HomeMy WebLinkAboutPLANSv F? General Notes A. CONCRETE & FOUNDATION DESIGN- 1. ALL CONCRETE GRADE BEAMS AND FOOTINGS SHALL BE 3000 PSI MINIMUM. 2. ALL CONCRETE FILLED SUPPORTED SLABS SHALL BE 2500 PSI MINIMUM, 3 1/2" NOMINAL THICKNESS. APPROPRIATE ACI AND ASTM REQUIREMENTS MAY BE USED IN LIEU OF WELDED WIRE MESH 4. ALL SLABS ON GRADE SHALL BE 4" THICK WITH FIBERIVI ESH. 5. AIL REINFORCING SHALL CONFORM TO ASTM A615, BE GRADE 60 (60 KSI MIN.) DEFORMED BARS, #3 BARS MAY BE GRADE 40 6. ALL OVER POUR CONCRETE FILLED SUPPORTED SLABS SHALL BE 3000 PSI MIN., 2" MINIMUM. THICKNESS, 7. SOIL BEARING PRESSURE SHALL BE A MINIMUM OF 1500 PSF. S. THE CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING: OPC (PORTLAND CEMENT TYPE 1,- ASTM C 150). AGGREGATES - #6 STONE, ASTM C 33 SIZE NO.67 LESS THAN 3/4". AIR ENTRAINING+/- 1%- ASTM C 260. WATER REDUCING AGENT - ASTM C 494. CLEAN POTA13LE WATER OTHER ADMIXTURES SHALL NOT BE PERMITTED. 9. METAL WELDED WIRE SHALL CONFORM TO ASTM A 185. 10. PREPARE & PLACE CONCRETE ACCORDING TO AMERICAN CONCRETE INSTITUTE MANUAL STANDARD PRACTICE, PART 1, 2, & 3 ALONG WITH HOT WEATHER CONDITIONS RECOMMENDATIONS. 11. IF UTILIZING EXISTING CONCRETE FOR FOUNDATION, CONCRETE SHALL BE A MINIMUM OF 4" IN THICKNESS, VISIBLY FREE OF ANY STRUCTURAL EXCESSIVE CRACKING, SPALLING OR OTHER DETERIORATION. B. MASONRY: 1. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR 2. ALL MORTAR SHALL BE OF TYPE M OR S. 3. ALL GROUT SHALL BE 2000 PSI MIINDAUM AND HAVE MAXIMUM COARSE AGGREGATE SIZE 01`21W. 4.PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS 5'-0" IN HEIGHT. C. ALUMINUM: 1. ALL STRUCTURAL ALUMINUM SHALL CONFORM TO THE MINIMUM REQUIREMENTS OF 6005-TS FOR ALLOY WITH A MINIMUM THICKNESS OF 0.040" FOR SUPPORTING MEMBERS. 2. WHERE KICK PLATES ARE USED A MINIMUM THICKNESS OF 0.024' SHALL APPLY. 3. STRUCTURAL ALUMINUM DESIGN CONFORMS TO "PART 1-A - SPECIFICATIONS FOR ALUMINUM STRUCTURES - ALLOWABLE STRESS DESIGN" OR "PART 1-B - SPECIFICATIONS FOR ALUMINUM STRUCTURES - BUILDING LOAD AND RESISTANCE FACTOR DESIGN" OF THE ALUMINUM DESIGN MANUAL PREPARED BY THE ALUMINUM ASSOCIATION, INC. WASIIINGTON D.C. THE FLORIDA BUILDING CODE 61h EDITION ( CHAPTER 16 STRUCTURAL DESIGN & CHAPTER 20 ALUMINUM). 4. WHERE ALUMINUM COMES INTO CONTACT WITH STEEL, OR PRESSURE TREATED LUMBER PROVIDE DIELECTRIC SEPARATION. 5. ALUMINUM MEMBERS SHALL BE STITCHED WITH NO LESS THAN #10 SMS 6" FROM THE ENDS AND IY ON CENTER, IF USING #12 SPACING MAY BE 24" ON CENTER. 6. VINYL AND ACRYLIC PANELS SHALL BE REMOVABLE. THEY SHALL BE IDENTIFIED WITH A DECAL ESSENTIALLY STATING "REMOVABLE PANEL SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH" . DECAL SHALL BE PLACED SO IT IS VISIBLE WHEN PANEL. IS INSTALLED. 