HomeMy WebLinkAboutEVALUATION REPORTProduct Evaluation Report
GULF COAST SUPPLY & MANUFACTURING, LLC.
26 Ga. GulfRibTm Roof Panel over 15132" Plywood
Florida Product Approval #11651.22 R3
Florida Building Code 2017
Per Rule 61 G20-3
FILE COPY Method: 1 -D
qO -a30' - Category: Roofing
11tik ( Subcategory: Metal Roofing
Compliance Method: 61G20-3.005(1)(d)
NON HVHZ
Product Manufacturer:
Gulf Coast Supply & Manufacturing,
14429 SW 2nd Place, Suite G30
Newberry, FL 32669
Engineer Evaluator:
Dan Kuhn, P.E. #75519
Florida Evaluation ANE ID: 10743
Validator:
Locke Bowden, P.E. #49704
9450 Alysbury Place
Montgomery, AL 36117
Contents:
Evaluation Report Pages 1 - 5
LLC.
* : No. 75519
STATE OF Q z
�0*FSi A.
O R 1 D P. •'a��:
/VAL ENti10/05/201yt
�'€
�. •COX;. ��.." _ ...,:
9
•
� 1 11 _ Y{-=v.1�
-
M
• e l
t-
Compliance Statement:
The product as described in this report has demonstrated compliance with the
Florida Building Code 2017, Sections 1504.3.2.
Product Description:
GulfRibTM, 3/a" Rib Roof Panel, Minimum 26 Ga. Steel, 36" Coverage,
through fastened roof panel over minimum 15/32" Plywood Decking. Non
Structural application.
Panel Material/Standards:
Material: Minimum 26 Ga. Steel, ASTM A792 or ASTM A653 G90 conforming to
Florida Building Code 2017 Section 1507.4.3.
Paint Finish Optional
Yield Strength: Min. 80.Oksi
Corrosion Resistance: Panel Material shall comply with Florida Building
Code 2017, Section 1507.4.3.
Panel Dimension(s):
Thickness: 0.018" Minimum
Width: 36" Coverage
Rib Height: 3/4" Major Rib at 9" O.C.
Panel Fastener:
#9-15xl.5" HWH with sealing washing or approved equal
1/4" minimum penetration through plywood.
Corrosion Resistance: Per Florida Building Code 2017, Section 1506.6, 1507.4.4
Substrate Description:
Minimum 15A2" thick, APA Rated plywood over supports at maximum 24" O.C.
Design of plywood and plywood supports are outside the scope of this
evaluation. Must be designed in accordance w/ Florida Building Code 2017.
Design Uplift Pressures:
Table "A"
iVlaximum/TotalFUplift Design'k,Pressure,��
69�25fpsf � „, -_
1�59?25 psf,� ' �
Fastener Pattern
2.5"6.5"-2.5"-6.5"
Fastener Pattern Spacmg��a �
?4v � C aa
1 Z"M tl^'.-°�,-v Y; C
x ' '
Design Pressure includes a Safety Factor = 2.0.
/ ® ^�
� a
\� j {
- \ ��
\dam f
Code Compliance:
The product described herein has demonstrated compliance with the
Florida Building Code 2017, Sections 1504.3.2.
Evaluation Report Scope:
The product evaluation is limited to compliance with the structural wind load
requirements of the Florida Building Code 2017, as relates to Rule 61 G20-3.
Performance Standards:
The product described herein has demonstrated compliance with:
• UL 580-06 - Test for Uplift Resistance of Roof Assemblies
• UL 1897-12 - Uplift Test for Roof Covering Systems.
Reference Data:
1. UL 580-94 / 1897-98 Uplift Test
Force Engineering & Testing, Inc. (FBC Organization # TST-5328)
Report No. 117-0062T-07A, B, Dated 02/19/2007
2. Certificate of Independence
By Dan Kuhn, P.E. (FL# 75519) @ Kuhn Engineering, LLC
(FBC Organization # ANE ID: 10743)
Test Standard Equivalence: 1. The UL 580-94 test standard is equivalent to the UL 580-06 test standard
2. The UL 1897-98 test standard is equivalent to the UL 1897-12 test
standard.
