NOTICE OF ACCEPTANCE (NOA) www.miamidade_eov/economv
James Hardie i3uiilding Product, Inc- SCANNED
10901 Elm Avenue BY
Fontana, CA92337 St. Lucie County
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER-Product Control Section to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The MLami-Dade County Product Control Section
(in Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this
product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted
manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or -
suspend suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance,
if it is determined by Miami -Dade County Product Control Section that this product or material fails to meet the
requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code,
including the High Velocity Hurricane Zone.
DESCRIPTION: "Hardie", "Cem" and "Prevail" Planks and Panels Fiber Cement Siding and Soffit
APPROVAL DOCUMENT: Drawing No. PNL, PLK & SOFF, titled "HardiePanel, CemPanel, Prevail
Panel; HardiePlank, CemPlank Prevail Lap Siding, HardieSoffit, CcmSoffit Panel; Installation Details
Wood/Metal Stud Construction", sheets 1 through 12 of 12, dated 04/24/2013, prepared by the
manufacturer, signed and sealed by Ronald I. Ogawa, P.E, bearing the Miami -Dade County Product
Control revision stamp with the Notice of Acceptance number and expiration date by the Miami -Dade
County Product Control Section.
MISSILE NIPACT RATING: Large and Small Missile Impact Resistant
LABELING: A permanent label with the manufacturer's name or logo, Plant City, Florida; and the
following statements: "ASTM C 1186 Type A compliant' and "Miami -Dade County Product Control
Approved" is to be located on each siding plank or panel and per FBC 1710.92 and 1710.93 on soffit
panels.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. if any portion of the NOA is displayed, then it shall be done
in its entirety:
IPTSPECITON: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA revises NOA # 17-0406.06 and consists of this page 1 and evidence pages E-1 and E-2, as well
as approval document mentioned above.
The submitted documentation was reviewed by Carlos NL Utrera, P.E.
NOA No-17-0821.21
Expiration Date: May 1, 2022
Approval Date: November 30, 2017
(1/2Z/V17 Page 1
James Hardie Buildine Products, Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
1. EVIDENCE SUBMPPTED UNDER PREVIOUS NOAs
A. DRAWINGS "Submitted under NOA # 13-0311.07"
1. Drawing No. PNL, PLK & SOFF, titled "HardiePanel, CemPanel, Prevail Panel;
HardiePlank, CemPlank Prevail Lap Siding; HardieSof(it, CemSoffit Panel;
Installation Details Wood/Metal Stud Construction", sheets 1 through 12 of 12, dated
04/24/2013, prepared by the manufacturer, signed and sealed by Ronald I. Ogawa,
P.E.
B. TESTS"Submitted under NOA #13-031L07"
1. Test reports on 1) Uniform Static Air Pressure Test, Loading per FBC TAS 202-94
2) Cyclic Wind Pressure Loading per FBC, TAS 203-94
along with marked -up drawings and installation diagram of HardiePlank, HardieSoffit
and HardiePanel, prepared by Intertek Testing Services NA LTD, Test Report No.
100733361COQ-004, dated 08/24/2012, with revision 1 dated 04/2V2013, signed and
sealed by Rick Curkeet, P.E.
"Submitted under NOA # 02-0729.02"
Laboratory Report Test Date Signature
2. ATI-16423-1 PA 202 & 203 03/18/96 A. N. Reeves P.E.
3. ATI 16423-2 PA 202 & 203 03/18/96 A. N. Reeves P.E.
4. ATI 16423-3 PA 202 & 203 03/18/96 A. N. Reeves P.E.
C., CALCULATIONS
1. None.
D. QUALITY ASSURANCE
1. Miami -Dade Department of Regulatory and Economic Resources (RER)
E. NIATERLAL CERTIFICATIONS
1. None.
F. STATEMENTS "Submitted under NO.A # 15-0122.04"
1. Statement letter of code conformance to the 50' edition (2014) FBC issued by Ronald
I. Ogawa & Associates, Inc., dated 10/26/2014, signed and sealed by Ronald I.
Ogawa, P.E.
*111ff149J7 .
Carlos M. Utrera, P.E.
Product Control Examiner
NOA No.17-0821.21
Expiration Date: May 1, 2022
Approval Date: November 30, 2017
E-1
James Hardie Buildine Products, Ina
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
2. NEW EVIDENCE SUBMITTED
A. DRAWINGS
1. None-
B. TESTS
1. None.
C. CALCULATIONS
1. None.
D. QUALITY ASSURANCE
1. Miami -Dade Department of Regulatory and Economic Resources (RER)
E. MATERIAL CERTIFICATIONS
1. None.
F. STATEMENTS
I. Statement letter of code conformance to the 6`b Edition (2017) FBC and of no financial
interest issued by Ronald I.Ogawa & Associates, Inc., dated 07/30/2017, signed and
sealed by Ronald I.Ogawa, P.E.
t112/200
Carlos M. Utrera, P.E.
Product Control Examiner
NOA No. 17-0821.21
Expiration Date: May 1, 2022
Approval Date: November 30, 2017
E-2
PROD
as cam
Bu11dIn
NOA-N
Stud Spacing at 16' O.C.
T'' rat ! 17 �i �' `V' Q� •c
m I•� o� tiL \gP'`C'y
Difemi fFaedtol �' `�s �J��, �:
UCT RENEWED
plying With the Florida
I Code
o. 17-0406.06
PRODUCT REVISED
as eomplying with the Florida
Building Coco
Boa -No. 17-0821.21
FxPlmtron Dgde 0510112022
BY
Mlam ro oat contfol
11
Nalls at 18 O.C. (typ.)