7. VX2"XO.045" NON-STRUCTURAL MEMBERS SHALL BE ATTACHED TO HOST WITH 1/4"0 X 1-3/4" EMBEDMENT & 24" O.C. MASONRY SCREW FOR CONCRETE & EQUIVALENT SIZE WOOD SCREW WHEN IN WOOD & 91OX 1/2' EMBEDMENT SMS OR TEK SCREWS IN ALUMINUM MEMBERS TYPICAL. D. FASTENERS: I. ALL LAG BOLTS SHALL CONFORM TO STAINLESS STEEL TYPE 30018-8, WITH STANDARD FLAT WASHER UNLESS MANUFACTURER GALVANIZES BOLTS SPECIFIES FOR USE WITH ACQ PRESSURE TREATED WOOD. 2. HEX BOLTS HAS TO BE ASTM A 325, PLATED WITH STANDARD FLAT WASHERS AND NUTS. 3. ALL CONCRETE SCREWS SHALL BE, SIMPSON, FIILTI, RAWL, TAPCON,REDHEAD, DYNABOLT, PORTECT OR APPROVED EQUAL. 4. ALL METAL TIES AND ASSOCIATED ACCESSORIES SHALL BE 5. ALL LAG BOLTS SHALL HAVE A MINIMUM EMBEDMENT OF BX BOLT DIAMETER INTO STRUCTURAL FRAMING (G=.42 MIN.). 6. LAG BOLTS AND SCREWS INTO WOOD FRAMING SHALL BE PROVIDED WITH PILOT HOLES HAVING A DIAMETER NOT GREATER THAN 70 PERCENT OF THE THREAD DIAMETER OF THE BOLT OR SCREW. ALL LAG 13OLTS AND SCREWS SHALL BE INSERTED IN PILOT HOLES BY TURNING AND UNDER NO CIRCUMSTANCES BY DRIVING WITH A HAMMER ]. ALL EXPANSION ANCHORS SHALL BE DESIGNED IN ACCORDANCE WITH THE SPECIFIC MANUFACTURER'S REQUIREMENTS AND ALLOWABLE LOADS AND SHALL ONLY BE APPLIED IN CONDITIONS ACCEPTABLE TO MANUFACTURER FASTENERS SHALL BE A MINIMUM OF SAE GRADE 45 OR BETTER ZINC PLATED. S. ALL FASTENERS CONNECTING ALUMINUM COMPONENTS OR PRESSURE TREATED LUMBER ARE STAINLESS STEEL TYPE 300 18-8, UNLESS MANUFACTURER GALVANIZED BOLTS SPECIFIES FOR USE WITH ACQ PRESSURE TREATED WOOD, OR OTHERWISE NOTED ON PLANS. 9. ALL FASTENERS SHALL COMPLY WITH ASTM A153. 10. ALL CONNECTORS SHALL COMPLY WITH ASTM A653 CLASS G-185. 11. FOR SMS, THE MINIMUM CENTER -TO -CENTER SPACING SHALL BE 3/4" AND MINIMUM CENTER -TO -EDGE SHALL BE 1/2" UNLESS NOTED OTHER WISE. E. REFERENCE STANDARDS: ASTM E 119 ASTM E 1300 CURRENT ASCE 7 CURRENT ALUMINUM DESIGN MANUAL -AA ASM35, AND SPEC. FOR ALUMINUM PART 1-A, & 1-B ASTM C94 ASTM C150 ASTM C33 ASTM C260 ASTM C494 ASTM A615 ASTM A185 FLORIDA BUILDING CODE 6th EDITION (CHAPTERS 16,20 & 23). F. ABBREVIATIONS: THE FOLLOWING LIST OF ABBREVIATIONS IS NOT INTENDED TO REPRESENT ALL THOSE USED ON THESE DRAWINGS, BUT TO SUPPLEMENT THE MORE CONL MON ABBREVIATIONS. 1. TYP -TYPICAL 2. SIM--SIMILAR 3. UON - UNLESS OTHERWISE NOTED 4. CONT - CONTINUOUS 5. VIF-VERIFY IN FIELD G. RESPONSIBILITY: 1. ALL SITE WORK SHALL BE PERFORMED BY A LICENSED CONTRACTOR INACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDINANCES, ETC. 2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND DETAILS, NOTIFYING ENGINEER OF ANY DISCREPANCIES BETWEEN DRAWINGS, FABRICATED ITEMS, OR ACTUAL FIELD CONDITIONS. 