7.6 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0.217
E Big Width = 1.5 Min Req = -
Spacing: 24.0 •
MWFRS Parallel Dist:0 to h/2
D Brg Width = 1.5 Min Req = -
C8C Dist a: 3.00 fit
Max Web CSI: 0.129
Bearing B is a rigid surface.
Loc. from endwall: not in 4.50 ft
Wgt: 21.0 Ibs
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.10%.21
Chords Tens.Cori Chords Tens. Comp.
Lumber
A-B 27 0 C-D 58 -125
Top chord 2x4 SP#2
B-C M -124
Bot chord 2x4 SP #2
Webs 2x4 SP 93
Maximum Bot Chord Forces Per Ply (Ibs)
-Plating Notes
Chords Tens.Comp. Chords Tens. Comp.
All plates are 1.5X4 except as noted.
B - F 44 -82 G - E 0 0
C-G 82 -36
Purling
In lieu of structural panels or rigid ceiling use purling
Maximum Web Forces Per Ply (Ibs)
to laterally brace chords as follows:
Webs Tens.Comp.
Chord Spacing(in oc) Stan(ft) End(fq
BC 24 0.15 1.99
G-F 42 -10
BC 44 1.99 4.97 '
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
^WARNING^ Please thoroughly review 0.-A-1 ROOF TRUSSESCSEUFR"). GENERAL TERMS and CONDITIONS CUSTOMER CBUYER') ACKNOWLEDGMENT' to..
VenN design parameters and read notes on Nis Truss Design Drawing CMD) and the AnMany T. Tambo ill, P.ERefemnm Sheet haters use. Unless otherwise stated
on Me MD. only Alpo
w 000rplatessllallbeuseWthe TDDbhewlld. PsaTlnss Desgn Engineemlg(i.e.Spepalty Engineer).Mowalonan TDDmpresetmamptancaof Nepmressiomiengimnn
Balding isme
A.t ROOF
�TRU$5E5
reslxnsreatyforthedeagnofthe single Truss depictedon"Too only.under TPI-1.The design assumptions. bidding conditions. a fabi6lymxthm of this Trussforany
Buhieg a Me mfponslNlilyof Me Ownef. Ne Ownelid eudgr¢ed agentortbe Buildii Designer,in the comndedthelRC.Me IBC.IocelbaDding code and V1.1.
Theapprarelorthe
."m.ona ro
respon53ialyaf Ne Owner. the Owreh auNmvedagent� Na Buildup Designenatne mnteriof Na lRC, dre�Bn^Iotal�W�d'wbJae.�1-uloat�WTDD
Anthony T. Tombo ill, P.E.
t aMCrampslagb¢P Ntfe Bui
useofthe Tnas,iwM"
and Nanpaaices and
Truss
0083
#.Luca
Tres SBv
Component gaiety lri(atmetgn (BBCI)prAfSn¢d by TPl argil g0('Aaea refeRn0.N tergen¢
mXng,storage, ffON
guEelinesaftse Tir1ahm _Ner¢slt,
n,nyaltp DeOtbeaMestai Nftlb
Desgner, Truss Design Ergmec artl Tnrss Manufachaer, uNess oNemisa defuutl hya CwaaGagreed upvnln wridrg hyag pvGes inwNed. ThaTnas oesgn Erlgineera NOT ma Ruud'
Design
4451 St. Lucie BIVtl.
oesgneror Trots sntem Fneer of arybwams AP aptafized Lama are m demwd h TPL1.
CaV/rgMOA18AI PmlTruvee-MYmyT. TmnM III,PE ItepMWbndNbGmneatmaryfm4bpWLredwNvrtam when RmY%slnatA-I noel Truaca-NNvryT. Tanta 1R P.E
Fort Pierce, FL 34946
Job
Truss
Truss Type
Oty
Ply
11112/2018 2755
74190 '
CJ5E
JACK
2
1
C
12
T
6
v
N
tV i7
=2X4(A1) B
57 A
1
D
SEAT PLATE REQ.
4n11" 11 =i
.
Loading Criteria (ps0
Wind Criteria
Code I Misc Criteria
DeflICSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Sid: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udell U#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Ste: 2014
VERT(LL): NA
Lac R+ / R- / Rh / Rw ! U / RL
B 273 /- /- 1298 1116 /111
SCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCDL: 10.00
Risk Category: II
FT/RT:10(0)/10(10)
HORZ(LL): 0.005 D - -
D 92 /- !- 1152 181 /-
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.008 D - -
C 130 /- /- 1103 177 /-
Des Ld: 40.00
Mean Height: 15.00 ft
WAVE
Creep Factor: 2.0
Wind reactions based an MWFRS
NCBCLL: 10.00
TCDL; 5.0 psf
457 Max TC CSI:
0
B Big Width = 8.0 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max 0393
D Big Width = 1.5 Min Req = -
Spacing:24.0'
MWFRS Parallel Dist h to 2h
-
C Big Width = 1.5 Min Req = -
•
CBC Dist a: 3.00 itMax
We CSICSI: 0..000
Web : .
Bearing B is a rigid surface.
Loc. from endwall: not in 9.00 It
Wgt: 16.8 Ibs
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver. 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Camp.
Lumber
A-B 27 0 B-C 58 -145
Top chord 2x4 SP #2
Bat chord 2x4 SP #2
Maximum Bot Chord Forces Per Ply (Ibs)
Purling
Chords Tens.Comp.
In lieu of structural panels or rigid ceiling use pulling
B - D 0 0
to laterally brace Chords as follows:
Chord Spacing(in DO) Start(ft) Ert
BC 58 0.15 4.97
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional CBC
member design.
Left bottom chord exposed to wind.
'N/ARNING^ Please Mamul review Me -A-1 ROOF TRUSSES(-SEt1ER'). GENERAL TERMS and CONDITIONS CUSTOMER CBUYER') ACKNOWLEDGMENT' form.
d
Verily design parameters and mad rates on Nis Truss Design Drawing(TOD) and the AnVwny T. Tombe ill, P.E. Refemnce sheet bebre use. unless orhemise salad an the TDD, ody9
MA-1
raunectar plates slat be used for Me Too to be valid. Asa Truss DesignE nneal le. Smal ly Eugineee.Mesent an any Too represents an acceptance of Me professlaral elgineervl
Me Tmesdepleed tie TODonP/.undet W4l.Thedesignaswmptions. hall conditions. swtabiliy and use alloys Truss lorerry Building is Me
ROOF
�sTnD55E5
responsibility br Me design of single on
Boding is Me responsibility or Me owner, the Cano's theorized agentor Me guide, Designer, in to centea ofthe IRO. the IBC. loml building code and TPl-1.
ToaPilah lol Me-
..nw.�..a
or Me Boeing of e Idealonial of
code and TPI-1. The ha
in Me lity
Me and s gold
tie
Anthony T. Tombo III, P.E.
of Mled
Me reasonabier.
use of therT s, IncMe luding handling, storage. brage. Insulation and bacin9 shall beain
Building Designer contractor. Al nods se out o dTDD
antl practicee and
Truss
# 80083
guidelines of Me Beleling Component Safety Infemlagon (BSCI) published by Mao SBCA are m(erenrotl for general guidance. TPI-1 defines Me respoasibilites and duties alone
Designer. Truss Design Engineer and Truss Manufacturer, unless omewdse defined by a Cmbad agreed man In annual by all pates inwhad. The Truss Design Engineer is NOT Me Buildi
4451 St. Lucie Blvd.
Designer or rm:: symem EngMcer arany banding. Ataal.uxedlannuaraasdenneaslTPI-1.
GpytlgNO ]0180.1 RmlTrvvm-PMrmy T. Tomb III. PE Repm,v an dtloa Eounuo ,hanyrmm, isryMIdIMwYhou[Ou wrinen penal ofA-1 eanl Tru—s-Moony T. TanM III, P.E.
Fort Pierce, FL 34946
Jab
Truss
Truss Type
City
Ply
11/12/2018
2756
'74190 •
CJ5P
JACK
2
1
C12
T
6
v
(V cD
h
E=2X4(A1) B
57
A
D
SEAT PLATE REQ.
4'11"11 ,
Loading Criteria (I
Wind Criteria
Cade / Misc Criteria
DefI/CSl Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Sid: ASCE 7-10
Code: FSC 2017 RES
PP Deflection in loc Udell L/#
Gravity Non -Gravity
TCDL 10.00
Speed: 160 mph
TPI Std: 2014
VERT(LL): NA
Loc R+ / R- / Rh / Rw / U / RL
B 273 /- /- /298 /116 /154
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCDL 10.00
Risk Category: II
FT/RT:10(0)/10(10)
HORZ(LL): 0.005 D - -
D 92 /- /- /152 /81 /-
EXP: C KzD NA
Plate Type(s):
HORZ(TL): 0.008 D - -
C 130 P /- 1103 1116 /-
Des Ld: 40.00
Mean Height: 15.00 It
WAVE
Creep Factor. 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL: 5.0 pat
Max TC CSI: 0.3
B Brg Width = 7.6 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Maz BC CSI: 0.393 93
D Brg Width =1.5 Min Req = -
Spacing: 24.0'
MWFRS Parallel Dist:0 to h/2
C Brg Width = 1.5 Min Req = -
C&C Dist a: 3.00 it
Max Web CSI: 0.000
Bearing B is a rigid surface.
Loc. from endwall: not in 4.50 it
Wgt: 16.8 lbs
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
1
VIEW Ver: 18.02,00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber A-B 27 0 B-C 58 -145
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Maximum Bot Chord Forces Per Ply (Ibs)
Purlins Chords Tens.Comp.
In lieu of structural panels or rigid ceiling use puffins B - D 0 0
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 58 0.15 4.97
Apply puffins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C _
member design.
Left bottom chord exposed to wind.
^WARNING^ Please thoroughly raWewMe'A-1 ROOF TRUSSESMEUER'). GENERAL TERMS and CONDITIONS CUSTOMER CBWER') ACKNOWLEDGMENT" fi
verify design parameters am read notes on Nis Tines Design Drangg(Too) aad ee AnMvry T. Tombo 111. P.E.Referenm S5 tbeWeu .UnlessoNe sesutl on Ne TDD.O*Alpin
conne"platys shoe be used for tla TOO m be valid As a Tuns Design Engraving (i.e. Spend, Engineer), Me seal on any Too represents an ansptarwe of Me professional enaineafin
res,arebtyfor the design of Me single Trussdepidedor Me TDD ONy,under WIA.ThedesenassumpdorM,b�ingmM�dma,swlabiGry and ussofesis Trussforary Bolding feMe
A-1 ROOF
�TI111$$E5
Bugdre, nrue responsSllnid Pe Ownal. Me Ownefs auRlmized agentwlhe Bulling Devgner,atice canted of NelRC. rue IBC.Ipal bYJdbg rode aM TPI-1. Theap rnodidf Me
.wmm.a�e
respons3i4ry of theOmer, the OwnefaeuNmzM aBenl orthe Bolding Designer.Mme meted of NeIRC. McIBD, Ioml building rode aM TPI-1. Theapprevaldrue TDDaMaMfied
handling, instagagon aM bracug slag ba tla responsibility afros Baud'vg Designer and ConUacdr. AllwtessetwtNNa TDD.WMaprelicesand
Anthon T.Tombo 111, P.E.
y
use of the Tross.indutivg storage.
guidelinssofrue Bwldug Component Bafetylnfcm Wn(BBCI)pubris by TPIaMSBCAa mMmnmdfergeneralguidanm. TP ldef Neresp mibilidesaMduWsofd Truss
#80083
Designer. Tnas Design Engineer and Truzs Manufacturer, unless oNemiso defined by a Cmbad agreed ,on in ening by an Asides Me Ned The Truss Design Engineer is NOT Me Build
4451 St. Lucie Blvd.
Nsigneror Tmu SV,Iem Engineerotanybwlding. Ao waUraM temta are ae aeened'a TPI-1.
GgydgMO'A18M1R Try -Mrs MT.TmWIII,PE Repro]utlbnal N'ndmmm{in anylotm.6pNVNW MNun PewMm pvmliSM or A�1amfTww-MdmyT. TmnW III. P.E
Fort Pierce, FL 34946
Job Truss Truss Type Qty Ply 11/1212018 2869 +
74190 D01 COMN 1 2
-tra•3 I a3.13
B1.sx5
Loading Criteria (psf)
TCLL:
20.00
TCDL:
10.00
BCLL:
0.00
BCDL:
10.00
Des Ld: 40.00
NCBCLL: 0.00
Load Duration: 1.25
Spacing: 24.0 "
SEAT PIATE REa
H*-I
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 it
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist:0 to h/2
C&C Dist a: 3.00 it
Loc. from endwall: not in 9.00 It
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top chord 2x4 SP #2
Bot chord 2x6 SP 2400f-2.0E
Webs 2x4 SP #3 :W5 2x4 SP #2:
:W6 2x8 SP 2400f-1.8E:
Nailnote
Nail Schedule:0.131"x3", min. nails
Top Chord: 1 Row @12.00" o.c.
Bot Chord: 1 Row @ 3.50" O.C.
Webs : 1 Row @ 4" o.c.
Use equal spacing between rows and stagger nails
in each row, to avoid splitting.
(1) 1/2" bolts may be used for
(2) 0.131"x3', min. nails on
The Bottom Chord Only.
Special Loads
--(Lumber Dur.Fac=1.25 / Plate Dur.Fac =1.25)
TC: From 60 plf at -1.00 to 60 pit at 7.13
TC: From 30 plf at 7.13 to 30 plf at 11.38
TC: From 60 pit at 11.38 to 60 pit at 19.70
BC: From 20 pit at 0.00 to 20 plf at 7.13
BC: From 10 plf at 7.13 to 10 pit at 19.70
BC: 26051b Cone. Load at 7.13
BC: 1033 lb Cone. Load at 9.06,11.06,13.06,15.06
BC: 1034 lb Cone. Load at 17.06,19.06
Purling
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Stad(ft) End(ft)
TC 24 11.38 19.70
BC 120 0.15 19.70
Apply pudins to any chords above or below fillers
at 24' OC unless shown otherwise above.
^WARNING" Please thoroughly review the'A-i ROOF TRUSSES
Vainly design parameters and read notes an Nis Truss Design Drawing (TDO)
mnnecmr plates shaA be used forthe MD to be valid As a Tmss Design Err
resoonsibiliN for Me desire of Me simoss Truss de0ided on the Too only. un&
5! 111033 2�Z1033p Y�r1034 Z�1�
26050 ta3M 10334' 1039#
Code / Misc Criteria Deft/CSI Criteria
♦ Maximum Reactions (Ibs)
Code: FBC 2017 RES PP Deflection in loc LldeO L!#
Gravity Non -Gravity
TPI Std: 2014 VERT(LL): 0.101 K 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: No VERT(CL): 0.200 K 999 240
B 4208 /- /- /- 11861 1-
FT/RT:10(0)/10(10) HORZ(LL): 0.019 H - -
G 5979 !- I- /- 12158 !-
Plate Type(s): HORZ(TL): 0.037 H - -
Wind reactions based on MWFRS
WAVE Creep Factor. 2.0
B Big Width = 7.6 Min Req = 1.7
Max TCCSI: 0.709
G Big Width= - Min Req = -
MaxBCCSI: 0.516
Bearing B is a rigid surface. _.
Bearing B requires a seat plate.
Max Web CSI: 0.833
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 282.8 lbs
Chords Tens.Comp. Chords Tens. Comp.
VIEW Ver. 18.02.00.1016.21
A-B 13 -10 D-E 705--1779
B-C 1840-4168 E-F 705 -1779
Hangers/Ties
C - D 1202 -2802
(J) Hanger Support Required, by others
Wind
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
Wind loads and reactions based on MWFRS.
Right end vertical not exposed to wind pressure.
B - K 3680 -1613 I - H 2492 -1064
K- J 3647 -1599 H- G 0 0
J -1 3647 -1599
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
K-C 1497 -654 E-H 104 -136
C -1 712 -1538 H - F 2968 -1176
D-1 2186 -989 F-G 980 -2431
D - H 628 -1250
horyL Tambo III, P.E. Reference sheet be
s. S x nally Engineer). Me seal on any Too i
e deagn assumptions, loading conditions, su
ssigner. in Me concert of Me Re. the IBC. Ira
context of Me IRC. the IBC, locel building cal
Ibit y of Me Building Designer and Cantradoi
CAare referenced for general guidance. Tr
Commad agreed upon In wnbng by all paides
ACKNOWLEDGMENT` form.
d
�as A-1 ROOF
mTR055E5
Anthony T.Tombo III, P.E.
# 80083
4451 St. Lucie Blvd.
Fort Pierce, FL 34946
Job Truss Truss Type Oy Ply 11/12/2018
2757
1-74190 D02 COMN 1 1 1
Loading Criteria (psf)
TCLL:
20.00
TCDL:
10.00
BCLL:
0.00
BCDL:
10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0"
Lumber
Top chord 2x4 SP #2
Bat chord 2x4 SP #2
Webs 2x4 SP #3
SEAT PLATE RED.
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C KzC NA
Mean Height: 15.00 ft
TCDL' 5.0 psf -
BCDL: 5.0 pi
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 It
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Purling;
In lieu of structural panels or rigid ceiling use puriins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 9.64 19.45
BC 88 0.15 19.45
Apply purling to any chords above or below fillers
at 24" OC unless shown otherwise above.
Hangers 1 Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right and vertical exposed to wind pressure.
Deflection meetsU360.
95'11 —
1111.5X4 1113X4(R)
=JX4 -ox. =one
19'1
Code / Misc Criteria
Defl/CSI Criteria
Code: FBC 2017 RES
PP Deflection in lac Udefl U#
TPI Std: 2014
VERT(LL): 0.030 J 999 360
Rep Factors Used: Yes
VERT(CL): 0.059 J 999 240
FT/RT:10(0)/10(10)
HORZ(LL): 0.010 H - -
Plate Type(s):
HORZ(TL): 0.021 H - -
WAVE
Creep Factor: 2.0
Max TC CSI: 0.364
Max BC CSI: 0.976
Max Web CSI: 0,966
Wgt: 109.2 Ibs
-
VIEW Ver: 18.02.00.1016.21
I
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ / R- / Rh / Rw I U / RL
B 846 /- A /591 /189 1335
G 770 /- /- /462 /326 /-
Wind reactions based on MWFRS
B Brg Width = 7.6 Min Req = 1.5
G Big Width =- Min Req = -
Bearing B is a rigid surface.
Bearing 6 requires a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-B 27 0 D-E 481 -601
B-C 663-1222 E-F 481 -601
C-D 546 -936
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
B-J 1032 -912 I-H 783 -657
J - 1 783 -657 H - G 170 -156
Maximum Web Forces Per Ply (Ibs)
Webs
Tens.Corl
Webs
Tens.
Comp.
C-J
306 -300
E-H
301
-340
D-J
404 -78
H-F
857
-574
D-H
208 -258
F-G
530
-726
-1VARNING- Please Noroughly review the -A-1 ROOF TRUSSES('SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER-) ACKNOWLEDGMENT" to.. A
War, design parameters and read notes on the Toss Design Orawblg (mO) and Me AnMOty T. Tombs Ill. P.E. Relerenw Sheet before use. Unless ogle ishe sfeled on Me TOO, only Alpin
.ane=rplaws shall be used for the TDD to be valid. Asa Truss Design Engineemg(io.Spedaly Engineer). Ne seal an any Too represents an acceptance of the pnobasional engineenp -A-L RODE
responsibility for to design of Me single Truss depicted an the TDD only, under TPl-I. The design assumplions, loading conditions. suitabitiy and use of his Tons; br any Building is Me �OTRD55E5
Building M Me tesponshifiry of Me Owner, Me Owners auf(wraed agent"" Budding Designer, in Me contest ofthe lRC, McIBQ local building code and TEM. Thsepprovalof Na .wmm.w+a
hoponsibiliyoflhe Ownep Me Owners authorized agent or line Building Designer. in the context of the IRC. Me IBC, local building code and TPI-1. The approval clubs TDD and any field Anthony. Tombo Ill, P.E.
use oftbe Truss, including handling, storage. Mineralantl bracing chat be Me responsihiliry offs, ButdingDesgner, and Conbatlor. Nimtessetoutin Me TDDand Mepmacesand y
guidelines of We Building Component Safety lnfomdgont9SCl) published by TPI and SSCAare referenced for general guidance. TPI-ldefines MeresponsibUiUe anddude oflha Tmss #80083
Designer, Toss Design Engineer and Truss Manufachrer, unless sushi defined by a Coneraal agreed upon in wslbng by all parties invall The Tmss Design Engineer is NOT Me Belifir 4451 St. Lucie Blvd.
DesignererToss System EtgM rofaMbuilding. Mcapmred Madareasdefinedin'r 1. FL 34946
CmMOM®M(6 AiRwl Tnsus-Mill T.TonOU In. EPeanductun offted—eµinanylmm.K pMlbited Without the rmEen asessaenof A-1 Rm(Tsses u-NMary T. Turned111. PE Fort Pierce,
Job Truss Truss Type Oty I Ply 11/12/2018 2758
74190 D03 COMN 1 1
SEAT PLATE REG.
Loading Criteria (par) Wind Criteria -
TCLL 20.00 Wind Std: ASCE7-10
TCDL 10.00 Speed: 160 mph
BCLL: 0.00 Enclosure: Closed
BCDL: 10.00 Risk Category: II
EXP: C Kzt NA
Des Ld: 40.00 Mean Height: 15.00 ft
NCBCLL: 10.00 TCDL: 5.0 psf
Load Duration: 1.25 BCDL: 5.0 psf
Spacing: 24.0" MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 ft
Loc.. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top chord 2x4 SP 42
Sot chard 2x4 SP #2
Webs 2x4 SP #3
:Rt Slider 2x6 SP #2: BLOCK LENGTH = 1.500'
Purlins
In lieu of structural panels or rigid ceiling use puffins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 9.00 11.33
BC 119 0.15 19.45
Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
2.4- —T 8.1.6 �
=4X4
=sx4=sx4 =anti
Code / Misc Criteria
Code: FBC 2017 RES
TPI Sid: 2014
Rep Factors Used: Yes
FT/RT:10(0)/10(10)
Plate Type(s):
WAVE
19'5"6
Defl/CSI Criteria
PP Deflection in loc Udell L/#
VERT(LL): 0.042. K 999 360
VERT(CL): 0.102 K 999 240
HORZ(LL): 0.0181 - -
HORZ(TL): 0.036'I - -
Creep Factor: 2.0�
Max TC CSI: 0.356
Max BC CSI: 0.982
Max Web CSI: 0.174
Wgt: 95.2 Ibs
VIEW Ver: 18.02.00.1016.21
♦ Maximum Reactions (Ibs)
Gravity Nan -Gravity
Loc R+ / R- / Rh / Rw / U / RL
B 846 /- /- /550 1174 /189
H 770 /- /- /456 1148 /-
Wind reactions based on MWFRS
B Brg Width = 7.6 Min Req = 1.5
H Big Width =- Min Req = -
Bearing B is a rigid surface.
Bearing B requires a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Camp.
A-B 27 0 E-F 5% -968
B-C 730-1260 F-G 707 -1130
C - D 577 -976 G - H 724 -1237
D-E 586 -815
Maximum Sot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp
B - K
1074 -598
J - 1
815
-328
K-J
815 -328
I-H
960
-537
C
Maximum
Web Forces
Per Ply (Ibs)
Webs
Tens.Comp.
Webs
Tens.
Comp.
C-K
308 -327
E-1
223
-81
D-K
282 -73
I-F
245
-213
-WARNING— Please thoroughly review Me'A-1 ROOF TRUSSES CSELU3R7), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMENT` form.
Verify design parameters and read notes on this Tress Design Drown,, (TOD) and the Anthony T. Tombo ill, P.E. Refemnce Sheet bafine uae. Unless olhendae slated on Ne TOD, only Npin
asnnector plates shall be used brute TOO to be valid As a Truss Design Engineering (i.e. specully Engineer). the seal on any TOD represents an acceptance of Me professional engineerin MA-1 RRRF
responsibility far Me design ofMe single Truss depicted oa the Too ad,, under TPI-1. The design assumptions, bsQng conddlons, suitability and useaf this Truss for any Budding is the #®TRUSS6
Building is the responsibility of Me Owner, Me Owner's authorized ag.t.r Me Building Designer, in the context of Me IRC, the IBC, least building code and TPI-1. Theappmvalof Me ••�•��
responsibility of the Owner, Me Owners authorized agent mthe Building Designer, in Me contend of Me IRC. Me IBC, local building code and TPI.1. The approval of Me TOD and any field Anthony. Tombo III, P.E.
e of the Truss, trotting handling, storage, installation and brecing shall b , Me responsibi fty of the Building Designer and Contractor. All notes set out in the TOD and the practices and
y
guidelines of Me Building Component Safety lnbrmadan(BSCI) published by TIP! and SECAare referenced for general guidance. Tal-1 defines the responsMnfies and duties of the Truss #80083
Designer, Truss Design Engineer and Truss Manufacturer. unless otherwies definetl by a contract agreed upon In writing by all parties brvahad. The Truss Design Engineer is NOT Me Burain g 4451 St. Lucie Blvd.
Cosigner or Truss System Engineer of any Malting.Allaspllakeed terms are as defined In TPLl. Pe Fort Pierce, FL 34946
Job Truss Truss Type Qly Ply 11/12/2018 2759
74190 ' D04 COMN 1 1
I
n
1 yr
SEAT PLATE REQ.
Loading Criteria (par) Wind Criteria
TCLL 20.00 Wind Sid: ASCE7-10
TCDL: 10.00 Speed: 160 mph
BCLL: 0.00 Enclosure: Closed
BCDL: 10.00 Risk Category: II
EXP: C Kzt NA
Des Ld: 40.00 Mean Height: 15.00 ft
NCBCLL: 10.00 TCDL: 5.0 psf
Load Duration: 1.25 BCDL: 5.0 psf
Spacing: 24.0" MWFRS Parallel Dist: hi to h
C&C Dist a: 3.00 it
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
:Rt Slider 2x6 SP #2: BLOCK LENGTH = 1.500'
Purling
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Slart(ft) End(ft)
TC 24 7.00 13.33
BC 95 0.15 19.45
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
6'4" i— 6'1.6 --1
Sa4X6
IIILSX4 =snw =sna
19'5"6
Code / Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
Code: FBC 2017 RES
PP Deflection in loc Udell U#
Gravity Non -Gravity
TPI Sld: 2014
VERT(LL): -0.040 E 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.063 1 999 240
B 846 /- /- /551 1352 1150
FT/RT:10(0)/10(10)
HORZ(LL): 0.023 E - -
F 770 /- /- /457 1313 /-
Plate Type(s):
HORZ(TL): 0.034 E - -
Wind reactions based on MWFRS
WAVE
Creep Factor: 2.0
B Big Width = 7.6 Min Req = 1.5
Max TC CSI: 0.427
F Brg Width =- Min Req = -
Bearing S is a rigid surface.
Max BC CSI: 1.000
Bearing B requires a seat plate.
Max Web CSI: 0.169
Maximum Top Chord Forces Per Ply (Ibs)
WgC 86.8 lbs
Chords Tens.Comp. Chords Tens. Comp.
VIEW Ver: 18.02.00.1016.21
A-B 27 0 D-E 655 -1114
B - C 674 -1206 E - F 692 -1210
C - D 660 -945
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
B - I 999 -507 H - G 1004 -505
I - H 1004 -505 G - F 935 -463
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
C-1 264 0 G-D 263 -7
C-G 151 -182
^WARNING' Please thoroughly review Me'A-1 ROOF TRUSSESCSELrER"), GENERAL TERMS and CONDITIONS CUSTOMER CBUYER") ACKNOWI.EOGNi form.
Verity design parameters and read notes on this Truss Design Wareing (TOO) and the Anthony T. Tombs ill, P.E.Reference sheet bdad use. Unless otherwise slated on the TOD, any Alpin
connectar plates Stall be used forthe TOD to be valid. As a Truss Design Engineer'ig(i.e. SpesalN Engineer),Meseat on any Too represents an amaplance or Pe professional engineeim =q-s ROOF
responsibility for Me design of Me single Truss depicted on the TOD only. under TPIA. The design assumptions, loading conditions. suitability and use of his Truss for any Building is the =iRr155F5
Building is Me responsibility ofthe Chinni Pe Ouri audmreed agent or the Building Designer, in Me context ofthe IRC, Mel Si local building code and TPIA. Theapproval of the
esponsiblliy of the Owner. the Owners saturated agent orthe Building Designer.inlhe content ofdle Ill the IBC, local budding code and TPI-1. The approval of the TDD andanyfek AnthonyT. Tombo ill, P.E.
use oftha Tmss.istuding handling, storage, Installation and heeling shall b, him responsibiliy ofthe Building Designer and Contractor. NlnotessetmLLinthe TODandthepradieesand
guidelines of the Building Component Safety Informatiin(BSCI) published by TPI am SECA are referenced for general guidanco. TPI-1 def es the responsbilities and dudes of the Tmss #80083
Designer, Tmas Design Engineer and Tmss Manufacturer, unless onershe deshad by a Contract agreed upon in wnErg by all pates inwived. The Tmss Design Engineer is NOT Me Buildi 4451 St. Lurie Blvd.
DesignerorTrue, system Engineer of any building. Aural>ilaliaedterm: are as dermea:rTPl-t. Fort Pierce, FL 34946
ry
en 9Pme L1 Rmf Tosses-Me—T. Tombo III. P.E. ReW WeWm M Wz GcamenLd•ariY lmm, is prdilEiledw.NON the writlen armiuimo/Mt RoolTruzsn-PnVarry T. Tcmbo I0. PE
Jab Truss Truss Type Oh Ply 11/12J2018 2811
74190 ' D05 COMN 1 1
E=4X4
SEAT PLATE RED.
Z6'4
1019#
1578
t•]•1D
99]#
Loading Criteria (psf) Wind Criteria
Code / Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00 Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc L/defl U#
Gravity Non -Gravity
TCDL: 10.00 Speed: 160 mph
TPI Sld: 2014
VERT(LL): 0.060 D 999 360
Lee R+ / R- / Rh / Rw / U / RL
BCLL: 0.00 Enclosure: Closed
Rep Factors Used: Varies bi,
656M@L): 0.120 D 999 240
B 1824 /- /- f- /777 /-
BCDL: 10.00 Risk Category: It
FT/RT:10(0)/10(10)
HORZ(LL): 0.015 C - -
N 1808 /- /- /- [761 /-
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.030 C - -
Wind reactions based on MWFRS
Des Ld: 40.00 Mean Height: 15.00 ft
WAVE
Creep Factor: 2.0
B Brg Width = 7.6 Min Req = 1.5
NCBCLL 10.00 TCDL: 5.0 psf
Max TC CSI: 0.434
N Brg Width = - Min Req = -
Load Duration: 1.25 BCDL: 5.0 psf
Max BC CSI: 0.970
Bearing B is a rigid surface.
Spacing: 24.0 " MWFRS Parallel Dist: 0 to h/2
Bearing B requires a seal plate:.
C&C Dist a: 3.00 ft
Max Web CSI: 0.477
Maximum Top Chord Forces Per Ply (Ibs)
Loc. from endwall: not in 9.00 it
Wgl: 117.6 lbs
Chords Tens.Comp. Chords Tens. Comp.
GCpi: 0.18
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
A-B 27 -20 E-F 693 -1654
B - C 996 -2360 F - G 762 -1836
Lumber
C-D 883-2153 G-H 85.3 -2020
Top chord 2x4 SP #2
-
D - E 693 -1653 H - 1 881 -205B
Bot chord 2x6 SP 2400f-2.0E
_
Webs 2x4 SP #3
Maximum Chord Forces Per Ply (Ibs)
:Rt Slider 2x4 SP #3: BLOCK LENGTH = 1.500'
Chords Tens.s.Comp. Chords Tens. Comp.
Special Loads
B - M 2066 -855 K - J 2057 -872
--(Lumber Dur.Fac 1.25/Plate Dur.Fac=1.25)
M-L 2215 -932 J-1 1785 -747
TC: From 60 plf at -1.00 to 60 plf at 19.45
L - K 2057 -872
BC: From 20 plf at 0.00 to 20 plf at 19.45
BC: 10191b Cone. Load at 2.52
BC: 997 lb Cone. Load at 17.81
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
Purlins
845
C - M 773 -201 L - F 381 -332
In lieu of structural panels or rigid ceiling use puffins
M - D 73 F - J
-246
to laterally brace chords as follows:
' 747
-1067 J - G 747 -246
D - L 1067
Chord Spacing(in oc) Start(ft) End(ft)
255
E - L 1252 -467
TC 24 5.00 7.58
TC 24 12.75 15.33
BC 120 0.15 19.45
Apply puffins to any chards above or below fillers
at 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads and reactions based on MWFRS.
-WARNING- Please thoroughly review the'A-1 ROOF TRUSSES CSELIFR"). GENERAL TERMSand CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMEM'farm.
