GENERAL NOTES
1. DESIGN CRITERIA:
APPLICABLE CODES, REGULATIONS & STANDARDS: _
1. THE-2017-FLORIDA BUILDING -CODE, 6TH EDITION -SPECIFICALLY
CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM &
CHAPTER 23 WOOD.
2. ASCE 7-10. & SEI7
3. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD.
4. AC1318 CONCRETE REFRENCE MANUAL.
5. PCI PRECAST & PRESTRESSED CONCRETE.
6. AA ASM 35 & AA ADM 1
WIND LOADS:
1. BUILDING OCCUPANCY CATEGORY, PARAGRAPH 1604.5 & TABLE
1604.5: RISK CATEGORY 1.
2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS
REGION & BASIC WIND SPEED, PARAGRAPH 1609.3.1 & TABLE
1609.3.1 EQUIVALENT BASIC WIND SPEED: 150
MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3: C
3. SCREENED ROOF ENCLOSURE FBC 2017 CH. 20 TABLE 2002.4
CONCRETE & FOUNDATION DESIGN:
1. WHERE CONCRETE SPECIFICATIONS ARE REQUIRED, WHETHER
IN THE SCREEN ENCLOSURE SCOPE OF NOT, BY ONE OR MORE
REGULATORY AGENCY, THE FOLLOWING SPECIFICATIONS ARE
APPLICABLE:
A. CONCRETE SHALL CONFORM TO ASTM C94 FOR THE
FOLLOWING COMPONENTS:
I. PORTLAND CEMENT TYPE 1 - ASTM C 150
IL AGGREGATES - LARGE AGGREGATE 3/4" MAX. - ASTM C 33
III. AIR ENTRAINING +/- 1% - ASTM C 260
IV. WATER REDUCING AGENT - ASTM C 494
V. CLEAN POTABLE WATER
VI. OTHER ADMIXTURES NOT PERMITTED
B. METAL ACCESSORIES SHALL CONFORM TO:
I. REINFORCING BARS -ASTM A615, GRADE 60
II. WELDED WIRE FABRIC - ASTM A185
C. CONCRETE SLUMP AT DISCHARGE CHUTE NOT LESS THAN 3"
OR MORE THAN 5". WATER ADDED AFTER BATCHING IS NOT
PERMITTED.
D. PREPARE & PLACE CONCRETE PER AMERICAN CONCRETE
INSTITUTE MANUAL OF STANDARD PRACTICE, PART 1, 2, & 3
INCLUDING HOT WHEATHER RECOMMENDATIONS.
E. MOIST CURE OR POLYETHYLENE CURING PERMITTED.
F. PRIOR TO PLACING CONCRETE, TREAT THE ENTIRE
SUBSURFACE ARE FOR TERMITES IN COMPLIANCE WITH THE
FBC.
G. CONCRETE SHALL BE PLACED OVER A POLYETHYLENE VAPOR
BARRIER.
2. FOOTING SIZE: EXISTING CONCRETE SLAB. NO ADDITIONAL
FOOTING OR FOUNDATION SYSTEM IS REQUIRED BY THE
PROPOSED CONSTRUCTION IF A MINIMUM 4" CONCRETE
SLAB (3000 PSI) IS PROVIDED IN SOUND CONDITION, FREE
FROM STRUCTURAL CRACKING, SPALLING & OTHER
DETERIORATION. EXISTING FOUNDATION/FOOTING UNDER
CONCRETE SLAB MINIMUM 8"x8" W/ (1) #5 BAR TO BE
VERIFIED BY CONTRACTOR. SEE TYPICAL FOOTING DETAILS
FOR NEW FOOTING DESIGN MINIMUM REQUIREMENTS.
3. WHEN APPLICABLE FOR ATTACHING NEW FOOTER TO EXISTING,
DRILL & EPDXY NEW STEEL INTO EX. FOUNDATION WITH 1" MIN.
HOLE, EMBED 4" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE
(OR EQUAL) TYP. ALL LOCATIONS.
