EVALUATION REPORT St. Lucie Counjy
TRI-BUILT Materials Group, LLC Evaluation Report A42970.10.12-R2
PO Box70 FL16027-R2
Rutherford, NJ07070 Date of Issuance:10/23/2012
(800) 516-1485 Revision 2: 09/25/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the 6`" Edition (2017) Florida Building Code sections noted herein.
DESCRIPTION: TRI-BUILT Modified Bitumen Roof Systems
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity) ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words 'Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 4, plus a 26-page Appendix.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The Facsimile seal appearing was authorized by Robert Nieminen,
P.Eon0912 /2017. Th&doesnatserveasanelecteoniall"igned
dowment
CERTIFICATION OF INDEPENDENCE:
1. Exterior Research & Design, LLC. d/b/a Trinity I ERD does not have, nor does it intend to acquire or will it acquire, a financial interest
in any company manufacturing or distributing products it evaluates.
2. Exterior Research & Design, I.I.C. d/b/a Trinity I ERD is not owned, operated or controlled by any company manufacturing or
distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
S. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
TRINITY ERD -
Enti Examination Reference Date
FM Approvals(TST1867) FM 4470/4474 3023458 07/18/2006
FM Approvals (TST1867) FM 4470/4474 3030668 09/12/2007
FM Approvals(TST1867) FM 4470/4474 3032172 06/12/2009
PRI(TST5878) Physical Properties PUSA-062-02-01 12/04/2007
PRI(TST5878) Physical Properties PUSA-061-02-02 01/28/2008
PRI-(TST5878) Physical Properties PUSA-064-02-02 02/27/2008
PRI (TST5878) Physical Properties PUSA-062-02-02 12/04/2008
Miami -Dade (CER1592) HVHZ Compliance Various NOAs Various
Miami-Dade(CER1592) Proposal for Review 10-0823 10/12/2010
UL LLC (QUA9625) Quality Control MLAgreement 02/27/2012
UL LLC (QUA9625) Quality Control ML Correlation, R27202 08/20/2012
UL LLC (QUA9625) Quality Control Service Confirmation, R14571 Exp.10/06/2018
4. PRODUCT DESCRIPTION:
This Evaluation Report covers TRI-BUILT Modified Bitumen Roof Systems installed in accordance with TRI-BUILT
Materials Group, LLC published installation instructions and the Limitations / Conditions of Use herein. The
following membranes make up the subject systems.
Table 1: Roll -Goods for TRI-BUILT Modified ,Bitumen Roof Systems' ,
Type
Product
Specification
Reference
Grade
Type
SBS Membranes
TriBuilt SA SBS Base
ASTM D6163, Table 2
S
I
TriBuilt SBS Granular
ASTM D6164
G
I
TriBuilt SA SBS Cap
ASTM 06164
G
I
APP Membranes
TriBuilt APP Smooth
ASTM D6222
S
I
TriBuilt APP Granular
ASTM D6222
G
I
TriBuilt SA APP Cap
ASTM D6222
G
I
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity(ERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used
for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Refer to a current Approved Roofing Materials Directory for fire ratings of this product.
5.4 For steel deck installations, foam plastic insulation shall be separated from the building interior in accordance
with FBC 2603.4 unless the exceptions stated in FBC 2603.4.1 and 2603.6 apply.
5.5 The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural
members shall be in accordance with FBC requirements to the satisfaction of the Authority Having
Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC
Approval documentation.
5.6 For recover installations, the existing roof shall be examined in accordance with FBC 1511.
5.7 For mechanically attached insulation or membrane or strip -bonded insulation, the maximum design pressure
for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with
FBC Chapter 16. Zones 2 and 3 shall employ an attachment density designed by a qualified design
professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss
Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS
137. Assemblies marked with an asterisk' carry the limitations set forth in Section 2.2.10.1 of FM Loss
Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements.
Exterior Research and Design, LLC. Evaluation Report A42970.10.12-112
Certificate ofAuthorizadon#950a 6r"EDITION(2017)FBC NON-HVHZ EVALUATION FL16027-R2
TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Revision 2: 09/25/2017
Page 3 of 4
�I I RINi Y I ERD
The following: notes apply to the systems outlined herein:
1. The mofwournevaluation herein pertain[abovedeckroofcomPonents. Roof decks and structural members shall Win accordance with FRC requirements to the satisfaction of the Authority Having Jurisdiction.
