HomeMy WebLinkAboutEVALUATION REPORT'\lTwrviTr EVALUATION EXTERIOR RESEARCH & DESIGN, LLC. SCANNED Certificate ojAuthorization#9503 ERD BY 353 CHRISTIAN STREET, UNIT#13 St. Lucie Countv OXFORD, CT 06478 (203)262-9245 TRI-BUILT Materials Group, LLC PO Box 70 Rutherford, NJ 07070 (800)516-1485 ition Report A42960.10.12-R6 FL16048-R6 Date of Issuance:10/25/2012 Revision 6: 09/25/2017 SCOPE: This Evaluation Report is issued under Rule 611320-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under She Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 6w Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: TRI-BUILT Roof Underlayments LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. Trinityl ERD requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words 'Trinityl ERD Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 6. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DC4 ANE1983 lbe haW.DeseaI p,aann,.a auNorrzed by Robert Nia.1., P.E M �!25/2017. Tha does not serve as an eleaaoni,aRysiened dmn em CERTIFICATION OF INDEPENDENCE: 1. Trinityl ERD does not have, nor does it Intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. Trinityl ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. S. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. - _ ROOFING COMPONENT EVALUATION: 1. PIP C3 4. S. �TRINITY ERD SCOPE: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: TRI-BUILT Roof Underlayments, as produced by TRI-BUILT Materials Group, LLC, have demonstrated compliance with the following sections of the 61h Edition (2017) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. STANDARDS: Section 1504.3.1 1504.3.1 1504.6 1507.2.4 / 1507.1.1, 1507.2.9.2 1507.3.3 REFERENCES: fnNim ERD (TST6049) ERD (TST6049) ERD (TST6049) ERD (TST6049) ERD (TST6049) ERD (TST6049) ERD (TST6049) ERD (TST6049) ERD (TST6049) ERD (TST6049) ERD(TST6D49) ERD (TST6049) ERD (TST6049) UL, U.C. (QUA9625) UL, LLC..(QUA9625) Property Wind Resistance Wind Uplift Accelerated Weathering Physical Properties Physical Properties Examination Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Physical Properties Accelerated Weathering Wind Resistance Quality Control Quality Control Standard FM 4474 UL 1897 ASTM G155 ASTM D1970 FRSA/TRI April 2012 (04-12) Reference S40540.02.13-1 S40540.11.13 S40540.03.14 S44870.04.14-2 S44870.04.14-3 S44870.04.14-1 S44870.04.14-4 S43530.02.14-1-R1 S43530.05.14 540540.10.14 SC7645.02.15 SC8520.04.15 SC14045.05.17-91 Multiple -Listing R16814 Service Confirmation Year 2011 2012 2005 2015 2012 Date 02/19/2013 11/19/2013 03/26/2014 04/02/2014 04/02/2014 04/10/2014 04/10/2014 05/14/2014 05/28/2D14 10/31/2014 02/13/2015 05/27/2015 06/07/2017 12/10/2015 Exp. 07/18/2020 PRODUCT DESCRIPTION: 4.1 Tri-Built Sand-R SA Shingle Underlayment is a self -adhering, glass -mat reinforced, sand -surfaced, SBS modified bitumen roof underlayment, with a 36-inch sheet width; meets ASTM D1970. 4.2 Tri-Built 5/A HT TU Underlayment is a self -adhering, non -woven polyester fabric surfaced, SBS modified bitumen roof underlayment; meets ASTM D1970 and FRSA/TRI April 2012. 4.3 Tri-Built Smooth HT S/A Underlayment is a self -adhering, glass -mat reinforced, film -surfaced, SBS modified bitumen roof underlayment; meets ASTM D1970. LIMITATIONS: 5.1 This is.a building code evaluation. Neither TrinityjERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions. 5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of this product. Exterior Research and Design, LLC. Evaluation Report A42960.30.12-R6 CeWffcate afAuthorization#9503 6' EDITION(2017) FBC NON-HVHZ EVALUATION F1.16048-116 TRI-BUILT Roof Underlayments; (800) 516-14SS Revision 5: 09/25/2017 Page 2 of 6 SA 5.5 \l TRINITY ERD TRI-BUILT Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. Allowable Roof Covers: - _ COV -STABLE 1: ROOF_FROpiIONS :- Underlayment Asphalt Shingles Nail -On Tile Foam -On Tile Metal Wood Shakes Slate &Shingles Tri-Built Sand-R SA Shingle Underlayment Yes No No No Yes yes Tri-Built S/A HT TU Yes Underlayment Yes Yes See 5.5.1 Yes Yes Yes TrizBbilt'Smodth HT,S%A_) a:UnderlaymenttS Wes-3 No No LYesj Yes lYes] 5.5.1 "Foam -On Tile" is limited to use of the following Annrnverltilamr1 nee- .. .. _-__ _____.. _........ I w''­ 'ur Is IGII. 6Vn IUIIId LIUM. - TABLE IA: ALLOWABLE TILE ADHESIVE /UNDERL_AYMENT .C_OM_ 91NATIDNS1 Adhesive Florida Product Approval _ Underlayments ICP Adhesives PDlyseto AH-160 FL6332 Tri-Bulk S/A HT TU Underlayment Dow TileBond"' FL22525 Tri-Built S/A HT TU Underlayment 5.6 Allowable Substrates: 5.6.1 Direct -Bond to Deck: Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A Underlayment applied to; ➢ Plywood; ASTM D41 primed plywood; OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern Yellow Pine; ASTM D41 primed structural concrete. While not required over plywood, OSBor Southern Yellow Pine substrates, TRI-BUILT Materials Group, LLC recommends priming the deck if the final roof cover is not slated for installation within 24 hours. Note: TRI-BUILT Materials Group, LLC requires tongue -and -groove boarddeckingbe covered with plywood or OSB prior to installation of the self -adhering underlayment. 5.6.2 Bond -to -Insulation: Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A Underlayment applied to: ➢ Dens Deck Prime; SECUROCK Gypsum -Fiber Roof Board. For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile systems (Tri-Built S/A HT TU Underlayment only), insulation attachment shall be designed by a qualified design professional and installed based on testing of the insulation/underlayment system in accordance with FM 4474, Appendix D orTAS 114,Appendix J. 1 Refer to Tile Manufacturer's or Adhesive Manufacturers Florida ProducYApproval for Overturning Moment Resistance Performance. Exterior Research and Design, Ur Evaluation Report A429fi0.10.12-R6 Ce�cate of Authonzation#9503 6'x EDITION (2017) FBC NON-HVHZ EVALUATION FL36048-116 TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6: 09/25/2017 Page 3 of 6 5.6.3 Bond to Mechanically Attached Base Laver: \l I KINrrY ERD Tri-BuiltSand-RSA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A Underlayment applied to:_ ➢ ASTM D226, Type I or II felt. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under foam -on bile systems (Tri-Built S/A HT TU Underlayment only), base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04- 12). 5.6.4 Wind Resistance for Underlayment Systems in Foam On Tile Applications: FRSA/TRI April 2012 (04-12) does not address wind uplift resistance of all underlayment systems beneath foam -on file systems, where the underlayment forms part of the load -path. The fallowing wind uplift limitations apply to direct -deck underlayment systems that are not addressed. in FRSA/TRI April 2012 (04-12).and are used in foam -on tile applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to. FRSA/TRI April 2012 (04-12), Appendix A, Table 1A or FBC 1609 for determination of design wind pressures. #1 Maximum Design Pressure = -45 0 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: (Optional) ASTM D41 or RESISTO EXTERIOR PRIMER Underlayment: Tri-BuiltS/A HT TU Underlayment, self -adhered. #2 Maximum Design Pressure =-67 5 osf: Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: Soprema Elastocol 600c Underlayment: Tri-BuiltS/A HT TU Underlayment, self -adhered. #3 Maximum Design Pressure=-1500psf: Deck: Min. 15/32-inch APA-rated BCX plywood (may be installed C-side up) to meet project requirements to satisfaction of Authority Having Jurisdiction. Deck Preparation: Plywood shall be thoroughly cleaned to remove dust and debris that may inhibit adhesion. All sheathing fasteners