HomeMy WebLinkAbout0412-0354 - 707 KITTERMAN RD PAPERWORKsf�o°jeY�FO
CERTIFICATE OF OCCUPANCY
This Certificate is issued pursuant to the requirements of the Florida Building Code certifying that at the
time of issuance this structure was in compliance with,the various ordinances of St. Lucie County
regulating building construction or use. For the followingC� ,
Parcel/Folio Nbr: 3415-501-0041-000/0
Lot # 3
Subdivision: Kitterman Woods
Occupancy: Assembly - food & drink
Building Address: 707 KITTERMAN Rd
Legal Description:
Permit Job CONSTRUCT CHURCH BUILDING
Description
Permit Finaled: 04/26/2011
Contractor REAVES INNIS L
STEWARDSHIP SERVICES
2333 wynnewood st PORT SAINT LUCIE, FL 34953 (386) 679-0486
Kenneth Arnold
Building Official
Tuesday, April 26, 2011
Date Printed
NOTE:
This Certificate of Occupancy is issued to the above named, for building at the above named location only upon the express provision that
the applicant will abide by and comply with all the conditions of the Zoning Ordinances and all Ordinances or Building Codes of Saint
Lucie County pertaining to the erection, construction or remodeling of buildings or structures.
This also certifies that the electrical wiring and/or equipment, and the plumbing work have been inspected and approved. The issuance of
this Certificate grants permission to occupy and use the property described herein only for the use indicated. Any change in use will
require -a new Certificate of Occupancy.
POST IN A CONSPICUOUS PLACE
Fort Pierce, FL 34982
772-462-2172 Fax 772-462-6443 S
c+ C
CERTIFICATE OF TERMITE TREATMENT Sft���aytiFo
CONSTRUCTION SOIL TREATMENT &Co
el
PERMIT #. ' " OB ADDRESS: 1 On kigeiMntj �� L• �� `�°I��.
BUILDER/CONTRACTOR:
PEST CONTROL CONTRACTOR:
PEST CONTROL LICENSE #:
We, the undersigned, hereby certify that we have pretreated the above described construction for
subterranean termites in accordance with the standards of the National Pest Control Association.
Square feet if area treated: S r50 `If- Chemicals used: UIaSPdug
Percentage of solution: U 6
Date of Treatment:
Footing
19'Treatment
Re -Treat
Driveway
15t Treatment
Re -Treat
Other
1't Treatment
Re -Treat
Total gallons used: , 111,9
Time of Treatment:. jj} 3 6
Slab
11t Treatment
Re -Treat
Pools
Treat
Inspection
Note: There must be a completed form for each required treatment or re -treatment and this form must be on the job
s/te to be p/dced up by the Inspector at time of each inspection or the scheduled inspection wl//fall and a re-lnspecdon
fee charged
FBC104.2.6 Cert/f/cete of pmtect/ve it eatment for prevention of_termites A weather resistant jobs/te posting board
shall be pmWded to receive duplicate Treatment Certfficates as each required proteit/ve treatment Is wmpleted,
prov/d/ng a copy for the person the penn/t is issued to and another copy for the building permit fifes The Treatment
Certirrcate shall prov/de the product used, Identity of the applicator, time and data of the treatment, site /ocadon, area
treated, chem/cat used, percent concentration and number of gallons used, to estabilsh a ver/Aable record of
protective treatment. If the soil chemical battler method for termite prevention Is useo,final exterior treatment shall
be completed prior to Anal building approval.
St Lucie County requires for the final inspection for CO, a Permanent Sticker to be placed on
e
International
e
Certified Independent Test & Balance
Air - Hydronic - Sound & Vibration
Building Commissioning - LEED Consulting
CERTIFIED TEST & BALANCE REPORT
DATE: March 25, 2011
_ PROJECT:,
WANNED
NAME:
Grace Emmanuel
gY
ADDRESS:
Port St. Lucie, Florida
EE
��1C1@ COUiIf}/
DESIGN ENGINEER:
- NAME:
Not Available
ADDRESS:
Not Available
\
-ARCHITECT:
I NAME:
Not Available
( ADDRESS:
Not Available
r HVAC CONTRACTOR:
NAME:
Not Available
l . ADDRESS:
Not Available
PROJECT NUMBER: 1615
W*LE
National Enviromental Balancing Bureau Certification
THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL ADJUSTMENTS THAT
HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR
TESTING, ADJUSTING, AND BALANCING OF ENVIRONMENTAL SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITIES,
WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST- ADJUST- BALANCE REPORT PROJECT SUMMARY.