4. WHEN INSTALLING 4" CONCRETE SLAB -ADD ADJACENT TO
EXISTING-DOWELL INTO EXISTING CONCRETE 48" O/C W18" #5
REBARS- DRILL 3/4" HOLE 4" EMBEDMENT- EPDXY W/
NON -SHRINKING "SIMPSON EPDXY TIE" (OR EQUAL).
5. MINIMUM CONCRETE STRENGTH 3000 PSI UNLESS OTHER WISE
NOTED.
ALUMINUM SPECIFICATIONS:
1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS
- OTHERWISE SPECIFIED.
2. ALL SELF MATING BEAM SECTIONS ARE TO BE STITCHED WITH
#12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER.
3. ROOF BRACING SHALL BE A MINIMUM 2"X2"X.050".
4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS
(KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024
INCHES.
5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN
WIND SPEEDS EXCEED 75 MPH PER FBC.
6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS
APPROVED BY FLORIDA ENGINEERING LLC.
FASTNER SPECIFICATIONS:
1. FASTNERS ARE REQUIRED TO BE SAE GRADE 2 OR BETTER
ZINC PLATED. (CONCRETE ANCHORS ARE TO BE TAPCONS
OR BETTER, INSTALLED TO MFG.)
2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS,
AND FASTENERS TO MANUFACTURING SPECIFICATIONS.
3. WHERE WOOD DECK IS PRESENT USE 1/4"X3-1/2" GALV. LAG
SCREWS IN LIEU OF MASONRY ANCHORS. UNLESS OTHERWISE
SPECIFIED.
4. V%2" NON STRUCTURAL MEMBERS ATTACHED TO HOST
A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED
1 /4"X2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS
B. FOR WOOD APPLICATION USE #14X2-3/4" WOOD SCREW AT
24" O.C. AND 6" FROM ENDS.
C. FOR ALUMINUM APPLICATION USE #10X1-1i2" SMS OR TEK
SCREW AT 24" O.C. AND 6" FROM ENDS
D. WHERE VX2" INSTALLED THROUGHOUT AN "OPEN VIEW"
SPACING SHALL BE REDUCED TO 18" O.C. AND 6" FROM ENDS
MASONRY SPECIFICATIONS:
1. CONCRETEMASONRY UNITS (CMU) SHALL BE STANDARD
HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED
ON TYPE M OR S MORTAR.
2. ALL MORTAR SHALL BE TYPE M OR S.
3. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE
MAXIMUM COARSE AGGREGATE SIZE OF 3/8".
4. PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING
REINFORCEMENT WHEN GROUT POUR EXCEEDS 5'-0" IN
HEIGHT.
MISCELLANEOUS:
ST. LUCIE COUP
REVIEWED FOR
REVIEWED BY
PLANS AND PERMIT Neu!
SITE OR NO INSPEAC I
THESE PLANS AND ALL
ARESUDJECTTO ANYI
REQUIRED BY FIELD IN!
MAYBE NECESSARY IN
ALL PROPOSED WORK
`0 ANY CORRECTIONS
:?e0.3d FIELD INSPECTORS THAT
?c NECESSARY IN ORDER TO
PLY WITH ALL APPLICABLE CODES.
2. FOR -FAST ENERSWHICH;4iIEKli7l`t/ISIBLEAFTER INSTALLATION,
THE CONTRACTOR SHALL VERIFY AND INSURE INSTALLATION
HAS BEEN.ACCOMPLISHED IN ACCORDANCE WITH
MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE WITH
THE ATTACHED DETAILS.
3. FOR "PICTURE WINDOW" MODIFICATION TO EXISTING SCREEN
ENCLOSURES, ALL OTHER "EXISTING SCREEN ENCLOSURE"
FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED
IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSURE
EXISTING SCREEN ENCLOSURE IS STRUCTUALLY SOUND.
