Loading...
HomeMy WebLinkAboutPRODUCT APPROVAL - ROOFINGProduct Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC 26 Ga. GulfRibTm Roof Panel over 15132" Plywood Florida Product Approval #11651.22 R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 -D Category: Roofing Subcategory: Metal Roofing Compliance Method: 61 G20-3.005(1)(d) NON HVHZ Product Manufacturer: Gulf Coast Supply & Manufacturing, LLC. 14429 SW 2nd Place, Suite G30 Newberry, FL 32669 Engineer Evaluator: Dan Kuhn, P.E. #75519 Florida Evaluation ANE ID: 10743 Validator: Locke Bowden, P.E. #49704 9450 Alysbury Place Montgomery, AL 36117 Contents: Evaluation Report Pages 1 - 5 $CANNED BY St, Lucie County `Ituu1i11,,,� N1EL S, k �P --1GEIV,S No. 75519 STAT c��s C 0 RE G P . •�Qi�Q• Compliance Statement: The product as described in this report has demonstrated compliance with the Florida Building Code 2017, Sections 1504.3.2. Product Description: GulfRibTM, 3/a" Rib Roof Panel, Minimum 26 Ga. Steel, 36" Coverage, through fastened roof panel over minimum 15/32" Plywood Decking. Non Structural application. Panel Material/Standards: Material: Minimum 26 Ga. Steel, ASTM A792 or ASTM A653 G90 conforming to Florida Building Code 2017 Section 1507.4.3. Paint Finish Optional Yield Strength: Min. 80.Oksi Corrosion Resistance: Panel Material shall comply with Florida Building Code 2017, Section 1507.4.3. Panel Dimension(s): Thickness: 0.018" Minimum Width: 36" Coverage Rib Height: 3/a" Major Rib at 9" O.C. Panel Fastener: #9-15x1.5" HWH with sealing washing or approved equal 1/4" minimum penetration through plywood. Corrosion Resistance: Per Florida Building Code 2017, Section 1506.6, 1507.4.4 Substrate Description: Minimum 1%2" thick, APA Rated plywood over supports at maximum 24" O.C. Design of plywood and plywood supports are outside the scope of this evaluation. Must be designed in accordance w/ Florida Building Code 2017. Design Uplift Pressures: FL# 11651 Table "A" Maximum Total Upllft Qesgn Pressure 69.25 psf 159.25 psf Fastener Pattern 9"-9"-9"-9" 6.5"-2.5"-6.5"- 2.5"6.5"-2.5"-6.5" EFastener Pattern Spacing DRO.C. Design Pressure includes a Safety Factor = 2.0. Code Compliance: The product described herein has demonstrated compliance with the Florida Building Code 2017, Sections 1504.3.2. Evaluation Report Scope: The product evaluation is limited to compliance with the structural wind load requirements of the Florida Building Code 2017, as relates to Rule 61 G20-3. Performance Standards: The product described herein has demonstrated compliance with: • UL 580-06 - Test for Uplift Resistance of Roof Assemblies • UL 1897-12 - Uplift Test for Roof Covering Systems. Reference Data: 1. UL 580-94 / 1897-98 Uplift Test Force Engineering & Testing, Inc. (FBC Organization # TST-5328) Report No. 117-0062T-07A, B, Dated 02/19/2007 2. Certificate of Independence By Dan Kuhn, P.E. (FL# 75519) ® Kuhn Engineering, LLC (FBC Organization # ANE ID: 10743) Test Standard Equivalence: Quality Assurance Entity: Minimum Slope Range: Installation: Underlayment FL# 11651 1. The UL 580-94 test standard is equivalent to the UL 580-06 test standard. 