Submitted & Certified By:
?124,xlreu< 9. 7M
Matthew F. Fulghum
NEBB Certified Professional
Certification Number: 3459
Expiration Date: March -3151, 2013
MATTHEW F. FULGHUM
CERTIFICATION
3459
E.xlx 3/31l13
Seal:
TABCO International 3832-10 Baymeadows Rd. Suite 344 Jacksonville, Florida 32217
Office: 904.371.9077 e-mail: Info@tabcollc.com web site: www.tabcolic.com Fax: 904.371.9345
Certified
Pro ect Grace Emmanuel Church
Location PSL, Florida
TABLE OF CONTENTS
TABLE OF CONTENTS
INSTRUMENT CALIBRATION
AHU-1
AIR SIDE EQUIPMENT DATA
DX- COOLING COIL DATA
AIR COOLED DX- CONDENSING UNIT EQUIPMENT DATA
AIR DISTRIBUTION DATA
AHU-2
AIR SIDE EQUIPMENT DATA
DX- COOLING COIL DATA
AIR COOLED DX- CONDENSING UNIT EQUIPMENT DATA
AIR DISTRIBUTION DATA
AHU-3
AIR SIDE EQUIPMENT DATA
DX- COOLING COIL DATA
AIR COOLED DX - CONDENSING UNIT EQUIPMENT DATA
AIR DISTRIBUTION DATA
AHU-4
AIR SIDE EQUIPMENT DATA
DX- COOLING COIL DATA
AIR COOLED DX - CONDENSING UNIT EQUIPMENT DATA
AIR DISTRIBUTION DATA
AHU-5
AIR SIDE EQUIPMENT DATA
DX- COOLING COIL DATA
AIR COOLED DX- CONDENSING UNIT EQUIPMENT DATA
AIR DISTRIBUTION DATA
AHU-6
AIR SIDE EQUIPMENT DATA
DX- COOLING COIL DATA
AIR COOLED DX- CONDENSING UNIT EQUIPMENT DATA
AIR DISTRIBUTION DATA
AHU-7
AIR SIDE EQUIPMENT DATA
DX- COOLING COIL DATA
AIR COOLED DX - CONDENSING UNIT EQUIPMENT DATA
AIR DISTRIBUTION DATA
Measurements By. Fulahum
TABCO International / 20110
Date: March 25, 2011
Page: 1 of 18
Test Dates: March 24. 2011 and March 25 2011
2
12
3
7
9
13
4
7
10
14
4
7
10
15
5
8
10
16
5
8
10
17
6
8
11
18
rjl
l;
Certified
Project Grace Emmanuel Church
Location PSL, Florida
INSTRUMENT LIST
Date: March 25, 2011
Page: 2 of IS
Instrument
Manufacturer
Model
Serial Number
Calibration Data
H dronic Manometer
Alnor
HM-680
70734124
02-10-2011
Micromanometer
Alnor
EBT-721
90717007
02-10-2011
lowhood
Alnor
EBT-721
90717007
02-10-2011
elometer
Alnor
EBT-721
90717007
02-10-2011
haser Laser Tachometer
Monarch
PM-6669
SM3421
09-12-2010
Humidity Measurment
Alnor
AL72-TH1
90717007
07-01-2010
oIYArnmeter
Fluke
116-RMS
474505
-
eloci Matrix
Alnor
VLG84
1406-7
Airfoil
Alnor
SVP18
1406-8
Slag -Tube Manometer
Dwyer
1223-36WM
3575-8
itot Tube 12"
Dwyer
NAP
3575-3
itotTube 18"
Dwyer
NAP
3575-3
itotTube 36"
Dwyer
NAP
3575-4
itot Tube 48"
Dwyer
NAP
3575-3
itot Tube 60"
Dwyer
NAP
3575-4
elProbe
Alnor
SVP18
1406-8
ill
Measurements By.Rdghum
TABCO Intemational / 20110
Test Dates: March 24. 2011 and Mamh 25 2011
hi*
Certified
Project Grace Emmanuel Church
Location I PSL, Florida
AIR SIDE EQUIPMENT DATA
Date: March 25. 2011
Page: 3 of 18
Unit No.