Va" MiNmum Edge gistance
60.$ Sheathingfastenar, as described in
Note 1
�\ Panel fastener, as described in
Note 2
HardiePanel, Cempanel,
Prevail Panel Siding
Water-rosislve barrier per
Florida 00ding Code Section
14042
518" thick] 5 ply APA rated
plywood sheathing fastened In
accordance with Florida Building
Code Section 2322.3
2" X 4" S-P-F Wood Studs
The wall and soft frames are to be designed
by the Architect or Engineer of Record In
oompliance will the Florida Building Code.
SEE PgCDU-r-T-9 � Qll
HarddsPanem. Cempa em. &
DFTAILA Prevail® Panel Siding materials are
/ 8°tNdc/6pIyAPArated nonasbeslasfiber-osmentProducts
tested In accordance with ASTM
plywvodsheaudnoln C1186Grade R,lypeAand meadng.
accadaneennih Florida the requirements ofthe Pkidda
Building Code Section Building Code.
23223
Wafer-resis6ha �F4-91.�I.�lS1SZNS.
Wdih length Thlckness
barrlenper Flo Florida V 6,U,10' 5118"
s Code
Sec&on 74042 pF LWNyj�F--S-SjiRE RA1M
2-X4°8-P-F installation Design Pressure
vtaod Surds Wood Studs 46 psi
T
HpnlinpanW, Impact Resistant-
��� � Cernparnel Planks Insmned over 5t8" thick / 5 ply
Pmvan p APA rated plywood sheathing
Siding
pAH�k.� �2AAl�l.EMVAA1-M 7 �+DLa �Ni?ALi271LQ —E -1t,�
• All Installation shah be done in conionsence vdhh this Notice of Acceptance, Uhe manufaeturei's
installation recommendations, and the applicable sections of the Florida Building Coda.
• Wood studs where HardiePanel, Campanel, Prevail Panel Siding will be installed shell ba
designed by an Engineer or Architect per the Florida Building Coda and the requirements of this
N.OA
(Nato 1150 thick] 5 ply APA rated plywood sheathing shall be attached to the shads In
acodrdance With Florida Sutiding Code Section 2322.3,
• The siding panels shall be Installed over Ste' thick! 6 ply APA rated plywood sheaMin9 supporter
by a minimum elf2'4(4" S-P-F vrood studs spaced a maximum of 16• Q.C.
• [Note 21 The siding panel fastener shall bet a 2' long, 02=,, head diameter, 0.09 r shank
rfiamater, corrosion resistant siding na l; the fasteners shall be spaced at6" O.C. at panel edges
and intermediate studs; the fasteners shall be driven through the SW thick] 5 py APA rated
pywood sheathing into wood studs located at 16" O.C.
• Fasteners shall have a minimum edge distance of 318" and a minimum clearance of 2" from
comers.
HARDIEPANEL, CEMPANEL, PREVAIL PANEL
INSTAU.A-nCiN DETAILS WOOD STUD CONSTRUCTION
James Hardie Building Products, Inc.
lo301 Elm Avenue
Fontana, CA 02337
A I I PNLrPL1hSOFF
Creator E. Gonzales sale IM=1'-0° I Datn.4/2412013 Ialiesr 10F12
UCT RENEWED
plying With the Florida
I Code
o. 17-0406.06
PRODUCT REVISED
as eomplying with the Florida
Building Coco
Boa -No. 17-0821.21
FxPlmtron Dgde 0510112022
BY
Mlam ro oat contfol
11
Nalls at 18 O.C. (typ.)
Va" MiNmum Edge gistance
60.$ Sheathingfastenar, as described in
Note 1
�\ Panel fastener, as described in
Note 2
HardiePanel, Cempanel,
Prevail Panel Siding
Water-rosislve barrier per
Florida 00ding Code Section
14042
518" thick] 5 ply APA rated
plywood sheathing fastened In
accordance with Florida Building
Code Section 2322.3
2" X 4" S-P-F Wood Studs
The wall and soft frames are to be designed
by the Architect or Engineer of Record In
oompliance will the Florida Building Code.
SEE PgCDU-r-T-9 � Qll
HarddsPanem. Cempa em. &
DFTAILA Prevail® Panel Siding materials are
/ 8°tNdc/6pIyAPArated nonasbeslasfiber-osmentProducts
tested In accordance with ASTM
plywvodsheaudnoln C1186Grade R,lypeAand meadng.
accadaneennih Florida the requirements ofthe Pkidda
Building Code Section Building Code.
23223
Wafer-resis6ha �F4-91.�I.�lS1SZNS.
Wdih length Thlckness
barrlenper Flo Florida V 6,U,10' 5118"
s Code
Sec&on 74042 pF LWNyj�F--S-SjiRE RA1M
2-X4°8-P-F installation Design Pressure
vtaod Surds Wood Studs 46 psi
T
HpnlinpanW, Impact Resistant-
��� � Cernparnel Planks Insmned over 5t8" thick / 5 ply
Pmvan p APA rated plywood sheathing
Siding
pAH�k.� �2AAl�l.EMVAA1-M 7 �+DLa �Ni?ALi271LQ —E -1t,�
• All Installation shah be done in conionsence vdhh this Notice of Acceptance, Uhe manufaeturei's
installation recommendations, and the applicable sections of the Florida Building Coda.
• Wood studs where HardiePanel, Campanel, Prevail Panel Siding will be installed shell ba
designed by an Engineer or Architect per the Florida Building Coda and the requirements of this
N.OA
(Nato 1150 thick] 5 ply APA rated plywood sheathing shall be attached to the shads In
acodrdance With Florida Sutiding Code Section 2322.3,
• The siding panels shall be Installed over Ste' thick! 6 ply APA rated plywood sheaMin9 supporter
by a minimum elf2'4(4" S-P-F vrood studs spaced a maximum of 16• Q.C.
