Loading...
HomeMy WebLinkAboutEVALUATION REPORTSCANNED BY ENGINEER EVALUATE EVALUATION REPORT I CertainTeed Corporation 20 Moores Road Malvern, PA 19355 1 (610)651-5847 M NEMO I etc. Certificate of Authorization #32455 353 Christian Street, Unit #13 Oxford, CT 06478 (203)262-9245 TEST CONSULT CERTIFY ation Report 11610.09.08-R18 FL11288-R17 Date of Issuance:09/03/2009 Revision 18: 01/24/2019 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submittedJl as-5—en—reviewed r obert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 6tb Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: CertainTeed Roof Underlayments LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the product(s), the Quality Assurance or the production facility location(s). NEMO Ietc. requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMO[etc. Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 10. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DCAANE1983 THESE PLANS AND ALL PROPOSED WORK ARE SUBJECT TO ANY CORRECTIONS REQUIRED BY FIELD INSPECTORS THAT MAY BE NECESSARY IN ORDER TO CO"�IPLY WITH ALL APPLICABLE CODES. The faaimlie seal appearing was authorized by Robert Nleminen, P.E. on 01/24/2018. This does not serve as an electronically signed document. CERnFICATION OF INDEPENDENCE: 1. NEMO ETC, LLC does not have, nor does it intend to acquire or will it acquire, a financial interest In any company manufacturing or distributing products it evaluates. 2. NEMO ETC, LLC is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. S. This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluati eport, or previou v sions thereof, is/wa u)5d for�rmitting or design guidance unless retained specifically for that purpose.` oa �ry -QUYI/' Ste ST, WCIE COUNTY BUILDING SITE OR NO INSPECTIONS) WILL����� L NEMO I etc. ROOFING COMPONENT EVALUATION: 1. SCOPE: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: CertainTeed Roof Underlayments, as produced by CertainTeed Corporation, have demonstrated compliance with the following sections of the 61h Edition (2017) Florida Building Code throug testing in accordance with the fallowing Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: - Section Pro a Standard Year 1504.3.1 Wind Uplift FM 4474 2011 1507.23 / 1507.1.1 Physical Properties ASTM D226 2009 1507.2.3 / 1507.1.1 Physical Properties ASTM D4869 2016 1507.2.3 / 1507.1.1 Physical Properties ASTM D6757 2016 1507.3.3 Physical properties FRSA/TRI April 2012 (04-12) 2012 1507.2A / 1507.1.1,1507.2.9.2 Physical Properties ASTM D1970 2015 1507.10.2 Physical Properties ASTM D4601 2012 1507.31.2 Physical Properties ASTM D6163 2008 1507.31.2 Physical Properties ASTM D6164 2011 1507.11.2 Physical Properties ASTM D6222 2011 TA5110 Accelerated Weathering ASTM D4798 2011 3. REFERENCES: Entittv Examination Reference Date ERD (TST6049) Physical Properties C7290.01.08 01/16/2009 ERD (TST6049) Physical Properties C8440.04.08 04/28/2009 ERD (TST6049) Physical Properties C9560.05.08 05/25/2008 ERD (TST6049) Physical Properties C10080.09.08-111 04/17/2009 ERD (TST6049) Physical Properties C32960.06.09 06/02/2009 ERD (TST6049) Physical Properties 3530.12.05-1-113 10/05/2009 ERD (TST6049) Wind Uplift C8370.08.08-113 10/05/2D09 ERD (TST6049) Physical Properties 3523.03.05-R2 01/12/2010 ERD (TST6049) Physical Properties C30890.03.10-1 03/17/2010 ERD (TST6049) Physical Properties C3500.D4.10 04/07/2010 ERD (TST6049) Physical Properties C31840.05.10 05/10/2010 ERD (T5T6049) Physical Properties C31860.05.10 05/18/2010 ERD (TST6049) Physical Properties C31850.06.10 06/25/2010 ERD (TST6049) Physical Properties C35460.05.11 06/16/2011 ERD (TST6049) Physical Properties C34940.09.11-111 10/04/2011 ERD (TST6049) Accelerated Weathering C40840SC 06/11/2012 ERD (TST6049) Physical Properties C40050.09.12-2 09/28/2012 ERD (TST6049) Wind Uplift C39670.08.12 08/20/2012 ERD (TST6049) Physical Properties C31410.10.10-R1 11/02/2012 ERD (TST6049) Physical Properties C45240.01.14-1 01/15/2014 ERD (TST6049) Physical Properties C32930.01.11-R2 01/20/2014 ERD (TST6049) Physical Properties C45240.01.14-2 01/24/2014 ERD (TST6049) FM 4470 CrR-SC9920.01.16-RI 01/20/2016 ERD (TST6049) Wind Uplift CrR-SC10420.01.16 01/25/2016 ERD (TST6D49) FRSA/TRI April 2012, Tile Slippage CTR-SC11415.11.16 11/28/2016 MTI (TST 2508) Physical Properties DX08C4A 03/22/2OD4 MTI (TST 2508) Physical Properties TX1496A-001 02/27/2006 MTI (TST 2508) Physical Properties TX1486B-002 03/13/2006 MTI (TST 2508) Physical Properties TX14B6F-006 03/13/2006 MTI (TST 2508) Physical Properties TX14136E-005 03/13/2006 PRI (TST5878) Physical Properties CTC-034-02-01 11/24/2008 PRI (TST5878) Physical Properties CrC-075-02-01 02/15/2011 PRI (T5T5878) Physical Properties CTC-067-02-01 08/08/2011 PRI (TST5878) Wind Uplift Crc-112-02-01 12/12/2011 PRI CM5878) Physical Properties CTC-163-02-01(x3) 05/10/2013 PRI CT5T5878) Physical Properties CrC-189-02-01 11/18/2013 NEMO ETC, U.C. Evaluation Report 13610.09.08-R38 CertlPmte clAuthorfmtran AU455 bra EDITION (2017) FEC NON-HVHZ EVALUATION FL11288-1117 CertainTeed Roof Underlayments, (610) 651-5847 Revision 18: 01/24/2018 Page 2 of 10 NEmo l etc. Entity Examination Reference Date PRI (TSr5878) Physiml Properties CTC-327-02-01 06/28/2017 UL. LLG (QUA9625) Quality Control service Confirmation Exp.03/09/2020 4. PRODUCr DESQOPnON: 4.1 _ Self -Adhering Underlayments: 4.1.1 WjnterGuard" HT is a glass scrim reinforced, self -adhering, film -surfaced waterproofing underlayment; meets ASTM D1970. 4.1.2 VlrjrrterGuard" Sand is a glass mat reinforced, self -adhering, sand -surfaced waterproofing underlayment; meets ASTM D1970. 4.1.3 MrinterGuardm Granular is a glass mat reinforced, self -adhering, granule -surfaced waterproofing underlayment; meets ASTM D3970. 4.1.4 Metalayment" is a self -adhering, film -surfaced, waterproofing underlayment; meets ASTM D3970. 4.1.5 Black Diamond Base Sheet is a self -adhering, glass mat reinforced, fine -mineral surfaced, SBS modified roof underlayment; meets ASTM D3970. 4.1.6 Flintlastic SA PlyBase is a self -adhering, glass mat reinforced, film -surfaced, SBS modified roof underlayment for use as a base -layer in multi -ply underlayment systems; meets ASTM D3970. 4.1.7 Flintlastic SA Mid Ply is a self -adhering, polyester reinforced, film -surfaced, SBS modified roof underlayment for use as a base -layer in multi -ply underlayment systems; meets ASTM D6163, Type I, Grade S. 4.1.8 Flintlastic Ultra Glass SA is a self -adhering, glass mat reinforced, fine -mineral surfaced, SBS modified roof underlayment for use as a base -layer in multi -ply underlayment systems; meets ASTM D6163, Type I, Grade S. 4.1.9 Flintlastic SA Cap FR is a self -adhering, glass mat reinforced, granule -mineral surfaced, SBS modified roof underlayment; meets ASTM D6163, Type I, Grade G. 4.1.10 Flintlastic SA Cap is a self -adhering, polyester reinforced, granule -mineral surfaced, SBS modified roof underlayment; meets ASTM D1970, ASTM D6164, Type I, Grade G and FRSA/TRI April 2012. 4.2 Torch Applied Underlayments: 4.2.1 Flintlastic GTA Is a torch -applied, polyester reinforced, granule -surfaced, APP modified roof underlayment; meets ASTM D6222, Type 1, Grade G. 4.3 Asphalt Applied Underlayments: 4.3.1 Flintlastic GMS is an asphalt -applied, polyester reinforced, granule -surfaced, SBS modified roof underlayment; meets ASTM D6164, Type I, Grade G. 4.4 Mechanically Attached Underlayments: 4.4.1 Flindastic SA NallBase is a glass mat reinforced, film -surfaced, SBS modified roof underlayment for use as a mechanically attached base -layer in multi -ply underlayment systems; meets ASTM D4601, Type H. 4.4.2 Roofers' Select Is an asphalt -impregnated, organic felt reinforced with glass fibers roof underlayment; meets ASTM D6757. NEMO ETC, U.C. Evaluation Report 11610.09.08-R18 CeWleate a/Autlwdwdon 83245S eEDITION (2017)F6C NON-HVHZ EVALUATION FL11288-R17 Cerfaln7eed Roof Underlayments, (610) 651.5847 Revision 18: 02/24/2018 Page 3 of 10 NEMO l etc. S. LIMITATIONS: 5.