PLAN REVIEW FORM
l
S160 N.W. Milner Drive
Port Saint Lucie, FL 34983
Telephone: 772-621-3322
Fax: 772-621-3604
Web Address: www.slcfd.com
SCANNED
BY
St. Lucie County
Building Dept. ISLC FMO Permit#
Project Name DVBI Amazon Delivery Center SLOG Permit If
Address 17440 Commercial Circle
City IFt Pierce
B-19-100
1902-0594
Contractor Bryan Builders.
Address 7440 Commercial Circle City Ft Pierce
State FL Zip 34951 Telephone (800)336-3115
Architect/Engineer Progressive Architecture Telephone (616)361-1493
Occupancy Type Industrial Construction Type 116 Square Feet. 60,42E
Occupant. Load 345 per plans Number of Stories I Access Box Required Access Key Switch
AFS Permit Required FA Permit Required FFPPermit
General Notes
1..An electronic copy of the construction documents submitted on a CD Is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final Inspections through the Fire Marshal's Office.
S. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown Is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The, Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2015 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT-FRAMESRUSS-TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector. HVAC duct smoke detector(s)
shall be tied into the fire alarm system.
2. The Installation or Alteration of Fire Sprinkler, Fire Alarm Systems require a separate review and permit.
Page of I1 Reviewed by TonyJerger Date 03-21-2019