2. The UL 1897-98 test standard is equivalent to the UL 1897-12 test standard. The manufacturer has established compliance of roof panel products in accordance with the Florida Building Code and Rule 61 G20-3.005(3) for manufacturing under a quality assurance program audited by an approved quality assurance entity. Minimum Slope shall comply with Florida Building Code 2017, including Section 1507.4.2 and in accordance with Manufacturers recommendations. For slopes less than 3:12, lap sealant must be used in the panel side laps. Install per Manufacturer's recommended details. Shall comply with Florida Building Code 2017 section 1507.1.1. Roof Panel Fire Classification: Fire classification is not part of this acceptance. Shear Diaphragm: Shear Diaphragm values are outside the scope of this report. Design Procedure: For roofs within the parameters listed on the load table, fastening pattern must at a minimum meet those listed for the applicable wind zone. For all roofs outside the parameters listed on the load table, design wind loads shall be determined for each project in accordance with FBC 2017 Section 1609 or ASCE 7-10 using allowable stress design. The maximum fastener spacing listed herein shall not be exceeded. This evaluation report is not applicable in High Velocity Hurricane Zone. Refer to current NOA or HVHZ evaluation reportfor use of this product in High Velocity Hurricane Zone. � ArW ENGINEER LOAD TABLE: 26 Ga. GulfRibTM Panel over 15/32" Plywood Buildings`) aving=a Roof Mean Height <r20y 0u 1Roof�Sl6p`e 2,"/ . �,/1 Z aliEe94r Ip R`o'of VVInd Speeds 120 x 180mph"Exposure C Pork Category II _Enclosed Building ,based,on Florida Btulding -- 6' 01;7k _ �150 z � ' 4�1 y . 120 130 140 160 170 180 WAND FASTENER (MIN. 1/4' SUBSTRATE SPEED Penetration) (MIN. 15132') ON CENTER ON CENTER ON CENTER ON CENTER ON CENTER ON CENTER ON CENTER SPACING SPACING SPACING SPACING SPACING SPACING SPACING ZONE 1 #9 15x1 5 "^LPI ood; 24yNPE 1)' 24 TYPE 24 �TYPE(ts -24 TYPE 1 24', TYPE`? 24 TYPE'7 1' IMP 1 i 4 wa 5w TM dG't 's+a..a. r. .�Y�P ZONE 2 #9-15x1.5" Plywood 24", TYPE 1 24", TYPE 1 24", TYPE 1 24-, TYPE 1 24", TYPE 1 24", TYPE 1 24", TYPE 2 ZONE 3 `, 1#9 15XT 5? ,rL�.+,'PlyWoodP`y� r24 ,)TYPEy1v 24" TYPE 1 24 , TYPE 1 A2-4TYPEi21 12 TYPEIZ 12 TYPE 2 12=94i; TYPEi2) a. 1.) PANEL DESCRIPTION: GULFRIBT1A, MIN. 26 GA., GRADE 80, 36"COVERAGE, 3/4" TALL. 2.) PANEL FASTENER: 99-15M.5" HWH WITH SEALING WASHER OR APPROVED EQUAL 3.) MAXIMUM ALLOWABLE PANEL UPLIFT PRESSURE: 69.25 PSF 0 24" O.C. FASTENER SPACING TYPE I FASTENER PATTERN, 159.25 PSF ® 12" O.C. FASTENER SPACING TYPE 2 FASTENER PATTERN BASED ON TAS 125, UL 580/UL 1897 TESTING. 4.) PLYWOOD DECKING: MIN.11iz" THICK PLYWOOD MUST BE DESIGNED IN ACCORDANCE WITH FLORIDA BUILDING CODE 2017. 5.) ROOF SLOPE: ON ROOF SLOPES LESS THAN 3:12, LAP SEALANT MUST BE USED IN PANEL SIDE LAPS. 6.) LOAD TABLE BASED ON WIND PRESSURES CALCULATED PER ASCE 7-10 (KD = 0.85) MULTIPLIED BY 0.6 PER FLORIDA BUILDING CODE2017. ZONE2 i a ZONE3 T1 --------------- - `II ROG IDGE \ \/ /—\— ZONE I /\/♦ / FAVE 2 GARLE ROOF �----- __ FL# 11651.22 R3 Note: Dimension (a) is defined as 10% of the minimum width of the building or 40% of the mean height of the roof, whichever is smaller, however, (a) cannot be =:ja less than either 4% of the minimum width of the building or 3 feet. TYPE I FASTENER PATTERN #9-15 x 1-11r /Sealer Werner @ 24- O.C. Lim #9.15 a 1-11r w/Seelet Washer @ I O.C. Max. VTRINITYIERD ROOFING COMPONENT EVALUATION: 1. SCOPE: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: TRI-BUILT Roof Underlayments, as produced by TRI-BUILT Materials Group, LLC, have demonstrated compliance with the following sections of the 6v' Edition (2017) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Property Standard Year 1504.3.1 Wind Resistance FM 4474 2011 1504.3.1 Wind Uplift UL 1897 2012 1504.6 Accelerated Weathering ASTM G155 2005 1507.2.4 / 1507.1.1, 1507.2.9.2 Physical