• [Note 21 The siding panel fastener shall bet a 2' long, 02=,, head diameter, 0.09 r shank
rfiamater, corrosion resistant siding na l; the fasteners shall be spaced at6" O.C. at panel edges
and intermediate studs; the fasteners shall be driven through the SW thick] 5 py APA rated
pywood sheathing into wood studs located at 16" O.C.
• Fasteners shall have a minimum edge distance of 318" and a minimum clearance of 2" from
comers.
HARDIEPANEL, CEMPANEL, PREVAIL PANEL
INSTAU.A-nCiN DETAILS WOOD STUD CONSTRUCTION
James Hardie Building Products, Inc.
lo301 Elm Avenue
Fontana, CA 02337
A I I PNLrPL1hSOFF
Creator E. Gonzales sale IM=1'-0° I Datn.4/2412013 Ialiesr 10F12
pAH�k.� �2AAl�l.EMVAA1-M 7 �+DLa �Ni?ALi271LQ —E -1t,�
• All Installation shah be done in conionsence vdhh this Notice of Acceptance, Uhe manufaeturei's
installation recommendations, and the applicable sections of the Florida Building Coda.
• Wood studs where HardiePanel, Campanel, Prevail Panel Siding will be installed shell ba
designed by an Engineer or Architect per the Florida Building Coda and the requirements of this
N.OA
(Nato 1150 thick] 5 ply APA rated plywood sheathing shall be attached to the shads In
acodrdance With Florida Sutiding Code Section 2322.3,
• The siding panels shall be Installed over Ste' thick! 6 ply APA rated plywood sheaMin9 supporter
by a minimum elf2'4(4" S-P-F vrood studs spaced a maximum of 16• Q.C.
• [Note 21 The siding panel fastener shall bet a 2' long, 02=,, head diameter, 0.09 r shank
rfiamater, corrosion resistant siding na l; the fasteners shall be spaced at6" O.C. at panel edges
and intermediate studs; the fasteners shall be driven through the SW thick] 5 py APA rated
pywood sheathing into wood studs located at 16" O.C.
• Fasteners shall have a minimum edge distance of 318" and a minimum clearance of 2" from
comers.
HARDIEPANEL, CEMPANEL, PREVAIL PANEL
INSTAU.A-nCiN DETAILS WOOD STUD CONSTRUCTION
James Hardie Building Products, Inc.
lo301 Elm Avenue
Fontana, CA 02337
A I I PNLrPL1hSOFF
Creator E. Gonzales sale IM=1'-0° I Datn.4/2412013 Ialiesr 10F12
I
Fastener Spacing per Florida
Building Code.Saction 2322.3
PRODUCT REVISED
oa com ngg, thfh•Florldn
aulldlog a
NOA-No. 17.0821.21
explrouonp p0610'112022
•tllenuctRevfsFn Fastener Soong per Florida I•
fomw7id il6fncilw:�+ Building Code Section2322.3
-'a' 2Y
Pmdm L I I • frdd/�� ,
fl
I ; • • I ,tiff
PRODUC[RHVLSFD• PRODUCT RENEWED I �f
we wM��• as complying with the Florida
•� 1f'�Building Code
I ` ,
_ ..17 NOA-No. 17-0406.06 • I
Ecplmtlon e0510112022
nrn.ne FtodadCmb'A By I•I �'�dF :FGO
Mlaml- a duct Centro '•"
� I ---sS�oNa'.
i f;g w-13
• • NOMINAL 2" X 4" S•P•F WOOD STUDS 16" O.C. FASTENED
WITH 3.1/2.16d COMMON NAILS (2 PER TOP AND
BOTTOM CONNECTION)
• THE WALLAND SOFFIT FRAMES ARE TO BE DESIGNED
BY THE ARCHITECT OR ENGINEER OF RECORD IN
COMPLIANCE WITH THE FLORIDA BUILDING CODE
_EOMJINAL 518" THICK / 5 PLY APA RATED PLYWOOD
SHEATHING FASTENED IN ACCORDANCE WITH FLORIDA
BUILDNG CODE SECTION 2322.3
PLA-LnM
• THE PANEL 1S FASTENED WTH T LONG, 0,223" HEAD
DIAMETER, D.0921' SHANK DIAMETER, CORROSION
RESISTANT SIDING NAILS, PLACE NAILS S" O.C. AT
PANEL EDGES AND INTERMEDIATE STUDS
Cladding
Framing
Sheathing
r,
FOR METALAND WOOD STUDS, PROVISIONS FOR DIAPFIRAGMACTION AND GRAVITY LOAD ARE
NOT PART OF THIS APPROVAL (MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS)
HARDIEPANEL, CEMPANEL, PREVAIL PANEL
INSTALLATION DETAILS WOOD STUD CONSTRUCTION
James Hardle Building Products, Inc,
10901 Elm Avenue
Fontana, CA 92337
Fax909,421.0634 A I I PNL•PLK-SOFF I 1
Creator., E. Gonzales 6fe 1. M T4, 1 • Dalct4lZC013 1611m 20F 12
i
PRODUCT REVISED
as comp)ying with the Florida.
aunding Code
NOA-No. 17-0821.21
WALL LENOTI 1
Stud spacing at 16" O.C.
e•4--1 1- I _I
i I
i•I
� 8EV
�
FlottrM I
111111�:
I
•.Ord'•"'
.l
��
Co
troy
Jy.v7
\`\tt\
:
Nt).
l y90'
STATE
rro
•• c4 RIQ
J)JUA .la
PRODUCT RENEWED
as complying with the Florida
Building Coda
NOA-No. 17-0406.06
3/8" Mlnlmum Edge Distance NWs ate" O.C. (typ,)
Sheathing fastener, as
described in Note 1.
Panel fastener, as described In
Note 2
HardiePeneldl Siding
Water-reslin ve border per
Florida Building Code Section
1404,2
518" thick /5 ply APA rated
plywood sheathing fastened
to metal studs as described
in Note 1.