Load resistance of the mof deckshall be documented through pmpercodified and/or FKAppmval documentabcm.
2. Insulation/base sheet fastenersshall be of sufficient length for the followingdackengagement:
• Wood: Minimum 0.75-inch penetration.
i Steel: Minimum 0.75-Inch penetration and engage the topflute ofthe steel deck
> Structural concrete: Minimum 1-inch embedment into pilot hole inaccordance with fastener manufacturels published installation instructions.
3. Unless otherwise noted, insulation may be airy one layer or combination of polyisocyanurate, polystyrene, woad fiberboard, pedite, gypsum -based roof board or mineral -wool mof board that meets the OA
requirements of FA.C. Rule 61G20-3 and is documented as meeting FBC 1505.1and, forfoam plastic, FKOapter 26, when installed with the roof cover.
Eatedar Research and Design, lLC d/b/a TrinitylERD Evaluation Report A429)O.1o.12.R2 for FL16OZ2-RZ
UrHfirateof Authomiationg9503 6'a EDITION)ZO17)FeCNON-HVHZIWA UATION Revision 2: 09/25/2017
Prepared by Robert Nieminen, PE-59166 TRIdUHT Modtied Ritumen Roof Systems;)900) 5161485 Appendla 1, Page 1 of 26
Ul I RINITY I ERD
15. Unless otherwise noted, referto the following references for bonded bass, ply or up sheet applications.
- •.. •. , -.., ,- •, TMULTR1-BU1LTRWICOVOM '.'.. . ._. •_ :.. __ ._._
Reference
layer
Material
Application
BP -AA
Base Ply
FBCAPproved ASTM NMI, Type 11
HAat 20-0Olbs/square
PN
FBCApproved ASTM D2178, Type M or Vl
(Base and Plysheets, Asphalt -Applied)
09SPA
Ply
TSuik5BSGranular
HA at 20i loo/square
(505, Asphalt-Applied)Up
STA
Up Ply
TnBuiltSM(lianular
Tomh-ApPlid
(SBS, TomJrApplied)
(S
SBSSA
Base Ply
TnBultS SBSBase
(SM SeH-Adhering)
(cep Ply
TnButt SA SW Cap
SeH-Adhering
APP-TA
eax PNar PIY
ThBUik APPSnceth
TorttAPplied
(APP,Torch-Applid)
Cap Ply
TrlBuik APP Smooth, TnBult APP Granular
APP-SA
Cap Ply
TISu1t SAAPPUp
Self -Adhering
(APP, Self-Adhdng)
16. Vapor banieroptens for use over stmmral canaete deck followed by adhered insulation carry the following Maximum Design Pressure (MDP)Ilenhatiom. The lesser of the MDP listings Eelcua s. those in Table 3A
applies:
V..BuwfROPneursSTaucturnat vacrF9FOSApiOgsolrauungxe[aT�w[30. .... - .. ..-. ,. ... .,� -- ..•__ -. . .
--
Option
Primer
Vapor Banner
Insulation Adhesive
MOP(psf)
Type
Attavl
VB-1.
ASTM Dal
TriBuilt SA SM Base
Self -Adhering
bbt Stlk or CR-20, 12-inch o.c.
V9-2.
ASTM N1
Td9ullt ASBSUp
Self -Adhering
Insta-Stik 12-inch ox.
-75.0
VB.3.
ASTM DGl
TrIBUIIt SA5BSUp
Self -Adhering
Millennium One Step Foamable Adhesive,U-inch o.a
-n75
VB-d.
ASTM D61
Td9ulk SA SBS Up
Self -Adhering
CR-20,12-incho.c.
-VD.0
V&S.
ASTM Dull
Td9uik 5A SBS Base
Self -Adhering
Millennium One Step Foamable Adhesive, Millennium PG.1 Pump Grade
Adhesive, Olylsora 500 or M-20, 12-inch o.
