HomeMy WebLinkAboutGENERATOR CONCRETE PAD- GENERATOR
PAD
THICKNESS
PAD DIMENSIONS:
CONCRETE PAD
GENERATOR -
0
L,
GENERATOR UNIT BY
SEPARATE SUBMITTAL
(SEE SCHEDULE FOR
MINIMUM WEIGHT
REQUIRED)
Q )
54" LENGTH
PLAN VIEW
AMERICAST GENERATOR CONCRETE PAD
(ON -GRADE APPLICATIONS ONLY)
AMERICA3T
•MADIp INA&�Ws
FmTAxtaoasan IJCEga
NSBESW3tlBaIRT
.H:
RECEIVED
MAR 55 '119
ST. Luele County, P�6rml InL�
HVHZ OR NON-HVHZ
RISK
EXPOSURE (EXP)
RISK
EXPOSURE EXP)
RISK
EXPOSURE(EXP)
COUNTY
I
C
D
II
C
D
III, IV
C
D
P. BEACH
150 MPH
30.44 Psf
36.94 Psf
170 MPH
39.09 Psf
47.44 Psf
IM MPH
43.83 Psf
53.19 Psf
BROWARD
156 MPH
32.92 Psf
39.95 Psf
17G MPH
39.09 Psf
47.44 Psf
180 MPH
43.83 Psf
53.19 Psf
MIAMI-DADE
165 MPH
36.83 Psf
44.69 Psf
175 MPH
41.43 Psf
50.28 Psf
186 MPH
46.80 Psf
56.80 Psf
ISOMETRIC VIEW
CONCRETE PAD
ROAD IS
ASTERFIBER 3" MIN
MAC100 __,V_4" MIN
50"
54"
GENERATOR TABLE:
BRAND &MODEL
CAPACITY
WIDTH
LENGTH
HEIGHT
WEIGHT
ALLOWABLE
PRESSURE
COMMENTS
Generac 005871 & 005883
10 KW
25.00"
49.00"
29.00"
387lbs
41.43 Psf
EXPC 175 MPH &D 156 MPH
Generac 005872 & 005884
14 KW
25.00"
48.00"
29.00"
439 lbs
47.44 Psf
EXPC 186 MPH &D 156 MPH
Generac 6459, 6461, 6462
16 KW
25.00"
48.00"
29.00"
5131bS
47.44 Psf
Generac006721
16 KW
25.00"
48.00"
29.00"
448lbs
47.44 Psf
Generac 005873 & 005885
17 KW
25.00"
48.00"
29.00"
455Its
47.44 Psf
Generac 005874 & 005886
17 KW
25.00"
48.00"
29.00"
4211bs
47.44 Psf
Generac 005875 & 005887
20 KW
25.00"
48.00
800
29.00"
4511bs
47.44 Psf
Generac 006729 & 006730
20 KW
25.00"
48.00"
29.00"
516lbs
47.44 Psf
Generac 006551&006552
22 KW
25.00"
48.00"
29.00"
5261bs
47.44 Psf
Kohler 14RES&20RES
14-20 KW
26.00"
48.00"
29.00"
500 Its
47.44 Psf
GE 403236E&40324GE
13 KW
35.00"
39.40"
39.00"
5401bs
39.09 Psf
EXP C 170 MPH &D 156 MPH
GE 04038215KW
15 KW
33.00"
48.00"
30.50"
4841bs
43.83 Psf
EXP C 180 MPH &D 156 MPH
GE04037817KW
17 KW
33.00"
48.00"
30.50"
484 Its
43.83 Psf
GE 40330GE & 40331GE
20 KW
33.00"
48.00"
30.50"
600 lbs
43.83 PSf
Briggs& Stratton 040243.0
10 KW
31.00"
32.00"
34.00"
430lbs
43.83 Psf
Briggs & Stratton 040302-2
12 KW
33.75 "
50.00 "
31.60 "
5071Is
41.43 Psf
EXP C 175 MPH & D 156 MPH
Briggs & Stratton 040303-1
15 KW
33.75"
49.00"
31.60"
562lbs
43.83 Psf
EXP C 180 MPH &D 156 MPH
Briggs& Stratton 0403044
18 KW
33.75"
49.00"
31.60"
568lbs
44.00 Psf
Briggs&Stratton 040305-1
20 KW
33.75"
49.00"
31.60"
5701bs
44.00 PSI
Generac 703S, 7036, 7037
16 KW
25.00"
48.00"
29.00"
406lb5
47.44 PSI
EXP C186 MPH &D 156 MPH
Generac 007038 & 007039
20 KW
25.00"
48.00"
29.00"
448lbs
47.44 Psf
Generac 007042&7043
22 KW
25.00"
48.00"
29.00"
466lbs
47.44 Rd
GENERATOR MOUNTING CONFIGURATION:
GENERATOR
GENERATOR ATTACHMENT BASE
OR SIMPSON A24 ANGLE BRACE
W/ (4) #10 SS 316 SELF -DRILLING
O SCREWS
7 TO GENERATOR
I
ENERATOR
(SEECONCRETEPAD
SCHEDULE FOR
M 2 I DIMENSIONSWEIGHT
REQUIRED)I
7-32" WIDTH -�-54" LENGTH+
SIDE VIEW
FRONT VIEW
(SEE
ANCHOR TO PAD SCHEDULE:
SUBSTRATE
DESCRIPTION
CONCRETE:
(2)-3/8"0 TIfEN HD
(6000 PSI
OR EQUIVALENT,
MIN.)
