Loading...
HomeMy WebLinkAboutHVAC LOAD ANALYSISGrace Emmanuel Church HVAC Load Analysis for Grace Emmanuel Church Kitterman Road Port St. Lucie, FL MVACCOMMZRCIAL, HVAC: LOADS 8'ji' 1 r-8.0 J Prepared By: Eric J. Svoboda, PE Fort Pierce Engineering, Inc. 315 South 7th Street Fort Pierce, FL 34950 772-672-4636 Wednesday, November 18, 2009 iY n �,nr� ,�P iS�Ss ��Ya-. •k5^giz + + .* 1 q..*". -Qw '� re*q` s`P���rFp;a..,. J,,..�: B[rilding Summary Loads - Building peaks in August at 5pm. .µ.me QM D„es�rl,fl. n 1i Se I FIN s �i Cram Roof 13,550 20,122 12.39 0 22,142 22,142 4.07 Wall 6,276 9,527 5.87 0 6,579 6,579 1.21 Glass 240 6,574 4.05 0 12,450 12,450 2.29 Floor Slab 543 11,110 6.84 0 0 0 0.00 Skin Loads 47,332 29.16 0 41,170 41,170 7.57 Lighting 27,100 0 0.00 0 92,469 92,469 17.01 Equipment 13,880 0 0.00 0 47,361 47,361 8.71 People 519 0 0.00 55,495 117,045 172,540 31.74 Partition 0 0 0.00 0 0 0 0.00 Cool. Fret. 0 0 0.00 0 0 0 0.00 Heat. Pret. 0 0 0.00 0 0 0 0.00 Cool. Vent. 3,230 0 0.00 119,697 67,446 187,143 34.43 Heat. Vent. 3,230 115,013 70.84 0 0 0 0.00 Cool.lnfil. 0 0 0.00 0 0 0 0.00 Heat.lnfil. 0 0 0.00 0 0 0 0.00 Draw-Thru Fan 0 0 0.00 0 2,915 2.915 0.54 Blow-Thru Fan 0 0 0.00 0 0 0 0.00 Reserve Cap. 0 0 0.00 0 0 0 0.00 Reheat Cap. 0 0 0.00 0 0 0 0.00 Supply Duct 0 0 0.00 0 0 0 0.00 Return Duct 0 0 0.00 0 0 0 0.00 Misc. Supply 0 0 0.00 0 0 0 0.00 Misc. Return 0 0 0.00 0 0 0 0.00 Building Totals 162,345 100.00 175,192 368,406 543,598 100.00 N Ventilation 115,013 70.84 119,697 67,446 ......3 34.43 Infiltration 0 0.00 0 0 0 0.00 Pretreated Air 0 0.00 0 0 0 0.00 Zone Loads 47,332 29.16 55,495 298,045 353.540 65.04 Plenum Loads 0 0.00 0 0 0 0.00 Fan & Duct Loads 0 0.00 0 2,915 2,915 0.54 Building Totals 162,345 100.00 175,192 368,406 543.598 100.00 Total Building Supply Air (based on a 22° TD): 12,177 CFM Total Building Vent. Air (26.53% of Supply): 3,230 CFM Total Conditioned Air Space: 13,550 Sq.ft Supply Air Per Unit Area: 0.8987 CFM/Sq.ft Area Per Cooling Capacity: 299.1 Sq.ft/Ton Cooling Capacity Per Area: 0.0033 Tons/Sq.ft Heating Capacity Per Area: 11.98 Btuh/Sq.ft Total Heating Required With Outside Air: 162,345 Btuh Total Cooling Required With Outside Air: 45.30 Tons W:%... \Grace Emmanuel Sanctuary.CHV Wednesday, November 18, 2009, 10:54 AM Ch�7ac i ulf Co merc a e VA((�� + adsrCal� I on r re M x a" '�' `v '" � "'i ;, • ''� ' *-1ite"rS are De ' Ihae 1 Sanctuary 4,556 11,871 145,975 42,000 Direct Direct 6pmAugust 400 1,537 5,585 0 1,592 1,592 72,896 0.34 1.23 0 1,537 1,656 2 Office 1 340 892 4,616 210 Direct Direct 6pm August 2 115 177 0 89 89 4,080 0.34 0.52 0 115 52 3 Office 2 340 892 4,651 210 Direct Direct 5pm August 2 115 178 0 89 89 4,080 0.34 0.52 0 115 53 4 Sound Room 170 252 3,389 155 Direct Direct 5pm August 1 33 130 0 30 30 1,360 0.19 0.76 0 33 38 Zone Peak Totals: 5,406 13,907 158,631 42,575 Total Zones: 4 405 1,800 6,069 0 1,800 1,800 Unique Zones: 4 82,416 0.33 1.12 0 1,800 1,800 WA ... %Grace Emmanuel Sanctuary.CHV Wednesday, November 18, 2009, 10:54 AM Or Supply Air Fan: Draw-Thru with program estimated horsepower of 0.57 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio: 0.79 --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 5pm in August. Outdoor Conditions: 94° DB, 78° WB, 120.06 grains Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in August at 6pm is different from the total