2900
17. Dens Deck shall be field -primed with PG100 priartoseHadheriog membrane applintloe. Refertohbkshereinforotherpdmingrequimments.
18. 'MDP'=Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind bads. Refer to FBC 3609 for determination of design wind loads.
Warier Research and Design, LLC. d/b/a TrinitVI ERO Evaluation Report Ad2970.10.U-R2 for FLIW27-AZ
Urtdicareof Authariaatlon A9503 6a'FDRION IN171 MC NON-N EVALUATION Revision2:09/25/2DI7
Prepared by: Robert Niemben, PE-59166 TRI-SNIT Modified Bitumen Roof Systems; (800) 51&1485 Appendix 1, Page 3 of 26
V RINITY I ERD
I
' TABLEIA-2: WOOD DECKS-NEWCONSLRUCTION, REROOF(Tees OFF)OR RECOVER `•
SYSTEMTYPEA4: MECHANICALLYATTACHEDANCHORSH_EEF, BONDED INSULATION, BONDED ROOFCOVER_
System
Deck
Ancler5heet
Baselmarlation
Top Insulation
Roof Cover(Note15)
MDP
No.
(Note 1)
Type
Fasteners
Attach
Type
Attach
Type
Attach
Base Ply
Ply
Cap Ply
(Pat)
124nchc.c.in4-
Min. 0.25-inch Dens Deck
Min.
Poryglass
OMGmPl Flat
Inrhlapandl2-
(Optional)FBC
Dens Deck Prime, SECUROIX
lamp
inch DNwood
Elartabaseor
Bottom Plates
inch o.c in two,
ASTIMCI,
Bcard,
Gin.
(Optional(
SBS-AA,505-
W5
at max. 24-
Polyglbe
(square)with
equall"Paced,
AnM'C3289,
HA
0.7 mcb Fes
MIn.O.]Sinch FeswBoard
HA
BP -AA
BP -AA
TA, APP-TA
-M'0
Inchspans
Elartobase
RoofgdppII
staggered center
rrips ll palycso-
(homogeneotcrormin.05-
Poly
^ante
Inch Structodek High Denier
rows
Fiberboard Roof Insulation
Potyglass
12-mchc.ain4-
(Optional)FBC
(Optional)
Min. 19/32-
Elastobxse or
OMG Flat
Inch lap and 12-
Approved.
Min. 0.25-Inch Dens Deck
One or
SBi-SA,App-
W-fi
inch plywood
Polyglass
Bottom Plates
inch o.c in two,
ASTM Cl]89,
HA
Dens Deck Prime,SECUROIX
HA
SBS-SA
mare SM.
SA, SBSTA
-E0.0
atmax.24-
Elartobase
square with
equxllyeDaced,
typellixemso-
Gypsum -Fiber Roof Board
SA or APP-
or APP2A
in[h spans
Poly
RoeFgrlp#12
stam ggeredceer
ows
cyanurete
TA
TABLEIB: WOODDECKS�NEWCONSMUCNON, REROOF(TDw-0FF)OR RECOVER.'-
,_ SYSTEMTYPEB: MECHANIMLYATTACHEOBASEINSULATION,BONDEDTOPINSULATION;BONOEDROOFCOVER'
Sysem
Base insulation Layer
Tap Insulation layer
Roof Cover (Note 15)
MOP
No.
Deck (Note 1)
Type
Fasteners
Attach
Type
Alta[h
Base PIY
Ply
UpPly
(Psf)
Min. 19/32in[h
Min. 18mch
Dekfzst Hexwith
Min. O.]5-Inch FescoBoaN
IOPGOnil if
(Opvonal'rfusing
W4
plywood at max 24-inch
ENRGY 3, H-Shield
DekPartgl2 orTruFast
1per
(homogeneous)or min.05-inch
HA
using AA Ply)
pA Basel One or
SBS-AA, SBS-TA,
�'D
spans
or Porytherso
MP-3 with T.FasIDP
133ftz
Sfw[todek High Density Fiberboard
Bp -AA
are BP-AAor
APP-TA
Rooflosulation
APP-TA
Exterior Research and Design, I.I.C. d/b/a TdnitylERD Evaluation Report A42970.10.12-R2 for FL16027-R2
Cartifiwte of Atoln rizatwn R9503 6'" EDINON 1201]) FBC NON-HYHZ EVALUATION Revblan 2: 09/25/2017
Pmp mdbY RobertNieminen,PE-59166 TRI-BUILT Modified Bitumen Roof SWems;(800) 516-IMS Appendix 1, Page 5 of 26
V I RININ I ERD
TABLE1E2t WOODDECKS-NEWCANSTRUCT(ON,REROOF(TiaaAFF)mt REMoii.'-
` _ SYSTEMTYPEL'NON-INSULATED MECHANICALLYATTACHED BASESHEEG BONDED ROOFCOVER'
System
Base Sheet
Roof U.(Note 0)
MOP
No.
