HomeMy WebLinkAboutSCREEN ENCLOSUREFOUNDATION NOTES: EXISTING 16"X12" FOOTER CONTINUOUS INFORMATION PROVIDED BY CONTRACTOR NOTE: DOOR LOCATION IS OPTIONAL AND TO BE DETERMINED BY THE CONTRACTOR NOTE: CONTRACTOR CAN USE BIGGER SECTIONS FOR BEAMS AND COLUMNS r m m m a Z UPLIFT CALCULATIONS: TOTAL AREA OF STRUCTURE = 682 SQ. FEET WIND PRESSURE ON SCREEN ROOF: 6.96 PSF WIND PRESSURE ON SOLID ROOF: 24 PSF WEIGHT OF THE STRUCTURE: 2 PSF WIND UPLIFT FORCE = 6487 LB TOTAL LENGTH OF FOOTING = 83 FEET WEIGHT OF FOOTING=150X1X1.33X83 = 16558 LB TOTAL WEIGHT =16558 LB > 1.67X6487 = 10833 LB OF EXISTING CBS WALL 1 � I DOOR 2X2 N 2X2 N N 1X2 6X6X3/16 I NO 21' I, I ,W N N + o I � I � 6X6X3/16 RB = ROOF BRACING KB = K- BRACING ALL LIGHT GAUGE STEEL MEMBERS SHALL CONFIRM TO ASTM A653 WITH MIN YIELD STRENGTH OF 45 KSL ALL EXISTING SLABS AND FOOTING CONCRETE MUST BE WITHOUT ANY CRACK OTHERWISE NEED TO BE INSPECTED BY CALC ENGINEERING. ALL CONCRETE ANCHORS SHALL BE INSTALLED TO NON -CRACKED AND INTACT CONCRETE SURFACE. ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURES RECOMMENDATIONS. FILE COPY J14' HOST STRUCTURE (2" FASCIA I SLOPE , .4" 1 3"INSULATED ROOF FI (6.632 X 7L6) (NOA FL-7661) ` ! 10LB m 0 r m N W fM O N A 3 m U 2'-8" OST STRUCTURE (2" 7" SUPER 203 GUTTER m m 00 O 203 203+2X10 29' PLAN GENERAL NOTES: - WIND PRESSURES HAVE BEEN DETERMINED BASED ON ASCE 7-10, WIND SPEED OF 170 MPH, EXPOSURE C. THIS STRUCTURE HAS BEEN DESIGNED AND MUST BE FABRICATED IN ACCORDANCE WITH THE STRUCTURAL PROVISIONS OF FBC 2017. DESIGN CRITERIA OR SPANS BIGGER THAN STATED IN THE PLANS MAY REQUIRE ADDITIONAL CALCULATION AND CHANGE IN THE PLAN. CALC ENGINEERING SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO = REEVALUATE THE WORK AND DESIGN UPON DISCOVERY OF ANY INACCURATE - INFO PRIOR TO MODIFICATION OF EXISTING FIELD CONDITIONS AND FABRICATION AND INSTALLATIONOFMATERIALS. NO EXTRA LOAD IS PERMITTED TO APPLY ON THE STRUCTURE AT THE TIME OF INSTALLATION. - CONTRACTOR SHALL CAREFULLY CONSIDER POSSIBLE IMPOSING LOADS ON ROOF INCLUDING BUT NOT LIMITED TO ANY CONCENTRATED LOADS WHICH MAY JUSTIFY GREATER DESIGN CRITERIA. ALL FASTENERS TO,BE #10 OR GREATER ASTM F593 COLD WORKED 304 STAINLESS STEEL UNLESS NOTED OTHERWISE. ALL ANCHORS FOR ALUMINUM SHALL BE SPACED WITHIN 2 TIMES DIAMETER END DISTANCE AND 2 TIMES DIAMETER MIN SPACING TO ADJUST ANCHORS. 