HomeMy WebLinkAboutSCREEN ROOM PLANSTABLE OF ROOF BEAMS, COLUMNS, PURLINS AND GIRTS• }' SPECIFICATION NOTES AND DESIGN PARAMETERS: MANSARD SCREEN ROOM THIS SCREEN ENCLOSURE MEETS THE FLORIDA BUILDING CODE.FOR A HEIGHT 12'-0", 145 MPH , EXP. •B• 1 THIS DESIGN COMPLIES WITH THE GUIDELINES DEFINED IN CHAPTERS 16 & 20 OF THE 2017 FLORIDA BUILDING CODE, SIXTH DWG. # JRL-2019-01 1, REV. 0 WIND SPEED. THE ITEMS BELOW ARE BASED ON SIMULTANEOUS LOADING AS DEFINED IN THE FLORIDA EDITION, BUILDING, USING THE ALLOWABLE STRESS DESIGN PRESSURES LISTED IN TABLE 2002.4 AND TABLE 2002.4A. THE BUILDING CODE (FBC), CHAPTERS 16 AND 20, AND OTHER REFERENCES SUCH AS ALUMINUM ASSOCIATION AAF STANDARDS OF iHEI'GUIDELINES TO ALUMINUM CONSTRUCTION IN HIGH WIND AREAS" FOR THE TABLES ARE APPLIED. February 4, 2019 OF FLORIDA (AAF) "GUIDELINES TO ALUMINUM CONSTRUCTION IN HIGH WIND AREAS". STRUCTURAL A DESIGN BASICS: THIS SCREEN ENCLOSURE IS A RISK CATEGORY I STRUCTURE. HEIGHT 12'-0", 145 MPH, EXP.'B' VALUES FOR EXTRUDED ALLOY 6005T5 ARE TAKEN FROM THE ALUMINUM DESIGN MANUAL 2015 EDITION. B THE BUILDING CLASSIFICATION RISK CATEGORIES ARE FROM FBC, TABLE 1604.5 AND AREA LOCATION WIND SPEED PER SHEET 1 OF 4 i FBC FIGURE 1609C BUILDING CLASSIFICATION PER TABLE 27.2-1, ASCE 7-10. - TABLE 1 _ MAIN MEMBER. SCHEDULE MEMBER MARK SIZE IMATERIALI TYPE I THICKNESS LENGTH DESIGN BASIS b x t I ALLOY --I W"F- ROOF BEAM # 1 COLUMN # 1 COLUMN # 2 PURLIN # 1 CHAIR RAIL # 1 CHAIR RAIL # 2 CHAIR RAIL # 3 CHAIR RAIL # 4 EAVE RAIL # 1 EAVE RAIL # 2 WIND BRACING RI 2x8 ALUM SMB 1 0.072 0.224 28'-0" CALCULATION Cl 2x4H ALUM HOLLOW 0.050 0.050 9'-0" I CALCULATION C2 2x4H ALUM HOLLOW 0.050 0.050 8'-10" 1 CALCULATION P1 2x3 ALUM HOLLOW 0.050 0.050 NA #200 CALC. _ CR1 2x3.9 ALUM HOLLOW 0.090 0.090 12'-0- CALCULATION CR2 2x3-9 ALUM HOLLOW 0.090 0,090 13'-9" CALCULATION CR3 2x3-7 ALUM HOLLOW 0.070 0.070 10'-9" CALCULATION CR4 2x3-7 ALUM HOLLOW 0.070 0.070 9'-0" CALCULATION ER1 2x2 ALUM HOLLOW 0.046 0.046 V-9.5" CALCULATION ER2 2z2 ALUM I HOLLOW 0.046 0.046 14'-7" CALCULATION WB 1 2x2-12 1 ALUM .HOLLOW 0.125.. 0.125 NA CALCULATION 1 _ C DESIGN PRESSURE: (18114),W W @ 25.52 PSF, LW @ 18.92 PSF; SCREEN ROOF @ 7.48 PSF PER TABLE 2002.4. GENERIC DESIGN DATA D MAXIMUM HEIGHT: HEIGHTS HIGHER THAN LISTED ABOVE REQUIRE SITE -SPECIFIC DESIGN BY THE ENGINEER OF RECORD. E ALLOWABLE. DEFLECTION: L I60-MINIMUM, AS SPECIFIED IN TABLE #1604.3 OF FBC.— - HEIGHT I2'-0" 145 MPH EXP. 