Ne TDD, Mpin
verify design parameters and read notes an Nis Times Design Dudvdlg (Too) and t1le Antllony T. Tombo III, P.E Reterenm Sheet before use. Unless oNemdse slated on onty
Sunni plates shall beusedforlhe TDD Wbevalid. Asa Tmss Oesgn Engineelvlg(i.e.spedalry Engmeer),Ne walonanyTDD represenean acceptance of the professional engineerin
�q.r NOOF
msponsixityfor Me design of tie single Tmss deplded on Vie TDD only, under T 14.The design assumptions, loading donations, suitability add use of this Truss for any Building is tie
Uwner.Me Dvmers agent or the BuJd'vlg Designer, in tie comexlafthe IRC, Me LBO, local budding mole add TPIA. Theappmraloftie
_TRO55F5
•• �•m
Building is tie respasubllily of the authorized
responsibility ofum Owner. the Owners authorized agent or the Building Designer. in tie context of Pe IRC, Me IBC, local building code and TP1-1. The appravalorme, Too and anyfeltl
budding be We responsibility of the Building Designer and Contractor. All notes set m4 in the TDD aM tie Pmctims antl
AnthonyT. Tombo Ill, P.E.
y
e of the Those, indi ding handling, storage, installation and shall
guWelinesoftie Building Component Safetylahm tion(BSCI)publisbedby TPIaMSBCAammferencedrorgenemlWidanca. TPI-1 defines tie responsibirties and duties Store Times
Designer, Tmss Design Engineer and Trues Manufacturer. unless demansdefined by a Contract agreed upon in vmdng by all probes involvM. The Tmss Design Engineer is NOT tie Suldin
#80083
4451 St. Lucie Blvd.
Designerar Tmss System Engineer ofany building. MmoV112Mme areasdefinedin Wi.l.
CmMgM01616MI RwrTrusssz-AnNmy T. TomMIII.PE RepMuclbn WNK Emment'el any di apMJbYadwiNM NexnMn pe,masbnot Ml RmrTrusez¢-MVwny T. Tcmbo ill, Re.
Fort Pierce, FL 34946
Job Truss Truss Type QO' . Ply 1 11/12l2018 2760
74190 V D06 CO IN 1 1
�- T7" 77' 1
1=2X4(A1)
Loading Criteria (ps0 Wind Criteria
TCLL: 20.00 Wind Std: ASCE 7-10
TCDL: 10.00 Speed: 160 mph
BCLL: 0.00 Enclosure: Closed
BCDL: 10.00 Risk Category: II
EXP: C Kzb NA
Des Ld: 40.00 Mean Height: 15.00 it
NCBCLL: 10.00 TCDL: 5.0 psf
Load Duration: 1.25 BCDL: 5.0 psf
Spacing: 24.0MWFRS Parallel Dist: 11/2 to h
C&C Dist a: 3.00 It
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top chard 2x4 SP #2
Bol chord 2x4 SP #2
Webs 2x4 SP #3
Purlins
In lieu of structural panels or rigid Ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 105 0.13 15.04
Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Hangers I Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
D
III1.5X4
162"
Code / Misc Criteria
Def11CS1 Criteria
♦ Maximum Reactions (Ibs)
Code:FBC 2017 RES
PP Deflection in loc Udell U#
Gravity Non -Gravity
TPI Sid: 2014
VERT(LL): 0.008 D 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.015 D 999 240
A 607 /- /- /361 /243 1145
FT/RT:10(Ou10(10)
HORZ(LL): 0.009 D - -
C 607 /- /- 1361 /243 /-
Plate Type(s):
HORZ(TL): 0.013 D - -
Wind reactions based on MWFRS
WAVE
Creep Factor. 2.0
A Big Width = - Min Req = -
Max TC CSI: 0.599
C Big Width = - Min Req = -
Max BC CSI: 0.993
Maximum Top Chord Forces Per Ply (Ibs)
Max Web CSI: 0.129
Chords Tens.Comp. Chords Tens. Camp.
Wgb 53.2 Ibs
A- B 484 -846 B - C 484 -846
VIEW Ver: 18.02.00.1016.21
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-D 678 -288 D-C 678 -288
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp.
B - D 338 0
-WARNING— Please lboroughly rai to'A-1ROOF TRUSSESCSEUER'), GENERAL TERMS and CONDITIONS CUSTOMER (BUYER") ACRNOWLEDGMENT" flans.
Verify toogn Parameters We read notes on Nis Tuss Design Drawing(TOO) and dot Meany T. Tombo ill, PE. Refdrenue Bbeetbefve use. Unless othervdse slaiedonsir TOD, onty Alain
IA-1
mvmctar Floods sba0 be used for to TOD m be valid. As a Truaa Design Engmeertg(i.e.Sperally Engineer), to Seal w any Too national an e¢aplarde of the pmesousial angmeerin
Truss depicted on Me Too oNy, under TPM.mm design assumpans, adding candlliom. suiUbiGty and use of loch Trust forasy Building is the
ROOF
�TND55E5
respons'Elliryfor dmdes�ofMe single
Bundin,diberesper b!Utyof NeO er,me Omrersaup edagentwd BuSdeg Designer,hldmmrlte#of NeIRC.Me IBC.1=1 uddirg Meand TPI-1. The approval of
respons311ryafoac"ondn Vie Owneta euNor'vdA agentaem BUJdhg Ddsigner,m Na mnte loll Na IRG. NeIBC, bt lbui�ig Meats TPF1. Thoepprovalofda TODarMalrygeW
Truss. hltltlud'vg baMGrg, instaAation and bmdng saa0 be gm responsitigly Wdle Build'eg DesignaraM Contractor.Mroks salMNNe TDO end Ne pmrlicesaM
Anthony T. Tombo Ill, P.E.
rase of iha struage. as Othe Tess
ollna B eomponenl Udommgan (Bandeas M shed by rPl a�tl $aaAdre refaren Mar general by
aft rPl-t deflre Tre rase Design Engineer
aaagreed uponNwri4rg by all paNes hrvoNed. TM Trim Design ElgincerSNOTiIia Build
0083
# Lucia
4451SLo
Dearams.
okin T.
Designer. True Desgn Erg'meereMT�ManuMCWmr.uNdioNem$edefedill
Designvarruss srsltm Enghee faro bwdilg. An zPrar ea mnre era atmr varPl-1.
Gme`gNON118A1RmrTuima-MNmyT. Tamto W.PE RepeN9Mafpds6 rant ilam'tam,KPWIVINMdat Ne wriEn Pwr?¢vmelA-1 ROY Truav-MamyT. Tvroe111.P£
FI_U114
Fort Pierce, FL 34946
Job Truss Fwsspe Oty Ply 11/12/2018 2761
74190 ' D07 1 1
f- 7'-1'2"7'
:4X4 T2
B C D;4X4
F
III1.5X4
15'2"
Loading Criteria (ps0 Wind Criteria Code I Misc Criteria De0/CSI Criteria ♦ Maximum Reactions (Ibs)
TCLL: 20.00 Wind Std: ASCE 7-10 Code: FBC 2017 RES PP Deflection in loc Udell L/# Gravity Non -Gravity
TCDL: 10.00 Speed: 160 mph TPI Std: 2014 VERT(LL): 0.028 B 999 360 Loc R+ / R- / Rh / Rw / U / RL
BCLL: 0.00 Enclosure: Closed Rep Factors Used: Yes VERT(CL): 0.061 B 999 240 A 607 /- /- /364 /243 1134
BCDL: 10.00 Risk Category: II FTIRTAO(Op10(10) HORZ(LL): 0.019 C - - E 607 /- /- /364 /243 /-
EXP: C Kzb NA Plate Type(s): HORZ(TL): 0.028 C - - Wind reactions based on MWFRS
Des Ld: 40.00 Mean Height: 15.00 It WAVE Creep Factor: 2.0 A Brg Width = - Min Req = -
NCSCLL: 10.00 TCDL 5.0 psf Max TC CSI: 0.492 E Brig Width = - Min Req = -
Load Duration: 1.25 BCDL: 5.0 psf 0997 Maximum Top Chord Forces Per Ply (Ibs)
Spacing: 24.0" MWFRS Parallel Dist: h/2 to InMax BC CSI: . Chords Tens.Comp. Chords Tens. Comp.
C&C Dist a: 3.00 ft Max Web CSI: 0.127
Loc. from endwall: not in 4.50 ft Wgt: 54.6 Ibs A - B 527 -862 C - D 568 - 692
GCpi: 0.18 B-C 568 -692 D-E 527 -862
Wind Duration: 1.60 VIEW Ver. 18.02.00.1016.21
Lumber Maximum Bot Chord Forces Per Ply (Ibs)
Top chord 2x4 SP #2:T2 2x6 SP #2: Chords Tens.Comp. Chords Tens. Comp.
Bot chord Zx4 SP #2 A - F 699 -334 F - E 699 -334
Webs 2x4 SP #3
Purlins Maximum Web Forces Per Ply (Ibs)
In lieu of structural panels or rigid ceiling use puffins Webs Tens.Comp.
to laterally brace chords as follows: C - F 334 0
Chord Spacing(in DO) Start(ft) End(ft)
TC 24 7.00 8.17
BC 108 0.13 15.04
Apply puffins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Hangers / Ties
(J) Hanger Support Required, by others
Wind
Wind loads based on MWFRS with additional C&C
member design.
"WARNING— Rates thoroughly review the-A-1 ROOFTRUSSES CSELLEW), GENERAL TERMSand CONDITIONS CUSTOMER ("BUYER-) ACKNOWLEDGMENT' form. e
Very design parameters and read notes on this Truss Design Damns (TOD) and the Anthony T. Tombo Ill, P.E. Reference Sheet Were use. Unless otherwise stated on the TDD, ontyat,
connector plates sM1all be used roc the TDDbbe valid. As a Truss Design Engine,hg(ty Specialty Engineer). to seat on any TOD represents an aaepfance of thepmkssional eng�needr, pGnF
tesponubiliryforthedeslgn ofthesingle Trussdepictedpn the TDDonly, under TPl-1.The design assumptions, loading condhions, sudabilityand paper this Trussforany Building isthe �OTRUSSM
Building is the responsibility of the Oar, the Owners authored agent or The Bulling Designer, in the spread of thelRC, gee IBC. local building case and TPVI. Theapprevalofthe
responsibility of the Owner, the Owners authorge authorized Binding Designer, In the contend of the IRC, the 2C, local building code antl TPl-1. The appewal of the Too aMany food Anthony. Tombo Ill, P.E.
use of the Truss, induding handling, storage, installation and basing shall be the responsibility of the Building Designer and Contrador. All notes set out in the TDD and the practises and
y
guidelines of Ne Building Component Safety Warrention(BSCI) published by TPI and SBCA are referenced forgeneral guidance. TPI-1 defines the responsibilites and duties ofthe Truss 980083
Designs, Truss Design Engineer and Truss Manufacturer, unless itherwise lefinel by a Contrast agreed upon in wrung by all parties involved. The Truss Design Engineer is NOT the Builtir 3 4451 St. LUCID Blvd.
cr—.lROLlte A-ta Rmf Trews-AntronvT.TommlllT..P.E'Rainsoucwn"'Iaaf NizelwurroMh-1tum.agMlG4d—ut Ne wriEen Prosomnof AA Rwf ir,¢ves-PNM,ry T. Tors III, PE. Fort Pierce, FL 34946
Job I Truss Truss Type Qty Ply 11/12/2018 2805
74190 D08 I HIPS 1 1 1
Loading Criteria (psf)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
Lumber
Top chard 2x4 SP #2
Bot chard 2x4 SP #2
Webs 2x4 SP #3
21M 13011, 1380#+ 216#
1 5'0.6 �(- 2'0.6 -}-O•Z0.6 --� 50.6
a4X6
12 6=6X6 C
6 p
=axa(Al)^ D_4x4fAl7
1 F E G
SEATPIATERED.
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP:C Kzt NA
Mean Height: 15.00 it
TCDL: 5.0 psi
BCDL: 5.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 8
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Special Loads
-(Lumber Dur.Fac =1.25 / Plate Dur.Fac =1.25)
TC: From 60 p8 at 0.00 to 60 pit at
5.00
TC: From 30 plf at 5.00 to 30 plf at
10.17
TC: From 60 plf at 10.17 to 60 pif at
15.17
BC: From 20 plf at 0.00 to 20 pit at
5.03
BC: From 10 plf at 5.03 to 10 pit at
10.14
BC: From 20 plf at 10.14 to 20 plf at
15.17
TC: 216 lb Conc. Load at 5.03.10.14
TC: 130 It, Conc. Load at 7.06, 8.10
BC: 221 lb Conc. Load at 5.03,10.14
BC: 921b Conc. Load at 7.06, 8.10
Pudins
In lieu of structural panels or rigid ceiling use purilns
to laterally brace chords as follows:
Chord Spacing(in oc) Start(0) End(fl)
TC 24 5.00 10.17
BC 75 0.15 15.02
Apply puriins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads and reactions based on MWFRS.
SEAT PLATE RED,
1 92#1 4 2211
221# 92#
Code / Misc Criteria
Deg/CSI Criteria
♦ Maximum Reactions (Ibs)
Code: FBC 2017 RES
PP Deflection in loc Udell L/#
Gravity Non -Gravity
TPI Std: 2014
VERT(LL): 0.059 F 999 360
Loc R+ / R- / Rh l Rw / U / RL
Rep Factors Used: Varies lo
WtPML): 0.119 F 999 240
A 1162 1- b /- 1501 1-
FT/RT:10(0)/10(10)
HORZ(LL): 0.029 E - -
G 1162 /- P I- 1501 /-
Plate Type(s):
HORZ(TL): 0.057 E - -
Wind reactions based on MWFRS
WAVE
Creep Factor. 2.0
A Brg Width = 7.6 Min Req = 1.5
Max TC CSI: 0.908
G Brg Width = 7.6 Min Req = 1.5
Max BC CSI: 0.979
Bearings A & D are a rigid surface.
Bearings A & D require a seat plate.
Max Web CSI: OA35
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 64.4161
Chords Tens.COmp. Chords Tens. Comp.
VIEW Ver: 18.02.00.1016.21
A-B 928-2088 C-D 930 -2084
B - C 783 -1838
Maximum Bot Chord Forces Per Ply (IDS)
Chords Tens.Comp. Chords Tens. Comp.
A-F 1803 -789 E-D , 18M -791
F-E 18V -785
'
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
B-F 347 0 E-C 354 0
B-E 18 0
—WARNING^ Please 9noroughlyreview the-A-1 ROOF TRUSSES('SSU_ER-). GENERAL TERMS and CONDITIONS CUSTOMER (BUYER") ACIUOWLEDGMEN I- tons.
Verily design paaaolels and read notes on Nis Truss Design Drswbg(TDD) end es AnNsry T. Tombo ill, P.E. Referen®Sheet Delore use. Unless oNelwise stated on Ne TDD, only Alpin
mnne r platos shaft be sO W( TDD to he v W. M aTruss Design Engrannlg o.e. Specialty Engineer), the seal on any Too represent an ascepmnce of the professorial engineedn
A-r ROOF
36TRUSSE5
responsceity Win. daspn of1he single Truss depism on rile Too only. under TPpt.Ttro design asseepilona,:oading condition, sudabmry and use of Ins Tessa loran Building is tie
B 1Smg'¢Ne responsDlgly of Ne Owner,maO.mets autlwized agentsthe Buld'ulg De4gner, in the canaO of Ne IRC, the lBC.loral buiW'ug rude aM TPI-1. TbeaPPnmdl
rspons3�TN of the Omer, the Omwfa autllPaN agenlstla Buildug Resigner.mNewnteV of NeIRC, tlIa IBD.bal Wilding code aM TPI-1. TheapsoPalol#g TODandamyfield
Anthony Tool III, P.E.
%r
use of#re Tnlss. Missing handing. staage, insallyoxi and basing ahau be therespanebOy ofere 6ug#ag Designer ner and ConM noes set not a tie Too am me p2d� iand
Truss
#80083
gutleWsof the BwW'rug Compolcenlsafery 4darmatlon(BSCG pub4slN 6y TPIaM SBCAare relerensd lorgmnral guitlance. TPI-t def Ne asponslWNes anJ duties of the
Designer. Truss Design ErgineeraM Truss Mararnobrer.uJts.taennse defined or a Contrast agneed upon In voting by ag parties involved. Ta TluseD 11- Erginear is NOT Me Saran
4451 St. Lucie Blvd.
oen,narmT sssyaalnEn,seerpfanybuaaalg. Abc�irarasa m,lm ®e ac aer.,adb TPp1.
CwpFyl¢OAfe ht qwl Tuun-MYuny T.Tmda III. P.E RepW,tlM olpea dvmaLLF aryfam.b prluLledwOlub Neenmm IenlrmsYntlMl RmrT�w-MamyT.TmAolll, P.E
Fort Pierce, FL 34946
Job Truss Truss Type Oty I Ply 11/122018 2806
74190 D09 I COMN 1 1
Loading Criteria (pe0
TCLL: 20.00
TCDL: 10.00
SCLL: 0.00
BCDL: 10.00
Des Lit: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
Top chord 2x4 SP #2
But chord 2x6 SP #2
Webs 2x4 SP #3
Special Loads
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 it
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist:0 to h2
C&C Dist a: 3.00 it
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
-(Lumber Dur.Fac. 1.25 / Plate Dur.Fac =1.25)
TC: From 60 plf at 0.00 to 60 pit at 2A6
TC: From 30 plf at 2.46 to 30.pit at 5.00
BC: From 10 plf at 0.00 to 10 plf at 5.00
TC: 85lb Conc. Load at 2.49
TC: 53lb Conc. Load at 4.52
BC: 607 lb Conc. Load at 2.06, 4106
BC: 1021b Conc. Load at 2.49
BC: 43 lb Conc. Load at 4.52
Purling
In lieu of structural panels or rigid ceiling use pur ins
to laterally brace chords as follows:
Chord Spacing(in DO) Start(ft) End(ft)
TC 24 2.46 5.00
BC 58 0.15 5.00
Apply putting to any chords above or below fillers
at 24' OC unless shown otherwise above.
Hangers ITies
(J) Hanger Support Required, by others
Wind
Wind loads and reactions based on MWFRS.
85#53# 2
)--- Z5'14 t ZO-6 � 12
j 2'5'8 - -{ 2'6'8 --{
12
6 C7:;- B---4X4 s=3X4C
T
�g
=2X4(A1)A Pl
l
E E 6 113X8D
SEAT PLATE REQ.
-20'12� 1 16'14-f 1
607a 02# 607# 43#
Code / Mise Criteria Deg/CSI Criteria
Code: FBC 2017 RES PP Deflection in loc Udell U#
TPI Std: 2014 VERT(LL): 0.009 E 999 360
Rep Factors Used: Varies b) l L): 0.017 E 999 240
FT/RT:10(0)/10(10) HORZ(LL): 0.002 B - -
Plate Type(s): HORZ(TL): 0.003 B - -
WAVE Creep Factor. 2.0
Max TC CSI: 0.131
Max BC CSI: 0.416
Max Web CSI: 0.438
Will'. 25.9 Ibs
VIEW Ver: 18.02.00.1016.21
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ / R- / Rh / Rw 1 U / RL
A 751 /- /- /- /317 /-
D 1019 /- /- /- 1418 /-
Wind reactions based on MWFRS
A Brg Width = 7.6 MIn Req = 1.5
D Brg Width =- Min Req = -
Bearing A is a rigid surface.
Bearing A requires a seat plate.
Maximum Tap Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A - B 454 -1078 B - C 400 -1006
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-E 942 -391 E-D 10 -5
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
B - E 287 -44 C - D 298 -657
E-C 1151 -457
••WARNING'• Please thoroughly revle Me'W-1 ROOF TRUSSES('SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER CBUYEW) ACKNOWLEDGMENT form. A
Veray design pammoters aM read notes on Nis Truss Design Dranilp (fD0) aad"MNmy T. Tombo Ill. P.E. Referenw Sheet before use. Unless othemise slated on the TOO, onlyAna
conneoor plates ahau ba used fer the TDDWbe vatW. As a Truss Design Engineering es. Specialty Erg'vteen. the seal on any TOO represents an as¢ptaux.fNelaatessionul engineerpi ®Eq_f OF
RD
respaeftiliry Wrthedesign of the single Truss depicted on the TOD only. under TPI-1. The design assurinpdau. Watling rantlbions, suilanicy aMuseefdgs Truss forarry Building is Ma nv -1 ROOF
Bugdvg5 the resrMSbilYy of Ne Owner, the Owrefs avlhoazM egenlwlhe euddug Designer. in tM anteq INthe lRC, the lBC. bcal buddug Lade and TP41. The approval of Ne .wv..mna
rerpdvsiGlilyol the Owner,th�O.mels authprvatl agent or the BuiWWg Designer.mtheraimrt of the lRC, the IBC,Iral6uitSvg rude artl TPLl. The aDWovald Bte TDD aM amyfietl Anthony. Tombo 111, P.E.
use o<Ne Truss, uvdud'mg hantlfug,storage. inSWladm and bredm shad be theraponUbgdyUthe BugGug DesgneraM Convaear. MannesseloutWthe TDDandthepraracesand y
gu eO sotthe BYlWbg Composentsafetyldormaden(BSCI)pubu by WiI SBC ommferencedfargereralgwtivtce. TPI-1deN NemsponvNtl aMduliesofdm Truce #80083
Designer. Tn¢s Design Eagmeer and Truss ManuWchaer, unless otherw$e defined by a CmNadagreed upan in waging by ad parties b Ned. The Truss Design Engineer W NOT me Bulloi 4451 St. Lucie Blvd.
oesigmrerTraaasnlem Engveerafamy daaug. Ao mp�rxM Winn aeanderanednTPl-1. -r..„,,,„m.ve_ Fort Pierce. FL 34946
Job Trusts Truss Type - City Ply 11/1=018 2807
74190 D10 I HIPM 1 1 1
Loading Criteria (psf)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
Top chord 2x4 SP #2
Bot chard 2x6 SP #2
Webs 2x4 SP #3
78# 470
2'6'10 t 2.1'2--1-•�--
)-- 2'5'8 i 2'6'8
12
6 p B=04 as3X4C
T
=2X4(A1)A To
1 1
AS 1u3XBD
Wind Criteria
Wind Sit& ASCE7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: ll
EXP: C Kzt NA
Mean Height: 15.00 ft
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 R
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Special Loads
-(Lumber Dur.Fac=1.25 / Plate Dur.Fac =1.25)
TC: From 60 plf at 0.00 to
60 pit at 2A6
TC: From 30 plf at 2.46 to
30 plf at 5.00
BC: From 10 plf at 0.00 to
10 pit at 5.00
TC: 78 lb Cone. Load at 2.55
TC: 47 lb Conc. Load at 4.65
BC: 607 lb Cone. Loadat2.06, 4.06
BC: 89 lb Conc.,Load at 2.55 -
BC: 30 lb Conc. Load at 4.65
Purling
In lieu of structure] panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 2.46 5.00
BC 58 0.15 5.00
Apply pudins to any chords above or below fillers
at 24' OC unless shown otherwise above.
Hangers I Ties
(J) Hanger Support Required, by others
Wind
Wind loads and reactions based on MWFRS.
SEAT PLATE RED.
I
F- 2'0'12 - 141 1'6'2'i
6079 89# 607# 30#
Code / Misc Criteria
COde:FBC 2017 RES
TPI Sld: 2014
Rep Factors Used: Varies
FT/RT:10(0)110(10)
Plate Type(s):
WAVE
Defl/CSI Criteria
PP Deftection in too Udell L/#
VERT(LL): 0.008 E 999 360
lTY0R!MQ: 0.016 E 999 240
HORZ(LL): 0.002 B - -
HORZ(TL): 0.003 B - -
Creep Factor. 2.0
Max TC CSI: 0.125
Max BC CSI: 0.407
Max Web CSI: 0.428
Wgti 25.9 lbs
VIEW Ver: 18.02.00.1016.21
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ / R- / Rh / Rw / U / RL
A 735 1- l- 1- /317 /-
D 997 /- /- /- /423 P
Wind reactions based on MWFRS
A Erg Width = 7.6 Min Reel = 1.5
D Brig Width = - Min Req = -
Bearing A is a rigid surface.
Bearing A requires a seat plate.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp_
A-B 452-1052 B-C 4DO -982
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-E 919 -390 E-D 9 -5
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
S-E 287 -45 C-D 302 -643
E-C 1125 -456
-WARNING- Please%oroughlyreWew the 'AA ROOF TRUSSES (-SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER('aUYER'•)AcxnoWL UUMLN I -TO=.
Veiny design paremelers end read notes on Nh Tmss Design Drawing(mD)entl tlten„ueny T. Tombo III, P.EReferenm Sheetbeforeuse.Unless DNewisostated on Me MD. any Asir
meetlaplatwshoUbeosedbr Na TDDbbevalid. AsaTruss Desgn Ewinee"(i.e.Specialty EObeen,Nowalonany TDDrepresentsanaopspb .fNepmfesswlenginae-
responsbliyforte design oflhe single Truss depicted on We Too only, under TPl-t.The d"gn assuraptbns, boding sandigoas, aviToob"M use of Nis Truss foray Budding is We
-A.r ROOF
i3TRUSS6
aulldne'sdycf p. of Na Onsar Ownefmtori¢edegentorlhener.m eesig lRC,de IBC,bWbu lxdeand TP41. of Na
..om
ofNepontegoBC. Wd ftmDroval
responsgirdy al Na O.mer, Na Qanela auNor'vedagenl or Ne auiM'vg Desgner,bNe coNertol NeIRC, Ne IBC, oral Eudd'vg cotleeM TPM. TM1a approval of Na TOD aM anyfieN
er.
Anthony. Tombo ill, P.E.
y bo Ill
uSs of Ne Truss, halMin9 ha�ing.sNrage.imbdationeM batlng shad ba Na resrons'bsy al Ne aulltling DesgneraM Conaadu,ide, to Ne TDDaMNepretliosT
80083
#.Luca
Monti
glMerer.T Naeuildirlgngin.ent Safety lMomagon(BSCI)puaf¢RtlMTPI aM SBCAare relerenCtl lagercrelgueanln es soshad. Neresiss Design EnMduEes o(Neebol
Desi�er,T ct Design Engi
srrea. a dermNtrTPi-1. lS agreed uponlnwdEig byag parEes mwNed ll�a Truss Dmhyi Erginau¢NOT Ne eudll
4451 St. Lucie Blvd.
De oarar T. scoreEnlmeerot�yb Tuo,y,. Au apa rim terra sae, �rorineabTPI-1.
n!fTrvoMan. M sa,,Wom
_ .. _ .. n n nary rmm_h vtlWaeE w(Tan ae xiNm %n115410I 11 Rmf T.-P T. Twneo al. P.E.
Fart Pierce. FL 34946
Job Truss Truss Type City Ply 11/12/2018 2762
74190 ' E01 FIAT 1 1
Loading Criteria (psf)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCSCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
Lumber
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
I Webs 2x4 SP 93
IIIA3X4(R) 1113t4
SEAT PLATE RED. SEAT PLATE RED.
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt NA
Mean Height: 16.29 It
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: h/2 to It
C&C Dist a: 3.00 it
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Pudins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(fl) End(ft)
BC 87 0.00 7.27
Apply purling to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based an MWFRS with additional C&C
member design.
End verticals exposed to wind pressure. Deflection
meets U360.
Left bottom chord exposed to wind.
Additional Notes
Truss must be installed as shown with top chord up.
T3"4
Code / Misc Criteria
DeflICS1 Criteria
♦ Maximum Reactions (Ibs)
Code:FBC 2017 RES
PP Deflection in loc Udefl U#
Gravity Non -Gravity
TPI Std: 2014
VERT(LL): -0.001 A 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.001 B 999 240
D 291 1- /- 1196 1295 1225
FT/RT:10(Oy10(10)
HORZ(LL): 0.005 B - -
E 291 /- /- /298 ./160 /-
Plate Type(s):
HORZ(TL): 0.005 B - -
Wind reactions based on MWFRS
WAVE
Creep Factor. 2.0
D Erg Width = 7.6 Min Req = 1.5
Max TC CSI: 0.832
E Brg Width = 7.6 Min Req = 1.5
Max BC CSI: 0.763
Bearings D & E are a rigid surface.
Bearings D & E require a seat plate.
Max Web CSI: 0.598
Maximum Top Chard Forces Per Ply (Ibs)
Wgt: 44.8 lbs
Chords Tens.Comp.
VIEW Ver: 18.02.00.1016.21
A-B 153 -104
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
D - C 329 -350
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Camp.
A-D 406 -218 B-C 293 -218
A-C 240 -242
—WARNING^ Please thoroughly review the -A-1 ROOF TRUSSESrSELIER-), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACRNOMILEDGMENP from.
Verily design parameters and read noise w Mis Truss Design Drawn, (MCI) and the Anthony T. Tombv III, RE Rerseenm giver before use. Unless odtemise stated on the TDD, Dory Alpin
connecbrplatea$MUbeusedforthe TDDtobev M. AsaTross DesgnP-rlgmeer'vlg li.e. spetialy Engineer), dlv vealonany TDD represedb an ameptance of Ne profissioral etgmeerm
B&ding¢Me
A-1 ROOF
aiR0556
respms3ilityWftdvsignol Mos A9le Tr depk on Mo TDDony.undw WP 1.nodesgnassumpdws,badingmnditiom,suitabatyandusvof Nb Tmnfmary
Bulldlrg'Is be respmvUJiyol Ne Owner, th�OwreYs auNoriiad agenlar gb Bugdug Oesigner. in the mole#aINeIRC, NeIBC. bcal bulltlitry mde aM TPI-1. Theappmvalorme
.n®m.wav
LxiIn,09 end E25bg5"i,ss Me Bu�n, Coalraa�. M in MCI a
Anthony T. TOmb0111. P.E.
Ised GneT ss ha�M sexes, inneeresPonsti iy of Design ar nd M siaeslset the am� paw
guidellres ollhe Buiaitg Corneanentsafey INomation(MCI) ptNbshed byWI end SBCAare re(erenmdlm gercal guidin[e. TPFI tleNm NvresponvLlipes aM tlutles of me Tmss
#80083
Designer. Tmss Desi�Etglneerand Tn cMa,ufacwer. unless outemim mrured byacamael vgreetl upmmwnNg by ag paresmvdved. ma Truss oezi�Erginvera NOT my Bull
4451 St. Lucie Blvd.
Design Truss SpWm Etggeerolatry build'm9-Ao mpTar¢ed terms amvdefmatl nTPp1.
GpytgILL0IDI8 A-IRQITruifm-MNrvry T. Tanto lll,P.E Repolu9nddn dmneN.bmry Mn.6ptl�tedwMwl AemOen peeleElmolAA Rmf Tmm�-MdmyT. TamW tII, P.E
Fort Piece, FL 34946
Job Truss Truss Type Orly ply 11/12/2018 2763
174190 E02 I HIPM 1 1 1
Loading Criteria (psf)
TCLL 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0 "
Lumber
Top chord 2x4 SP #2
Bat chord 2x4 SP #2
Webs 2x4 SP #3
�-55"11 —1 1'9•9
SEAT PLATE REQ.
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.80 ft
TCDL: 5.0 psf
BCDL 5.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Purlins
In lieu of structural panels or rigid ceiling use puffins
to laterally brace chords as follows:
Chord Spacing(in cc) Start(ft) End(ft)
TC 24 0.00 5.47
BC 87 0.00 7.27
Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
End verticals exposed to wind pressure. Deflection
meets U360.
Left bottom chord exposed to wind.
••WARNING^ Please dmroughlyreviewthe'A-1 ROOFTRUSSES
leafy design pa2meters and rear notes on Nis Tmss Design D2wgg E
r`eee�mr Ufee star! be usetl her Me TDD to be valid. Asa Tessa Design gnE
12
6 p �
)F
SEAT PLATE REQ.
Code / Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
Code: FBC 2017 RES
PP Deflection in loc Udell L/#
Gravity Non -Gravity
TPI Std: 2014
VERT(LL): 0.001 B 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.002 B 999 240
E 291 /- /- 1213 1261 /224
FT/RT:10(0)/10(10)
HORZ(LL): 0.002 C - -
F 291 /- /- /311 /128 /-
Plate Type(s):
HORZ(TL): 0.002 C - -
Wind reactions based on MWFRS
WAVE
Creep Factor: 2.0
E Erg Width = 7.6 Min Req = 1.5
Max TC CSI: 0.529
F Erg Width = 7.6 Min Red = 1.5
Bearings E & F are a rigid surface.
Max BC CSI: 0.740
Bearings E & F require a seat plate.
Max Web CSI:0.453
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 46.21bs
Chords Tens.Comp. Chords Tens. Comp.
VIEW Ver: 18.02.00.1016.21
A-B 102 -88 B-C 95 -172
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
E-D 111 -259
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
A - E 243 -170 B - D 343 -196
E-B 225 -151 C-D 141 -52
a Andmny T. Tondo 111. P.E. Raferenm Sheet be
ig li.e. Spedafty Engineer), the assal o any Too t
1. The designSons, loading
ndidOnS. Su
ng Designer, N Me context of de Inc. 0e IBC. Ia
i Me ranted of 0e IRC. the IBC, local building co,
Ponsibi5y of the BuiMing Designer and Contractor
d SSCAarereferenmdforgenualguidan,a. V
by a Contract agreed upon In wrNng by all parties
N TPI-1.