1X2 203+2X10 \ 0 1X2 �co X m \��4` G`j / Co X N X \Py me% ccoo r N Et x \ m 2X3 Q ��� 1X2 1X2 - - - - - --------------- -24 7 Q1' FRONT ELEVATION f�'-6r,-� EXISI7NG CBS WALL TRANSOM WALL F$ r \V r �P �X W , EXISTING 16"X12" PERIMETER FOOTING REVIEWED FOR CODE' COMPLIANCE ST. LUCIE COUNTY BOCC DESIGN CALCULATION: BASIC WIND SPEED (RISK CATEGORY 1)170 MPH DESIGN BASED ON CATEGORY I EXPOSURE CATEGORY:C 3-SEC PEAK GUST IN MPH DESIGNED BASED ON 6005-TS ALUMINUM 18X14 MESH TYPE WIND PRESSURE ON SCREEN ROOF: 6.96 PSF WIND PRESSURE ON WALLS: 22 PSF WIND PRESSURE ON SOLID ROOF: 24 PSF O W m 0 U Z W Z W W LL' U m Y 2 U SCANNED BY St. Lucie Cow U E o LL 00) N M OT J LL. LL Z U O N c1L LL Z O F LU W F `° w n N U m m LL co O �Z" Cl) W Z rn U3 Z m W>CIO00 m Z a� CoZ U � (y) LL Z C7mJLo o�- 0 Z LL (y7 W F- W Ix W J O C 5 U 0LCl)o0ELW U 2" THICK SUPERGUTTER ATTACHED WITH ADD'L 3/8'X5" LAGS 0 ROOF TRUSS OR� RAFTER TAIL Ek/s7- 7RUsS CONT. SHIM ANGLE (FOR SLOPED FASCIA) 7" SUPER GI IX7X1/8" ANGLE (6" LONG) 0 EACH BEAM ATTACHED TO FASCIA W/ Y4"X3" LAGS (2 PER ANGLE) AND #14 TEK SCREWS (2 PER ANGLE). 7" SUPERGUTTER ATTACHED TO FASCIA WITH Y4' X 3" LAGS 0 24" O.C. 0 0 MANSARD BEAM 2X3X3/16" ANGLE W/ (4) #14 TEK SCREWS TO MANSARD BEAM AND (1) Y4" THRUBOLT WASHER & NUT AND (2) #14 TEK SCREW (THROUGH 1X3) TO 5" SUPERGUTTER 1X3 ATTACHED TO SUPERGUTTER WITH #12 TEK SCREWS 0 16' O.C. BEAM TO FASCIA CONNECTION CHAIR RAIL DIAGONAL (K-BRACE) SCREEN SIDE GUSSET ANGLE BEHIND PARTIAL ELEVATION/ K-BRACE AT CHAIR RAIL GLE BRACKET W/(9) #14 TO WALL MEMBERS — EAVE RAIL 16" EYE -BOLT WELDED CLOSED WITH DEL NUTS DOUBLE COMPRESSION SLEEVES y" STAINLESS STEEL CABLE DOUBLE COMPRESSION SLEEVES ,->� r- COLUMN y" STAINLESS STEEL 1 1/'x 5 %" x %"FLAT BAR � (2) ONI 1/2" TAPCON CABLE BRACE DETAIL (4) #10 S.M.S. FROM INSIDE FACE OF COLUMN INTO SCREW SPLINES OF 1/4' THRUBOLT/ `\ 20 (1-YZ: EMBEDMENT MIN.) 3/4 0 WASHER/ `\ `2X3 CHAIR RAIL NUT `COLUMN CHAIR RAIL CONNECTION "K" BRACE INSTALLED AT COL OUTSIDE FACE: USE 5" X B" X 0.064' MIN. PLATE W1(12)-#10'S INSIDE: USE 0.0B4' MIN ANGLE 1'X3'X8' LG. Wl(12)10'S OR (2) 1'X3-X4' LG. ANGLES W/(6) -o10'S °K" BRACE INSTALLED W15'X 51 X mow MIN. PLATE OUTSIDE W/ (9) -010 S.M.S PER PLATE INSIDE: USE 0.064" MIN ANGLE 1' X 3' X 4° LG, ANGLES W1(9) -#10'S NOTES: "ICBRACING 1) PROVIDE MIN r