AHU-1
AHU-2
Equipment Location
Mechanical Room
Mechanical Room
Area Served
West Sanctus / Sound Room
East Sanctuary I Sound Room
Equipment Manufacture
Trane
Trane
Model Number
TWE180E300AA
TWE180E300AA
edal Number
104510CGWA
11022NRDWA
Fan Data
Specified
Actual
Specified
Actual
Total CFM - Fan
4800
4545
4800
4590
Total CFM - Outlets
4800
4545
4800
4590
Return Air CFM
3900
3682
3900
3675
ut Side Air CFM
900
863
900
915
otal / Ext. Static Pressure
1.0"
0.79
1.0"
0.82
Inlet Pressure
0.37.
0.33
Discharge Pressure
0.42
0.39
Fan RPM
NA
802
NA
794
Motor Data
Specified
Actual
S edfied
Actual
Motor Manufacture
Marathon
Marathon
Motor Horse Power / RPM
3.0 / -
3.0 / 1725
3.0 / -
3.0 / 1725
Phase /Hz
3/60
3/till _
3160
3/60
Service Factor / Frame No.
1.15 / 56HZ
1.15 / 56HZ
otor Voltage
208-208-208
231-228-230
.208-208-208
228-225-231
otorAm era a
9.0-9.0-9.0
1 7.3-7.2-7.4
9.0-9.0-9.0
6.9-7.0-6.6
Drive Padm e
Motor Sheave & Shaft
1VP44 X 718
1VP44 X 7/8
Fan Shave & Shaft
BK90 X 1-7/16
BK90 X 1-7116
Number / Belt Size
1 BX58
1 BX58
Center to Center
20.5
20.5
Final Filters
8 15X20X2
8 15X20X2
Comments:
- Measurements By. Fulahum
TABCO Intematlonal 120110
Test Oates: March 24. 2011 and March 25 2011
Certified
Project Grace Emmanuel Church
Location PSL, Florida
AIR SIDE EQUIPMENT DATA
Date: March 25, 2011
Page: 4 of 18
Unit No.
AHU-3
AHU4
Equipment Location
Mechanical Room
Mechanical Room
Area Served
Administration Offices
Youth / Nurse / Conference
Equipment Manufacture
Trane
Trane
Model Number
ZTEC3F60B1000AA
ZTEC3F60B1000AA.
Serial Number
8065LCFZV
8065K4D2V
Fan Data
Specified
Actual
Spectilled
Actual
Total CFM - Fan
2000
1758
2000
1593
Total CFM- Outlets
2300 *
1758 *
1600 **
1593 **
Return Air CFM
1770
1516
1770
1370
ut Side Air CFM
230
242
230
223
Total / Ext. Static Pressure
0.64
0.47
1.0
0.45
Inlet Pressure
0.18
0.19
Dischar a Pressure
0.29
0.26
Fan RPM
Direct Drive
Direct Drive
Motor Data
Specified
Actual
Specified
Actual
Motor Manufacture
General Electric
General Electric.
Motor Horse Power / RPM
1.0 / -
1.0 / -
1.0 / -
1.0 / -
Phase / Hz
1160
1 160
1 / 60
1 / 60
Service Factor / Frame No.
-
-
Motor Voltage
230
233
230
233
MotorAm era a
3.0
1 2.5
1 3.0
2.5
Drive Package
Motor Sheave & Shaft
Direct Drive
Direct Drive
Fan Shave & Shaft
Number / Belt Size
Center to Center
Final Filters
1
20 X 25 X 1
1
20 X 25 X 1
Comments: * Hallway diffusers omitted new supply design =1740 CFM. Valanced to obtain summation of supply diffusers.
** Also, air distribution does not match schedule, balanced to obtain summation of supply diffusers.
Measurements By. Fulghum Test Dates: March 24. 2011 and March 25 2011
TABCO International 12011©
Ni*
Certified Date: March 25, 2011
Page: 5 of 18
Project Grace Emmanuel Church
Location PSL, Rodda
AIR SIDE EQUIPMENT DATA
Unit No.