ACKNO W LEDGM ENr" form.
en staled on Ne TDD. elv As
Design
and
�OA-1 ROOF
�TRrl5$F5
Anthony T•Tombo III, P.E.
# 80083
4451 St. Lucie Blvd.
Fort Pierce, FL 34946
'Job Truss Truss Type Cry Pi y 11/12/2018 2808
•74190 E03 I HIPS 1 1 1
Loading Criteria (psf)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0"
Lumber
Top chord 2x4 SP #2
Bot chord 2x4 SP M-30
Webs 2x4 SP #3
2799 1879 1181 1 y q 2T9tt+
j 2'D1-I-.1 1°P.74 l_276-I
SEAT Pi RED. SEAT Pl_A E RED.
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt NA
Mean Height: 15.00 it
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 It
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Special Loads
-(Lumber Dur.Fac =1.25 / Plate Dur.Fac =1.25)
TC: From 60 plf at 0.00 to 60 pit at
7.00
TC: From 30 pit at 7.00 to 30 pit at
13.27
TC: From 60 pit at 13.27 to 60 plf at
20.27
BC: From 20 pit at 0.00 to 20 plf at
7.03
BC: From 10 pif at 7.03 to 10 pit at
13.24
BC: From 20 pit at 13.24 to 20 plf at
20.27
TC: 279lb Conc. Load at 7.03,13.24
TC: 187lb Conc. Load at 9.06,10A4,11.21
BC: 483 lb Conc. Load at 7.03,13.24
BC: 130 lb Conc. Load at 9.06,10.14,11.21
Purling
In lieu of structural panels or rigid ceiling use purling
to laterally brace chords as follows:
Chord Spacirl oc) Start(ft) End(ft)
TC 24 7.00 13.27
BC 58 0.15 20.13
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads and reactions based on MWFRS.
Left bottom chord exposed to wind.
483# 13clu
fare 13U 483#
Code / Misc Criteria
De0)CSI Criteria -
A Maximum Reactions (Ibs)
Code: FBC 2017 RES
PP Deflection in Ice L/defl L/#
Gravity Non -Gravity
TPI Sid: 2014
VERT(LL): -0.156 C 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Varies b
l 0.261 C 919 240
A 1924 /- /- /- /1184 /-
FT/RT:10(0)/10(10)
HORZ(LL):-0.062 F - -
I 1924 /- 1- 1- 11184 1-_
Plate Type(s):
HORZ(TL): 0.100 F - -
Wind reactions based on MWFRS
WAVE
Creep Factor: 2.0
A Erg Width = 7.6 Min Req = 2.3
Max TC CSI: 0.910
1 . Brg Width = 7.6 Min Req = 2.3
Bearings A & E are a rigid surface.
Max BC CSI: 0.999
Bearings A & E require a seat plate.
"
Max Web CSI: 0.216
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 93.8 lbs
Chords Tens.Comp. Chords Tens. Comp.
VIEW Ver: 18,02.00.1016.21
A-B 2297-3557 C-D 2273 -3477
B - C 2273 -3477 D - E 2297 -3557
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chards Tens. Comp.
A - H 3084 -1983 G - F 3105 -1995
H - G 3105 -1995 F - E 3084 -1983
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
B - H 546 -303 G - D 568 -425
B - G 568 -426 F - D 546 -303
_
C - G 296 -496
"WARNING•• Please lforooghly review the -Ai ROOF TRUSSES('SELLER•), GENERAL TERMS and CONDITIONS CUSTOMER(•BUYER") ACKNOWLEDGMENT" fort".
Verify design reasonable and read notes on this Truss Design Craving(TDD) and Me Anthom, C Tombo Ill, PiRefemi Sheet before use. Unless otherwise stated an Me TDD, only Alp,n �
comfodor plates shall beusedfair Me TDD to W valid As a Truss Design Engineering(i.e. Spemlly Engineer), the seal on any TDD represents an acceptance of Me professional lingineerin OA-r RDGP
responsibility for Me design of Me single Truss depicted on the TDD ord. under TPN. The design assumptions, funding conditions. salability and use of this Truss for any Building is Me TRUSSES
Building is Me respansibility ofthe01 the Demers auooiized agenlor Me Bulding Designer. in Me orate#of Me IRO, the IBC, local funding cede and TP-1. Theappmral of Pe rr.w.ewnv
responsibility oftbe Owner, Me Diner's authorined agent or Me Building Designs, illMemntmd.ftieIRC, the lBi local buildingaxle=1 TPI-1. The approval of Ire TDD and any field Anthony TLTombo Ill, P.E.
use brute Truss, inducing handling, storage. installation and brai shall be Me responsibility ofthe Building Designer and Contactor. Allnomesetoutinele TDDaMthepradioesand
guidelines& Me Broiling Component Safety Information(BSCI) published by TPl and SECA are referenced for general guidance. TPWdefines the responsibilities and duties ofthe Truss #80083
Designer. Truss Design Engineer and Truss Manufacturer, unless o@ewdse defined by a closed agreed upon in writing by all notes involved. The Truss Design Engineer is NOT Pe BuiMi g 4451 St. Lucie Blvd.
Designer or Truss system Engineer of any building. All wpiolaaa temps ere es defined N TPI.1. NTLsFort Pierce, FL 34946
.... r PmfTwsai-Mmonv T. Twnba Ili.P.E. Femto]vpMn dmmenlln arty mar. prcMElredv+IMur Newn¢en p mmmsm lNMl Prof Tn+sses- anal T.Tombo Ill, P.E.
Job Truss Truss Type Day Ply 11/12/2018 2791
74190 HJ1 I HIP_, 4 1
Loading Criteria (ps0
TCLL 20.00
TCDL' 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.60
Load Duration: 1.25
Spacing: 24.0'
Top chord 2x4 SP #2
Sot chord 2x4 SP #2
1
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Krt NA
Mean Height: 24.61 it
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: 0 to 1,/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Special Loads
-(Lumber Dur.Fac =1.25 / Plate
Dur.Fac =1.25)
TC: From 0 plf at -1.41 to
60 plf at 0.00
TC: From 2 plf at 0.00 to
2 plf at 2.32
BC: From 2 plf at 0.00 to-
2 plf at 2.32
TC: -8 It, Conc. Load at 1.41
BC: 25 lb Conc. Load at 1.41
Purling
In lieu of structural panels or rigid ceiling use puriins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 26 0.15 2.32
Apply pudins to any chords above or below fillers
at 24' OC unless shown otherwise, above.
Wind
Wind loads and reactions based on MWFRS.
-8#
-
12 424 C
� T T
=2X4(A1) B n rn
A 1
D
F- 1'5" -j 2714 -�
Code/ Misc Criteria
Code:FBC 2017 RES
TPI Sit: 2014
Rep Factors Used: Varies
FT/RT:10(0y10(10)
Plate Type(s):
WAVE
4
25#
Defl/CSI Criteria
PP Deflection in loc Udell L/#
VERT(LL): NA
L): NA
HOR7(LL):-0.000 D - -
HORZ(TL): 0.000 D - -
Creep Factor. 2.0
Max TC CSI: 0.054
Max BC CSI: 0.040
Max Web CSI: 0.000
Wgt: 11.21bs
VIEW Ver: 18.02.00.1016.21
♦ Maximum Reactions (Ibs)
Gravity Non -Gravity
Loc R+ / R- / Rh / Rw / U / RL
B 114 /- /- /- 188 /-
D 38 /- /- I- /7 I-
C 16 /-8 /- /- 126 /-
Wind reactions based on MWFRS
B Brg Width =4.2 Min Reg = 1.5
D Erg Width =1.5 Min Req = -
C Brg Width =1.5 Min Req = -
Bearing B is a rigid surface.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-B 14 -15 B-C 13 -9
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
B-D 0 0
"WARNING- Please toroughly review Me 'AA ROOF TRUSSES ('SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER CBUVEW) ACNNOWLEDGMENP roan.
Verify design parameter and madnobsontis TMss Design Drawing(TDD)and Me Antony T. rotate III, P.E.Refem�Sheetpe uw.Unlessotendsestaledonte TOO ovy Npi
mmseas Mass onto lea used fro MD D to be vatld. As a Truss Design Engineemlg (i.e. Specialty Engineer), to mal on any TDD represents an assonance of to professional ergmeeM
msponsitiiity for lye desgn of to origin Toss depicted on to TDD only. underT W. The design assumptions, leading sanctions. sitaluty aM use oftb Trues foramy Madding is Me
A-1 ROOF
Building is to respansibitty alum Donner, dm Owners autMrted e9amorte Evading Designer. in Me coned of to IRC, to lad, burl building We and TPI-I. Theapponmi to
•nPv.m•vev
res ylte
Cwthgr a l.
eNtb2BCn9lobe Merespa�t5i0,TM)aforame switeag TIDaMNewaaasanma
Anthony T. Tombo ill, P.E.
ap �r,�e� 9 wboa Dasgnu a=iN Mn�setwinth
#.Luca
Dezegvv nis�s Dssgn�EAgme anE Taruers Manulewae(wiDl)sssp pure �mfirealryac�mays,iegreed�upan ul vniugq panissa. �m waa TltrmT� ignE neder�is NOT me auu
4451SLLurie Blvd.
Desgnror to IRoal DgureemamT.T-b.ailmdaltedbmaaaaaoeo mTPpL
CmnbdOaneNl Rord Trl¢aea-MmmYT. TanMN.PE RepMvmdmeaEmnmN.Nvryfmm.sPosjadvllM^ala'.ttbvl W^rmzv,^rM1RM�-MNny T. Tonto II1, P.E.
Fort Pierce, FL 34946
Job
Truss
Truss Type
Ory
Ply
11/12/2016 - 2792
-74190
HJ2
HIP_
2
1
-8#
F- 1'4"8 -j- 2'0"7 ={ _ _ _
12 C
4.24 p T T
,s
2X4(A7) e �o
N
I1�
1
A 1
D
SEAT PLATE RED.
3'5"
m
25#
Loading Criteria lost)
Wind Criteria
Code I Misc Criteria
Deft/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL 20.00
Wind Sld: ASCE 7-10
Code: FBC 2017 RES
PP Defieclion in loc Lldeft U#
Gravity Non-Gmvity
TCDL: 10.00
Speed: 160 mph
TPI Std: 2014
VERT(LL): NA
Loc R+ ! R- I Rh / Rw . I U / RL
8 143 /- /- /- 180 /-
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Varies by
I> WnL): NA
BCDL: 10.00
Risk Category: II
FT/RT:10(0)/10(10)
HORZ(LL): -0.001 D - -
D 59 /- /- /- /4 /-
EXP: C Kzt NA
Plate Type(s):
HORZ(TL): 0.002 D - -
C 31 /-2 /- /- /14 /-
Des Ld: 40.00
Mean Height: 15.00 ft
WAVE
Creep Factor: 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.
B Brg Width = 10.0 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0.108 108
D Brg Width = 1.5 Min Req = -
Spacing: 24.0 °
MWFRS Parallel Dist: 0 to h/2
C Brg Width = 1.5 Min Req = -
C&C Dist a: 3.00 ft
Max Web CSI: 0.000
Bearing B is a rigid surface.
Loc. from endwall: not in 9.00 it
Wgt: 14.0 Ibs
Bearing 8 requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber A-B 14 -10 B-C 16 -10
Top chord 2x4 SP #2 "
Bat chord 2x4 SP #2
Maximum Bot Chard Forces Per Ply (Ibs)
Special Loads Chords Tens.Comp.
--(Lumber Dur.Fac. 1.25 / Plate Dur.Fac =1.25) B - D 0 0
TC: From 0 pit at -1.41 to 60 plf at 0.00
TC: From 2 pit at 0.00 to 2 plf at 3.41
BC: From 2 plf at 0.00 to 2 pit at , 3.41
TC: -8 Ill, Conc. Load at 1.38
BC: 25 lb Conic. Load at 1.38
Purlins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 39 0.15 3.41
Apply purling to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads and reactions based on MWFRS. -
^WARNING^ Please thoroughly review Me 'A-1 ROOF TRUSSES (SELLER"),GENERA( TERMS and CONDITIONS CUSTOMER ("BUYER") ACKNOWLEDGMENT' to..
Verify design parameters and Mad notes on Nis Tmss Design Draving(TOD) and de Anthony T. Tombs Ill, RE Reference Sheet before use. Unless othemise stated on the TOD,oNy Alpin
- a
Wnnedor plates shall caused for Me TDDto assalid. As a Tmss Design Engineerhg(re.5pecatty EngneeQ,Mussel onany TDD representsan acceptancaofthe professional engine
responsibilMforthedesign ofdresingle Tmss depicted onthe TODonly,under TPIA. The design assumptions. loading conditions, suitabihNantl useof this Tmss forany Building isthe_TRUSSER
-p-1 pDeF
Building B the responsibility, dthe Owner, the Owners authorized agent or the Building Designer, in the context of the IRC, the IBC, local building rode and TFl-1. Theapprovalofthe
••wwmw•�
the bmdrg be Ne rresposibilty of the Buildof Me ing Designer and Connbuildinector. All notes set out iand W1,1. n Pe TOO na me prencious a�a
mtldnghantlthe in,storage,
Anthony T. TDmbo III, P.E.
inrs stallation andent
ueeofMetTruss, stall
guidelinesofthe Bwlding Component Safeylnf.r b.n(BSCI)publishedbyT lI WSBCAarereferencedforgenemlguidanw. TPI-1 defines the responsibilities and duties of Me Tmss
#80083
Designer, Tmss Design Engineer and Thus Manufacturer, unless otherwise defied by a Contrad agreed upon in writing by all parties imroladd. The These Design Engineer is NOT the Bundij
g 4451 St. Lucie Blvd.
Designer of system Engnearaaln building. An rapitalbed reins are as der ea n TPI-1.
Wpyn9ht0ID16h1 RwfTrvsses-MthonY T. Tanbo ill, PE.ReyWu mdthisd=menthanyrmin.krytluLit mMw thewnttencermis mofAl1 fTvssea-M.,T.T.Iii.P.E
Fort Pierce. FL 34946
Job
Truss
Truss Type
Oty
Ply
11/12/2018 2793
74190 '
HJ5
HIP_
2
1
A# 140#
I-1-4-8 Z9°15 219,10�- - -
C
2 TT
424 71-
iV
-2X4(A1) B
1 11I
L A
D
SEAT PLATE REQ. -
772
+
106N
25#
Loading Criteria (psi
Wind Criteria
Code / Misc Criteria
Defl/CSl Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Sid: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loci Udeft U#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Sld: 2014
VERT(LL): NA
Lac R+ / R- / Rh / Rw / U / RL
B 247 /- /- /- /135 /-
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Vanes ti
I i f;L): NA
BCDL 10.00
Risk Category: ll
FURTAO(Op10(10)
HORZ(LL):-0.009D - -
D 129 /- /- /- /1 /-
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.018 D - -
C 85 /- /- /- 169 /-
Des Ld: 40.00
Mean Height: 15.00 ft
WAVE
Creep Factor: 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.
B Brg Width =10.0 Min Req = 1.5
Load Duration: 125
BCDL: 5.0 psf
Maz BC CSI: 0.564 564
D Brg Width = 1.5 'Min Req = -
Spacing: 24.0 "
MWFRS Parallel Dist: 0 to h/2
C Big Width = 1.5 Min Req = -
C&C Dist a: 3.00 it
Max Web CSI: 0.000
Bearing B is a rigid surface.
Loc. from endwall: not in 9.00 ft
Wgt: 25.21bs
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver. 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber A-B 14 -10 B-C 41 -23
Top chord 2x4 SP #2
Sot chard 2x4 SP #2
Maximum Bo[ Chord Forces Per Ply (Ill
Special Loads Chords Tens.Comp.
-(Lumber Dur.Fac =125 / Plate Dur.Fac=125) B - D 0 0
TC: From 0 pIf at -1.41 t0 60 pIf at - 0.00
TC: From 2 pit at 0.00 to 2 plf at 7.01 '
BC: From 2 pIf at O.00 to 2 pIf at 7.01
TC: -8 Ib Conc. Load at 1.38
TC: 140 lb Conc. Load at 4.21
BC: 251b Conc. Load at 1.38
BC: 106 lb Conc. Load at 4.21
Purlins
In lieu of structural panels or rigid ceiling use pudins '
to laterally brace chords as follows:
Chord Spacing(in oc) Start(fl) End(ft)
BC 75 0.15 7.01
Apply purling, to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads and reactions based on MWFRS.
"WARNING^ Please thoroughly review the "A-1 ROOF TRUSSES(SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER (BUYER")ACKNOW DGMENr"farm.
e
Verify design paromtea and read notes on this Tmss Design Dawng TDD) and the Anthony L Tombo III, P.E. Reference Sheet Name use. Unless otherwise staled an the MD. only Arpin
cannectorplates shall be used fro the TOD to to valid. Asa TmssDesign Engineervlg(i.e. Spedalty Engineer), Me seal an eny TOD represenLv an acceptanrn of the Professional engineenn
responsibility, wramanignot thesingle Tmss depicted on the Too only. under TPH. The design assume[ions, loading conditions, suitability and use of this Truss for any Building is the
gA-s RDDF
�®iRU55F5
Budding is the respansibild of the Conan. the O+meh aulheved agentarthe Building Designer, in thecanlertofthelRC, the IBC, to al building code and TPl-0. Theappram, of the
••�•�•�
Me andO� ann
TPI-1. �utnttimMoane the
rin Me contextreaWnsoMyofthe of Suilthn,
rlring �eAll
Anthony T. Tombo Ill, P,E.
notes stond
Dessigne�ld Cen4ebul
Greao
uzetofthe Ttyrue,, Muudcifthe
hsndllinwg,, swrage.nnssttallllabun ant nd troche sr tall) beero
Truss
#80083
guimune Me Suitable Camponent Safety informal(BSCI) published by TPl and SBCA are referenced for general guidance. TPI-1 defines the nesponsiblliaes and duties ofthe
Designer, Tmss Design Engineer and Truss Manufacturer, unless outewdse defied by a Contract agreed upon in wrung by all parties involved. The Tmss Design Engineer is NOT the Sown
a 4451 St. Lucie Blvd.
DesignerorTmwSysem EMinWrOanybwming. m ospitaruaedteremareeadetneo inwil
Copyrlgm CM16A-1Rwl Tvsma-MNony T.To Will,P.E.Reprodudein also dmmex many form,hpM3itedvnNout the wrtlm Cumissun of A-1 Roof Tosses-AMany T. TomN III, P.E.
Fort PiFL 34946
Foerce,
Jab
Truss
Truss Type
Ply
11/12/2018 2794
Y4190 '
HJ7
HIP_
r3'y
1
�p11 25W
- )-1-4-8--t--2'9'15 ibg 25.15-(-2'V10-�
D
2
2
4.24
'a1.5x4G
la 2x4(A1)8
-
A11
it
a�
SFATPIATE FEe.
'
F 1'S• 71WI -i
254 183#
Loading Criteria (ps0
Wind Criteria
Code / Misc Criteria
DefgCS1 Criteria '
A Maximum Reactions (Ibs) -
Non -Gravity
TCLL: 20.00
Wind Sid: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udell U#
Gravity
Lee R+ / R- / Rh / Rw / U / RL
TCLL: 10.00
Speed: 160 mph
P
TPI Std: 2014
( - 0 017 C 999 360
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Varies b
�L) : 0.030 F 999 240
g 351 Y217 !-
BCDL: 10.00
Risk Category: II
FT/RT:10(0y10(10)
HORZ(LL): 0.007 F - -
E 370 P /1 /- 1133 /0
EXP: C Kzt: NA
Plate TYPe(s):
HORZ(TL): 0.019 F - -
D 66 /- /- /- 163 /-
Des Ld: 40.00
Mean Height: 15.00 R
WAVE
Creep Factor. 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.624
B erg Width = 10.0 Min Reg = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0.24
E Brg Width = 1.5 Min Req = -
Spacing: 24.0
MWFRS Parallel Dist: 0 to h/2
D Big Width ni Min Reg = -
C8C Dist a: 3.00 it
Max Web CSI: 0.286
Max
B is a nightsurface.
Loc. from endwall: not in 9.00 it
Wgt: 40.6 Ibs
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber
A-B 14 -10 C-D 55 -68
Top chord 2x4 SP #2
B - C 416 -519
Bot chard 2x4 SP 2400f-2.0E
Webs 2x4 SP #3
Maximum Bot Chord Forces Per Ply (Ibs)
Special Loads
Chords Tens.Comp. Chords Tens. Comp.
-(Lumber Our.Fac=1.25/Plate Dur.Fac=1.25)
B-F 506 -371 F-E 1 0
TC: From 0 pit at -1.41 to 60 pit at 0.00
TC: From 2 pit at 0.00 to 2 plf at 9.84
BC: From 2 pit at 0.00 to 2 pit at 9.84
Maximum Web Forces Per Ply (Ihs)
TC: -8 lb Cone. Load at 1.38
Webs Tens.Comp.
TC: 140 lb Cone. Load at 4.21
C - F 404 -551
TC: 259 lb Conc. Load at 7.03
BC: 25 It, Conc. Load at 1.38
_
BC: 106 lb Cone. Load at 4.21
BC: 183 lb Conc. Load at 7.03
Purling
In lieu of structural panels or rigid ceiling use pudins
,
to laterally brace chords as follows:
Chord Spaciril oc) Start(H) End(fl)
BC 75 0.15 9.84
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads and reactions based on MWFRS.
"WARNING- Please thoroughly review me•A.1 ROOF TRUSSES('SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER(-BUYER-)ACKNOWLEDGMENP form.
Venfydesgn paremeteraanlread roteson mis Tress Design Dromg(Too)and 0e AnNmry T.Tanbo III, P.ERiferenca Sheet Whom use. Unless otherwise sentence
the TDD,anty Alpin
/
niredorplates shall be used tar lie TODbbe valid. Asa Truss Design Eagreares;0.e.Spe(ially Engineer). Vie seal an any TCD represents an aCCepWle9 elthe professional engineers,
Ue Too Curdy, under TPI-1. The deagn assumptions, leading mndill suuablfity am use of Truss for any Bufitling is the
ASP-MA-1ROFF
responsibility la Me design of Me single Truss depleted on
Bugdvgts Ne respansailly of the Owner.NaO.mers authorized agenlw Ne Bulling Designer,ntlg mnteq a/Ne IRC, Ibs IBC.lo sl bufidugmdeareTPI-1.
Tbeapprovalef Ne
.•mm.woa
responsmady mths Owner, me aauMaiaed agent athe Buddug Desgner, Nthe ociand ofthe IRC, the IBC,1.1 bwldigead..ed TPI-1. Theapprovalofthe
and bracing shag he me resonshilly ofthe Budding esi Dgner am Contractor. M notes set M In Me TOD
TDDaMarrifieW
am Me pramias and
Anthony. Terrible ill, P.E.
y
use of the Truss, idudiig hmNfing, storage.iretafiatim
guidelines ofWBuild'ug Component Salety Nfomulan(BSC9 pubrsnttlgTPIaM SBCA are reterencedlor general guidanm. TPpt tlegnes Ne respansNdiEes aM doles oftle Truss
#80083
Designer. Truss Design Esgmea am Tnm Mara,a aar, Mail ome ise defined by a cantrad agreed unseen entng by all pates inwNed. The Truss Design
Engineer 6 NOT Me Bufi'
4451 St. Lucie Blvd.
oeeyp arms, system Erg, many dtildmg. Ae CaIMa@ed tame are a+der anTPl-t. -
DesignsoT MtamlTrviw-lef.1balMeoYI,P£Rep,bucbm Wredmdredinwilam.is pdiYileJ,NEatTewriOen Ymvsb,mM1fbolTn¢w-MemrT.TmAoll, P.E
Fort Pierce, FL 34946
Job
Truss
Truss Type
City
Ply
11/12/2018 2795
74190
HJ7C
HIP_
1
1
.e# 142# 281#
- �1'4-8--�-25"152795
E
2
6.24 r 2 03X40
t
D
ml � =2X6(A1)B 103X N a4X4F G
1 A 11
JI
SEAT MTE REQ.
T11's I 8'109
9'10'1
91#t
250 16N
Loading Criteria (psf)
Wind Criteria
Cade / Misc Criteria
DeflICSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udee U#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
P
TPI Sid: 2014
VERT LL 0 120 1 971 360
( ): -
Loc R+ / R- / Rh / Rw I U / RL
B 339 /- /- !- /217 /-
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Varies b
ML): 0.229 1 506 240
BCOL: 10.00
Risk Category: ll
FT/RT:10(0)/10(10)
HORZ(LL):.0.055 G - -
F 394 /- !- /- 1174 /-
EXP: C Kzt NA
Plate Type(s):
HORZ(TL): 0.103 G - -
E 27 /- !- /- 121 /-
Des Ld: 40.00
Mean Height: 15.00 it
WAVE
Creep :2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL 5.0 psf
CSI:
Max TC CSI: 0688
B Brg Wdth = 10.0 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0,,720
F Brig Width = 1.5 Min Req = -
Spacing: 24.0"
MWFRS Parallel Dist: 0 to h/2
E Brg Width = 1.5 Min Req = -
C&C Dist a: 3.00 it
Max Web CSI: 0.365
Bearing B is a rigid surface.
Loc. from endwall: not in 9.00 fl
Wgt: 46.2 lbs
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver. 18.02.00.1016.21
Chords Tens.Comp. Chards Tens. Comp.
Lumber A-B 14 -10 C-D 452 -934
Top chord 2x4 SP#2 B-C 157 D-E 65 -81
_-250
Bot chord 2x4 SP #2
Webs 2x4 SP #3
Maximum Bot Chord Forces Per Ply (Ibs)
Special Loads Chords Tens.Comp. Chords Tens. Comp.
--(Lumber Dur.Fac=1.25 / Plate Dur.Fac =1.25) B - I 146 .90 H - G 985 -436
TC: Ffom 0plf at -1.41 to 60 pit at 0.00 C-J. 756 -346 G-F 0 0
TC: From 2 pIf at 0.00 to 2 pIf at 9.84 J - H 899 -435
BC: From 2 pIf at 0.00 to 2 plf at 9.94
TC: -8 It, Conc. Load at 1.38
TC: 142 Ile Conc. Load at 4.21 Maximum Web Forces Per Ply (Ibs)
TC: 261 lb Conc. Load at 7.03 Webs Tens.Comp. Webs Tens. Comp.
BC: 25 lb Conc. Load at 1.38
BC: 91 lb Conc. Load at 4.21 J - I 68 -16 D - G 472 -957
BC: 168 lb Cone. Load at 7.03 H - D 233 0
Plating Notes
All plates are 1.5X4 except as noted. _
Purlins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in cc) Start(ft) End(ft)
BC 34 0.15 2.81
BC 96 2.81 9.84
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads and reactions based on MWFRS.
^WARNING^ Please thoroughly review Me'A-1 ROOF TRUSSES CSELLER"), GENERAL TERMS and CONDITIONS CUSTOMER ("BUYER') ACKNOWLEDGMENT` man.
d
Verify design pamareters and read notes on this Truss Design Draining (iDD)and the Anthony T. Tombo Ill, P.E.Refemnm Sheetbe muse.Unlessotherwisesratmonthe TDD,.*Alpin
connectorplates shall be used forthe Too to to valid. As a Tese Design Engineemy(i.e. Specialty engineer). Me seal on any Too represents an acceptance of the professional engineer.
responsibility for Me design of Me single Truest depicted On Me Too any, under TPld. The design assumptions, leading abridger, suitability antl use of Mis Truss for any Building is the
aA-r RDRF
=TR1155F5
Buildings the responsibility of the Onions, the Oerm's surnamed agent ar the Buldig Designer, in the oontetl ofthe IRC, the IBC, local building code and 171-1. Theapprovalofthelitillmmed .,.Of turn,
and
building eNina[eelsetoulnthaTDDandthepmeticesand
ofthe tyrsa0wl�nghndg,storage. signerraand
Anthony T. Tombo ill, P.E.
installation and trading emir be Me responstiliy addle. BuildingeM.
use CDntrzcto
Truss
#80083
guidoines of the asking Component Safety Infomation(BSCI) published by TPl am Sacs are referenced for general guidance. TPI-ldefestherespmrsib0itiesanddu9esofthe
UseeireA Tess Design Engueerand Truss Manufacturer, unless othemise defined by a Contract agreed upon in venting by all parties inmivad. The Tress Design Engineer is NOT the Budifi
4451 St. Lucie Blvd.
Designeror Tess System Engineer of any building. NlcarytuarroreatimasdefinedinTPI-1.
CmyrIgM02018 n-1 Rmf Tonex-Mthany T.TamMIII, 1 monsoucwnottltizdmmenl,Fany(win.kprcNtirMwMoutthe xnMnpemrissh of AA RwfTmsses-AnNmy T. TomWI11, P.E
Fort Pierce, FL 34946
Job
Truss
Truss Type
City
Ply
11/12/2018 2796
74190
HJ7E
HIP_
2
1
�# 150# 26Wt
F- 1'4'S -�- 2'9'152'9'152'9'10 �-
- -
@TT
2
4.24 p
_13X4 C
A
11
GG FFFF
111.5X4 =5X6
- SEATPIATEREO.
-1.5-12 910.1
101f111
25# 18440'
Loading Criteria into
Wind Criteria
Code / Misc Criteria
DeflfCSI Criteria
♦.Maximum Reactions (Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in roc L/deft L/#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Std: 2014
VERT(LL): -0.034 G 999 360
Loc R+ / R- / Rh / Rw / U / RL
B 361 /- /- /- /317 /-
SCLL: 0.00
Enclosure: Closed
Rep Factors Used: Vanes by
4ff%eIsML): 0.048 G 999 240
BCDL: 10.00
Risk Category: ll
FT/RT:10(0)/10(10)
HORZ(LL):-0.009 F - -
E 353 /- /0 /- /276 /0
EXP: C Kzb NA
Plate Type(s):
HORZ(TL): 0.013 F - -
D 92 /- /- /- 159 /-
Des Ld: 40.00
Mean Height: 15.00 ft
WAVE
Creep Factor: 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0697
B Brg Width = 10.1 Min Fact= 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0..973
E Brg Width = 1.5 Min Fact= -
Spacing: 24.0 "
MWFRS Parallel Dist: 0 to h/2
D Brg Width = 1.5 Min Req = -
C8C Dist a: 3.00 It
Max Web CSI: 0.438
Bearing B is a rigid surface.
Loc. from endwall: not in 9.00 It
Wgt: 43.4 Ibs
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens -Comp. Chords Tens. Comp.
Lumber
-
A-B 15 -11 C-D 42 -61
Top chord 2.4 SP #2
B - C 647 -797
Bat chord 2x4 SP #2
Webs 2x4 SP #3
Maximum Sot Chord Forces Per Ply (Ibs)
Special Loads
Chords Tens.Comp. Chords Tens. Camp.
---(Lumber Dur.Fac =125 / Plate Dur.Fac. 125)
B - G 748 -590 F - E 0 0
TC: From 0 pit at -1.48 to 60 pif at 0.00
G - F 736 -580
TC: From 2 pit at 0.00 to 2 plf at 9.84 -
BC: From 2 pit at 0.00 to 2 plf at 9.84
TC: -8 lb Conc. Load at 1.38
Maximum Web Forces Per Ply (Ibs)
TC: 150 lb Conc. Load at 4.21
Webs Tens.Comp. Webs Tens. Comp.
TC: 264 It, Conc. Load at 7.03
BC: 25 lb Conc. Load at 1.38
G - C 234 -197 C - F 623 -791
BC: 107 lb Conc. Load at 4.21
BC: 184 lb Conc. Load at 7.03
Purlins
In lieu of structural panels or rigid ceiling use puffins
to laterally brace chords as follows:
Chord Spacing(in Do) Slart(ft) End(ft)
BC 80 0.15 9.84
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads and reactions based on MWFRS.
_
Left bottom chord exposed to wind.
-WARNING- Please Overeager review the'A-1 ROOF TRUSSES('SEL.EIT), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER-) ACKNOPILEDGMENT' form.
verity design parameters and read notes on his Truss Design Drawing(TOD)and lm Anmmy T. Tombs In. P.E.Refemnce Sheet before use. Unless othemise soled an the TOD. only Arpin
�-
oannecnrplates shall heated! for Nto Too be valid As a Team Design EngmeeMg(i.e.Specialty Engineer), the seal an any Too represents an acceptance of me pmkssrmiomlm,edn
is
ETR FIXIIF
�TpM6�
responsibility forme design ofthe single Truss deeded on the TOD only, under TPI-1. The design assumptions, leading sometime, suitabiliy and use of line Trussfor
y Building the
SSp
Building is the responsibility oftheOwner. the Owner's summoned agent or the Building Designer, in the mused ofthelRC, the IBC. local building wdeand TPI-1.
Theappmvalafthe
the or the in the contold of the IRC. the lB9ner0. raand Ne
Anthony T. Tombo Ill, P.E.
ding star beSthe responsibility dine Building Dener.
ling, sW2ge. NstaAaO n and trant
use of me Trvss ineuuofthe ding handl ContratlaodreAlliniwtessetoutin TOlD
am tth.p.m.srield
and
Tmss
#BDD83
guidelines mf ma Builtllog Component Safety Inforation(BSCI) published by TPI and SECA are referenced for general guidanw. TPI-1-deWu memsponvieifties
and dares ofine
Designer. Truss Design4inaerand Tmss Manufacturer, unless olhervdze dermed by a Carried agreed upon in wiring by all comes invoked The Tmss Design Engineer is NOT the Buildir
g 4451 St. Lucie Blvd.
Designer or Tmss System Engineerafany building.M costersed tome are as defeat!0 TPI-1.
LapyngMOID16A-1 RmlToom,7pnMwy T. Tombo I11. PE RepMunnn oftrodoament N myna,m. Ispeebeledw W the edEen amJssgn Of A.1 Rwf T,uaes-MIMiry T. Tonne III, P.E
Fort Pierce, FL 34946
Job
Truss
Truss Type
ly
11/12/2018 2797
74190 '
HJ7P
HIP_
in,
1
AH 140M 2591
f-1'4'B�T9'15--T2'9'15-I-2'9'10-(
- - - -- -- - ---
DTT
2
4.24 p
a1.5%4C
=2x4(A1)B
t
A
FE
=4X4
SEAT PLATE RED.
9'10.1
25o t06# 183e
Loading Criteria (psf)
Wind Criteria
Code / Misc Criteria
DeflfCSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Sld: ASCE 7-10
Code:FBC 2017 RES
PP Deflection in loc L/de6 L/#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Sid: 2014
VERT(LL): -0.021 F 999 360
Loc R+ / R- / Rh f Rw / U / RL
B 351 f- /- !- 1333 /-
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Vanes bir
L Pr,): 0.030 F 999 240
BCDL: 10.00
Risk Category: ll
FT/RT:10(0)/10(10)
HORZ(LL):-0.013 F - -
E 370 f- /1 /- 1315 11
EXP: C Kzb NA-
Plate Type(s):
HORZ(TL): 0.019 F - -
D 66 !- /- /- /49 /-
Des Ld: 40.00
Mean Height: 15.00 it
WAVE
Creep Factor: 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.6
B Brg Width = 10.1 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 024
E Brg Width = 1.5 Min Req = -
Spacing: 24.0 °
MWFRS Parallel Dist:0 to h/2
.624
D Big Width = 1.5 Min Req = -
C&C Dist a: 3.00 it
Max Web CSI: 0.286
Bearing B is a rigid surface.
Loc. from endwall: not in 9.00 it
Wgt: 40.6 lbs
Bearing B requires a seat plate.
GCpr 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver. 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber
A-B 14 -10 C-D 58 -68
Top chord 2x4 SP 42
B - C 482 -519
Bot chord 2x4 SP 24001-2.0E
.
Webs 2x4 SP #3 -
Maximum Bot Chord Forces Per Ply (Ibs)
Special Loads
Chords Tens.Comp. Chords Tens. Comp.
-(Lumber Dur.Fac=1.25 / Plate Dur.Fac =1.25)
B - F 506 -450 F - E 1 -1
TC: From 0 plf at -1.41 to 60 pIf at ODO
TC: From 2 plf at 0.00 to 2 plf at 9.84
BC: From 2 pIf at 0.00 to 2 plf at 9.84
Maximum Web Forces Per Ply (Ibs)
TC: -8 lb Cone. Load at 1.38
Webs Tens.Comp.
TC: 140 lb Conc. Load at 4.21
C - F 49D -551
TC: 259 lb Conc. Load at 7.03
BC: 251b Conc. Load at 1.38
BC: 106 lb Conc. Load at 4.21
BC: 1831b Conc. Load at 7.03
Purlins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Stan(it) End(ft)
BC 75 0.15 9.84
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads and reactions based on MWFRS.
Left bottom chord exposed to wind.
"WARNING" Please thoroughly review me'A.1 ROOF TRUSSES rSELLER'), GENERAL TERMS and CONDMONS CUSTOMER ('BUYER") ACKNOWLEDGMENT" farm.
-
Verifydesignpaameters and read notes on this Trusts Design Donnas (me) and the Antony T. Tombo Of. P.E.Referencs Sheet before use. Unhoo othervnse staled an the ADO. only Arpin
I
connector plates shall be used forthe TDD to the valid. As a Tmss Design Engineering (Ie. Specialty Engineer). Me seal on any Too represents an acceptance ad me professional en9irun
responsibility forms design of me single Tmss depicted on no TDD only, under Wt.l. The design assumptions, loading conditions, suitabidty and use of ma Tmss for any Burning is this
/- A-1 ROOF
/ --TRUSS
Building is the responsiblity arms cannot, meO.mers authorized agent or me Building Designer, in me contestant IRC, me IBC. local building seas and TPI-1.
Taappmvalofthe
or no 6 in me contest of me IRC. Me IBC,eranbuilding
Contractor. and
nootessettoouutin me Tooand
the paraccesane
Anthony T. Tombo ill, P.E.
sal home responsibility ofthe Building Dougher,
susaf Uel Truss. lonsng handling, storage, Installation and b2nt
t
Tmss
#80083
guidelines of the Building Component Safety information (SSCI)punamed by TPI and SBCA are references for summit guidance.. WiFldefinesmeresponsmllite Sndduaesofine
Designer.Truss Design Engineerana Tmss Manufacturer, unless othemse defined by a Contadogrees upon in wring byall pates involved. The Tmss Design Engineeris NOTme Buddir
g 4451 St. Lucie Blvd.
Desigmror Tms sotem Engineermanybuilding.
LnghtCnieMlTms-ManyT.TomWIll,P£PepMUMnaltltis tlDYmenthanY(arn\bprMTll�wiNM NawnMn perm%51moIMl Root Trusua-M1aryT. TomEOIII, P.E.
Fort Pierce, 34946
Job Truss Truss Type Qty Ply 11/12/2018 2812
•74190. J10G I MONO 1 1
Loading Criteria (psi
TCLL:
20.00
TCDL:
10.00
BCLL:
0.00
BCDL:
10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0 "
0
SEAT PLATE REQ SE TPIATEREp.
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk.Category: II
EXP: C Kid: NA
Mean Height: 15.00 it
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3:00 it
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Top chord 2x4 SP #2
Bot chord 2x6 SP 2400f-2.0E
Webs 2x4 SP#3
Special Loads
---(Lumber Dur.Fac =1.25 / Plate
Dur.Fac =1.25)
TC: From 60 pit at -1.00 to
60 pit at
7.06
TC: From 30 plf at 7.06 to
30 plf at
10.57
BC: From 20 plf at 0.00 to
20 plf at
7.06
BC: From 10 plf at 7.06 to
10 off at
10.57
BC: 1060 lb Cone. Load at 7.06
BC: 416 Ib Cone. Load at 9.06
Purlins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in cc) • Start(ft) End(ft)
BC 120 0.15 10.57
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads and reactions based on MWFRS.
Right end vertical not exposed to wind pressure.
Left bottom chord exposed to wind.
1OZ-14
TO.12
-`-2'--1.6.2-�
416o
10600
Cade / Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
Code: FBC 2017 RES
PP Deflection in loc L/deFl L/#
Gravity Non -Gravity
TPI Std: 2014
VERT(LL): -0.024 F 999 360
Lee R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Vanes b
WitrFi3nL): 0.044 F 999 240
B 886 /- /- /- 1507 /-
FTlRT:10(0)/10(10)
HORZ(LL): 0.010 D - -
G 1355 /- /- !- /804 /-
Plate Type(s):
HORZ(TL): 0.017 D - -
Wind reactions based on MWFRS
WAVE
Creep Factor: 2.0
B Brg Width = 7.6 Min Req = 1.5
Max TC CSI: 0.374
G Brg Width = 6.9 Min Req = 1.5
Bearings B & G are a rigid surface.
Max BC CSI: 0.944
Bearings B & G require a seat plate.
Max Web CSI: 0.825
Maximum Tap Chord Forces Per Ply (Ibs)
Wgt 63.0 Ibs
Chords Tens.Comp. Chords Tens. Comp.
VIEW Ver: 18.02.00.1016.21
A-B 27 -20 C-D 39 -53
B - C 924 -1495
Maximum Bot Chord Forces Per Ply (Ibs) -
Chords Tens -Comp. Chords Tens. Comp.
B-F 1269 -7T7 F-E 1238 -758
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Corl Webs Tens. Comp.
F-C 1193 -700 D-E 36 -49
C-E 914-1491
-WARMING- Please Moroughly review the -A-1 ROOF TRUSSES ('SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER ("BUYER) ACKNONALEDGMENr" form. -
Vedry design parameters and read notes on Ibis Tress Design Drawing(Too) and the AnNoWT. Tombo Ill. P.EReference sheet t timed had. Unless otfur,om slated on the MD, only Npin �
odoodor plates shall be used for the TDD to be wild. As a Tress Design Engineerbg ew (i.e. Specialty Engineer), Me seal on any TDD represents an acceptae of Me professional engineerin ,A.1 RDRP
mspotsibilityfor the design ofthe single Truss depicted on the Too only. under TPI-I.Thedesign assumptions, loading sanctions, suitabiLty and use of Nis Truss for any Building is Me 111TRUSNE5
Building is the responsibillly of To Owner. the Ownern oudommal agent or Ne Bustling Designer. in Me concert oftheIRC, Me IBC, local beading code and TPI-1. Theappmvalofthe •=mu�.m^
responsibility ofthe Owner,Me owners authorized agent orthe Building Designer. in Me curator ofthe[Be. Me IBC, local building code and! TPI-L The approval of Me TOD and any field Anthony. Tombo lll, P.E.
use of Me Tress, including handling, storage, installation and bracing shall be Me respmaibiliy of Me Building. Designer and Contracbr. All notes set Out in Me Too and the practices and
y
guidelines ofble Building Componentm safety lnfoabon(BSCI)pubashed byTPI exISBCAarereferenced forgeneralguidance. TPI-1 der es Merespansibili0esand duties of Me Tress #80083
Designer, Truss Design Engineer and Tress Manufaraureg unless otherwise defined by a Contrail agreed upon in wring by all parties involved. The Tress Design Engineer is NOT Me Buildir g 4451 St. Lucie Blvd.
Desgner or Truss System Eagineerof any building. Aa capita@ed terra are asdefined NTPI-1. Fort Pierce, FL 34946
fuoMoht®i018h1RmlTrvzsez-M1hom T. TarMeIII,P.E. Reprcdu1i-nal Nise-th.nlN anytann, b pMItordwtlwN M. vmtlen armhosim011 RoalTrms-Mfishi TamW III. RE
Job Truss Truss Type City Ply 11/12/2018 2872
74190 ' 1 J10P I MONO 10 1
Loading Criteria (par)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0"
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
12 0�ax4C
6 �
a
to=2X4(A1)
ua
B
A
F_
EG
SEAT PLATE RED.
Wind Criteria
Wind Sld: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Purlins,
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Stan(ft) End(ft)
BC 115 0.15 10.57
Apply pudins to any chords above or below fillers
at 24' OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Left bottom chord exposed to wind.
SEAT PIATE RED.
10'i
Code / Misc Criteria
Defil Criteria
♦ Maximum Reactions (Ibs)
Code: FBC 2017 RES
PP Deflection in loc Udell L/#
Gravity Non -Gravity
TPI Std: 2014
VERT(LL): 0.008 F 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.011 F 999 240
B 493 /- !- 1539 /195 /304
FT/RT:10(0)/10(10)
HORZ(LL):-0.004 F - -
G 413 /- /- 1467 1193 !-
Plate Type(s):
HCRZ(TL): 0.006 F - -
Wind reactions based on MWFRS
WAVE
Creep Factor: 2.0
B Brg Width = 7.6 Min Reg = 1.5
Max TCCSI: 0,424
G Brg Width =6.9 Min Req=1.5
Max BC CSI: 0.996
Bearings.B & G are a rigid surface.
Bearings B & G require a seat plate.
Max Web CSI: 0.310
Maximum Top Chord Forces Per Ply (Ibs)
Wgt: 56.0 Ibs
Chords Tens.Comp, Chords Tens. Comp.
VIEW Ver: 18.02.00-1016.21
A-B 27 0 C-D 41 -110
B - C 488 -520
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
B-F 469 -599 F-E 461 -591
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
F-C 416 -464 _D-E 165 -91
'
C - E 734 -573
^WARNING^ Please thoroughly review the -A-1 ROCF TRUSSES("SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMENT- fare.
Verify design parameters and mad notes on this Tons Design Dmiring(Mi and the Andua T. Tombo ill, P.E.Reference Sheet before use. Unless passivism stated on Me MD. only Npin 9
wnneslorpUteashaAbeusedfor Ne TDOtOWe 10. Asa fire.Design Engmeemy(i.e.Speculty Engineer), the seal on any TOD represents an acceptance or Pe professional engineerin /I MA.1 ROOF
responsibility for Me design of this single Trust depleted on the TDD only, under TPI-1.The deal assumption, loading wndilions. suitability and use of Nu Tmss for any Building is Me -JSTR11556
Building i5 the responsibility, often Diane. the Owners ashamed agent or Me Building Designer, in the pantexta the IRC, the IBC, local building pads and TPI-1. Theappmvaloferm •ru�u�•.a
hoppns2illty offle owner, Me Owners auNomed agent or the Building Designer. in 0e wntexlofthe Mo. Me IBC, loot building ease and TPI-1. The appraval of the TOD and any field Anthony T. TombD III, P.E.
use ofthe True, including handle , seems, installaron and bracing shall be Me resp risibility afthe Slowing Designer and Cormunter. All notes set out in Me MD and Me practices and
guidelines ofine Building Comwnent Safety lnfomallon(BSCI) published by Tint and SSCAare referenced par general guidance. TPI-1 defines the responsibililies and duties ofthe Truss #80083
Designs, Truss Design Engineer and Those Manufacturer, unless othendse earned by a Coupled agreed upon in writing by all pates involved. The Truss Design Engineer is NOT Pe Builifir g 4451 St. Lucie Blvd.
Designer or TussBRMm Engineer t any building. Allcapitalized letmsare asdefined in iPl-1.
.,.. ,., n c_ , T. TamWIII.P.EReorWugbn WNizdmmentnaeryMn.bpmNLtetivNhout Nevrtltlen pemtis9cnalA-1 RcolTrvuea-PnNanyT.Tgnbo ill; P.E Fort Pierce, FL 34946
Jab
Truss
Truss Type
Oty
Ply
11/12/2018 2765
74190 '
J2
EJAC
2
1
C
12
6
T
B o
=2X4(A1)
CV
57 A
D
SEAT PLATE REQ
GfC
r
Loading Criteria (psf?
Wind Criteria
Code / Misc Criteria
DeefIfCSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Sid: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in lob Udell U#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Std: 2014
VERT(LL): NA
Loc R+ / R- / Rh / Rw / U / RL
B 181 /- /- 1159 162 186
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCDL: 10.00
Risk Category: ll
FT/RT:10(0)/10(10)
HORZ(LL):-0.000 D - -
D 43 /- /- /23 P /-
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.001 D - -
C 53 /- /- 136 153 /-
Des Ld: 40.00
Mean Height: 15.00 it
WAVE
Creep Factor: 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0,111
B Big Width = 7.6 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0.052
D Big Width = 1.5 Min Req = -
Spacing: 24.0"
MWFRS Parallel Dist: 0 to h/2
C Big Width = 1.5 Min Req = -
C&C Dist a: 3.00 it
Max Web CSI: 0.000
Bearing B is a rigid surface..
Loc. from endwall: not in 4.50 it
Wgt: 11.2 lbs
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber A-B 27 0 B-C 24 -64
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Maximum Bot Chord Forces Per Ply (Ibs)
Purling Chords Tens.Comp.
In lieu of structural panels or rigid ceiling use pudins B - D 0 0
to laterally brace chords as follows:
Chord Spacirl oc) Stad(ft) End(ft)
BC 28 0.15 2.46
Apply purlins to any chords above or below fillers _
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
"V✓ARNING" Please thoroughly review Me 'AA ROOF TRUSSES ('SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER (-BUYER") ACKNOWLEDGMENT" form.
Verily design parameters and nail notes an this Tress Design Drawing (Too) and be Anthony T. Tomas III, RE Reference Sheet Lerore use. Unless o0mwise stated on tie TDO, only Alpin
se
.nneGorplatesshallbeusedbr Me TDDWb valid. As a Treas Design Engineering (i.e.Spedalty Engineer). Me seal on any Too represents an addeptance offhe professional engineerin
gA-r ROOF
�aTRl155F5
responsibility us ilityforMedesign of tie single Truss depined on tie TOD only, under TPI-1. The design assumptions, loading conditions, suitability and use of this Truss for any Building is Me
Building is Pe, responsibility of the Caem,the Dwae(a auNmlad agent or tie getting Designer, in tie meted of tie IRC, Me IBC. 1=1 building bode and TPI-1- Theappmvalofine
•��•�
rsspone liyafthe Owner. tie Owners authored agent or tie Building Designer. N the bartender the IRC, Me IBC, local building wile and TPIA. Theappmeralof Oe TDDandanyleld
AnthonyTombo Ill, P.E.
y
use of the Trusts, i,mludin9 healing, etmage,instated. and handing shal be Me responsbility of tie Building Designer and Contractor. All notessetouarn Oe TODand 0e p2tlices and
#80083
guidelines of 0e Sodding Component Safety lemeralltSSCI) published by TPI add SBCA are referenced for general Wearers. TPI-1 deMes Neresponsiblitiens and dubesoftes Tress
Designed Tmss Design Engineer and Tmss Manufacturer. Unless aMemisa defined by a Commol agreed upon in carting by all parties involved The Tmss Design Engineer is NOT tie Buithdin
g 4451 St. Lucie Blvd.
Designeror Trusssystem Engineerroam building. wpUl¢a te.s etaasdermain TPI-1.
CocoolMlfi A.1 Rwf Trvs[es-Mtho,ry T, Tomw IIIs,. P£ PepMUGm W tltia tlmment, F anyfa..ls prMibitM wmom never. Ix,misLcn of-4RMTtussa-MNarty T. TanEo III, PE.
Fort Pierce, FL 34946
Job Truss Truss Type Oty Ply 11/12r2018 2766
74190 J2A EJAC 2 1
12
6 F_ - C
Loading Criteria (psf)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0 "
.,
N
0
■f
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 fit
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 It
Loc. from endwall: not in 4.50It
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top chard 2x4 SP #2 But chord 2x4 SP #2
:Lt Slider 2x6 SP 92: BLOCK LENGTH = 1.500'
Purlins
In lieu of structural panels or rigid ceiling use puffins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(it) End(ft)
Sc 19 0.00 1.57
Apply puffins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
0
�-- 1'6"14 - - {
Code I Misc Criteria
Code: FBC 2017 RES
TPI Std: 2014
Rep Factors Used: Yes
FT1RT:10(0yI0(10)
Plate Type(s):
WAVE
••WARNING•• Please thameghly review Me 'A-1 ROOF TRUSSES ("SELLER').GENERAL
r.eil40sD)
a-ae atszh.le..MfoMTDDWWwid. AaTruesyEn9aavnaq((L.Spedafty
of Via
i
i
De0/CSI Criteria
PP Deflection in loc L/defl L/#
VERT(LL): NA
VERT(CL): NA
HORZ(LL):-0.001 B - -
HORZ(TL): 0.002 B - -
Creep Factor. 2.0
Max TC CSI: 0.084
Max BC CSI: 0.022
Max Web CSI: 0.003
Wgt: 9.8 Ibs
VIEW Ver: 18.02.00.1016.21
♦ Maximum Reactions (Ibs)
- Gravity Non -Gravity
Loc R+ / R- / Rh 1 Rw I U I RL
A 63 1- /- /37 /- 140
D 30 I- 1- 116 1- 1-
C 47 /- 1- 139 154 /-
Wind reactions based on MWFRS
A Big Width = - Min Req = -
D Big Width =1.5 Min Req =-
C Erg Width = 1.5 Min Req = -
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Ccmp. Chords Tens. Comp.
A-B 53 -114 B-C 23 -58
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
A-D 2 -2
CONDITIONS CUSTOMER (-SHYER') ACKNOWLEDGMENT" form.
e(erenm Sneet before use. Unless otherwise stated ea Me MD. only Ali
seal is on any TDD represent an acceptanof tha professional ergineen
lion conditionsswtabieN and use of e1b Truss for any 801ding 0 the
ndanoe. TPI-1 del the rezpn,leoNesam ouues arurei
by ell pares, inwNed. Tre Tress Design Enyaaw is NOT the
1
�A-1 RDDF
`�TR1155E5
Anthony T.Tombo Ill, P.E.
# 80083
4451 St. Lude Blvd.
Fort Pierce, FL 34946.
Job
Truss
Truss Type
City
Ply
11/12/2018 2767
'74190 '
J5
EJAC
4
1
C
T
12
6
n
uD
(V (h
2X4(A1)B
l�
57 A
D
SEAT PLATE REQ.
Loading Criteria (psf)
Wind Criteria
Code / Misc Criteria.
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Sld: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc L/defl L/#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Std: 2014
VERT(LL): NA
Loc R+ / R- / Rh / Ray / U- / RL
B 274 /- /- 1218 181 /154
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCDL: 10.00
Risk Category: ll
FT/RT:10(0)/l0(10)
HORZ(LL):-0.005 D - -
D 92 /- /- /52 /- /-
EXP: C Kzt NA
Plate Type(s):
HORZ(TL): 0.008 D - -
C 130 /- /- 197 /119 /-
Des Ld: 40.00
Mean Height: 15.00 it
WAVE
Creep Factor: 2,0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI; 0.470
B Brg Width = 7.6 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max BC C51: 0.262
D Brg Width = 1.5 Min Req = -
Spacing: 24.0 "
MWFRS Parallel Dist:0 to h/2
C Brg Width is 1.5 Min Req = -
C&C Dist a: 3.00 it
Max Web CSI: 0.000
Bearing B is a rigid surface.
Loc. from endwall: not in 4.50 it
Wgt: 16.8 Ibs
Bearing B requires a seat plate.
GCpi: 0.18
1
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber A-B 27 0 B-C 58 -134
Top chord 2x4 SP #2
Bat chord 2x4 SP #2
Maximum Bat Chord Forces Per Ply (Ibs)
Puffins Chords Tens.Comp.
In lieu of structural panels or rigid ceiling use pu ling, B - D 0 0
to laterally brace chords as follows:
Chord Spacing(in oc) Stad,(ft) End(ft) -
BC 58 0.15 5.00
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design. -
"WARNING- Please thoroughly review tMeW1 ROOF TRUSSES CSELLER'), GENERAL TERMS and CONDITIONS CUSTOMER CBUYEW) ACKNOWLEDGMENT' f.ml.
Very design parameters and read notes on the Truss Design Draen,(TOD) and th Anthotry T. Turtles Ill, P.EReference Sheet before use. Unless otherwise slated on the TOO ,ony Alpin
�
nnedorpOtsshallbeusedWNe TDDtobevalid. Asa Truss DesignEngineerig(i.e. Sbreany Engineer), Me seal on any Too represents an accordance of Peprofessimul engineer'
is
Aq ROUF
��TNf155E5
respresibilityforthedesgn of Me single Truss depicted onthe TDDony, undarTPIA.The design assumptions, loadmgcontithol suilabMiNand useof Nis Tmssforany Building Ma
Building is the maponsitaity of me oxoer, the Goners authorized agent or me Building Designer, MeeimaNdef the IRC, the IBC, local building rode and WI-1. Theapprovalofthis
respdnsibilityofth. Onner, the Owne(s auNorized agi Me Building Designer, in Me contest of Me IRC, Me IBC, local building rude and WI-1. The approval.( Me TOO and any field
Anthony. Tombo III, P.E.
y
use of Me Truss, including handling,storage. instartitionand timing shall be Me responsibility of the Building Designer and Contractor. Alnotessetmdin Ne TDcandthepradwsand
#80083
guidelines of the Building Component Safety information (BSCI) published by TPI and SBCA are referenbed for general guidance. TPI-1 defines theresponsibilities and dutiesofthe Truss
Designer,Truss Design Engineer and Truss ManufaeWre6 unless othereds, defined by a Confined agreed upon In wilting by all pates involved. The Truss Design Engineer is NOT the Smith
4451 St. Lucie Blvd.
Designer or Tress S=rn Engineers any building. M osaistiaa l terme areareaeed in TPI-1.
Cnpynght 02016 FI R.Nnvnes-Mlh.1T.Tom su. PE Rep,cEuctim ofiNsdcamentheny twm. is pmhi.RedwiNou NexXtten Irt,missi.nWA-1 Rcof Tnm.s-MtMny T.T—billl.P.E
Fort Pierce, FL 34946
Job •
Truss
Truss Type
Qty
Ply
11/12/2018
2768
'74190 '
J6
EJAC
14
1
C .
12
6
of
io
i�
2X4(A1) B
T
57
A
D
SEAT PLATE REQ.
Loading Criteria (psf)
Wind Criteria
Cade / Misc Criteria
De11/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code:FBC 2017 RES
PP Deflection in loc L/de0 L1#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI SID: 2014
VERT(LL): NA
Loc R+ / R- / Rh / Rw / U I RL
B 297 /- !- /233 140 1123
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCDL' 10.00
Risk Category: II
FT/RT:10(0)/10(10)
HORZ(LL): 0.006 D - -
D 104 /- !- 159 /- /-
EXP: C Kzt NA
Plate Type(s):
HORZ(TL): 0.012 D - -
C 148 !- !- /110 190 /-
Des Ld: 40.00
Mean Height 15.00 ft
WAVE
Creep Factor. 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL 5.0 psf
Max TC CSI: 0.3
g Brg Width = 7.6 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
D Brg Width = 1.5 Min Req = -
Spacing: 24.0'
MWFRS Parallel Dist: IT to 2h
.333
Max BC CSI: 033
C Brg Width = 1.5 Min Req = -
C&C Dist a: 3.00 it
Max Web CSI: 0.000
Bearing B is a rigid surface.
Loc. from endwall: not in 9.00 It
Wgt: 19.6 Ibs
Bearing a requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber
A-B 27 0 e-C 66 -146
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
- Maximum Bo[ Chord Farces Per Ply (Ibs)
Puffins Chords Tens.Comp.
In lieu of structural panels or rigid ceiling use puriins B - D 0 0
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 66 0.15 5.60
Apply pudins to any chords above or below fillers
at 24' OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
—WARNING— Please thomugnly review the'A-t ROOF TRUSSES('SELLEW). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER-) ACMOWLEDGMF.Nr` farm.
Verity design parameters and mad notes on Nis Time Design Drawing (TDO) and vie MlM1ony T. Tombs III, P.E Reference Sheet beam use. Unless olbenwise stated on Ne TOD, mtly Alpin
mureaorpmesshaAbausedfortie TDDfobevalid. AS a Time Design Enginesso,a.e.Spedalry Engineery. vie seal an any TOD mpreseMs se aecepta s, of Ne profess iomle�ineenin
//. A-r ROOF
nopeaviVity far Na dmignafthe single Time depicted on me TOO only, under TPI-1. The design asswnptiana, loading 000diuons, sombllity aM use of this Tmss foreny..BUJtlinghNe
/ oTRu55r3
of endlat
or Never.
Ne Owner,Nebsdgigot
eupGna Nere,.c,o.,
in re coriaer,Ni.IRC.ert
aranedagenl
asnd TR-1. no.p,ami the Too
C.1.1 adeCseas
on �
uadtiane eta w�be9 in re
Anthony T80083 ill, P.E.
tea°=afnN�e�r lrataunga ,stama9ne. mstandaume oruee oey�eara�a�
5M..pNT0a. t�nepaOfM.T
#.Luca
of vie sMd by TPlaMSaCAaret ldada duties Tmss
for generalguiyan¢. TPNdved. NeTime
Tafelyarmlame, aess
DesigienaM
esigngng..end
Doodefes OTT
sensedu
oesigic, T. Design rsglneer aria Tram MarsalamapitimessaucmasilenedbTPI-1. Contract sensed ewnmwntwg In all nantiea vweleed. no Time Design Enyneob NOTNe anaa
o
4451 St. Lucie Blvd.
Desgnerar Tnas Syslom nms- otam• .Tosco. M rep:uraea temp areazdefapd loTPbt. -
Wjy,•yv030feM RbxT�n-MVVFly T.TmJn II.PE Repodu,Ybndatlfamnmti,ayfmn.6p�WMedWoaOvwrlen pemdssun W/•-1RwfTri¢xs-MYany T. Tani0o 111, p.E
Fort Pieree, FL 34M
Job
Truss
Truss Type
Qty
Ply
11/12/2018 2769
74190
J7
EJAC
18
1
G
12
p
6UD
n
Vs in
r
2X4(A1) B
T
1 A PA
D
SEAT PLATE REQ.
1, l — 7-
Loading Criteria (ps0
Wind Criteria
Code I Misc Criteria
Def#CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in too L/defi L/#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Sid: 2014
VERT(LL): NA
Loc R+ / R- / Rh / Rw / U / RL
B 352 /- !- /270 /99 208
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCDL: 10.00
Risk Category: ll
FTIRT:10(0)/10(10)
HORZ(LL): 0.013 D - -
D 130 /- /- 176 /- /-
EXP: C Kzb NA
Plate Type(s):
HORZ(TL): 0.025 D - -
C 187 !- /- 1141 1167 /-
Des Ld: 40.00
Mean Height: 15.00 it
WAVE
Creep Factor. 2.0
Wind reactions based an MWFRS
NCBCLL: 10.00
TCDL: 5.0 pat
Max TC CSI: 0.5
B Big Width = 7.6 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Maz BC CSI: 026
D Brg Width =1.5 Min Req = -
Spacing: 24.0'
MWFRS Parallel Dist: h/2 to h
.526
C Brg Width = 1.5 Min Req = -
C&C Dist a: 3.00 it
Max Web CSI: 0.000
Bearing B is a rigid surface.
Loc. from endwall: not in 4.50 it
Wgt: 23.8 lbs
Bearing B requires a seat plate.
-
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber A-B 27 0 B-C 84 -169
Top chord 2x4 SP 92
Bat chord 2x4 SP #2
Maximum Bot Chord Forces Per Ply (Ibs)
Purling Chords Tens.Comp.
In lieu of structural panels or rigid ceiling use purring B - D 0 0
to laterally brace chords as follows: _
Chord Spacing(In oc) Start(ft) End(ft)
BC 75 0.15 7.00
Apply puffins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
-WARNING- Please thoroughly review Me -A-1 ROOF TRUSSES(-BELLEW). GENERAL TERMS and CONDITIONS CUSTOMER CBUYEW) ACKNOWLEDGMENT' form.
A
Venfy design paremoters and read notes on N¢ Truss Design Drawing (TDD) and tho Anthony T. Tonto III, P.E. Reference Sheet before use. Unless oNemia8 staled on Me TDD, only Alpin
mrmegar pUtes sba0 be uaetl ror Me TODrobe valid. Asa Truss Design Engineenng(Le- Specialty Enlneer),Ne seal on any Too represents an acceplanto of gee professioinI gineenn
q-rTR 9pE5
responslDJl'ryfortfia design 01 Ne single Tnist CepidMm Ne TDD oNy, under TPl-t.TM1a tlesign assumptions, boding auMe18C suila use al N6 Truss forany BWtllnl tthe
MaaM
BurPuIg LS Ills responsSmry of Ne Owner, the Owln(s autMdzadagenlor Na Bulltlug Designer, in MocmlextollAa IRC, NOIBC.IaelNdding cWeaM TP41. TheaDDm al oltba
•aam.�w.v
respms3igry of Ne _.,theOwnofa augm'¢id agemmgle Bodd irg Devgno,, in Memntextof thelRC, the1BC,bpIWWug node alW TP41. Theapproval of Ne TDD aM any fietl
Anthony T. TOmbo ill, P.E.
use oltln Trust, indudhg handGlg, sbmge, iratNladon aM brachg star Ee tin resppnvbiGry of Ne Buitl'ug Designer antl ConVactar. M notes set Min Un TDD aM the prarLas antl
Trvu
#80083
guide esaressBuutl_Compwrant gafery lydolmagon(aS,)pubfislletl byTPIand'a--retererced forgerrral guidanm. TPFl eeraat ma resprnsibgities am nudes oftna
Desgner,T_Design ErghleeraM Try Maadesioer. uNsss othemise aeNndM a--..9reetl upon in wnNg by aO paNes mrtivN. ThaTreat Des6pl Ergineu is NOT the Bu'
44$1 St. Lucie Blvd.
oai�erm rhea syala,n Ellgneer famsanhhg. Ab vash.discos xe asdeN dnTPI.1.
Gpy,gNOMlleAIRMTrvvws—Mllmy T. T.0 PE RHvodtlYn of abdassm. tons.¢qr/Abdu�wnllewiam remains ntA-t PmfTwsm—M�dnry T. TmnM nl,PE
Fort Pierce. FL 34946
Jab
Truss
Truss Type
City
Ply
11/12/2018 2770
74190
J7C
EJAC
4
1
D
12
T
I
6p
fV
v
C
=2X4(A1)B
E
GF
SEAT PLATE REQ.