12022 209a, 3-518"X 1.518" Metal Catud
The wall and soffit fraihes are to be designed
on rot by the Architect or Engineer of Reoond In
compliance with the Florida Building Code.
SEE
DE7AILA
rT
P$Q2UGTT SIEION
Hard aPanelS. Cempanela, & PfeVEAD
Panel Siding materlals are nonashestos
516'thicklS plyAPA rated fiber -cement products tested In
plywood sheathingfasta66d accordancewlthASTMC11186GradeII,
to metalatuds as dasrxhad Type Aand meeting the requirements of
In Note the Florida Building Coda.
`
P9I`tF"L.AINLENSAON�
!� Z;
walenresrstive Vvidth Length Thickness
bsrderperAcrlda 4' 10' S/1ri"
' k
qutdfng Code
Section 140a2 R.>zS_I_QN�.13b9,TUH 14yrJJ�O
�� \�x
1
Installation Design Pressure
20ga, -.Wa" X 1-1a" Metal Studs -104 psr
G�yC'f
K\ Mete) Cstud
t�
rplll
\ HerdlaPal,
stalstant—
PanelImpac
ledover
ve
\\Campenel, Panel Installed aver&8"thick/5 ply
a5G'QT101J1i•@
Prevail Panel APA rated plywood sheathing
Wins
• ' A4 Installation shall be done In conformance with this Notice of Acceptance, the manufacturers
Installation recommendations, and the applicable sections of the Pladda Bullding Code.
• Metal studs where HordiePanel, .Cempanel, Prevail Panel Siding will be installed shall be
designed by an Engineer or Architect per the Florlda Building Code and the requirements of this
N.OA
• [Note 115/8" Not 15 pyAPA rated plywood sheathing shall be attached to metal studs at6"oc
at panel edges and all Intermediate supports using a No.6-18, 0.315" head diameterx 1-1/4' long
bugle head screw sheathing • The siding panels shell be installed over 5/8" thick/ B ply APA rated pywoe,d
supported by a minimum 20ga, Nominat3.5l8" X 1-518" Metal C-studsspaeed a mwdmum of 16"
O.C.
• tNtice 21 The siding panel fastener shall be a minimum No. 8-18, 0.816" head diameter X 1-5/8"
long* ribbed bugle head screw (*or screw shall have at least 3 full threads penetrating metal
framing); the fasteners shall be spaced at G' O.C. at panel edges and Intermediate studs; the
fasteners shall be driven through the B/0" thick / 5 ply APA rated plywood sheathing Into metal
studs located at 16" O.C.
• Fasteners shall have a minimum edge distance of 3/8" and a minimum clearance of T from
comers.
HARDiEPANEL,CEMPANEL PREVAIL PANEL
INSTALLATION DETAILS METALSTUO CONSTRUCTION
James Hardie Building Products, Ina
10901 Elm Avenue
Fontana, CA=7
PNL-PLKSOFF
Creator; E. Gonzales IMAL11' 112" a T-U' I Data. 4/24/2013 IsHe5r 3 OF 12
ft.00iI1.
�I
I
PRODUCT RENEWED
as eolnpl Ing with the Florida
Building Code
NOA-No. 17-0406.06
T
s.00in.
PRODUCrBEMLSM
t*ma*ft WhhibcRmma
Fesr
s�j
I I
II
I.I
II
,I
alv� NOMINAL 20 GAUGE _
~ FASTENED WITH 51W WAF RI4/8HEAD CREWS (2 PER TOP
AND BOTTOM CONNECTION)
• THE WALL AND SOFFIT FRAMES ARE TO BE DESIGNED
BY THE ARCHITECT OR ENGINEER OF RECORD IN
COMPLIANCE WITH THE FLORIDA BUILDING CODE
NOMINAL SHFQ
• NOMINAL 518" THICK ! 6 PLY APA RATED PLYWOOD
SHEATHING TO METAL STUDS AT G' OC AT PANEL
EDGES AND ALL INTERMEDIATE SUPPORTS USING A
NO.S-ia, 0.316' HEAD DIAMETER X 1-114 LONG BUGLE
HEAD SCREW
AI Ad1�JNA
• THE PANEL IH FASTENED WITH NO. SAG, 0.31W HEAD
DIAMETERX 1-5I8' LONG CORROSION RESISTANT
RIBBED BUGLE HEAD SCREWS (SCREW SHALL HAVE AT
LEAST 8 FULLTHIZPADS PENETRATING THE METAL '
FRAMING), PLACE SCREWS 6" O.C. AT PANEL EDGES
AND INTERMEDIATE STUDS
PRODUCT REVISBD
ao complying with t o Florida
Dulldinfl Code
Evplr®tlon
Cladding
/ Framing
Sheathng
' OriRp�snanp. y .
itrr4lDUA
0, 121
ZL
ZL o' S?ATE OF �:
S/0NA1-+�✓
FOR METAL AND WOOD STUDs, PROVISIONS FOR DIAPHRAGM ACTION AND GRAVITY LOA13
NOT PART OF THIS APPROVAL (MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS) £
HARDIEPANEL, CEMPANEL, PREVAIL PANEL
INSTALLATION DETAIIS METAL STUD CONSTRUCTION
James Hardie Building Products, Ina.
10g01 Elm Avenue
Fontana, CA02337
-nane; we-ww��� I PNL-PLK'BOFF
Fa(go 427-063h _ A — —
Creator I- Gonzales Gonzales ISW1"01'-0" Date:4124=13 _ Is1 W 4OF 12
i
PRODUC'
as compli
aullding Cci
Non_NO. 17.0821.21
PRODUCT RENEWED
as complying with the Florida
Building Code
NOA-No. 17-0406.06
Eupiration WteOS101/2022
^=t 5he4iing fastener, as
(r described In Note 1
siding fastener, as
described in Note
HardiePiank,
Cemplank, Prevail
Lap Siding
Water -resistive barrier
per Florida Building
Code Secti 1404.2.