Oerk (Note 1)
Base
Fasteners
ANaN
Base Ply
Cap Ply
(PA
Polyglass Elastobace, Polyelass VamooseMin.19/32-Inch
OMGFIat Bottom Plates )with
obi in 4-inch lap and laeres
(Opm ar
W-1
p4-inch at max.
Poly, Palvglass G2 Base, CartainTeed
.with
Roofgrip 014, Oekfart Hexwhh Oekfast p14
o.c. in two, e4uallyspared, saggered
In two,.
more BP -AA or
BP-Mor
AP
-52.5
24-inch spans
Plly tone,Glass MB lMPerma-
orTruFast MP-3 with TroFast HD
centerrowz
APP-TA
-TA
TA, APP TA
TA,
U,T,Fiko Brier,
Ply 28, Tamko Glass Base or WFGLAS R]5
Min. 19/32tinch
PolyglassElartobamorPplyglass
OekFart Hex with Dekfart 416 or TruFart MP-
12-Inch o.c. in 4-Inch lap and 12-Inch
Oneormore5B5-
SBS-SA,APP-
W-2
patmax.
Elastobase Poly with Poly top sudxre
3with TruFast HD
in two, equally
o.c. tyspamd, staggered
SA
SA
g38S-TA or
SA.
-52.5•
24-Inch4inch spans
renter rows
Min. 19/32imh
Painless Elactoinme or Polyelass
OMG Flat Bottom Plates(s4uare) with
12-insh o.c. in" rich lap and 12-Inch
(Optional) One or
SBSAA,SBS-
W-3
plywood at max.
Elazmbase Poly
Roofgrip p12
o.c. in two, e4uallyzpaced, saggered
more BP -AA or
TA APP-TA
-150.0
24-Inch spans
ranter rows
ApP-TA
Min. 19/32-inch
polyglass Elartobaze or PalygUss
DMG Flat Ba[mm Plates (square) with
12-Inch o.c. in flinch lap and l2-Inch
Oneor more SBS
SBY50.APP-
W-4
plywood at max.
o.c. in two, e,uaW spaced, staggered
50.38S-TA ar
-60.D'
24-Inchsmnz
Vestobase Poly with poN top surfam
Roofgrippl2
cimte' ows
SA
APP-TA
' TABLE SF: WOOD DECKS-NEWCONSrRUCTION OR REROOF(TMR-0) 5' -
--Y '. ••, =-5Y5TEMTPEF:NON-INSUIdTEDr BONDED ROOFCOVER
System
Roof Cover (Note 15)
MOP
No.
Deh
Primer
IPafl
loiiRTreatment
Base Ply
Ply
Cap Ply
W-5
Min. 15/32-Inch plywood
(Optional) ASXM Dal
None
SBS-SA
(Opuonal)S8 SAar
SBSSA, APP-SA, SBS-TA
4rO'D
I
at max. 24-Inch spans
APP-TA
or APP-TA
Min. 15/32-inch plywood
Plywood joints an covered with 44nch Md. ado of ThBUIlt SA
(Opdonal)SBS-SAor
SBS-SA,APP-9A,SBSTA
WE
atmax.l4-inchspans
(Optional)ASTM D41
SM Base, rolled into Place to cream continuous bond.
