HomeMy WebLinkAboutGENERATOR CONCRETE PAD�\ \ GENERATOR
LD
PAD
THICKNESS
PAD DIMENSIONS:
CONCRETE PAD
GENERATOR -
r
T BY
SEPARATE I ESUBMITTAL
(SEE SCHEDULE FOR
MINIMUM WEIGHT
REQUIRED)
�- 54" LENGTH
PLAN VIEW
CONCRETE
MAC100
AMERICAST GENERATOR CONCRETE PAD
(ON -GRADE APPLICATIONS ONLY)
1
HVHZ OR NON-HVHZ
RISK
EXPOSURE (EXP)
RISK
EXPOSURE EXP)
RISK
POSURE(EXP)
COUNTY
I
C
D
II
C
D
III, IVC
D
P. BEACH
150 MPH
30.44 Psf
36.94 Psf
170 MPH
39.09 Psf
47.44 Psf
180 MPH
3 Psf
L46.80Psf56.8OPsf
53.19 Psf
BROWARD
156 MPH
32.92 Psf
39.95 PSf
170 MPH
39.09 Psf
47.44 Psf
18O MPH
3 Psf
53.19 Psf
MIAMI-DADE
165 MPH
36.83 PSF
44.69 Psf
175 MPH
41.43 Psf
50.28 Psf
186 MPH
ISOMETRIC VIEW
R1
3" MIN s4" MIN
GENERATOR TABLE:
BRAND &MODEL
CAPACITY
WIDTH
LENGTH
HEIGHT
WEIGHT
ALLOWABLE
PRESSURE
COMMENTS
Generac 005871 & 005883
IO KW
25.00"
48.00"
29.00"
3871bs
41.43 Psf
EXP C 175 MPH &D 156 MPH
Generac 005872 & 005884
14 KW
25.00"
48.00"
29.00"
4391bs
47.44 Psf
EXPC 186 MPH &D 156 MPH
Generac 6459, 6461, 6462
16 KW
25.00"
48.00"
29.00"
513lbs
47.44 Psf
Generac 006721
16 KW
25.00"
49.00"
29.00"
4481bs
47.44 Psf
Generac 005873 & 005885
17 KW
25.00"
48.00"
29.00"
4551bs
47.44 Psf
Generac 005874 & 005886
17 KW
25.00"
48.00"
29.00"
4211bs
47.44 Psf
Generac 005875 & 005887
20 KW
25.00"
48.00"
29.00"
4511bs
47.44 Psf
Generac 006729 & 006730
20 KW
25.00"
48.00"
29.00"
516lbs
47.44 Psf
Generac 006551 & 006552
22 KW
25.00"
48.00"
29.00"
5261bs
47.44 Psf
Kohler 14RES&20RES
14-20 KW
26.00"
48.00"
29.00"
5001bs
47.44 PSf
GE 40323GE & 40324GE
13 KW
35.00"
39.40"
39.00"
5401bs
39.09 Psf
EXPC 170 MPH &D 156 MPH
GE04038215KW
15 KW
33.00"
48.00"
30.50"
4841bs
43.83 Psf
EXP C 180 MPH &D 156 MPH
GE 04037817KW
17 KW
33.00"
48.00"
30.50"
484lbs
43.83 Psf
GE 40330GE&40331GE
20 KW
33.00"
48.00"
30.50"
6001bs
43.83 Psf
Briggs& Stratton 040243.0
10 KW
31.00"
32.00"
34.00"
430lbs
43.83 Psf
Briggs & Stratton 040302-2
12 KW
33.75 "
50.00"
31.60 "
5071bs
41.43 PSI
EXP C 175 MPH & D 156 MPH
Briggs&Stratton 040303.1
15 KW
33.75"
49.00"
31.60"
5621bs
43.83 Psf
'
EXP C 180 MPH & D 156 MPH
Briggs & Stratton 040304-1
18 KW
33.75 "
49.00"
31.60 "
5681bs
44.00 Psf
Briggs&Stratton 040305-1
20 KW
33.75"
49.00"
31.60"
5701bs
44.00 Psf
Generac 7035, 7036, 7037
16 KW
25.00"
48.00"
29.00"
406lbs
47.44 Psf
EXP C 186 MPH &D156 MPH
Generac 007038 & 007039
20 KW
25.00"
48.00"
29.00"
448lbs
47.44 Psf
Generac 007042&7043
22 KW
25.00"
48.00"
29.00"
466lbs
47.44 Psf
GENERATOR MOUNTING CONFIGURATION:
GENERATOR
GENERATOR ATTACHMENT BASE
OR SIMPSON A24 ANGLE BRACE
W/ (4) A30 SS 316 SELF -DRILLING
SCREWS
1 TO GENERATOR
FS (SEE ONCRETE PAD
SCHEDULE FOR
UU
DIMENSIONS & WEIGHT
REQUIRED)
�32" WIDTH-54" LENGTH
SIDE VIEW
FRONT VIEW
(SEE
ANCHOR TO PAD SCHEDULE:
SUBSTRATE
DESCRIPTION
CONCRETE:
(2)-3/8"0 TITER HD
(6000 PSI
OR EQUIVALENT,
MIN.)