AHU-5
AHU-6
Equipment Location
Mechanical Room
Above Ceiling
ea Served
Front main Buildin / Westside
Stage / Music Room
Equipment Manufacture
American Standard
Trane
Model Number
TWE120A300EL
2TEC3F36B1000AA
anal Number
7366KB4BD
80735821V
Fan Data
Specified
Actual
Specified
Actual
otal CFM -fan
4000
3537
1000
1191
otal CFM - Outlets
3830 *
3537 *
990 *
1191
Return Air CFM
3500
3083
900
1089
ut Side Air CFM
500
454
100
102
Total / Ext. Static Pressure
1.0
0.80
0.80"
0.61
Inlet Pressure
0.29
0.25
ischar a Pressure
0.51
0.36
Fan RPM
NA
1031
NA
Direct Drive
Motor Data
Specified
Actual
S edfied
Actual
Motor Manufacture
General Electric
General Electric
Motor Horse Power / RPM
NA
2.0 / 1725
3/4 / -
% / -
hase/Hz
3/60
3/60
1/60
1/60
Service Factor / Frame No.
1.15 / 145T
-
Motor Voltage
208-208-208
231-227-226
230
227
otorAm era a
6.2-6.2-6.2
4.7-5.1-4.9
2.2
1.9
Drive Package
Motor Sheave & Shaft
4-1/2 X 7/8
Direct Drive
Fan Shave & Shaft
7 X 1
Number / Belt Size
1 A50
Center to Center
17.5"
Final Filters
4
16X25X1
1 20 X 20 X 1
Comments: ' Balanced to obtain design summation of supply air distribution.
Measurements By. Fulghurn
TABCO International / 2011©
Test Dates: March 24. 2011 and March 25. 2011
Ni6
Certified
Project Grace Emmanuel Church
Location PSL, Florida
AIR SIDE EQUIPMENT DATA
Date: March 25* 2011
Page: 6 of 16
Unit No.
AHU-7
NAP
Equipment Location
Above Ceiling
-
rea Served
Stage / Music Room
-
Equipment Manufacture
Trane
-
Model Number
2TEC3F36B1000AA
-
Serial Number
807377AV
-
Fan Data
Specified
Actual
Speeffied
Actual
Total CFM - Fan
1000
1200
Total CFM - Outlets
990 *
1200
Return Air CFM
900
1103
Out Side Air CFM
100
97
Total / Ext.:Static Pressure
0.80"
0.58
Inlet Pressure
0.23
Discharge Pressure
0.35
Fan RPM
NA
Direct Drive
Motor Data
Specified
Actual
Specified
Actual
Motor Manufacture
General Electric
Motor Horse Power / RPM
3/4 / -
% / -
-
-
hase / Hz
1 / 60
1160
Service Factor / Frame No.
-
Motor Voltage
230
225
otorAm era a
2.2
1 1.8
Drive Package
NAP
otor Sheave & Shaft
Direct Drive
:an Shave & Shaft
Number / Belt Size
enter to Center
Final Filters
1
202 X 20 X 1
Comments: * Balanced to obtain design summation of supply air distribution.
Measurements By: Fulghum
TABCO International 12011©
Test Dates: March 24. 2011 and March 25, 2011
m4i�
Certified Date: March 25, 2011
Page: 7 of 18
P,ro ect Grace Emmanuel Church
Location PSL, Florida
DX- COOLING COIL DATA
Unit No.
AHt1,1
Mechanical Room
AHU-2
Mechanical Room
Equipment Location
Area Served
West Sanctus / Sound Room
East Sanctus / Sound Room
Equipment Manufacture
Trane
Trane
Model Number
TWE18OE300AA
TWE180E300AA
Serial Number
104510CGWA
11022NRDWA
Temperature Profile
E.A.T. DB/WB
Specified
78.6 / 65.5
Actual
74.2163.1
Speafied
78.6 / 65.5
Actual
.73.9 / 62.6
L.A.T. DB / WB
:54.8 / 53.6
54.7153.8
54.8 / 53.6
54.1 / 52.8
FM
'4800
4545
4800
4590
.•�lJmt,No.:' .:_�
I AHU-4_x , ,
Equipment Location
Mechanical Room
Mechanical Room
Area Served
Administration Offices
Youth / Nurse / Conference
Equipment Manufacture
Trane
Trane
Model Number
ZTEC3F60B1000AA
ZTEC3F60B1000AA
Seriaf Number
8065LCFZV
8065K4D2V
Tem natureProfile
S edRM
KW.Kcff$M
jW8pMclfiidWjWPWAZQlw
•.