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert N(em(nen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in FBC HVH_Z jurisdictions. 5.3 Fire Classification Is not part of this Laboratory Report; refer to current Approved Roofing Materials Directory or test report from accredited testing agency for fire ratings of this product. 5.4 CertainTeed Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction (AHJ) for approval based on this evaluation combined with supporting data for the prepared roof covering. 5.5 Allowable Roof Covers: 5.5.1 COVERTABLE 1: ROOF OPTIONS Underlayment Asphalt Nail -On Foam -On Mortar- Metal wood Shakes& Slate Shingles Tile Tile Set Tile Shingles Roofers' Select Yes No No No No No No WinterGuard HT Yes No No No Yes Yes Yes WinterGuard Sand or Granular Yes No No No No Yes Yes Black Diamond Base Yes No No No No Yes Yes Flintlastic SA Cap Yes Yes Yes Yes No Yes Yes See I 5.Flintlastic SA Cap FR No No No No No Yes Yes MetaLayment Yes No No No Yes Yes Yes Flintlastic GTA No Yes Yes No Yes Yes SeeYes Flintlastic GMS No Yes Yes Yes No Yes Yes See 55.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combinations. ' Refer to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance. NEMO ETC, LLC. Evaluation Report 11610.09.08-R36 Cerdji<are ofAotho,irodon 932455 6TeEDITION (2017)FBC NON-HVHZ EVALUATION FL11288-R17 Certain'reed Roof Undedayments; (610) 651-SS47 Revision 18: 01/24/2018 Page 4 of 10 '4k� NEMO l etc. 5.6 Allowable Substrates: 5.6.1 Direct -Bond to Deck: WinterGuard HT, WinterGuard Sand, WinterGuard Granular or MetaLayment self -adhered to: ➢ New or existing plywood ➢ FlintPrime or ASTM D41 primed new or existing plywood. Black Diamond Base, Flintlastic SA PlyBase, Flintlastic SA Mid Ply, Flintlastic Ultra Glass SA, Flintlastic SA Cap or Flintlastic SA Cap FR self -adhered to: ➢ New or existing plywood; D FlintPrime, FlintPrime SA or ASTM D41 primed new or existing plywood; ➢ FlintPrime, FlintPrime SA or ASTM D41 primed structural concrete. Flintlastic GMS In hot asphalt to: ➢ FlintPrime or ASTM D41 primed structural concrete. Flintlastic GTA torch -applied to: ➢ FlintPrime orASTM D41 primed structural concrete. 5.6.2 Bond to Mechanically Attached Base Sheet or Adhered Base Ply: ➢ WinterGuard HT, WinterGuard Sand, WinterGuard Granular or MetaLayment self -adhered to: ASTM D226, Type I or II felt. ➢ Black Diamond Base Sheet, Flintlastic SA PlyBase, Flintlastic SA Mid Ply, Flintlastic Ultra Glass SA, Flintlastic SA Cap, Flintlastic SA Cap FR self -adhered to: Flintlastic SA NailBase or ASTM D226, Type I or II felt. ➢ Flintlastic SA Cap or Flintlastic SA Cap FR self -adhered to: Flintlastic SA PlyBase or Flintlastic SA MidPly. D Flintlastic GMS in hot asphalt to: ASTM D226, Type I or II felt, ASTM D4601, Type II base sheet, Black Diamond Base Sheet or Flintlastic Ultra Glass SA. D Flintlastic GTA torch -applied to: ASTM D226, Type I or II felt, ASTM D4601, Type II base sheet, Black Diamond Base Sheet or Flintlastic Ultra Glass SA. 5.6.3 Wind Resistance for Underlayment Systems inFoam-On TiileApplications : FRSA/TRI April 2012 (04-12) does not address wind uplift resistance of all underlayment systems beneath foam -on or mortar -set tile systems, where the underlayment forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not addressed in FRSA/TRI April 2012 (04- 12) and are used in foam -on or mortar -set tile applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-12), Appendix A, Table 1A or FBC 1609 for determination of design wind loads. #1 Maximum Desien Pressure = -240 osf Deck: Structural concrete to meet project requirements to satisfaction of AHJ. Primer: FlintPrime or ASTM D41. Base Sheet: Black Diamond Base Sheet or Flintlastic Ultra Glass SA, self -adhered. Underlayment: Flintlastic GTA, torch -applied or Flintlastic GMS, applied In hot asphalt. 