3. THESE DRAWINGS REPRESENT THE ACCEPTABILITY OF THE 'SUNROOM' ROOM ADDITION ELEMENTS AS PROVIDED BY THE CONTRACTOR. 4. ALL DETAILS ON THESE DRAWINGS ARE ENGINEERED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND MANUFACTURER. 5. ANY DETAILS NOT SHOWN ARE TO BE ENGINEERED BY A LICENSED P.E. IN ACCORDANCE WITH STANDARD ENGINEERING PRACTICES. IL MISCELLANEOUS: 1. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAS HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPARATE 4TH WALL SUPPORT SYSTEM MUST BE ENGINEERED SO THAT NO ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. z. IFENCLOSURE CONTAINS ASWIMMING POOL OR SPA, THE ENCLOSURE SHALL COMPLY WITH RESIDENTIAL SWIMMING COPY Y BARRIER REQUIREMENTS OF 771E FLORIDA BUILDING CODE 61h FILE EDITION R4501.17 IN ITS ENTIRETY. _ CONTRACTOR 4. IF PAVERS ARE UNDER ALUMINUM MEMBERS THEY SHALL HAVE EPDXY ADHESIVE TO CONCRETE OR IF USING GROUT, ENSURE BONDING AGENT IS USED FIRST. SCREENING MATERIAL SHALL BE ISX14XO.013 OR EQUIVALENT DENSITY SCREEN MESH ONLY UNLESS NOTED ON DRAWING S-2. i. PLEASE NOTE: 2x2 (typ) DIAGONAL BRACING SHALL BE 2'X2"XO.055" MATERIAL, UNLESS OTHERWISE NOTED ON S-2. DESIGN DATA: 1. ULTIMATE DESIGN WIND SPEED Vu11, (3 SECOND GUST): NOMINAL DESIGN WIND SPEED VaMI: 2. RISK CATEGORY: 3. WIND EXPOSURE: 4. RIND LOADS: SCREEN ROOF: 9 PSF SCREEN WALLS: 31 PSF SOLID ROOP (SCREEN WALL): 25 PSF COMPONENTS AND CLADDING LOAD: +16.00/-28.52 PSF 1^ 1 ISO MPH 116 bPH 1 B 5. FACTOR APPLIEDTO SCREEN WIND LOADS FOR 18X14XO.013 OR EQUIVALENT DENSITY SCREEN MESH: 0.89 6. FACTOR APPLIED TO SCREEN WIND LOADS FOR ALLOWABLE STRESS DESIGN:_0.6 7. LIVE LOAD: 3001b. VERTICAL DOWNLOAD ON PRIMARY SCREEN ENCLOSURE MEMBERS. 2001b. VERTICAL DOWNLOAD ON SCREEN ENCLOSURE PURLINS. 8. EXISTING SLAB AND OR FOOTING MEETS THE REQUIREMENTS TO RESIST THE UPLOADS FOR THE PROPOSED STRUCTURE. 9. SCREEN ROOF TYPE: N/A 10. SOLIDROOFTYPE: 3"X48"XO.024" STRUCTALL FPS FOAM CORE COMPOSITE PA ALUMINUM STRUCTURAL MEMBERS HOLLOW SECTIONS 2 x 2----------------------------------------2" x 2" x 0,044„ 2 x 3----------------------------------------2" x 3" x 0.050„ 2 x 4:---------------------------------------2" x 4" x 0.050„ 2 x 5:------------------ _-------------------- 2" x 5" x 0.050" 3 x 3:---------------------------------------3" x 3" x 0.125" OPEN BACK SECTIONS 1 x 2:---------------------------------------- 1" x 2" x 0.040" 1 x 3-----------------------------------------1" x 3" x 0.045' SNAP SECTIONS 2 x 2 SMS:----------------------------------2" x 2" x 0.045" 2 x 3 SMS----------------------------------2"x 3" x 0.072" 2 x 4 SMS---------------------------------- 