E.A.T. DB / WB
NA
73.7 / 62.1
NA
74.1 162.5
L.A.T. DB / WB
NA
53.8 / 570
NA
54.3 152.7
CFM
2000
1758
2000
1593
Comments
Measurements By. FWahum
TABCO Intemabonal12011©
f
Test Dates: March 24, 2011 and March 25, 2011
Certified Date: March 25, 2011
Page: 8 of 18
WWA Project I Grace Emmanuel Church
Location PSL, Florida
DX- COOLING COIL DATA
VOWWRNOMO
R&WHOWAHWOKAMM"
Equipment Location
Mechanical Room
Above Ceiling
rea Served
Front main Building / Westside
Stage / Music Room
Equipment Manufacture
American Standard
Trane
Model Number
TWE120A300EL
2TEC3F36BI000AA
enalNumber
7366KB4BD
80735821V
Temperature Profile
Specified
Actual
Speafied
Actual
EAT DB/WB
NA
73.7162.5
77.8 / 64.7
74.1 / 63.2
L.A.T. DB / WB
NA
54.1 153.5
54.4 / 54.0
53.5 / 52.4
CFM
4000
3537
1000
1191
NAP
Equipment Location
Above Ceiling
-
Area Served
Stage / Music Room
-
Equipment Manufacture
Trane
-
ModelNumber
2TEC3F36B1000AA
-
Serial Number
807377J1V
-
Tem ratumreWProfile T
gip- S ecifiedl :
}!? Actual
S eafied r
- Acival
E.A.T. DB / WB
77.8 / 64.7
73.7 / 62.1
L.A.T. DB / WB
54.4 / 54.0
53.8 /52.4
CFM
1000
1200
wmments
Measurements By Fed hum Test Dates: Mardi 24 2011 and March 25 2011
TABCO Intemational / 2011©
Certified
Date: March 25, 2011
Page: 9 of 18
AIR COOLED DX - CONDENSING UNIT EQUIPMENT DATA
Unit No.
CU-1
CU-1
ui menttocation
Mechanical Pad NE
Mechanical Pad NE
rea Served
AHU-1
AHU-1
ui ment Manufacture
Trane
Trane
odel Number
TTA 180 E300AA
TTA 180 E300AA
anal Number
11012Y8LTA
11012Y8LTA
Condenser
S cified
Actual
Specified
Ardual
lEntering Air Temp
NA
78.3
NA
78.3
Electflod
Specified
Actual
S cified
I Actual
om ressorAm s
25.0-25.0-25.0
18.3-17.2-17.4
25.0-25.0-25.0
17.6-17.7-17.3
om ressor Volts
230-230-230
238-242-237
230-230-230
240-237-241
ondenser Fan Amps
5.0
4.1
5.0
3.9
ondenser Fan Volts
230
238
230
240
Unit No.
CU-2
CU-2
ui ment Location
Mechanical Pad NE
Mechanical Pad NE
rea Served
AHU-2
AHU-2
ui ment Manufacture
Trane
Trane
odel Number
TTA 180 E300AA
TTA 180 E300AA
erial Number
10393U91TA
10393U91TA
EJectdcal
Specified
Actual
SDeclfied
Actual
om ressorAm s
25.0-25.0-25.0
17.6-17.1-17.2
25.0-25.0-25.0
16.8-17.3-17.1
om ressor Volts
230-230-230
233-234-237
230-230-230
230=231=222
ondenser Fan Amps
5.0
3.9
5.0
3.8
ondenser Fan Volts
230
233
230
234
Measurements By: Fulabum
TABCO Intemational / 2011©
Test Dates: March 24. 2011 and March 25 2011
Ni6
Certified
Project I Grace Emmanuel Church
Location I PSL, Florida
Date: March 25, 2011
Page: 10 of 18
AIR COOLED DX - CONDENSING UNIT EQUIPMENT DATA
Unit No.
CU5
CU4
ui ment Location
Mechanical Pad NE
Mechanical Pad NE
rea Served
AHU-3
AHU-4
ui ment Manufacture
Trane
Trane
ode[ Number
2TTA 0060A3000AA
2TTA 0060A3000AA
e0alNumber
43253J23F
4325U9L3F
Condenser
Specified
Actual
Specified
Actual
Entering Air Tern
NA
78.3
NA
78.3
Electrical
Specified
Actual
S ecified
Actual
om ressorAm s
19.7-19.7-19.7
15.6-16.1-16.2
19.7-19.7-19.7
17.1-16.3-16.2
om ressor Volts
208-208-208
233-231-240
208-208-208
238-236-134
ondenser Fan AnnDs
1.9
1.3
1.9
1.6
ondenser Fan Volts
208
233
208
238
Unit No.