82 Maximum Design Pressure = -555 osf: Deck: Structural concrete to meet project requirements to satisfaction of AHJ. Primer: FlintPrime, FlintPrime SA or ASTM D41. Base: (Optional) Flintlastic SA PlyBase or Flintlastic SA Mid Ply, self -adhered. Underlayment: Flintlastic SACap, self -adhered. NEMO ETC, LLC. Evaluation Report 11610.09.08-Ri6 Cerdlkm of Authurrrodon932455 e EDMON (2017) FBC NON-HVH2 EVALUATION FL1128&R17 CerlalnTeed Roof Underlayments; (620) 651-5847 Revision 18: 01/24/2018 Page 5 of 10 'k.% NEMO I etc. #3 Maximum Design Pressure = -105.0 osf: Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of AHJ. Primer: (Optional) FlintPrime, FlintPrime SA or ASTM D41 Base Ply: (Optional) Flintlastic SA PlyBase or Flintlastic SA Mid Ply, self -adhered. Underlayment: Flintlastic SA Cap, self -adhered. #4 Maximum Design -Pressure -=-127.5 Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of AHJ. Primer: FlintPrime, FlintPrime SA or ASTM D41 Joints: Min. 4-Inch wide strips of Flintlastic SA PlyBase, self -adhered over all plywood joints. Base Ply: (Optional) Flintlastic SA PlyBase or Flintlastic SA Mid Ply, self -adhered. Underlayment: Flintlastic SA Cap, self -adhered. #5 Maximum Design Pressure=-37.5 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ. Base Sheet: ASTM D226, Type II felt or Flintlastic SA NailBase Fasteners: 12 ga., IY.-inch long galvanized ring shank nails through 32 ga., 15/8-Inch diameter tin caps Spacing: 6-inch o.c. at the 4-inch laps and 12-inch o.c. at two (2) equally spaced, staggered rows in the field of the sheet. Base Ply: (Optional) Flintlastic SA PlyBase or Flintlastic SA Mid Ply, self -adhered. Underlayment: Flintlastic SA Cap, self -adhered. #6 Maximum Design Pressure = -45.0 osf•: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ. Base Sheet: Glasbase Base Sheet; Flexiglas Base Sheet; Flintlastic Base 20; All Weather / Empire Base Sheet; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base or Yosemite Venting Base Sheet Fasteners: Simplex MAxX Cap Fasteners Spacing: 9-inch o.c. at the 2-inch wide side laps and Minch o.c. at two (2) equally spaced, staggered center rows. Underlayment: Flintlastic GMS, applied in hot asphalt or Flintlastic GTA, torch -applied. #7 Maximum Design Pressure=-52.5 osf: Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of AHJ. Base Sheet: Glasbase Base Sheet; Flexiglas Base Sheet; Flintlastic Base 20; All Weather / Empire Base Sheet; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base or Yosemite Venting Base Sheet Fasteners: Simplex MAxX Cap Fasteners Spacing: 9-inch o.c. at the 2-Inch wide side laps and 12-inch o.c. at two (2) equally spaced, staggered center rows. Underlayment: Flintlastic GMS, applied in hot asphalt or Flintlastic GTA, torch -applied. #8 Maximum Design Pressure=-52.5 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ. Base Sheet: Flintlastic SA NailBase Fasteners: Min. 1-inch long, 12 ga. Simplex Metal Cap Nails Spacing: 6-inch o.c. atthe min. 2-Inch laps and 6-inch o.c. at four (4) equally spaced, staggered rows in the field of the sheet. Base Ply: (Optional) Flintlastic SA PlyBase or Flintlastic SA Mid Ply, self -adhered. Underlayment: Flintlastic SA Cap, self -adhered. #9 Maximum Design Pressure=-60.0 osf: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of AHJ. Base Sheet: Flintlastic SA NailBase Fasteners: 12 ga., IX -inch long galvanized ring shank nails through 32 ga., 15/8-inch diameter tin caps Spacing: 8-inch o.c. at the min. 2-Inch laps and 8-Inch o.c. at three (3) equally spaced, staggered rows in the field of the sheet. Base Ply: (Optional) Flintlastic SA PlyBase or Flintlastic SA Mid Ply, self -adhered. Underlayment: Flintlastic SA Cap, self -adhered. NEMO ETC, U.C. Evaluation Report 11610.09.08-R18 Cefidko a nfAuVwdmdan 4324SS 6' EDITION (2017) FBC NON-HVHZ EVALUATION FL11288-1117 CertalnTeed Roof Underlayments, 1610) 651.5847 Revision IS: 01/24/2018 Page 6 of 10 '7k_% NEMO I etc. #10 Maximum Design Pressure =-67.5 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of AHI. Base Sheet: Glasbase Base Sheet; Flexiglas Base Sheet; Flintlastic Base 20; All Weather / Empire Base Sheet; Flintlastic Poly SMS Base, Flintlastic Ultra Poly SMS Base or Yosemite Venting Base Sheet Fasteners: Cap nails: 1-inch diameter, 0.032-inch thick metal cap with 0.120-inch shank diameter, annular ring shank nails Spacing: 6-inch o.c. at 4-inch lap and 6-inch o.c. at five (5) equally spaced, staggered center rows In the field of the sheet. Underlayment: Flintlastic GMS, applied in hot asphalt. #11 Maximum Design Pressure =-75.0 osf: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of AHI. Base Sheet: Flintlastic SA NailBase Fasteners: 12 ga., SY.-inch long galvanized ring shank nails through 32 ga., 15/8-inch diameter tin caps Spacing: 6-Inch o.c. at the min. 2-inch laps and 6-inch o.c. at four (4) equally spaced, staggered rows in the field of the sheet. Base Ply: (Optional) Flintlastic SA PlyBase or Flintlastic SA Mid Ply, self -adhered. Underlayment: Flintlastic SA Cap, self -adhered. #12 Maximum Design Pressure = -90.0 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ. Base Sheet: Glasbase Base Sheet; Flexiglas Base Sheet; Flintlastic Base 20; All Weather / Empire Base Sheet; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base or Yosemite Venting Base Sheet Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-Inch o.c. at the 2-inch wide side laps and 6-inch o.c. at two (2) equally spaced, staggered center rows. Underlayment: Flintlastic ISMS, applied in hot asphalt or Flintlastic GTA, torch -applied. #14 Maximum Design Pressure = -105.0 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of AHJ. Base Sheet: Glasbase Base Sheet; Flexiglas Base Sheet; Flintlastic Base 20; All Weather / Empire Base Sheet; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base or Yosemite Venting Base Sheet Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-inch o.c. at the 2-inch wide side laps and 6-inch o.c. at three (3) equally spaced, staggered center rows. Underlayment: Flintlastic ISMS, applied in hot asphalt or Flintlastic GTA, torch -applied. #15 Maximum Design Pressure = -105.0 psf: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of AHJ. Base Sheet: Flintlastic SA NailBase Fasteners: 12 ga., 1Y.-inch long galvanized ring shank nails through 32 ga, 15/B-inch diameter tin caps Spacing: 4-Inch o.c. at the min. 2-inch laps and 4-inch o.c. at four (4) equally spaced, staggered rows In the field of the sheet. Base Ply: (Optional) Flintlastic SA PlyBase or Flintlastic SA Mid Ply, self -adhered. Underlayment: Flintlastic SA Cap, self -adhered. 5.6.3.1 All other direct -deck, adhered Certa(nTeed underlayment systems beneath foam -on or mortar -set tile systems carry a Maximum Design Pressure of -45 psf. 5.6.3.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk' carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. NEMO ETC, I.I.C. Evaluation Report 11610.09.084118 Certyla OfAuthartzatbn 1324S5 a EDITION (2017) FBC NON-HVHZ EVALUATION FL11288-1137 CertainTeed Roof Undedayments; (610) 651-5847 Revision 28: 01/24/2018 Page 7 of 10 NEnnO I etc. 5.7 Exposure Limitations: Roofers' Select shall not be left exposed for longer than 30-days after installation. Refer to installation instructions specific to anticipated exposure in Section 6. Black Diamond Base, WinterGuard HT, WinterGuard Sand, WinterGuard Granular or MetaLayment shall not be left exposed for longerthan180-days after installation. Flintlastic SA Cap, Flintlastic SA Cap FR, Flintlastic GTA or Flintlastic GMS do not have an exposure limitation, unless the prepared roof covering is to be adhesive -set tile atop Flintlastic SA Cap, GTA or GMS, in which case the maximum exposure is 180 days. Flintlastic SA NailBase, Flintlastic SA PlyBase, Flintlastic SA Mid Ply and Flintlastic Ultra Glass SA, for use as a base -layer in a multi -ply underlayment system, shall not be left exposed for longer than 30-days after installation, prior to placement of subsequent underlayment layer. 