'B' F CONTINUOUS LOAD PATHt S PROVIDED WITHIN THE CALCULATIONS USING ALLOWABLE STRESS DESIGN PRESSURES. JRL ALUMINUM SERVICES, INC. 2 MATERIALS (UNLESS OTHERWISE SPECIFIED BY THE ENGINEER OF RECORD): 1304 NE 24 ST. A ALL EXTRUSION MATERIAL'S SHALL BE ALUMINUM ALLOY # 6005T5 OR # 6061T6; ALLOY # 6063T6 IS NOT ACCEPTABLE. JENSEN BEACH, FL 34957 ' B FASTENERS: ALUMINUM ALLOYS #2024-174 8. #7075-T6, DOUBLE CAD -PLATED STEEL, HOT -DIPPED GALVANIZED STEEL OR OFFICE (772) 529-2674 300SERIES STAINLESS STEEL IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE FOR SEPARATION OF FAX (772) 398-2997 DISSIMILAR MATERIALS AS- DEFINED IN THE FBC. HE/SHE MAY IMPLEMENT ANY OF THE MEANS LISTED IN THESE SECTIONS. ALTERNATIVES MUST BE REVIEWED AND APPROVED IN WRITING BY THE ENGINEER OF RECORD PRIOR TO ANY INSTALLATIONS UTILIZING THE SUBJECT METHODS. C SCREEN CLOTH:. SHALL BEIMNYL-COATED, WOVEN FIBERGLASS, MAXIMUM DENSITY OF 18 x 14, 58%OPEN MINIMUM. LOCATION: OTHER SCREEN DENSITY.REQUIRE ADDITIONAL ENGINEERING CONSIDERATION. D ANY CONNECTION USED, THAT IS NOT SHOWN ON THESE SHEETS, MUST MEET ALL FBC AND AAF GUIDELINES. i E MATERIAL UPGRADESI(STRONGER AND/OR HIGHER GRADE MATERIALS) CAN BE SUBSTITUTED AT ANY TIME. ADDITIONAL SITE SPECIFIC INFORMATION F A 2x2 OR A 2x3 SNAP MEMBER CAN ALWAYS REPLACE A 2x2 OR A 2x3 HOLLOW MEMBER, RESPECTIVELY. THIS SCREEN ENCLOSURES IS LOCATED IN A RESIDENTIAL COMMUNITY SOUTH OF THE GLADES CUT OFF ROAD AND G WHEREVER SCREENING OR KICKPLATES ABUTS THE HOUSE OR CONCRETE THE MEMBER USED TO SUPPORT THAT WEST OF ROUTE 951N PORT ST. LUCIE. THE ENCLOSURE HAS MANY OTHER HOUSES AROUND IT. UNDER THE ; SCREENING OR KICK PLATE•WILL BE A 1" x 2" x 0.046" O.B. OR STRONGER ALUMINUM MEMBER. EXPOSURE CATEGORIES LISTED IN SECTION 1609.4.3 OF THE FLORIDA BUILDING CODE THIS ENCLOSURE IS AN 1 HALL DOOR JAMS (DJ) SHALE BE 2" x 2" x 0.046" ALUMINUM MEMBERS OR STRONGER. EXPOSURE 13'. ACCORDING TO THE COMPUTER PROGRAM "WINDSPEED BY LOCATION", A PRODUCT OF 'APPLIED I, 1 IT IS ALWAYS ACCEPTABLE TO ADD A SCREEN DOOR AS LONG AS THE COLUMNS ARE NOT DISTURBED. TECHNOLOGY COUNCIL' THE DESIGN WIND LOAD REQUIREMENTS FOR A RISK CATEGORY I ENCLOSURE IN THIS -I _ NAME: BATRA RESIDENCE ADDRESS: ' 8020 PLANTATION LAKES DRIVE CITY/STATE: PORT ST. LUCIE FL 34986 COUNTY: ST. LUCIE LOCATION IS DICTATED BY A WIND SPEED OF 145 MPH. HENCE, THE DESIGN PARAMETERS BEING USED HERE ARE 145, 3 ALL HOUSE FASCIA DETAILS; BOLTING OR SCREW SELECTIONS, BEAM SPLICE DETAILS, DIAGONAL "K" BRACING DETAILS, COLUMN TO BEAM DETAILS; STRUCTURAL GUTTER DETAILS, WALL AND FASCIA DETAILS, CORNER