1. SCREENED ENCLOSURES CONTAINING SWIMMING POOLS SHALL
COMPLY WITH THE APPLICABLE REQUIREMENTS OF FBC
R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS.
2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A
MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME.
IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPERATE 4TH
WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO
ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME.
3. DOOR LOCATION MAY BE RELOCATED BY CONTRACTOR IN
THE FIELD.
4. WHERE PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR
SHALL EPDXY TO DECK OR GROUT TO DECK W/3000 PSI
GROUT WITH BONDING AGENT.
5. INTEGRITY OF EXISTING/ HOST STRUCTURE SHALL NOT BE
COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED.
STRUCTURE.
6. ALL 2X4 & GREATER ARE TO BE SMB UNLESS OTHERWISE INDICATED.
RESPONSIBILITIES:
1. ALL SITE WORK SHALL BE PERFORMED BY A LISCENED
CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING
CODES, LOCAL ORDANANCES, AND THE ENGINEER SHALL
BE NOTIFIED OF ANY DISCREPANCIES.
LEGEND: (ALL MAY NOT APPLY)
SCR = SCREEN
KP = KICK PLATE
PW = PICTURE WINDOW
X = HORIZ. SLIDING WINDOW
0 = HORIZ. STATIONARY WINDOW
DH = DOUBLE HUNG WINDOW
SH= SINGLE HUNG WINDOW
SIP = SOLID INSULATED PANEL
CT = CABLE TIE
SG = SUPER GUTTER
CS = CLEAR SPAN
KB = KNEE BRACE
ALUMINUM MEMBERS DIMENSIONS
HOLLOW SECTIONS
2 x 2: 2"x2"x0.044"
2 x 3: 2"x3"x0.044"
2 x 4: 2"x4"x0.044"
2 x 5: 2"x5"4.050"
OPEN BACK SECTIONS
1 x 2: 1 "x2"x0.044"
1 x 3: 1 "x3"x0.044"
SNAP SECTIONS
2 x 2 SNAP: 2"x2"x0.050"
2 x 3 SNAP: 2"x3"x0.050"
2 x 4 SNAP: 2"x4"0.045"
SELF MATING (SMB)
2 x 4 SMB: 2"x4"x0.644"x0.100"
2 x 5 SMB: 2"x5"x0.050"x0.100"
2 x 6 SMB: 2"x6"x0.050"x0.120"
2 x 7 SMB: 2"x7"x0.057"x0.120"
2 x 8 SMB: 2"x8"x0.072"x0.124"
2 x 9 SMB: 2"x9"4.082'k0.124
2 x 10 SMB: 2"x10"x0.092"x0.398"
NOTE: AS INDICATED ABOVE ALL
MEMBER PROFILES ARE INDICATED
IN INCHES.
of
w
z
CD
Q
0
LL
LL 4rwi
w
0 : J
a
a
Ln
N
p
00
m
M
co
U
� p U
10 m
LL Lo C
I
0)
�cco C
r.'p1
0't N
2
U
H
CL
St, Lucie[County
0
m
0
0
rn
LL
z
Z
QL
QU
}aw
Q
o wOa
O ZOF
m
F o tY
06
w 0mLL
DESIGN DATE:
01114/2019
REVISION I:
DATE
PAGE:
REVISION 2:
DATE
SCALE:
NTS
I— WALL HEIGHT PER PI -A p
I I §g—
P
m I G I
F I
m
1
I111-011�{
4X4X.125
i
i
i
i
i
i
N
N
O
0
J
co
F�
n
-
W
\
\
4X4X.125 \ \`
J & B ALUMINUM'
DOWNEY
6705 OCALA AVE
FORT PIERCE, FL
121-011-{
1X2
2X2 �I
x l0
O N N
_ 4�
A
N
0
00 1 v
�4 8 2n
2X2
2X5SM B
V'
F�
O
0011V
1 2X5SM B
2X2
x
� � N
NX
I 2X2
1X2
82
1,0-,ZT
0
V)
N
A
0
N
�O
C
n
G)
C
m
UNDER TRUSS OR
CONVENTIONAL ROOF
GZIZvmO�z D � m
Z
en
CA p Z 3 p` D m
m D>'�z mm D m
D ZrrZ-��D-DiO0 o y
m m K m ti O D K S m
D p
0�G�Xy mmnin O Z D m
> Z, 0��o
K A 0 p m y n o o Z
O C ti � z �
p D m C Cn O D m O-G
m[��>mc:mm mmm
D p Z �n m< O m 0 3
� D p m m K Z G
Z j>m C y y-> m
m 3 Z
z 1m 0 mZ 2DI N D m -
G1
m O y p "' I D Z
p n p K D m m m m
m' w o'
D e n< x m O n A x
� Z 0 x p m m< O
m m
n`L
0 M m, N n O =
A Z m N m GZ
S O m D p A y N
m -1 D
m G m C
x Z m l
O
O2: Z m
O m
Z
UNDER TRUSS OR
CONVENTIONAL ROOF
xI
N rn
X I
V p N
l0 x Ol
1- X Oo
1 un u
-I r 31-011-1.