5.8 Tile Slippage Limitations (per FRSA/TRI April 2012 (04-12)): When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. TABLE 2: TILE SLIPPAGE LIMITATIONS FOR DIREcT-DECK TILE INSTALLATIONS Underlayment Tile Profile Staging Method Maximum Slope FlintlasticGMS All Max. 30-tile stack 4:12 Flintlastic GTA All Max. 30-tile stack 6:12 Flintlastic SA Cap Flat Max. 6-tile stack (4 over 2) 6:12 Lugged Max. 6-tile stack (4 over 2) 5:12 6. INSTALLATION: 6.1 CertalnTeed Roof Undedayments shall be installed in accordance with CertainTeed published installation requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application, and primed the substrate (if applicable). 6.3.1 Flintlastic SA NailBase, Flintlastic SA PlyBase and Flintlastic SA Mid Ply are limited to use as a base or mid - layer in multi -ply underlayment systems beneath Flintlastic SA Cap or Flintlastic SA Cap FR. 6.3.2 Flintlastic Ultra Glass SA is limited to use as a base -layer in multi -ply underlayment systems beneath Flintlastic GTA or Flintlastic GMS. 6.3.3 Install the base -layer underlayment to the substrates detailed in Section 5.6 in accordance with CertainTeed published installation instructions, followed by the final underlayment layer in accordance With the instructions outlined below for the particular top -layer underlayment. 6.3.4 Roof cover limitations are those are those associated with the top -layer underlayment, as set forth in Table 1. NEMO ETC, U.C. Evaluation Report 11610.09.08-RlB CenWmee o7Authoriio8on N32455 61e EDITION (2017) FBC NON-HVHZ EVALUATION FL11288-R17 Certainlreed Roof Underlayments, (610) 651-5B47 Revision 18:01/24/2016 Page 9 of 10 NEMO I etc. 6.4.1 Shall be installed in compliance with current CertainTeed published installation requirements and FBC 1507 for the type of prepared roof covering to be installed. 6.4.2 Non -Tile Applications: Shall be fully self -adhered to the substrates noted in Section 5.6. Side laps shall be minimum-4-inch and end -laps minimum 6-inch wide, pressed firmly with a seam -roller, and offset end -laps minimum 2 feet from course to course. Consult CertainTeed instructions for use of FlintOond SBS Modified Bitumen Adhesive, trowel grade, on the 6-inch end laps and T-seam detailing. Consult Certa)nTeed instructions regarding back -nailing requirements. 6.4.3 Tile Applications Wintlastic SA Cap only): Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein. For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12), Table 1. For adhesive -set tile applications, refer to Section 5.6.3 herein. 6.5.1 Flintlastic GTA shall be installed in compliance with current CertainTeed published installation requirements. For use in tile applications, Flintlastic GTA is for use as an alternate to the Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems (Base Sheet Limited per 5.6.2) 6.5.2 Flintlastic GTA shall be fully torch applied to the substrates noted in Section 5.6. Side (horizontal) laps shall be minimum 3-inch and end (vertical) laps minimum 6-inch wide, and offset end -laps minimum 3 feet from course to course. Side and end -laps shall be fully heat -welded and inspected to ensure minimum 3/8-inch flow of modified compound beyond the lap edge. 6.5.3 Consult Certa)nTeed instructions regarding back -nailing requirements. 6.6.1 Flintlastic GMS shall be installed in compliance with current CertainTeed published installation requirements. For use in tile applications, Flintlastic GMS is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the 'Two Ply System" +from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. 