--1'—f-2'1°104'10°6 j
T I
Loading Criteria (ps0
Wind Criteria
Code I Misc Criteria
De0/CSI Criteria -
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Std: ASCE 7-10
Code:FBC 2017 RES
PP Deflection in lot Udell U#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Std: 2014
VERT(I-Q: 0.120 F 687 360
LOC R+ / R- / Rh / Rw if U 1 RL
B 352 !- !- /270 199 /208
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.232 F 354 240
BCDL: %00
Risk Category: ll
FT/RT:10(0y10(10)
HORZ(LL): -0.054 G - -
E 123 /- /- f75 /- /-
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.104 G - -
D 187 /- A 1142 /162 P
Des Ld: 40.00
Mean Height: 15.00 it
WAVE
Creep Factor: 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0,4
B Brg Width = 7.6 Min Req = 1.5
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0.472 72
E Big Width = 1.5 Min Req = -
Spacing: 24.0 °
MWFRS Parallel Dist: hf2 to h
D Brg Width = 1.5 Min Req = -
CSC Dist a: 3.00 ft
Max Web CSI: 0.270
Bearing B is a rigid surface.
Loc. from endwall: not in 4.50 If
Wgt: 28.0 Ibs
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
1
1 VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber
A-e 27 0 C-C, 84 -161
Tap chord 2x4 SP#2
B-C 0 -217
Sot chard 2x4 SP 92
1
Webs 2x4 SP #3
Maximum Sot Chard Forces Per Ply (Ibs)
Plating Notes
Chords Tens.Comp. Chords Tens. Comp.
All plates are 1.5X4 except as noted.
B - F 98 -146 G - E 0 0
C-G 144 -82
Pudins
In lieu of structural panels or rigid ceiling use pudins
Maximum Web Forces Per Ply (Ibs)
to laterally brace chords as follows:
Webs Tens.Comp.
Chord Spacing(in oc) Start(ft) End(fl)
BC 24 0.15 1.99
G-F 45 -20
BC 68 1.99 7.00
Apply puffins to any chords above or below fillers
at 24° OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
-
member design.
—WARNING" Please Blornal review Me 'AI ROOF TRUSSESrSEl-EW), GENERAL TERMS and CONDITIONS CUSTOMER (BUYER') ACKNOWLEDGMEM' form.
A
Venly design pararrelersand read rtaa3 w bb Truss (Nesgn Draxilg (TOD) and do AaMmy T. T. W Ill, P.E Roferenm 5te0tbebre ase. Unless oNemise statetl on Me TDD, aNy Alryn
cervagon platos stag be used for pie TODto be ralN. Asa Truss Design Engmeerug(he.Speoalty Eg r),dle wonany TDDmmre nnana=ptarceof Neprofes lmgineervi
A-1 ROOF
�TR11556
pons3ility forNe design of Ne single Truss aleplpM on the TOD Wy, undo TPl-1.TM Design assumptions, bating mndidere, witaEDlyaM use of ptc Truss loraM Buffing is pie
Busdmg'¢Me respgnsb'diy o/1he Owner, lAe Gwa0r9 authored agenton Ne Bualdug Oesigner,bMe conteatWNeIRC. tla IBC. brat hurtling cetle and TPN.
Theappmvaloftfle
respansgaliryol Ne Owner, the Ovmeh autlwizea agent ar Na Bwid'mg pevgner,bNe mn[ertMbelRC, tiro IBC.locelbuddbg coaleaM TPI-1. Tbeappmvolof
Me TDDaManyfield
Anthony. Tombo 111, P.E.
y
use oftM Tmss,'uxlWing laMling, atonge. insanauon aM Crating stall be ttw rezpons3Lty of lne aWd'ug DazgneraM ContraCor. mmtessetmtinlhe TDDaMthepract .nd
of the Belong component Safety intentional (MCI) published by not and SSCAam referenced forgerarsl guidance. TPI-ldefiMe MemsponsibRibesanddW4 ofine Truss
#80083
guide0nes
Designer, Truss Design Engineer anal Truss Manufacbrer, uNess obrervdse defined by a CattraG agreed upon in wriCng by all patges LrvoNal The Tress Deslgn Engineer m NOT the Etillifil
g 4451 St. Lucie Blvd.
De9gneror TmssSystem Enyneerofan,bwlding. Mcepitagzed lermsare as defuced'm TPFt.
Lo. y�kjM02010A1 RoorT�ussei-MNOIry T. Tmnh�Ilt P.E RepWin4n WNaEmnet6banYf�^.sP^+NT�1rd`�nRntlawn0en{e�MssbnNA�l Roof TUSan-N�arny T. Tvnbo ill, P.E
Fort Pleme, FL 34946
Job
TTUSS
Truss Type
Qty
Ply
11/1212018 2771
*74190 '
RE
EJAC
5
1
C
12
6
r
N (7
C
=2X4(A1) B
57
1 A
D
SEAT PLATE REQ.
1, l T
Loading Criteria (ps0
Wind Criteria
Code / Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Sid: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udefl L 10
Gravity Non-Gmvity
TCDL: 10.00
Speed: 160 mph
TPI Std: 2014
VERT(LQ: NA
Loc R+ / R- f Rh / Rw / U / RL
B 352 /- /-. 1385 /144 1150
SCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCDL: 10.00
Risk Category: II
FT/RT:10(0)/10(10)
HORZ(LL): 0.016 D - -
D 130 /- I- /217 1116 f-
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.025 D - -
C 187 /- - /- /150 1109 /-
Des Ld: 40.00
Mean Height: 15.00 It
WAVE
Creep Faclor: 2.D
Wind reactions based on MWFRS
NCBCLL: 10.00-TCDL:
5.0 psf
Max TC CSI: 0.779
B g Width = 8.0 Min Req = 1.5
Bi
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0.793
D Big Width = 1.5 Min Req = -
Spacing: 24.0"
MWFRS Parallel Dist: h to 2h
C Brig Width = 1.5 Min Req = -
C8C Dist a: 3.00 It
Max Web CSI: 0.000
Bearing B is a rigid surface.
Loc. from endwall: not in 9.00 ft
Wgt: 23.8 Ibs
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver. 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber A-B 27 0 8-C 84 -185
Top chord 2x4 SP #2
Sot chord 2x4 SP #2 Maximum Bot Chord Farces Per Ply (Ibs)
Purlins Chords Tens.Comp.
In lieu of structural panels or rigid ceiling use purling B - D 0 0
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 75 0.15 7.00
Apply pudins to any chords above or below fillers
at 24" OC unless shown Othelwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Left bottom chord exposed to wind.
—WARNING— Please Namughly review Ne'A-I ROOF TRUSSES('SELLER"). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMENT" roan.
vent' design parameters and mad nags on P¢ Truss Design crown, (TDD) and the Anthony T. Tombo U. P.E Relerenco BM1ee! before osa. Unless otherwise staletl on Ne iDD. anty Alpi
/
coiumaor plates shad be used Tor the Too b to, valid. As a Truss Design Engineer g g.e. Specialty Eglneen, the seal an any Too represents an acceptance or the professional angineenn
respanaid0y fonts designof Me single Truss depiaetl on the Too Only. under TPI-1. The de4gn assumptions. kal conditions. sulabi0y and use of rNs Truss tar any Beltleg title
`aA-1 ROOF
1111TRUNNES
Bmitl'ugblM1e responsgx'Igy O/Ne Owner, the owrers audMzed agantor the Bugd'ug pesigner,eNe melt o/the lRC, meIBC.locolbwtlitg code artl TPpt. maappmmd of Na
•.uw�o
responvTiGyaf Ne O.met,tlre Ovmeh auNtttrcd agentwNe Bwldirg Designer,mNe wnlert Of Ne IRC, the IBL,IouI WOSitg cotle and TPN. Theeppmval Ol the lDD and anY field
Anthony. Tombo ill, P.E.
y
useer Ne Truss.Inclug luM .tt bmpubll lemerespa lbe
OuM+g Desigmir
# 0083
By ammtl MDO dOpoisT
fely.inaalwnaM WOntract-Idemless.mp rmss
guidelines of tie BuiHug COmlaanant 0arey lnfomatlOn (BSCI) pubGsfetl bye m bOaC are reagre u Tor inrea gaNan p TPI-1 tler ueTnaa CebuNaa am awes NOT
oesyner rTma Deign Etginee ver.mdessemsemb der aMaeormaaagreea upanmwnnrtg by au pamas mvanad metros, cesyn Ergnaer is Nor me ewd'
Thor Mes.
. Lucie
g451 SLLude Blvd.
.f All
Dezigmrarmsa system etgmeer ranymaTcag. Ao vPimraea mnm as as aao-ea r, rnl-1.
C�y�l9at0 Af0 M RbY Teaxa-PmhmyT. TmnCo N. P£ nepoewfMMN9awuwmtinamtan^.b paaaledvWORaewnEm Ivmsa'malMt PM Trvssea-ammyT. Tanm IR P.E
Fort Piercee, FL 34946
Job
Truss
Truss Type
Dry
Ply
111121211111 2772
74190
J7P
EJAC
2
1
C
12
6p
57
42X4(Al)
1 F
D
SEAT PLATE RED.
Loading Criteria (psf)
Wind Criteria
Code I Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
TCLL: 20.00
Wind Sid: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udefi U#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Std: 2014
VERT(LL): NA
Loc R+ / R- / Rh / Rw I U I RL
B 352 /- /- /385 1144 208
BCLU 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): NA
BCDL 10.00
Risk Category: II
FT/RT:10(0y10(10)
HORZ(LL): 0.016 D - -
D 130 !- A 1217 1116 /-
EXP: C Kzt NA
Plate Type(s):
HORZ(TL): 0.025 D - -
C 187 /- A 1150 1164 1-
Des Ld: 40.00
Mean Height 15.00 ft
WAVE
Creep Factor. 2.0
Wind reactions based on MWFRS
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.7
B Big Width = 7.6 Min Req = 1.6
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0.793
D Brg Width = 1.5 Min Req = -
Spacing: 24.0'
MWFRS Parallel Dist: 0 to h/2
C Big Width =1.5 Min Req = -
C&C Dist a: 3.00 ft
Max Web CSI: 0.000
Bearing B is a rigid surface.
Loc. from endwall: not in 4.50 it
Wgt: 23.81bs
Bearing B requires a seat plate.
GCpi: 0.18
Maximum Top Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21 1
Chords Tens.Comp. Chords Tens. Comp.
Lumber A-B 27 0 B-C 84 -185
Top chord 2x4 SP #2
Bot chord 2x4 SP #2'
Maximum Bot Chord Forces Per Ply (Ibs)
Puffins Chords Tens.Comp.
In lieu of structural panels or rigid ceiling use puffins B - D 0 0
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft) -
BC 75 - 0.15 7.00
Apply puffins to any chords above or below fillers
at 24' OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Left bottom chord exposed to wind.
-WARNING' Please thoroughly review tbe'A-1 ROOF TRUSSES[SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER('BUYER°) ACKNOWLEDGMENT' Icrm.
Verify design parameters and read holes an this Truss Design Drawing (TOO)and the An" T. Tombo ill, P.ERefemnw Sheetb muw.UNessobemwsbtedon Oe TOD, Doty Arpin
Cormectpr pbee ebegbe usM fprthe TDDtebe valid. Asa Trade Design Engineering (i.e. Specialty Eng'vrea).the seal on any MD represent an acceptance of ba pmessimul ergineerb�
A-1 ROOF
respms3itiyforthe design of the single Truss depicted an the TOD my.under TPH. The design asnmgdons. Ioa2ng conditions, suibbBy and use of this Truss forany adding is the
1910WOTRUSSEN
Bmldug tithe respansbilily of the Owner, the Owrela auNazed agenlor the Buidvg Designer.btln oentedof Ne lRC, theIBC.Ipcol buJONg cotleeM lDH1. Tba aDPmral oltha
.,,®�+�
r¢sponsibitih of the Owner, the Ownels auduabedagenl of Na Baidi119 Designer,n Ue ranted of the lRC, theIBC, kxal buiYlvg cotleaM TPI-1. The approval of the TDD and anyfieJtl
Anthony. Tombo ill, P.E.
y
t the T.. iromitg llandf,y, sWma. boababosi brimin, Ybe the mi,onsibifycifereB.3ifigDesigneraM COM2Ga.M roed Is selwthe MD and the pta lias and
#80083
guiderves of ba Bwb'n, Componam Safely lnformatgn(BSCQ pubcomed by TPl and SBCAara referenced for general guicianco. TPptdetmestl mspmbdtmanddu dee Truss
,mourner. Tons Design E,..M TnrSManWarNrer,nrmssothemisa signed by a Conbactagreed upon in wring by au parties anoved. The Truss Design Egineu¢ NOT the Budd
4451 St. Lucie Blvd.
DesIp urTruas S,sxm Ergmeerofarybmlding. Ae mpibreM terra areas aermeam TPl-l.
C�gNOalteAl RmlTrmu—MVvny T.Tonilaln.P£RNWvlim WPh hamnLhvryrum,bpMaCVIrNVIIVbwinOm pennixffi,WA1 PmfTwave—NdmyT.TanEh al. P.E.FOIE
Pierce, FL 34946
Job Truss Truss Type Ory Ply 11/12/2018
'74190 PB01 COMN 1 1 2n3
Loading Criteria (ps()
Wind Criteria
TCLL: 20.00
Wind Std: ASCE 7-10
TCDL: 10.00
Speed: 160 mph
BCLL: 0.00
Enclosure: Closed
BCDL: 10.00
Risk Category: II
EXP: C Kzt: NA
Des Ld: 40.00
Mean Height: 15.00 it
NCBCLL: 0.00
TCDL: 5.0 psf
Load Duration: 1.25
BCDL: 2.0 psf
Spacing: 24.0
MWFRS Parallel Dist: It to 2h
C&C Dist a: 3.00 it
Loc. from endwall: not in 9.00 R
GCpi: 0.18
Wind Duration: 1.60
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Plating Notes
All plates are 2X4(At) except as noted.
Purlins
In lieu of structural panels or rigid ceiling use purling
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 1.03 2.36
BC 37 0.15 3.25
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading
Design Dead Loads based on material weight
adjusted for slope: BC: 8.00 PSF
Wind
Wind loads based on MWFRS with additional C&C
member design.
12
6 SS F4 �3Uzl
B CC E
A — — — — — — — F
,1- 11"1 -t 3'4"12 11"1 'A
1 4,3"13
Code / Misc Criteria
Code: FBC 2017 RES
TPI Std: 2014
Rep Factors Used: Yes
FT/RT:10(Oy10(10)
Plate Type(s):
WAVE
62"14
Defl/CSI Criteria
PP Deflection in roc Udell
L/#
VERT(LL): 0.001 D 999
360
VERT(CL): 0.001 D 999
240
HORZ(LL): 0.000 -
-
HORZ(TL): 0.001 -
-
Creep Factor. 2.0
Max TC CSI: 0.033
Max BC CSI: 0.052
Max Web CSI:, 0.000
Wgt: 16.8 Ibs
VIEW Ver: 18.02.00.1016.21
T
1
♦Maximum Reactions (Ibs), or'=PLF
Gravity Non -Gravity
Loc R+ / R- / Rh / Rw / U / RL
A 21 !- A
/12 /13 132
B• 98 /- !-
151 /30 A
F 21 /- A
/9 /10 !-
Wind reactions based on MWFRS
A Brg Width = 7.3
Min Req = 1.5
B Brg Width = 40.7
Min Req = -
F Brg Width = 7.3
Min Req = 1.5
Bearings A, B, & F are a rigid surface.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
Chords Tens. Comp.
A-B 38 -34
D-E 195 -136
B-C 195 -136
E-F 18 -9
C -1 185 -116
Maximum Bat Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
B-E 116 -96
-WARNING- Please Noreugllly review tire-A-1ROOF TRUSSESCSELIEW), GENERAL TERMS and CONDITIONS CUSTOMER (-BUYER") ACIWOWLEDGMENT• form.
A
verify design parameters and read nose on Nis Toss Design Drawing(Too)and floe sai T. Tonto lll, P.E. Refereneo Sbeelbefore use. Unless onemse statadondbo TDD, call
-a
wrNe pNtessllaflW. dfo Ne TDDto We id. Asa Trvss Desgn Engineervg(ie. Spetially Engineer), No seal on any TDO represenb ane¢aplanw e(Ne pro(esslonal engineerin
A-r ROOF
responaftsIityfm Nedesgnof Ne aingNToss depicted oriel¢TDD only, under TPYl.The design assumption,knongondiYons, suiNbiOtyand useVN5Truss erany SuildingbNe
aTRU55E5
Buildingsure resporslbAlyot Ne Ownerthe Ownefs autnexasidagentor Ne Building Designer. NNe contenol Ne IRC, ds IBC, local buildingcodeand TPl-1, Theappovalafdle
respof Nors.a Own Ne IBC, local aMTPN.TheappovalDNe TDDeMdeea.d
agenand Ne Build mg Oeslgner,m Neantatthe
Anthony. Tombo 111, P.E.
y
handli.metsaungr¢ed B1RC,
Connecode
of the Truss, indudNg aroWnent Salary oanationantlI) Nbsbad be Ne read WCAtyarafiencedg Designer antlence. o.Anroresset oathNeTOD and Nepractices antl
usst the
guitleGnesof floe Builoing Component Safey lNomadon(BSCQ pubpsRM by TPl and SBCAare referexMla general guidanw. TP4l tlefuws Ne resposibdAes antl duties D(Ne Truss
#80083
Designer. Truss oesigtl Engineer antl Toss ManufacWrer, wtless dMrvrise defulMgaContratl agreed upon in writing Ey aA paNes invaNed. lTaTruss DeskJn Ergineer is NOT Ne BUJG
4451 St. Lucie Blvd.
Designeror, Toss System Elghaer far,bWcir , AlIezptaf¢ed IvmtlareasdefeadhWi-I.
FL 34946
CrypgMBMteLl acq Tnime-NVIany T, TtmMIII,P£RepMu[Ua,af Nisdmmem,Inary M1rm.tPtluLIMMNwn mewrgmpermavnarFl PmfTnwe�-PrvMny T. TvnEonl, P.E
Fort Pierce,
Job Truss Truss Type - Cry I Ply 11/12/2018
74190 ' PB02 I COMN 2 1 2774
Loading Criteria Unit)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 0.00
Load Duration: 1.25
Spacing: 24.0"
Lumber
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
2'7"7 2'7"7
12
6 C=3X4
T B p T
r 11"1 34"12
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 it
TCDL: 5.0 psf
BCDL: 2.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 it
GCpi: 0.18
Wind Duration: 1.60
Plating Notes
All plates are 2X4(A1) except as noted.
Purling
In lieu of structural panels or rigid ceiling use puffins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(fl) End(ft)
BC 37 0.15 3.25
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading
Design Dead Loads based on material weight
adjusted for slope: BC: 8.00 PSF
Wind
Wind loads based on MWFRS with additional C&C
member design.
1 4'3"13
Code I Miss Criteria
Code: FBC 2017 RES
TPI Std: 2014
Rep Factors Used: Yes
FT/RT:10(0)/10(10)
Plate Type(s):
WAVE
5'2"14
Defi/CSI Criteria
PP Deflection in roc Udell U#
VERT(LL): 0.001 999 360
VERT(CL): 0.001 999 240
HORZ(LL): 0.000 - -
HORZ(TL): 0.000 - -
Creep Factor: 2.0
Max TC CSI: 0.027
Max BC CSI: 0.045
Max Web CSI: 0.000
Wgt: 14.0 Ins
VIEW Ven 18.02.00.1016.21
♦ Maximum Reactions (Ibs), or ".=PLF
Gravity
Non -Gravity
Loc R+ / R- / Rh
/ Rw / U / RL
A 11 /- /-
/17 119 145
B' 92 /- /-
154 147 /-
E 11' /- /-
/7 113 /-
Wind reactions based on
MWFRS
A Big Width = 7.3
Min Rep = 1.5
B Big Width = 40.8
Min Req = -
E Big Width = 7.3
Min Req = 1.5
Bearings A, B, & E are a
rigid surface.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
Chords Tens. Comp.
A-B 53 -48
C-D 149 -110
B-C 149 -110
D-E 16 -5
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
B - D 87 -42
-'APARNING^ Please thoroughly review Me-A-1ROOF TRUSSES("SELLER"), GENERAL TERMSand CONDITIONS CUSTOMER ('BUYER") ACKNOWLEDGMENT" forth.
Veidy design parameters and read name on this Truss Design Omdng (MO) and the Anthony T. Tombs ill, P.E. Reference Shadit Mom use. Unless othenvlse stated on Ne TDD, only Nunn
tiomneda plates shau be used for Ne TDD M be valid A i a Truss Design Engineering (i.e. Specialty Engineee, Me seal on any TDD represents an acceptance of the professional engineeri
aA-d ROOF
responsibility for Me design of Me single Truss depided on Me TDD only, under TPl-1.The design assumptions, leading minorities, suitability and use of this Truss for any Boding is the
"'TRIARE5
Building is the responsibility of the Qvneq Me Owner`s authm¢ed agent drum Building Designer. in Me mrsextofthe IRC, the IBC, local building cads and TP1-1. Theapprovaloftheros
building and
to banteA titne Ne
mnad
Anthony T. Tombo Ill, P.E,
braonlg shallDesigner.
use ofthsT Truss. indat ucing handling, stoage,nstillazed
responsiblity ofBuilding Desgnerraand contractor. Ninolessetmtm TODandN pmdlcesand
Truss
#80083
guidelinesof lee Building Component Safety lnfurration(BSCl) pub fined by TPl and SBOA are rebalanced for general guidance. TPI-1 defines Me maparroullities and does of the
Designer, Tress Design Engineer and Truss Manufacturer, unless oNerwise defined by a Comma agreed upon inwriing by all parties involved. TheTmssD¢siwEngineerisNOTIeBuildirg
4451 St. Lucie Blvd.
DesignerorTmss System Engineerofanybuilding. Allcaplisideotermsadeastlefnedin TPl-1.
CapyngN0al16>1 RwfTosses-Ma T.Tomh,111,P.E RepmauNon of tisdwument Otarryrmn.hpMtiteEwtNml Newntls penNssimaMlnwtTvssee-PrMa"y T.TmoolII.P.E.
Fort Pierce, FL 34946
Job Truss Truss Type Oh Ply 11/12J2018 2798
-74190 • 1 PB03 I COMN 1 1 1 2
Loading Criteria (psf)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 0.00
Load Duration: 1.25
Spacing: 24.0"
Lumber
Top chord 2x4 Sin #2
Bot chord 2x4 SP #2
It -- 2'77
2'7"7 {
12
T 6 C=3X4 T
V B DI
3'4"12
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category:
EXP: C Kzt: NA
Mean Height: 0.00 ft
TCDL: 5.0 psf
BCDL 2.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: NA
GCpi: 0.18
Wind Duration: 0.00
Nailnote
Nail Schedule:0.131'x3', min. nails
Top Chord: 1 Row @12.00' o.c.
Bot Chord: 1 Row @12.00" o.c.
Webs : 1 Row @ 4" o.c.
Use equal spacing between rows and stagger nails
in each row to avoid splitting.
Plating Notes
All plates are 2X4(Al) except as noted.
Puffins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord' Spacing(in oc) Start(ft) End(ft)
BC 37 0.15 3.25
Apply puffins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading .
Design Dead Loads based on material weight
adjusted for slope: BC: 8.00 PSF
i- 4'3"13
Code I Miss Criteria
Code: FBC 2017 RES
TPI Std: 2014
Rep Factors Used: Yes
FT/RT:10(OylO(10)
Plate Type(s):
WAVE
5'2"14
DefUCSI Criteria
PP Deflection in too Udefl U#
VERT(LL): 0.000 999 360
VERT(CL): 0.000 999 240
HORZ(LL): 0.000 - -
HORZ(TL): 0.000 - -
Creep Factor: 2.0
Max TC CSI: 0.009
Max BC CSI: 0.023
Max Web CSI: 0.000
Wgb 28.0 Ibs
VIEW Ver. 18.02.00.1016.21
♦ Maximum Reactions (Ibs), or'=PLF
Gravity
Non -Gravity
Loc R+ / R- / Rh
/ Rw / U / RL
A 11 /- /-
/- /- /-
B' 92 /- /-
/- /- /-
E 11/-
Wind reactions based on
MWFRS
A Brg Width = 7.3
Min Req = 1.5
B Erg Width = 40.8
Min Req = -
E Big Width = 7.3
Min Req = 1.5
Bearings A, B, 8 E are a
rigid surface.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
Chords Tens. Comp.
A-B 6 -3
C-D 0 -55
B-C 0 .55
D-E 6 -3
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
B-D 43 0
-WARNING— Please Noreughly review the 'A-11 ROOF TRUSSES("SELLER"). GENERAL TERMS and CONDITIONS CUSTOMER('BUYER-) ACKNOWLEDGMENT' form. ■
Venty design paremsters and read notes an Nis Trvss Donlan Drewing(r0D)md"Anthmy T.Tombplll, P.E. Reference Sheet before use. Unless odxe iw staled on Ne MD, only Alpin
wnnedor plats. shot be used forge Too b he valid As a Truss Design Engin.."(i.e. Specialty Engineer), the seal on any TDD represents an anseplance of the professional erglaeedn q.t ROOF
responsiii for Me design ofths single Truss depoled an the TDD only. under TPI-1.The design assumptions, leading candNons. suilabillty and use IN this Truss for any Building In; Me ®TRn59S
reepogaUerlineO nery of me Owner,Neowra gent actress
c dzedagent or Designer.
0 e conteer.nTe m�lert ISC.1 C.Ibe IBC,,de and ingmdeandpna-al of be Too and
any
.• ombo Io
rmp bihyofthe Ownghan ling. aulnarized agenlrcNeeuadserbeithehansemm�teafthe BlRC. geeil..l.ad conventual
TDDaMconaoa Anthony00830111, P.E.
useof Ne Tru BUilud"ug hand@g.storage,M%V tlan(RSCI) bracingsherbetVL2M nsi mfeautQug DgenMigMda n.a Wr idedessetmtin thenit aM d ps&t Tm y
guse .Mde Design
gCompaent These m(ormatlon (aSCllpubtshed by TPlaMSBCAare saran dlergene2l guitlanm. TP4lhnsl. NeTruss Design
esaM Julies OTOTruss #.Luca
Deagleis Tnue Design Engiire,rof.1bo ManufacNrer, uNev omenvLse dewed byaContrapagreed uponNvmWg by an parEes involved. The Truss Design EngineerSNOT Ne 8ut6 gg51SLe, FIL Blvd.
Desgreror Tuss SKbm Engneer INaM buildvg. AO mpitsf¢M Inrtu are as defined'm TP41.
..,-_.--_--- �."cPm/Tri¢vs-NOwrvT,Tanh�lll.PE Fort Pierce, FL 34946
Job Truss Truss Type Oty Ply 11/12Y2018
2775
74190 PB04 HIPM 1 1
r 14'0"7 -'- 2'6"11 --{
12
=4x4 Q s
A B C D E
Loading Criteria (ps0 Wind Criteria
TCLL: 20.00 Wind Std: ASCE 7-10
TCDL: 10.00 Speed: 160 mph
BCLL: 0.00 Enclosure: Closed
BCDL: 10.00 Risk Category: II
EXP: C Kzt NA
Des Ld: 40.00 Mean Height: 15.00 it
NCSCLL: 0.00 TCDL: 5.0 psf
Load Duration: 1.25 BCDL: 2.0 lost
Spacing: 24.0" MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 it
Loc. from endwall: not in 9.00It
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top chord 2x4 SP #2
Bat chord 2x4 SP #2
Webs 2x4 SP #3
Plating Notes
All plates are 1.5X4 except as noted.
Purlins
In lieu of structural panels or rigid ceiling use puffins
to laterally brace chords as follows:
Chord Spacing(in DO) Start(ft) End(ft)
TC 24 0.00 14.04
BC 120 0.00 15.52
Apply puffins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Loading
Design Dead Loads based on material weight
adjusted for slope: BC: 8.00 PSF
Wind
Wind loads based on MWFRS with additional C&C
member design.
TTTI
1 TAD
16'7"2
Code / VISO Criteria
De0/CSI Criteria
♦ Maximum Reactions (Ibs), or `=PLF
Code: FBC 2017 RES
PP Deflection in loc Udell U#
Gravity Non -Gravity
TPI Std: 2014
VERT(LL): -0.000 D 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.001 D 999 240
L' 77 /- /- /44 139 /3
FT/RT:10(0)/10(10)
HORZ(LL): 0.000 H - -
G 19 /- !- /14 17 !-
Plate Type(s):
HORZ(TL): 0.000 H - -
Wind reactions based on MWFRS
WAVE
Creep Factor: 2.0
L Brg Width = 188 Min Reel = -
Maz TCCSI: 0.468
G Brg Width = 7.3 Min Req = 1.5
Bearings L & G are a rigid surface.
Max BC CSI: 0.095
Max Web CSI: 0.104
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
Wgb 56.0 Ibs
A-B 3 -2 D-E 3 -3
VIEW Ver. 18.02.00.1016.21
B-C 3 -2 E-F 17 -51
C-D 3 -2 F-G 11 -8
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
L-K 2 -3 I-H 2 -3
K-J 2 -3 H-F 31 -34
J-1 2 -3
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
A-L 60 -53 D-1 350 -380
B-K 213 -219 H-E 193 -169
C-J 32 -40
^WARNING" Please thoroughly review the'A-1 ROOF TRUSSES("SELIFR'), GENERAL TERMS and CONDITIONS CUSTOMER('BUYER°) ACKNOVdLEDGMEM" form.
Verily design parameters and read notes an tlas Thus, Design Drawitg(Too)and Me Ammon, T. Tombo Ill, P.E. Rehrence Sheet before use. Unless oth¢raise=led on Me MD. only Non
�
connector plates shelf be used forth¢ TOD to be valid As a Tons Design Engineerngg.e, SpecialSpecialtyEngineer).Meseal assay== represents an acceptance of the professional eagineenn
responsibiLy for Vie design of Me single Truss; depicted an the TOD only,under T➢IA The design assumptions, loading conditions, suitability and use of this Truss for any Building is Me
A - ROOF
r
�2TRD59e9
Building is Me responsibility of the Qvner, Me Ovmefs aarl agent or the Building Designer, Is Me carted of the IRC, the IBC, 1=1 building bode and TPI-1. Theapprovalofine
ofthe Me and TPI-I. the
in the ry
orthe Bng
drum oviner, andlig,sbrage,
lToo,mGuding
Anthony T. Tombo Ill, P.E.
of Me Burnised
nstallationad bment
useaf the hstalll be to respe sting Designer and AfirshosdoutnTODandthpmoUcesand
&Me Tmss
#80083
guidelines ofthe Building ComponentSafety Innrvaton(BSCI) published by TPI and SBCA are referenced for general guidance. TPI-ldefinesmeme iibfitiesaddvlle
Designer. Tmss Design Engineer and Tmss Manufacturer, uNeas otherwise defined by a Contract agreed upon In wring by of parties involved The Thus Dasign Engineer is NOT the Buildi
4451 St. Lucie Blvd.
Designer w Tmss System Engineer W any building. Ail eepinraed terms areas dented sTPI-1.
Ccpyryn®30180.1flatl Trusses-MNwry T. Tombo lll,P.E Reproduction ofamdmment zany rmm.bprMlGledwMout Tex+111m ixrmibi of Ml Rrot Trusses-NMonrT.TomCo III, P.E.
Fort Plerce, FL 34946
Truss Truss Type
T01 I COMN
City I Ply 111122CI18 2809
1 1
659
i
f--19' i 1,9,
12 C=3X4
T 6p T
=2X4(A1)B Da2X4(A1) m
T
1 1 A E
Loading Criteria (pill Wind Criteria
TCLL: 20.00 Wind Std: ASCE 7-10
TCDL: 10.00 Speed: 160 mph
BCLL: 0.00 Enclosure: Closed
BCDL: 10.00 Risk Category: II
EXP: C KzD NA
Des Ld: 40.00 Mean Height: 24.64 it
NCBCLL: 10.00 TCDL 5.0 psf
Load Duration: 1.25 BCDL 5.0 psf
Spacing: 24.0MWFRS Parallel Dist: 0 to h/2
C&C Dist a:.3.00 it
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Lumber
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Special Loads
-(Lumber Dur.Fac =1.25 / Plate Dur.Fac.=1.25)
TC: From 60 pit at -1.00 to 60 pit at 4.50
BC: From 10 plf at 0.00 to 10 pit at 3.50
TC: 651b Conc. Load at 1.75
BC: 150 lb Conc. Load at 1.75
Purling
In lieu of structural panels or rigid ceiling use pur ins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(R) End(ft)
BC 38 0.15 3.35
Applypurling to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads and reactions based on MWFRS.
F- 1' J
i
151W
Code / Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs)
Code: FBC 2017 RES
PP Deflection in loc Udefl U#
Gravity Non -Gravity
TPI Sid: 2014
VERT(LL): -0.003 C 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Varies D L):-0.003 C 999 240
B 290 /- /- /- 231 /-
FTIRT:10(Oy10(10)
HORZ(LL):-0.002 - -
D 290 /- /- /- /231 /-
Plate Type(s):
HORZ(TL): 0.002 - -
Wind reactions based on MWFRS
WAVE
Creep Factor. 2.0
B Brg Width = 3.5 Min Req = 1.5
Max TC CSI: 0'133
D Brg Width = 3.5 Min Req = 1.5
Max BC CSI: 0.270
Bearings B & D are a rigid surface.