2" x 4" x 0.045" 3 x 3 SMS---------------------------------- 3" x 3" x 0.090" SELF MATING fSMB 2 x 4 SMB:-------------•-------- 2" x 4" x 0.044" x 0.100' 2 x 5 SMBr------------•-_------ 2" x 5" x 0.050" x 0.118" 2 x 6 SMB:------------- •-------- 2" x 6" x 0.050" x 0.120" 2 x 7 SMB-------------•-------- 2" x 7" x 0.057" x 0.120" 2 x 8 SMB:---------------------- 2" x B" x 0.072" x 0.224" 2 x 9 SMBr------------•-------- 2" x 9" x 0.072" x 0.224" 2 x 10 SMB-------------------- 2"x 10" x 0.092"x 0.37V TUBE SECTIONS 2 x 2________________________________________2" x 2" x 0.090" o : .9 m OP DA ENGINEER OF RECORD: David W, Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson RE FLORIDA LICENSE: 38654 Mark R. Dunn P.E. FLORIDA LICENSE: 73968 Joel Falardeau P.E. FLORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineerir Services, Inc. 6272 AbbottStation Dr. Unit 101 Zephyrhills, FL 33542 Ph#(813)788.5314 Fax# 1-(866)824-7B94 E-mail-erb@fbcplans.com W ebS ite- W ww. fbcplans.com C.O.A.429054 DATE: 1/22/2018 DRAWN BY: TLK DATE: RO 1 RO 2 RO 3 RO 4 PROJECT ADDRESS: SMITH 4908 PALMETTO DR =T PIERCE, FL 34952 ONTRACTOR: �t K & S INDUSTRIES, INC. 1379 SW BILTMORE ST. PORT ST LUCIE, FL 34983 NOTES S-1 10, OR IN PART W THOUT EXPRESSED WRITTEN PERMISSION OF 1X2 o N N 2X311mw Lwu a o I N r X N 2X4So N X O T I 2X5SMB CL X N X N 1 X2 N X I W301 m cn N m (n S-3 N ro 2X2 t N c I I 0 o X X N N s-3 Imo[ 7-0 1X''`` 2 r� \2,_6„ .aE4`�tnelllF/Os nth � 1.ICE,yS. p d 706 f U _� •Ce TAf�O[; t e j ORiDA ,r ENGINEER OF RECORD: David W. Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson P.E FLORIDA LICENSE: 38654 Mark R. Dunn P.E. FLORIDA LICENSE: 73968 Joel Falardeau P.E. FLORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineering Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph# (813)788-5314 Fax# 1-(866)824-7894 E-mail-erb@fbcplans.com Website-www.fbcplans.com C.O.A. #29054 I DATE: 1/22/2018 I DRAWN By: TLK REVISION; DATE: RO 1 F 2 3�E R0 4 Job# 19010930 PROJECT ADDRESS: 18 PALMETTO DR PIERCE, FL 34952 :ON"TRACTOR: K & S INDUSTRIES, INC. 1379 SW BILTMORE ST. PORT ST LUCIE, FL 34983 FLOOR PLAN S-2 BE REPRODUCED IN WHOLE OR IN PART WITHOUT EXPRESSED WRITTEN PERMISSION OF TRAC BEAM SCREWS 2"X 4' SMB 6 2"XS"SMB 6 2"x7"SMB 8 2"XB"SMB 10 2"X9"SMB 10 2"X10"SMB 12 BEAM 00 FLATOR 00 SLOPPED 00 U U SECONDARYANGLE MIN (4)#IOX3/4"SMS 0,125"THICK(NOT FASTENING SECONDARY REQUIRED FOR 2X3 L � a13V ANGLE TO COLUMN(n MEMBER) 1 2 � #lOX4"SMSASHE EgCHS1DE)- PRIMARY2"X2" NEOPRENEWASHER 8"O.C. PER PANEL (B)-3/8'OCONCRETE SCREW XO.125"ANGLE SOLID ANCHOR INTO SECONDARY I (2) #10 X3/4" SMS FASTENING ROOF PANEL ANCLE('IYP EACH SIDE)(SEE O