Properties ASTM D1970 2015 1507.3.3 Physical Properties FRSA/TRI April 2012 (04-12) 2012 3. REFERENCES: gntiw Examination Reference Date ERD (TST6049) Physical Properties 540540.02.13-1 02/19/2013 ERD (TST6049) Physical Properties 540540.11.13 11/19/2013 ERD (TST6049) Physical Properties 540540.03.14 03/26/2014 ERD (TST6049) Physical Properties 544870.04.14-2 04/02/2014 ERD (TST6049) Physical Properties 544870.04.14-3 04/02/2014 ERD (TST6049) Physical Properties 544870.04.14-1 04/10/2014 ERD (TST6049) Physical Properties 544870.04.14-4 04/10/2014 ERD (TST6049) Physical Properties 543530.02.14-1-R1 05/14/2014 ERD (TST6049) Physical Properties 543530.05.14 05/28/2014 ERD (TST6049) Physical Properties 540540.10.14 10/31/2014 ERD (TST6049) Physical Properties SC7645.02.15 02/13/2015 ERD (TST6049) Accelerated Weathering SC8520.04.15 05/27/2015 ERD (TST6049), Wind Resistance SC14045.05.17-R1 06/07/2017 UL, I.I.C. (QUA9625) Quality Control Multiple -Listing R16814 12/10/2015 UL, I.I.C. (QUA9625) Quality Control Service Confirmation Exp. 07/18/2020 4. PRODUCT DESCRIPTION: 4.1 Tri-Built Sand-R SA Shingle Underlayment is a self -adhering, glass -mat reinforced, sand -surfaced, SBS modified bitumen roof underlayment, with a 36-inch sheet width; meets ASTM D3970. 4.2 Tri-Built S/A HT TU Underlayment is a self -adhering, non -woven polyester fabric surfaced, SBS modified bitumen roof underlayment; meets ASTM D1970 and FRSA/TRI April 2012. 4.3 Tri-Built Smooth HT S/A Underlayment is a self -adhering, glass -mat reinforced, film -surfaced, SBS modified bitumen roof underlayment; meets ASTM D1970. S. LIMITATIONS: 5.1 This is a building code evaluation. Neither Trinity(ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions. 5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of this product. Exterior Research and Design, LLC. Evaluation Report A42960.10.12-R6 Certifrcaee of Authorization#9503 6r"EDITION (2017)FBC NON-HVHZ EVALUATION FLI6048-116 TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6:09/25/2017 Page 2 of 6 -, TRINITY ERD 5.4 TRI-BUILT Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data -for the prepared roof covering. 5.5 Allowable Roof Covers: TABLE 1: ROOF COVER OPTIONS Underlayment Asphalt Nail -On Tile Foam -On Tile Metal Wood Shakes Slate Shingles & Shingles Tri-Built Sand-R SA Shingle Underlayment Yes No No No Yes Yes Tri-Built S/A HT TU Yes Underlayment Yes Yes See 5.5.1 Yes Yes Yes Tri-Built Smooth HT S/A Underlayment Yes No No Yes Yes Yes 5.5.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combinations. TABLE IA: ALLOWABLE TILE ADHESIVE '/.UNDERLAYMENT COMBINATIONSs Adhesive Florida Product Approval I Underlayments ICP Adhesives Polyset® AH-160 FL6332 Tri-Built S/A HT TU Underlayment Dow TileBond'" FL22525 Tri-Built S/A HT TU Underlayment 5.6 Allowable Substrates: 5.6.1 Direct -Bond to Deck: Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A Underlayment applied to: ➢ Plywood; ASTM D41 primed plywood; OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern Yellow Pine; ASTM D41 primed structural concrete. While not required over plywood, OSB or Southern Yellow Pine substrates, TRI-BUILT Materials Group, LLC recommends priming the deck if the final roof cover is not slated for installation within 24 hours. Note: TRI-BUILT Materials Group, LLC requires tongue -and -groove board decking be covered with plywood or OSB prior to installation of the self -adhering underlayment. 