TnBuitt SA SW Base
APP-TA
or APP-TA
-9].5
Exterior Research and Design, LLO d/b/a TdnitylERD Evaluation ReportA429]0.10.12-R2 for FLL6027-R2
Certifimm of Authorimtbn g9503 6'"EDITION(20121MCNON-H EVAWATION Revision 2: 09/25/2017
Preparedby: Robert Nleminen,PE-59166 TRI-BUILT Modified Bltumen Roof Systems;(800)5162485 Appendix 1, Page 8 of 26
Certificate of Authorization 2
C R E-E K
17520 Edinburgh
urghgh Dr
Dr
Tampa, FL 33647
H-TECHNICAL SERVICES, LLC (813) 480-3421
EVALUATION REPORT FLORIDA BUILDING CODE, EP EDITION
Manufacturer: TAMKO BUILDING PRODUCTS
220 West 4" Street
Joplin, MO64801
(417) 624-6644
Manufacturing Plants: Joplin, MO
Phillipsburg, KS
Frederick, MD
Dallas, TX
Tuscaloosa, AL
Quality Assurance: UL LLC (QUA9625)
SCOPE
Issued September25, 2017
SCANVEQ
BY
St. Lucie COUflty
Category: Roofing
Subcategory: Asphalt Shingles
Code Sections: 1504.1.1. 1507.2.5, 1507.2.7.1, 1523.6.5.1
Properties: Physical properties, Wind Resistance, Wind Driven Rain
REFERENCES
Enti
Report No.
Standard
Year
PRI Construction Materials Technologies (TST5878)
TAP-043-02-01
TAS 000
1995
PRI Construction Materials Technologies (TST5878)
TAP-051-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-054-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-114-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-117-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-130-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-131-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-165-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-280-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-303-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-307-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-314-02-01 Rev 2
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-315-02-01
ASTM D 6381
2008(2013)el
PRI Construction Materials Technologies (TST5878)
TAP-317-02-01
TAS 100
1995
UL LLC (TST9628)
02NK9507
ASTM D 3161
2016
UL LLC (TST9628)
04NK24366
ASTM D 3462
2010A
UL LLC (TST9628)
05NK28006
ASTM D 6381
2008(2013)el
UL 2390
ASTM D 7158
2011
UL LLC (TST9628)
06NK03898
ASTM D 3161
2016
ASTM D 3462
2010A
UL LLC (TST9628)
08CA59132
ASTM D 3161
2016
UL LLC (TST9628)
09NK07896
ASTM D 3161
2016
ASTM D 3462
2010A
UL LLC (TST9628)
1 OCA50498
ASTM D 3462
2010A
UL LLC (TST9628)
10CA64882
ASTM D 3161
2016
UL LLC (TST9628)
11 NK14014
ASTM D 3161
2016
ASTM D 3462
2010A
UL LLC (TST9628)
12CA24551
ASTM D 3161
2016
UL LLC (TST9628)
4786110543
ASTM D 6381
2008(2013)el
UL LLC (TST9628)
4787043752
ASTM D 3161
2016
UL LLC (TST9628)
4787148748
ASTM D 7158
2011
ASTM D 3161
2016
ASTM D 3462
2010A
CREEK Technical Services LLC (ANE11669)
TBP15001.3
Calculations
2017
TBP15001.4
FL18355-R4
Page 1 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK TAMKO BUILDING PRODUCTS
- Asphalt Shingles
TECHNICAL SERVICES, LLC
PRODUCT DESCRIPTION
Elite Glass -Seal@
12-1/4" x 36", ASTM D 3161, Class F and ASTM D 7158, Class H self-sealing, 34ab
(Frederick, Joplin &
asphalt shingle with fiberglass mat coated on both sides with asphalt and surfaced with
Tuscaloosa)
ceramic granules complying with ASTM D 3462.
Glass -Seal
12-1/4" x 36", ASTM D 3161, Class F and ASTM D 7158, Class H self-sealing, 3-tab
(Frederick &
asphalt shingle with fiberglass mat coated on both sides with asphalt and surfaced with
Tuscaloosa)
ceramic granules complying with ASTM D 3462.
Glass -Seal
12-1/4" x 36", ASTM D 7158, Class H self-sealing, 34ab asphalt shingle with fiberglass
(Joplin)
mat coated on both sides with asphalt and surfaced with ceramic granules complying
with ASTM D 3462. Shingles shall be used in the non-HVHZ only.
