March 6, 2018
Florida Contract Services
420 NW Peacock Blvd - Suite # 8044
Port Saint Lucie, FL 34986
RE: ROOF ANALYSIS
Sloped Roof Decks (2)
Smythe Residence - House and Detached Garage
4844 Christensen Road; Fort Pierce, FL 34981
Dear Sir or Madam:
ENGINEERING & TESTING, INC.
Phone: (866) 781-6889 •Fax: (866) 784-8550
www.floridaengineeringandtesting.com
250 S.W.1P Avenue
Pompano Beach, FL 33069
Job Order No.: 19-1052
SCANNED
BY
St. Lucie County
BILE COPY
Per your request, Florida Engineering & Testing Inc. has reviewed client provided in -progress photographs
and a client provided roofer affidavit/letter, dated March 2, 2019, to verify the re -roofing workmanship and
materials used to determine if underlayment installation including metal flashings was completed to meet
the minimum standards of Florida Product Approval # FL 16048-R6, the manufacturer's installation
instructions, and the 2017 Florida Building Code. The following is a summary of our observations of the
roof in -progress installation:
Underlayment Sheet Including Metal
Flashing From Photographs
Underlayment Sheet Including Metal
Flashing From Roofer Affidavit/Letter
Underlayment consistent with Tri-Built Smooth
"...installed one layer of Tri-Built Smooth HT SA
HT S/A underlayment was observed to be installed
underlayment back nailed twelve (12) inches on
on the roof and back nailed at a spacing of 12" o.c.
center, installed 24 gauge galvalume valley
and rolled with a 401b roller.
flashing and bullnose drip edge nailed 6" o.c. with
1-1/4" ring shank nails. We then rolled a 40lbs
The drip edge metal and valley metal attachment
metal roller over the entire roof covering to adhere
was observed to be consistent with the spacing
the new underlayment to the plywood substrate."
detailed on the roofer affidavit.
We were able to determine to the best of our ability, based solely on the information provided by the
client, that the underlayment (including metal flashing) installation has been performed in
accordance with the above referenced standards.
Florida Engineering & Testing, Inc. appreciates the opportunity to be of service to you at this phase of your
project. Should you have questions or comments, please feel free to contact us.
Sincerely, ,\\\.t\\111PLAN v���/,
Mark A,-M%iano, P.E* = Attachment:
Florida M&'eerirg1* JWing, ` Client Provided Photographs
Florida ItBg`.' ,. 4.8202 ; .� #qc --Z� Roofer Affidavit/Letter, Dated 3/2/19
%I
Qxa/ify ,QA��/.lasnrance
March 2, 2019
Project: George and Josephine Smythe
Project address: 4844 Christensen Road Fort Pierce, Florida 34981
Permit # SLC-1901-0393
Tri-Built Smooth HT S/A // FL16048-R6 (Approval Number)
To whom it may concern, at the above address we Fl Contract Services tore off the existing shingle
roof covering down to the 5/8" CDX plywood, re -nailed the decking with 8d ring shank nails six (6)
inches on center throughout, hammered down any nail heads that weren't flush with the plywood
decking, installed one layer of Tri-Built Smooth HT S/A underlayment back nailed twelve (12)
inches on center, installed 24-gauge galvalume valley flashing and bullnose drip edge nailed 6" O.0
with 1-1/4" ring shank nails. We then rolled a 401b metal roller over the entire roof covering to
adhere the new underlayment to the plywood substrate.
If you have any questions please let us know
Ylaioic'
y
Operations manager �a.=88tateMFbnoa
y -G 1VA79vka F
1111111IF" - I- - "
rl*�
Awl
.4
0
'P� 10
Oil-
79
w1
Y..
,
�1
i
n r0c, -
x
711
77
5i
--
- III—"-�---��-►.�_---„' T �` � �
KK
.,A , - Arl
•
-Yy
� i i n I I I� �� I •_
_ ry 1 �•
. !' sex,,. i ii' •+ .�_ �T��_., to
-
r l ...
�. %X
At
�� � ���•�� it _ I�I� � s• � �. ��� � � -
r
fix
,_.-.LMLIP I ,rA_
m"11
J