COLUMNTO PRIMARY ANGLE TABLE) O (TTPEACH SIDE) O 1" X 2" BASE MEMBER (TYP EACH SIDE) ANCHOR SPA .L OPTION #1 (MIN)(7"P)(SEE TABL) (1)-3/8"OCONCAETE SCREW ANCH ®® i 3 0 2" x 2"x Y," ALUM RECEIVING CHANNEL w/ CONNECTION SIMILAR TO D, S-3, (10)#12 x 3/4" INTO FOR NUMBER OF #14X 3/4" BEAM&(10)#12x3/4" SCREWS SEE TABLE BELOW INTO CARRIER BEAM 2" x—" SMB 2X_ SMB UPRIGHT ARRIER BEAM (SEE (SEE SHEET S-2 FOR SHEET S-2 FOR SIZE) SIZE) A CARRIER BEAM CONNECTION DETAIL S 3 SCALE NTS Column Size 3/8" 0 Concrete Screw Anchor B Min. Spa 2x3 2x4 3 D5 2x6 2X7 2x8 2 2x9 4' 2x10 2 4. d OR INTO PRIMARY ANGLE AND @ 1/4" 0 CONCRETE- 3"(MIN) SCREWANCHOR@ 24" O.C. BETWEEN COLUMNS NOTES: (IYP EACH SIDE) 1. NUMBER OF ANCHORS"B" IS EACH SIDE INTO THE SECONDARY ANGLE AND DOES NOT INCLUDE THE ANCHOR INTO THE IXZ. 2. MINIMUM EMBEDMENT OF ANCHORS INTO CONCRETE FOOTING SHALL BE 2-31V ATAT ALL UPRIGHT LOCATIONS. ALL SCREW LENGTHS AT UPRIGHT CONNECTIONS SHALL BE OF SUFFICIENT LENGTH FOR REQUIRED EMBEDMENT INTO CONCRETE FOOTING WHEN A PAVER DECK IS PRESENT. 3. CONCRETE SCREW ANCHOR DESIGNS ARE BASED ON ITW RED HEADS LOT 3/8" O STAINLESS STEEL CONCRETE SCREW. OTHER SIZE OR TYPE OF ANCHORS SHALL NOT BE USED. 4. 2X3W/1X2 CORNER POST SHALL REQUIRE SAME BASE CONNECTIONS AS 2X4 SHOWN IN TABLE. -(4)#lox-1'/, .SMS INTO�I1 iI OPTION#2 2"X2"OR2"X3"_j I I 0.062"ALUMINUM INTERNAL OR MEMBER EXTERNAL RECEIVING CHANNEL W/ (4) #IO X 3/4" INTO INTO LBEAM OR UPRIGHT. (2) #14X 3/4" EA LEG INTO GIRT OR PURLIN- (0.062"ANGLE CLIPS W/ (2) - #140/4" SMS EA LEG) UPRIGHT OR BEAM -SNAP OR SELF MATING OR � ,\ HOLLOW / n \ PURLIN OR GIRT TO BEAM OR POST DETAIL S-3 SCALE: NTS BEAM SCREWS 1" X 5" or 7" X4" WIDTH EXTRUDED GUTTER 2" X 4" SMB 6 BRACKET(THICKNESS OF LEG @ LAG 2' X 5 "SMB 6 3" RECEIVING CHANNEL SCREW SHALL BE 0.125" MIN. 2" X 6'SMB 8 8 W/#12 X 4" SMS IONG LEG SHALL BE 0.072" MIN) 2' X 7" SMB 10 1-1/4' NEOPRENE EACH BEAM1 (4) 2"XS"SMB 2"X9"SMB 10 WASHER @ 8° O.C. PER #12X3/4" SMS 1" SPA. 1 Z' X 10" SMB 12 PANEL INTO GUTTER LIP&ANGLE HINGE LOCATION (2) 3/8" LAG SCREWS @ 1-112" 3" COMPOSITE PANEL SPACING @ EA. GUTTER BRACKET FOR SLOPED BEAMS, (1) @ 12" O.C. MAX- MIN EMBEDMENT 2" x 2" EXTRUSION 2" x 2" EXTRUSION MAINTAIN ALL SCREW SPACING SHALL BE 2" FROM EDGE OF BEAM / BEAM ------------------ - �i'SELF-MATING SHALL BE NOTCHED - - - -_--_----_---_ -_ -_ - - - - HINGE LOCATION DOOR 2"x2"EAVE RAIL SECTION 5 V FORUPRIGHT _ ------------- - - (UNLESS OTHERWISE SHOWN ON S-2) - ATTACHED TO BEAM w/�� (3) IOX 2" SMS INTO SCREW BOSS O O �I rk 1"X2"OPEN BACK EAVE RAIL ATTACHED TO oil HINGELOCATION UPRIGHTw/(2 #lox l Y," SMS INTO SCREW I i BOSS \.2'NOTCHOF INSIDEBEAM 2X8 SMB STITCHED TO #30 X 1 %' SMS 24" C/ TO SLIDE OVER UPRIGHT SUPER GUTTERW/(2)#14 THE HOST STRUCTURE NOTES: 414X 3/4"SCREWS X3/4" @ 24O.C. & @ EA - SHALL HAVE AT LEAST 1. HINGES SHALL BE ATTACHED TO STRUCTURE W/ (3) #10 x 5/8" SMS MINIMUM. (SEE TABLE Aeove) GUTTER BRACKET '" 2"X4"FASCIA AND ROOF 2. DOOR SHALL BE ATTACHED TO ENCLOSURE w/(2) HINGES MINIMUM. "(MIN)UPRIGHT SUPER GUTTER TRUSSSYSTEM. 