ANCHOR DETAILS, .ROOF BRACING DETAIL'S, EAVE BRACING DETAILS, ETC., IF NOT EXPLICITLY OUTLINED ON THIS SPECIFICATION, SHALL BE IN ACCORDANCE WITHITHE LATEST FBC EDITION, INCLUDING THE AAF. ALL INTERNAL CONNECTIONS SHALL MEET THE FBC (AAF) AND THERE INSTALLATION ARE THE RESPONSIBILITY OF THE CONTRACTOR. i, 4 THE LOCATION OF ALL�'`K" BRACING, WIND BRACING, EAVE RAILS AND CHAIR RAILS, ALONG WITH ANY DESIGN ABNORMALITY, ARE SHOWN AND/OR LISTED ON SHEET 2, THE "SITE SPECIFIC DRAWING". ' 5 ALL STRUCTURES ERE�TED ON CONCRETE SLABS AND / OR FOOTERS SHALL BE CALCULATED FOR SUFFICIENT HOLD DOWN CAPABILITY TO MEET THE CODE REQUIREMENTS. ALSO, ALL TAPCONS, WEDGE ANCHORS (OR EQUAL) SHALL BE 24" O.C. (MIN.), BE 3" FROM THE EDGE OF THE SLAB AND HAVE A MINIMUM EMBEDMENT OF 2" INTO THE CONCRETE SURFACE. 6 ' THE AVERAGE SPACING BETWEEN BEAMS IS SHOWN ON THE "SITE SPECIFIC DRAWING". THE ACTUAL SPACING BETWEEN ANY TWO BEAMS MUSTBE THE LISTED SPACING, +/-2". THE OVERALL AVERAGE SPACING MUST BE EQUAL TO THE AVERAGE SPACING Sii_OWN ON THE "SITE SPECIFIC DRAWING". ALL SPACING MUST NEVER BE GREATER THAN 8.0' O.C. .7 IF DESIRED, THE 318" BOLT LT SHOWN IN THE WIND BRACING CONNECTION (SHEET 3, #2), THAT SECURES THE 2x2x0.090 MEMBER TO. THE U-BRACKET AND THE U-BRACKET TO THE ROOF BEAM CAN BE REPLACED WITH FOUR (4) #14 SMS. THE #4 SMS MUST BE 112" FROM THE END OF THE U-BRACKET AND AT LEAST 314" APART (STAGGERED) FROM EACH OTHER. NOTE: L-BRACKET, 2x3.0A25 OR STRONGER, CANBESUBSTITUTED FOR THE U-BRACKET. - WHEN USING L-BRACKETS; SIX (6) #14 SMS MUST BE USED, THREE (3) INTO THE ROOF BEAM AND THREE (3) INTO THE WIND BRACE MEMBER. 8 IN LIEU OF "SITE SPECIFIC ENGINEERING" AN EXISTING SLAB SHALL MEET THE FOLLOWING REQUIREMENTS: A THE SLAB MUST BE IN GOOD CONDITION, 4" OR GREATER THICKNESS, CONSTRUCTED WITH REBAR, WIRE OR FIBER MESH. B ALL BASE, WALL $ CEILINGFASTENERSMUST BE NO MORE THAN 24" O. C. WITH MINIMUM ENGAGEMENT OF 2". 1 9 ALL NEW SLABS, WITH OR WITHOUT FOOTERS, SHALL MEET THE FOLLOWING REQUIREMENTS AS A MINIMUM: L A PREPARED SOIL MUST BE COMPACTED AND TERMITE PROTECTED AS REQUIRED BY THE COUNTY, '�B 4" NOMINAL PATIO SLAB REQUIRES A VAPOR BARRIER IF THE SLAB ABUTS LIVING QUARTERS, �C 4" NOMINAL PATIO SLAB WITH CONCRETE @ 3000 PSI (MIN) WITH FIBER MESH OR REBAR AND WIRE. D WHEREVER NECESSARY' NEW CONCRETE SLABS SHALL BE SECURED TO EXISTING CONCRETE SLABS WHERE THEY ABUT ( WITH #5 REBAR EVERY 24"I`O.C. TO AVOID SETTLEMENT. SCANNED 10 ' ALL NEW PERIMETER FOOTERS SHALL MEET THE FOLLOWING REQUIREMENTSASA