FLORIDA ENGINEERING LLC
4456 TAMIAMI TRAIL, UNIT B14
PORT CHARLOTTE, FLORIDA 33980
(941)391-5980
www.flengineeringlic.com
PROJECT NO. 1900905
GU/VD '
VQP \0EN ..,LP
0
- * i No. 60102 =
- .. STATE OF i kji c
VAL
I II III
reig E'. Gunderson, P.E. #60102
CA CERT. #30782 DATE: 01/14/2019'
(6 012 TOTAL
EACH END)
WIND BRACING
DIAGONALATRCOF
PURLIN TO POST
ROOF BEA
2X3 W/
ANGLE W/(3) 014
TEKS (6) TOTA ° 2%2X125
2X POST VY/ (2) #14
TEKS
-ROOF BEAM TO POST
1/4' L
AT
2X3 PURL
TEKS "SUPERGUTTER
LIN @ SUPER GUTTER
1X5XVSX8- EACH
BMW/ (3) 1/4'
X3" LAGS
FASCIA
�2X2XI25"X4" ANGLE EACH
SIDEW/(4)#14TEKS
OVER 36' SPAN USE (3)
3/8'X3"LAGS
BEAM @ SUPER GUTTER
#12 TEKS
CH CLIP
N
T 2X2X.05' RECEIVER
CHANNEL W/ (2)
TYPICAL RAIL #12TEKS
2X3X05' ROOF BEAM
CHAIR RAIL TO POST PURLIN TO ROOF BEAM
4X_ O.B. SCREEN CHANNEL
W/ lw DIA TAPCONS
@24. O.C.
2X2X3 CUP ANGLE
(4)#14 EACH SIDE
8 (1) 3V)(2' EMBED
TAPCON EA SIDE
L2X2X2X1/4 ANGLE CLIP
W/ NI #14 TEKS EACH
IK4-CONCRETE SLAB
/O X CONT.
II X
THICKENED SLAB EDGE
(2) 2X2X.125" ANGLE
AT ALL BEAM CONN
(2) #14 TEKS TYP.
(12) TOTAL PER I
BEAM GUTTER I1
UTTER
ice --FASCIA
MIN.
L-7r
PURLIN OR
ROOFBEAM
BEAM.& PURLIN @ GUTTER
SCREEN CHANNEL
TYPICAL
/4" DIA BOLT
125"ANGLE
EA. SIDE W/ (2)
SPANDREL-- (2)#14 TEKS
ROOF BEAM
BEAM TO SPANDREL
4X O.B. SCREEN CHANNEL
W/ 1/4' DIA TAPC_ONS
@24" O.C.
K2' EMBED
EA_ SIDE
W/ (4) #14 TEKS EACH
SIDE OF POST
3/8' DIAX3' MIN. EMBED
TAPCON EACH SIDE
I Z
O j
_____ I 2'X72'OR 9'X1fi'
W/ (2) 05 GOUT.