Heritage@
13-1/4" x 39-3/8", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
(Dallas, Frederick,
reinforced, laminated architectural asphalt shingle surfaced with mineral granules
Joplin, Phillipsburg &
complying with ASTM D 3462.
Tuscaloosa)
Heritage@ Premium
13-114" x 39-3/8", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
(Dallas, Frederick,
reinforced, laminated architectural asphalt shingle surfaced with mineral granules
Phillipsburg &
complying with ASTM D 3462.
Tuscaloosa)
Heritage@ Premium
12" x 36", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass reinforced,
(Frederick)
laminated architectural asphalt shingle surfaced with mineral granules complying with
ASTM D 3462.
Heritage® Vintage@
17-1/2" x 40% ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass reinforced,
(Phillipsburg)
laminated architectural asphalt shingle surfaced with mineral granules complying with
ASTM D 3462.
Heritage@ Woodgate
13-114" x 39-3/8", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
(Dallas & Frederick)
reinforced, laminated architectural asphalt shingle surfaced with mineral granules
complying with ASTM D 3462.
Heritage@ Woodgate
12" x 36-3/8", ASTM D 3161, Class F fiberglass reinforced, laminated architectural
(Frederick)
asphalt shingle surfaced with mineral granules complying with ASTM D 3462. Shingles
shall be used in the non-HVHZ only.
Hip and Ridge Shingles
12-1/4" x 12", ASTM D 3161, Class F fiberglass reinforced, hip and ridge asphalt
(Frederick & Joplin)
shingle surfaced with mineral granules complying with ASTM D 3462.
Vintage@ Hip and Ridge
12" x 12% ASTM D 3161, Class F fiberglass reinforced, hip and ridge asphalt shingle
(Phillipsburg)
surfaced with mineral granules complying with ASTM D 3462.
TBP15001.4 FL18355-R4 Page 2 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
_j CREEK TECHNICAL SERVTAMKO BUILDING PRODUCTS
LSERVICES, LLC _ _ _ Asphalt Shingles
-
INSTALLATION
Elite GlassSeal®
Basic Wind Speed (Vur):
Max. 194 mph
(Frederick, Joplin &
Basic Wind Speed (Vase):
Max. 150 mph
Tuscaloosa)
Deck (HVHZ):
In accordance with FBC requirements;
&
Solidly sheathed min. 19/32 in. plywood or wood plank for
Glass -Seal
new construction; Min. 15132 - in. plywood existing
(Frederick, Joplin (Non-
construction.
HVHZ) & Tuscaloosa)
Deck (Non-HVHZ):
In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7/16 in. OSB existing construction.
Undedayment:
In accordance with FBC requirements.
Min. slope:
2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12.
Installation (HVHZ):
Installed with 5-1/8 inch exposure in accordance with RAS
115 and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installation (Non-HVHZ):
Installed with 5-1/8-inch exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either "4 Nail
Pattern" or "6 Nail Pattern' detailed below.
Iii
Figure 1. Elite Glass -Seal & Glass -Seal
4 Nail Pattern (Non-HVHZ only)
MW
Butt Edge
Figure 2. Elite Glass -Seal & Glass -Seal
6 Nail Pattern
TBP15001.4 FL18355-R4 Page 3 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK TAMKO BUILDING PRODUCTS
_ _ - Asphalt Shingles
-- _ TECHNICAL SERVICES, LLC
Heritage®
Basic Wind Speed (Vdt):
Max. 194 mph
(Dallas, Frederick, Joplin,
Basic Wind Speed (Vow):
Max. 150 mph
Phillipsburg & Tuscaloosa)
Deck (HVHZ):
In accordance with FBC requirements;
&
Solidly sheathed min. 19/32 in. plywood or wood plank for
Heritage@ Premium
new construction; Min. 15/32 in. plywood existing
(Dallas, Frederick
construction.
Phillipsburg & Tuscaloosa)
Deck (Non-HVHZ):
In accordance with FBC. requirements;
& -
Solidly sheathed min. 15/32 in. plywood or wood plank for
Heritage@ Woodgate
new construction; Min. 7/16 in. OSB existing construction.
