HomeMy WebLinkAboutTEST REPORTS - BLOWER DOOR -DUCTa � � 151ighryears, Inc 15 776 Bennett Drive Longwood, Florida 32750 June 1, 2018 L, , To: Local Building Department (ightyears SCANNED BY St. Lucie County a RE: Blower Door Test & Duct Leakage Test Reports To whonfit may concern, This letter is to request that the attached forms be accepted for compliance of the 2017 Florida Building Code statute R402.4.1.2 Envelope leakage testing (Blower Door Testing) and R403.3.3.Duct testing...... The attached forms were provided by the Florida Bulding Commission as the accepted forms to be submitted. These forms are listed on the 2017 Florida Building Code; Energy Conservation Technical Assistance Manual, Document Number. TAM-2017-1.0, released February 02, 2018, pages R-78,through R-80 (page numbers 156-161). Web link provided for quick access to the TAM document htfpsa/tlnyurl.com/2017FBC-TAM These forms meet all three required Residential Energy Efficiency'Compliance Paths listed under R401.2, Prescriptive, Performance, and Energy Rating Index (ER4 paths. We are working with building departments across Florida to standardized the form submittal process and , would like your department to allow thesedorns to meet compliance. If there are any issues with accepting these forms, please reach out to me directly and I will ensure that we submit any 'specific form that you will require. Tim Smith (407)-951-3236 tsmith@151fghtyears,com Respectfully, / 2 TlmothyZih== 1S Lightyears, Chief Operations 0%ficer Energy Technical Advisor RESNET Quality -Assurance Designee , IECC Residential Energy Inspector/ Plans Examiner Member Bur7d rrg Ofhcia1S Association of FlOdde Memberand Code Development Committee padiclpaffng member. Also, representative to the Florida Building Commissions, Ene Advisory Committee for the BOAF-CDC rgy Technical Ift Planning & Development Services Building 6 Code Regulation Division 2300 Virginia Ave, Rm 201 Fort Pierce, FL 34962 772462-2165 Fax M4624M FBC ENERGY CONSERVATION CODE Duct Searing CertlRc38on Prescriptive and Performance Method Date: �,\ Pemalft: cSIL—i�3^OTq� 1 Loth: 21 Contractor: R�#'�-� Address: MG— Corshiction: a Post ConsWctonTest oRoughinTest Test Conditlons: u Date: Floor Area (ft2):. 1 �� Time: Primary Location of Supply Ductwork Indoor Temperature.(F): "js' - Primary Location ofReturn Ductwork . Outdoor Temperature(F): - Total Leakage Test (Outsidel � Dud Leakage: a Default a Prop. Leak Free ee<ro ed On TestPressure: Baseline Dud Pressure footionan rani Total Leakage (rim): 01 ::� Total Leakage perlWsgft 0-0/7 CFM25 x 100 d'mded by the CFA= Dud Leakage CFW160 sq0. Testfnn Comoa Company Name: isL S Address: 214B#KnzL+ i�lri�rtg ratio k—, -- SCANNED BY St. Lucie County I hereby certify that the above Duct Searing Leakage results den onstrate compliencewflh 5e Edition FBC Energy Conservation requirements In accordancewrli Section R40322 Signature: Printed Name: rVbr, ucenselcert mate 8: I VL(pg b Certificate of Achievement THIS ACKNOWLEDGES THAT Alexander Rivera .HAS MET THE STANDARD REQUIRED BY 1S lightye rs Inc, RESNET QUALITY ASSURANCE AS A RESIDENTIAL ENERGY FIELD ANALYST REFA # 1'51-6981 Certification Date: March 1, 2019 Certification Expires: March 1, 2020 Tim Smith, RESNET Quality Assurance Designee 15 lightyears RES9ET QA Provider # (1998-199) /�63 - 6190 Planning & Development Services ` Building & Code Regulation Division -; 2300 Virginia Ave, Rm I01 _ Fort Pierce, F134982 Phone'. M-462-2165 Fax: M-46;-6443 BLOWER DOOR TEST FORM ` House Infiltration Test Certification Prescriptive and Performance Method File COPY _SCANNED BY St. Lucie County Date- Ili_ �ilT Permit#: SLC fRD3- Oil _ Contractor: s Job Address: Asa lot@ Qo� (:.h : -C_W_ Construction: ( w"ew'Construction—Complete ( • )Existing—Af6rAdd)tlon House Infiltration �esults SLC Climate Zone 2 CFM (50),= Test Date: Volume = ACH (50) = CFM (50) x 60 / Volume = lv • / mechESW Ventilation required less than 5 ACH Passing results must be & ACH (50) or less ( . ass ( ) Fail . FBC, Energy The building or dwelling unit shall.be tested and verified as having an air leakage rate of not exceeding Z air changes per hour In Climate Zone 1, 2 and 3 air changes per hour In Climate tones 3 through B. Testing shall be conducted with a blower door at a pressure of 0.2Inches w. g. (50 Pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7); Florida Statutes or individuals licensed as set forth in Section 489.205 (3)(f), (g) or (1) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code officlal. Testing shall be performed at any time after rreation of all penetrations of the building ,thermal envelope. FBC;Residential--'--.__:_._•--.._....;.-- _..�._.._.__----:..-_—.__.. ---_..--•--_--._. Where the air infiltration rate of a dwelling unit is less than Lalrchanges per hourwhen tested with a blower doorata pressure of 0.21nch w. c. (50 Pa) in accordance with Section R402.4.1.2 of the Florida Building Code, Energy Conservation -the dwelling unit shall be provided with whole•house mechanlcal0entllationtn'accordance with Section M3507.3. Testlna Company ' ` l Company Name: (�1nl'Irnni Address:I'V4 n4i+- Dyo �cN� wg��• - —17. . I hereby certify that the above House Infiltration results demonstrate compliance with FBC Energy Conservation requirements in accordan with Section R402.4.1.2 Climate Zone 2. Signature: _ _ 1�_ {� r Printed Name: ba%fav �v Prva✓a Ucense/Certification #: IS'(et%'