Product Evaluation Report SCANNED
GULF COAST SUPPLY & MANUFACTURING, 'LLC. BY
St. Lucie County
26 Ga. Gu1f/i'ibTm Roof Panel over 15132" P►yvvood
Florida Product Approval #11651.23 R3
Florida Building Code 2017
Per Rule 61620-3
Method: 1 —D
Category: Roofing
Subcategory: Metal Roofing
Compliance Method: 61G20-3.005(1)(d)
HVHZ
Product Manufacturer:
Gulf Coast Supply & Manufacturing, LLC.
14429 SW 2nd Place, Suite 630 �%0 %ANF—L S.
Newberry, FL 32669 ?� �• ' �Cery
EngineerEvaluator:
Dan Kuhn, P.E. #75519
Florida Evaluation ANE ID: 10743
Validator:
Locke Bowden, P.E. #49704
9450 Alysbury Place
Montgomery, AL 36117
Contents:
Evaluation' Report Pages 1 — 5
11651.23 R3 • OCTOBER 5, 2017
L�t71 MOu IIlrn M GEC " a Fff
No, 75519
' 9 = STATE OF
��T�'�� OAIOP•.•��
SS;ONAL ENG•�`:
�1811L& 1o/[
GulfCl3�t
SUPPLY 'F MANUTACTURING
Compliance Statement: The product as described in this report has demonstrated compliance with the
Florida Building Code 2017, Sections 1504.3.2, 1.518.9, 1523.&5.2.4.
Product Description:
GulfRibTM, l" Rib Roof Panel, Minimum 26 Ga. Steel, 36" Coverage,
through fastened roof panel over minimum 15/32" Plywood Decking. Non
Structural application.
Panel Material/Standards:
Material: Minimum 26 Ga. Steel, ASTM A792 or ASTM A653 G90 conforming to
Florida Building Code 2017 Section 1507.4.3.
Paint Finish Optional
Yield Strength: Min. 80.Oksi
Corrosion Resistance: Panel Material shall comply with Florida Building
Code 2017, Section 1507-4.3.
Panel Dimension(s):
Thickness: 0.018" Minimum
Width: 36" Coverage
Rib Height: 3/4"'Major•Rib at 9" O.C.
Panel Fastener:
#9-15 HWH'1.5" with sealing washing, or approved equal
1/4" minimum penetration through plywood,
Corrosion Resistance: Per Florida Building Code 2017, Section 1506.6, 1507A.4
Minimum 15/n" thick, APA Rated plywood over supports at maximum 24" O.C.
Substrate Description:
Design of plywood and plywood supports are outside the scope of this
evaluation. Must be designed in accordance w/Florida Building Code 2017.
Design Uplift Pressures:
'AFL# 11651.23'R3 •OCTOHER S, 2a17
Is
_
l Uplift Design Pressure
71.75 psf
159.25 psfrn
=Uplift
9-9-99"
6'S -2.5 65 -
2.56.5"-2.5 -6.5"rn
Spacing
24" O.C.
t2" OCe
includes a Safety Factor = 2.0.
ffi MOD IV(D-T & ° ` °t OLI&iL_
U-000 Nt
SUPPLY 6 MAMUFACIURING
Code Compliance: The product described herein has demonstrated compliance with the
Florida Building 'Code 2017, Sections 1504.3.2, 1518:9, 1523.6.5.2.4.
Evaluation Report Scope: The product evaluation is limited to compliance with the'structural wind load
requirements of the Florida Building Code 2017, as relates to Rule-61 G20-3.
Performance Standards: The product described herein has demonstrated compliance with:
• TAS 125-03
• UL 586-06 -Test for Uplift Resistance of Roof Assemblies
UL 1897-12 - Uplift Test for Roof Covering Systems.
• TAS 100-95 - Test Procedure for Wind and Wind DrivemRain
Resistance of Discontinuous Roof Systems
• TAS 110-00 - Accel. Weathering ASTM G 155 / Salt Spray ASTIv1
B 117.
Reference Data: 1. TAS 125-03: UL 580-94 / 1897-98 Uplift Test
Force Engineering & Testing, Inc. (FBC organization # TST 5328)
Report No. 117-0062T-07A-C Dated 02/19/2007
2. TAS 100-95
Farabaugh Engineering & Testing, Inc. (FBC Organization # TST-1654)
Report No. T126-07, Dated 02/26/2007
Report No. T270-08, Dated 10/13%2008
3. TAS 110-00: Valspar Fluropon coated metal panel testing
A) ASTM G 26 by'PRI Asphalt Technologies dated 01/19%2004
'..B) ASTM B 117 by PRI..Asphalt Technologies dated 01/19/2004
4. Certificate of Independence
By Dan Kuhn, P.E. (FL# 75519) @ Kuhn 'Engineering, LLC
(FBC Organization # ANE ID: 10743)
Test Standard Equivalence: 1. The UL 580-94 test standard is equivalent to theUL'580=06 test standard.
2. The UL 1897-98 test standard is equivalent to the UL 1897-12 test
standard.