518" thick 15 ply APA rated
plywood sheathing fastened
,in accordance with Flodda
Building Code Section
2322.3
2" X 4" S-P-F Wood studs
The wail and soffit frames are to be designed
by the ArchRector Engineer of Record In
cemogance with the Florida Bulkiing Code.
SEB
pROD11GT DESCRt;77JSi.L
ETAILA
NerdlaPlani Cempiank®, &
Prevall® Plank lap Siding materials
5I8"thlck16APA
are nonashestnsflbarucemerd
ply
producta tested In accordance vMh
rated plywood
ASTM C1186 Grade It, Type A and
sheathing In
meeting the requirements of the
aoeardanmwith
Florida Building Code.
Flodda augding code
Secgan 2322.3
?AN iFg,AJI191=L`iS.LobLq
water4oswIve
Width Let,0 Thicknessharder
per Flodda
59.1PZ" 12' 6/16'
Building Coda
escuon 14042
VX4°sP•F
Wood Studs
Installation DesignPre?sure
Wood Studs .92 psi
Lap siding
Impact Resistant —
Planks Installed over WV' thick15ply
1-1/4• tall X ails, APA rated plywood sheathing
D1
thick slanei%strip
ii/iJ_'�IVI�,—r'J+P1CW!L`rLbJJ6�.cvt..o,=u+ui,—..u».=
• All Installaion shall be done In conformance with this Notice of Acceptance, the manufacture's
Installation recommendations, and the applicable sections of the Florida Building Coda.
• Wood studs where HardIpPlank, Cemplank, Praveil Up Siding will be Installed shall be designed by an
Engineer or Architect per the Florida Building Code and the requirements of thia N.O.A.
• [Note 1151W thick 15 ply APA rated plywood sheathing shall be stleci to the stude In accordance _
with Flodda Building Cods Section 2322.3,
• Planks shell be applied horizontally commencing *am the bottom course of the wall with 141V wide
laps at the top of the plank such that the exposure area of each plank is 5 8-`IM'v0Mcsny.
• L,Note 21 The siding fastener shall be a 2-112" long, 0.M' head diameter, 0.092' sheok diameter,
corrosion -resistant siding nag; The siding Is fastened 58-1/4" O.C. vertically and lEsheathing,
I horizontally:
fasteners are driven Into wood studs through SM" thlgc / 8 ply APA rated plywood
ng, fa
are placed In the overlapping area approximately 8/4" from the bottom edge of the Overlapping plank
• Vertical Joints shall be placed over studs.
• The planks shall be installed over 5/8" thick / 8 ply APA rated plywood sheathing supported by a
minimum of 2"X4, &P-P wood studs spaced a maximum of 16" O.C.
• Fasteners shag have a minimum edge distance of 9/8".
HARDIEPLANK, CEMPLANX, PREVAIL LAP SIDING
INSTALLATION DETAILS WOOD STUD CONSTRUCTION
James Hardie Building Products, Inc,
iolioi elm Avenue
Fontana, CA 92337
PMIrPLKSOFF
Creator;l- Gonzales sous 1P2"=1I.V I- Date:4/24201a I6HMT GOP12
REV
Fastener Spacing pet
Building Code Section
PRODUCT REVISED
as camp ryln with tee Florida
Building Code
NOA-No. 17-0821.21
PRODUCT RENEWED
as complying with the Kladdn
Building Code
0.761n _�..1"'__.
NOA-No. 17-0406.06
Expiration Dot e05/01/2D22
Oy
Miami—WaftMiuml-Waft Product Codtrol
ERAJRM
• NOMINAL 2" X 4° S-P-F WOOD STUDS IW O.C. FASTENED
WfrH 3.1/2P 18d COMMON NAILS (2 PER TOP AND '
BOTTOM CONNECTION)
• THE WALL AND SOFFIT FRAMES ARE TO BE 09BIGNED
BY THE ARCHITECT OR ENGINEER OF RECORD IN
COMPLIANCE WITH THE FLORIDA BUILDING CODE
SHRE—kiljm.
• NOMINAL SWTHICK/ S PLY APA RATED PLYWOOD
SHEATHING'FASTENED IN ACCORDANCE WITH FLORIDA
BUILDING CODE SECTION 2322.3
PLADA1.NS3
• PLANKS,DVGRLAP 1.1W
• THE EXPOSURE IS s8.1/4"
• THE PLANKS ARE FACE NAILED WITH 2-VT LONG, 0.223•
HEAD DiAMETFR, 0.092'SHANK DIAMETER, CORROSION
RESISTANT SIDING NAILS; PLACED 3/4' UP FROM THE
BOTTOM EDGE OF THE PLANKAT EACH STUD LOCATIOt
la
I I'
Faatanors,e ing perFlodds
Building Code Seetlon 2322.3 .�
Cladding
Framing
Sheathing
I
1111,,1 i. I/1 2
PR@+pUL7IIEyiSPD ,ltlt • • S t
Ip 000,plyiagwithdj Flnl � •I �1 �- Y
.a .Na otz . No. 121 `
a STATE OF
1;y rklMldnd
FOR METAL AND WOOD STUDS. PROVISIONS FOR DIAPHRAGM ACTION AND�/LOAD ARE
NOT PART OF THIS APPROVAL (MUSTPROVIDE ALTERNATE PROVISIONS FOR THESE LOADS)
HARDIEPLANK, CEIt4PLANK, PREVAIL LAP SIDING
114SFALLATION DFTAILS WOOD STUD CONSTRUCTION
James Hardle Building Products, Inc.
