HomeMy WebLinkAboutSCREEN ENCLOSUREa GENERAL NOTES 1. DESIGN CRITERIA: APPLICABLE CODES, REGULATIONS & STANDARDS: _ 1. THE-2017-FLORIDA BUILDING -CODE, 6TH EDITION -SPECIFICALLY CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CHAPTER 23 WOOD. 2. ASCE 7-10. & SEI7 3. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD. 4. AC1318 CONCRETE REFRENCE MANUAL. 5. PCI PRECAST & PRESTRESSED CONCRETE. 6. AA ASM 35 & AA ADM 1 WIND LOADS: 1. BUILDING OCCUPANCY CATEGORY, PARAGRAPH 1604.5 & TABLE 1604.5: RISK CATEGORY 1. 2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS REGION & BASIC WIND SPEED, PARAGRAPH 1609.3.1 & TABLE 1609.3.1 EQUIVALENT BASIC WIND SPEED: 150 MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3: C 3. SCREENED ROOF ENCLOSURE FBC 2017 CH. 20 TABLE 2002.4 CONCRETE & FOUNDATION DESIGN: 1. WHERE CONCRETE SPECIFICATIONS ARE REQUIRED, WHETHER IN THE SCREEN ENCLOSURE SCOPE OF NOT, BY ONE OR MORE REGULATORY AGENCY, THE FOLLOWING SPECIFICATIONS ARE APPLICABLE: A. CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING COMPONENTS: I. PORTLAND CEMENT TYPE 1 - ASTM C 150 IL AGGREGATES - LARGE AGGREGATE 3/4" MAX. - ASTM C 33 III. AIR ENTRAINING +/- 1% - ASTM C 260 IV. WATER REDUCING AGENT - ASTM C 494 V. CLEAN POTABLE WATER VI. OTHER ADMIXTURES NOT PERMITTED B. METAL ACCESSORIES SHALL CONFORM TO: I. REINFORCING BARS -ASTM A615, GRADE 60 II. WELDED WIRE FABRIC - ASTM A185 C. CONCRETE SLUMP AT DISCHARGE CHUTE NOT LESS THAN 3" OR MORE THAN 5". WATER ADDED AFTER BATCHING IS NOT PERMITTED. D. PREPARE & PLACE CONCRETE PER AMERICAN CONCRETE INSTITUTE MANUAL OF STANDARD PRACTICE, PART 1, 2, & 3 INCLUDING HOT WHEATHER RECOMMENDATIONS. E. MOIST CURE OR POLYETHYLENE CURING PERMITTED. F. PRIOR TO PLACING CONCRETE, TREAT THE ENTIRE SUBSURFACE ARE FOR TERMITES IN COMPLIANCE WITH THE FBC. G. CONCRETE SHALL BE PLACED OVER A POLYETHYLENE VAPOR BARRIER. 2. FOOTING SIZE: EXISTING CONCRETE SLAB. NO ADDITIONAL FOOTING OR FOUNDATION SYSTEM IS REQUIRED BY THE PROPOSED CONSTRUCTION IF A MINIMUM 4" CONCRETE SLAB (3000 PSI) IS PROVIDED IN SOUND CONDITION, FREE FROM STRUCTURAL CRACKING, SPALLING & OTHER DETERIORATION. EXISTING FOUNDATION/FOOTING UNDER CONCRETE SLAB MINIMUM 8"x8" W/ (1) #5 BAR TO BE VERIFIED BY CONTRACTOR. SEE TYPICAL FOOTING DETAILS FOR NEW FOOTING DESIGN MINIMUM REQUIREMENTS. 3. WHEN APPLICABLE FOR ATTACHING NEW FOOTER TO EXISTING, DRILL & EPDXY NEW STEEL INTO EX. FOUNDATION WITH 1" MIN. HOLE, EMBED 4" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE (OR EQUAL) TYP. ALL LOCATIONS. 