FIELD AND LABORATORY REPORT COVER PAGE St, Lucie COUnty
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 69 9 I
5341 Oakland Lake Circle Permit #,Ft. Pierce, St. Lucie County, FL
I
As requested, Universal Engineering Sciences, Inc. (LES) representative(s) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No. Date Type of Report
106660-1 1 02/06/2019 In -Place Density Test Report w/Activity Record
We hope this information is sufficient for vour immediate needs. If you have anv auestions_ nleace dh not hesdate to onntart
the undersigned.
RECEIVED
MAR 18 019
ST. Lucie County, Permitting
Attachments (1)
Sincerely, 0%
Universal Engineering Sciences, Inc.
Certificate of Authorization No; 00000549
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
[CC Email. cbugg@nvrinc.com; rhager@nvdne.com; sign/seal MAIL to ryan homes at5369 Oakland Lake, Vero Beach, FL 32966
Revised May 2015
820
Y 1
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering •Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
1.1E6 r'roject No: 0310.1700251.0042
LIES DOCS No:
UES Report No: 106660-1 ARC 020619
On -Site Time (hrs): 1.00
Lab Time (hrs): 0.00
Travel Time (hrs): 0.25
Total Time (hrs): 1.25
Avenue, Rockledge, FL 32956 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 69
5341 Oakland Lake Circle Permit #,Ft. Pierce, St. Lucie County, FL
Dates of Activity: Wednesday, 06 February, 2019
Technician: Cliff Cherrnay
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing forthe House pad.
While on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for House
pad. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records.
1UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
Avenue, Rockledge, FL 32965 - P: 321.638.0808 - F: 321.638.0978
UES Project No: 0310.1700251.0042
UES DOCS No:
LIES Report No: 106660-1 DT 020619
In -Place Denser Test Report
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 69
5341 Oakland Lake Circle Permit #,Ft. Pierce, St. Lucie County, FL
Area Tested: House pad
Type of Test: Field` ASTM D-6938 Nuclear Gauge Method Date of Test: 02/06/2019
Lab: ASTM D1557 Modified Proctor
Technician: Cliff Cherrnay
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the underivinc soils below the tested deoths_
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
, Field.
Moisture
%
%
Compaction
Comments
(3)
1
NMI Test
0-1 ft
12.00
. 21180
108.8
11.4
97
A
2
N/E Test
0-1 ft
12.00
21180
107.7
9.9
96
A
3
SIE Test
0-1 ft
12.00
21180
107.8
10.0
96
A
4
SAN Test
0-1 ft
12.00
21180
109.0
10.2
97
A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
21180
112.0
11.0
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This test was performed without deviation from AS7M pmcedums.
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
/Wt-- r'o 4.3
I R
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering - Environmental Sciences
Geophysical Services - Materials Testing - Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32955 • P: 321.638.0808 - F: 321.638.0978
In -Place Density Test Report S`f a'9�
Client: Ryan. Homes
1450 Centrepark Blvd Suite 340 eC o
West Palm Beach, FL 33401 04'�
Project: Oakland Lake Subdivision Lot 69
5341 Oakland Lake Circle Permit #,Ft. Pierce, St. Lucie County, FL
Area Tested: House pad
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 02/06/2019
Lab: ASTM D1557 Modified Proctor
Technician: Cliff Cherrnay
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
nnly and do not address the condition of the underlvino soils below the tested depths.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
4-
NM Test
0-1 ft
12.00
21180
108.8
11.4
97
A
2
N/E Test
0-1 ft
12.00
21180
107.7
9.9
96
A
3
S/E Test
0-1 ft
12.00
21180
107.8
10.0
96
A
4
S/W Test
0-1 ft
12.00
21180
109.0
10.2
97
A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
# '
Density
Content
21180
112.0
11.0
(3) comments rcey
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
RECEIVED
FEB 15 2019
Permitting Department
St. Lucie County, FL
This tesrwas performed without deviation from ASTMprocedures.
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
,
0
UES Project No: 310.170251.0042
U N I V E R S A L UES Report No : 106660-1 ARC 020619
ENGINEERING SCIENCES On -Site Time (hrs): 1.00
Consultants In: Geotechnical Engineering • Environmental Sciences Lab Time (hrs): 0.00
Geophysical Services • Materials Testing * Threshold Inspection Travel Time (hrs): 0.25
Building Code Administration, Compliance Inspection & Plan Review Total Time (hrs): 1.26
820 Brevard Avenue, Rockledge, FL 32966 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 69
5341 Oakland Lake Circle Permit #,Ft. Pierce, St. Lucie County, FL
Date of Activity: Wednesday, 06 February, 2019
Technician: Cliff Cherrnay
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the House pad.
While on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for House
pad. All,test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records.
042
UNIVERSAL Date
Project No.: February
2 19
Date Typed: February 07, 2019
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
93 Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32966 - P: 321.638.0808 - F: 321.638.0978
Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 69
5341 Oakland Lake Circle Permit #,Ft. Pierce, St. Lucie County, FL
As requested, Universal Engineering Sciences, Inc. (UES) representative(s) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No. I Data I Type of Report
106660-1 1 02/06/2019 In -Place Density Test Report w/Activity Record
We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
NQ 146. '
ISTATE-op
Attachments (1)
Sincerely,
Universal Engineering Sciences, Inc.
Certificate of Authorization No. 00000549
FMTI - e:
Hoaglin, P.E.
2019.02.07
13:00:37
-05'00'
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
This item has been electronically signed and seated by
Richard E. Hoaglin, P.E. using a Digital signature. Printed
copies of this document are not considered signed and
sealed and the signature must be verified on any electronic
copies.