5.6.2 Bond -to -Insulation: Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A Underlayment applied to: ➢ Dens Deck Prime; SECUROCK Gypsum -Fiber Roof Board. For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile systems (Tri-Built S/A HT TU Underlayment only), insulation attachment shall be designed by a qualified design professional and installed based on testing of the insulation/underlayment system in accordance with FM 4474, Appendix D orTAS 114, Appendix). ' Refer to Tile Manufacturer's orAdhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance. Exterior Research and Design, I.I.C. Evaluation Report A42960.10.12-R6 Certificate of Authodzationtl9503 6rvEDITION (2017)FBC NON-HVHZ EVALUATION FL16048-R6 TRI-BUILT Roof Underlayments; (800) 516-14a5 Revision 6:09/25/2017 Page 3 of 6 ',,I I KINIIY ERD 5.6.3 Bond to Mechanically Attached Base Laver: Tri-Built Sand-R SA Shingle Underlayment, Tri-Built 5/A HT TU Underlayment or Tri-Built Smooth HT S/A Underlayment applied to: — — — -- ➢ ASTM D226, Type I or II felt. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under foam -on tile systems (Tri-Built S/A HT TU Underlayment only), base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04- 12). 5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12) does not address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment forms part of the load -path. The following wind uplift limitations apply to direct -deck underlayment systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-12), Appendix A, Table JA or FBC 1609 for determination of design wind pressures. #1 Maximum Design Pressure= -45.0 psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: (Optional) ASTM D41 or RE515TO EXTERIOR PRIMER Underlayment: Tri-BuiltS/A HT TU Underlayment, self -adhered. #2 Maximum Design Pressure = -67.5 psf: Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: Soprema Elastocol 600c Underlayment: Tri-BuiltS/A HT TU Underlayment, self -adhered. #3 Maximum Design Pressure=-150.0 psf: Deck: Min. 15/32-inch APA-rated BCX plywood (may be installed C-side up) to meet project requirements to satisfaction of Authority Having Jurisdiction. Deck Preparation: Plywood shall be thoroughly cleaned to remove dust and debris that may inhibit adhesion. All sheathing fasteners shall be driven flush with the surface. All sharp splinters and wood projections shall be removed/sanded. Primer: (Optional) RESISTO EXTERIOR PRIMER Underlayment: Tri-Built S/A HT TU Underlayment, self -adhered, shall be thoroughly roll using hand roller and/or weighted roller to ensure there are no voids, and ensure there are no voids/bridging at side and end -laps. #4 Maximum Design Pressure=-60.0 psf: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Soprema Sopra-G or Modified Sopra-G mechanically attached with nails (FBC 1517.5.1) and tin caps (FBC 1517.5.2) spaced 6-inch o.c. at the 4-inch laps and 6-inch o.c. in three, equally spaced rows in the center of the sheet. Underlayment: Tri-BuiltS/A HT TU Underlayment, self -adhered. Exterior Research and Design, U.C. Evaluation Report A42960.10.12-R6 Certificate of Authodration #9503 6TM EDmON (2017) FBC NON-HUHZ EVALUATION FL16048-R6 TRI-BUILT Roof Underiayments; (800) 516-1485 Revision 6:09/25/2017 Page 4 of 6 �,,l I KINITY ERD 5.6.4.1 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A. Alternatively, the -maximum -design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk' carry the limitations set forth In Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. 