MINIMUM:R i A SOIL BEARING PRESSURE IS 1500 PSF (MIN) AND VAPOR BARRIER IF THE FOOTER ABUTS LIVING QUARTERS„ BY L B ONE#5REBARFOR8"xaIAND TWO #5REBAR FOR LARGER FOOTERS St. LUCID COU 11 ALL NEW PERIMETER FOOTER POURED WITH A SLAB SHALL MEET THE FOLLOWING CONDITIONS: L� B ALL REQUIREMENTS OFjA PERIMETER FOOTER 1CALLY POURED ITEM 9AND 10 ABOVE. WITH CONCRETE @ 3000 PSI (MIN). ALL REQUIREMENTS OFIITEMS 9 AND 10 ABOVE. MPH WIND LOAD, EXPOSURE 'B', RISK CATEGORY I. ' THIS NEW SCREEN ENCLOSURES IS BEING INSTALLED ON A PROPOSED 12" x 12" PERIMETER FOOTER (BY OTHERS). ) THIS FOUNDATION IS ACCEPTABLE FOR THIS STRUCTURE. THE MANSARD SCREEN ROOF IS BEING ERECTED ON 'y PROPOSED STEEL WALLS 10" STEEL COLUMNS (BY OTHERS). THE MANSARD HAS A RISE OF 3'-0" AND A RUN OF 4 7'-0' FOR A SLOPE OF 230. THE DESIGN DRAWINGS FOR THE SCREEN ENCLOSURE IS SHOWN ON SHEET 2. CONNECTION DRAWINGS ARE SHOWN ON SHEETS 3 AND 4. i i FOR BUILDING OFFICIALS ONLY: THIS DRAWING IS ONLY ACCEPTABLE FOR BUILDING PERMITS & ONLY WHEN IT HAS THE ENGINEER OF RECORDS RAISED SEAL. COPIES ARE NOT DEEMED VAUD. r� �� w _ j VPT ij i ( THIS DOCUMENT IS THE PROPERTY OF R. A. DUNLEA, P.E. AND SHALL NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE WRITTEN CONSENT OF R. A. DUNLEA. _ e--) J FOR%j REVIEWEE) R. A DUNLEA, P.E. 1513 CERVANTES PLACE THE VILLAGES, FLORIDA 32159 (352) 750-6207, (772) 285-6444 IJObC)UIIIe2(clIcentUPVIl11((.rlet FLORIDA LIC. NO.42835 ea¢ac9aaa® 00, Q� ......�y� �Bpe 000 � S�• G mo ov a//1 �• y` e� " 77 * ✓1 / * m P -D - pC / �� o y O o S A. Or "• <L�` Q °Oo0 �Cc•"••A.`�ORID... •. •. ��atw ®oQs®ado n to w �1nc /'�A11 PLI A L+T �, ICI COU14TY V Bocc 1 I ;; Ir 10• 10'•9" 3'-0" II �L 10" 30'-0" 13..9" t0" 3'-0• 6'-0" 3'-0" LEFT SIDE ELEVATION VIEW NOTE: THE 2x8 SMB ROOF BEAM CAN BE ATTACHED TO A 2x2x0.44 MEMBER THAT CAN BE BOLTED TO THE EXISTING STEEL BEAMS THAT RUN ACROSS THE TOP OF THE EXISTING WALLS. t 6'-0" SITE SPECIFIC DRAWING HOUSE nuubL WB-> Ria a-2x8 R1> <-2x8 R1a <-2x8 Rta <-2x8 R1� <-2x8 R1> <.2x8 R17> <-2x6 R1a <-2x8 R1-> WB-> c2x8 Pt 2x3 Pt 2x3 P1 2X3 P1 2x3 P7 2x3 2,3 Pi 2x3.? P1 2x3 Pt 2x3 P1 2x3 Ri-> 4-2x8 R1a <-2x8 Rte <-2x8 R1-> 4-2x8 R1-> <-20 Rta ,r <-2x8 I R1-> <2x8 Rt-> <-2x8 Rta <-2x8 P7 2x3 P1 2x3 I P1 2x3 P1 2x3 P1 2x3 2x3 Pi 1x3'N P1 2X3 Pt 2x3 P'I 2x3 Rt-> <.2x8 Rt-> <-2x8 R7-> <-2x8 RN <•2x8 Rt> o-2x8 Rta <-2x8 Rta <-2x8 Rt-> <-2x8 Rt> <.2x8 , P1 2x3 P1 2x3 P1 2x3 P7 2x3 Pt{ 2x3 2x3 P1 2x3 P7 2x3 Pt 2x3 Pt 2x3 1 R1a <-2X8 R1-> <.2x8 Rt-> <-2x8 R1-> <-2x8 _- R1> <-2x8 Ri-> <-2x8 ' R1a 