10S01 Elm Avenue
Fontana, CA 92337
Fox 9D 7-0894 A PNL-PLKSOFF I 1
Greater. E. Gonzales ISCME 1•=14• 1 Dote; 412412018 IsIrm a OF 12
AAi ' '. Cot
REVISED 314' M•mimum Edge Distance Nails At
with the horde
0
17-0821.21 '
e� 05/01/2022 D�•AI
°�' Sheathing Fastener, as
described in Note 1
PRtaDIJCt' 52D
gomypili,q hA OK Fla"
w400prao� 5- �)-L4 Siding fastener, as
described in Note 2
MLa1 Glared
1 HardlAPlank,
i Cemplank,
Prevail Lap Siding
'�
a( / Water-ras(silve
barrier per Plorlds
BtIDdtng Code
Skilon 14042
5/8" thick /6 ply APA rated
PRODUCT RENEWED
plywood sheathing fastened to
as complying with the Florida
metal studs as described in
Building Code
Note 1
NDA-No. 17-0406.06
Eupinrtron 0510112D22
20ga, 3•Sl8"X 1.5/8" Metal C $Wd
The wag and soffitfiamez are to be designed
By
by the Architect or Engineer of Pecord In
Miami-Dd d robce Control I
compliance with the Roilda Building Code.
SEE SDI-01D11 IP (ON
DETAILA HardkePlank®, CemplankS, and
51ewhickl5 plyaPA PrevaiM Plank Lap Siding materials
-- _•-- --•— i false plywood are nonasbestos fiber -cement
sheathing fastened products tested In accordance with
to metal studs
r I ASTM C118fi Grade II, Type A and
irk i Nutt
meeting the requirements of the
•• ryu ••'l, r drsalbed In Note 1 Florida Budding Code,
tr11� i W � Wale°resistive
` _ 6anierper Flodda gL�IC DI J
CC ; Building rode: VJIdth Length Thickness
Z Section 1404.2 s 9-1W 12' 6/18"
* 2pga, 3.Y10" X 1�678• g1GN pRE?48URE RATtj
• - HaralC-sWd
`�'Gxr F ` Installation Design Pressure
Ha rdlePlenk Metal Studs -92 put
+ tc mplank, Provall
cgs •.•.....••: �? . f _,r_ Lap 6ltpng Impact Resistant -
Planks Installed oyer 518" thick 16 ply
'°� i th(ek sta tersu p APA rated plywood sheathing
HAR��LC+NK�CE�'IP1J�J��C.P��VAf I�P�[C�O INBTALtAT10-pl DETAIIS
• All installation shall be dope in conformance with this Notice of Acceptance, the manufacturers installation
recommendations, and the applicable sections of tiro Florida Building Code.
• Metal studs where HardlePlank, CemplariK Prevall Lap Slding vdll be installed shall be designed by an
Engineer or Ar&toct per the Florida Building Code and the requirements of this N.O.A.
• ' [Note 1] 5/e" thick 15 ply APA rated plywood sheathing shall be attached to metal studs at 6"0o at panel
edges and all Intennedlate supports using a No.8-18, D.315° head diameter x 1-1/4' long bugle head screw
+ Planks shall be applied horizontally commencing from the bottom oourso of the wall with 1-lie wide laps at
the top of the plank such that the exposure area of each plank is s8-1/4" vertically.
• [Note 21 The ald'mg fastener shall be a minlrnum No. 8.18, 0.315" head diameter X 2- W long' bugle head
screw over metal studs ("or screw shall have at least 3 full threads penetrating metal framing); The siding is
fastened 5 &114" O.C. vertically and 18° O.C. horizontally; fastener; are driven Into metal shads through 518"
thick / 5 ply APA rated plywood shoathing,'fastenom are placed in the overlapping area approximately 3/4'
from the bottom edge of the overlapping plank.
Vertical joints shall be placed over studs.
The planks shall be Instalfed over 6/8" thick / 5 ply APA rated plyvrood aheathing supported by a minimum
loge, Nominal3-SWX 1.5/8" Metal 4-studs spaced a maxim of 16" O.C.
Fasteners shall have a minimum edga distance of 3/8",
HARDIEPLANK, CEM PLANK, PREVAIL LAP SIDING
INSTALLATION DETAILS METAL STUD CONSTRUCRON
James Hardie Building Products, Ina.
10s01 Elm Avenue
Fontana, CA 023V
PNL-PLK SOFF
^Creator. E. Gonulas IWALE 1/2'u 1'-0" I Date.412412M ISHW 70P12
PRODUCT REVISED
as comp)yyingg with the Florida
Building Code
NOA-No. 17-0021.21
Expirutlon pets 0510112022
6.001n.
I•I -
PRODUCT RENEWED
aB complying with the Florida
Building Dodo
NOA-No. 17-0406.06
Expiration D to0510112022 ,
By
Miam Product Control
I '-JliNdiilKY P/IX
58.251n.
• NOM�20 GAUGE 3.5I6" X 1-SB" STEEL STUDS 18"
O.C. FASTENED WITH SIB" LONG RIBBED BUGLE BEAD
SCREWS (2 PER TOP AND BOTTOM CONNECTION)
• THE WALLAND SOFFIT FRAMES ARE TO 8E DESIGNED
BY THE ARCHITECT OR ENGINEER OF RECORD IN
COMPLIANCE WITH THE FLORIDA BUILDING CODE
AEATHING
• NOMINAL 618" THICK 15 PLY APA RATED PLYWOOD
SHEATHING TO METAL STUDS AT 8" OC AT -PANEL
EDGES AND ALL INTERMEDIATE SUPPORTS USING A
NO.8-18, 0.315" HEAD OIAMETERX 1-1l4' LONG BUGLE
HEAOSCREW
PLANKS OVERLAP 1-114"
• THE EXPOSURE IS 5 8-114"
• THE PLANKS ARE FASTENED WFFH N0.8-18, 0.31V
HEAD DIAMETER X 2-114' LONG CORROSION -
RESISTANT RIBBED BUGLE HEAD SCR (SCREW
SHALL HAVE AT LEAST FULL THREADS
PENETRATING THE METAL FRAMING), PLACED SW UP
FROM THE BOTTOM EDGE OF THE PLANK AT EACH
Cladding
Framing
Shealhlog
.I
LSPD • I
t
t We Fib"
tiit
t
ow
FOR METALAND WOOD STUDS, PROVISIONS FOR OIAPHRAOM AMION AND GRAVITY LOAD ARE
NOT PART OF THIS APPROVAL (MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS)
HARDIEPLANK, CEMPLANK, PREVAIL LAP SIDING
INSTALLATION DETAILS METAL STUD CONSTRUCTION
James Hardie Building Produots,.ino.