Quality Assurance Entity:
The manufacturer has established compliance of roof panel products in
accordance with the Florida Building Code and Rule 61 G20-3.005(3) for
manufacturing under a quality assurance program audited by an approved quality
assurance entity.
Minimum Slope Range:
Minimum Slope shall comply with Florida Building Code 2017, including
Section 1507.4.2 and in accordance with Manufacturers recommendations. For
slopes less than 3:12, lap sealant must be used in the panel side laps.
Installation:
Install per Manufacturer's recommended details.
Underlayment:
Shall comply with Florida Building Code 2017 section 1507.1.1.
C 4w1
y
I (�
IM
w.�
loom
No
I
WKS,
4t
--a.
J
A,u _fill
wx
Raw
Aw
NQ
W.
sp
-
}
� SFr
_ _-Z"' {•
Y.
:: -
Roof Panel Fire Classification: Fire classification is not part of this acceptance.
Shear Diaphragm: Shear Diaphragm values are outside the scope of this report.
Design Procedure: For roofs within the parameters listed on the load table, fastening pattern must
at a minimum meet those listed for the applicable wind zone. For all roofs outside
the parameters listed on the load table, design wind loads shall be determined
for each project in accordance with FBC 2017 Section 1609 or ASCE 7-10
using allowable stress design. The maximum fastener spacing listed herein shall
not be exceeded. This evaluation report is not applicable in High Velocity
Hurricane Zone. Refer to current NOA or HVHZ evaluation report for use of this
product in High Velocity Hurricane Zone.
ENGINEER LOAD TABLE: 26 Ga. GulfRibTm Panel over 15/32" Plywood
6 a°Roof
MeaHeigF�t�5200
/1292 /1'2' Gable o �NI
Roof Slope alp
Roof; Wlnd
S eeds'
P '
20
�uildings,Fiaving
80mplfi;Ezposure C -Risk
Catego� I1EnclosedBullding,basedlon
Flonda(Buiiding,Code207_•
' m120> A
130
140_
150
160
170
180
WIIND
FASTENER
SUBSTRATE
SPEED
(MIN,
penetration)
( MIN. 15132•)
ON CENTER
ON CENTER
ON CENTER
ON CENTER
ON CENTER
ON CENTER
ON CENTER
SPACING
SPACING
SPACING
SPACING
SPACING
SPACING
SPACING
:;ZONE 1�
-`#9 15x1°S;
lyv foodaTYPE
1
24" TYPE1
124 TYPE 1
P24", T,YPE•1
24 TYP,E'1t
2�4>, TYPE 1
24 -k1
c-65`
..
.rrc"x.
ZONE 2
#9-15x1.5"
Plywood
24", TYPE 1
24", TYPE 1
24", TYPE 1
24", TYPE 1
24", TYPE 1
24", TYPE 1
24", TYPE 2
,ZONE 3�
#9 415xn5
Plywood
"_, TYPEpt
124�, TYPE 1�
24"„TYPE 1
12 TYPEi2)
12 'TXPE>2
12 7YPEI2
12", TYPE 2.
_.
�
1.) PANEL DESCRIPTION: GULFRIBT , MIN. 26 GA., GRADE 80, 36"COVERAGE, 3/4" TALL.
2.) PANEL FASTENER: #9-15X1.5" HWH WITH SEALING WASHER OR APPROVED EQUAL
3.) MAXIMUM ALLOWABLE PANEL UPLIFT PRESSURE: 69.25 PSF @ 24" O.C. FASTENER SPACING TYPE I FASTENER PATTERN, 159.25
PSF @ 12" O.C. FASTENER SPACING TYPE 2 FASTENER PATTERN BASED ON TAS 125, UL 580/UL 1897 TESTING.
4.) PLYWOOD DECKING: MIN. 15hx" THICK PLYWOOD MUST BE DESIGNED IN ACCORDANCE WITH FLORIDA BUILDING CODE 2017.
5.) ROOF SLOPE: ON ROOF SLOPES LESS THAN 3:12, LAP SEALANT MUST BE USED IN PANEL SIDE LAPS.
6.) LOAD TABLE BASED ON WIND PRESSURES CALCULATED PER ASCE 7-10 (KD = 0.85) MULTIPLIED BY 0.6 PER FLORIDA BUILDING
CODE 2017.
ZONEZ
I
ZONE 1d
---------------�
RIDGE
ZONE
\\\\\I
i e
`EAVE
Note: Dimension (a) is defined as 10% of the minimum width of the building or
40% of the mean height of the roof, whichever is smaller, however, (a) cannot be
a less than either 4% of the minimum width of the building or 3 feet.
2 GABLE ROOF 1RT
�_________________.T _ya
--RIDGE
�----------
- ____________________4a
I
ZONE 1
'ZONE3 HEAVE
FL# 11651.22 R3 • OCTOBER S. 2017
CAnt. Tape Seal Vr use on sic
#9-15 x 141r WSealer Washer @ 17 O.C. Max.
=-d
n'•
lam.
�.1
'
x
"
�
� - _ "➢ [
is � Evl _^ 4Ib 1'
xi
,
£
1
Yx
Certilcate of Authorization No. 29824
CREEK _ 17520 Edinburgh Drive
Tampa - -FL 33647
TECHNICAL SERVICES, LLC (813) 480-3421
EVALUATION REPORT FLORIDA BUILDING CODE, 6°i EDITION (2017)
Manufacturer: TAMKO BUILDING ODUCTS, INC. q rZIssued October 19, 2017 . �t
CONC&1M FASTENERS OR ATTACHMENTS P.O. Box 1404 is (Z � 1©( - Q 3 o T �fI UN, C�-
ARETIERESPONSIBIUTYOFTHE Joplin, M064802 LUCIE COUNTY BUILDING DIV
CONfRACTOROgRECORD (417)624-6644 REVIEWED FOR COMPLIANCE /
htto:/hvww.tamko.com �C%1TC1e1en1RV I^/ -='
Quality Assurance:
SCOPE
PLAND PERM MUST BE KEPT t OB
UL LLC (QUA9625) " `ffOR
SITE O INSPECTIONS) WILL MADE
Category:
Roofing FILE COPY
Subcategory
Code Sections:
Unded16071 yments THESE PLANS AND ALL PROPOSED WORK
1507.1.1
Properties:
Physical prope 1QRE SUBJECT TO ANY CORRECTIONS
QUIRED BY FIELD INSPECTORS THAT
MAY BE NECESSARY IN ORDER TO
PRODUCT DESCRIPTION
COMPLY WITH ALL APPI IGARI F CODESor
[/
®
TAMKOASTM Slate
ASTM D 6380, Class M, Type 11 underlayment constructed from organic felt saturat�d'j�y��0
Surfaced Roll Roofing
with asphalt and coated on both sides with asphalt and surfaced with granules. 004
TAMKOO ASTM Tile
ASTM D 6380, Class M, Type II underlayment constructed from an organic felt saturated
Underlayment
with asphalt then coated on both sides with asphalt and surfaced with granules.
TAMKO® Master
ASTM D 6380, Class S, Type IV underlayment constructed from an organic felt saturated
Smooth
with asphalt then coated on both sides with asphalt and surfaced with a fine mineral. For
use in non-HVHZ only.
TAMKOO Moisture
Self -adhered, ASTM D 1970, fiberglass reinforced, modified bitumen sheet membrane
Guard®
with a mineral surfacing and a removable release film on the adhesive side and
removable selvedge release tape.
TAMKO® No. 15 ASTM
ASTM D 226, Type I underlayment constructed from a non -perforated organic felt that is
Asphalt Saturated
saturated with asphalt.
Organic Felt
TAMKO® No.15 UL
ASTM D 226, Type I underlayment constructed from a non -perforated organic felt that is
Asphalt Saturated
saturated with asphalt
Organic Felt
TM
�y��7AMK0® No�30/`�ISTM
ASTM D 226, Type II underlayment constructed from anon -perforated organic felt that is
FAsp911:,Saturated
saturated with asphalt.