5.7 Exposure Limitations: Tri-Built Sand-R SA Shingle Underlayment or Tri-Built Smooth HT S/A Underlayment shall not be left exposed for longerthan 30-days after installation Tri-Built S/A HTTU Underlayment shall not be left exposed for longer than 180-days after installation. 5.8 Tile Slippage Limitations (TAS 103 per FRSA/TRI April 2012 (04-12)): When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. TABLE 2: TILE SLIPPAGE LIMITATIONS FOR DIRER -DECK TILE INSTALLATIONS _ Underlayment Tile Profile Staging Method Maximum Slope Flat Max. SO -tile stack 6:12 Lugged Max. 10-tile stack 5:12 Max. 10-tile stack (bottom 2-tile stack shall be inverted, followed by 8 tiles high 6:12 on slope, as shown below) I,ll-I l Tri-Built S/A HT TU Underlayment Lugged Exterior Research and Design, LLC. Evaluation Report A42960.10.12-R6 CertiJlcate afAuthorization#9503 6m EOrnON(2017)FBC NON-HVHZ EVALUATION F1.16048-116 TRI-BUILT Roof Underlayments, (800) 516-1485 Revision 6: 09/25/2017 Page 5 of 6 VTRINITYIERD 6. INSTALLATION: 6.1 TRI-BUILT Roof Underlayments shall be installed in accordance with TRI-BUILT Materials Group, LLC published installation requirements subject to the Limitations set forth -in Section 5 herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application, and prime the substrate (if applicable). 6.3 Tri-Built Sand-R SA Shingle Underlavment. Tri-Built S/A HT TU Underlavment or Tri-Built Smooth HT S/A Underlavment• 6.3.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table 1507.1.1 for the type of prepared roof covering to be installed. 6.3.2 Non -Tile applications: While priming is optional, TRI-BUILT Materials Group, LLC recommends priming the deck if the final roof cover is not slated for installation within 24 hours. Apply sheet parallel to the roof edge. Roll out approximately 30 ft of membrane and peel back the first 3 ft of release film. Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible. Once the entire length of membrane is in place, peel -off the release film diagonally while holding the membrane tight. Firmly roll, broom or hand -press the membrane into place to achieve a bond. Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6- inches and staggered not less than 2-ft from vertical seams in the course below, sealed in accordance with TRI-BUILT Materials Group, LLC requirements. When installing at slopes above 8:12, TRI-BUILT Materials Group, LLC recommends back -nailing in the overlap area at the top of the sheet at 12-inch o.c. For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet over valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge in each direction. For valleys, apply the sheet starting at the lowest point and work upward. 6.3.3 Tile Applications (Tri-Built S/A HT TU Underlavment only): Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions noted above as a guideline. For foam -on tile applications, reference is made to Section 5.6.4 herein for wind resistance limitations that fall outside the scope of FRSA/TRI April 2012 (04-12). Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment. See Table 2 herein, and TRI-BUILT Materials Group, LLC published requirements for tile staging. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. 8. MANUFACTURING PLANTS: Gulfport, MS 9. QUALITY ASSURANCE ENTITY: UL, LLC —QUA9625; (314) 578-3406; k.chancellor@us.ul.com - END OF EVALUATION REPORT - Exterior Research and Design, U.C. Certificate of Authorization k9503 61N EDITION (2017) FBC NON-HVHZ EVALUATION TRI-BUILT Roof Underlayments; (900) 516-14115 Evaluation Report A42960.10.12-R6 FL16046-R6 Revision 6; 09/25/2017 Page 6 of 6