(Dallas & Frederick)
Underlayment:
In accordance with FBC requirements.
Min. slope:
2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12.
Installation (HVHZ):
Installed with 5-5/8 in. exposure in accordance with RAS
115 and manufacturers published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installation (Non-HVHZ):
Installed with 5-5/8 in. exposure in accordance with FBC
requirements and manufacturers published installation
instructions. Shingles shall be attached using either "4 Nail
Pattern" or "6 Nail Pattern" detailed below.
6-1
FASTENERS NAILZONE
�COMMON
s BOND
EXPOSURE 5-6/9'
1 " h-- 12-1 /211-+- 12-3/811 -+- 12-1 /21`
Figure 3. Heritage®, Heritage® Premium, and Heritage@ Woodgate (Dallas)
4 Nail Pattern (non-HVHZ only)
FASTENERS NAIL ZONE
COMMON
■ BOND
EXPOSURE 5-518"
1" �-7-1/2'4�-7•
Figure 4. Heritage@ & Heritage@ Premium
6 Nail Pattern
TBP15001.4 FL18355-R4 Page 4 of 11
This evaluation report is provided for Slate of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
_ C_R_ EEK
TECHNICAL SERVICES, LLC
1! �7-1/2+7-1/2+7-M 1/2+7-1/22� I —1"
Figure 5. Heritage® Woodgate
6 Nail Pattern
PAINT
7-719'
6-1181,
TAMKO BUILDING PRODUCTS
— Asphalt Shingles
BOND
9 Common Bond
Figure 6. Heritage®, Heritage® Premium, & Heritage® Woodgate
Alternate 6 Nail Pattern
ACCEPTABLE
FASTENER LOCATION
DO NOT FASTEN
ALONG' EDGE OF
COMMON BOND
ZONE
Figure 7. Heritage® (Tuscaloosa)
Expanded Nail Zone
Nail patterns from Figures 3, 4, and 6 may be placed in the nail zone as described above
.4
FL18355-R4
5 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
C_R_EEK ___
— -- — — TECHNICAL SERVICES, LLC
Heritage® Premium Basic Wind Speed (Vur):
(Frederick) Basic Wind Speed (V" )
Deck (HVHZ):
Deck (Non-HVHZ):
Underlayment:
Min, slope:
Installation (HVHZ):
Installation (Non-HVHZ)
TAMKO BUILDING PRODUCTS
- Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7/16 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12. .
Installed with 5 in. exposure in accordance with RAS 115
and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installed with 5 in, exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either "4 Nail
Pattern" or "6 Nail Pattern" detailed below.
NAIL ZONE!
COMMON BOND
511
1'r—►I �— 11"— -- 12" �-1"
® Figure 8. Heritage' Premium (Frederick)
4 Nail Pattern (non-HVHZ only)
1"�I I 9"—+-3" 9y2" I4,1"
Figure 9. Heritage® Premium (Frederick)
6 Nail Pattern
6ko
TBP15001.4 FL18355-R4 Page 6 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
TAMKO BUILDING PRODUCTSG LV
—Asphalt Shingles --
TECHNICAL SERVICES, LLC
Heritage® Woodgate
Basic Wind Speed (V,n): Max. 194 mph
(Frederick)
Basic Wind Speed (Va,d): Max. 150 mph
Deck (Non-HVHZ): In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7116 in. OSB existing construction.
Underlayment: In accordance with FBC requirements.
Min. slope: 2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12.
Installation (Non-HVHZ): Installed with 5 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either "4 Nail
Pattern" or "6 Nail Pattern" detailed below.
NAIL ZONE!
OMMON BOND
FASTENERS WT
EXPOSURE 5"
i
11" —+-12-3/8IF 11" Ir1"
Figure 10. Heritage@ Woodgate (Frederick)
4 Nail Pattern (non-HVHZ only)
NAIL ZON E1
FASTENERS COMMON BOND
♦
1
5 1/2
EI<POSURE P
1"�
� 9-1/2"-�-3'�9.i'/8"�3'+�t-9-1/2u-►I �l"
Figure 11. Heritage@ Woodgate (Frederick)
6 Nail Pattern
TBP15001.4 _
FL18355-R4 Page 7 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
___MCREEK
TECHNICAL SERVICES, LLC
Heritage® Vintage®
(Phillipsburg)
TBP15001.4
Basic Wind Speed (Vul): Max. 194 mph
Basic Wind Speed (V,,d): Max. 150 mph
TAMKO BUILDING PRODUCTS
- - - - - Asphalt Shingles
Deck (HVHZ):
In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15132 in. plywood existing
construction.