CU5
CU5
ui ment Location
Mechanical Pad NW
Mechanical Pad SW
rea Served
AHU-5
AHU-6
ui ment Manufacture
Trane
Trane
odelNumber
TTA120D300AA
4A7C3036A3000BA
erial Number
10425M49YA
10394WY43T
Condenser
Specified
Actual
Specified
Actual
FntedngAirTemp
NA
78.3
NA
78.3
Electrical
Specified
Actual
Specified
Actual
om ressorAm s
30.0-30.0-30.0
24.6-24.3-24.0
11.5-11.5-11.5
9.6-9.1-9.3
om ressor Volts
230-230-230
241-233-240
208-208-208
233-228-230
ondenser Fan Amps
5.0
4.1
0.7
0.51
ondenser Fan Volts
230
232
208
233
Measurements By. Nahum
TABCO International / 2011©
Test Dates: March 24.2011 and March 25 2011
N40
Certified
Pro ect Grace Emmanuel Church
Location PSL, Florida
Date: March 25, 2011
Page: 11: of 18
AIR COOLED DX - CONDENSING UNIT EQUIPMENT DATA
Unit No.
CU-7
NAP
ui ment Location
Mechanical Pad SW
rea Served
AHU-6
ui ment Manufacture
Trane
odelNumber
4A7C3036A3000BA
e6al Number
11024WYR3F
Condenser
Specified
Actual
Spedfied
Actual
�ntering Ak Temp
NA
78.3
Electrical
Specified
Actual
Specified
Actual
om ressorAm s
11.5-11.5-11.5
10.7-10.4-9.2
om ressor Volts
208-208-208
233-228-237
ondenser Fan Amps
0.7
0.61
ondenser Fan Volts
208
233
Unit No.
NAP
NAP
ui ment Location
rea Served
1"Iedal
ui ment.Manufacture
ode[ Number
Number
Electrical
Spedfied
Actual
Spedfied
Actual
om ressorAm s
om ressor Volts
ondenser Fan Amps
ondenser Fan Volts
Measurements By. Fulahum Test Dates: March 24. 2011 and March 25 2011
TABCO International 12011©
N* - P
Certified
ProjectGrace Emmanuel Church
Location' PSL, Florida
AIR DISTRIBUTION DATA
Date: March 25. 2011
Page: 12 of 18
YSTEM I AHU-1
Comments:' Unable to capture complete diffuser face. Due to lighting. Velocity pressure measurement performed on
diffuser with airfoil. To obtain actual CFM.
Return ducting was increased. Due to restriction caused by fired damper connection. FD installed is internal vs
external connection blocking net area of return duct, a additional 16" return duct and fire damper was added to
sanctuary, installed up stream of existing fire damper. Referenced above in test-1 before and test-2 after. System is
balanced to low end of design. If additional airflow is required a pulley change will be required.
Measurements By. Fulghurn
TABCO International / 2011©
Test Dates: March 24, 2011 and March 25 2011
Ni6
Certified
Proect Grace Emmanuel Church
Location PSL, Florida
AIR DISTRIBUTION DATA
Date: March 25, 2011
Page: 13 of 18
YSTEM I AHU-2
zpq—
(:omments: ' unable to capture complete diffuser face. Due to lighting. Velocity pressure measurement performed on
diffuser with airfoil. To obtain actual CFM.
Return ducting was increased. Due to restriction caused by fired damper connection. FD installed is internal vs
external connection blocking net area of return duct, a additional 16" return duct and fire damper was added to
sanctuary, installed up stream of existing fire damper. Referenced above in test-1 before and test-2 after. System is
balanced to low end of design. If additional airflow is required a pulley change will be required.
Measurements aY: uIF ahem
TABCO International / 2011©
Test Dates: March 24. 2011 and March 25, 2011
Certified
Project Grace Emmanuel Church
Location PSL, Florida
AIR DISTRIBUTION DATA
Date: March 25, 2011
Page: 14 of 18
YSTEM I AHU-3
15:La5i:�JWMWMI
Comments:' Hallway diffusers omitted. Due fire barrier, additional CFM proportionally balanced between surrounding
diffusers.