STRIP FOOTING
�IWANGLE BRACKET
W/ (9) 014X3/4-
SMS TO WALL MEME.
'_�/S' S'faNLESS
STEEL CPBLE
\ OUBLE COMPRESSION
SLEEVES
5116' EYE BOLT WELDED
CLOSED W/ DOUBLE NUT
CABLE BRACE ALTERNATE
571
1X2 SCREEN CHANNEL
W/ 1/4" DIA TAPCON
@ 24- O.C. (2- EMBED)
- 4_1 - -
EACH SIDE W/ (2)
#14 TEKS AND (1)
1/472" EMBED
TAPCON TYPICAL /
ADD (1)2X2 ANGLE
EACH SIDE TO SPANS
OVER 30'
ROOF BEAM TO MASONRY
=Z fc/o o_
O
Oi J
=LU
U:v
¢
:Z—
,y'•.� Z
..... ......PROF
,.
///InHI
Iji11N1�
J
0
m
00
r�J
t! ~
rn
co
Z Z
o Q
BEAM
TEKS
18"
18" O.C.
16) #14 TEKS MIN. EACH SIDE
ADD (4) MORE FOR SPANS OVER
33 FEET
GUSSET AT RIDGE & MANSARD
—2X3X05' BRACE
2X3X.05- RAIL
TYR
4:�ff2S)#12TEKSTYP.
HNUMBER
NS OVER 3Y.
#14 TEKS)
TABLE B-1
BEAM
SIZE
COL. TO
BEAM
CwsB
SDECFCCL
BEAMTo
BFAM'
oTYS
FACMDE
2x4
(5)#14
(9)#14
2 x 5
(5) #14
(9) #14
2 x 6
(n #14
(9) tt14
2x7
(10)#14
(10)#14
2x8
(12)#14
(14)#14
2x9
-(14)#14
(14)914-
2z10
(16)#14
(15)#14
y U
LL p U
WJ.00�
W
U_ Ln .L
Z -
LU
LU M C
Z�o��)
UJ Q
J
�i
1
U
F_
Lfi
Of
J a
LL
L-2X3XOS"BRACE
K-BRACE ALTERNATE
2X3X.05" RAIL
z
.09' PLATE
Z
7
°
2)#12TEKSTYP.
O Q
EACH NUMBER
Ib
(SPANS OVER 32'
U
°�
USE#14TEKS)
QQ
K �
K-BRACE ALTERNATE
1n
O
m
O
O
m
O
Z
F_
U
W
7
O
Ix
IL
W.J
>LL
Q W
U
} Q W_
ZOD
>LU~
> O
0 CD LL
DATE: 01/14/2019
N 1: DATE PAGE:
N2: _ DATE13
NTS
I�
(3) U" DIA. MACHINE BOLTS
W/ 3/4' DIA. WASHERS THRU
CARRIER BEAM 6 POST
® CARRIER BEAM
POST
NOTE FOR DOUBLE OR TRIPLE CARRIER
BEAM. OUTSIDE WEBS SHALL OVERLAP
44 POST OR NOTCH POST AS ABOVE
FOR 6X6 POST. ALL CASES. CONNECT
USING MACHINE BOLTS DECRIBED ABOVE.
2'xY FASTENED TO CARRIER
BEAM w/(Z) RI0xl-1/2'SMS INTO
SCREW BOSSES EACH END
CARRIER BEAM 1
I-xZ'MEMBER
FOR SCREENING
VARIES
(DYx—SHE
HOR120NTAL BEAM
REER
(SEE PAGE 2 FORFOR SCREENI
ON ITS SIDE
FOR SIZE)
RILxI SMS 12- O.C.