BETWEEN FASTENERS & MIN z" EDGE DISTANCE 2) PROVIDE A MIN. OF TWO FASTENERS PER MEMBER 3) 2X2X.090 MAY BE USED IN LIEU OF 2X3X.060 2X2X1/8" "C" CHANNEL-1 W/(1)1/4" THRUBOLT/WASHER/NUT ROOF BRACING " ANCHOR OTHER END TO BEAM W/ (1) Y4" THRUBOLT/WASHER/NUT OR (2) #14 TEK SCREWS ** ANCHOR OTHER END TO PURLIN W/ (1) Y4" THRUBOLT/WASHER/NUT FILE COPY 2 .Wz" 05" .07' i° 1 N m 07U 203 DOORJAMB (EAVE RAIL) L224W —1'.04411 .044 1X3 ;50105� 203 8LB 9LB 6X6X3/16 EXIST. WOOD/CONC. j `\ HOUSE ROOF = ` o ` (2) #10 SMS i o Y4-TAPCONS 024° O.C. FOR CONCRETE Y4 J & " LAGS 0 18" O.C. FOR WOOD r 3 REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCC w 1X2 0 (2) #10 SMS F SEE SITE SPECIFIC DRAWING v1 FOR FOUNDATION DETAILS X w PORCH PANEL 3" INS. ROOF 9 LB CARRY BM. USE (2) 1/12"X7" THRUBOLTS .37 6X6X3/16 COLUMN 10 LB (NOTCH TO SIT - BEAM ON COLUMN) Daa" 'a 4LB i " T 2' .044"1 FIT 25" .09" .044202 `° .090' li 303 2X5x.125" ATTACH INSULATED PANELS WITH (1) 1/4"X4" LAGS 0 8" O.C. (USE 1" WASHER) O 3X3X1/4 ANGLE W/ (6) #14 TEKS SCREWS EACH SIDE (AS SHOWN) CARRY BEAM TO 6X6 COLUMN USE #12 SMS ® 24" O.C./ TOP & BOT. FOR 7LB OR SMALLER o AND #14 SMS 0 24" p O.C./ TOP & BOT. FOR 8LB OR GREATER ' , L LAP BEAM CONNECTION Z O H- 0 W 2 m 0 N U m ILL Z O 0 W Q 00 D Z 0 Tn LU 0 "/"IllIOi�u�`` 0) 1n N~ Z CD H Q Z(DY 0 U) coo 6' O U- W U C 0 W 1L m —i U �_ >, -1 ILL! Ix LL Z 1n 3 W 2 Z U o� O 0 E U 2 o m (n H N 0_ Uco W C4 Lo z Z rnDO LUW coobED- Z U) cl) U C7 co _j 0 w z _ j -T W O-' Z y Z LU j o c U UWW))0dw0 2"X2"XY8' CLIP ANGLE SMS EA. SIDE 2X2X1/8 CLIP ANGLE W/(3) #14 TEKS EACH r6X6X SIDEASSHOWN 3/16 3" (MIN.) UMN 2"X2"X3/16" CLIP ANGLE W/(3) #14 SMS EA. SIDE X2 W1.1ss EXIST. 16X12 4 a FOOTING 4 a d a a 4 (1) YB"X4"'TAPCON (1) 1/4"X3" TAPCONS (EACH SIDE) (MIN 2 Y2" EMBEDMENT TO CONCRETE) 2-}"X3" THRU-BOLTS AT EA. COL. TO BEAM (EACH SIDE) ADD 1 EXTRA CLIP ANGLE W/ (MIN 2 Y2" EMBEDMENT (5) #14 SMS EA. SIDE & TO CONCRETE) (1) 1/4"X3" TAPCON EA. SIDE (2 Y2" MIN. EMBEDMENT) COLUMN ATTACHMENT TYP. SELF„ - MATING BEAM CO CO NN10"gyp., I%'AL GUSSET PLATE INSIDE OF SPLICE W/ SCREWS PER SCHED. BELOW MANSARD BEAM SPLICE REQ'D # OF #14 TEK SCREWS 4LB - 6LB 6 V24 8 32 9 36 10 40 11 44 2X2X1/8 CLIP ANGLE W/ (2) #14 TEK SCREWS EACH FACE, EACH SIDE MANSARD SPLICE DETAIL NOTE: PROVIDE MIN 1" SEP BETWEEN FASTENERS. MIN 1" EDGE DISTANCE BETWEEN