" Hallway diffusers existing 8" flex ducting, was replaced by HVAC contractor with 10" flex ducting. In order to
obtain design CFM.
Balanced to obtain summation of supply diffusers.
Measurements By. Fulghum
TABCO Intemdona112011©
Test Dates: March 24. 2011 and March 25 2011
Comments:' Hallway diffusers omitted. Due fire barrier, additional CFM proportionally balanced between surrounding
diffusers.
" Hallway diffusers existing 8" flex ducting, was replaced by HVAC contractor with 10" flex ducting. In order to
obtain design CFM.
Balanced to obtain summation of supply diffusers.
Measurements By. Fulghum
TABCO Intemdona112011©
Test Dates: March 24. 2011 and March 25 2011
Certified Date: March 25, 2011
Proieof _ Grace Emmanuel Church
Location PSL, Florida
AIR DISTRIBUTION DATA
Page: 15 of 18
YSTEM I AHU 4
Comments:. Balanced to obtain summation of supply diffusers.
Measurements %r. Fulghum
TABCO Intemational 120110
Test Dates: March 24 2011 and March 25 2011
Certified Date: March 25, 2011
Page: 16 of 18
Project I Grace Emmanuel Church
Location I PSL, Florida
AIR DISTRIBUTION DATA
YSTEM I AHUS
illigN al
Nurttber
Room
T
Type
size,
lDeaign
CFM
Test -1=
Tes CFM
T61: 2. ::Test - 3
Final: -
CFM
Gorrwnenls
1
Food Pantry 114
Lay In
24 X 24
250
251
253
2
Kitchen 115
Lay In
24 X 24
250
166
227 .
3
Women's TLT 116
Lay In
24 X 24
70
96
77
4
Women's TLT 116
Lay In
24 X 24
70
46
73
5
Men's TLT 117
Lay In
24 X 24
70
117
72
6
Men's TLT 117
Lay In
24 X 24
70
62
70
7
Foyer 101 North
SW
10"
400
184
368
8
Foyer 101 South
SW
10"
400
178
374
9
Class Room 110
Lay In
24 X 24
250 _
NA
**
10
Class Room 105
Lay In
24 X 24
250
280
263
11
Class Room 106
La In
24 X 24
250
256
252
12
Class Room 107
Lay In
24 X 24
250
221
247
13
Class Room 108
Layin
24 X 24
250
336
253
14
Class Room 108
Lay In
24 X 24
250
263
241
15
Class Room 105
La In
24 X 24
250
224
247
16
Class Room 105
Lay In
24 X 24
250
228
262
17
Class Room 109
Lay In
24 X 24
250
284
258
Supply Total
3830
3537
Comments:' Hallway diffusers existing 8" flex ducting, was replaced by HVAC contractor with 10" flex ducting. In order to
obtain design CFM.
" Class Room 110 supply diffuser omitted, Class Rooms 105 to 110 is one large open area; that will be
section off, and appears to have air coverage to all proposed sections. Additional CFM proportionally
balanced between surrounding diffusers.
Measurements By. ul hu
TABCO International / 2011©
Test Dates: March 24. 2011 and March 25 2011
Ni ip
Certified
ftlect Grace Emmanuel Church
Locadon PSL, Florida
AIR DISTRIBUTION DATA
Date: March 25, 2011
Page: 17 of 18
YSTEM I AHU 6
o
• ..
®ate®��®o
Comments:' Added diffuser no design CFM provided, on revised mechanical drawings.
" Balanced to obtain summation of supply diffusers.
Measurements By. uF IDhum
TABCO Intemabonal / 2011©
Test Dates: March 24. 2011 and March 25 2011
Ni ip
Certified
Project Grace Emmanuel Church
Locatlbh. PSL, Florida
Date: March 25, 2011
Page: 18 of 18
AIR DISTRIBUTION DATA
YSTEM I AHU-7
LJL
Lan, 7
�>
I of . •�
®
.—
o
(;omments: 'Addeo olltuser no design GFM provided, on revised mechanical drawings.
" Balanced to obtain summation of supply diffusers.
Measurements By. Fulahum
TABCO Intemaltional / 20110
Test Dates: March 24. 2011 and March 25 2011