4. WHEN INSTALLING 4" CONCRETE SLAB -ADD ADJACENT TO EXISTING-DOWELL INTO EXISTING CONCRETE 48" O/C W18" #5 REBARS- DRILL 3/4" HOLE 4" EMBEDMENT- EPDXY W/ NON -SHRINKING "SIMPSON EPDXY TIE" (OR EQUAL). 5. MINIMUM CONCRETE STRENGTH 3000 PSI UNLESS OTHER WISE NOTED. ALUMINUM SPECIFICATIONS: 1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS - OTHERWISE SPECIFIED. 2. ALL SELF MATING BEAM SECTIONS ARE TO BE STITCHED WITH #12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER. 3. ROOF BRACING SHALL BE A MINIMUM 2"X2"X.050". 4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS (KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024 INCHES. 5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH PER FBC. 6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS APPROVED BY FLORIDA ENGINEERING LLC. FASTNER SPECIFICATIONS: 1. FASTNERS ARE REQUIRED TO BE SAE GRADE 2 OR BETTER ZINC PLATED. (CONCRETE ANCHORS ARE TO BE TAPCONS OR BETTER, INSTALLED TO MFG.) 2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS, AND FASTENERS TO MANUFACTURING SPECIFICATIONS. 3. WHERE WOOD DECK IS PRESENT USE 1/4"X3-1/2" GALV. LAG SCREWS IN LIEU OF MASONRY ANCHORS. UNLESS OTHERWISE SPECIFIED. 4. V%2" NON STRUCTURAL MEMBERS ATTACHED TO HOST A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED 1 /4"X2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS B. FOR WOOD APPLICATION USE #14X2-3/4" WOOD SCREW AT 24" O.C. AND 6" FROM ENDS. C. FOR ALUMINUM APPLICATION USE #10X1-1i2" SMS OR TEK SCREW AT 24" O.C. AND 6" FROM ENDS D. WHERE VX2" INSTALLED THROUGHOUT AN "OPEN VIEW" SPACING SHALL BE REDUCED TO 18" O.C. AND 6" FROM ENDS MASONRY SPECIFICATIONS: 1. CONCRETEMASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR. 2. ALL MORTAR SHALL BE TYPE M OR S. 3. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE MAXIMUM COARSE AGGREGATE SIZE OF 3/8". 4. PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS 5'-0" IN HEIGHT. MISCELLANEOUS: ST. LUCIE COUP REVIEWED FOR REVIEWED BY PLANS AND PERMIT Neu! SITE OR NO INSPEAC I THESE PLANS AND ALL ARESUDJECTTO ANYI REQUIRED BY FIELD IN! MAYBE NECESSARY IN ALL PROPOSED WORK `0 ANY CORRECTIONS :?e0.3d FIELD INSPECTORS THAT ?c NECESSARY IN ORDER TO PLY WITH ALL APPLICABLE CODES. 2. FOR -FAST ENERSWHICH;4iIEKli7l`t/ISIBLEAFTER INSTALLATION, THE CONTRACTOR SHALL VERIFY AND INSURE INSTALLATION HAS BEEN.ACCOMPLISHED IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE WITH THE ATTACHED DETAILS. 3. FOR "PICTURE WINDOW" MODIFICATION TO EXISTING SCREEN ENCLOSURES, ALL OTHER "EXISTING SCREEN ENCLOSURE" FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSURE EXISTING SCREEN ENCLOSURE IS STRUCTUALLY SOUND. 