4-2x8 Rt-> <2x8 R'L> <-2x8 P7 2x3 I Pi 2x3 1 Pt 2x3 Pt 2x3 Pt 2x3 2x3 I P1 2x3 'P1 2x3 I Pi 2x3 Pi 2x3 WB> R1-> <-2x8 RN <-2xW B R <-2x8 R1> <.2x8 '`R1a <-2x8 Rt-> <.2x8 R1-> [4"218 Rta <-2x8 Rt-> <-2x8 WB-> 7'.9.5• I 7' 7-9.5" I -95" I 7-9.5" I 7-9.5" I 7-9.5" I 7-9.5• I 7-9.5^ I 7'-9.5"I 77' 10^ PI AM VIPllU FRONT ELEVATION VIEW FILE COPY REVIEWED F OR CODE COMPLIANCE , t ` ST. LUCIE COUNTY r BOCC 1. 70" 16•-0" 3'-0" 10" 130'-0" 61-10.5 6'-10.5 _1. io• 3'-0" 1 6'-0• 3'-0" RIGHT SIDE ELEVATION VIEW MANSARD SCREEN ROOM DWG. # JRL-2019-011, REV. 0 February 4, 2019 SHEET 2 OF 4 SITE DESIGN DRAWING HEIGHT 12'-0", 145 MPH, EXP. 'B' JRL ALUMINUM SERVICES, INC. 1304 NE 24 ST. JENSEN BEACH, FL 34957 OFFICE (772) 529-2674 FAX (772) 398-2997 LOCATION: NAME: BATRA RESIDENCE ADDRESS: 8020 PLANTATION LAKES DRIVE CITY/STATE: PORT ST. LUCIE, FL 34986 COUNTY: ST. LUCIE DRAWINGS NOT TO SCALE R. A DUNLEA, P.E. 1513 CERVANTES PLACE THE VILLAGES, FLORIDA 32159 (352) 750-6207, (772) 285-6444 bobdu nlea(diaenturvli nk.net FLORIDA LIC. NO.42835 NIATHO/yY NO.428a!T y 2 ^* Y J�• ^�,®bOos�,��NAL ENaoe°o MANSARD SCREEN ROOM pIfice ate MIFi'rspN¢s �IOND far---dwas, Me10-1 S1T6 50_g2HJ: �eDfi��nsfw 9?hle andfor3YdgMbean Wgm1 ..fi0fi1T6 a5052h-� Maxunum angle for n¢nsa1ds35^ . e' 4 R` 4 , + b z-`!14SA5TyP1od � + •'f:' v=r iP SvewpSSlti rs RgterJdntDeybeatuSem - . to a®nmd iS plan -.Pam betm. fits a)mg rNbxldm nay 11671n r, WGI-Uri -Tlwdrsxm, aTuf *g. M�n¢s I,e[iveP,1saexa. EQge Di .farS g•A' MNM,um Sc, N Sp d-9: 5/8- SPLICE SPECIFICATIONS PER TABLE BELOW TYPICAL ELEVATION FOR BEAM MITER SPLICE [ DETAIL MAY BE ROTATED FOR GABLE RIDGE SPLICE, AND MAY ALSO SERVE AS SPECIFICATIONS FOR A STRAIGHT SPLICE, MAINTAIN 3116" PLATE AND CONNECTOR SPECIFICATIONS,IN TABLE below FOR ALL] �1 Table for Beam Splice Plate Size and Fastener Re uirements Beam Splice Plate Requirements for -,Beams of 6005T5 alto .Beams of 6005T5.allo #14 SMS-. Total Fastener Spaces MEMBER ISMS)LENGTH PLATE Me 6005T5 Required Thickness Per Side #14 SMS Number.of Spaces 5052H32 ,6061T6 Per End Per Splice Horizontal Vertical 2x4 - 2X6 10" 8.7,13-9,17.4 3/16" 118" 6 24 2 2 2x7 14" 223 3/16" 1!8" 8 32 3 3 Zx8 18" 6.7 5116" 1/4" 9 36 4 4 2x9 18" 107 318^ 1 1!4^ 1 10 40 6 5 2x10 20" i 1475 3/8" 1 5116" 1 11 - - 44 ..-..................­.� ..