Max Web CSI: 0.000
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
Wgt: 16.8 lbs
A-S 27 .28 C-D 178 -182
VIEW Ver: 18.02.00.1016.21
B-C 178 -182 D-E 27 -28
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
B-D 142 -126 "
"WARNING- Please lhomughly renew Me'A-1 ROOF TRUSSES('SELLER'). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER') ACMOWLEDGMEN1' form.
Verify design parameters and reed notes on nib Tmss Deign DmMng(TOD) and the Anthony T. Tombo HI, P.E. Reference Sheet harem use.Unlew omamise sated on Me TDD, only Npin
cannerlorpWesshQbeuWfw Ne TDDmbavdlid. As a Tress Design Engineering (i.e.S,cialry Engineer), the seal on any TDD represents anaccepance of Me prefassional engineerin
q-s RMF
nmpoeeMlity for the design cfthe single Truss depicted on Me Too onty.under TPl-f. The devgn asamptions, badog conditions, suiatra, not use ofdds Truss for any Sending a da
Buadinge Matesponsibitity of the Owner. Vte Owrch auBwrzed agenrwNS BuiNLg Oetignu,a Necmtezl of NeIRC, Ne IBC.bolb ldugmTne,TPH. Theo fNe,
�ign5$f3
••���
Dand
rgpons3dryet Na Owner, Ne Ownels authwaea egentwihe BuiBirg Designer; in Ne cenart of aelRC,ib IBC, IoralWWeg mdeaM TPF1. The appmmal o/ihe TDDartl any fieM
use or Me Truss.'urlWag haMfug,storage, in5agadon and bmvg ghat be Merespv�tidryat the Balding OesgneraM Cantractw. All notes setoma Ne TDD and Ne prermcs arW
AnthonyT. TOmb0111, P.E.
Truss
guidelines Tees eiiigng Dwnponent Safety 4Rormation(BSCenes Whena tr/TPIaMSBGlare agencedfor in wMig by an pe TP4l defre no responsibSdksvd dud es NOT
Designer. Truss Design FsgineeraM Truce ManuaWrt,uNessresereedefuiedbya Contrail agreed upon In wnNg by all parries imolred. The Truss Design Engineer is NOT Me BuI
80083
#.Luca
a461erce,
Oes9m+CMt�svat�a r�ecwamlultewg, mnapaagzea temp ma as aerwadnnl-t.
wnrmyn mm�myr.rwnm m,Pa Rem,ulmarroem�t.hanrrm,�.mo,amlmdwvonvwwanpemaslman"t l:Werww-Atmv�yr.rmm m. FF.
l 3494
Fort Pierce. FL 34946
Job Truss Truss Type Oty Ply 11/12/2018
74190• V10 VAL 1 1 zns
Loading Criteria (par)
TCLL:
20.00
TCDL:
10.00
SCLL:
0.00
BCDL:
10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0 "
Lumber
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
'1
6"15
— 3' 1 '4"6 —..I
2 5 ;gX4 1111�X4 =�4
i- 47"10
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph.
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.26 ft
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 It
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Purlins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TC 24 3.28 6.28
BC 75 0.00 7.64
Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design. _
Additional Notes
See standard detail package for valley details.
71"12
3T"2
1.5X4 jT
�I
Code / Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs), or'=PLF
Code: FBC 2017 RES
PP Deflection in loc Udell L!#
Gravity Non -Gravity
TPI Ste: 2014
VERT(LL): 0.017 B 999 360
Loc R+ / R- ! Rh / Rw 11.1 / RL
Rep Factors Used: Yes
VERT(CL): 0.035 B 999 240
H' 80 /- !- 143 /29 77
FT/RT:10(0y10(10)
HORZ(LL): 0.006 8 -
Wind reactions based on MWFRS
Plate Type(s):
HORZ(TL): 0.012 B - -
H Brg Width = 91.7 Min Rect = -
WAVE
Creep Factor. 2.0
Bearing A is a rigid surface.
Max TC CSI: 0.267
Maximum Top Chord Forces Per Ply (Ibs)
Max BC CSI: 0.207
Chords Tens.Comp. Chords Tens. Comp.
Max Web CSI: 0.108
A-B 62 -55 C-D 97 -21
Wgt: 28.0 lbs
S-C 95 -21 D-E 77 -46
VIEW Ver: 18.02.00.1016.21
Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-G 48 -33 G-F 48 -33
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
C-G 362 -254 E-F 97 -58
"WARNING^ Please thoroughly nifew the-A-1ROOF TRUSSES('SELLER'). GENERAL TERMS and CONDITIONS CUSTOMER (BUYER") ACI(NOwLEDGMEM" form.
Verfy design pan coders and read notes on this Truss Design Dmwirg (MD) area We Mthany T. Torto Ill. P.E. Renamnoa Sheet betm use. Unless oderwlse Hated on Ne TOD, ony Npi
mmreMr platirsshaE be used farms MOW bevalid. Ae a Tmse Design Elgineemg(i.e.Specialty Engineer), the seal on any TOD represents an arcapiance of the pmfessioial enginearin A-r RDDF
raspoready for are design ofthe single Tmsstlepicue ones TODONy, under TPFl.The deignassumptions. leading mnd0ons, suitaGityand useofthb Tmssforany BWd'ag ¢tho LiRr155E5
eudGig bmeiesponsmJityorge Owner, me Twiefs aumgr¢ed agent or Ne BWdvg Desgrer,wme rmbnolme lRC, meIBC. brat Eugdug cede and TPl-1. The approval of me .TomboAa
respms3ilEy of me Owner, me OwrefsadMr¢ed agent or the Bamirg Designer,Nme mitea NmelRC. me ISC,bol Witl'vg aria artl TP4l. The approval al Ne T00 artl any fieN Anthony. Tombo ill, P.E.
use of me Truu.'vrdudvg hantlGig,storage. inzWladonaM bndrg shal lea me rezpo�itigtyortne Budd'ug Desynerartl Cantrador.Anmtes McMinnie T00 aMmeperdcesam y
g ignesoftne eWang Compon.stSafetyufnmadpn(95Cp pub�sned bye a�bSaCA are rererrlmafmgenerel guidanee. s aaroe Theespawbrnmsanddwes OTtTmss St.Lud
DesignewT Design EEng and Tr shoe Aftwm, wuess omaiwhe eerredgacannaaageea apenmwfwg crag paNes mveNed. Tna rmssDesign Eiginaarm NOT me eag g451SLLude Blvd.
oavgnerarTmaa sremm Er�eerNa�ybWtlotg. ao eaPeagzea mnre eras tlar",ea mTPl-1.
(vmvle03etaAt RmfTruraa-Meanr T. TanMl11.P.E Rmo]afMalOvf 6wmeN.hz"Yr�^.6ptluNNwteMNewrlempum�+n"IM1 Fu�Tusve-MCmyT. TanEo 111, P.E Fort P_erOD, FL 34946
Job Truss Truss Type Ory Ply 11/12/2018 2777
74190 V4 I VAL 1 1
T
20
Loading Criteria (ps0
Wind Criteria
TCLL: 20.00
Wind Std: ASCE 7-10
TCDL: 10.00
Speed: 160 mph
BCLL: 0.00
Enclosure: Closed
BCDL: 10.00
Risk Category: II
EXP: C Kzt: NA
Des Ld: 40.00
Mean Height: 17.36 it
NCBCLL 10.00
TCDL: 5.0 psf
Load Duration: 1.25
BCDL: 5.0 psf
Spacing: 24.0
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Purlins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 45 0.00 3.75
Apply pudins to any chords above or below fillers
at 24"OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes -
See standard detail package for valley details.
15�_ 1 t3n9 �� 1 t3e9 �6"1 '
12
6
A2X4(D8
B=3X4
_ \2X4(D8CR)
3'9"1
C
Code / Misc Criteria
DeflICSI Criteria
♦ Maximum Reactions (Ibs), or `=PLF
Code: FBC 2017 RES
PP Deflection in too L/defl L/#
Gravity Non -Gravity
TPI Sid: 2014
VERT(LL): 0.003 999 360
Loc R+ / R- I Rh / Rw / U / RL
D' 80 /- /- /32 /18 /6
Rep Factors Used: Yes
VERT(CL): 0.006 999 240
FT/RT:10(0)/10(10)
HORZ(LL):-0.001 - -
Wind reactions based on MWFRS
Plate Type(s):
HORZ(TL): 0.002 - -
'D Big Width = 45.0 Min Req = -
WAVE
Creep Factor: 2.0
Bearing A is a rigid surface.
Max TC CSI: 0.064
Maximum Top Chord Forces Per Ply (Ibs)
Max BC CSI: 0.096
Chords Tens.Comp. Chards Tens. Comp.
A-B 184 -165 B-C 184 -165
Max Web CSI: 0.000
Wgt 11.2 lbs
Maximum Bot Chord Forces Per Ply (Ibs)
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp.
A-C 162 -140
^WARNING' Please thoroughlymeme, the'A-1 ROOF TRUSSES('SELLER"),GENERAL TERMS and CONDITIONS CUSTOMER('BUYER")ACKNOWLEDGMENPfotm.
_
Vowy design parameters and read notes on this Truss Design Omwing(mD) and the Mthony T. Tombo ill, P.S. Reference Sheetbefore use. Unless otherwise stated onthe TDO, onlympin
onrmeaor plates stal be used forthe TOO lobevalid. As a Trues Design anginaerhtg(i.e. spedaly Engineer).Meseat on any Too represents an ameptanis of the professional engineedn
eqd RGBF
�®TRl15BE5
for Me design Me Tmss depiclad on Me Ton only, under TPl-1.nodesign assumptions. bading conditions. suitability and use of this Truss for any Building is Me
amponmbllity of single
Building S Me responsibility of the Owner, Me Owames auedurad agent or the Building Designer, in the centextafee IRO, Me IBC, 1=1 building code and TPI-1. Theappmvalofthe
•+vram.wun
authorizedor the Designer,in Me carbide of Me and iane
and TPI-1. idnth rl)ozodth
Me sign anld
nstallaion ad
Anthony T. Tombo ill, P.E.
uresponsibility
broibiliy of Me Building Connetltor. Afro>esseoe vrallodo
se or theT sz�tlaming hantlg�estoorage and area, slt ash be De
#80083
guidelines of Pe Building Component Safety lnfarana n(BSCI) publishetl by TPI anal SBCA are referenced far general guidance. TPI-1 defines 0e responsibilities and dunes of Me Tmss
Designer, Tmss Design Engineer and Truss Manufacturer, unless othemiae dermal by a Contract agreed upon in wMng by all parties involved. The Truss Design Engineer is NOT Me Buildis q
4451 St. Lucie Blvd.
Devgneror Tmss System EnginettofaMbmlding. M�apitali Vterms are as defmM in TPI-L
Lopylgh1aN118 Al Md Trvsses-MthwyT.Tombo Ill,P.E Rep,�u]bn althh tloo�menbNanylom.,6p^iilEileE'xilMu[Nevmtten pemiiuianol frl Rcaf Tnaues-MNmyT. TaMOI11, P.E.
Fort PIDfCB, FL 34948
Jop .. ,.-,_-.,Yy,,. , .Tsyss Truss Type Oty Ply 11/12/2018
'74190 ' V8 VAL 1 1 2778
Loading Criteria (psf)
TCLL: 20.00
TCDL: 10.00
SCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0 "
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
�1
IT151 2'8"6 17"6 _"}^ 273
i�3X4
6 2 ;3X4 IIIJ.5X4)
1 319"
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 16.71 it
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 It
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Purlins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(fl) End(ft)
TC 24 3.28 4.47
BC 75 0.00 6.65
Apply pudins to any chords above or below fillers
at 24" OCunless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
See standard detail package for valley details.
6'8"14
Code / Mise Criteria
Code: FBC 2017 RES
TPI Sld: 2014
Rep Factors Used: Yes
FT/RT:10(0)/10(10)
Plate Type(s):
WAVE
3X4(B1)
_L
2'11"15 -{
Defl/CSI Criteria
♦ Maximum Reactions (Ibs), or'=PLF
PP Deflection in too Udell U#
Gravity Non -Gravity
VERT(LL): 0.007 F 999 360
Loc R+ / R- I Rh / Rw / U I RL
VERT(CL): 0.014 F 999 240
G' 80 /- /- /40 /28 /8
HORZ(LL): 0.002 F - -
Wind reactions based on MWFRS
HORZ(TL): 0.003 F - -
G Brg Width = 80.9 Min Req = -
Creep Factor. 2.0
Bearing A is a rigid surface.
Max TC CSI: 0.138
Maximum Top Chord Forces Per Ply (Ibs)
Max BC CSI: 0.142
Chords Tens.Comp. Chords Tens. Comp.
Max Web CSI: 0.071
A-B 116 -63 C-D 163 -37
Wgt: 25.2 ibs
B-C 163 -37 D-E 122 -70
VIEW Ver: 18.02,00.1016.21
1 Maximum Bot Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-F 58 -46 F-E 58 -46
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp.
C-F 240 -184
"WARNING" Please thompghlyreview Me'A-1 ROOF TRUSSES rSELLER"). GENERALTERMS and CONDITIONS CUSTOMER(BUYER")ACKNOWLEDGMENrvfonn.
A
Venfy design pammeters and read notes on this Truss Design Drawing (IDD)and We Anthorsy T. Tombolll, P.E.Referenm Sheetb muw.UnlessoNerwlseslatedon Pe TDD,pnty AJpin
ne conctorDli,se shall be used br to TDD to bemfd. As a Tmss Design Engineering (i.e.spelolly Engueep, the seal on any Too represents an acceptance of Me professional engineer!
a
/I�v A-r ROOF
responsibility forth.design o1Ne single Truss delisted on Me TDD only, under TP4l.The design assumptions, loading conditions, suftabiity and use ofthis Truss for any Building is Me
/ aTNl155E5
Budding is 0e responsibility of We Owner, Me Owners authorized agent or Me Building Designer. In the context ofthe IRC, the IBC, local building mite and TPI-1. Theapprovalofthe
.mum"a
of the Me and nPi-I. n NaTooandthepraancugcesana
the ecmg shall
Me tlutg rrewasibin Me uty and
Anthony T. Tombo ill, P.E.
altar, Buildist
handling, storage InstalllaEwtnand braor
use of of MedTruty ss lInclf beme ng Designer ConneMre Allmumbetoutl
It80083
guidelines of the Bushing Component Safety Information (BBC[)published by TPI and SBCA are referenced for general guidance. TPP1 Wilma Me responslbirmes and duties of Wa Truss
Designer, Tmss Design Engineer and Truss ManufaeWrm. unless oNerwise dented by a Contrast agreed umn in mailing by all parties inyoNed. The Trams Design Engineer is NOT Me Builifir
4451 St. Lucie Blvd.
Designeror Tmss Syxtem Engineerafanybuilding. PP mptalbed temsare as def edNTPI-1.
LopydghtOMISMl Rm Tmsws-NMmy T.To III.P.E RePMuniss ofNlsdocarmA a anylors. ssdoiGLLMxiMour Msvrnpsaru Wo&A-1 RmfTrusso-Anhony T. TomW III. P.E.
Fort PIEfCB, FL 34946
WLiBD:
VH4
VAL
City
11y 111/12/2018
2779
Loading Criteria (poll
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0"
Top chord 2x4 SP #2
Bat chord 2x4 SP #2
Webs 2x4 SP #3
Wind Criteria
Wind Std: ASCE7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.00 ft
Loc. from endwall: not in 4.50 ft
GCpi: 0.18
Wind Duration: 1.60
Purling
In lieu of structural panels or rigid ceiling use poring,
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
TIC 24 2.34 3.88
BC 47 0.00 3.88
Apply purling to any chords above or below fillers
at 24' OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
See standard detail package for valley details.
1'6"8
12
a l qYA
DE
1113X6
I— 3'10"8 —j
f 3 7" — -P
T
7r
N
1
Code / Misc Criteria
DefUCSI Criteria
♦ Maximum Reactions (Ibs), or `=PLF
Code: FBC 2017 RES
PP Deflection in loc Udell U#
Gravity Non -Gravity
TPI Std: 2014
VERT(LL): 0.014 B 999 360
Loc R+ / R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): 0.029 B 999 240
E' 80 /- /- 146 125 /11
FT/RTA0(0)/10(10)
HORZ(LL): 0.005 B - -
Wind reactions based on MWFRS
Plate Type(s):
HORZ(TL): 0.010 B - -
E Brg Width = 46.5 Min Req = -
WAVE
Creep Factor: 2.0
Bearing A is a rigid surface.
Max TC CSI: 0.212
Maximum Top Chord Forces Per Ply (Ibs)
Max BC CSI: 0.227
Chords Tens.Comp. Chards Tens. Comp.
Max Web CSI: 0.164
A-B 60 -59 B-C 49 -30
Wgt 12.6 Ibs
Maximum Bot Chord Forces Per Ply (Ibs)
VIEW Ver: 18.02,00.1016.21
1 Chords Tens.Comp.
A-D 40 -4
Maximum Web Forces Per Ply (Ibs)
-
Webs Tens.Comp.
C - D 208 -92
"WARNING" Please lhomughly revisor the'A-1 ROOF TRUSSES("SELLER'). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER') ACxNOWLEDGMF film.
_
Ventrdlesign parameters and read notes on Nis Truss Design Dewing (TDD) and the Andlony T. Tombo Ill. P.E. Rohl Sheet before use. Unless odlelwlae staled on the ME, only Alpin
mnnedor plates shaA be used fw Ne TDD to be valid. As a Truss Design Engineering (i.e. Specialty Engineer), the seal on any Too represents an acceptance of the professional engineef
qq gDGp
��TRO$5E5
responsibility forme design of Ne single Truss depicted onto TODonly. under TPI-LThedeaignassumptions. leading conditions, suitathityand uSOWNis Truss forany Building isthe
Budding a no respareUiliy of me Owner, me Owners aumoneed agent or the Building Designer. iMewnteMOfine RC, ma IBC. to al building mdeand TPI-1. The approval of Ne
.m.u�w•+e
responsibility argue Owner, the owners authored agent" a Budding Besil in me contest of me IRC. to IBC,1=1 building code and TP(l The approvalafine Too and any field
Anthony. Tort ill, P.E.
Y
use bite Truss, doctoring using, storage, installation and bracing shall be all responsibidy ofine Building Designer and ConthaMr. All notes Setoutin NeTDDice and me practices and
dutiesof Ne Tmas
#80083
guidelines ofble Building Component Barely lnfwmation(BSCg Published by Viand SBCA are referenced Or general guidance. TPHdeMes Peresponsibilibesal
Designer, Truss Deeiga Engineer and! Truss Manufacturer. unless omemise defect by a Coal agreed upon in ending by all parties involved. The Truss Design Engineer is NOT me Surldfir g
4451 St. Lucie Blvd.
Deagneror Tmee svatam enginaeroramr banding. mcepilarlzad baneareasdel ad In TPI-1.
Lcyy1g1x02n611 Rm- f'r Amery T. Tombs Ill, PERepm]urdn or NamopMitiled ..m isdoent inanyfaa. MEhaul M.peshad.INM1 Real Trusses-NMmy T. T. III, PE.
Fort Pierce, FL 34946
Job
Truss
Truss Type
DTy
Ply
11112121118
2780
'74190 '
VM10
VAL
1
1
93 9
01.5X4C TII
2
B IB1.5X4B
A
w OF
02X4(DBR) E101. 4 N3X6
9'10'8
t 5.10.4 4V-4
Loading Criteria (pat)
Wind Criteria
Code Misc Criteria
Def l Criteria
♦Maximum Reactions (Ibs), or'=PLF
TCLL: 20.00
Wind Sid: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udefl U#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Std: 2014
VERT(LL): 0.025 E 999 360
Lac R+ ! R- / Rh / Rw/ U / RL
F' 80 /- /- /57 117 /32
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.051 E 999 240
BCDL: 10.00
Risk Category: II
FT/RT:10(0)/10(10)
HORZ(LL): 0.007 E - -
Wind reactions based on MWFRS
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.013 E - -
F Brg Width = 118 Min Reg = -
Des Ld: 40.00
Mean Height: 17.62 ft
WAVE
Creep Factor: 2.0
Bearing A is rigid surface.
9 a 9
NCBCLL: 10.00
TCDL: 5.0 pelf
Max TC CSI: 0.
Maximum Top Chord Forces Per Ply
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0.298 298
Chords Tens.Comp. Chords Tens.Comp.
Spacing: 24.0"
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 It
Max Web CSI: 0.761
A - B 132 -405 B - C 147 -245
Loc. from endwall: not in 9.00 It
Wgt: 42.0 IDS
GCpi: 0.18
Maximum Bot Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver. 18.02.00.1016.21 1
Chards Tens.Comp. Chords Tens. Comp.
Lumber A-E 427 -115 E-D 436 -120
Top chord 2x4 SP 92
Bot chord 2x4 SP #2 - Maximum Web Forces Per (Ibs)
Webs 2x4 SP #3 Tens. Comp.
Webs Tens.Comp. Webs
Purlins B-E 401 -343 C-D 217 -76
In lieu of structural panels or rigid ceiling use puriins
to laterally brace chords as follows:
Chord Spacing(in oc) Stan(ft) End(ft) _
BC 75 0.00 9.88
Apply putting to any chords above or below filers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical exposed to wind pressure.
Deflection meets 1-1360.
Additional Notes
See standard detail package for valley details.
"WARNING" Please honsughfy review Me-A-1ROOF TRUSSES(SELLER"), GENERAL TERMS and CONDITIONS CUSTOMER (-BUYER")AGMOVAEDGMEM-forth.
Vedfy design pammetws and read notes on this Truss Design Drawing Too) and he Anthony T. Tombo III, P.E. Reference Sheet before use. Unless otherwise stated on he To[) Doty Alpin
connector plates shall be used for the TDD to be valid. As a Tress Design Engineempew g (i.e. Salty Engineer), he seal on any TOD represents an acceptance of he professional engineedn
A-1 ROOF
�TpO55e5
ressell foTvapplonalofthO
under TPH. The e,lin
egenlor
editing is the sp ersibforthe gNo<he Onof wner, he ownees auhmient he B dung Desgn, the coneN of the IRC, the BC, Idal building code add TPI-1.
add field
no gainingDesigns,and l
of to 0ng
resof outm Ne
Anthony T•Tombo lll, P.E.
handier,
use MenlTons urlng, storage. installation and broul lDbe spe stihtyof the Building Designer and connbuildinector. Pill notese set TOlD and he purchase andand
#80083
s Of Me by III and! SSCA are refibranesol for
s iBundessotherrese
dafnedyblished
MandrestureInfidensibrin
Engineuand Trusnent
Oesignsr.Tmssscdagn a Conhactagteed uupoodeneraldivanigy all parties inwNed. The Tmss Oevugn Engineer isNOThe Buildi
4451St.Lucie Blvd.
.Luca
Desiwn wTmsssystem Enginrafanybwldmg. AD copitagzed termsare es tleMed in TPI-1.
fupy,IgM®M16 M1RMTmaes-MNony T. TomW I11.P.ERep,Wuction of WaEcameN.bony(o,m.'sO,ohiEited witlqut Ne wflhenceimisson ofA-1 RwfTmv¢-MNo,ry T. TanW III, P.E
Fort Pierce, FL 34946
Job
Truss
Truss Type
Qty
Ply
11/12/2018
2566 -
'74190
VM12
VAL
1
1
I
r1� 11'a'9
pt.SxdC
2
8 1711
111.5m
A
� OF
/2X4( BR) E61.6X4 10X6
I n•m•s
610.4 6G•4
Loading Criteria (psf)
Wind Criteria
Code / Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs), or'=PLF
TCLL: 20.00
Wind Std: ASCE 7-10
COde:FBC 2017 RES
PP Deflection in lac Udell V#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Sid: 2014
VERT(LL): 0.020 E 999 360
Loc R+ / R- / Rh / Rw / U / RL
F' 80 A !- /57 117 /19
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.041 E 999 240
BCDL 10.00
Risk Category: II
FT/RT:10(0yl0(10)
HORZ(LL): 0.005 E - -
Wind reactions based on MWFRS
EXP: C Kzt: NA
Plale Type(s):
HORZ(TL): 0.011 E - -
F Brg Width = 142 Min Req = -
Des Ld: 40.00
Mean Height: 17.12 it
WAVE
Creep 2.0
Bearing A is a rigid surface.
NCBCLL 10.00
TCDL 5.0 psf
Max TC CSt: SI: 0.
r Ply(Ibs)
Maximum Top Chord ForcesPer
sCamp.
Load Duration: 1.25
BCDL: 5.0 psf
Max Be CSI: 0.401 04
Chords Tens C mp.
Spacing: 24.0'
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00it
Maz Web CSI: 0.137
A-B 123 -352 B-C 62 -133
Loc. from endwall: not in 9.00 it
Wgb 49.0 IDS
GCpi: 0.18
Maximum Bot Chord Forces Per Ply (Ibs)
Wind Duration: 1.60
VIEW Ver: 18.02.00.1016.21
Chords Tens.Comp. Chords Tens. Comp.
Lumber A-E 369 -103 E-D 380 -109
Top chord 2x4 SP #2
Bol chonl 2x4 SP #2 Maximum Web Forces Per Ply (Ibs)
Webs 2x4 SP #3'
Webs Tens.Camp. Webs Tens. Comp.
Purlins B-E 459 -416 C-D 230 -138
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in cc) Starl(ft) End(ft)
Be 75 0.00 11.88
Apply puffins to any chords above or below fillers
at 24' CC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Additional Notes
See standard detail package for valley details.
—WARNING' Please thoroughly review me -A-1 ROOF TRUSSES(•SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER(•BUYER') ACKNOWLECGMENP forth.'
d
venfy design Moderators am read notes on This Truss Design Drawing (Too) and the Anthony T. Tombo III, P.E. Reference Sheet before use. unless othelwlse stated on the MD. only Alpin
RA-1
pmmector plates shag be used for die Too to be valid. As a Truss Design Engineering (i.e. Specialty Bugmeer), No seal on any TOO represents an acmptance of 0e professional ergmeetin
respenstbl0ty for 0a design of the single Truss depicted online TODonly, underrPH-Thedesign assump4ans, boding conditions. suitsbuyanduseaf Ne TuThoseforany Building istha
ROOF
� ®TRO556
Mudmg'¢Neresppnsblityof Ne Owner,meO saudnrcedagentwr Building Designw.inthemntMOf WIRC.Ihe IBC.lomlbugd0gcodewdTP41. Tmapptovatofthe-
mh aired
�ase �ty euuirg wit m moo m aM
Anthony T. Tombo ill, P.E.
of Me se. hE�vgr'nandiinn�gtt storage. installation bracing slashbeme leseen orma DesignerandCoon maldrennahomeeset and prraa'�
Truss
#80083
Misleads of the evoking component safety loadviDon(aSOI)publahed by TPl and sil are refaenreE for general guidance. TPI-1 dews Nerespensbriussand dudesofgre
Designer,Truss Design EnneeralW Truss Manureaurer,andes otnemise dermed byatgnbabagreeduponbwdti,g byall parties evowed. The Truss Design Engineerb 1,107-dreBuildir
4451 St. Lucie Blvd.
Cesigrm or rruss sys<m 6ginevof eny bwabg. Al eapuaraed lema are as dafned bTPI-1.
Ggy,gMO A18 Al RmlTwen-MVwryT TpnM III, P£ Repcdvt4n W MEcament Nmry rmm. b prlulitedwNoa do vneen pm,¢v-m of Mt Roor Tuzua-Mdmy i. TvnEo el, P.E
Fort Pierce, FL 34946
Job Truss Truss, Type Ory Ply 11/1212018
2569
74190 VM14 VAL I 1 1
Loading Criteria (ps0
TCLL:
20.00
TCDL:
10.00
BCLL'
0.00
BCDL:
10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
P
(s10-a
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt NA
Mean Height: 16.62 R
TCDL 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: P 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 fl
GCpi: 0.18
Wind Duration: 1.60
Purlins
In lieu of structure panels or rigid ceiling use pudins
to laterally brace chords as follows:
.Chord Spacing(in oc) Start(ft) End(ft)
BC 75 0.00 13.88
Apply purlins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Additional Notes
See standard detail package for valley details.
r
S•10.9
Code 1, Mise Criteria
DefUCSI Criteria
♦ Maximum Reactions (Ibs), or'=PLF
Code: FBC 2017 RES
PP Deflection in loc Udell L/#
Gravity Non -Gravity
TPI Std: 2014
VERT(LL): 0.023 G 999 360
Loc R+ ! R- I Rh / Rw I U ! RL
Rep Factors Used: Yes
VERT(CL): 0.045 G 999 240
H' 80 !- /- 158 /17 /19
FT/RT:10(Oy10(10)
HORZ(LL):-0.006 C -
Wind reactions based on MWFRS
Plate Type(s):
HORZ(TL): 0.012 G -
H Brg Width =166 Min Req = -
WAVE
Creep Factor. 2.0
Bearing A is a rigid surface.
Max TC CSI: 0.511
Maximum Top Chord Forces Per Ply (Ibs)
Max BC CSI: 0.361
Chords Tens.Comp. Chords Tens. Comp.
_Max Web CSI: 0.188
A-B 141 -394 C-D 4 -55
Wgb 64.41bs
B-C 74 -214
VIEW Ver. 18.02.00.1016.21
Maximum Bot Chord Forces Per Ply (Ibs)
-
Chords Tens.Comp. Chords Tens. Camp.
A-G 413 -122 F-E 426 -129
G - F 423 -127
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
B-G 403 -385 D-E 20 -8
C - F 383 -289
"WARNING- Please Noreughly review Me'A-1 ROOF TRUSSES ('SELLER"). GENERAL TERMS and CONDITIONS CUSTOMER ("BUYER") ACKNOWLEDGMENT. form.
Verify design aggeraters.nd read rates. Nis Truss Design Draving (MD) and dle Anthonry T. Tdmbo Ill, P.E. Reference Sheet befare use. Unless oNenwise staled on the TDDonly Alpin
Zgineerel
,
mmecNr plates shad bR usbtl lv Ne TD0lo be valid. Asa Truss Design Erginearhlg C,.-. Specialty Engaleer), Me seal on any TDD represents an aompbase olthe prefessioral
A-yR OF
responsblity far No design ofMe angle Tuv deplored! on Me TDD only, under TPM.TM design assumptions, boding mndigarts. suilabiNy and use of Bds Tars for any Budding is Mrs,
aiR0556
Bugfug aNe reslx0s0ilgy of Na Owner, Iha Owrefs au0rodzad egentnds eudd'ag Designer,Ntice mnte4 of the lRC. gle 18C.Ncel buJdug buds antl TPl-1. Th0xcr6valofg19
responstigtyo/the Owner, Ina pvnMsauNol¢N agents Ne Bwlding Designer, in Ne mnM�d of Ne IRC.Ihe iBC.laml Wild'vg code aM TPN. TheapgentdNe TDDanda,flM
Anthony. Tombo III, P.E.
y
usedithe Truss.iricudblg handGn9. stamge. hstagadan and breCing shag be Me reSporoutgRy of" BuNeg Designer and! redn Cont. AN merge set out in Me MD and Me pracU� and
Su LnesafMe BuMgComponent Safetylntom Wn(BSCI)pubr¢hedby Win SBC ammferenmdforgene2lguWd . TP4lde esNerespt Mbesa dudceofMe Truss
#80083
Designer. Truss Design Engineer and Trlffi Manfie1 uer. unless Wenwbe de5ted by a Cantradagneed upon N waiting by of pardes i ed. The Truss Design Engineer NOT Me Buffifir g
4451 St. Lucie Blvd.
Designer orT,uae Menem En urger of any building. Ad,aN=M mma=e as derned InTPI-1.
4TmgM0 2016 h1 Roof Tagues-MNvIy T. TanW 111.PERepo]asotd Me dmvnmtbsay, tmn.bpd,SBed whoa Pe when lvmrssbn of Roof Trlwn- Maeny T. Tore, In, P.E.
Fort Pierce, FL 34946
Job Truss — - — Truss Type Oty I Ply 11/12/2018 2572
74190 VM16 VAL 1 1
Loading Criteria (ps0
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0"
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kad: NA
Mean Height: 16.12 It
TCDL: 5.0 cast
BCDL: 5.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 8
Loc. from endwall: not in 9.00 ft
GCpi: 0.18
Wind Duration: 1.60
Purlins
In lieu of stmctuml panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(fi) End(it)
BC 75 0.00 15.88
Apply purling to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Additional Notes
See standard detail package for valley details.
tst0T
Code / Misc Criteria
Deft/CSI Criteria
♦ Maximum Reactions (Ibs), or'=PLF
Code: FBC 2017 RES
PP Deflection in loc Udell U#
Gravity Non -Gravity
TPI Sid: 2014
VERT(LL): 0.023 H 999 360
Loc R+ / R- / Rh / Rw l U I RL
Rep Factors Used: Yes
VERT(CL): 0.046 H 999 240
1' 8() /- /- /58 117 119
FT/RT:10(Oy10(10)
HORZ(LL): -0.009 D - -
Wind reactions based on MWFRS
Plate Type(s):
HORZ(TL): 0.012 H - -
I Big Width = 190 Min Reel = -
WAVE-
Creep Factor. 2.0
Bearing A is a rigid surface.