3. HINGES SHALL BE ATTACHED TO DOOR WITH (3)#30x5/8"SMS. FASTEN CONTRACTOR SHALL 1" x 2" x 0.044" TO UPRIGHT W/#12 x 1" SMS @ 12" O.C. AND WITHIN 3" FROM VERIFY THIS AND IF END OF THE UPRIGHT. S SMALLER -CONTRACTOR COMPOSITE ROOFTO GUTTER DETAIL SHALL BRING STRUCTURE S 3 SCALE: NTS UP TO A 2"X4" FASCIA AND ENSURE LESS THAN A2'-0" OF TypICALSCREEND00RCONNECT[ONDETAILD UPRIGHT TO BEAMCONNECTION-ALLWINDZONES OVERHANG. S_3 SCALE: NTS SCALE: NTS 3 �-3j •:�O FOR vj .• e �,`�s i a���F°ENGI• David W. Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson RE FLORIDA LICENSE: 38654 Mark R. Dunn P.E. FLORIDA LICENSE; 73968 Joel Falardeau P.E. FLORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineering Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph# (813)788-5314 Fax# 1-(866)824-7894 E-mail-erb@fbcplans.com W ebs ite-ww W.fbcp]ans.com C.O,A: #29054 DATE: 1/22/2018 DRAWN BY: TLK REVISION; DATE: RO 1 2 3 R4 Job# 19010930 PROJECT ADDRESS: SMITH 4908 PALMETTO DR FT PIERCE, FL 34952 :ONTRACTOR: K S S INDUSTRIES, INC. 1379 SW BILTMORE ST. PORT ST LUCIE, FL 34983 DETAILS S-3 NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT EXPRESSED WRITTEN PERMISSION OF TRAC DESIGN. U w FORM HEADER OR #10 SMS AT EACH RISER FOR PAN OR#10 SMS@ 8" O.C. FOR COMPOSITE PANEL / \010 SMS@8"O.C. FOR COMPOSITE PANEL (2) #10 SCREWS PER 12" WIDTH CONNECTING PAN TO HEADER (BOTTOM OR BACK OF PAN) #10 X 2" SCREWS PER 12" WIDTH CONNECTL\ WER OR CHANNEL TO FASCIA. Sl ROOF PANEL TO FASCIA CONNECTION DETAILS S_4, SCALE: NTS C ILE COPY ` Ge�l� p(-053D ROOF n• �Tgp oC: F ; O 57 r,�I:-.s�ailll ENGINEER OF RECORD: David W. Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson P,E FLORIDA LICENSE: 38654 Mark R. Dunn P.E. FLORIDA LICENSE: 73968 Joel Falardeau P.E. FLORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineering Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph# (813)788-5314 Fax# 1-(866)824-7894 E-mail-erb@fbcplans.com W ebs ite- W ww. fb cp I an s. c o m C.O.A: #29054 DATE: 1/22/2018 DRAWN BY: TLK REVISION: DATE: RO 1 RO 2 RO 3 RO 4 Job# 19010930 PROJECT ADDRESS: SMITH 4908 PALMETTO DR FT PIERCE, FL 34952 CONTRACTOR: K & S INDUSTRIES, INC. 1379 SW gILTMORE ST. PORT ST LUCIE, FL 34983 DETAILS S-4 THIS DOCUMENT SHALL NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT