EVALUATION REPORT
Manufacturer.
WC —IN 46410
516-1485
Certificate of Authorization No. 29824
17520 Edinburgh Drive
Tampa, FL 33647
(813)480-3421
FLORIDA BUILDING CODE Ere EDITION
Issued February 21, 2018
Quality Assurance: Intertek Testing Services (QUA1586) SCANNED
BY
SCOPE St- Lucie County
Category:
Roofing
Subcategory:
Undedayments
Code Sections:
1507.1.1,1518.4
Properties:
Physical properties
REFERENCES
Entitv
Report No.
Standard
Year
Intertek Testing Services (TST1585)
102074565COQ-004
AC 81AC S
2012
Intertek Testing Services (TST1585)
102074566COQ-004A
AC 18W
2012
Intertek Testing Services (TST1585)
102074565COQ-007
ASTM D 226
2009
Intertek Testing Services (CER1497)
CCRR-1045
IBC, IRC
2012
PRI Construction Materials Technologies (TST5878)
CMI-048-02-01A
ASTM D 226
2009
PRI Construction Materials Technologies (TST5878)
CMI-048-02-01B
ASTM D 226
Y0o9
PRI Construction Materials Technologies (17ST5878)
CMI-048-02-DI C
ASTM D 226
2009
PRI Construction Materials Technologies (TST5878)
CMI-055-02-01
ASMT D 4533
2015
PRI Construction Materials Technologies (TST5878)
CMI-056-02-01
ASMT D 4533
2015
'Determined to be equivalent to ASTM D 226 (2009), Type I and II
PRODUCT DESCRIPTION
Tri-built Synthetic 10 A mechanically attached, woven polypropylene undedayment (nominal weight = 1.74
Roof Underlayment Ib/100le) used an alternative to ASTM D 226, Type I and Type II with a minimum tear
strength per ASTM D 4533 of 20.pounds. The undedayment is available in rolls 48-inch
wide by 250-ft long.
Tri-Built Synthetic 25 A mechanically attached, woven polypropylene undedayment (nominal weight = 2.05
Roof Underlayment IbI100fl?) used an alternative to ASTM D 226, Type I and Type 11 with a minimum tear
strength per ASTM D 4533 of 20 pounds. The undedayment is available in rolls 48-inch
wide by 250-ft long.
Tri-Built Synthetic Plus A mechanically attached, woven polypropylene undedayment (nominal weight = 2.46
Roof Underlayment Ib/100ft) used an alternative to ASTM D 226, Type 1 and Type II with a minimum tear
strength per ASTM D 4533 of 20 pounds. The undedayment Is available in rolls 48-inch
wide by 250-ft long.
Tri-Built Synthetic MAX A mechanically attached, woven polypropylene undedayment (nominal weight = 3.69
Roof Underlayment Ib/100fe) used an ahemative to ASTM D 226, Type I and Type 11 with a minimum tear
strength per ASTM D 4533 of 20 pounds. The undedaymentis available in rolls 48-inch
wide by 25D-ft long.
1 of 3
This evaluation report is provided for State of FWda h Tduct approval under 61G203. The manufacturer shall notify CREEK
Technical Services, LLC of any product change& -or qua gss throughout the duration for which this report is valid.
This evaluation report does not express nor imply Karranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK TRI-BUILT MATERIALS GROUP
T ECHNICAL SEITViCES. LLC Synthetic Undedayments
APPLICATION INSTRUCTIONS
Deck Type: The roof deck shall be constructed of closely fitted, solid sheathing for new or existing
construction. Sheathing shall be installed in accordance with FBC requirements. New
construction in the HVHZ shall be minimum 19/324nch plywood. Roof decks shall
have no more than 1/84nch gap at abutting joints.
Attachment method Undedayment shall be attached in accordance with the FBC Table 1507.1.1 and
(non-HVHZ): manufacturer's installation instructions.
Attachment method Undedayment shall be installed with a minimum 4-inch head lap and minimum 6-inch
(HVHZ): end lap and be fastened as specified in FBC Section 1518.2.
Allowable roof coverings Mechanically attached roof systems as prescribed in FBC Section 1507.1.1.
(Non HVHZ):
Allowable roof coverings Undedayment shall be used with mechanically attached asphalt shingles, metal roof
(HVHZ): panels and shingles, composite shingles and wood shingles and shakes
LIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) Wind uplift resistance is not within the scope of this evaluation.
3) Installation of the evaluated product shall comply with this report, the FBC, and the manufacturers published
application instructions. Where discrepancies exist between these sources, the more restrictive and FBC
compliant installation detail shall prevail.
4) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlaymentapplication_
5) Roof slope limitations shall be in accordance with FBC requirements.
6) All underiayments shall be installed with the roll length parallel to the save, starting at the save, and lapped
in success courses installed up the deck in a manner that effectively sheds water from the deck.
7) The undertayment may be used as described in other current FBC product approval documents.
8) Roof coverings shall not be adhered directly to the underlayment. Roof coverings shall be mechanically
fastened through the underiayment to the roof deck.
9) The underiayment shall not be installed over existing roof coverings.
10) The undedayment shall be exposed on the roof deck for a maximum 30 days unless othervvise stated.
11) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G203.
c.auauon report is.provrded for State of Florida product approval under Rule 61G20.4. The manufacturer shall notify CREEK
Technical Services. LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
Thisevaluation report does not express nor Imply warranty, Installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
I..:J TECHNICAL SERVICES, LLC
COMPLIANCE STATEMENT
TRI-BUILT MATERIALS GROUP
Synthetic Underlayments
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code, 6h Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer.
i`% %% ..........
E NSF
— No 74021
0'. STATE OF : 1JJ
�.
'•i�cC'�C O R 19
2018.02.21
l��'- 13:42:11
-05,001
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE9641
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services, LLC does not have, nortw7l it
evaluation. acquire, a financial interest in any company manufacWdng or distributing products under this
CREEK
CREEK Teduticai Services, LLC Is not owned, operated, orconlmtied by any company manufacturing or distributing products underthia evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial Interest in any company manufacturing or distributing products under Oft evaluation.
Zachary R Priest P.E. does not have, nor will acquire, a financial Interest In arty other entity immured In the approval process of the product.
END OF REPORT