Max TC CSI: 0.500
Maximum Top Chard Forces Per Ply (Ibs)
Max BC CSI: 0.354
Chords Tens.Comp. Chords Tens. Comp.
Max WebCSI: 0.211
A-B 163 -445 C-D 97 -256
'
Wgt: 71.4 lbs
B-C 76 -274 D-E 36 -79
VIEW Ver. 18.02.00.1016.21
Maximum Bat Chard Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-H 459 -142 G-F 472 -149
_
1
H - G 468 -147
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
B-H 384 -380 E-F 133 -81
D- G 378 -325
"WARNING'' Please thoroughly review die-A-1ROOF TRUSSES('SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER(BUYEFr) ACKNOWLEDGMENT' farm. _
Verity design parameters and read notes an Nis Trues Design Drawing TDO) and Vce Mthoay T. Tombs ill, P.ERererenmgheet %muse.UnlesSONoMw SWWdon Ne TDD, an Alpin
mnrlectarpUWsshelbomedlorthe TDDtobevalid. M a Truss Design Engiassmg(m.SpecIalty Eagireed, Na seal an any TOD represents an acceptance al Ne luolessiolul ellgineerm
glROOF
respon MtylorVtedesignol Nesingle Tr depl ontha TDDCNy,underVt.l.Thadevgnassurrpdons.b ingmMiGal;suit E"MusaofMb Tmwwaw BwlOing is theA11011TRUSWEE
8ugdvlgbthe respansiL'YitydNa O.vner. the Dwnefa auNa¢ed agent mltle 8ugdug Designer, in the mob#o1NeIRC. MaIBC.lotal buJEing aatle eM TPI-i. TheapproralINNe
.•um.�.s
respmsbJM al Ne Omer, Vie Ownefs auNariadagentnthe BuiWbg Desgner,NNem�le#ol Ne1RC. Nelee.bcel btiM'ug wdeaM TPI-1. Tlleappnwalargre TDDaMaMfield
Anthony. Tombo ill, P.E.
y
LduSvghaMGrg, artlbaagyWl be dm essemsin the TDDamde
artlanw.
#.Luca
sf.aT
TPI imd SB Aao meemedfr prener Wr ide
gnissainrsaolNd ar ft Safety Womna4m
i.o� Ery"exaroT�Mnnaraw�rna��aaol�ou~ aeefineedeya�beaegreed uoonin ."bnd yaure. TVI.1dafi sNaress Desioesam dwsi NOTUTmss
pardea invoNea. ThaTmss Design Ergneeris Northe euiw�
g451 St. Lucie Blvd.
oesig,worTmu system Err�eerolerry bwMmg. Al mpiralRed terra ereudefv NFTPpt.
fury,rylaOAIaMI Rbtl Trvaef-Anemyi.Tamtom.P.E RapblvJvnNMe Govmu4 rrarylmm,upd�BNrienM1WvrWenl�nL¢vrdA-1PmITri¢w-MdmyT. Tonh, 14 P£
Fort Pierce, FL 34946
Job Truss . Truss Type _Qty.,_ Ply 11/12/2018
74190 VM18 I VAL 1 1 zags
Loading Criteria (psf)
TCLL: 20.00
TCDL. 10.00
BCLL: 0.00
BCDL 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
Lumber
I Sirs
Wind Criteria
Wind Std: ASCE7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.62 ft
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: It to 2h
C&C Dist a: 3.00 ft
Loc. from endwall: not in 9.00 R
GCpi: 0.18
Wind Duration: 1.60
Top chord 2x4 SP #2
Bol chord 2x4 SP #2
Webs 2x4 SP 93 :W3 2x4 SP 2400f-2.0E:
Bracing
(a) Continuous lateral restraint equally spaced on
member.
Purling
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 75 0.00 17.88
Apply pudins to any chords above or below fillers
at 24' OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical not exposed to wind pressure.
Additional Notes
See standard detail package for valley details.
"WARNING" Please thoroughly review the'A-1 ROOF
VeMy design parameters and rand notes an this Toss Design Di
mnmtlor oleos slay be used for me TrlD bbe vdl'q. AsaTm�
Code I Misc Criteria
Code: FBC 2017 RES
TPI Sid: 2014
Rep Factors Used: Yes
FT/RT:10(0y10(10)
Plate Type(s):
WAVE
DeRICSI Criteria
PP Deflection in loc Udell
VERT(LL): 0.024 1 999
VERT(CL): 0.048 1 999
HORZ(LL):-0.007 D -
HORZ(fL): 0.013 1 -
Creep Factor. 2.0
Max TC CSI: 0.562
Max BC CSI: 0.330
Max Web CSI: 0.260
Wgb 78.4 Ibs
♦ Maximum Reactions (Ibs), or •=PLF
U# Gravity Non -Gravity
360 Loc R+ / R- / Rh / Rw / U / RL
240 J' 80 /- /- /58 117 . 119
- Wind reactions based on MWFRS
J Big Width = 214 Min Req = -
Bearing A is a rigid surface.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-B 184 -494 C-D 124 -317
B-C 103 -336 D-E 63 -117
VIEW Ver. 18.02.00.1016.21 I Maximum Bat Chord Forces Per Ply (Ibs)
Chords Tens.Comp. Chords Tens. Comp.
A-1 503 -162 H-G 5 -5
I-H 512 -167 G-F 0 0
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp. Webs Tens. Comp.
B-I 351 -360 E-F 196 -141
D-G 431 -399
TERMS and CONDITIONS CUSTOMER('BUYER°) ACKNOWLEOGMENr room.
IN, III. P.E. Referenm Sheet before use. Unless olhernise stated on the MO. only A,,
g�er,NNe mntert of McIRC, Ne IBC, loml buJtlitg code aM TPI-1. TheaPpm'mlor Vn lu---Zneo Anthony. TOmbo III, P.E.
the raspowbDesignerty of the Binding Designer aM Cennontm. M notes set out In and Too and the aneac aM Y
TPIaM gaConnot"re vWin re2lg byance. Teem eructs Ne responeogn sa sneer m 01 Truss #8Luci
'.0083
efaM bye Cantratl agreedelxn in writing by eO PaNes invrtved. The Truss Desgn Ergneere NOT NaBWd 44$1 St. Lucie Blvd.
IemeO em TPl-1.
cban, rvm.bwdvvn.dwtmm ew.dem a=,nsa,mA-t aomToaso,-,wumyT. Team III. RE Fort Pierce, FL 34946
Job Truss Truss Type Qry Ply 11/12/2018
74190 VM2 VAL 8 1 2785
6"15
1'3"9
12
6
U
�-- 1'10"8 �{
Loading Criteria (ps0
Wind Criteria
Code / Misc Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs), or'=PLF
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc L/de0 L/#
Gravity Non -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Bid: 2014
VERT(LL): -0.005 B 999 360
Lee R+ / R- / Rh / Rw / U / RI
D- 80 /- /- 146 /23 /20
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.009 B 999 240
BCDL: 10.00
Risk Category: II
FT/RT:10(0)/10(10) -
HORZ(LL): -0.002 B - -
Wind reactions based on MWFRS
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.004 B - -
D Brg Width = 22.5 Min Req = -
Des Ld: 40.00
Mean Height: 19.62 ft
WAVE
Creep Factor: 2.0
Bearing A is a rigid
9 ghord
NCBCLL: 10.00
TCDL 5.0 psf
Maz TC CSI: 0.054
Maximum Top Chord Forces Per Ply (Ibs)
For
Load Duration: 1.25
BCDL: 5.0 psf
Max BC CSI: 0.097
Chords Tens.Comp.
Spacing: 24.0"
MWFRS Parallel Dist: 0 to h/2
C&C Dist a: 3.008
Max Web CSI: 0.000
A-B 0 -20
Loc. from endwall: not in 4.50 it
Wgt: 5.6 Ibs
GCpc 0.18
Maximum Bot Chord Forces Per Ply (Ibs)
VIEW Val 18.02.00.1016.21
Wind Duration: 1.60
Chards Tens.Comp.
Lumber
A-C 68 -11
Top chard 2x4 SP #2
Bat chord 2x4 SP #2
Purlins
In lieu of structural panels or rigid ceiling use puffins
to laterally brace chords as follows:
Chord Spacing(in oc) Stan(ft) End(ft)
BC 23 0.00 1.88
Apply puffins to any chords above or below filers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
-
See standard detail package for valley details.
.
-WARNING' Please thoroughly review Me -A-1 ROOF TRUSSES('SELLER'). GENERAL TERMS and CONDITIONS CUSTOMER ("BUYER') ACKNOWLEOGl Mn.
Verify design parameters and read notes on Nis Toss Design Dravring(Too) and the Anthony T. Tombo ill, P.E. Reference Sheet before use. Unless otherwise spied on the MD. only Aptn
nneplor plates shall be used for Me Too robe valid. As a Truss Design Engineering(i.e. Specialty ErgineeQ, Me seal an any Too represents an ameplance of the professional engineem
�A-y RRRF
�®Tp1155E5
responsibilf,WMedesign of Me single Toss depicted on Me Too orry,underTPl-L The design assumptions, loading conditions, suitability and use of Mp Toss for.ny Building is to
Building R the responsibility or the Owner. the Owners authored agent or Me Building Designer.p Me ontest or Me Be. Me IBC, loot building oWe and TPIA. TheapponaleMe
responsibility of Me Owneo Me OwmersauNadzetlagentarthe Building Designer. intheocrundof Ne IRC, the IBC,lool building wde and TPIl. Theapprovalof Me ToDandanygeld
Anthony. Tombo Ill, P.E.
y
use of the Truss. indudNg handling, storage. instalatlon and bradng shall W Me responsibility ofthe Buying Designer and Contractor. All nolessetoutinthe TDOand Me practices and and
#80083
guidelines of Me Building Component Safety Information (BSCI)published by TPI and SBCA are referenced for general guidance. TPI-1 defs Me responslbgines and duties of Me Truss
Designer. Truss Oasan Eignmer and Truss Manufacturer, unless otherwise def d by a CanbaR agreed upon in wdGng by all parties involved. The Truss Design Engineer is NOT Me Buildi g
4451 St. Lucie Blvd.
design«Or EngMeermanybandpg.AncalsJanommoeareasdunsnr.maryf
Fort Pierce, FL 34946
CepyngM0301a A-f Root Trusses-ArMony T. TwnEo III. PE. RepreEucYon of INSEmmenLNanylum, k pMiGletivANOW NexnRen cennusim MA-1 Rwf Trusses-Nuheny T. TomM III. P.E.
165 i mf
Job Truss Truss Type City Ply 11/12/2018
74190 VM4 VAL 5 1 veB
Loading Criteria (ps0
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0 "
Lumber
Top chord 2x4 SP #2
Bot chord 2x4 SP #2
Webs 2x4 SP #3
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kitt: NA
Mean Height: 19.12 it
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: h/2 to h
C&C Dist a: 3.00 8
Loc. from endwall: not in 9.00 it
GCpi:0.18
Wind Duration: 1.60
Puffins
In lieu of structural panels or rigid ceiling use pudins
to laterally brave chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 47 0.00 3.88
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Additional Notes
See standard detail package for valley details.
FT151 Ti
i 3'10"8
i 3-7-
Code I Misc Criteria
Code: FBC 2017 RES
TPI Bid: 2014
Rep Factors Used: Yes
FT/RT:10(0)/10(10)
Plate Type(s):
WAVE
R
T
T
Defl/C81 Criteria
PP Deflection in loc Udell L/#
VERT(LL): NA
VERT(CL): NA
HORZ(LL): 0.003 C - -
HORZ(TL): 0.005 C - -
Creep Factor: 2.0
Max TC CSI: 0.205
Max BC CSI: 0.164
Max Web CSI: 0.095
Wgt 14.0 Ibs
VIEW Ver: 18.02.00.1016.21
♦ Maximum Reactions (Ibs), or'=PLF
Gravity Non -Gravity
Loc R+ / R- / Rh / Rw / U ! RL
D' 80 /- /- 153 125 /22
Wind reactions based on MWFRS
D Big Width =46.5 Min Req=-
Bearing Ais a rigid surface.
Maximum Top Chord Forces Per Ply (Ibs)
Chords Tens.Comp.
A-B 34 -83
Maximum Bot Chord Forces Per Ply. (Ibs)
Chords Tens.Comp.
A-C 161 -25
Maximum. Web Forces Per Ply (Ibs)'
Webs Tens.Comp.
B-C 179 -94
"WARNING^ Please Moraughty review the -A-1 ROOF TRUSSES ('SELLER'), GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER") ACKNOWEDGMENP' form.
_
Ve1ity Betgn parameters and lead notes on distress Design D2«ing CMD) and BceAMhony T. Tombo III, P.E. Referencesheet before use. Unless othave se staled on the MD. onlympin
connector plates shag teased for Me Too to be valid. Asa Tmss Design Engcneenn go.Spedaly Engineer). Me sealed any TOD represents an aceepladMaol Oepmfessional engineenn
A-1RDRF
responsibil,yforthe design ofthe single Tmss depicted on Pe Too only, under TP14. The design assumptions, loading conditions. suitability and use of Nis Trues,for any adding is the
'990®TRUS5
Building is 0e responsibility of Me Oaner. the Onmlers auNmked agent or Me Bugling Designer, in Me contest ofinelRC, the 180. Iocol building Made and TPI-l. Theappmvaimmu
..m —f-
agent or [he building Mode andaessetoutinba MD
Me Re. �Designer antl
lTmrussNmddNg Me hatonstilin me �y
Anthony T. Tomb0111, P. E.
of the Buildingtextat
use oime handling, Storage, torage. maft odeling. and area, stag b e Conned Alleadd preusesanE
Tmss
#80083
guidelines of the Building Component Safety tdolmaled(6SCI)Published by TPI and SBCAma referenced forgereml guidance. TPI-1 defines me responsmiliges and dunes of Me
Designer, Truss Design Engineer and Tmss Manufacturer. unless Mari defined by a Contract agreed upon in vmiglg by all FNes involved. The Tmss Design Engineer is NOT the Buildi
4451 St. LUOle Blvd.
Oesil or Tares System Engineer of any building. A➢capitagzed tends are as defured'n TP41.
G pgh102g16MlR T ss -M yT.To III.PEReg¢Ib o1,n order tlovwnam.Na,rytrcm, ufiniii mumed Me enden pemerrion dX1 Rwl Tnusee-Anlhmy T. Tune ill. P.E
Fort Pierce, FL 34946
Job Truss Truss Type Oty I Ply 11/12/2018 2787
74190 VM5 VAL 1 1
Loading Criteria (ps0
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0 "
Top chord 2x4 SP #2
Bot chard 2x4 SP #2
Webs 2x4 SP #3
Wind Criteria
Wind Sid: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: II
EXP: C Kzt: NA
Mean Height: 15.00 ft
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: h to 2h
C&C Dist a: 3.00 It
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Purlins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 63 0.00 5.22
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical exposed to wind pressure.
Deflection meets U360.
Additional Notes
See standard detail package for valley details.
IT155 i 47"12
i
i
5'2"11 —j
F — 4'l 1"3
r
Code / Misc Criteria
DegICSI Criteria
♦ Maximum Reactions (Ibs), or •=PLF
Code: FBC 2017 RES
PP Deflection in loc Udell U#
Gravity Non -Gravity
/ / Rh / Rw ! U ! RL
TPI Std: 2014
VERT(I-Q: NA
Loc R+ R-
Rep Factors Used: Yes
VERT(CL): NA
D" 80 !- /- /55 /14 /28
FTIRT:10(Ov10(10)
HORZ(LL): 0.007 C - -
Wind reactions based on MWFRS
Plate Type(s):
HORZ(TL): 0.013 C - -
D Big Width = 62.7 Min Req = -
WAVE
Creep Factor. 2.0
Bearing A is a rigid surface.
Max TC CSI: 0.367
Maximum Top Chodd Forces Per Ply (Ibs)
Max BC CSI: 0.295
Chords Tens.Comp.
Max Web CSI: 0.221
A-B 48 -162
Wgb 21.1lbs
Maximum Sot Chord Forces Per Ply (Ibs)
VIEW Ver'S.02.00.1016.21
Chords Tens.Comp.
A-C 234 -50
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp.
B-C 251 -130
Please Ihoma,dy review the "A-t ROOF TRUSSES ('SELLER"). GENERAL TERMS and CONDITIONS CUSTOMER ('BUYER') AC"CWIEDGMENr' ram.
.-_— _-.-------- IF711""n me AMMm T. Tnmhn la. PEReference Bbeet hefom use. UNess etharvise staled on 0e TDD, only X{
sties
A
,A#n RA-1 ROF
52TRussFs
Anthony T•Tombo III, P.E.
# 80083
4451 St. Lune Blvd.
Fort Pierce, FL 34946
Job Truss I Truss Type City I Ply 11/12/2018 2788
74190 VM6 VAL 3 1
Loading Criteria (psf)
TCLL: 20.00
TCDL: 10.00
BCLL: 0.00
BCDL: 10.00
Des Ld: 40.00
NCBCLL: 10.00
Load Duration: 1.25
Spacing: 24.0'
Lumber
Top chord 2x4 SP #2
Bol chord 2x4 SP #2
Webs 2x4 SP #3
Wind Criteria
Wind Std: ASCE 7-10
Speed: 160 mph
Enclosure: Closed
Risk Category: It
EXP: C Kzt: NA
Mean Height: 18.62 it
TCDL: 5.0 psf
BCDL: 5.0 psf
MWFRS Parallel Dist: h/2 to IT
C&C Dist a: 3.00 it
Loc. from endwall: not in 9.00 it
GCpi: 0.18
Wind Duration: 1.60
Puffins
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in cc) Start(ft) End(ft)
BC 71 0.00 5.88
Apply puffins to any chords above or below fillers
at 24' CC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical exposed to wind pressure.
Deflection meets U360.
Additional Notes
See standard detail package for valley details.
F61� 5'3'9�
5'10"8
Code / Misc. Criteria
Defl/CSI Criteria
♦ Maximum Reactions (Ibs), or'=PLF
Code:FBO 2017 RES
PP Deflection in (cc Udell U#
Gravity Non -Gravity
TPI Sld: 2014
VERT(LL): NA
Loc R+ I R- / Rh / Rw / U / RL
Rep Factors Used: Yes
VERT(CL): NA
D' 80 /- /- 155 127 /30
FT/RT:10(0)/10(10) .
HORZ(LL): 0.009 C - -
Wind reactions based on MWFRS
Plate Type(s):
HORZ(TL): 0.019 C - -
D Brg Width = 70.5 Min Req = -
WAVE
Creep Factor. 2.0
Bearing A is a rigid surface.
Max TC CSI: 0.488
Maximum Top Chord Forces Per Ply (Ibs)
Max BC CSI: 0.436
Chords Tens.Comp.
Max Web CSI: 0.294
A-B 53 -191 -
Wgt: 21.0 Ibs
Maximum Bot Chord Forces Per Ply (Ibs)
VIEW Ver. 18.02.00.1016.21
Chords Tens.Comp.
A-C 269 -56
-
Maximum Web Forces Per Ply (Ibs)
Webs Tens.Comp.
B-C 293 -147
"WARNING- Please thoroughly review Me'A-1 ROOF TRUSSES('SF1LE8'), GENERAL TERMS and CONDITIONS CUSTOMER ("BUYER-) ACKNOWLEDGMENT" form.
Verily design parameters and! mad notes on lM16 Truss Design crowning Cri and ee ANho,ry T. Tombs Ill, P.EReferenm Sheetbefoeuse.UnlossoNerwise'steedon Ne TDD.oNy Alpin
mrvetlorpbtea alu0 be used fu Me TDD toWvalid. se a Truss Design Enginerag(i.e. 5pecally Eghieer). are isal on any TDO represents an eddeptance d M.,ndilesoonale gnatL A-r ROOF
responsaillty forthadleign of Ue single Truss derided th on e Me only, under TPl-1. The dools asses ¢and. boding mMNms, awtaderyaM ussofgds Truss lorany, BSWugame , TRr155E5
BuilGug bNe responvLTH oI Na Owner. Ne Ousels augxrbed agents NoeWdvg Designer,btle rantea of MelRC, be IBC.bd Widllg mdeaMTPs1. tha ToD ndle,Ne .,Tory Ill
respdrsbitiryol Ule Oener, the Owrela authorized ageldutM Breldug Designer, in be mntertof Na lRC.tle IBC, Io al Wit?eg mde arW TP41. TM1e appmral of Na TDD alM airy field Anthony: Tombo ill, P.E.
useof Dieofthe Mdirig handling,storage. inefallabon and brepbgalled belie asx!Mibilllyofthadroeug Desynel and Conlmctn. All rotes satMin PeTDDeM the p2Gices and y
guidellncs ed. Building Component Safely l ard.d. don (MCI)Installedo0e ra ft, TPl aM SaCA are refere agreed
losegene Us,al by
11 p TPN d isid. the Truss D ibJi Erri duties of Me Truss # . Lucl
W0083
algner Trosa Design Engineer and Tmssding. AlWrenload aNenddSo darned aya I-1. agreed uponbwddng by all paNes lnvoNetl. The Truss Design FnglneeAS NOT Na Build 4451 $t. LDCIe Blvd.
Wagner Mrmsa.�sremm Engineer of ely Wilding. All mpallutl tame mesa denmtl m rnln. Fort Pierce, FL 34946
e uMTnsw_MIMrvT.TmJn III.P£Raomfue(un WetlaOmmeRb�yf�^.I+GbtlNladufVnM1Ne w+1R^Wrm1a51T or A-1nmlTwea-MEvryT. TwnEOI11, P.E
Job
Truss
Truss Type
Oty
Ply
11/1212018 2789
74190
VM8
VAL
2
1
)= 1 7'3.9
B1.SX6C
T
12 Ig1.5X4B
6 p
m
A l
ea DF
>s2X4( R) EIg1.5X4 111.5X4
r T10'81
�— 5.10.4 2'0'4
Loading Criteria (psf)
Wind Criteria
Code / Misc Criteria
Deft/CSl Criteria
♦ Maximum Reactions (Ibs), or'=PLF
TCLL: 20.00
Wind Std: ASCE 7-10
Code: FBC 2017 RES
PP Deflection in loc Udefl U#
Gravity Nan -Gravity
TCDL: 10.00
Speed: 160 mph
TPI Sld: 2014
VERT(LL): 0.026 E 999 360
Loc R+ / R- / Rh / Rw / U / RL
F' 80 /- /- /56 117 /31
BCLL: 0.00
Enclosure: Closed
Rep Factors Used: Yes
VERT(CL): 0.051 E 999 240
BCDL: 10.00
Risk Category: II
FT/RT:10(0)(10(10)
HORZ(LL): 0.007 E - -
Wind reactions based on MWFRS
EXP: C Kzt: NA
Plate Type(s):
HORZ(TL): 0.014 E - -
F Bing Width = 94.5 Min Req = -
Des Ld: 40.00
Mean Height: 18.12 ft
WAVE
Creep Factor. 2.0
Bearing A is a rigid surface.
NCBCLL: 10.00
TCDL: 5.0 psf
Max TC CSI: 0.369
Maximum Top Chord Forces Per Ply (Ibs)
Load Duration: 125
BCDL: 5.0 psf
Max BC CSI: 0.286
Chords Tens.Comp. Chords Tens. Comp.
- Spacing: 24.0"
MWFRS Parallel Dist: h to 2h
CBC Dist a: 3.00ft
Max Web CSI: 0.384
A-B 103 -317 B-C 152 -154
Loc. from endwall: not in 9.00 it
Wgt: 33.6 Ibis
GCpi: 0.18
Maximum Bet Chord Forces Per Ply (Ibs)
VIEW Ver: 18.02.00.1016.21
Wind Duration: 1.60
Chords Tens.Comp. Chards Tens. Comp.
Lumber A-E 355 -90 E-D 365 -94
Top chord 2x4 SP #2 .
Bol chord 2x4 SP #2 Maximum Web Forces Per Ply (Ibs)
Webs 2x4 SP #3 Webs Tens.Comp. Webs Tens. Comp.
Purlins B-E 420 -318 C-D 92 -92
In lieu of structural panels or rigid ceiling use pudins
to laterally brace chords as follows:
Chord Spacing(in oc) Start(ft) End(ft)
BC 75 0.00 7.88
Apply pudins to any chords above or below fillers
at 24" OC unless shown otherwise above.
Wind
Wind loads based on MWFRS with additional C&C
member design.
Right end vertical exposed to wind pressure.
Deflection meets U360. -
Additional Notes
See standard detail package for valley details.
"WARNING" Please thoroughly review Na'A-1 ROOF TRUSSES('SELLER'), GENERAL TERMS antl OONDmONS CUSTOMER ('BUYER") ADKNOWLEDGMENP burn.
Verily design parameters anal ad oohs an Nis Truss Design Draxblg(mO)and Me Missal T. Tool ill, P.E.ReferenceStreetbefore use. Unless offender stated an Me MD. only All
eomaetprpbW3sabsused MMa TODbbevagd. As a Truss Design Engineering (i.e. Specialty Isi inwr),Meseal on any MD represents an aanphrce ofthe professional ergineeNl
q.T pnpF
�iR05bg
responail lath design of Me single Truss depicted on the MD.*.firderTP4f.Th design assumrotxxa, Istal vondil slubde or this and us's Truss foranY Building is the
. Binding he Me areponsibSdy of the Cvmer-the Cwnls sadharized agenf or me SulDesigner, in th rnntert of Me ll ere IBC, inal baldly and- and TT'll The approval of theThe
Anthony T. Tombo ill, P.E.
used Ne Truss, including handlD'in9,sturnal�msbdlbtim and bhc'uy shall Me respo sibility of Me Building Designernd eont2MreAlinolesselariinpthe TDDendN p ist.and
goidelines of Me Building Component Safety lnfomabon(Bsm) published by TPI and SSCA are referenced be general guldance. TPN defines Me responoullities and duties of Me Tmss
#80083
Designer, Truss Design Engineer and Truss Manufacturer. unless oth iee deg ed bya contrast agreed upon in will by all parties involved. The Tmss Design Engineer is NOT Me sunlit
4451 St. Lucie Blvd.
Designeror Truss System Engineer of any building. m mgralaed rema are as defined bTPln.
4pyl�l0 a118 Al RaxT�sea-PMmy T. Tanbr III,P£ RePo9�Svi W tivadmmeN. FanYfam. bponlNW Vlluul Na Moen Cmn'¢+vnalA-1 RwlTuivea-AnemY T. Tanh, III, PE
Fort Pierce, FL 34946
JANUARY 17, 2017 I TYPICAL HIP / KING JACK CONNECTION STDTLOI
CORNERSET GENERAL SPECIFICATIONS
MAX LOAD: 55 psf Roof Load, 175 mph, ASCE
=_ 7-10, Exp. B, C up to IS -Mean Roof Height
and Exposure D up to 30' Mean Roof Height.
A-1 ROOF TRUSSES
4451 ST. LUCIE BLVD.
FORT PIERCE, FL 34946 Attach King Jack w/ (3) 16d Toe
nzros-,o,o Nails @ TC & 24" Strap w/ (6)
10d x 1.5" ea. end.@ BC
Attach End Jack's
w/ (4) 16d Toe Nails @ TC
& (3) 16d Toe Nails @ BC
0
r`
ich Corner Jack's
(2) 16d Toe Nails
I TC & BC (Typ)
Attach Corner Jack's
w/ (2) 16d Toe Nails @ TC &
BC (Typ)
elfin LPq J4h Ibh1996r6il �tmvvYeplgml iPq'19v*:YW q'S�qum�aymtlbgYW�psgmq�MbbmpOYuyh lnuN01mb 9lmr.wal."nbyniv -Wq` —veht� ,Ny�„Y T. T g bo 111, P.E.
' ym/hlf YglNpebm, lYY.iN0q.01]evYmaalgYVYbYq Y.p¢ hoWtlY[YYgY WhWgotl M111L 1Y@ tlb Aelc±Ytl.xtlb MtvYgbfglM1NatYnutltq]limhgmYmYhtl _BW63
bMYghvplfmv... mA tr. "515t. Lde Bk
4Fikelhl m4MTvK9tr0P .LL M lmuh/fTntglbPY9 W4 t11,pf XP'✓rd, Y!p6mYm kld'DLl Fat A..,R 34946
m Gpr]L0111111tnotlmbl idmL]mh0.11. teP"imtttldrtblwen[amlW '4PolAietiv Mmllegivn Plq"clh 41 [tldLYal ldml].bebm.l.1.
FEBRUARY 17, 2017 I ALTERNATE GABLE END BRAetNG DETAIL 1 STDTL03
A-1 ROOF TRUSSES
4451 ST. LUCIE BLVD.
FORT PIERCE, FL UN6
ALTERNATE DIAGONAL BRACING TO THE BOTTOM -CHORD
1' - 3' MAX.
DIAG. BRACE
AT 1/3 POINTS
IF NEEDED
IT IS THE RESPONSIBILITY OF THE BLDG.
DESIGNER OR THE PROJECT ENGINEER/ARCHITECT
TO DESIGN THE CEILING DIAPHRAGM AND ITS
ATTACHMENT TO THE TRUSSES TO RESIST ALL
OUT OF PLANE LOADS THAT MAY RESULT FROM
THE BRACING OF THE GABLE ENDS.
HORIZONTAL BRACE
(SEE SECTION A -A)
TRUSSSES e
I— 24' O.C.
2XG DIAGONAL BRACE SPACED 48'
O.C. ATTACHED TO VERTICAL WITH
(4) - 16d NAILS, AND ATTACHED TO
BLOCKING WITH (5) - IOd COMMONS.
NAIL DIAGONAL BRACE TO
PURLIN WITH tTWO 16d NAILS.
2X4 PURLIN FASTENED TO FOUR
TRUSSES WITH (2) - 16d NAILS
EACH. FASTEN PURLIN TO BLOCKING
W/ (2) - 15d NAILS (MIN.).
/ PROVIDE 2X4 BLOCKING BETWEEN
THE TRUSSES SUPPORTING THE -
BRACE AND THE TWO TRUSSES ON
EITHER SIDE AS NOTED. TOENAIL
\BLOCKING TO TRUSSES WITH (2) -
\ 10d NAILS AT EACH ENO. ATTACH
DIAGONAL BRACE TO BLOCKING WITH.
(5) - 10d COMMON WIRE NAILS.
ENO WALL
CEILING SHEATHING
BRACING REQUIREMENTS FOR STRUCTURAL GABLE TRUSSES
STRUCTURAL GABLE TRUSSES MAY BE BRACED AS NOTED:
METHOD 1: ATTACH A MATCHING GABLE TRUSS TO THE INSIDE FACE
OF THE STRUCTURAL GABLE AND FASTEN PER THE
FOLLOWING NAIL SCHEDULE.
METHOD 2: ATTACH 2X_ SCABS TO THE FACE OF EACH VERTICAL
MEMBER ON THE STRUCTURAL GABLE PER THE FOLLOWING
NAILING SCHEDULE. SCABS ARE TO BE OF THE SAME SCAB ALONG
SIZE, GRADE, AND SPECIES AS THE TRUSS VERTICALS. VERTICAL
NAILING SCHEDULE:
- FOR WINO SPEEDS 120 MPH (ASCE 7-98, 02, 05), 150 MPH (ASCE
7-10) OR LESS, NAIL ALL MEMBERS WITH ONE ROW OF IOd (.131'
X 3') NAILS SPACED 6' O.C.
- FOR WINO SPEEDS GREATER 120 MPH (ASCE 7-98, 02, 05), 150
MPH (ASCE 7-10) NAIL ALL MEMBERS WITH TWO ROWS OF 10d
(.131'X3') NAILS SPACED 6' O.C. (2X4 STUDS MINIMUM).
MAXIMUM STUD LENGTHS ARE LISTED ON PAGE 1. ALI
BRACING METHODS SHOWN ON PAGE i ARE VALID
AND ARE TO BE FASTENED TO THE SCABS OR
VERTICAL STUDS OF THE STANDARD GABLE TRUSS
ON THE INTERIOR SIDE OF THE STRUCTURE.
---I—URAL
TRUSS
Y��Itl
STRUCTURAL / AN AOEOUATE DIAPHRAGM OR OTHER METHOD OF BRACING
GABLE TRUSS / MUST BE PRESENT TO PROVIDE FULL LATERAL SUPPORT OF
THE BOTTOM CHORD TO RESIST ALL OUT OF PLANE LOADS.
THE BRACING SHOWN IN THIS DETAIL IS FOR
VERTICAL/STUDS ONLY.