(IF REQUIRED)
STALERED ROWS
TRIZONTFAIR SINGLE
RECEIVING
RECEIVING CHANNEL
HORIZONTAL BEAM
OR ANGLE EACH SIDE
FOR DOUBLE
HORIZONTAL
(6) #I04.75' SMS
BEAM OR 4-AL'
EACH SIDE
(12) RIOAA75' SMS
2 ROWS OF (6) FOR
RECEIVING CHANNEL
OR (6) EACH ANGLE
CARRIER BEAM TO POST DETAIL
CONNECTION SCALE: N.T.S.
(D 3/e' DIA. EXPANSION BOLTS
SEE NOTE It THIS PAGE
FOR BOLT PLACEMENT
YfROM EDGEOF SUB Af ,
II TOP VIEW
(2)I/4'DIA. MACHINE
DOLTS W/ WASHERS
SEE N' EXPANSION BOLTS
SEE /
NOTE
.I THIS PAGE
FOR BOLT PLACEMEM
2' FROM EDGE
OF SUE .
3'x3- POST
(SEE PAGE-2
FOR SIZE)
3-A3'xO.123 ANGLE
3000 PSI CONIC. •• n
SLAB/FTG.
6x6-I0x10 WWM
OR FIBERMESH
FRONT VIEW
YxY POST CONNECTION DETAIL
SCALE: N.T.S.
#IOxI-I/2' SMS 0 24'
O.C. MAX CONNECTING
TO MA2- CARRIER BEAM
#IOXIU?' SMS 0 24-
O.C. MAX CONNECTING
TO I.Q. POST
I
TV
2'x2'x.062
RECEIVING CHANNEL
ROOFBEAM
(SLOPED OR FLAT)
NOTE USE SIMILAR DETAIL
FOR NOTCHED UPRIGHT
CONNECTION TO CARRIER
DEAN
1 # EACH (5) P. EACH
SMS
( SIDE)
(2) ROWS OF (5)
012x3/4' SMS
NOTE: FOR DOUBLE OR TRIPLE CARRIER
BEAM, OUTSIDE WEBS SHALL OVERLAP
4X4 POST OR NOTCH POST AS ABOVE
FOR 6x6 MST. ALL CASES. CONNECT
USING MACHINE BOLTS DECRIBED ABOVE.
ROOF BEAM TO CARRIER BEAM
CONNECTION DETAIL SCALE: N.T.S.
(2) 1/2- CIA. EXPANSION BOLTS
SEE NOTE R2 THIS PAGE
FOR BOLT PLACEMENT
WI/4' DIA. MACHINE
BOLTS W/ WASHERS
(2) I/Y DIA. EXPANSION
BOLTS SEE NOTE #2
THIS PAGE FOR BOLT
PLACEMENT
3000 PSI CONC.
SLAB/FTG.
6x6-IOXIO WWM
OR FIBERMESH
2-x_ SHE
/(SEE PAGE-2
FOR SIZE)
3-3/4'FROM EDGE
OF SLAB (TYP.)
TOP VIEW
4' A' POST SIZE
VARIES SEE PG 2
STITCH W/0
#I2x3/4' SMS
0 12'O.C.
2'x_ SHE
(SEE PAGE-2
FOR SIZE)
z PxL'x0.125 ANGLE
FRONT VIEW
4"W' POST w/ 2x SMB CONNECTION
DETAIL SCALE: N.T.S.
NOTES:
I. 3x3 POST TO HAVE 3/8- RED HEAD - TRUBOLT WEDGE ANCHORS (STAINLESS STEEL, PROVIDE MINIMUM 2- FROM EDGE OF SLAB AND PROVIDE MINIMUM
2- SPACING TO ANY OTHER CONNECTOR. SEE MFG. NOTES FOR INSTALLATION REQUIREMENTS. THREADED ROD REQUIRES 3' MINIMUM EDGE DISTANCE.
2. 4X4 POST TO HAVE 1/2' RED HEAD - TRUBOLT WEDGE ANCHORS (STAINLESS STEEL. PROVIDE MINIMUM 3-3/4' FROM EDGE OF SLAB AND PROVIDEBMINIMUM
}514' SPACING TO ANY OTHER CONNECTOR. SEE MFG. NOTES FOR INSTALLATION REQUIREMENTS.