Deck (Non-HVHZ):
In accordance with FBC requirements; - -
Solidly sheathed min. 15132 in. plywood or wood plank for
new construction; Min. 7/16 in. OSB existing construction.
Underlayment:
In accordance with FBC requirements.
Min. slope:
2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12.
Installation (HVHZ):
Installed with 5 in. exposure in accordance with RAS 115
and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installation (Non-HVHZ):
Installed with 5 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either "5 Nail
Pattern' or "6 Nail Pattern" detailed below.
�IP3/6'� �-1PL6•-�
Figure 12. Heritage@ Vintage@
5 Nail Pattern (non-HVHZ only)
Figure 13. Heritage@ Vintage®
6 Nail Pattern
FL18355-R4
:wsu�
nnrcn
8of11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
_ _ _ _CREEK
TECHNICAL SERVICES, LLC
TAMKO BUILDING PRODUCTS
Asphalt Shingles
Hip & Ridge Basic Wind Speed (Vut):
Max. 194 mph
(Frederick & Joplin) Basic Wind Speed (Vae ):
Max. 150 mph
Deck (HVHZ):
In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15132 in. plywood existing
construction.
Deck (Non-HVHZ):
In accordance with FBC requirements;
-
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7/16 in. OSB existing construction.
Underlayment:
In accordance with FBC requirements.
Min. slope:
2:12 and in accordance with FBC requirements.
Installation:
Installed with 5-1/8 inch exposure in accordance with the
FBC and manufacturers published installation instructions.
The direction of the exposed end shall be away from the
prevailing wind.
Direction of prevailing wind
exposure
Figure 1
Fastener
Figure 2
Figure 14. Hip & Ridge (Frederick & Joplin)
exposure
TBP15001.4 FL18355-R4 Page 9 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
Vintage® Hip & Ridge Basic Wind Speed (Vur):
(Phillipsburg) Basic Wind Speed (Vad):
Deck (HVHZ):
Deck (Non-HVHZ):
Underlayment:
Min. slope:
Installation:
TAMKO BUILDING PRODUCTS
-- - - - - - -Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7116 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements.
Installed with 5 inch exposure in accordance with the FBC
and manufacturer's published installation instructions. The
direction of the exposed end shall be away from the
prevailing wind.
Direction of prevailing wind
exposure
Figure 1
1"
Fastener
y„
Kposure
1/2"
Figure 2 r"' Figure 3
Figure 15. Vintage® Hip & Ridge (Phillipsburg)
TBP15001.4 FL18355-R4 Page 10 of 11
This evaluation report is provided for Stale of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
®,CREEK--
EE tij - - _ TAMKO BUILDING PRODUCTS
I'F I� -- Asphalt Bhingles
TECHNICAL SERVICES, LLC
LIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) The roof deck and the roof deck attachment shall be designed by others to meet the minimum design loads
established for components and cladding and in accordance with FBC requirements.
3) The mean roof height shall be restricted to a maximum 33 ft in the HVHZ.
4) Classification to ASTM D 7158 applies to exposure B & C with a building mean roof height of 60-ft or less.
5) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
6) Shingles shall be installed starting at the eave in horizontal layers such that the laps shed water from the
deck.
7) Installation of the evaluated products shall comply with this report, the FBC, and the manufacturer's
published application instructions. Where discrepancies exist between these sources, the more restrictive
and code compliant detail shall prevail.
8) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code, 6� Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer.
No 74021
5)'._ STATE OFOR N
G%
SS �O N A11 t0
CERTIFICATION OF INDEPENDENCE
2017.09.25
11:31:41
04'00'
Zachary R. Priest, P.E.
Florida Registration No. 74021
Organization No. ANE11669
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
TBP15001.4
END OF REPORT
FL18355-R4
11 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.