CONSTRUCTION MATERIALS
SCANNED
LABORATORY TEST RESULTS BY
St. Lucie County
TECHNOLOGIES-____-- -
FILE COr I
Report for: Gardner Gibson Attention: Matt Mullins
4146 E. 71` Avenue Tampa, FL33605 CONC FALEDFASTENERSORATTACHMENTS
ARE THE RESPOHSIBIIJTY OFTHE
CDMRACTOR OR RECORD
Product Name(s): APOC Tuff -Felt 26
Manufacturer:
Gardner Gibson
PRI-CMT Project No.: GGI-207-02-01
Source:
Gardner Gibson
Date Received: January 31, 2018
Dates Tested:
Feb. 26, 2018 — Mar. 5, 2018
Purpose: Evaluate APOC Tuff -Felt 26 for compliance with the physical properties of
ASTM D 226 Asphalt -Saturated Felt Used in Roofing and Waterproofing,
Type II.
Test Methods: Testing was completed as described in ASTM D 226-09: Standard
Specification for Asphalt -Saturated Organic Felt Used in Roofing and
Waterproofing. Test methods assigned or referenced include ASTM D 70:
Standard Test Method for Density of Semi -Solid Bituminous Materials
(PycnometerMethod)' ASTM D 146: Standard Test Methods for Sampling and
Testing Bitumen -Saturated Fells and Woven Fabrics for Roofing and
Waterproofing; and ASTM D 6136: Standard Test Method for Kerosine
Numberof Unsaturated (Dry) Felt by Vacuum Method.
Samp 'ng: Product samples were provided by Gardner Gibson in Tampa, FL
ST. W C I E C t gUILDIN�
REVIEWED FOR COMPLIANCE THESE PLANS ,gj4jD
REVI2 �y ARESUBJECTTOANY CORRECTIONSORK
DATE O -1 REQUIRED BY FIELD INSPECTORSTHAT
PLANS AND PERMIT MUST BE KE NJ B MAY BE NECESSARY IN ORDER TO
SITE OR NO INSPECTION(S) WI E MADE COMPLY WITH ALL APPLICABLE CODES.
I ne rest resuns, opinions, or Interpretations are based on the material supplied by the client. This report is for the exclusive use of
staled crienl. No reproduction or facsimile In any form can be made without the client's permission. This report shall not be reproduced
except in full without the written approval of this laboratory. PRI Construction Materials Technologies LLC assumes no responsibility
nor makes a performance or warranty statement for this material or products and processes containing this material in connection
with this report.
PA ConsUmbonl.lateria'sTechmbgles LLC 64128aeger0mm Tampa,FL33610 Te1:8136215777 Fac813-621-5840 emal:malo6alslestingQpncmLcom WebSdo:hnpJ,%%ya.prkmtcam
1
Gp rdner Gihpon
ASTM D 226 for
APOC Tuff -Fell 26
Page 2 of 3
Results: ASTM D 226
Requirement
Property Test Method Result .• I 11
Type
Physical Requirements
Breaking Strength (Ibf/in-width)
20 specimens; 1" x 6" x thickness;
ASTM D 146
Cond. 2h @ 73.4t3.6°F & 50t5%RH;
Test 73.4t3.6°F; Rate=tin/min
Longitudinal (with fiber grain)
69
>_ 30
>_ 40
Transverse (across fiber grain)
32
2 15
z 20
Pliability [PassyFailj
10 specimens; 1" x 8" x thickness;
ASTM D 146
'/" radius
%" radius
Cond. 10-15min in water @ 77t1.80F;
Test 90" around'/" radius in 2s
Longitudinal (with fiber grain)
Pass
No Failures
No Failures
Transverse (across fiber grain)
Pass
No Failures
No Failures
Loss on Heating (weight %)
2 specimens; 12" x 6" x thickness;
ASTM D 146
1
5 4
5 4
Test Cond. 221t5°F for 5ht3min
Dimensions and Masses
Width of Roll (in)
ASTM D 146
36
36±114
36t1/4
Area, min (ft2)
ASTM D 146
217
432
216
Moisture at Point of Manufacture (%)
ASTM D 146
NT
5 4.3
54.1
As Received'
1.0
5 4.3
s 4.1
Net Mass of Saturated Felt (lb/1 O0ft2)
ASTM D 146
26
a 11.5
? 26
Mass of Saturant (lb/1 O0ft2)
ASTM D 146
15.0
a 6.2
15.0
Mass Ratio of Saturant to Desaturated Felt
ASTM D 226
1.5
a 1.2
2 1.5
Saturation Efficiency (%)
ASTM D 226
71
i 70
••
Mass of Desaturated Felt (lb/1O0ft2)
ASTM D 146
10.0
�! 5.2
t 10.0
Ash (%)
ASTM D 146
9.0
510.0
510.0
Continued on Following Page
The lest results, opinions, or interpretations are based on the material supplied by the client, This report is for the exclusive use of
staled client. No reproduction or facsimile in any form can be made without the client's permission. This report shall not be reproduced
except in full without the mitten approval of this laboratory. PRI Construction Materials Technologies LLC assumes no responsibility
nor makes a performance or warranty statement for this material or products and processes containing this material in connection
with this report.
PWContudionhlalenais Tmhmlogies LLC 64126adger Criro Tampa,F1.33610 Te1:813.621-5777 Fax:813621.5840 e-matma;erialstes5ag@pncmtaom WebSlto:hltp:!lravrv.pdrmL=
Gardner Gibson
ASTM D 226 for
APOC Tug -Fell 26
Page 3 of 3
NT- Not Tested;
NA- Not Applicable
Statement of Compliance:
The product was tested has demonstrated compliance with the physical requirements of Type II prescribed
in ASTM D 226.09: Standard Specification for Asphalt -Saturated Organic Felt Used in Roofing and
Waterproofing.