2-3/4" FULL EMBED
O CONCRETE, 3" MIN
EDGE DISTANCE, 6"
MIN. SPACING TO ANY
ADJACENT ANCHOR.
NOTES:
1. ANCHOR QUANTITY PER LONG SIDE
2. EMBEDMENT AND EDGE DISTANCE
EXCLUDES FINISHES, IF
APPLICABLE.
3. ENSURE MINIMUM EDGE DISTANCE
AS NOTED IN ANCHOR SCHEDULE.
4. ENSURE MINIMUM SPACING TO
ANY ADJACENT ANCHORS.
S. FOLLOW MANUFACTURER'S
INSTALLATION INSTRUCTIONS TO
INSTALL ANCHORS.
GENERATOR
ATTACHMENT BASE,
VARIES WITH MODEL
SEE GENERATOR SPECS
%" SIMPSON TITEN HD, -
SEE ANCHOR SCHEDULE
2"x3"x%" GALV. STEEL
WASHER
RUBBER VIBRATION PAD
THICK GALVANIZED
WASHER& RUBBER
VIBRATION PAD
Z
CONCRETE PAD -
6,000 PSI
LIGHTWEIGHT
CONCRETE PAD
X
CONCRETE MIX t
6,000 PSI
LIGHTWEIGHT
\ MASTERFIBER
MAC 100
& ROAD MESH
CONCRETE MIX
NOTES:
FOAM CORE
1. Y DISTANCE DEPEND ON GENERATOR BASE LENGTH, NO LESS THAN 2".
2. X DISTANCE 3" FROM UNIT EDGE TO CLIP.
3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO LESS THAN
ANCHOR REQUIREMENTS
t-- 2„--f
WIND DESIGN REOUIREMENTS
(BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH EDITION
(2017))
AT -GRADE SIGN METHOD
ULTIMATE DESIGN WIND SPEED Vult = 186 mph
NOMINAL DESIGN WIND SPEED Vasd = 144 mph
RISK CATEGORY = III INTERNAL PRESSURE COEF = N/A
EXPOSURE CATEGORY = D WIND DIRECTIONALITY FACTOR Kd=
0.85
ENCLOSURE CATEGORY = N/A HEIGHT H = AT GROUND
GUST EFFECT FACTOR = 0.85 PRESSURE AT HEIGHT H qh = 77.56
Ib/ft2
FORCE COEFFICIENT Cf = 1.44
WIND PRESSURE:
P = Chi G Cf = 56.80 Ib/ft2 (ASD)
GENERAL NOTES
1. THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED IN
ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE
SIXTH EDITION (2017).
2. REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR USE WITH
THIS SYSTEM SHALL BE DETERMINED UNDER SEPARATE CERTIFICATION ON A
JOB -SPECIFIC BASIS IN ACCORDANCE WITH THE GOVERNING CODE.
SITE -SPECIFIC LOAD REQUIREMENTS AS DETERMINED INACCORDANCE WITF
THE APPLICABLE BUILDING CODE SHALL BE LESS THAN OR EQUAL TO THE
DESIGN PRESSURE-ASD" CAPACITY VALUES LISTED HEREIN FOR ANY
ASSEMBLY AS SHOWN.
3. DIMENSIONS AND WEIGHT OF UNITS SHALL CONFORM TO SPECIFICATIONS
STATED HEREIN.
4. UNITS MUST BE CENTERED ON PAD WITH OPPOSITE SIDES HAVING EQUAL
CLEARANCE. A MINIMUM DISTANCE FROM UNIT TO PAD EDGE IS SPECIFIED.
5. CALCULATIONS MADE USING LIGHTWEIGHT CONCRETE 125 PCF
6. THE AREA UNDER CONCERETE SLOB ON GROUND SHALL HAVE ALL
VEGETATION, STUMPS, ROOTS, AND FOREIGN MATERIALS REMOVED PRIOR
TO INSTALLATION ON COMPACTED SOIL AS VERIFIED BY OTHERS.
