HomeMy WebLinkAboutTEST REPORTIntertek
Architectural Testing
TEST REPORT
Report No.: E5100.01-401-44
Rendered to:
INNOVATIONS MANUFACTURING, INC.
Denver, Colorado
PRODUCT TYPE: Transom Window
SERIES/MODEL: IM
too
coin
SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11, NAFS 2011 -North American
Fenestration Standard/Specification for Windows, Doors, and Skylights
Title
SummaKy
of Results
AAMA WDMA CSA 101 I.S.2 A440-11
Class R-PG50 1829 x 309 72 x 12 -TR
Design Pressure
±2400 Pa
±50.13 s
Air Infiltration
<0.1 L s/mz
<0.01 cfm/ftz
Water Penetration Resistance Test Pressure
440 Pa
9.19 pso
This report contains in its entirety:
Cover Page:
1 page
Report Body:
5 pages
Alteration Addendum:
1 page
Location Air Seal:
1 page
Drawing:
1 page
Test Completion Date: 02/11/15
0��•41N P.' M Cp01/,���
Joi::•�10ENSF•.9� :�
* No. 77418
,t =
•a STATE OF ' C
PST •`:�<ORIOP:' _A;
w.,ey.aera�a,m
2015.04.23 16:17:11-04'00'
Reference must be made to Report No. E5100.01-401-44, dated 04/23/15 for complete test
specimen description and detailed test results.
2250 Massaro Boulevard wwwarchtest.com . www.intertek.com/building p• 813.628.4300
Tampa, FL 33619 f. 717.764.4129
®� Architectural Testing - — - -- � Test Report No.: E5100.01-401-44
Report Date: 04/23/15
Page 1"of 5
1.0 Report Issued To: Innovations Manufacturing, Inc.
4555 Grape Street
Denver, Colorado 80216
2.0 Test Laboratory: Architectural Testing, Inc.
an Intertek company ("Intertek-ATI")
2250 Massaro Boulevard
Tampa, Florida 33619
813-628-4300
3.0 Project Summary:
3.1 Product Type: Transom Window
3.2 Series/Model: IM
3.3 Compliance Statement: Results obtained are tested values and were secured by
using the designated test method(s). The specimen tested successfully met the
performance requirements for a Class R-PG50 1829 x 309 (72 x 12)-TR rating.
3.4 Test Dates: 02/10/15 - 62/11/15
3.5 Test Record Retention End Date: All test records for this report will be retained
until February 11, 2019.
3.6 Test Location: Intertek-ATI test facility in Tampa, Florida.
3.7 Test Specimen Source: The test specimen(s) was provided by the client.
Representative samples of the test specimen(s) will be retained by Intertek-ATI for
a minimum of four years from the test completion date.
3.8 Drawing Reference: The test specimen drawings have been reviewed by
Intertek-ATI and are representative of the test specimen(s) reported herein. Test
specimen construction was verified by Intertek-ATI per the drawings located in
Appendix C. Any deviations are documented herein or on the drawings.
3.9 List of Official Observers:
Name
Owen Bunker
Wilferson Simbert
Company
Innovations Manufacturing, Inc.
Intertek-ATI
www.archtest.com . www.intertek.com/building
®� Architectural Testing
4.0 Test Specification(s):
Test ReportNo.: E5100.01-401-44
Report Date: 04/23/15
Page 2 of 5
AAMA/WDMA/CSA 101/1.S.2/A440-11, NAFS 2011 - North American Fenestration
Standard/Specification for Windows, Doors, and Skylights
5.0 Test Specimen Description:
5.1.Product Sizes:
Overall Area:
0.6 In (6 ft2)
Width
IHeight
millimeters
inches
millimeters
inches
Overall size
1 1829
72
305
12
5.2 Frame Construction:
Frame Member
Material
I Description
Head, sill and
Aluminum
Extruded
jambs
joineryType
Detail
Each corner was sealed with sealant and
All corners
Mitered and keyed
secured with one inside aluminum corner key
with epoxy,
5.3 Weatherstripping: No weatherstripping was utilized.
5.4 Glazing: No conclusions of any kind regarding the adequacy or inadequacy of the
glass in anyglazed testspecimen(s) can be made.
