Mr. Joseph Fersch, please see the plans review comment responses below: �CqN
Planmier t CUc/eColl,
O
S F
t''
1) PL ASE SHOW ON PLANS THE REQUIRD INSULATION R VALUES AND MATERIAL OF TEE
INSULATION FOR THE WALLS AND CEILINGS
A: See revised plans, typical sections sheet 2.3.
2) PLEASE ADD THE CUBIC VOLUME OF THE CONDITIONED SPACE TO INFORMATION BLOCK
CONTAINING THE SQUARE FOOT INFORMATION SPECIFYING THE CUBIC VOLUME OF THE
Y CONDITIONED SPACE.
A: See revised plans, cover sheet.
Comments 3 through 5: Answered by MEP engineer.
6) PLEASE REVIEW AND CORRECT ACCORDINGLY. 2017 6TH EDTION FLORIDA BUILIND CODE
RESIDENTIAL R311.6 THE WIDTH OF A HALLWAY THE WIDTH OF THE A HALLWAY SHALL BE
NOT LESS THAN THREE FEET
A: See revised plans, sheet 1.1 floor plan.
7) PLEASE PROVIDE A DOOR SCHEDULE 107.1 THE FLORIDA BUILDING CODE -RESIDENTIAL
A: See revised plans, sheet 1.1.
8) PLEASE PROVIDE STAIR DETAIL SHOWING COMPLIANCE WITH R311.7 OF THE FLORIDA
BUILDING CODE -RESIDENTIAL 2017 6TH EDTION
A: See revised plans, details 2 & 3, sheet 2.4.
9) PLEASE PROVIDE DETAILS COMPLYING WITH R312.1.2 OF THE FLORIDA BUILDING CODE -
RESIDENTIAL 2017 6TH EDITION
A: See revised plans, details 2 & 3, sheet 2.4.
10) PLEASE PROVIDE DETAIL IN COMPLIANCE WITH R312.1 THE FLORIDA BUILDING CODE -
RESIDENTIAL 2017 6TH EDTION
A: See revised plans, details 2 & 3, sheet 2.4.
Mission Statement: To provide the client with a fast and accurate design that is ecologically and economically
friendly.
CAGE #: 62NW7
Re -
New
Renewable Design
West -Palm Beach, F1 -
(561)373-2327
rhaggerty7@bellsouth.net
www.renewable-eng.com
Structural Engineering
Plans
Design
Consultation
Review -
11) PLEASE SHOW ON PLANS SOIL COMPACTION DENSITY SEE SECTION 107 OF THE 2017
FLORIDABUILDING CODE SIXTH EDITION
A: See revised plans, note added to foundation plan. Also see soil report from Allterra dated 2-
14-19.
12) PLEASE SHOW COMPLIANCE WITH R320 ACCESSIBILITY OF THE FLORIDA BUILDING
CODERESIDENTIAL 2017 6TH EDITION
A: See revised plans, landings added. Also see door threshold detail, sheet 2.3.
13) PLEASE FURNISH A NONBEARING INTERIOR WALL DETAIL SHOWING STUD SPACING, STUD
SIZE, WALL FINISH AND FASTENERS IN ACCORDANCE WITH 602.2 OF THE 2017 FLORIDA
BUILDING CODE SIXTH EDTITION.
A: See revised plans, details, sheet added 3.1.
14) PLEASE FURNISH AN LOAD -BEARING INTERIOR WALL DETAIL SHOWING STUD SPACING,
STUD SIZE, WALL FINISH AND FASTENERS IN ACCORDANCE WITH 602.2 OF THE 2017 FLORIDA
BUILDING CODE SIXTH EDTITION.
A: See revised plans, sheet 2.3.
15) PLEASE PROVIDE ON THE CONSTRUCTION DOCUMENTS DETAILS OF THE EXTERIOR WALL
ENVELOPE AS REQUIRED, INCLUDING FLASHING, CORNERS, END DETAILS, INTERSECTIONS
AT ROOF, EAVES OR PARAPETS, MEANS OF DRAINAGE, WATER -RESISTIVE MEMBRANE AND
DETAILS AROUND OPENINGS. 107.2.4 EXTERIOR WALL ENVELOPE
A: See revised plans, details, sheet added 3.1.