7. RESISTANCE TO SLIDING OF THE PAD ON THE GROUND IS NOT PART OF THIS
DOCUMENT AS SOIL CHARACTERISTICS AND PAD PLACEMENT VARIES.
S. ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED & INSTALLED BY
OTHERS. ALL MECHANICAL SPECIFICATIONS (CLEAR SPACE, TONNAGE, ETC.)
SHALL BE AS PER MANUFACTURER RECOMMENDATIONS AND ARE THE
EXPRESS RESPONSIBILITY OF THE CONTRACTOR.
9. ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS
INCLUDING LEGAL FEES & APPELLATE FEES RESULTING FROM MATERIAL
FABRICATION, SYSTEM ERECTION, CONSTRUCTION PRACTICES BEYOND THAT
WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES & FROM
DEVIATIONS OF THIS PLAN.
10. WATER -TIGHTNESS OF EXISTING FINISHES SHALL BE THE FULL
RESPONSIBILITY OF THE INSTALLING CONTRACTOR. CONTRACTOR SHALL
ENSURE THAT ANY REMOVED OR ALTERED WATERPROOFING MEMBRANE IS
RESTORED AFTER FABRICATION AND INSTALLATION OF SNLUCTURE
PROPOSED HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY
WATERPROOFING OR LEAKAGE ISSUES WHICH MAY OCCUR AS
WATER -TIGHTNESS SHALL BE THE FULL RESPONSIBILITY OF THE INSTALLING
CONTRACTOR.
11. THE ROLE OF THIS ENGINEER FOR THIS PROJECT 15 THAT OF SPECIALTY
ENGINEER AND NOT THE ENGINEER OF RECORD. CONSEQUENTLY, THE
ARCHCTECT/ENGINEER OF RECORD SHALL BE RESPONSIBLE FOR THE
INTEGRITY OF ALL SUPPORTING SURFACES TO THIS DESIGN WHICH SHALL
BE COORDINATED BY THE PERMITTING CONTRACTOR.
12. THIS DOCUMENT IS GENERIC AND DOES NOT PERTAIN TO ANY SPECIFIC
PROJECT SITE. INFORMATION CONTAINED HEREIN IS BASED ON
CONTRACTOR -SUPPLIED DATA AND MEASUREMENTS. ENGINEERING EMPRESS
SHALL NOT BE HELD RESPONSIBLE OR LIABLE IN ANY WAY FOR ERRONEOUS
OR INACCURATE DATA OR MEASUREMENTS. DIMENSIONS ARE SHOWN TO
ILLUSTRATE DESIGN FORCES AND OTHER DESIGN CRITERIA. THEY MAY VARY
SLIGHTLY, BUT MUST REMAIN WITHIN THE LIMITATIONS SPECIFIED HEREIN.
WORK SHALL BE FIELD VERIFIED BY OTHERS PRIOR TO CONSTRUCTION.
ENGINEERING EMPRESS SHALL BE NOTIFIED AND GIVEN AN OPPORTUNITY TO
REEVALUATE OUR WORK UPON DISCOVERY OF ANY INACCURATE
INFORMATION PRIOR TO MODIFICATION OF EXISTING REM CONDITIONS
AND FABRICATION AND INSTALLATION OF MATERIALS. ALTERATIONS OR
ADDITIONS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE OUR
CERTIFICATION.
13. EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERTIFICATIONS
ODED
R t0ARE I)n"--N2Z,171-0 SCANNED
B NARDO, P.E.
549 n(�
018
'O E.4VFARS a.'
M. A .STO, P.E.
O VUN
IF -THIS SHEET DOES.
TAIN AN ORIGINAL
[RE & ENGINEER SEAL
15 A DIGITAL
is ON SHEET 1, THIS
PART OF A DIGRALLY
LE, SHALL REMAIN IN
ORMAT, & PRINTED
IFTHISDOCUMENT
CONSIDERED SIGNET
LED. IF THERE IS NO
RGNAWRE ON SHEET 1
;HEEr DOES NOT
AN ENGINEER'S
u O N
oy
ST o
STnu,.e
W FFL tij LLmvim
WLI1110 LL(A Xw#
zO T Ozx
/�IL 4Q LU�w LB'� O
1I11'' O O z L DO- E
W W N n w W u
y W Qp z
LD
3LL w
U)W'xW
O W W
�O
V/
U
H
LU
G
Q
RIGHT ENGINEERING E% SS
17-3961.1
I
St. Lucie County