�� tea„" P,"- a- vu-,, I Dea,Irs,Dwans< Is a sneer augy, buev b Is a plate auoy- •• AM1Ma[iIRJAL iINi c$Ilt[H 33L-WS x48I YRFAN+l BeD9iG - P�GUTaT1 PuW I ale' B emT xu'xsz�>o=Pw1E l+�m BPDJNG RA,e(ABUTa I48LLAD PD1IE aY�IG PIATEMAY eE DREW, W L'MM EdT TMOI IffRR BEAN t"1®D'OY ALTI N(ATE CONNS:�(TON OF 01ANNEL' A^ L 4EAO1R145MSTHRUOUANWLWEB Plan.VeW THIN) BEAM WEH OdTO BACKING PU lE NB'OSOQ BPHwa.Ye'&QLL R.QEPBytat® rmr+aa rnser�¢Nw Daaa,AL T3�NAaie[ - fu�ammal SEE ITEM 7, SHEET [72] 3Ta-a eoc— �` i . eaUf.Yil1 NPG ATav'v ' mG' R m -. 6vx. -Oraxx,L Rze>3nar �xNaaetrl \` ed ��AImANWvr�wxm Section CG1 Beam SCREEN P.00F DIAGONAL BRACING S0j5VMC (.Tl) ? zBn.va,IG NrircTHE�mNM�Talmusl+ae<umITarmxswc,c PMB,R6'n2 Raa Plan View K-BRAC:1NG :Dr=TAtL TYPICAL SCREEN WALL ELEVATION ( NOTE: ALL K-BRACE MEMBERS ARE 2x3x0.1370. ALL SHEET METAL CONNECTING SCREWS (511AS) ARE 914. ) .0 xr xLB'ANGLE FA iH4 SMS EACH SIDE DWG. # JRL-2019-011, REV. 0 February 4, 2019 U1/4-EMSEDMENi(MIN. r w it SHEET 3 OF 4 ■ ■ STANDARD CONNECTIONS _ _ LECOPY _ —_— � 4-1'xY O.B. BASE PLATE rMIN. a r^� p£ � HEIGHT12'-O',145MPH,EXP.'B' k.x JRL ALUMINUM SERVICES, INC. .14]"M 1304NE24ST. xiMPEamrai�2 t JENSEN BEACH, FL 34957 :. -; w �GGIE .oR. tAe;._;s..,<„ OFFICE (772) 529-2674 3" x 4' z 1/B-PLATE ON EXTERIOR; 3- LONG. x 1' K-BRACE x 3- x lir ANGLE ON IFT—. ORW/16sA1StS PER SIDE) INTO BRACING CORNER POST AND WALL AS SHOWN. K-BRACE. DETAIL"A" v x r x 1/e' ANGLE, T LONG WI SMS INTO BRACE & INTO POST POSTIODLUMN HORizONTAL MEMBER' Ms (fYP.J TOP VIEW 3112' x 6" x 1/8" PLATE K-BRACE 12(6PERSIDE, TYP.) _ 14 7PER SIDE, TYP.) GIRT CHAIR RAIL GIRT CHAIR RAIL t � Q K-BRACE 3-U2' x 6• x COLUMN 118' PLATE —V K -BRACE DETAIL "B" ' 1"x3-x 119"ANGLE, r POSTICOLllMN LONG WI SMS INTO BRACE AND INTO POST SMS fP. TOP VIEW 3-112'x6'x 11B'PLATE K-BRACE 3"x 4' x 1/6- PATE ON EXTERIOR CORNER 3" LONG x1-x3"xl/e"ANGLE ON POST INTERIOR YdI a EMS( B PER SIDE) IL7 BRACING& WALL AS SHOWN. .61 B PER SIDE TYP.' 1x2 OR US SOLE PLATE ■ v ■ a FOUNDATION - ) ) K - BRAG E DETAIL "D•• COLUMN / FOUNDATION FASTENER FOR 2x2 AND 2x3 NOTES: LOAD CONDITIONS: CONNECTION UPLiFTCAPACITY= 1,1Ola, SHEM CAPACITY=mg. 1)THISDETAR.MAYNOTBEUSEOFOROOWMNSLMGERTIUWrx3•, 2)7W0D)EACHX319-DULBOLTS 'MAYBE_W13STRUTED FOR THE 3 EACH g14SMS (2 THRU BOLTS REPLACE 6 SCREWS) 31 Cb,, .FASTENER SPECIFICATIONS: CONCRETE FASTENERS MUSTHAVEA (MIN.) ULTIMATE ULTIMATE TENSION CAPACITY OF 2,SCO A ORA WoNMIG (MIN.) TENSION CAPACITY OF 640E, AN0, A (MIN.1 WORKING SHEM CWACIY OF30Dg. MONOTSUBSTTRITE We DIA CONCRETE ANCHORS FORLMGERSDEANCHORS4 FORT x4-8 rx SCOWMNS SIX(6) g14 SMS(IYP. ANCHOREDGEMSTANCE=3- 1M' DIA CONCRETE ANCHOR wI (� ® ANCHOR SPACING=2-FOR 2x4 2 EMBEDMEM IN. P. "OSTS.3"FORK POSTS NOTE