3. WHERE PAVERS ARE PRESENT ANCHOR LENGTH SHALL BE INCREASED BY THICKNESS OF PAVER NOT TO EXCEED 2-1/2' FOR PAVER THICKNESS MORE THAN
2-I/2- SPECIFICATIONS SHALL BE REQUIRED. PAVERS SMALL BE BONDED TO UNDERLYING CONCRETE FOUNDATION. _
L. WHERE RETURN WINDOW BEAM MEETS MASONRY WALL USE I/8' U-CHANNEL W/ (3) 2-1/4• TAPCONS INTO WALL AND #I4 x 3/4' INTO BEAM E/S OUANITY= BEAM SIZE
(3)1/4'DM. MACHINE BOLTS
w/ 3/4' DIA. WASHERS THRU
CARRIER BEAM 6 POST POST
TOP VIEW
IJ
CARRIER BEAM 1 O
POST
(3) IW DIP. MACHINE BOLTS
w/ 31W DIA. WASHERS THRU
CARRIER BEAM D POST
(3) IW DIA. MACHINE
BOLTS W 3/W DIA,
WASHERS THRU CARRIER
BEAM B POST
CARRIER BEAM
(3) 1/4' DIA. MACHINE
BOLTS n/ 3/L' DIA,
WASHERS THRU CARRIER
BEAM G POST
FRONT VIEW
CORNER CARRIER BEAM CONNECTION
DETAIL SCALE: N.T.S.
(4) 3/8'x4' TAPCON THRU
BOTTOM LEG OF ANGLE
INTO CN-
3-3/4' FROM EDI
OF SUS (TV.)
(2) I/Y DIA. EXPANSION BOLTS
SEE NOTE #2 THIS PAGE
FOR BOLT RACEME"-
3-3/4' FROM EDGF
OF SLAB (TYP.)
NN\N \ {.
..........
�_
- N
o
LL Q-
O O,J
d
Lu �:Q=.
G
Z
U)
j
"'11llllllll lRO\\�
U'qo
J 00
m
0
�
f�J��11
V ~ M
z z ❑_ O
ULI
U
Q' p U
o
w 0 Do ol
W lJi
W a)c a)
L•T
V
z�o��
Q 2 <
0
m ••
Lo
o
a
CD
CD
0)
}3/4' FROM EDGE
OF SLAB (TTP.)
TOP VIEW
TOP VIEW
(3)1/4'DIA. MACHINE
BOLTS n/ WASHERS
V 4- POST
(3) IM DIA. MACHINE
(SEE PAGE-2
BOLTS n/WASHERS
FOR SIZE)
(Z)DIA. EXPANSION
(SEPOST
1/e'x2'x1'x33/L,
BOLTSTS BEE NOTE R2
(SEEPAGE-2
(LENGTH) ANGLE
THIS PAGE FOR BOLT
FOR SIZE)
(4) 5/0'x4• TAPCON
(INTERNAL)
PLACEMENT
2'x4'x0.125 ANGLE
THRU BOTTOM LEG
OF ANGLE INTO CONIC.
3000 PSI CONC.
3000 PSI CONC.
SLAB/FTG.
SLAB/FTG.
6x6-IOXIO WWM •
6x6-IOgO WWM
OR FIBERMESH
OR FIBERMESH
FRONT VIEW
FRONT VIEW
4"x4° POST CONNECTION DETAIL
4"x4" POST CONNECTION
DETAIL
(INTERNAL BASE)
SCALE: N.T.S.
SCALE: N.T.S.
LL
z
Z
<L
U
ULF }QW
DO
OfZ0F
�o�
06
H¢-
w 0(0LL
DESIGN DATE: 01/14/2019
REVISION 1:
DATE
PAGE
REVISION 2:
DATE
4
SCALE:
NTS