HomeMy WebLinkAboutPRODUCT REPORTPalm City, FL 34990 Compliant with Florida Building Code 2017 (6d' ed.) SCANNED Compliant with'Florida Product Approval Rule # 61G20-3 BY Compliant: Keystone Certifications St. Lucie Countv Product: 5 V Crimp 26GA Steel. Roof Panel FBC Sec. 2507.4.2 Yield strength: 50 ksi min.; Attached to min.15/32" plywood or Wood Deck w/ min. 0.42 specific gravity with screws. 24" Coverage Rib Height 3/8" Corrosion Resistant Compliant: FBC Sec. 1507.4.3 Fastener 1 (Method 1 Attachment): #9 x 1-1/2" Hex -Washer Head wood screw* to penetrate 3/16" min. thru deck or 5/8" embedment into wood plank. (*or sufficient length to meet requirements) Fastener 2 (Method 2,3, & 4 Attachment): #10 x 1-1/2" Hex -Washer Head wood screw* to penetrate 3/16" min. thru deck or 5/8" embedment into wood plank. (*or sufficient length to meet requirements) Underlayment: To be compliant with FBC Sec. Chart 1507.1.1 Slope: Shall be in compliance with FBC Sec.1507. See Fastener attachment specifications above Install Details: Table A . Allowable Loads - METHOD i __METHOD 2 METHOD 3 _ _ _ METH . DESIGN PRESSURE" -86 PSF -93.5 PSF -101 PSF � __�. SF_ ROW SPACING _ _ - 16"-o.c. 16" D.C._._ 8" D.C. MOM FASTENER SPACING (ALONG Panel, width) 12" o.c. 12" o.c. _ 12" D.C. FASTENER SIZE #9 #10 #10 #10 Reference Data: ARCHITECTURAL TESTING, INC. TST ID#: 1527 UL 580-06 & 1897-041 Test Report Db893.01-450-18 05/02/14 Test Report F3366.01-450-18 22/18/15 TAS 125-03 Test Report D05893.02-450-18 07/22/14 *EQUIVALENCY-UL1897-04 is equivalent toteststandardUL1897-i1&1Fit" *Design pressure margin of safety2:1 Locke Bowden, P.E. does not have, not will acquire a financial in-tp:� �r! a , 9 �T laituring or distributing products under this evaluation. �. Locke Bowden, P.E. is not owned, operated, or controlled by a& coinpadtlpw"0f%4urI or distributing products under this report. ; Ar" ? FL17O22.1 5v"�rimp (26GA Steel), 24" Wide Rooanel -Details Limitations: 1. Underlaymenftc be compliance with current Florida Building Code (FBC)2017 61h ed. 2. Minimum slope to be compliant with Florida Building Code 2017 61h ed., and per with Manufacturer's installation reference..- - 3. Products are compliant for State of Florida product approval per Rule 61G20-3. Compliance Method: 1-D 4. Engineering analysis for "project specific approval by local authorities w/jurisdiction is allowed by other registered engineers. 5. Fire classification is not part of this acceptance. Shear diaphragm values are outside this report. 6. Support framing in compliance w/FBC 2017 fish ed., Chapter 22 for Steel, Chapter 23 for Wood and Chapter 16 for Structural Loading. 7. This report does not imply warranty, installation, recommended product use outside of this report. #9.1-1d6lin. or #10 x 1-VZ Min. per Table A' for Row 5-V Qftrp Roof Panel Spacing and Design Pressures Hex Washer Head Wood Screws Deck Wood orgreater Prylwod, or - Wood Wank 24' 1r T Panel Profile Nominal12" Nominal12" D.C. o.c. Fasten x 1-1/2" Min. or #10 x 1-1/2" Min. per -fable "A" Hex Washer Head Screw Spaced 12" o.c. across the Panel Width Panel Refer to Table "A" for Spacing Along Panel Overlap Length Deck- 15/32" or greater Plywood, or -1Abod plank