1. SCREENED ENCLOSURES CONTAINING SWIMMING POOLS SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF FBC R4501.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS. 2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPERATE 4TH WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. 3. DOOR LOCATION MAY BE RELOCATED BY CONTRACTOR IN THE FIELD. 4. WHERE PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR SHALL EPDXY TO DECK OR GROUT TO DECK W/3000 PSI GROUT WITH BONDING AGENT. 5. INTEGRITY OF EXISTING/ HOST STRUCTURE SHALL NOT BE COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED. STRUCTURE. 6. ALL 2X4 & GREATER ARE TO BE SMB UNLESS OTHERWISE INDICATED. RESPONSIBILITIES: 1. ALL SITE WORK SHALL BE PERFORMED BY A LISCENED CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDANANCES, AND THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES. LEGEND: (ALL MAY NOT APPLY) SCR = SCREEN KP = KICK PLATE PW = PICTURE WINDOW X = HORIZ. SLIDING WINDOW 0 = HORIZ. STATIONARY WINDOW DH = DOUBLE HUNG WINDOW SH= SINGLE HUNG WINDOW SIP = SOLID INSULATED PANEL CT = CABLE TIE SG = SUPER GUTTER CS = CLEAR SPAN KB = KNEE BRACE ALUMINUM MEMBERS DIMENSIONS HOLLOW SECTIONS 2 x 2: 2"x2"x0.044" 2 x 3: 2"x3"x0.044" 2 x 4: 2"x4"x0.044" 2 x 5: 2"x5"4.050" OPEN BACK SECTIONS 1 x 2: 1 "x2"x0.044" 1 x 3: 1 "x3"x0.044" SNAP SECTIONS 2 x 2 SNAP: 2"x2"x0.050" 2 x 3 SNAP: 2"x3"x0.050" 2 x 4 SNAP: 2"x4"0.045" SELF MATING (SMB) 2 x 4 SMB: 2"x4"x0.644"x0.100" 2 x 5 SMB: 2"x5"x0.050"x0.100" 2 x 6 SMB: 2"x6"x0.050"x0.120" 2 x 7 SMB: 2"x7"x0.057"x0.120" 2 x 8 SMB: 2"x8"x0.072"x0.124" 2 x 9 SMB: 2"x9"4.082'k0.124 2 x 10 SMB: 2"x10"x0.092"x0.398" NOTE: AS INDICATED ABOVE ALL MEMBER PROFILES ARE INDICATED IN INCHES. of w z CD Q 0 LL LL 4rwi w 0 : J a a Ln N p 00 m M co U � p U 10 m LL Lo C I 0) �cco C r.'p1 0't N 2 U H CL St, Lucie[County 0 m 0 0 rn LL z Z QL QU }aw Q o wOa O ZOF m F o tY 06 w 0mLL DESIGN DATE: 01114/2019 REVISION I: DATE PAGE: REVISION 2: DATE SCALE: NTS I— WALL HEIGHT PER PI -A p I I §g— P m I G I F I m 1 I111-011�{ 4X4X.125 i i i i i i N N O 0 J co F� n - W \ \ 4X4X.125 \ \` J & B ALUMINUM' DOWNEY 6705 OCALA AVE FORT PIERCE, FL 121-011-{ 1X2 2X2 �I x l0 O N N _ 4� A N 0 00 1 v �4 8 2n 2X2 2X5SM B V' F� O 0011V 1 2X5SM B 2X2 x � � N NX I 2X2 1X2 82 1,0-,ZT 0 V) N A 0 N �O C n G) C m UNDER TRUSS OR CONVENTIONAL ROOF GZIZvmO�z D � m Z en CA p Z 3 p` D m m D>'�z mm D m D ZrrZ-��D-DiO0 o y m m K m ti O D K S m D p 0�G�Xy mmnin O Z D m > Z, 0��o K A 0 p m y