HomeMy WebLinkAboutFIELD - LABORATORY REPORT7 UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
UES Project No.: 0310.1700251.0043
Date Typed: February 07, 2019
Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 24 O t30
5286 Oakland Lake Circle Permit #, Ft. Pierce, St. Lucie County, FL
SCANNED
St tUBy
� e coUn fy
As requested, Universal Engineering Sciences, Inc. (LIES) representative(s) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No.
Date
Type of Report
106662-1
1 02/06/2019
In -Place Density Test Report w/Activity Record
We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
MAR 18 `019
ST. Lucie County, Permitting
Attachments (1)
Sincerely,
Universal Engifiearing Sciences, Inc.
Certificate of Authorization No `00000549
. ri it 149
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
ICC Email: cbugg@nvrinc.com; rhager@nvrinc.com; sign/seal MAIL to ryan homes at 5369 Oakland Lake, Vero Beach, FL 32966
Revised May 2016
Utsrroject No: 0310.1700261.0043
1_ 1 N I i ? _ , L
-� UES DOCS No:
t 1 . � UES Report No: 106662-1 ARC 020619
ENGINEERING SCIENCES On -Site Time (hrs): 1.00
Consultants In: Geotechnical Engineering • Environmental Sciences Lab Time (hrs): 0.00
Geophysical Services • Materials Testing • Threshold Inspection Travel Time (hrs): 0.25
Building Code Administration, Compliance Inspection & Plan Review Total Time (hrs): 1.25
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Activity Record
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 24
5286 Oakland Lake Circle Permit #, Ft. Pierce, St. Lucie County, FL
Date of Activity: Wednesday, 06 February, 2019
Technician: Cliff Cherrnav
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the House pad.
While on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for House
pad. All test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records.
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering -Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Client:
Project:
Area Tested:
Type of Test:
Technician:
Requirements
In -Place Density Test Report
UES Project No: 0310.1700251.0043
UES DOCS No:
UES Report No: 106662-1 DT 020619
Ryan Homes
1450 Centrepark Blvd Suite-340
West Palm Beach, FL 33401
Oakland Lake Subdivision Lot 24
5286 Oakland Lake Circle Permit #, Ft. Pierce, St. Lucie County, FL
House pad
Field: ASTM D-6938 Nuclear Gauge Method
Lab: ASTM D1557 Modified Proctor
Cliff Cherrnay
Date of Test: 02/06/2019
95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
only and do not address the condition of the undarlvinn snila helms/ tha taetari rionnc.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
.Field
Moisture
%
%
Compaction
Comments
(3)
1
NNV test
0-1 ft
12.00
21180
110.4
10.7
99
A
2
N/E test
0-1 it
12.00
21180
109.7
11.0
98
A
3
S/E test
0-1 ft
12.00
21186
109.5
10.6
98
A
4
1 SNV test
0-1 ft
12.00
21180
110.0
12.0
98
A
t rf _ KeT. uatum: u = I op of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
21180
112.0
11.0
This test was performed without deviation from ASTM procedures.
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This report shall not he reproduced, except in full, without the written approval of Universal Engineering Sciences.
/fin/-oo70
UNIVERSAL
UES Pro
UES DO N Evoll 51. 43 PY
UES Report No: 106662-1 ARC 020619
ENGINEERING SCIENCES On -Site Time (hrs): 1.00
Consultants In: Geotechnical Engineering • Environmental Sciences Lab Time (hrs): 0.00
Geophysical Services - Materials Testing • Threshold Inspection Travel Time (hrs): 0.25
Building Code Administration, Compliance Inspection & Plan Review Total Time (hrs): 1.25
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
Activity Record
SCANNE®
Client: Ryan Homes BY
1450 Centrepark Blvd Suite 340 St. Lucie COunty
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 24
5286 Oakland Lake Circle Permit #, Ft. Pierce, St. Lucie County, FL
Date of Activity: Wednesday, 06 February, 2019
Technician: Cliff Cherrnay
As requested, a Universal Engineering Sciences Technician was present at the above referenced project site for the purpose of
earthwork testing for the House pad.