3. ASTM G 26iis equivalent to ASTM G 155.
Quality Assurance Entity: The manufacturer hasestablished compliance of roof panel products in
accordance with the Florida Building Code and Rule 61 G20-3.005(3) for
manufacturing under a quality assurance program audited by an approved quality
assurance entity.
FLO 11651.23 R3 •OC-OBER`5, 2017
I p�
Minimum Slope Range: Minimum Slope shall comply with Florida Building Code 2017, including
Section 1515.2 and in accordance with Manufacturers recommendations. For
slopeslless than 3:12, lap sealant must be used in the panel side laps.
Installation: Install per' Manufacturer's recommended.details and RAS 133.
Underlayment: Shall comply with Florida Building Code 2017 section 1518.2, 15183,'1518.4
Fire Barrier: Any approved fire barrier having a current NOA. Refer to a current fire directory
Misting for fire ratings of this roofing system assembly as well as the location of the
fire barrier within the assembly. Fire classification is not part of this acceptance.
Shear Diaphragm:
Design Procedure:
Shear Diaphragm values are outside the scope of this report
For roofs within the parameters listed on the load table, fastening pattern must
at a minimum meet those listed for the applicable wind zone. For all roofs outside
the parameters listed on the load table, design wind loads shall be determined
for each project in accordance with FBC 2017 Section 1609 or ASCE 7-10
using allowable stress design. The maximum fastener spacing listed herein shall
not be exceeded.
LU-L1LqL5g,0 tLILO-wo If/"U. LLL; amils
GulfC5�Mr
SUPPLY F. MANUPACTURING
.ENGINEER LOAD TABLE: 26 Ga. Gulf RibTM Panel over 15/32" Plywood
Buildings having a Roof Mean Heights 20'-0"; Roof Slope: 2"/12" - 12"/12" Gable or Hip Roof; Wind Speeds 120-
180mph, Exposure C, Risk Category 11, Enclosed Building, based on Florida Building Code 2017.
120
130
140
150
160
170
180.
WIND
SPEED
FASTENER
(MIN. 114
SUBSTRATE
(MIN. 15/32")
ON CENTER
ON CENTER
ON CENTER
ON CENTER
'.ON CENTER
ON CENTER
ON CENTER
SPACING
Penetration)
SPACING
SPACING
SPACING
SPACING
SPACING
'SPACING
ZONE 1
#9-15x1.5"
Plywood
24", TYPE 1
24", TYPE 1
2,V,TYPE 1
24", TYPE 1
24", TYPE 1
24", TYPE 1
24", TYPE 1
ZONE 2
#9-150.5"
'Plywood
24". TYPE 1
24", TYPE 1
24", TYPE 1
24", TYPE 1
24", TYPE 1
24", TYPE 1
24", TYPE 1
ZONE 3
#9-15x1.5"
PIyWOOd
24", TYPE 1
24", TYPE 1
24", TYPE 1
12", TYPE 2
12", TYPE 2
12%TYPE 2,
12", TYPE 2
1.) PANEL DESCRIPTION: GULFRIBTM, MIN. 26 GA., GRADE 80, 36"COVERAGE, 3/4" TALL.
2.) PANEL FASTENER: #9-15XLS" HWH WI I H SEALING WASHER OR APPROVED EQUAL
PANEL UPLIFT PRESSURE: 71.75'PSF 0 74" O.C. FASTENER SPACING TYPE I FASTENER PATTERN,159.25
3.) MAXIMUM ALLOWABLE
PSF Q 1.2"-O.C..FASTENER SPACING TYPE 2 FASTENER PATTERN BASED ON TAS 125, UL 580/UL 1897 TESTING.
4.) PLYWOOD DECKING: MIN. "/n" I HICK PLYWOOD MUSI BE DESIGNED IN ACCORDANCE W!1 H FLORIDA BUILDING CODE 201 /.
5.) ROOF SLOPE: ON ROOF SLOPES LESS THAN 3:12, LAP SEALANT MUST BE USED IN PANEL SIDE LAPS.
6.) LOAD TABLE BASED ONWINDPRESSURES CALCULATED PER ASCE 7-10 (KD = 0.85) MULTIPLIED BY 0.6 PER FLORIDA BUILDING
- CODE 2017.
�jpNE2 HIPROOF
ZONE3-\i
BRIDGE
7/ZONE1
/I20NE2 GABIEROOF a`
\ I
RIDGE
ZONE 1
Note: Dimension (a) is defined as 10% of the minimum width of the building or
40•/a of the mean'height of the roof, whichever is smaller, however, (a) cannot be
Tess than either 4% of the minimum width of the building or 3 feet.
TYPE I FASTENER PATTERN
" ZONE 3- — - �w c -
FL# 11651.23 R3 • OCTOBER5, 2017
• a u l i�G1L', fff,' iJ�I@k) G3�C I
Coni Tape seal for use on Slopes less
.#&15 i 1.112, w,5aala, Washer at 24. O.C.
TYPE 2 FASTENER PATTERN
At Panel