shall be driven flush with the surface. All sharp splinters and wood projections shall be removed/sanded. Primer: (Optional) RE51STO EXTERIOR PRIMER Underlayment: Tri-Built 5/A HT TU Underlayment, self -adhered, shall be thoroughly roll using hand roller and/or weighted roller to ensure there are no voids, and ensure there are no voids/bridging at side and end -laps. 44 Maximum Design Pressure=-600psf: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. . Base Sheet: Soprema Sopra-G or Modified Sopra-G mechanically attached with nails (FBC 1517.5.1) and tin caps (FBC 1517.5.2) spaced 6-inch o.c. at the 4-inch laps and 6-inch o.c. in three, equally spaced rows in the center of the sheet. Underlayment: Tri-Bui1tS/A HT TU Underlayment, self -adhered. Exterior Research and Design, LLC. Evaluation ReportA4296D.10.12-R6 Csrtifcete ofAuthoAzoUon d9503 6' EDIT10N (2017) FBC NON­HVHZ EVALUATION FU604B-R6 TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6: 09/ZS/2017 Page 4 of 6 \1 I R Nrry ERD 5.6.4.1 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly sh all meet or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density designed by a -qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk' carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29:(January 2016) for Zone 2/3. enhancements. 5.7 Exposure Limitations: Tri-Built Sand-R SA Shingle Underlayment or Tri-Built Smooth HT S/A Underlayment shall not be left exposed for longer than 30-days after installation Tri-Built S/A HT TU Underlayment shall not be left exposed for longer than 180-days after installation. 5.8 Tile Slippage Limitations (TAS 103 per FRSA/TRI April 2012 (04 12))- When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. ' TABLE 2: TILESLIPPAGE LIMITATIONS FOR DI RELT-_DECKTLEINSTALLATIoNs Underlayment Tile Profile Staging Method _ Maximum Slope Flat Max. 10-tile stack 6:12 Lugged Max. 30-tile stack 512 Max. 10-tile stack (bottom 2-tile stack shall be inverted, followed by 8 tiles high 6:12 on slope, as shown below) �1^, Si 11` Tri-Built S/A HTTU Underlayment Lugged Exterior Research and Design, LLG Evaluation ReportA42960.10.12-R6 Certlflcote afAuthori:adon l<9503 6'v EDMON(2017)FBC NON-HVHZ EVALUATION FL16048-R6 TRI-BUILT Roof Undedayments; (800) 516-1485 Revision 6:09/25/2017 Page S of 6 ,l I KINIIY I ERD S. INSTALLATION: 6.1 TRI-BUILT Roof Underlayments shall be installed in accordance with TRI-BUILT Materials Group, LLC published installation. requirements subject -to the Limitations set forth in Section "S herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application, and prime the substrate (if applicable). 6.3 Tri-Built Sand-ft SA Shingle Underlayment Tri-Built S/A HT TU Underlayment or Tri Built Smooth HT S/A Underlayment, 6.3.1 Shall. be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table 1507.1.1 for the type of prepared roof covering to be installed. 6.3.2 Non -Tile applications: While priming is optional, TRI-BUILT Materials Group, LLC recommends priming the deck if the final roof cover is not slated for installation within 24 hours. Apply sheet parallel to the roof edge. Roll out approximately 10 ft of membrane and peel back the first 3 ft of release film. Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible. Once the entire length of membrane is in place, peel -off the release film diagonally while holding the membrane tight. Firmly roll, broom or hand -press the membrane into place to achieve a bond. Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6- inches and staggered not less than 2-ft from vertical seams in the course below, sealed in accordance with TRI-BUILT Materials Group,. LLC requirements. Wheninstalling at slopes above 8:12, TRI-BUILT Materials Group, LLC recommends back -nailing in the overlap area at the top of the sheet at 12-inch o.c. For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet over valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge in each direction. For valleys, apply the sheet starting at the lowest point and work upward. 