n o o Z O C ti � z � p D m C Cn O D m O-G m[��>mc:mm mmm D p Z �n m< O m 0 3 � D p m m K Z G Z j>m C y y-> m m 3 Z z 1m 0 mZ 2DI N D m - G1 m O y p "' I D Z p n p K D m m m m m' w o' D e n< x m O n A x � Z 0 x p m m< O m m n`L 0 M m, N n O = A Z m N m GZ S O m D p A y N m -1 D m G m C x Z m l O O2: Z m O m Z UNDER TRUSS OR CONVENTIONAL ROOF xI N rn X I V p N l0 x Ol 1- X Oo 1 un u -I r 31-011-1. FLORIDA ENGINEERING LLC 4456 TAMIAMI TRAIL, UNIT B14 PORT CHARLOTTE, FLORIDA 33980 (941)391-5980 www.flengineeringlic.com PROJECT NO. 1900905 GU/VD ' VQP \0EN ..,LP 0 - * i No. 60102 = - .. STATE OF i kji c VAL I II III reig E'. Gunderson, P.E. #60102 CA CERT. #30782 DATE: 01/14/2019' (6 012 TOTAL EACH END) WIND BRACING DIAGONALATRCOF PURLIN TO POST ROOF BEA 2X3 W/ ANGLE W/(3) 014 TEKS (6) TOTA ° 2%2X125 2X POST VY/ (2) #14 TEKS -ROOF BEAM TO POST 1/4' L AT 2X3 PURL TEKS "SUPERGUTTER LIN @ SUPER GUTTER 1X5XVSX8- EACH BMW/ (3) 1/4' X3" LAGS FASCIA �2X2XI25"X4" ANGLE EACH SIDEW/(4)#14TEKS OVER 36' SPAN USE (3) 3/8'X3"LAGS BEAM @ SUPER GUTTER #12 TEKS CH CLIP N T 2X2X.05' RECEIVER CHANNEL W/ (2) TYPICAL RAIL #12TEKS 2X3X05' ROOF BEAM CHAIR RAIL TO POST PURLIN TO ROOF BEAM 4X_ O.B. SCREEN CHANNEL W/ lw DIA TAPCONS @24. O.C. 2X2X3 CUP ANGLE (4)#14 EACH SIDE 8 (1) 3V)(2' EMBED TAPCON EA SIDE L2X2X2X1/4 ANGLE CLIP W/ NI #14 TEKS EACH IK4-CONCRETE SLAB /O X CONT. II X THICKENED SLAB EDGE (2) 2X2X.125" ANGLE AT ALL BEAM CONN (2) #14 TEKS TYP. (12) TOTAL PER I BEAM GUTTER I1 UTTER ice --FASCIA MIN. L-7r PURLIN OR ROOFBEAM BEAM.& PURLIN @ GUTTER SCREEN CHANNEL TYPICAL /4" DIA BOLT 125"ANGLE EA. SIDE W/ (2) SPANDREL-- (2)#14 TEKS ROOF BEAM BEAM TO SPANDREL 4X O.B. SCREEN CHANNEL W/ 1/4' DIA TAPC_ONS @24" O.C. K2' EMBED EA_ SIDE W/ (4) #14 TEKS EACH SIDE OF POST 3/8' DIAX3' MIN. EMBED TAPCON EACH SIDE I Z O j _____ I 2'X72'OR 9'X1fi' W/ (2) 05 GOUT. STRIP FOOTING �IWANGLE BRACKET W/ (9) 014X3/4- SMS TO WALL MEME. '_�/S' S'faNLESS STEEL CPBLE \ OUBLE COMPRESSION SLEEVES 5116' EYE BOLT WELDED CLOSED W/ DOUBLE NUT CABLE BRACE ALTERNATE 571 1X2 SCREEN CHANNEL W/ 1/4" DIA TAPCON @ 24- O.C. (2- EMBED) - 4_1 - - EACH SIDE W/ (2) #14 TEKS AND (1) 1/472" EMBED TAPCON TYPICAL / ADD (1)2X2 ANGLE EACH SIDE TO SPANS OVER 30' ROOF BEAM TO MASONRY =Z fc/o o_ O Oi J =LU U:v ¢ :Z— ,y'•.