2-3/4" FULL EMBED
0 CONCRETE, 3" MIN.
EDGE DISTANCE 6"
MIN. SPACING TO ANY
ADJACENT ANCHOR.
NOTES:
1. ANCHOR QUANTITY PER LONG SIDE
2. EMBEDMENT AND EDGE DISTANCE
EXCLUDES FINISHES, IF
APPLICABLE.
3. ENSURE MINIMUM EDGE DISTANCE
AS NOTED IN ANCHOR SCHEDULE.
4. ENSURE MINIMUM SPACING TO
ANY ADJACENT ANCHORS.
S. FOLLOW MANUFACTURER'S
INSTALLATION INSTRUCTIONS TO
INSTALL ANCHORS.
GENERATOR
ATTACHMENT BASE,
VARIES WITH MODEL
SEE GENERATOR SPECS
fie° SIMPSON MEN HD,
SEE ANCHOR SCHEDULE
2"x3"x1/s" GALV. STEEL -
WASHER
RUBBER VIBRATION PAD -
ale" THICK GALVANIZED
WASHER& RUBBER
VIBRATION PAD
Z
CONCRETE PAD -
6,000 PSI
LIGHTWEIGHT
CONCRETE PAD
X
CONCRETE MIX
6,000 PSI
Nf
Nf
LIGHTWEIGHT
MASTERFIBER
MAC 100
CONCRETE MIX
& ROAD MESH
NOTES:
FOAM CORE
1. Y DISTANCE DEPEND ON GENERATOR BASE LENGTH, NO LESS THAN 2".
2. X DISTANCE 3" FROM UNIT EDGE TO CLIP.
3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO LESS THAN
ANCHOR REQUIREMENTS
�2" --t
JK L. BEN ARDO, P.E.
0046549
'1 �018
.E.01RE0P5 B6N
TISTO, P.E.
O L UNi
ICE: IF THIS SHEET. DOES
CONTAIN AN ORIGINAL
NATURE & ENGINEER SEA
IERE 15 A DIGITAL
IAIURE ON SHEET 1, THIS
IT IS PART OF A DIGITALLY
LED FILE, SHALL REMAIN IN
TAL FORMAT, & PRINTED
WIND DESIGN REQUIREMENTS-
0R THIS SIEEETTDDOOES NOTEEII
NMAtry AN ENGINEERS
ORIGINAL SIGNATURE & SEAL,
(BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH EDITION
(
THIS SHEET ISt COPY DRAFT.
AT -GRADE DESI SIGN METHOD
rr(nf
N
ULTIMATE DESIGN WIND SPEED V01t = 186 mph
U
NOMINAL DESIGN WIND SPEED VaSD = 144 mph
Z •+ V
RISK CATEGORY =III INTERNAL PRESSURE COEF = N/A
W M - U £
EXPOSURE CATEGORY = D WIND DIRECTIONALITY FACTOR K0=
LL iti H in $ O m
w
0.85
LL �
LU
ENCLOSURE CATEGORY = N/A HEIGHT H = AT GROUND
GUST EFFECT FACTOR
1�1 LL in y W �y
W =
= 0.85 PRESSURE AT HEIGHT H qh = 77.56
0 :`,+ K x
Ib/ft2
�� wW UPzw�
FORCE COEFFICIENT Cf = 1.44
UI a tt Q, W o w (7
WIND PRESSURE
OLm-�z�
P= qh G Cf = 56.60 Ib/ft2 (ASD)
ZX
O N o m w w u
W W w
U� W -
GENERAL NOTES
NO
3
Ul W aiw
1. THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED IN
ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE
W w
Q
SIXTH EDITION (2017).
n
2. REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR USE
Q S WITH
THIS SYSTEM SHALL BE DETERMINED UNDER SEPARATE CERTIFICATION ON A
JOB -SPECIFIC BASISAD IN THEGOVERNINGI NACCORDE.
N N
REQUIREMENTS S DE
LOAD REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH
O
THE AB BUILDING CODE SHALL BE LISTEDTHAN
THEGNPRES
W
U
DESIGN PRESSURE'ASD" CAPACITY YAW ES LISTED HEREIN FOR ANY
HERON FOR
J H
ASSEMBLYASSHOWN.
3. DIMENSIONS AND WEIGHT OF UNITS SHALL CONFORM TO SPECIFICATIONS
LLl U C3
,� //��
STATED HEREIN.