10301 Elm Avenue
Fontana, CA 92337
s FEW No OWauo pav
A I PNL-PLKSOFF 1
Creator. I- Gonzales Ise. -Is illy 1'-0' I Date 4k412013 ISHEET a OF 12
WALL
REVISED
i with the Florida
Or
r ILIA
NEWED
as complying with the Florida
Building Code
NDu-No. 17-0406.06
Expiration
Stud
et1fr'O.C.
SEE
MopllSiLi1� G111112—MI`S
DETATLA
HardieBofiObi&Cemsofhttlnatedalsare
-
nonasbestos fiber -cement products tested In
accordance with ASTM C1186 Grade IL Type A
1
and meeting the requirements of the Florida
Building Code.
Width Length Thickness
Wood Studs
4' 8' 114"
' .� •� •� p.�iI�.ALP_8�.65ugE_RA77Cid
HardleSoftt, Insiellatlon Design Pressure
i- i j•i ;I i Comsoret -Wood Studs -7D Pat
i I! Ii i rrll/Iplii�ii�4
dA
Neils 'at 4"oA. (typ.j UWuCi'REVISED m onvcrs>vum ���`
318"Minimum Edge Distance oaslgyteavXAliufloriA. E� �mg.ri,hdmF6nrldn N0. 4 21• w`
D1Swmacede -0t AcmM:roo�r o�rr,a y
SOW Dole
� ♦ Pl
o `•. STATE OF L
s' F
t�P `
ent�xxtFrodeq S R10'C���f,
�OPJ4 � �i
k1.A.t3R1R50�F_LT�CEMJ,"zOFF1Ip1j,NFJ.JNS7LLLATION DE'Y,yy.,'q """""'
Soffftfestener, as • All Installation shall be done, In conformance with this Notice ofAcceptence, the manufacturer's
described In Note 1 Installation recommendations, and the applicable sections of the Florida Building Code.
Wood studs where HardleSafit, Cemsoffit will be Installed shall be designed by an Engineer or
Architect per the Florida Building Code and the requirements otthls N.O.A.
- HardleSofit, Cemsoffit The soffit shall be Installed over minimum 2"X4" 3-P.Fvrood studs spaced a maximum of 16" O.C.
[Note 11 The sofrd fastener shah be a 2" king, 0.223" head diameter, 0.092" stank diameter,
corrosion resistant siding hall; the fasteners shall be spaced at 4" O.C. at panel edges and
intermediate studs; the fasteners shell be driven Into wood studs load et i6".O:C.
Fasteners shall have a minimum edge distenoe of 316" and a minimum clearance of2" from comers.
HARDiUOFFIT, CEMSOFFIT PANEL
INSTALLATION DETAILS WOOD STUD CONSTRUCTION
Minimum 2" X 4" S-P-F Wood Studs James Handle Building Products, Ina
The wall and soffit frames are to be o 10901 Elm Avenue
designed by the Architect or Fontana, CA 92397
Engineer of Record in compliance Phone: D9356.6300 sas PSC61 Na o�wuc
with the Florida Building Code. F 09 9-027 A PNL-PLJGSOFF
Creator. I- Gonzales ::jSALE I/V-1'•e• Date: 412=13 sheer a OF 12
PRODUCT REVISED PRODUCT RENEWED
as eompplvina with the Florida • . as complying with the Florida
EYiltlln Codda Building Code
NOA-No. 17-0821.21 NOA-No. 17-0406.06
expimtlon Do 006/01/2022 Expiration Onto05101/2022
Dy By
MIomL a Protluat Contro
• 4.00ln.1 Miam1- Product Control /
a pRabutT REVISER PRODUCrDctrtc9T
a 6tiHta eCaAe 4dae dtori4r - Bml�' COd• dmFLori@a
Aoo.Pww?4u -0 weapleaarNo 8311,07
6y gy
Afiomi Podrsl Camel . Mi ' Uado 'r04uct Control
P M—Ms
NOMINAL 2° X4` S-P-F WOOb SPUDS 16" O.C. FASTENED
WITH 3-1/2' 16d COMMON NAILS (2 PER TOP AND BOTTOM
CONNECTION) '
THE WALL AND SOFFIT FRAMES ARE TO BE DESIGNED BY
THE ARCHITECT 0R ENGINEER OF RECORD IN COMPLIANCE
WITH THE FLORIDA BUILDING CODE
Sd,90�if�C '
THE SOFFIT IS FASTENED WITH 2' LONG, 0223" HEAD
DIAMETER, 0.0S2" SHANK DIAMETER, CORROSION
RESISTANT SIDING NAILS, PLACE NAILS 4" O.C. AT PANEL
EDGES AND INTERMEDIATE STUDS
4
Cladding
Framing
No. V121
STATE OF
M
FOR METAL AND WOOD STUDS, PROVISIONS FOR DIAPHRAGM ACTION AND GRAVITY LOAD ARE
NOT PART OF THIS APPROVAL (MUST PROVIDE ALTERNATE PROVISIONS FOR THESE LOADS)
HARDIESOFFIT, CEMSOFFIT PANEL
INSTALLATION DETAILS WOOD STUD CONSTRUCTION
James Hardie Balding Products, Ina
10201 Elm Avenue
Fontana, CA02W
Fwc90S427-0834 j A I I PHL-PLK.SOFF 1 1
Creator. E. Gonzales sna.s 1°=i'0• 09ir. 4/2412013 SHEEP 10 OF12
WALL
PRODUCT REVISED
as cam tyI g, with the Florida
Bulidlhs Code
NUA-No. 17-0821,21
�a WALL L5NGTI 1 3C6 ERID _U-Cor-D_F.RMIEMPIS!