� Z ..... ......PROF ,. ///InHI Iji11N1� J 0 m 00 r�J t! ~ rn co Z Z o Q BEAM TEKS 18" 18" O.C. 16) #14 TEKS MIN. EACH SIDE ADD (4) MORE FOR SPANS OVER 33 FEET GUSSET AT RIDGE & MANSARD —2X3X05' BRACE 2X3X.05- RAIL TYR 4:�ff2S)#12TEKSTYP. HNUMBER NS OVER 3Y. #14 TEKS) TABLE B-1 BEAM SIZE COL. TO BEAM CwsB SDECFCCL BEAMTo BFAM' oTYS FACMDE 2x4 (5)#14 (9)#14 2 x 5 (5) #14 (9) #14 2 x 6 (n #14 (9) tt14 2x7 (10)#14 (10)#14 2x8 (12)#14 (14)#14 2x9 -(14)#14 (14)914- 2z10 (16)#14 (15)#14 y U LL p U WJ.00� W U_ Ln .L Z - LU LU M C Z�o��) UJ Q J �i 1 U F_ Lfi Of J a LL L-2X3XOS"BRACE K-BRACE ALTERNATE 2X3X.05" RAIL z .09' PLATE Z 7 ° 2)#12TEKSTYP. O Q EACH NUMBER Ib (SPANS OVER 32' U °� USE#14TEKS) QQ K � K-BRACE ALTERNATE 1n O m O O m O Z F_ U W 7 O Ix IL W.J >LL Q W U } Q W_ ZOD >LU~ > O 0 CD LL DATE: 01/14/2019 N 1: DATE PAGE: N2: _ DATE13 NTS I� (3) U" DIA. MACHINE BOLTS W/ 3/4' DIA. WASHERS THRU CARRIER BEAM 6 POST ® CARRIER BEAM POST NOTE FOR DOUBLE OR TRIPLE CARRIER BEAM. OUTSIDE WEBS SHALL OVERLAP 44 POST OR NOTCH POST AS ABOVE FOR 6X6 POST. ALL CASES. CONNECT USING MACHINE BOLTS DECRIBED ABOVE. 2'xY FASTENED TO CARRIER BEAM w/(Z) RI0xl-1/2'SMS INTO SCREW BOSSES EACH END CARRIER BEAM 1 I-xZ'MEMBER FOR SCREENING VARIES (DYx—SHE HOR120NTAL BEAM REER (SEE PAGE 2 FORFOR SCREENI ON ITS SIDE FOR SIZE) RILxI SMS 12- O.C. (IF REQUIRED) STALERED ROWS TRIZONTFAIR SINGLE RECEIVING RECEIVING CHANNEL HORIZONTAL BEAM OR ANGLE EACH SIDE FOR DOUBLE HORIZONTAL (6) #I04.75' SMS BEAM OR 4-AL' EACH SIDE (12) RIOAA75' SMS 2 ROWS OF (6) FOR RECEIVING CHANNEL OR (6) EACH ANGLE CARRIER BEAM TO POST DETAIL CONNECTION SCALE: N.T.S. (D 3/e' DIA. EXPANSION BOLTS SEE NOTE It THIS PAGE FOR BOLT PLACEMENT YfROM EDGEOF SUB Af , II TOP VIEW (2)I/4'DIA. MACHINE DOLTS W/ WASHERS SEE N' EXPANSION BOLTS SEE / NOTE .I THIS PAGE FOR BOLT PLACEMEM 2' FROM EDGE OF SUE . 3'x3- POST (SEE PAGE-2 FOR SIZE) 3-A3'xO.123 ANGLE 3000 PSI CONIC. •• n SLAB/FTG. 6x6-I0x10 WWM OR FIBERMESH FRONT VIEW YxY POST CONNECTION DETAIL SCALE: N.T.S. #IOxI-I/2' SMS 0 24' O.C. MAX CONNECTING TO MA2- CARRIER BEAM #IOXIU?' SMS 0 24- O.C. MAX CONNECTING TO I.Q. POST I TV 2'x2'x.062 RECEIVING CHANNEL ROOFBEAM (SLOPED OR FLAT) NOTE USE SIMILAR DETAIL FOR NOTCHED UPRIGHT CONNECTION TO CARRIER DEAN 1 # EACH (5) P. EACH SMS ( SIDE) (2) ROWS OF (5) 012x3/4' SMS NOTE: FOR DOUBLE OR TRIPLE CARRIER BEAM, OUTSIDE WEBS SHALL OVERLAP 4X4 POST OR NOTCH POST AS ABOVE FOR 6x6 MST. ALL CASES. CONNECT USING MACHINE BOLTS DECRIBED ABOVE. ROOF BEAM TO CARRIER BEAM CONNECTION DETAIL SCALE: N.T.S. (2) 1/2- CIA. EXPANSION BOLTS SEE NOTE R2 THIS PAGE FOR BOLT PLACEMENT WI/4' DIA. MACHINE BOLTS W/ WASHERS (2) I/Y DIA. EXPANSION BOLTS SEE NOTE #2 THIS PAGE FOR BOLT PLACEMENT 3000 PSI CONC. SLAB/FTG. 6x6-IOXIO WWM OR FIBERMESH 2-x_ SHE /(SEE PAGE-2 FOR SIZE) 3-3/4'FROM EDGE OF SLAB (TYP.) TOP VIEW 4' A' POST SIZE VARIES SEE PG 2 STITCH W/0 #I2x3/4' SMS 0 12'O.C. 2'x_ SHE (SEE PAGE-2 FOR SIZE) z PxL'x0.125 ANGLE FRONT VIEW 4"W' POST w/ 2x SMB CONNECTION DETAIL SCALE: N.T.S. NOTES: I. 3x3 POST TO HAVE 3/8- RED HEAD - TRUBOLT WEDGE ANCHORS (STAINLESS STEEL, PROVIDE MINIMUM 2- FROM EDGE OF SLAB AND PROVIDE MINIMUM 2- SPACING TO ANY OTHER CONNECTOR. SEE MFG. NOTES FOR INSTALLATION REQUIREMENTS. THREADED ROD REQUIRES 3' MINIMUM EDGE DISTANCE. 2. 4X4 POST TO HAVE 1/2' RED HEAD - TRUBOLT WEDGE ANCHORS (STAINLESS STEEL. PROVIDE MINIMUM 3-3/4' FROM EDGE OF SLAB AND PROVIDEBMINIMUM }514' SPACING TO ANY OTHER CONNECTOR. SEE MFG. NOTES FOR INSTALLATION REQUIREMENTS. 3. WHERE PAVERS ARE PRESENT ANCHOR LENGTH SHALL BE INCREASED BY THICKNESS OF PAVER NOT TO EXCEED 2-1/2' FOR PAVER THICKNESS MORE THAN 2-I/2- SPECIFICATIONS SHALL BE REQUIRED. PAVERS SMALL BE BONDED TO UNDERLYING CONCRETE FOUNDATION. _ L. WHERE RETURN WINDOW BEAM MEETS MASONRY WALL USE I/8' U-CHANNEL W/ (3) 2-1/4• TAPCONS INTO WALL AND #I4 x 3/4' INTO BEAM E/S OUANITY= BEAM SIZE (3)1/4'DM. MACHINE BOLTS w/ 3/4' DIA. WASHERS THRU CARRIER BEAM 6 POST POST TOP VIEW IJ CARRIER BEAM 1 O POST (3) IW DIP. MACHINE BOLTS w/ 31W DIA. WASHERS THRU CARRIER BEAM D POST (3) IW DIA. MACHINE BOLTS W 3/W DIA, WASHERS THRU CARRIER BEAM B POST CARRIER BEAM (3) 1/4' DIA. MACHINE BOLTS n/ 3/L' DIA, WASHERS THRU CARRIER BEAM G POST FRONT VIEW CORNER CARRIER BEAM CONNECTION DETAIL SCALE: N.T.S. (4) 3/8'x4' TAPCON THRU BOTTOM LEG OF ANGLE INTO CN- 3-3/4' FROM EDI OF SUS (TV.) (2) I/Y DIA. EXPANSION BOLTS SEE NOTE #2 THIS PAGE FOR BOLT RACEME"- 3-3/4' FROM EDGF OF SLAB (TYP.) NN\N \ {. .......... �_ - N o LL Q- O O,J d Lu �:Q=. G Z U) j "'11llllllll lRO\\� U'qo J 00 m 0 � f�J��11 V ~ M z z ❑_ O ULI U Q' p U o w 0 Do ol W lJi W a)c a) L•T V z�o�� Q 2 < 0 m •• Lo o a CD CD 0) }3/4' FROM EDGE OF SLAB (TTP.) TOP VIEW TOP VIEW (3)1/4'DIA. MACHINE BOLTS n/ WASHERS V 4- POST (3) IM DIA. MACHINE (SEE PAGE-2 BOLTS n/WASHERS FOR SIZE) (Z)DIA. EXPANSION (SEPOST 1/e'x2'x1'x33/L, BOLTSTS BEE NOTE R2 (SEEPAGE-2 (LENGTH) ANGLE THIS PAGE FOR BOLT FOR SIZE) (4) 5/0'x4• TAPCON (INTERNAL) PLACEMENT 2'x4'x0.125 ANGLE THRU BOTTOM LEG OF ANGLE INTO CONIC. 3000 PSI CONC. 3000 PSI CONC. SLAB/FTG. SLAB/FTG. 6x6-IOXIO WWM • 6x6-IOgO WWM OR FIBERMESH OR FIBERMESH FRONT VIEW FRONT VIEW 4"x4° POST CONNECTION DETAIL 4"x4" POST CONNECTION DETAIL (INTERNAL BASE) SCALE: N.T.S. SCALE: N.T.S. LL z Z <L U ULF }QW DO OfZ0F �o� 06 H¢- w 0(0LL DESIGN DATE: 01/14/2019 REVISION 1: DATE PAGE REVISION 2: DATE 4 SCALE: NTS