Glass Type
Glazing
Glazing Method
Interior glazed against adhesive
Monolithic
3 mm thick
backed foam glazing tape and
annealed glass
secured with snap -in PVC glazing
beads.
Location
Quantity
Daylight Opening
Glass Bite
millimeters
inches
Transom daylight
1
1784 x 260
70-1/4 x 10-1/4
1/2"
opening
www.archtest.com . www.intertek.com/building
Archl�l Testing
5.0 Test Specimen Description: (Continued)
5.5 Drainage:_ No drainage was utilized.
5.6 Hardware: No hardware was utilized.
5.7 Reinforcement: No reinforcement was utilized.
6.0 Installation:
Test Report N E5100.01-401-44
Report Date: 04/23/15
Page 3 of 5
The specimen was installed into a 2x6 Southern Yellow Pine wood buck. The rough
opening allowed for a 1/8" shim space. The exterior perimeter of the window was
sealed with sealant.
Location
chor Description
Anchor Location
t2ng
3" from each corner and spaced 8"
Head, sill and jamb
roofing nails
on center, through the nail fin and
trim board into the wood buck
7.0 Test Results: The temperature during testing was 19°C(6717). The results are
tabulated as follows:
Title of Test
Results
Allowed
Note
Air Leakage,
Infiltration per ASTM E 283
<0.1 L/s/mz
1.5 L/s/mz
at 75 Pa 1.57 s
<0.01 cfm ftz
0.3 cfm ftz max.
1
Water Penetration,
per ASTM E 547
N/A
N/A
2
Uniform Load Deflection,.
per ASTM E 330
N/A
NIA
2
Uniform Load Structural,
- per ASTM E 330
N/A
N A
2
Forced Entry Resistance,
per ASTM F 588,
Type: D -Grade: 10
Pass
No entry
www.archtest.com . www.intertek.com/building
®— Architectural Testing
7.0 Test Results: (Continued)
Test ReportNo.: E5100.01-401-44
Report Date: 04/23/15
Page 4 of 5
Title of Test
Results
Allowed
Note
0 tional Performance
Water Penetration,
per ASTM E 547
at 440 Pa .9.19 pso
Pass
. No leaka e
3
Uniform Load.Deflection,
per ASTM E 330
Deflections taken at the head
+2400 Pa (+50.13 psf)
<0.3 mm (<0.01")
-2400 Pa -50.13 s
0.3 mm 0.01"
Report Only
4, 5, 6
Uniform Load Structural,
per ASTM E 330
Permanent sets taken at
the head
+3600 Pa (+75.19 psf)
0.5 mm (0.02")
0.8 mm (0.03") max.
-3600 Pa -75.19 s
0.5 mm 0.02"
0.8 mm 0.03" max.
4, 5, 6
Note 1: The tested specimen meets (or exceeds) the performance levels specified in
AAMA/WDMA/CSA 101/LS.2/A440 for air leakage resistance.
Note 2: The client opted to start at a pressure higher than the minimum required. Test
results are reported under Optional Performance.
Note 3: Without insectscreen.
Note 4: The deflections reported are not limited by AAMA/WOMA/CSA 101/1.S2/A440
for this product designation. The deflection data is recorded in this report for special
code compliance and information only.
Note S. Loads were held for 10 seconds.
Note 6: Tape and film were not used to seal against air leakage during structural testing.
www.archtest.com . www.intertek.com/building
Ak
—® IAtcSi�l Testing— — -
Test Report No.: E5100.01-401-44
Report Date: 04/23/15
Page 5 of 5
Intertek-ATI will service this report for the entire test record retention period. Test records
such as detailed drawings, datasheets, representative samples of test specimens, or other
pertinent project documentation, will be retained by Intertek-ATI for the entire test record
retention period.
This report does not constitute certification of this product nor an opinion or endorsement
by this laboratory. It is the exclusive property of the client so named herein and relates
only to the specimen(s) tested. This report may not be reproduced, except in full, without
the written approval of Intertek-ATI.
For ARCHITECTURAL TESTING, Inc.