4. UNITS MUST BE PAD WITH OPPOSITE SIDES HAVING EQUAL
LJ J Q LL N Y DI Z
O Dj M L-
MINIMUM D ST
CLEARANCE. AMINIMUM DISTANCE FROM UNIT C PAD EDGE F SPECIFIED.
S. MADE USING LIGHTWEIGHT CONCRETE 125 PCF
.Pi
f
( ) r LLl
`� 1[-j W
THE AREA
fi. THE AREA VNDER CONCERETE SLAB ON GROUND SHALL HAVE ALL
UNDER GROUND
w
HI � W W M 0
VEGETATION, STUMPS, ROOTS, AND FOREIGN MATERIALS REMOVED PRIOR
J a K M U
TO INSTALLATION ON COMPACTED SOIL AS VERIFIED BY OTHERS.
d F N m Z U
W
7. RESISTANCE TO SLIDING OF THE PAD ON THE GROUND IS NOT PART OF THIS
L n V Q iD
M J
DOCUMENT AS SOIL CHARACTERISTICS AND PAD PLACEMENT VARIES.
C C) Z
G M LL O
8. ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED & INSTALLED BY
y
OTHERS. ALL MECHANICAL SPECIFICATIONS (CLEAR SPACE, TONNAGE, ETC.)
Q N W
SMALL BE AS PER MANUFACTURER RECOMMENDATIONS AND ARE THE
N m
EXPRESS RESPONSIBILITY OF THE CONTRACTOR.
AFFIXED HERETO VALIDATES
9. ENGINESHOWN
(W7
YSTRUCTURALONRACTOR, Et. 1.
ONLY.
SHOWN ONLY. USE OF THIS SPECIFICATION BYCONTRACTOR, al.
of
INDEMNIFIES HARMLESS THIS ES FOR ALL T&DAMAGES
T
O
GAL FEE
INCLUDING LEGAL FEES &APPELLATE FEES RESULTING FROM MATERIAL
UL RESULTING MOM M
IJy
FABRICATION, SYSTEM ERECTION, CONSTRUCTIONNDER PRACTICES BEYOND THAT
WHICH IS CALLED FOR BY LOCAL, STATE, &FEDERAL CODES &FROM
F a m m ti 5o i 5
DEVIATIONS OF THIS RAN.
Q $
10. WATER -TIGHTNESS OF EXISTING PUNISHES SHALL BE THE FULL
G ? v ? g
o 0 0
RESPONSIBILITY OF THE INSTALLING CONTRACTOR. CONTRACTOR SHALL
ENSURE THAT ANY REMOVED OR ALTERED WATERPROOFING MEMBRANE IS
O
x Q6-6
RESTORED AFTER FABRICATION AND INSTALLATION OF STRUCTURE
U m w !9 x
U ww ES
PROPOSED HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY
, ,
WATERPROOFING OR LEAKAGE ISSUES WHICH MAY OCCUR AS
ESS SHALL BE THE FULL RESPONSIBILITY OF THE INSTALLING
2
00 iogF
CONTRACTOR.
11. THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF SPECIALTY
o g Z
'a U "' �
ENGINEER AND NOT THE ENGINEER OF RECORD. CONSEQUENTLY, THE
ARCHITECT/ENGINEER OF RECORD SHALL BE RESPONSIBLE FOR THE
6v:
w
INTEGRITY OF ALL SUPPORTING SURFACES TO THIS DESIGN WHICH SHALL
BE COORDINATED BY THE PERMITTING CONTRACTOR.
Ncow�
o r F ¢ o
12. THIS DOCUMENT IS GENERIC AND DOES NOT PERTAIN TO ANY SPECIFIC
w
y wo
PROJECT SM. INFORMATION CONTAINED HEREIN IS BASED ON
CONTMCTDR-SUPPLIED DATA AND MEASUREMENTS. ENGINEERING EXPRESS
M w m E
SHALL NOT BE HELD RESPONSIBLE OR LIABLE IN ANY WAY FOR ERRONEOUS
w
SU
OR INACCURATE DATA OR MEASUREMENTS. DIMENSIONS ARE SHOWN TO
C z n
'
ILLUSTRATE DESIGN FORCES AND OTHER DESIGN CRITERIA. THEY MAY VARY
COPYRIGHT ENGINEERING EXPRESS®
SLIGHTLY, BUT MUST REMAIN WITHIN THE LIMITATIONS SPECIFIED HEREIN.
WORK SHALL BE FIELD VERIFIED BY OTHERS PRIOR TO CONSTRUCTION.
ENGINEERING EXPRESS SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO
��_����"�
REEVALUATE OUR WORK UPON DISCOVERY OF ANY INACCURATE
INFORMATION PRIOR TO MODIFICATION OF EXISTING FIELD CONDITIONS
SCALE: NTS UNLESS NOTED
AND FABRICATION AND INSTALLATION OF MATERIALS. ALTERATIONS OR
OF
ADDITIONS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE OUR
CERTIFICATION.
/'T
13. EXCEPTAS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERi1PUC4TI0N5
_rl(LJIII
OR AFFIRMATIONS ARE INTENDED. SCANNED
St. Lucie County