Signed:
J son Slmn ors
trrec or
Signed: Dj
Duc T. Nguyen
Date:'I Date:
Report Issue History:
Issue# Date
Oriainal 03/08/2018
END OF REPORT
Florida Registered Professional Engineer
PE No.: 65034
3�oe) `�Lol R
O,1`�NpNN A/GGr'G
No 65034
it f applica$lej
0 •, STATE OF =�
i'0*
<O•RtQ ir�`tC`S`S r� I I
Ine test results, opinions, or interpretations are based on the material supplied by the client. This report is for the exclusive use of
staled client. No reproduction or facsimile in any form can be made without the client's permission. This report shall not be reproduced
except in full without the written approval of this laboratory. PRI Construction Materials Technologies LLC assumes no responsibility
nor makes a performance or warranty statement for this material or products and processes containing this material in connection
Wth this report.
PMCamtwcUonllasdalsTechmlogiea LLC 6412Dadger Drive Tampa,FL33610 Te1:813621.5777 Fax813821.5840 e-maikmaledalantJn9@Pdaml.wm w0bS4e:h0p7A•rxw.plcmLmm
INTERNAL REVENUE SERVICE
CINCINNATI OH 45999-0023
SUNRISE ROOFING LLC
ADRIAN BUSTAMANTE SOLE MBR
2181 SE MIDTOWN RD
PORT ST LUCIE, FL 34952
0
0
lam-- �3�g
Compliant with Florida Building Code 2017 (61h ed.)
Compliant with Florida Product Approval Rule q 61G20-3
Compliant: Keystone Certifications
Product: 5 V Crimp 26GA Steel Roof Panel FBC Sec.1507.4.2
RECEIVED.
MAR 13 2818
Permitting Department
St. Lucie County
Yield strength: 50 ksi min.; Attached to min.15/32" plywood or Wood
Deck w/ min. 0.42 specific gravity with screws. 24" Coverage
Rib Height 3/8"
Corrosion Resistant Compliant: FBC Sec.1507.4.3
Fastener 1(Method 1 Attachment): #9 x 1-1/2" Hex -Washer Head wood screw* to penetrate
3/16" min. thru deck or 5/8 embedment into wood plank. (*or sufficient length to meet
requirements)
Fastener (Method 2,3, & 4 Attachment): #10 x 1-1/2" Hex -Washer Head wood screw* to
penetrate 3/16 min. thru deck or 5/8" embedment into wood plank. (*or sufficient length
to meet requirements)
Underiayment: To be compliant with FBC Sec. Chart 1501.1.1
Slope: Shall be in compliance with FBC Sec.1507.
See Fastener attachment specifications above
Install Details: Table A Allowable Loads
METHOD 1
_METHOD 2
METHOD 3_. _
_ METHOD 4 "
DESIGN PRESSURE .
-86 PSF
-93.5 PSF
-101 PSF
-228;PSF.__ .
ROW.SPACING_. _ _
:.__ _16"_o.c. -.
_ 16" o.c._. - _
8" O.C.
6" o.c.
FASTENER SPACING (ALONG Panel width),.
12" o.c.
12" o.c..-
12" o.c.
12"-o.c. _
FASTENER SIZE
#9
#10 ,
.., .
#10
#10
Reference Data: ARCHITECTURAL TESTING, INC. TST ID#:1527
UL 580-06 & 1897-041 Test Report DES893.01-450-18 05/02/14
Test Report F13366.01-450-18 12/18/15
Us 125-03 Test Report D05893.02-450-18 07/22/14
*EQUIVALENCY-UL 1897-04 is equivalent to test standard UL 1897-1(rrnr *Design
pressure margin of safety2:1
Locke Bowden, P.E. does not have, not will acquire a financial
under this evaluation.
Locke Bowden, P.E. is not owned, operated, or controlled by;
report.
V
coAparNombbilfakturer, or
distributing products
products under this
4.'
FI-17022.1 5V Grirnp (26GA Steel), 24" Wide Roof I el - Details
Limitations:
1. Underlayment to be compliance with current Florida Building Code (FBC)2017 6th ed.
2. Minimum slope to be compliant with Florida Building Code 2017 61h ad., and per with Manufacturer's installation reference.
3. Products are compliant for State of Florida product approval per Rule 61 G20-3. Compliance Method: 1-D
4. Engineering analysis for "project specific approval by local authorities w/jurisdiction is allowed by other registered engineers.
5. Fire classification is not part of this acceptance. Shear diaphragm values are outside this report.
6. Support framing in compliance w/FBC 2017 6th ad., Chapter 22 for Steel, Chapter 23 for Wood and Chapter 16 for
Structural Loading.
7. This report does not imply warranty, installation, recommended product use outside of this report.
— Fasteners -
#9.1-112"Mtn. or
#10 z 1-1/2' Min. per Table A' for Row 9-V Crimp Roof Panel
Spacing and Design Pressures
Hex Washer Head Wood Screws
Deck:
.15132" a greater Plywood, or
- Wood plank
24'
37
Panel Profile
Nominal 12" _ Nominai 12'
O.C. o.c.
Fasten '
g x -1/2" Min. or #10 x 1-1/2" Min. per
Table "A" Hex Washer Head Screw
Spaced 12" c.c. across the Panel Width
Panel Refer to Table "A" for Spacing Along Panel
Overlap Length
Deck-15/32" or greater
Plywood, or
-Wood plank