D4t*&%mdbr.Dada)P.Bm D4b YBi9JWbr.JPMtDwWd
Daniel P. Braun J.P. McDonald, P.E.
Senior Vice President Director - Regional Operations
VLM:vlm
Attachments (pages): This report is complete only when all attachments listed are included.
Appendix -A: Alteration Addendum (1)
Appendix-B: Location of Air Seal (1)
Appendix-C: Drawing(s) (1)
This report produced from controlled document template ATI 00438, revised 06/27/14.
www.archtest.com . www.intertek.com/building
Test ReportNo.: E5100.01-401-44
Repo�te--W4/Z2j15
Appendix A
Alteration Addendum
Note: No alterations were required.
www.archtest.com • www.intertek.com/building
E510
®— ^•- - — — Test ReportNo.: tUafte 04/22-44 — -
n n tuTesting Report�te�4J22/15
Appendix B
Location of Air Seal: The air seal between the test specimen and the test wall is detailed
below. The seal is made of foam weatherstripping and is attached to the edge of the test
specimen buck. The test specimen buck is placed against the test wall and clamped in
place, compressing the weatherstripping and creating a seal.
Test
Air Seal (WeathwWppIno
Test Spedmen Bic
Test Spedmen
www.archtest.com . www.intertek.com/building
^, T Test ReportNo.: E5100.01-401-44
—��Architectural
re.noa—Reporflfte3 �4�22�15
Appendix C
Drawing(s)
www:archtest.com . www.intertek.com/building
M
AS TESTED INSTALLATION NOTES:
1. WINDOW.MUST BE INSTALLED INTO A SPF OR BETTER
2X WOOD MEMBER
3 2. WINDOW MUST BE INSTALLED USING 2" LONG, #8
ROOFING NAILS. ALL NAILS MUST BE SPACED A
MAXIMUM OF 6" ON CENTER, THROUGH THE NAIL FIN
.INTO THE 2X WOOD MEMBER.
3. ALL INSALLATION FASTENERS MUST BE LOCATED A
MINIMUM OF 1/2" FROM THE EDGE OF THE NAIL FIN AND
HAVE A MINIMUM EMBEDMENT OF 1-1/2".. I
1-1/2" MIN
EMBEDMENT
#8 x2" LONG 1/2" MIN 2X WOOC
ROOFING NAILS BUCK
MIN (SPF min)
EDGE
EDGE DISTANCE
EDGE DISTANCE 1-1/2" MIN 1/8" SHIM
EMBEDMENT SPACE,
�I
TRANSOM /
WINDOW 1/8" SHIM #8x2"LONG _l
SPACE ROOFING NAILS TRANSOM
WINDOW
SECTION A -A
hEAD/SILL DETAILS 2X WOOD Busl�ingBetterTog6theG
SECTION B-B compiles vAth se defogs.
BUCK ,IAMB DETAILS Deviations ere noted. II
(SPF min) Report#: E5100.01-44011--44 /gLDate: 04/
13/201
Verified by:
TUFF SHED ONel k. PO# THEBEDRETHEaANOTHE TITLE APwL-
DESIGNAHED IN ROPEfttt TUFF SHED, INC. aPfl-TRA soM
Customer. Drexm By. PK DRAWNG AREFC THESE INSTALLATION INSTRUCTIONS I
OPAWINGTOBEF02F
Storage Buildings&Garages DateCheclm!By. AND BUILT09EBFPNap INHOUSE 1777. HARTINGDETREET NT REV. LEVEL 01
not
TUFF SHED, INC. Situ P AVER, COLORA O80210 x FOR
MANUFA T WINDOWS
AND BUILT TUFF SHED. 1777 S. HARRISON STREET
Cata: tlBy, FNYOTHERUBEIB DENVE$COL3-TUFF 0210 MANUFACTURED BY $HEFT
Data: INCFORBIDNBYTUER OF (..4.3-TUFF
Bulltling Sire:.m..uwm..,ur.e"n. )� F�ENt8T EE�NG ENGINEER o[ rvneiaome, wvwuie p swunro" INNOVATIONS MFG,INC SHEET 10F�3
$tale: N.T.S. RECORD.