16) PLEASE PROVIDE DETAIL FOR WALL FINISHINGS AND FASTENERS 107 OF THE 2017
FLORIDA BUILDING CODE SIXTH EDITION
A: See revised plans, however this code reference is not clear, 107 is listed as "Reserved".
17) PLEASE PROVIDE IN DETAIL HOW THE STAIR STRINGER IS TO BE FASTENED TO THE
EXTERIOR WALL WITH FLASHING AND WATERPROOFING 107.2.4 EXTERIOR WALL ENVELOPE
A: See revised plans, note added sheet 2.2, and flashing detail on sheet added 3.1.
18) PLEASE PROVIDE IN DETAIL HOW THE STAIR STRINGER IS TO BE FGASTENED TO THE
EXTERIOR WALL WITH FLSHING AND WATERPROOFING 107.2.4 EXTERIOR WA14���
A: Duplicate of question 17, see above.
RECEIVED
Respectfully, FEB 2 0 21151
Ruth Haggerty, PE Permitting bePar€Ment
St. Lucie C€ urty ;: L
Mission Statement: To provide the client with a fast and accurate desi n that ' coiogically-andecono
friendly.
CAGE #: 62NW7
January 27, 2019
-Mechanical-Plan -Review
St. Lucie County Building and Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Attention: Mechanical Reviewer
Joseph Fersch
RE: Bobby Garnett Residence
12331 S Indian River Drive
Jensen Beach, FL 34957
Permit: 1901-0161
SCgNN 4)
St 4Uci�CoU
ntv
This letter is in response to the Mechanical Reviewer Comments Dated 01/17/19:
1. Please show on plans the required insulation R values and materials of the insulation for
the wall and ceilings. 107-2017 Florida Residential Building Code 6th Edition.
Response: Insulation values to be shown on the revised Architectural plans.
2. Please add cubic volume of the conditioned space to information block...
Response: To beshowr on revised Architectural plans.
3. Energy Calcs information block at the top of cover page are incomplete/incorrect permit
office and jurisdiction. See Section 107.1 Florida Building Code Residential 6th Edition
(2017).
-Response: -Energy-Calculatiuns-have been Tevised-to-reflect correctpermitoffice and
jurisdiction.
4. The Energy calculations must have the original signatures of the preparer, owner or
agent. Please furnish new energy calculations with original signatures per 107.1 of the
2017 Florida Building Code -
Response: Energy Calculations have been revised to show original signatures.
Michael Bassford, P.E.
2107 N.E.17`h Avenue
Wilton -Manors, FL '33305
(9S4) 298-0700
mbassford@aol.com
FEB 2 0 2019
Permitting Department
St. Lucie County, FL
S. The Energy Performance Level display card must have the builder's signature per 107.1
of the 2017 Florida Building Code.
Response: See attached EPL card signed by the Builder.
Si W uU.rt,t�
Q0 ij .
,O t
�In i cTA7. OF : ,4L�
unn►
Michael Bassford, P.E.
Michael Bassford, P.E.
2107 N.E. 17`h Avenue
-Wilton Manors,TL 33305
(954)298-0700
mbassford@aol.com
1901-0161
1) PLEASE SHOW ON PLANS THE REQUIRD INSULATION R VALUES AND MATERIAL OF THE
INSULATION FOR THE WALLS AND CEILINGS 107 2017 FLORIDA RESIDEN6 Akl�-DING
CODE 6TH EDITION. SS BY
St. Lucie County
2) PLEASE ADD THE CUBIC VOLUME OF THE CONDITIONED SPACE TO INFORMATION
BLOCK CONTAINING THE SQUARE FOOT INFORMATION OR A LETTER FROM THE DESIGN
PROFESSIONAL SPECIFYING THE CUBIC VOLUME OF THE CONDITIONED SPACE. SEE
CHAPTER 1 SECTION 107 OF THE 2017 FLORIDA BUILDING CODE.
