Product Evaluation Report
METALFORMING, INC. SCANNED
I" Snap Lock, 24 Ga. Roof Panel over Plywood St. LuBy
Cie County
Florida Product Approval # 8629.4
Florida Building Code 2017
Per Rule 61620-3
Method: 1—D
Category: Roofing
Subcategory: Metal Roofing
Compliance Method: 61G20-3.005(l)(d)
HVHZ
Product Manufacturer:
Metalforming, Inc.
100 International Drive
Peachtree City, Georgia 30269
Engineer Evaluator:
Terrence E. Wolfe, P.E. # 44923
Florida Evaluation ANE ID: 1920
Validator:
Brian Jaks P.E. #70159
Contents:
Evaluation Report Pages 1-4
,A C E rFirr2�,',
No. 4499
STATE OF ;�
. 13"
'oe,ALORI9A �v:
i� 4, .
J'1111% Ito
FL# 8629.4
August 1, 2018
Force Engineering & Testing Inc.
19530 Ramblewood Drive
Humble,= 77338
Compliance Statement: The product as described in this report has demonstrated compliance with the
Florida Building Code 2017, Sections 1504.3.2, 1518.9, 1523.6.5.2.4.
Product Description: 1" Snap Lock Standing Seam Roof Panel, 24 Ga. Steel, 17" Wide, Roof Panel
restrained with steel slider clips into APA Plywood decking. Non-structural
Application.
Panel Material/Standards: Material: 24 Ga. Steel, ASTM A792 unpainted or painted with Valspar Fluropon
or ASTM A653 G90 conforming to Florida Building Code 2017 Section 1507.4.3.
Yield Strength: Min. 50.0 ksi
Corrosion Resistance: Panel Material shall comply with Florida Building Code
2017. Section 1507.4.3
Panel Dimension(s): Thickness: 0.024"
Width: 17" max coverage
Rib Height: 1"
Panel Seam: Snap Lock
Roof Panel Clips: Product Name: 1000SNS
Type: Fixed, 18 Ga., 3 %" long
Corrosion Resistance: Per Florida Building Code 2017 Section 1506.7
Roof Clip Fastener: (2) #12-11 Pancake Type A
Y" minimum penetration through plywood
Corrosion Resistance: Per Florida Building Code 2017, Section 1517.6.
Substrate Description: 1) For HVHZ construction, use 19/32" or greater APA Rated plywood or wood
plank. In reroofing applications where the deck is less than 19/32" thick (min.
15/32") the attachment of the decking in no case shall be less than 8D annual
ring shank nails at 6" O.C. Design of plywood and plywood supports are outside
the scope of this evaluation. Substrate must be designed in accordance w/
Florida Building Code 2017.
FL# 8629.4
2) For Non-HVHZ applications, use min. 15/32" thick, APA Rated plywood over
supports at maximum 24" O.C. Design of plywood and plywood supports are
outside the scope of this evaluation. Substrate must be designed in accordance
w/ Florida Building Code 2017.
04,IllNtE 'E for, C���i♦
CENSF��♦�
No. 4499
�,�
ATE OF
♦ 4
AL0RI9A �
♦♦ er, .004
August 1, 2018
rForce Engineering & Testing Inc.
19530 Ramblc,00d Dtiw
Humble,'17f 77338
Allowable Design Uplift Pressures:
Table"A"
Maximum Total Uplift Design Pressure:
67.3 psf
131.0 psf
Clip Spacing:
24" O.C.
6" O.C.
#Fasteners per Clip:
2
2
*Design Pressure includes a Safety Factor= 2.0.
Code Compliance:
The product described herein has demonstrated compliance with
The Florida Building Code 2017, Section 1504.3.2, 1518.9, 1523.6.5.2.4.
Evaluation Report Scope:
The product evaluation is limited to compliance with the structural wind load
requirements of the Florida Building Code 2017, as relates to Rule 61G20-3.
Performance Standards:
The product described herein has demonstrated compliance with:
• TAS 125-03
• UL 580-06-Test for Uplift Resistance of Roof Assemblies
• UL 1897-2012- Uplift Testfor Roof Covering Systems
• TAS 100-95 -Test Procedure for Wind and Wind Driven Rain Resistance
of Discontinuous Roof Systems
• TAS 110-00 - Accel. Weathering ASTM G 155/ Salt Spray ASTM B 117
Reference Data:
1. TAS 125-03: UL 580-94 / 1897-98 Uplift Test
Force Engineering & Testing, Inc. (FBC Organization # TST-5328)
Report No. 72-0210T-07, Dated 07/12/2007
2. TAS 100-95
Farabaugh Engineering & Testing, Inc. (FBC Organization # TST-1654)
Report No. T233-07, Dated 07/14/2007
3. TAS 110-00: Valspar Fluropon coated metal panel testing
A) ASTM G 155 by PRI Asphalt Technologies dated 10/31/2012
B) ASTM B 117 by PRI Asphalt Technologies dated 10/31/2012
4. Certificate of Independence
By Terrence E. Wolfe, P.E. (No. 44923) @ Force Engineering & Testing, Inc.
(FBC Organization # ANE ID: 1920)
Test Standard Equivalency: 1. The UL 580-94 test standard is equivalent to the UL 580-06 test standard.
2. The UL 1897-98 test standard is equivalent to the UL 1897-2012 test
standard.
..
,`�tVutirtrp�'
,AC E• E
C E t4
i
STATEOF ; C %
�i0't`• AL OR19A ••r"��
i�jj 11rnt"?,,,,
FL# 8629.4
August 1, 2018
s
rForce7Engineerig & Testing Inc.
Ramblewood Dme
Humble,TX 77338
Quality Assurance Entity:
The manufacturer has established compliance of roof panel products in
accordance with the Florida Product Code and Rule 61G20-3.005 (3) for
manufacturing under a quality assurance program audited by an approved
quality assurance entity
Minimum Slope Range:
2:12. Minimum Slope shall comply with Florida Building Code 2017, including
Sections 1515.2.2 and in accordance with Manufacturers recommendations.
Installation:
Install per manufacturer's recommended details and RAS 133.
Underlayment:
Per Manufacturers installation guidelines per Florida Building Code 2017 Section
1518.2, 1518.3, 1518.4.
Fire Barrier:
Any approved fire barrier having a current NOA. Refer to a current fire directory
listing for fire ratings of this roofing system assembly as well as the location of
the fire barrier within the assembly. Fire classification is not part of this
acceptance.
Shear Diaphragm:
Shear diaphragm values are outside the scope of this report.
Design Procedure:
Based on the dimensions of the structure, appropriate wind loads are
determined using Chapter 16 of the Florida Building Code 2017 for roof cladding
wind loads. These component wind loads for roof cladding are compared to the
allowable pressure listed above. The design professional shall select the
appropriate erection details to reference in his drawings for proper fastener
attachment to his structure and analyze the panel fasteners for pullout and
pullover. Support framing must be in compliance with Florida Building Code 2017
Chapter 22 for steel, Chapter 23 for wood and Chapter 16 for structural loading.
FL# 8629.4
T �
No 4t.3
•° • STATE OF : a
i
.41
.P.
�ot:.ALORI9A. 4,�
August 1, 2018