NOTE: THIS DETAIL IS TO BE USED ONLY FOR/
STRUCTURAL GABLES WITH INLAYED
STUDS. TRUSSES WITHOUT INLAYED
STUBS ARE NOT ADDRESSED HERE. /
STANDARD GABLE
\S I
JULY 17, 2017 STANDARD PIGGYBACK TRUSS STDTL04
CONNECTION DETAIL
THIS DETAIL IS APPLICABLE FOR THE FOLLOWING WIND CONDITIONS:
ASCE7-98,ASCE 7-02,ASCE7-05, ASCE7-10 WIND STANDARDS UNDER ALL ENCLOSURE AND EXPOSURE
CONDITIONS AS LONG AS NO UPLIFT EXCEEDS 377 LBS. REFER TO ACTUAL PIGGYBACK TRUSS DESIGN
DRAWING FOR UPLIFTS.
� NOTE: THIS DETAIL IS VALID FOR ONE PLY TRUSSES SPACED 24' O.C. OR LESS.
rROOF TRUSSES
1 ST. LUCIE BLVD.
T PIERCE, FL MW
772409-1010
PIGGYBACK TRUSS
REFER TO ACTUAL TRUSS DESIGN DRAWING FOR
ADDITIONAL PIGGYBACK TRUSS INFORMATION.
SPACE PURLINS ACCORDING TO THE MAXIMUM
SPACING ON THE TOP CHORD OF THE BASE TRUSS
(SPACING NOT TO EXCEED 24' O.CJ A PURLIN
TO BE LOCATED AT EACH BASE TRUSS JOINT.
ATTACH PIGGYBACK TRUSS TO THE BASE TRUSS WITH 2- X B'
TEE -LOCK MULTI -USE CONNECTION PLATES SPACED 48' O.C. PLATES
SHALL BE PRESSED INTO THE PIGGYBACK TRUSS AT48' O.C.
STAGGERED FROM EACH FACE AND NAILED TO THE BASE TRUSS WITH
-FOUR (4) 6d (I.5- X 0.099') NAILS IN EACH PLATE TO ACHIEVE A MAXIMUM
UPLIFT CAPACITY OF 377 LBS. AT EACH 2' X 8' TEE -LOCK MULTI -USE
CONNECTION PLATE. (MINIMUM OF 2 PLATES)
ATTACH EACH PURLIN TO THE TOP CHORD OF
THE BASE TRUSS.
(PURLINS AND CONNECTION BY OTHERS)
BASE TRUSS
REFER TO ACTUAL TRUSS DESIGN DRAWING FOR
ADDITIONAL BASE TRUSS INFORMATION.
AnAfwny T. Twbo 1i1, P.E.
80083
FOR R.re, FL 36946
Uek mlf.
JULY-17, 2017 I TRUSSED VALLEY SET DETAIL -SHEATHED 1 STDTL05
AA ROOF TRUSSES
4451 ST. LUCIE BLVD.
FORT PIERCE, FL 34946
772409-1010
VALLEY TRUSS
(TYPICAL)
GABLE END, COMMON
TRUSS, OR GIRDER
TRUSS
GENERAL SPECIFICATIONS:
1. NAIL SIZE =3'X 0.131'=10d
2. WOOD SCREW = 4.5' WS45 USP OR EQUIVALENT.
3. INSTALL SHEATHING TO TOP CHORD OF BASE TRUSSES.
4. INSTALL VALLEY TRUSSES (24' O.C. MAXIMUM)AND
SECURE TO BASE TRUSSES AS PER DETAIL 'A.
5. BRACE VALLEY WEBS IN ACCORDANCE WITH THE
INDIVIDUAL DESIGN DRAWINGS.
6. NAILING DONE PER NOS -01.
7. VALLEY STUD SPACING NOT TO EXCEED 48' O.C.
BASE TRUSSES
^"".E END, COMMON
;S. OR GIRDER TRUSS
TRUSS CRITERIA:
SECURE VALLEY TRUSS
WIND DESIGN PER ASCE 7-98. ASCE 7-02, ASCE 7-05: 146 MPH
W/ ONE ROW OF 10d
WIND DESIGN PER ASCE 7-10: 170 MPH
NAILS 6' O.C.
MAX MEAN ROOF HEIGHT =30 FEET
ROOF PITCH = MINIMUM 3/12 MAXIMUM 6112
CATERGORY II BUILDING
EXPOSURE
WIND DURATION OF LOAD INCREASE: 1.60
MAX TOP CHORD TOTAL LOAD = 50 PEP
ATTACH 2X4 CONTINUOUS #2
MAX SPACING = 24' O.C. (BASE AND VALLEY)
SYP TO THE ROOF W/TWO USP
MINIMUM' REDUCED DEAD LOAD OF 6 PSF ON THE TRUSSES.
WS45(1/4' X 4.5') WOOD SCREWS
_
INTO EACH BASE TRUSS.
nFTAII A
Auft., T. Twbo III, PE
a W083
a4.1 SG Lucie BIM.
Fat Pierce, FL 34-46
FEBRUARY 5, 2018 1 TRUSSED VALLEY SET DETAIL I STDTL06
A-1-ROOF TRUSSES
4451 ST. LUCIE BLVD,
FORT PIERCE, FL 34946
772-409-1010
VALLEY TRUSS
(TYPICAL)
SECURE VALLEY TRUSS
W/ ONE ROW OF 10d
NAILS 6' O.C.
GABLE END, COMMON
TRUSS, OR GIRDER
TRUSS
DETAIL A
(NO SHEATHING) N.T.S.
GENERAL SPECIFICATIONS:
1. NAIL SIZE =3'X 0.131'=10d
2. WOOD SCREW = 3' WS3 USP OR EQUIVALENT.
3. INSTALL VALLEY TRUSSES (24- O.C. MAXIMUM) AND SECURE PER DETAIL
'A'
4. BRACE VALLEY WEBS IN ACCORDANCE WITH THE INDIVIUAL DESIGN
DRAWINGS.
5. BASE TRUSS SHALL BE DESIGNED WITH A PU RUN SPACING EQUIVALENT
TO THE RAKE DIMENSION OF THE VALLEY TRUSS SPACING.
6. NAILING DONE PER NOS - 01.
7. VALLEY STUD SPACING NOT TO EXCEED 48' O.C.
P �2
SEE DETAIL'A'
BELOW (TYP.)
ATTACH ZX4 CONTINUOUS #2
SYP TO THE ROOF W/ TWO USP
WS3 (1/4-X X) WOOD SCREWS
INTO EACH BASE TRUSS.
BASE TRUSSES
GABLE END, COMMON
TRUSS. OR GIRDER
VALLEY TRUSS TRUSS
(TYPICAL)
WIND DESIGN PER ASCE 7-98, ASCE 7-02, ABLE 7-05: 146 MPH
WIND DESIGN PER ASCE 7.10: 170 MPH
MAX MEAN ROOF HEIGHT = 30 FEET
ROOF PITCH = MINIMUM 3/12 MAXIMUM 6112
CATERGORY II BUILDING
EXPOSUREC
WIND DURATION OF LOAD INCREASE: 1.60
MAX TOP CHORD TOTAL LOAD = 50 PSF
MAX SPACING = 24' O.C. (BASE AND VALLEY)
MINIMUM REDUCED DEAD LOAD OF 6 PSF ON THE TRUSSES.
MttIanY T. Twtm III, P.E
r SM3
4451 St. 4 le Bled.
Fort Reim, FL 319 6
W^IOOO NBIIBtltnrm,44vP 1. NaEOIM1PL Gpefxiimd4islmmxleePBmi�peb7iul Yeaip.�am
•JULY'17, 2017
IGH WIND VELOCITY)
A-1 ROOF TRUSSES
4451 ST. LUCIE BLVD.
FORT. PIERCE, FL 34946
772409.1010
ATTA(
WIND DESIGN PER ASCE 7.98, ASCE 7-
WIND DESIGN PER ASCE 7-10: 170 MPI
MAX MEAN ROOF HEIGHT = 30 FEET
CATERGORY II BUILDING
EXPOSURE B OR C
WIND DURATION OF LOAD INCREASE:
MAX TOP CHORD TOTAL LOAD =50 PS
MAX SPACING = 24' O.C. (BASE AND V1
SUPPORTING TRUSSES DIRECTLY UNDER VALLEY TRUSSES MUST BE
DESIGNED WITH A MAXIMUM UNBRACED LENGTH OF 7 -10' ON AFFECTED
TOP CHORDS.
NOTES:
1. SHEATHING APPLIED AFTER INSTALLATION OF VALLEY TRUSSES.
2. THIS DETAIL IS NOT APPLICABLE FOR SPF-S SPECIES LUMBER.
FOR BEVELED BOTTOM
CHORD, CLIP MAY BE APPLIED
TO EITHER FACE.
0
(gpioi C 20151414dfmus-40:ag L icbN..L
CLIP MAY BE APPLIED
TO THIS FACE UP TO A
NON -BEVELED MAXIMUM 6112 PITCH
BOTTOM CHORD
CLIP MUST BE APPLII
THIS FACE WHEN
EXCEEDS 6112 (MAX
12/12 F
W i nnas-Inl.g L Ts.W eat
Antkny T. Tambo III, P.E
s S0083
4451 St W. a 81W.
Fort Pierce, R. 34946
FEBRUARY 17, 2017 1 STANDARD GABLE END DETAIL I STDTL08
A-1 ROOF TRUSSES
4451 ST. LUCIE BLVD,
FORT PIERCE. FL 34946
772409-1010
TYPICAL 2X4 L-BRACE
NAILED TO 2X4 VERTICALS
W/IDd NADS, 6' O.C.
VERT
STUD
SECTION B-B
TRUSS GEOMETRY AND CONDITIONS
SHOWN ARE FOR ILLUSTRATION ONLY.
VERTICALVIBRACE
2X6 SP OR SPF
STUD02
DIAGONAL
BRACE
(4) - 16d
NAILS16d
NAILS
SPACED 6' O.C.
(2) IOd NAILS
INTO 2X62X6
SP OR
SPF k2
2X4 SP ORSPF
02L
HORIZONTAL
NAILED TO
ERTICALS
SECTION A -A
W/(4) - 10d NAILS
OIAGONAL BRACE 4' - 0' O.C. MAX.
'
SEE INDIVIDUAL ENGINEERING DRAWINGS
TRUSS DESIGN CRITERIA.
12
PROVIDE 2%4 BLOCKING BETWEEN
fAFOR THE
FIRST TWO TRUSSS AS
Q VARIES TO COMMON TRUSS
GETO TRUSSES
* WITH
(2) - 10d NAILS AT EACH ENO.
ATTACH DIAGONAL BRACE TO
BLOCKING WITH (5) - 10d NAILS
A
**
(4) Bd NAILS MINIMUM,
ROOF
3X4=
PLYWOOD SHEATHING TO
SHEATHING
B
2%4 STO SPF BLOCK
*
DIAGONAL BRACING ** L - BRACING REFER
/
REFER TO SECTION A -A TO SECTION B-B 24' MAX.
NOTE:
lOd
1.
MINIMUM GRADE OF 02 MATERIAL IN THE TOP AND BOTTOM CHORDS.
/
NAILS.
2.
CONNECTION BETWEEN BOTTOM CHORD OF GABLE ENO TRUSS AND WALL TO
12' MAX
BE PROVIDED BY PROJECT ENGINEER OR ARCHITECT.
3.
BRACING SHOWN IS FOR INDIVIDUAL TRUSS ONLY. CONSULT BLOG.
ARCHITECT OR ENGINEER FOR TEMPORARY AND PERMANENT BRACING OF ROOF
SYSTEM.
/
4.
'L' BRACES SPECIFIED ARE TO BE FULL LENGTH, SPF OR SP N3 OR
BETTER WITH ONE ROW OF 10d NAILS SPACED 6' O.C.
TRUSSES B 24' O.C.
DIAGONAL BRACE TO BE APPROXIMATELY 45 DEGREES TO ROOF DIAPHRAGM
/
_5.
6.
AT 4' - 0' O.C.
CONSTRUCT HORIZONTAL BRACE CONNECTING A 2X6 AND A 2X4 AS SHOWN
2X6 OIAGCNAL BRACE
SPACED 48' O.C. ATTACHED
WITH 16d NAILS SPACED 6' O.C. HORIZONTAL BRACE TO BE LOCATED AT
TO
VERTICAL WITH (4) -
THE MIOSPAN OF THE LONGEST GABLE STUD. ATTACH TO VERTICAL GABLE
_ 16d
NAILS, AND ATTACHED
STUOS WITH (3) 10d NAILS THROUGH 2X4 (REFER TO SECTION A -A)
TO
BLOCKING WITH (5) -
7.
GABLE STUD DEFLECTION MEETS OR EXCEEEDS L/240. OIAG.
BRACE 10d
10
NAILS.
S.
THIS DETAIL DOES NOT APPLY TO STRUCTURAL GABLES. AT 1/3
POINTS
9.
00 NOT USE FLAT BOTTOM CHORD GABLES NEXT TO SCISSOR TYPE IF
NEEDED
10.
T
TRUSSES.
10d AND 16d NAILS ARE 0.131'X3.0' AND 0.131'X35' COMMON WIRE NAILS
HORIZONTAL BRACE
RESPECTIVELY.
(SEE SECTION A -A)
11.
SOUTHERN PINE LUMBER DESIGN VALUES ARE THOSE EFFECTIVE 06-01-12
BY SPIB/ALSC.
ENO
WALL
MINIMUM STUD
SIZE SPECIES
AND GRADE
STUD
SPACING
WITHOUT
BRACE
2X4
L - BRACE
DIAGONAL
BRACE
(2) DIAGONAL
BRACES AT
1/3 POINTS
MAXIMUM STUD LENGTH
2(4SPC31STUD
12'O.C.
3-8-10
R41
6{H11
11-1-13
2X4SPR31STUD
16'O.C.
3-3-10
4-9-12
6&11
91015
2X4 SP 931 STUD
24'O.C.
24-6
3-1w
54-12
8-1-2
ZX4 SP P2
12'O.C.
3.10-16
5&11
6&11
11&14
2X4 SP tR
16'O.C.
3-&ll
4-9-12
66-11
1w
2X4 SP #2
24'O.C.
3.1-4
3.11-3
6.2-9
93.13
DIAGONAL BRACES OVER 6' - 3' REQUIRE A 2X4 T-BRACE ATTACHED TO ONE
EDGE. DIAGONAL BRACES OVER 12' - 6' REQUIRE 2X4 I -BRACES ATTACHED TO
BOTH EDGES. FASTEN T AND I BRACES TO NARROW EDGE OF DIAGONAL BRACE
WITH I0d NAILS 6' O.C., WITH 3' MINIMUM ENO DISTANCE. BRACE MUST COVER
90% OF DIAGONAL LENGTH. T OR I BRACES MUST BE 2X4 SPF #2 OR SP #2.
MAX MEAN ROOF HEIGHT =30 FEET
EXPOSURE B OR
ASCE 7-10 190 MPH
DURATION OF LOAD INCREASE: 1.60
I -IJI .,-,..,� , I-...r..,� .. I , .'� STDTL09
FEBRUARY17,2017 WITH 2X BRACE ONLY
NOTES:
T-BRACING / I -BRACING TO BE USED WHEN CONTINUOUS LATERAL BRACING
IS IMPRACTICAL. T-BRACE / I -BRACE MUST COVER 90% OF WEB LENGTH.
THIS DETAIL NOT TO BE USED TO CONVERT T-BRACE-/ I -BRACE WEBS TO
CONTINUOUS LATERAL BRACED WEBS,
A-1 ROOF TRUSSES
4451 ST. LUCIE BLVD.
FORT PIERCE. FL S4B46
7724091010
NAILING PATTERN
T-BRACE SIZE
NAIL SIZE
NAIL SPACING
2X4 OR 2X6 OR 2X8
10d
6" O.C.
NOTE: NAIL ALONG ENTIRE LENGTH OF T-BRACE / ]-BRACE (ON
TWO-PLY TRUSSES NAIL TO BOTH PLIES)
NAILS
BRACE
SIZE FOR ONE -PLY
TRUSS
SPECIFIED CONTINUOUS ROWS OF
LATERAL BRACING
WEB SIZE
1
2
2X3 OR 2X4
2X4 T-BRACE
2X4 I -BRACE
2X6
2X6 T-BRACE
2X6 I -BRACE
2X8
2X8 T-BRACE
2X8 I -BRACE
BRACE
SIZE FOR TWO-PLY
TRUSS
SPECIFIED CONTINUOUS ROWS OF
LATERAL BRACING
WEB SIZE
.1
2
2X3 OR 2X4
2X4 T-BRACE
2X4 I -BRACE
2X6
2X6 T-BRACE
2X6 I -BRACE
2X8
2X8 T-BRACE
2X8 I -BRACE
T-BRACE / I -BRACE MUST BE SAME SPECIES
AND GRADE (OR BETTER) AS WEB MEMBER.
NAILS
WEB
NAILS
I -BRACE
NAILS
WEB
T-BRACE
SECTION DETAILS
FEBRUARY17,2017 1 LATERAL BRACING RECOMMENDATIONS I STDTL10
TO MINIMIZE VIBRATION COMMON TO ALL SHALLOW FRAMING SYSTEMS,
2XG 'STRONGBACK' IS RECOMMENDED, LOCATED EVERY 8 TO 10 FEET
ALONG A FLOOR TRUSS.
C
NOTE
1: 2X6 STRONGBACK ORIENTED VERTICALLY MAY BE POSITIONED
DIRECTLY UNDER THE
C
TOP CHORD OR DIRECTLY ABOVE THE BOTTOM CHORD, SECURELY FASTENED
TO THE TRUSS USING ANY
A-1ROOFTRUSSES
OF THE
METHODS ILLUSTRATED BELOW.
4451 ST. LUCIE BLVD.
FORT PIERCE, FL 34946
NOTE
2: STRONGBACK BRACING ALSO SATISFIES THE LATERAL BRACING
REOUIREMENTS FOR THE
T12-09}la to
BOTTOM
CHORD OF THE TRUSS WHEN IT IS PLACED ON TOP OF THE BOTTOM
CHORD, IS CONTINUOUS
FROM ENO TO ENO, CONNECTED WITH A METHOD OTHER THAN METAL FRAMING ANCHOR, AND PROPERLY
CONNECTED, BY OTHERS, AT THE ENDS.
INSERT WOOD SCREW THROUGH
OUTSIDE FACE OF CHORD INTO
EDGE OF STRONGBACK (00 NOT
USE METAL
ANCHOR TO
FRAMING
TTACH TO VERTICAL CCC ATTACH TO VERTICAL
SCAB WITH
USE DRYWALL TYPE SCREWS)
OO TOPCTTACHHORD1
\�Ell
ILS (0.131' X 3')d NAILS (0131�3X 3')ad
ATTACHVER3I)AL
TTA
H0TO
WEB WITH (3) - Uld
r
I
\
NAIL
BLOCKING BEHIND THE VERTICAL
WEB IS RECOMMENDED WHILE
NAILING THE STRONGBACK
USE METAL FRAMING ATTACH TO VERTICAL
ANCHOR TO ATTACH WEB WITH (3) - 10d
TO BOTTOM CHORD NAILS (0131' X 3')
ATTACH 2X4 VERTICAL
TO FACE OF TRUSS,
FASTEN TO TOP AND
BOTTOM CHORD WITH
(2) - 10d NAILS (0.131'
X 3') IN EACH CHORD
ATTACH TO VERTICAL
SCAB WITH (3) - 10d
NAILS (0.131' X 3')
TRUSS 2X6 r 4' - 0' WALL
STRONGBACK(TYPICAL SPLICE) � (BY OTHERS)
ATTACH TO CHORD
WITH (2) #12 X 3'
WOOD SCREWS
(0.216' OIA.)
INSERT SCREW THROUGH
OUTSIDE FACE OF CHORD INTO
EDGE OF STRONGBACK (00 NOT
USE DRYWALL TYPE SCREWS)
THE STRONGBACKS SHALL BE SECURED AT THEIR ENOS TO AN ADEQUATE SUPPORT,
DESIGNED BY OTHERS. IF SPLICING IS NECESSARY, USE A 4' - 0' LONG SCAB
CENTERED ON THE SPLICE AND JOINED WITH (12) - 10d NAILS (0.131- X 3-)
EQUALLY SPACED.'
ALTERNATE METHOD OF SPLICING:
OVERLAP STRONGBACK MEMBERS A MINIMUM OF 4' - 0' AND FASTEN WITH (12) -
10d NAILS (0.131' X X) STAGGERED AND EQUALLY SPACED (TO BE USED ONLY
WHEN STRONGBACK IS NOT ALIGNED WITH A VERTICAL).
BLOCKING
(BY OTHERS)
FEBRUARY 17, 2017 1 LATERAL TOE -NAIL DETAIL I STDTL11
A-1 ROOF TRUSSES
4451 ST, LUCIE BLVD.
FORT PIERCE, FL 34946
n240&1010
NOTES:
1. TOE -NAILS SHALL BE DRIVEN AT AN ANGLE OF 45' WITH THE MEMBER
AND MUST HAVE FULL WOOD SUPPORT (NAIL MUST BE DRIVEN
THROUGH AND EXIT AT THE BACK CORNER OF THE MEMBER END AS
SHOWN).
2. THE END DISTANCE, EDGE DISTANCE. AND SPACING OF NAILS SHALL
BE SUCH AS TO AVOID UNUSUAL SPLITTING OF THE WOOD.
3. ALLOWABLE VALUE SHALL BE THE LESSER VALUE OF THE TWO
SPECIES FOR MEMBERS OF DIFFERENT SPECIES.
TOE -NAIL SINGLE SHEAR VALUES
PER NOS 2001_(LB/NAIL)
CIA
SP
OF
HF
SPF
SPF-5
.131
88.0
80.6
69.9
68.4
59.7
z
.135
93.5
85.6
74.2
72.6
63.4
o
J
ri
.162
108.8
99.6
86.4
84.5
73.8
.128
74.2
67.9
58.9
57.6
50.3
�
0
.131
75:9
69.5
60.3
59.0
51.1
h
N
.148
81.4
74.5
64.6
63.2
52.5
M
VALUES SHOWN ARE CAPACITY PER TOE -NAIL.
APPLICABLE DURATION OF LOAD INCREASES MAY 8E APPLIED.
EXAMPLE:
(3) - 16d NAILS (0.162' CIA. X 3.5') WITH SPF SPECIES BOTTOM CHORD
FOR LOAD DURATION INCREASE OF 1.15:
3 (NAILS) X 84.S (LB/NAIL) X 1.15 (OOL) = 291.5 LB MAXIMUM CAPACITY
ANGLE MAY
VARY FROM
30' TO 60'
45.00°
ANGLE MAY
VARY FROM
30` TO 60°
THIS DETAIL IS ONLY APPLICABLE TO
THE THREE END DETAILS SHOWN BELOW,
VIEWS SHOWN ARE FOR ILLUSTRATION PURPOSES ONLY.
SIDE VIEW
(2X3) 2 NAILS
NEAR SIDE
NEAR SIDE
SIDE VIEW
(2X4) 3 NAILS
NEAR SIDE
NEAR SIDE
NEAR SIDE
45.00'
SIDE VIEW
(2X3) 2 NAILS
NEAR SIDE
NEAR SIDE
NEAR SIDE
NEAR SIDE
ANGLE MAY
VARY FROM
30° TO 60°
45.00'
FEBRUARY 17, 2017 1 UPLIFT TOE -NAIL DETAIL I STDTL12
A-1 ROOF TRUSSES
4451 ST. LUCIE BLVD.
FORT PIERCE, FL 04946
7nAO0 1010
THIS DETAIL SHALL BE USED FOR A CONNECTION
RESISITING UPLIFT FORCES ONLY. BUILDING DESIGNER
IS RESPONSIBLE FOR LOADS IN OTHER DIRECTIONS.
TOE -NAIL WITHORAWAL VALUES
PER NOS 2005 (LB/NAIL)
OIA.
SP
OF
HF
SPF
SPF-S
7
.131
59
46
32
30
20
z
O
J
.135
60
48
33
30
20
N
.162
72
58
39
37
25
J
=
O
.128
54
42
28
27
19
z .
z
O
.131
55
43
29
28
19
L1
J
.148
62
48
34
31
21
J
N
z
.120
51
39
27
26
17
CO
z
.128
49
38
26
25
17
O
.131
51
39
27
26
17
J
.148
57
44
31
28
20
M
NOTES:
L TOE -NAILS SHALL BE DRIVEN AT AN ANGLE OF 30' WITH THE MEMBER AND STARTED 1/3 THE LENGTH OF THE NAIL FROM THE
MEMBER ENO AS. SHOWN.
2. THE END DISTANCE, EDGE DISTANCE, AND SPACING OF NAILS SHALL BE SUCH AS TO AVOID UNUSUAL SPLITTING OF THE WOOD.
3. ALLOWABLE VALUE SHALL BE BASED ON THE SPECIE WITH LOWER NAIL CAPACITY BETWEEN THE TWO MEMBERS IN THE CONNECTION.
VALUES SHOWN ARE CAPACITY PER TOE -NAIL.
APPLICABLE DURATION OF LOAD INCREASES MAY BE APPLIED.
EXAMPLE:
(3) - IGd NAILS WAGE' CIA. X 3.5') WITH SPF SPECIES TOP PLATE
FOR WIND OOL OF 1.33:
3 (NAILS) X 37 (LB/NAIL) X 1.33 (OOL FOR WINO) = 14B LB MAXIMUM ALLOWABLE UPLIFT REACTION DUE TO WINO
FOR WINO OOL OF 1.60:
3 (NAILS) X 37 (LB/NAIL) X 1.60 IDOL FOR WINO) = 177 LB MAXIMUM ALLOWABLE, UPLIFT REACTION CUE TO WIND
IF THE UPLIFT REACTION SPECIFIED ON THE TRUSS DESIGN DRAWING EXCEEDS 147 LBS (177 LBS) BUILDING
DESIGNER IS RESPONSIBLE TO SPECIFY A DIFFERENT CONNECTION.
•.a USE (3) TOE -NAILS ON 2X4 BEARING WALL
•.. USE (4) TOE -NAILS ON 2X6 BEARING WALL
NEAR SIDE
FAR S
)E
TOP PLATE
OF WALL
VIEWS SHOWN ARE FOR
ILLUSTRATION PURPOSES ONLY
JAIL
IA1L
SIDE VIEW END VIEW
FEBRUARY 5, 2016
A-1 ROOF TRUSSES
4451 ST. LUCIE BLVD.
FORT PIERCE, FL 34946
772-409-1010
-I .5 x 4
TYP 2x2 NAILER ATTACHMENT I STDTL13
2x2 NAILER ATTACHMENT
GENERAL SPECIFICATIONS
MAX LOAD: 55 psf Roof Load, 170 mph, ASCE
7-10, 29'-0" Mean Height, Exp. B, C or D.
April 11, 2016 TYPICAL ALTERNATE BRACING DETAIL STDTLI4
FO EXTERIOR FLAT GIRDER TRUSS
�i!3RQ F TRUSSES
4461 ST`LUCIE BLVD.
FORT PIERCE, FL 34946
772-409-1010
(4) 12d
TRUSS 2411 O.C.
UPLIFT CONNECTION
(SEE ROOF TRUSS)
EXTERIOR FLAT
GIRDER
12
VARIES
(4) 12d
MAX 30" (21-6")
2x6 #2 SP (Both Faces)
24" O.C.
SIMPSON H5
MMuy T. Tp Ill. P.
= WUS3
�+51 St, m .8Nd.
faR Pierce. R P946
STANDARD REPAIR DETAIL FOR BROKEN CHORDS, WEBS, AND STDTL15
FEBRUARY 17, 2017 DAMAGED OR MISSING CHORD SPLICE PLATES .
A-1 ROOF TRUSSES
4451 ST, LUCIE BLVD.
FORT PIERCE, FL 34946
772409-1010
I�
jyP�
TOTAL NUMBER
OF NAILS EACH
SIDE OF BREAK *
X
(INCHES)
MAXIMUM FORCE (LBS) 157 LOAD DURATION
SP
OF
SPF
HF
2X4
2X6
2X4
2X6
2X4
2X6
2X4
2X6
2X4
2X6
20
30
24"
1706
2559
1561
2342
1320
1980
1352
2028
26
39
30"
2194
3291
2007
3011
1697
2546
1738
2608
32
48
36"
2681
4022
2454
.3681
1O74
3111
2125
3157
38
57
42"
3169
4754
2900
4350
2451
1
3677
2511
3767
44
66
48"
3657-
5485
3346
51119
21129
4243
2898
4347
DIVIDE EQUALLY FRONT AND BACK
ATTACH 2X_ SCAB OF THE SAME SIZE AND GRACE AS THE BROKEN MEMBER TO EACH FACE OF
THE TRUSS ( CENTER ON BREAK. OR SPLICE) WITH 10d NAILS (TWO ROWS FOR 2X4, THREE
ROWS FOR 2XG) SPACED 4' O.C. AS SHOWN (.131' OIA. X 3').
STAGGER NAIL SPACING FROM FRONT FACE AND BACK FACE FOR A NET 2' O.C. SPACING IN
THE MAIN MEMBER. USE A MIN. 3' MEMBER END DISTANCE.
THE LENGTH OF THE BREAK (C) SHALL NOT EXCEED 12'. (C=PLATE LENGTH FOR SPLICE REPAIRS)
THE MINIMUM OVERALL SCAB LENGTH RECUIRED (L) IS CALCULATED AS FOLLOWS: L = (2) X + C
• 10d NAILS NEAR SIDE
+ 10d NAILS FAR SIDE
NOTES
BREAK
X
X- MIN
S' MIN
TRUSS CONFIGURATION
AND BREAK LOCATIONS
FOR ILLUSTRATIONS ONLY
THE LOCATION OF THE BREAK MUST BE GREATER THAN OR EQUAL TO
THE REQUIRED X DIMENSION FROM' ANY PERIMETER BREAK OR HEEL JOINT
AND A MINIMUM OF S" FROM ANY INTERIOR JOINT (SEE SKETCH ABOVE).
DO NOT USE REPAIR FOR JOINT SPLICES
1. THIS REPAIR DETAIL IS TO BE
ODES NOT IMPLY THAT THE REM
TRUSS SHALL BE INSPECTED TO
THE REQUIRED REPAIRS ARE FIR
SUPPORTING THE LOADS INOICAI
2. ALL MEMBERS MUST BE RETURNI
AND HELD IN PLACE DURING API
3. THE ENO DISTANCE, EDGE GIST,
UNUSUAL SPLITTING OF THE WC
4. WHEN NAILING THE SCABS, THE
LOOSENING OF THE CONNECTOR
S. THIS REPAIR IS TO BE USED F
6. THIS REPAIR IS LIMITED TO TR
JLY FOR THE APPLICATION SHOWN. THIS REPAIR
PORTION OF THE TRUSS'IS UNDAMAGED. THE ENTIRE
( THAT NO FURTHER REPAIRS ARE REQUIRED, WHEN
APPLIED, THE TRUSS WILL BE CAPABLE OF
'HEIR ORIGINAL POSITIONS BEFORE APPLYING REPAIR
IN OF REPAIR.
JO SPACING OF NAILS SHALL BE SUCH AS TO AVOID
A BACKUP WEIGHT IS RECOMMENCED TO AVOID
AT THE JOINTS OR SPLICES.
LE PLY TRUSSES IN THE 2X_ ORIENTATION ONLY.
dITH NO MORE THAN THREE BROKEN MEMBERS.
FEBRUARY17,2017 SCAB APPLIED OVERHANGS I STDTL16
A-( ROOF TRUSSES
4451 ST. LUCIE BLVD.
FORT PIERCE, FL 3 946
772-409,1010
TRUSS CRITERIA:
LOADING: 40-10-0-10
DURATION FACTOR: 1.15
SPACINGS 24. O.C.
TOP CHORD: 2X4 OR 2X6
PITCH: 4/12 - 12/12
HEEL HEIGHT: STANDARD HEEL UP TO 12' ENERGY HEEL
ENO BEARING CONDITION
NOTES'.
1. ATTACH 2X SCAB (MINIMUM k2 GRADE SPF, HF, SP, OF) TO ONE FACE OF TRUSS
WITH TWO ROWS OF 10d COMMON WIRE NAILS (.148' DIA. X 3') SPACED 6' O.C.
2. THE ENO DISTANCE, EDGE DISTANCE, AND SPACING OF NAILS SHALL BE SUCH
AS TO AVOID UNUSUAL SPLITTING OF THE WOO&
3. WHEN NAILING THE SCABS, THE USE OF A BACKUP WEIGHT IS RECOMMENOED TO
AVOID LOOSENING OF THE CONNECTOR PLATES AT THE JOINTS OR SPLICES.
2X SC
NOTE' TRUSS BUILT WITHOUT AN OVERHANG. THIS DETAIL IS NOT TO BE USED
WHEN OVERHANG HAS BEEN BROKEN OFF.
IMPORTANT
THIS DETAIL TO BE USED ONLY WITH TRUSSES (SPANS LESS THAN 40') SPACED 24'
O.C. MAXIMUM AND HAVING PITCHES BETWEEN 4/12 AND 12/12 AND TOTAL TOP CHORD
LOADS NOT EXCEEDING 50 PSF.-
TRUSSES NOT FITTING THESE CRITERIA SHOULD BE EXAMINED INDIVIDUALLY.
REFER TO INDIVIDUAL TRUSS DESIGN
FORPLATE SIZES AND LUMBER GRADES