TAMKO® No. 30 UL
ASTM D 226, Type II undedayment constructed from a non -perforated organic felt that is
Asphalt Saturated
saturated with asphalt.
Organic Felt
TAMKO®TW Metal and
Self -adhered, flexible, ASTM D 1970 and TAS 103, rubberized asphalt sheet membrane
Tile Underlayment
with a polymer film on the surface and a removable release film on the adhesive side.
TAMKO®TW
Self -adhered, flexible, ASTM D 1970, rubberized asphalt sheet membrane with a
Underlayment
polymer film on the surface and a removable release film on the adhesive side.
TBP14001A FL12328-RB Page 1 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G203. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply wananty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
.'
.��=
_
-_
_ _
,,
-
„_I
., .. 4 .. ..
,.�
- _ �
ti. 1 �_
-,�
- -
-_ - -
';
`✓
♦
f `
.. �Y� �..
.
��
.e
�
.. •
L..
� �
.,
.. - n - .' .. ...
.. .. r ��
..
t y�
'�
t
V
.,
`�
_ J e l � y
1.
� i 3 � �:+
.. ..
I _
_
r=i'
�L' .�
��:
CNREEK
iiuPAKOBUILDINGPRODCUTS,INC.
TAMKO Undedayments
- TECHNICAL SERVICES,-LLC— - — - - - - -
TAMKO® TAM -FELT Alternate to ASTM D 226, Type I and Type II underayment constructed from a non -
perforated organic felt that is saturated with asphalt
APPLICATION METHOD
Installation shall be in accordance with the published manufacturer's installation instructions, the FBC, and the
requirements below.
Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck shall be
checked for protrusion and corrected prior to underayment application.
The roof deck shall be constructed of closely fitted plywood sheathing for new or existing construction. Plywood deck
shall be installed in accordance with FBC requirements. Roof decks shall have no more than 1/8' gap at abutting
joints.
The minimum application temperature shall be 50'F except as follows:
a) The minimum application temperature of TAMKO® TW Metal and Tile Undedayment and TAMKO@ TW
Undedayment shall be 40'F.
b) The minimum application temperature of TAMKO® Moisture Guard® shall be 35°F.
The minimum roof slope shall be in accordance with FBC requirements except as follows:
a) The minimum slope of TAMKOO ASTM Slate Surfaced Roll Roofing shall be 2:12.
Underlayments shall be exposed in accordance with the manufacturer's recommendations, but in no case shall
exposure exceed 30 days.
Exception: TAMKOS TW Metal and Tile Underlayment may be exposed for a maximum 90 days.
Self -adhering undedayments may be adhered to primed or unprimed plywood substrates in the non-HVHZ.
All roof coverings shall be mechanically fastened through the undedayment to the roof deck.
Allowable Roof Coverings:
-
Metal Root
Mineral '
Wood
-
--
Asphalt
Panels and
Surfaced Roll
Shingles and
Slate
Clay and
Underlayment
Shln Ies.
Shinales
Roofing
Shakes
Shingles
Concrete Tile
TAMKOO ASTM Slate
Y'
N
N
N
N
Y
Surfaced Roll Roofing
-FA KOS ASTM Tile
N
N
N
N
N
Y
Undedayment
TAMKOOMaster Smooth
Y'
N
N
N
N
N
TAMKOO Moisture Guard®
Y
N
N
N
N
N
TAMKOO No.15 ASTM
Asphalt Saturated Organic
Y
Y
Y
Yz
N
N
Felt
TAMKOO No.15 UL Asphalt
Y
Y
Y
Y'
Y
N
;, Saturated ,Organic Fe!t„-,
. TAMKO®.No.30`ASTMA;P,'
Asphalt,Sajdrated'Oiganic
Y
Y
Y
Y
Y
Y
,.TAMKOO No. 30 UL Asphalt
Y
Y
Y
N
Y
N
Saturated Organic Felt
TAMKOO TW Metal and Tile
Y
Y
N
N
N
Y
Underlayment
TAMKOOTWUnderlayment
Y
Y
N
N
N
N
TAMKOOTAM-FELT
Y
N
N
N
N
N
Notes: 1) Open valley applications per 1507.2.9.2
2) Wood shingles only
TBP14001.4 FL12328-RB Page 2 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CD �)(K TAMKO BUILDING PRODCUTS, INC.
IZ TAMKO Underlayments
- TECHNICAL SERVICES,-LLC — -- -
LIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) Wind uplift resistance in not within scope of this evaluation.
3) Installation of the evaluated product shall comply with this report, the FBC, and the manufacturer's published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
4) Contact the manufacturer when installing at temperatures below the minimum application temperature.
5) Unless otherwise stated, the minimum roof slope shall be in accordance with FBC requirements.
6) All undedayments shall be installed with the roll length parallel to the eave, starting at the eave, and lapped
in successive courses installed up the deck in a manner that effectively sheds water from the deck. End
laps shall be staggered between courses in accordance with the manufacturer's application instructions.
7) The undedayment may be used as described in other current FBC product approval documents.
8) The undedayment shall not be installed over existing roof coverings.
9) Contact the manufacturer regarding specific exposure limits for each undedayment.
10) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61G20-3.
REFERENCES
ED&
Report No.
Standard
Year
PRI Construction Materials Technologies (TST6049)
TAP-192-02-01
ASTM D 1970
2015a
PRI Construction Materials Technologies (TST6049)
TAP-193-02-01
ASTM D 1970
2015a
PRI Construction Materials Technologies (TST6049)
TAP-214-02-01
ASTM D 4869
2016
PRI Construction Materials Technologies (TST6049)
TAP-215-02-01
ASTM D 226
2009
PRI Construction Materials Technologies (TST6049)
TAP-216-02-03
ASTM D 6380
2003(2013)
PRI Construction Materials Technologies (TST6049)
TAP-217-02-01REV
ASTM D 6380
2003(2013)
PRI Construction Materials Technologies (TST6049)
TAP-218-02-01
ASTM D 226
2009
PRI Construction Materials Technologies (TST6049)
TAP-219-02-01
ASTM D 226
2009
PRI Construction Materials Technologies (TST6049)
TAP-220-02-01
ASTM D 6380
2003(2013)
PRI Construction Materials Technologies (TST6049)
TAP-222-02-01
ASTM D 4869
2016
PRI Construction Materials Technologies (TST6049)
TAP-245-02-01
TAS 103
1995
ASTM D 4798
2011
PRI Construction Materials Technologies (TST6049)
TAP311-02-01
ASTM D 1970
2015a
PRI Construction Materials Technologies (TST6049)
TAP319 )2-01.1
ACC 188
2012
PRI Construction Materials Technologies (TST6049)
TAP387-02-01
ASTM D 1970
2015a
PRI Construction Materials Technologies (TST6049)
TAP388-02-01
ASTM D 1970
2015a
UL LLC (TST9628)
13CA12269
ASTM D 226
2009
TBP14001.4 FL12328-RB Page 3 of 4
This evaluation report is provided for State of Florida product approval under Rule 61G203. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
I
CREEK 'TAMKOBUILDIMKOUnderlaymNC.
TAMKO Underlayments
TECHNICAL SERv10Es,.LLC
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code, 6 h Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer.
j%J11111111111, I.,
E N F �Fsj•��
No 74021
9•• STATE OF *441�
O R�`,
.J.Z 9,Q N A %%%��
CERTIFICATION OF INDEPENDENCE
2017.10.19
12:15:58
-04 00
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing products under this
evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under this evaluation.
Zachary R. Priest, P.E. does not have, nor vrill acquire, a financial interest in any company manufacturing or distributing products under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved In the approval process of the product
END OF REPORT
TBP14001.4 FL12328-R8 Page 4 of 4
This evaluation report is provided for State of Florida product approval under Rule 6113203. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.