6.3.3 Tile Applications(Tri-Built S/A HT TU Underlayment only): Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions noted above as a guideline. For foam -on tile applications, reference is made to Section 5.6.4 herein for wind resistance limitations that fall outside the scope of FRSA/TRI April 2012 (04-12). Tile shall be loaded and staged in a manner that prevents the slippage and/or damage to the underlayment. See Table 2 herein, and TRI-BUILT Materials Group, LLC published requirements for tile staging. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. B. MANUFACTURING PLANTS: Gulfport, MS 9. QUALITY ASSURANCE ENTITY: UL, LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com - END OF EVALUATION REPORT - Exterior Research and Design, U.C. Evaluation Report A42960.10.12-R6 Certi/Imte of Authorization#9503 6'"EDITION (2017)FBC NON-HVHZ EVALUATION FL16048-RG TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6: 09/25/2017 Page 6 of 6 EVALUATION REPORT OF METAL SALES MANUFACTURING CORPORATIS(:ANNED 126 GA. 5V-CRIMP PANEL' BY St. Lucie County FLORIDA BUILDING CODE 6TH EDITION (2017) FLORIDA PRODUCT APPROVAL FL 14645.4-R3 ROOFING METAL ROOFING Prepared For: Metal Sales Manufacturing Corporation 545 South 3rd Street, Suite 200 Louisville, KY 40202 Telephone: (502) 855-4300 Fax: (502) 8554290 Prepared By: Bala Sockalingam, Ph.D., P.E. Florida Professional Engineer 062240 1216 N Lansing Ave., Suite C Tulsa, OK 74106 Telephone: (918) 492-5992 FAX`. (918) 493-3568 This report consists of Evaluation Report (3 Pages including cover) , o �`Ss����urrrN Installation Details (1 Page) %OCKAk/ !., Load Span Table (1Page) .`P%,P-'GENs*,- -vy.�� m; a No 62240 �131 . STATE OF441 Report No. C21824 1..�0 _ ..a P Date: 9.9.17 `.,��`S • O R •' C?,`� -� . q. '201—? Manufacturer: Product Name: Panel Description: Materials: FL 14645.4-R3 C2182-4 9.9.17 Page 2 of 3 Metal Sales Manufacturing Corporation SV-Crimp 24" wide coverage with (5) 1/2" high ribs Min. 26 ga., 50 ksi steel. Galvanized coated steel (ASTM A653) or Galvalume coated steel (ASTM A792) or painted steel (ASTM A755). Deck Description: Min. 7/16" thick OSB or min. 15/32" thick plywood or min. '/4" thick wood plank (min SG of 0.42) for new and existing constructions. Designed by others and installed as per FBC 2017. Deck Attachment: 8d x 2.5" long ring shank nails or #8 x 2" long wood screws @ 6" o.c. (Minimum) in the plywood field and edges. Designed as per FBC 2017. Underlayment: Minimum underlayment as per FBC 2017 Section 1507.4.5.1. Slope: 1/2:12 or greater in accordance with FBC 2017 Section 1507.4.2. Requires applied lap sealant for roof slopes less than 3:12. Design Uplift Pressure: 30.0 psf @ fastener spacing of 36" o.c. (Factor of Safety = 2) 172.5 psf @ fastener spacing of 6" o.c. Fastener Pattern: Type: #9-16 or #10-14 hex head wood screws with sealed washer. Fastener shall be of sufficient length to penetrate through the deck a minimum of 3/8" and installed as per Metal Sales current installation procedure. At panel ends @ 6" o.c. across panel width At intermediate @ 12" o.c. across panel width Test Standards: Roof assembly tested in accordance with UL580-06 `Uplift Resistance of Roof Assemblies' & UL1897-04 `Uplift Tests for Roof Covering Systems'. Test Equivalency: The test procedures in UL 1897-04 comply with test procedures prescribed in UL 1897-12. Code Compliance: The product described herein has demonstrated compliance with FBC 2017 Section 1507.4. Product Limitations: Design wind loads shall be determined for each project in accordance with FBC 2017 Section 1609 or ASCE 7-10 using allowable