FASTENERS & GUSSET PLATE 2X2Xl/8 CLIP ANGLE W/(3) 914 TEKS EACH SIDE AS SHOWN 91-13 MANSARD BEAM 203 WITH (1) #14X4" LG. TEK SCREW@ IT C.C. 6" LONG "Z" BRACKET ® EACH BEAM ATTACHED p TO BEAM W/ #12 TEKS (3 PER BRACKET) ® 1X2 (OPTIONAL) ATTACHED TO SUPERGUTTER ® W/ (1)#14 X 2' TEK SCREWS ® 24" O.C. —ER/NU' ANGLE W/ (1) Yc" TEA. SIDE 0001 � 10L8 WASHER/NUT & (3) #14 TEKS EA. SIDE ® (#14'S CAN BE REPLACED W/(2) '�� 1/4- THRUBOLTS) u 1X2 ATTACHED TO MANSARD BEAM —TEKS WITH (1)#14 CUT OFF+CAP OPTIONAL FOR MANSARD BEAMS TEK SCREW �B"C.C. ( ) 5 SUPER GUTTEF 6XGX3116 6XBX3/16 COLUMN NSULATED ALUM. PANEL ATTACHED TO CARRY BEAM W/ #14 TEK OR LAGS (4"1-G.) W/1" WASHER ® 8" O.C. ATTACH S. GUTTER TO CARRY BEAM W/ Y: THRUSOLTS 0 24' O.C. 9LB,CARRY'BEAM BEAM TO COL. ATTACHMENT 1 REVIEWED FOR INS. PANELS TO BEAMS. ATTACHMENT' =' CODE COMPIL-5 Mom FILEST. I.UCIE COUNTY3" ALUM. COPY e®cC OSCR 3" LONG 2"X2"X}' A. PURLIN U-CHANNEL W/(4) - #14 TEK SCREWS TO BMB" r THRU - BOLTS OR (4) 914 TEK SCREWS EA. SIDE PURLIN CONNECTION � 203 PURLIN 203 NTH (1) #14X4" LG. TEK SCREW @ 12" C.C. 10LB 6X6X3/16 COLUMN IX2 ATTACHED TO —10 LB WITH (1) #14 TEK SCREW @ 8" C.C. 7LB COLUMN PURLIN ATTACHMENT "BACKER PLATEINTERNAL SLOPING PURLIN ' DOWN PURLIN CONNECTION F--1 0 0 00 (3 000 0 ol 10 LB CARRY BEAM o 0 3"XW/ () 1/4 X3" TAPCONS TO CBS WALL AND (6) #14 SMS TO CARRY BEAM EACH SIDE (#14 TEK SCREWS CAN BE REPLACED W/ (2) Y4"X3" THRU BOLTS CARY BEAM TO CBS WALL 1X2 2X3X1/8 CLIP ANGLE W/ (2) 3/8"X5 1/2" TAPCONS (2" MIN. EMBEDMENT) & 07 (3) #14 TEK SCREWS ® lX2OR1X3 RECEIVING CHANNEL WITH #12 S.M.S. B 8" O.C. TOP & BOTTOM 1X2 OR 1X3 1X2� ME 2X3X7/8 CLIP ANGLE W/ (2) 3/8'%5 1/2" TAPCONS (2" MIN. EMBEDMENT) & (3) #14 TEK SCREWS CORNER COLUMN 1 0?:� 3" INS. PANEL 3" INSULATED ROOF TO FASCIA ATTACHMENT N F Z 0 46 41, / /�llllliVl��� V4"x3" LAGS 16" O.C. ALONG HEADER. 3/8"x5' LAGS TO TRUSSES (0 24" MAX) — 2" SUB FASCIA CONT. SHIM ANGLE (FOR SLOPED FASCIA) W Lo F- N Z o 111 2 2 ~ ¢ z O Y 0 W R U Q W C lL co V i3 J M co J LU LL LLI Z U w D_'O0 E U co) 2 F o N m 0_ z 3 O F- O W F- � lLV t` O N M LL LL w Z co W N O CO� Z cn Z rn=)0 W W ccooEDmF- (o Zac')mZU C9 � — lL Z C7EDJoER- W J "W W J o c U ❑ o 0cr)U))DaWU FILE. co-%OPY y )pzz FILE COPY REVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY BOCC REVIEWED FOR, CODE COMPLIANCE ST. LUCIE COUNTY Bocc