While on site, the technician observed the general condition of the areas to be tested and performed 4 density test(s) for House
pad. All,test(s) were performed in accordance with the ASTM D-6938 Nuclear Gauge Method and were found to meet the
project compaction requirements of 95% of the maximum dry density per ASTM D-1557.
The Contractor was notified of the test results or a copy was left for their records.
VOR
W1
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering • Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
UES Project No: 0310.1700251.0043
UES DOCS No:
UES Report No: 106662-1 DT 020619
In -Place Density Test Report
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 24
5286 Oakland Lake Circle Permit #, Ft. Pierce, St. Lucie County, FL
Area Tested: House pad
Type of Test: Field: ASTM D-6938 Nuclear Gauge Method Date of Test: 02/06/2019
Lab: ASTM D1557 Modified Proctor
Technician: Cliff Cherrnay
Requirements: 95% of Proctor maximum dry density. These tests apply to the fill and/or surficial soil conditions
oniv and do not address the condition of the underlying soils below the tested depths.
Test
No.
Location of Test
Range
Depth
(inch)
Proctor
(2)
Field Dry
Density
(PCF)
Field
Moisture
%
%
Compaction
Comments
(3)
1
N/Wtest
0-1 ft
12.00
21180
110.4
10.7
99
A
2
N/E test
0-1 ft
12.00
21180
109.7
11.0
98
A
3
S/E test
0-1 it
12.00
21180
109.5
10.6
98
A
4
S/W test
0-1 it
12.00
21180
110.0
12.0
98
A
(1) Ref. Datum: 0 = Top of Final Grade
(2)
Maximum
Optimum
Proctor
Dry
Moisture
#
Density
Content
21180
112.0
11.0
This test was performed without deviation from ASTM procedures.
(3) Comments Key
A. Compaction meets min. requirements
B. Compaction does not meet min. requirements
C. Moisture does not meet requirements
D. Recompaction required
E. Recompacted, Retested, Meets Requirements
This report shall not be reproduced, except in full, without the written approval of Universal Engineering Sciences.
r� I
UNIVERSAL
ENGINEERING SCIENCES
Consultants In: Geotechnical Engineering• Environmental Sciences
Geophysical Services • Materials Testing • Threshold Inspection
Building Code Administration, Compliance Inspection & Plan Review
820 Brevard Avenue, Rockledge, FL 32955 - P: 321.638.0808 - F: 321.638.0978
UES Project No.: 0310.1700251.0043
Date Typed: February 07,2019
Construction Materials Testing Services
FIELD AND LABORATORY REPORT COVER PAGE
Client: Ryan Homes
1450 Centrepark Blvd Suite 340
West Palm Beach, FL 33401
Project: Oakland Lake Subdivision Lot 24
5286 Oakland Lake Circle Permit #, Ft. Pierce, St. Lucie County, FL
As requested, Universal Engineering Sciences, Inc. (UES) representative(s) performed construction materials testing and/or
field inspection services on the above project. Testing results and/or inspection observations are reported on the attached
sheets. The contents of this package are summarized below:
Scope of Work
Work Order No.
I Date
Type of Report
106662-1
1 02/06/2019
In -Place Density Test Report w/Activity Record
We hope this information is sufficient for your immediate needs. If you have any questions, please do not hesitate to contact
the undersigned.
Attachments (1)
Sincerely,
Universal Engineering Sciences, Inc.
111ji l l'j l ;g/ Certificate of Authorization No. 00000649
�N\����p5>i� rFlfi�� Richard E.
G�:• �c�+vsF��G��% Hoaglin, P.E.
2019.02.07
r40. asy
m 96 13:01:32
r
►'. s- A of ' �i= 05'00'
Richard E. Hoaglin, P.E.
FLORIDA
Professional Engineer No. 48796
This item has been electronically signed and sealed by
Richard E. Hoaglin, P.E. using a Digital Signature. Printed
copies of this document are not considered signed and
sealed and the signature must be verified on any electronic
copies.
ICC Email: cbugg@nvrinc.ccm; rhager@nvrinc.com; sign/seal MAIL to ryan homes at 5369 Oakland Lake, Vero Beach, FL 32966
Revised May 2015