DO NOT SUBSTITUTE LMGER OIANETER CONCREILANCHORS TMW. rxros BASEP CONCRETE PERIMETER . FOOTER OR SLAB COLUMN / FOUNDATION FASTENER FOR 2x4 8:2x5 LOAD CONORONS: CONNECTION UPLIFT CAPACITY=1,680E, SHEM CAPACITY=1.184E. NOTES 11 THIS DETAIL IS FOR h4 AND 3 S COLUMNSIPOSTS ONLY. 2) CONCRETE FM712NERS MUST HAVE M ULTIMATE PULL OUT CAPACITY OF 2.110 9OR A WORKING PULL-0UT CAPACITY OF 32W. 3) TWO (2) EACH x 3/8" DIA BOLTS MAYBE SUBSTITUTED FOR THE 3 EACH E14 SMS ( 2 THRU BOLTS REPLACE 6 SCREWS } (r x 6'COWMN SHOWN ) x MEWW rI1MIN) Ta' A• C 6 NOTE:6A1x3BASEPLATEISTO ...8"BE TIN BE USm THEN IHEANGLES CAN OFMEANS ORSMUSTR ME N COFOOTERORSLARER M SAME. ORS MUGTREMAIN I FOOTIIL OR SLAB' 'RIE SANE COLUMN / FOUNDATION. FASTENER FOR 2x6 THRU 2x10 NOTES: LOAD CQNDmONS: CONNECTON UPLIFT CAPACITY=2,400E, SHEAR CAPACITY=2,000, 1)^THIS OETML IS FOR2x67HRUh10 COLUMNIPOSTPERTABLE 1. SIIEETt. 21 2 x 3M' DIA BOLTS MAY BE SUBSTITUTED FOR THE 3 EACH 114 SMS (2 WRU BOLTS REPLACE 6 SCREWs6 3) CONCRETE FASTENER SPECIFICATIONS: ANCHOR -A• (CLOSESTTO EDGE] IS 318" DIA x 3- LONG..I r EMBEDMEM UL71M M"E'(FARRi PAC OF IS318^ AWO LONG I -)ENBED6fENT,ANCHOR'A'MUS HAVERMIN.ULTIMATETENSION (OF30YOF2,550E EANWORKING (MIN.)TENSIONCAPACm'OF 640E:4i AMIN W4°JAK9511EMCAFKRY OFRIONCONCRETE ANCHOR Cal -SODA,&MIM WOWING GS EWCPE TENSION CAPACITY BSTn T M ' CONCRETE TENSIONS WITH ANCHORS E; d MIN- GVIID SHEAR CAPACII =1,ODPg.0)O NOT SIWSTTUiE 3/e' CONCRETE ANCHORS WITH ANCHORS OF LARGER DIAMETER} NAME: BATRA RESIDENCE ADDRESS: 8020 PLANTATION LAKES DRIVE CITY/STATE: PORT ST. LUCIE, FL 34986 COUNTY: ST. LUCIE THE "CIRCLED" CONNECTIONS ON THIS SHEET ARE BEING USED FOR THIS PROJECT. LUCIE COUNTY J3OCC5 6 DRAWINGS NOT TO SCALE R. A DUNLEA, P.E. 1513 CERVANTES PLACE THE VILLAGES, FLORIDA 32959 (352) 750-6207, (772) 285-6444 bobdu nlea(afcentu rVli nk.net FLORIDA LIC. NO.42835 PYTHON), P. IoF LU �,S O[� 1 o ` V gOo�,.c\�s . h OR O, ® °4ey S�ONA� w 9EN4(Ax�L se (sBFMATmG man 0 0 BFlQ4RM%2TRBLM Dm �EINSEmm OF AA W/ �UYELPOST Po�/�M19519 Pd19GlEOF talnwGtwrtG ewlnD®gsTTDN/LAP �M1 wxA R4B [�-MArnuGBEAM n GGE PWE (1% wm OD OB) TASR31510 fOMV6ATxINWRH wv CWIGIEI-'HiQgRS ATN 6G 1PR09IDElwtmmm24 UPARWIDATIGNOx1NEClICN �SCQ i`�'. .' �O]MAGTERJMSABON (TLl:T7PVL.4�5(AI :. G UWffiSNOIHi.DI}�wL5E1 LDGfAL-FL] TYPICPL (BEAM BEARING] WALL SECTION 2'Xd'xi/8' ANG EFACH SIDE 4 EALN #14,%% WIDPURtIN WEBAND 4 EAOI MID BEAM WEB (ANGLE ExTENDSTO WOMN A -OF AND B9n0M OF CONNECTING MIRLM AND RSTETR'RS SPAGED EVE Dl PURLIN MAY BE SLOPING OR HORIZONTAL