Stud Spacing at Id" HatdleSoffitO & Cemsofli* materials
O.C. DEIAILA
Bed are nonasbestos fiber -cement products
tested In accordance wdhASTM 01166
-- T Grade 11, Type and meeting the
requirements ofthe Florida Buildin
IIPRODUII IICT RENEWED
1• � T-
ing complying with the Florida .I
• ,
Bullding Code OPYEL�Iw"t •� �NDA-No. 77-0406.06 , e� crud 4 Length Thl Y"ass
•Expiration Da 05101/2022 i
I.i J I Hardie5oirtt, P_i~SIGN ER -- UBURATItLG .
I I i I By e' Cemsoint Installation Design Pressure
.i 1.1 •�Mlaral-D d roductlControl
Metal studs
Is
B j ,�BScTfl�ti^B PttO11UCtItbvl3[p �1r
J Nails at en O.0P �Dt1C{'
. (typ.) WEtaida M OD"1 Ayim'Aft nilodda %,, Na....- SF -`
318"Minimum Edge Distance apt Coft R"IA / : -0 1Z r
iSTATE OF
mill l'ndaet f.SieUd' to adepredeelCantrol '_"`te�,s/��RID N `��tt
Soffit fastener, as
described In Note 1
Hardiesoffit, Cemsoffit
ki{�fj)1_(Fa�OEEIT�ScFh13. _j PANELI&BTALLATIDNDETAIL$
All Installation shall be done In conformance wtlhthts Notice o}Arxeptan6d!tHe'M>3{lufacturer's
Installation recommendations, and the applicable sections of the Florida Building Code.
Metal sfuda where HardleSoffit, Cemsofflt WIII be Installed shall be designed by on Engineer or
Amhtteot per the Flodda Bugding Code and the requirements of this N.O.A.
The soffit shall be installed over minimum 209a, Nominal $.5/8"X 1-5/8" Metal C eiuds spaced
a maximum at IV' D.C.
" ENote, 11 The soffit fastener shall be a minimum No. 848, 0.315" head diameter X 1-114' long"
ribbed bugle head screw (*or screw shall hovel at least 3 full threads penetrating metal •
Itaming);the fasteners shall be spaced at 8" O.C. at panel edgos and Intermediate studs; the
fasteners shall be driven Into metal studs loomed at 16" C.C.
Fasteners shall have a minimum edge distance of 3/8" and a minimum clearance of 2" from
comers.
• HARDIESOFFIT, CEMSOFFlT PANEL
i INSTALLATION DETAILS METAL STUD CONSTRUCTION
James Hardie Bullding Products, Inc.
20ga, 3-518141.516" Metal C-stud 10901 Elm Avenue
The wall and oof5t frames are to beWF--Gon=z,1as
Fontana, CA 92337
designed by the Architect or Engineer :< rscm+un D%% aeI
of Record In compliance withthe A PNL-PLKFlodda Bullding Coda, tu. 12`=1W" Dale:liN412013 ISMST 11 OF 12
(r.0(fln
FBODUC{• IRMSED
PRODUCT RENEWED 'sCOMO Nmlhc•vtntidt
as complying with the Florida
Building Code
NOA-No. 17-0406.06 `
• Expiration 05101/2022 yyy
Mk E e�ixTv4�.nmW
By
Miami-D d Product Control
Cladding
Forming
NOA-No. 1
17-0821.21
Expiration
to 05/0112022
By
Miami -Gaffe
Product Contra
21
`
�10• 2
l'• t�' 1
rr
lLliSllJl)iK -� w�/i�••-
NOMINAL 20 OAUGE 3.5/fi'• X 1-5/8" STLS1'U0916" O.C.
FASTENED WITH 6!8" WAFER HEAD SOREWS (2 PER TOP FOR METAL AND WOOD STUDS, PROVISIONS FOR DIAPHRAGM ACTION AND GRAVITY LOAD ARE
AND BOTTOM CONNECTION) • NOT PART OF THIS APPROVAL (MUST PROVIDEALTERNATE PROVISIONSFOR THESELO"
+ THE WALL AND SOFFIT FRAMES ARE TO BE DESIGNED • • '
BY THE ARCHITECT OR ENGINEER OF RECORD IN
COMPLIANCE WITH THE FLORIDA BUILDING CODE
c� g1Zb�N HARDIFSOFFIT, CEMSOFFTf PANEL
THE SOFFIT IS FASTENED WITH NO, "8, 0.315" HEAD INSTALLATION DETAILS METAL STUD CONSTRUCTION
DIAMETER X'I-1/4 • LONG CORROSION RESISTANT RIBBED
BUGLE HEAD SCREWS (SCREW SHALL HAVE AT LEAST 3 James Hardie Building Produo* Inc.
FULL THREADS PENETRATING THE METAL FRAMING), PLACE 10901 EIm Avenua
SCREWS G' O,C. AT PANEL EDGES AND INTERMEDIATE m Fontana, CA 92337
STUDS
V
Creator,E.Gomales �scus 1"=i!e, I Dete14/24=13 I6HH6( 12OF12