3) ENERGY CALC??S INFORMATION BLOCK AT THE TOP OF COVER PAGE IS
INCOM EPLETE/IN CORRECT. SEE SECTION 405.4.2 (1) OF THE 2017 FLORIDA ENERGY
CODE.
4) THE ENERGY CALULATIONS MUST HAVE THE PREPARERS ORIGINAL SIGNATURE PLEASE
FURNISH NEW ENERGY CALULATIONS WITH ORIGINAL SIGNATURES PER 107.1 OF THE
2017 FLORIDA BUILDING CODE
5) THE ENERGY PREFORMANCE LEVEL DISPLAY CARD MUST HAVE THE BUILDERS PER 107.1
OF THE 2017 FLORIDA BUILDING CODE
6) PLEASE REVIEW AND CORRECT ACCORDINGLY. 2017 6TH EDTION FLORIDA BUILIND CODE
RESIDENTIAL R311.6 THE WIDTH OF A HALLWAY THE WIDTH OF THE A HALLWAY SHALL
BE NOT LESS THAN THREE FEET
7) PLEASE PROVIDE A DOOR SCHEDULE 107.1 THE FLORIDA BUILDING CODE -RESIDENTIAL,
6TH EDITION (2017)
8) PLEASE PROVIDE STAIR DETAIL SHOWING COMPLIANCE WITH R311.7 OF THE FLORIDA
BUILDING CODE -RESIDENTIAL 2017 6TH EDTION
9) PLEASE PROVIDE DETAILS COMPLYING WITH R312.1.2 OF THE FLORIDA
BUILDING CODE -RESIDENTIAL 2017 6TH EDITION
10) PLEASE PROVIDE DETAIL IN COMPLIANCE WITH R312.1THE FLORIDA BUILDING
CODE- RESIDENTIAL 2017 6TH EDTION
11) PLEASE SHOW ON PLANS SOIL COMPACTION DENSITY SEE SECTION 107 of the 2017
FLORIDA BUILDING CODE SIXTH EDITION
12) PLEASE SHOW COMPLIANCE WITH R320 ACCESSIBLITY OF THE FLORIDA BUILDING
CODE -RESIDENTIAL 2017 6TH EDITION
13) PLEASE FURNISH A NONBEARING INTERIOR WALL DETAIL SHOWING STUD SPACING,
STUD SIZE, WALL FINISH AND FASTENERS IN ACCORDANCE WITH 602.2 OF THE 2017
FLORIDA BUILDING CODE SIXTH EDTITION.
14) PLEASE FURNISH AN LOAD -BEARING INTERIOR WALL DETAIL SHOWING STUD SPACING,
STUD SIZE, WALL FINISH AND FASTENERS IN ACCORDANCE WITH 602.2 OF THE 2017
FLORIDA BUILDING CODE SIXTH EDTITION.
15) PLEASE PROVIDE ON THE construction documents details of the exterior wall envelope
as required, including flashing, corners, end details, intersections at roof, eaves or
parapets, means of drainage, water -resistive membrane and details around openings.
107.2.4 EXTERIOR WALL ENVELOPE
16) PLEAS PROVIDE DETAIL FOR WALL FINISHINGS AND FASTENERS 107 of the 2017
FLORIDA BUILDING CODE SIXTH EDITION
17) PLEASE PROVIDE IN DETAIL HOW THE STAIR STRINGER IS TO BE FGASTENED TO THE
EXTERIOR WALL WITH FLSHING AND WATERPROOFING 107.2.4 EXTERIOR WALL
ENVELOPE
18) PLEASE PROVIDE IN DETAIL HOW THE STAIR STRINGER IS TO BE FGASTENED TO THE
EXTERIOR WALL WITH FLSHING AND WATERPROOFING 107.2.4 EXTERIOR WALL
ENVELOPE
19) PLEASE NOTE THAT THE COMMENTS ARE FOR THE CLARIFICATION, CORRECTION OR
ADDITIONAL INFORMATION NEEDED OF THE SUBMITTED DOCUMENTS. ADDITIONAL
REVIEW MAY BE REQUIRED AFTER SUBMITTING CORRECTED DOCUMENTS.