6.6.2 Flintlastic GMS shall be fully asphalt -applied to the substrates noted in Section 5.6. Side (horizontal) laps shall be minimum 3-Inch and end (vertical) laps minimum 6-inch wide, and offset end -laps minimum 3 feet from course to course. Side and end -laps shall be fully adhered in a complete mopping of hot asphalt with asphalt extending approximately 3/8-inch beyond the lap edge. 6.6.3 Consult CertainTeed instructions regarding back -nailing requirements. NEMO ETC, U.C. Evaluation Report 11610.09.08-R18 Ceafkate OfAudwrliadon 932455 e EDITION (2017) FBC NON-HVHZ EVALUATION FL11288-R17 CertainTeed Roof Underlayments, (610) 651-5B47 Revision 18:01/24/2018 Page 9 of 10 -O- Nenno l etc. 6.7.1 Standard -Slope Application (4:12 and greater): Starting at the lower edge of the roof, apply a single layer of Roofers' Select parallel to the eaves, overhanging drip edge by %-inch. Overlap ends (vertical laps) at least 4-inch and sides (horizontal laps) at least 2-inch. Offset end laps from course to course at least 6- feet. Apply flat and unwrinkled, fastening as required to hold in place. 6.7.2 Low Slope Application f2:12 up to 4:12): Starting at the lower edge of the roof, cover the entire deck by applying a double layer of Roofers' Select parallel to the eaves. Begin by applying a 19-inch wide starter strip of Roofers' Select along the eaves, overlapping the drip edge by %-inch. Place a full -width sheet over the starter, with lower edge flush to the starter's lower edge. Apply succeeding 36-inch wide courses up the roof slope, overlapping the previous course by 19-inch in "shingle -fashion". Overlap ends at least 12- inch. Offset end laps from course to course at least 6-feet. Apply flat and unwrinkled, fastening as required to hold in place. 6.7.3 Eaves Flashing for Ice Dam Protection fall slopes): Eaves flashing may be constructed from self -adhering waterproofing underlayment holding Florida Product Approval, or by applying a double layer of Roofers' Select cemented together with asphalt roofing cement (ASTM D 4586, Type II). Eaves flashing should be installed to a level of at least 24-inch inside the interior wall line, or in areas of severe icing, at least up to the highest water level expected to occur from ice dams to the satisfaction of the Authority Having Jurisdiction (AHJ). 6_8 Tile Staging (Flintlastic SA Gap, Flintlastic GTA or Flintlastic GMSI: 6.8.1 Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment. Refer to Table 2 herein, and Certa(nTeed published requirements for tile staging. 6.8.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI April 2012 (04-12) must be used on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or nail -boards, to prevent tile sliding and/or damage to the underlayment during the loading process. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction (AHJ) in order to properly evaluate the installation of this product. S. MANUFACTURING PLANTS: Contact the noted QA agency for information on product locations covered for F.A.C. 61G20-3 CIA requirements. The fallowing plants have qualified products under their respective physical properties specifications. Plant Specification ASTM D1970 Product(s) WinterGuard HT, MetaLayment, Flintlastic SA PlyBase ASTM D4601 Flintlastic SA NailBase ASTM D6163 Flintlastic SA Mid Ply, Flintlastic Ultra Glass SA, Flintlastic SA Cap FR Little Rock, AR ASTM D6164 Flintlastic GMS ASTM D1970, ASTM D6164 & FRSA/TRI April 2012 Flintlastic SA Cap ASTM D6222 Flintlastic GTA Shakopee, MN ASTM D1970 WinterGuard Sand, WinterGuard Granular, Black Diamond Base Sheet, Shreveport, LA I ASTM D6757 I Roofers' Select 9. QUAuTYAssURANCE ENTITY: UL, LLC. — QUA9625; (414) 248-6409; karen.buchmann@ul.com -END OF EVALUATION REPORT — NEMO ETC, U.C. Evaluation Report 11610.09.08-R38 CertlJlmte a/Autaar4a0an 4324SS eEDITION (2017)FBC NON-HVHZ EVALUATION FL31288-R17 CertalnTeed Roof Underlayments; (610) 651-5847 Revision 18: 01/24/2018 Page 10 of 10