COVER PLATE ; WALL END - COLUMN SELECT. PER TABLE 1 I - 2 EACH -010 SWS X 4" - LONG TM EAVE RAIL 2X2' INTO SLOPING Pu" SCRE'14 SPLINES I 4 2-1MV LAG BOLTS @ EA GUTTER BRACE TO FASCIA 81-1l4'Y3' LAG 24.O.C.ELSEWHEREAT GUTTER TXY C!P ZGUTTERBRACE SIDE INCLINED FASCIA) SUPER GUTTER/ V TOTAL4-M,, PER CUP,TWO(2ITHRU THE W OR W MEMBER AND TWO MTHRU THEGUTTER@GU BRACE SUPER GUTTER CONNECTION DETAIL BEAM NOTC,wSD AROUND '; 2" x 2" OR (4) LE COP #12 SMS Roo- ® !D ALTERNATE FLAT ROOF �.® ----------I NUMBER OF #12 SMS PER ROOF BEAM - 2x3-4 2x7-10 2x4-6 2x8-14 _ 2x5 - 6 2x9 -18 %3• LG 2x6 - 6 2x10 - 18 ONE EA M T BEA .. L. UPRLGHTTO ROOF BEAM CONNECTION -DETAIL (!NT D R MAY NG! H4V E 31AP ' I' FFAIVfiB519WNMro5R* I t I PM4WGB�rNIGVARYJ AYF E RAILOINNECISTO EFMSV(A - INTBWAL4185.G%IW'(1WG - L4-iV1MNiG: STLIpIGG1EWGAT .zracroPum MzrTGM suss . ., _ R8(z%9MD 2%10,ALLOREEa5 i10 vs 1a01ER4RII6APE Mk@ITIa D4Gd W. Pas+ �G. a,.ara maanalas a� aocec AM�U16DeEW^�Ca �NGI1GfW6 1 0 HOLLOW RIRLIIJ ixra a 2aa j MAYBE9OPINGO&HOR NRIWIIH ]WI.p4asgmppagwg-J I �Im�:aaA4 Ih-LONG S16-16 FROM INSIDE msbcI PRQBEYIwO I NAYxs1✓FL, 0 BEPM INTO MIRIII(SOtE'NSLOIS fBs'� -.- - FA9r7'PlASiCNQ ua'scm+Grwa:+vsamxmmlKULWadP.p°s PPy0A 41 aC ga2yfE3,em SF.�dy 9,tiaQ i1G ] .. - S10wro[ils�.am5vsamnuene=�as�aw ROOF BEAM -SON / 41443rR"NN5CR ]ONG NATESMID B #f&SMS INTO HOLLOW PUMM M IN M MPH ZONES AND GREATER, IN WIND ZONES FUP.LTN TO 3E44 CONNEC�]GNS 19 MPH, ILE4 010 SMS MTO:PURINS 0 O ' ' 0 0N,--- EFAM (HAYBFN0.RTQDY V SECTON (21 AT SCREEN EAVE ON LONGITUDINAL WALLS (F)R WIND ZONE 120 MPH AND GREATER F 4-.'(B `�If8N 0.iIDE FAT.cOF 'T /�, PLST aBO saeN EPN'I'i DFHQtIAP 1 `Ij I . Gt�s(1-yra4e®r4a[rnmaluNl� I 2= RAi!1G �N-N._•,-,CN ;Y/ �ANG'L'Fsa� 7J=: 2=.hip."L �_4A.iLCP/c1r_giTO?O_I GNNcrONS 0 MANSARD SCREEN ROOM DWG. # JRL-2019-011, REV. 0 February 4, 2019 SHEET 4 OF 4 STANDARD CONNECTIONS HEIGHT 12'-0", 145 MPH, EXP. 'B' JRL ALUMINUM SERVICES, INC. 1304 NE 24 ST. JENSEN BEACH, FL 34957 OFFICE (772) 529-2674 NAME: BATRA RESIDENCE ADDRESS: 8020 PLANTATION LAKES DRIVE CITY/STATE: PORT ST. LUCIE, FL 34986 COUNTY: ST. LUCIE THE "CIRCLED" CONNECTIONS ON THIS SHEET ARE BEING USED FOR THIS PROJECT. VIEWED FOI 4 IE COMPLIANCE LRUCIECCOUIVW B EOCC DRAWINGS NOT TO SCALE R. A DUNLEA, P.E. 1513 CERVANTES PLACE THE VILLAGES, FLORIDA 32159 (352) 750-6207, (772) 285-6444 bobdunlea(d.)centurVlink.net FLORIDA LIC. NO.42835 °yaseco�sanx#aaa pr1T HON y40°0000 * . LLJ / I�f�/��9 c s . f1 (� Af 00 Ptz�4,9,91ONAt •�ao°°moo I FILE COPY FILE COPY