system peak time, hence the air system CFM was computed using a zone sensible load of 158,620. Summer: Ventilation controls outside air, ---- Winter: Ventilation controls outside air. Zone Space sensible loss: 13,907 Btuh Infiltration sensible loss: 0 Btuh 0 CFM Outside Air sensible loss: 64,094 Btuh 1,800 CFM Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: 78,001 Btuh Heating Supply Air: 13,907 / (.999 X 1.08 X 7) = 1,800 CFM Winter Vent Outside Air (100.0% of supply) = 1,800 CFM Zone space sensible gain: 158,602 Btuh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 1,453 Stuh Supply duct sensible gain: 0 Stuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: 160,055 Btuh Cooling Supply Air: 160,072 / (.999 X 1.1 X 24) = 6.069 CFM Summer Vent Outside Air (29.7% of supply) = 1,800 CFM Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 37,586 Btuh 1,800 CFM Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: 37,586 Btuh Total sensible gain on air handling system: 197,641 Btuh Zone space latent gain: 42,575 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 66,704 Btuh Total latent gain on air handling system: 109,279 Btuh Total system sensible and latent gain: 306,920 Btuh Total Air Handler Supply Air (based on a 240 TD): 6,059 CFM Total Air Handler Vent. Air (29.66% of Supply): 1,800 CFM Total Conditioned Air Space: 5,406 Sq.ft Supply Air Per Unit Area: 1.1226 CFM/Sq.ft Area Per Cooling Capacity: 211.4 Sq.ft/Ton Cooling Capacity Per Area: 0.0047 Tons/Sq.ft Heating Capacity Per Area: 14.43 Btuh/Sq.ft Total Heating Required With Outside Air: 78,001 Btuh Total Cooling Required With Outside Air: 25.58 Tons W:1... 1Grace Emmanuel Sancluary.CHV Wednesday, November 18, 2009, 10:54 AM 5 Platform 578 1,941 9,722 2,000 Direct Direct 6pm August 10 90 425 0 117 117 10,404 0.16 0.74 0 68 103 6 Baptismal 306 1,885 4,623 210 Direct Direct 6pm August 2 87 202 0 41 41 3,672 0.29 0.66 0 66 49 7 Music Room 306 1,885 4,604 210 Direct Direct 7pm August 2 87 201 0 41 41 3,672 0.29 0.66 0 66 49 Zone Peak Totals: 1,190 5,712 18,948 2,420 Total Zones: 3 14 265 828 0 200 200 Unique Zones: 3 17,748 0.22 0.70 0 200 200 WA ... %Grace Emmanuel Sanctuary.CHV Wednesday, November 18. 2009. 10:54 AM �R Chvac05�Fu¢lclt;~�C�omroe[oia11F(VACrLoads�'Casutati�on�Pro �ai�{� sR��c(.�,a��",�`��';,x��t�r'�,,�,,,���j��x��,�E���°��ac`eFE�ie1a uel��`�gA ch ���,�.. ��.x.=�a�.,"Em"vt� �.',__a•�i �.w.'.•p9vRP,a �� ^`rl,�nsz"rtx+e ,,"� ky,��u�XA��„_.� �- w'� �, '� �:v ^ eY6� ,.0 Air Handler #2 -AHU 6 & 7 -Total Load Summary - -- Air Handler Description: AHU 6 & 7 Constant volume - vroportlon Supply Air Fan: Draw-Thru with program estimated horsepower of 0.08 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio: 0.89 --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 5pm in August. Outdoor Conditions: 940 DB, 780 WB, 120.06 grains Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in August at 6pm is different from the total system peak time, hence the air system CFM was computed using a zone sensible load of 18,921. Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Zone Space sensible loss: 5,712 Btuh Infiltration sensible loss: 0 Btuh Outside Air sensible loss: 7,122 Btuh Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: Heating Supply Air: 5,712 / (.999 X 1.08 X 20) _ Winter Vent Outside Air (75.6% of supply) = Zone space sensible gain: 18,854 Btuh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 198 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: Cooling Supply Air: 19,119 / (999 X 1.1 X 21) _ Summer Vent Outside Air (24.1% of supply) = Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 4,176 Btuh Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: Total sensible gain on air handling system: Zone space latent gain: 2,420 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 7,412 Btuh Total latent gain on air handling system: Total system sensible and latent gain: 0 CFM 200 CFM 265 CFM 200 CFM 828 CFM 200 CFM 200 CFM Total Air Handler Supply Air (basea on a n- i u): 200 CFM Total Air Handler Vent. Air (24.14% of Supply): Total Conditioned Air Space: 1,190 0.6961 Sq.ft CFM/Sq.ft Supply Air Per Unit Area: 431.9 Sq.ft/Ton Area Per Cooling Capacity: 0.0023 Tons/Sq.ft Cooling Capacity Per Area: 10.78 Btuh/Sq.ft Heating Capacity Per Area: Tbtal Heating Required With Outside Air: 12,834 Btuh Total Cooling Required With Outside Air: 2.76 Tons 12,834 Btuh 19,052 Btuh 4,176 Btuh 23,228 Btuh 9,832 Btuh 33,060 Btuh W:\...\Grace Emmanuel Sanctuary.CHV Wednesday, November 18, 2009, 10:54 AM Air Handler #3 - Classrooms / 8 Fellowship 5pm August Zone Peak Totals: Total Zones: 1 Unique Zones: 1 4&5- 6,954 27,713 120,589 10,500 Direct Direct 100 1.284 5,280 0 1.230 1.230 83,448 0.18 0.76 0 1,230 1.230 6,954 27.713 120,589 10,500 100 1,284 5,280 0 1,230 1,230 83,448 0.18 0.76 0 1,230 1.230 Wednesday, November 18, 2009, 10:54 AM W:\...\Grace Emmanuel Sanctuary.CHV Air Supply Air Fan: Draw-Thru with program estimated horsepower of 0.50 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio: 0.92 -- This system occurs 1 time(s) in the building. --- Air System Peak Time: 5pm in August. Outdoor Conditions: 94° DB, 78° WB, 120.06 grains Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Zone Space sensible loss: 27,713 Btuh Infiltration sensible loss: 0 Btuh Outside Air sensible loss: 43,798 Btuh Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: Heating Supply Air: 27,713 / (.999 X 1.08 X 20) _ Winter Vent Outside Air (95.8% of supply) Zone space sensible gain: 120,589 Btuh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 1,264 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: Cooling Supply Air: 121,853 / (.999 X 1.1 X 21) _ Summer Vent Outside Air (23.3% of supply) _ Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 25,684 Btuh Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: Total sensible gain on air handling system: Zone space latent gain: 10,500 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 45,581 Btuh Total latent gain on air handling system: Total system sensible and latent gain: 0 CFM 1,230 CFM 1,284 CFM 1,230 CFM 5,280 CFM 1,230 CFM 1,230 CFM Total Air Handler Supply Air (based on a 21- 1 u): o,cou 1,230 �' ,., CFM Total Air Handler Vent. Air (23.30% of Supply): Total Conditioned Air Space: 6,954 0.7592 Sq.ft CFM/Sq.ft Supply Air Per Unit Area: 409.8 Sq.ft/Ton Area Per Cooling Capacity: 0.0024 Tans/Sq.ft Cooling Capacity Per Area: 10.28 Btuh/Sq.ft Heating Capacity Per Area: Total Heating Required With Outside Air: 71,511 Btuh Total Cooling Required With Outside Air: 16.97 Tons 71.511 Btuh 121,853 Btuh 25,684 Btuh 147.537 Btuh 56,081 Btuh 203,618 Btuh W:\...\Grace Emmanuel Sanctuary.CHV Wednesday, November 18, 2009, 10:54 AM