stress design. The maximum fastener spacing listed herein shall not be exceeded. The design pressure for reduced fastener spacing may be Supporting Dobuments: U'. ) & 1897 Test Reports PRI Construction Materials Technologies MSMC-017-02-01, Reporting Date 9/20/13 FL 14645.4-R3 C2182-4 9.9.17 Page 3 of 3 computed using rational analysis prepared by a Florida Professional Engineer or based on Metal Sales load span table. This evaluation _report is not applicable in High Velocity Hurricane Zone. Fire classification is not within scope of this Evaluation Report. Refer to FBC 2017 Section 1505 and current approved roofing materials 6i 6A PANEL OVERLAP 5V-CRIMP FASTENER AT PANEL FLAT SEE DETAIL 2 / SEE DETAIL 1 REQUIRED FOR PANEL a ENDS ONLY. D ' I MINIMUM ATTACHMENT: PANEL FASTENER PER UPLIFT LOAD TABLE fid K 2.5' LONG RING SHANK NAIL UNDRIAYMENT SHALL BE INSTALLED OR is • 2' LONG WOOD SCREWS AS PER MANUFACTURERS INSTALLATION SPACED 0 6' O.C. IN THE FIELD ¢ GUIDELINES d:, AT EDGES MIN. 2X_ WOOD RAFTER/JOIST/ a TRUSS AT MAX. 24' O.C. n TYPICAL PANEL INSTALLATION X—SECTION 19-16 OR 110-14 WOODSCREWS WITH SELF SEALING WASHER AT MAXIMUM SPACING OF 36' O.C. 5 in 5V-CRIMP 09 MIN 26 GA d GENERAL NOTES• p S 1. ARCHITECTURAL ROOF PANEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE a @ qH FLORIDA BUILDING CODE (FBC). UNDERLAYMEM 2. ROOF PANELS SHALL BE MIN: 26 GA (t - 0.019'). EFFECTNE COVERING E POS LYWOOD 1 THICK (MIND OR ' DETAIL 1 PLYWOOD 15/32 THIGH (MIN.) WIDTH'OF PANEL = 24'. 3. THE ROOF PANELS SHALL BE INSTALLED. OVER SHEATHING k STRUCTURE AS11 SPECIFIED ON THIS DRAWING. m 4. REQUIRED DESIGN MIND LOADS SHALL BE DETERMINED FOR EACH PROJECT. THIS A9-16 OR'{110-1M1 WOODSCREWS PANEL SYSTEM MAY NOT BE INSTALLED WHEN THE REQUIRED DESIGN WIND LOADS WITH SELF SEALING WASHER AT ARE GREATER THAN THE DESIGN UPLIFT PRESSURES' SPECIFIED ON THIS DRAWING.ALL ' MAXIMUM SPACING OF 36' O.C. 5 BUILDI GTEUST CODE. NERS MF A DIFFER NCEBINRTH OCCURS DANCE (BETWEEN TTHISRHEE MINIMUM THE FLORIDA REQUIREMENTS OF THIS DRAWING & THE CODE. THE CODE SIAN.L CONTROL 4 /— MIN RIMGA. 6 REQUIRERAFTERSD EACH APPLICATION ANDST BE ENARE THE RESIGNED TO PONTAND WIND LOADS AS SIBILITY OF OTHERS. $ UNDERLAYMENTJ \—OSB 7/16" THICK (MIN) OR 11 DETAIL 2 PLYWOOD 15/32' THICK (MIN.) I A, METAL. SALES MANUFACTURING CORPORATION 5V-Crimp Uplift Loads (Min. 26 ga.) Description - Fastener Spacing along panel length (in) Allowable Uplift Load (psfl Coverage width: 24" Panel Fasteners #9-16 or #1044 hex head wood screws with sealed washer 6 172.5 9 120.0 __ 1:2 s C900'3 15 72.0 18 60.0 _ 21 51.4 24 45.0 27 40.0 30 36.0 33 32.7-- _ 36 30.0 Notes: 1. The bold numbers indicate design loads calculated from test data with safety factor of 2. 2. Panels must be installed as per Evaluation Report FL 14645.4 and Metal Sales current.. installation procedure. 3. Three or more spans condition. 1216 N Lansing Ave., Suite C Tulsa, Ok 74106 918 492 5992 `pttltutt°r `%% SOCKgZI, J-*, No 62240 aY ; STATE OF O R 1.0 p\�O 4.h.2c,\-7 Bala Sockalingam, Ph.D., P.E. FL 62240 EXTERIOR RESEARCH & DESIGN, LLC. SCANNED Certificate of Authorization#9503 TRINITY I ERD BY 353 Christian Street St. Lucie County Oxford, CT. 06478 (203)262-9245 EVALUATION REPORT TRI-BUILT Materials Group, LLC Evaluation Report A42970.10.12-R2 PO Box 70 FL16027-RZ Rutherford, NJ 07070 Date of Issuance: 10/23/2012 (800) 516-MBS Revision 2: 09/25/2017 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for compliance with the 6th Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: TRI-BUILT Modified Bitumen Roof Systems LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. Trinity[ ERD requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. . ADVERTISEMENT: The Evaluation Report number preceded by the words 'Trinity, I ERD Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPErnON: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection atthejob site at the request of the Building Official. This Evaluation Report consists of pages 1 through 4, plus a 26-page Appendix. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DC4 ANE1983 i r Imfle.e.l appeal cwoo auhor vl by Robert NiemN , PZ.09/25/2017. misdre, not nerve as an electronipllysigned do< mem CERTIFICATION OF INDEPENDENCE: 1. Exterior Research & Design, U.C. d/b/a Trinity I ERD does not have, nor does it intend to acquire or will it acquire, a financlaI interest in any company manufacturing or distributing products it evaluates. 2. Exterior Research & Design, LLC, d/b/a Trinity I ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial Interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entmA involved in the approval process of the product S. This is a building code evaluation. Neither Trinity] ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. TRINITY i ERD ROOFING SYSTEMS EVALUATION: 1. SCOPE: Product Category: Roofing Sub -Category: Modified Bitumen Roof Systems - Compliance Statement: TRI-BUILT Modred Bitumen Roof Systems, as produced by TRI-BUILT Materials Group, LLC, have demonstrated compliance with. the fallowing sections of the 60' Edition (2017) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Property Standard Year 1504.3.1 Wind FM 4474 2011 1504.7 Impact FM 4470. 2012 1507.11.2 Physical Properties ASTM D6163 2008 1507.11.2 Physical Properties ASTM D6164 2011 1507.11.2 Physical Properties ASTM D6222 2011 3. REFERENCES: Enti Examination Reference Date ERD (TST6049) Physical Properties P10490.10.08-2 10/30/2008 ERD (TST6049) FM 4470/4474 P13760.09.09 09/10/2009 ERD (TST6049) FM 4470/4474 P13770.09.09 09/10/2009 ERD (TST6049) FM 4470/4474 P30540.11.09-111 11/30/2009 ERD (TST6049) FM 4470/4474 P30550.12.09 12/02/2009 ERD(TST6049)Physical Properties. P33960.12.30 12/30/2010 ERD (TST6049) FM 4470/4474 P33970.03.11 03/15/2011 ERD (TST6049) Physical Properties P37590.03.13-3A 03/06/2013 ERD (TST6049) FM 4470/4474 P39680.03.13 03/04/2013 ERD (TST6049) Physical Properties P37590.03.13-1-111 06/26/2013 ERD (TST6049) Physical Properties P37590.03.13-2-RS 07/01/2013 ERD (TST6049) Physical Properties P37590.07.13-2 07/01/2013 ERD(TST6049)Physical Properties P37590.03.13-5-R1 07/01/2013 ERD (TST6049) Physical Properties P37590.07.13-1 07/02/2013 ERD (TST6049) Physical Properties P45940.09.13 09/04/2013 ERD'(TST5049) Physical Properties P44370.10.13 10/04/2013 FM Approvals (TST1867) FM 4470 2W7A7.AM 08/04/1994 FM Approvals (TST1867) FM 4470 OD3A3.AM 04/04/1997 FM Approvals (TST1867) FM 4470 2DOAO.AM 12/23/1998 FM Approvals (TST1867) FM 4470 2DSA9AM 06/22/1999 FM Approvals (TST1867) FM 4470 3006646 01/04/2000 FM- Approvals (TST1867) FM 4470 3001334 01/25/2000 FM Approvals (TST1867) FM 4470 3001334 02/15/2000 FMApprovals (TST1867) FM 4470 3000857 01/12/2000 FM Approvals (TST1867) FM 4470 3004091 01/12/2000 FM Approvals (TST1867) FM 4470 3006115 05/02/2001 FM Approvals (TST1867) FM 4470 3012321 07/29/2002 FM. Approvals (TST1867) FM 4470 3014692 08/05/2003 FM Approvals (TST1867) FM 4470 3014751 08/27/2003 FM Approvals (TST1867) FM 4470 3007170 01/13/2004 FM Approvals (TST1867) FM 4470 3019317 06/30/2004 FM Approvals (TST1867) FM 4470 3020703 07/30/2004 FM Approvals (TST1867) FM 4470/4474 3018332 01/31/2006 FM Approvals (TST1867) FM 4470/4474 3023368 03/20/2006 FM Approvals (TST1867) FM 4470/4474 3024594 05/23/2006 Exterior Research and Design, U.C. Evaluation Report A42970.10.12-RZ cerdfiuHr a7Authoritution 99503 6`vEDI nON(20171 FBC NON-HVHZ EVALUATION F116027-112 TRI-BUILT Modified Bitumen Roof Systems; (860)516.1485 Revision 2:09/25/2017 Page 2 of , TRINITY ERD EntitV Examination Reference Date FM Approvals (TST3867) FM 4470/4474 3023458 07/18/2006 FM Approvals (TST1867) FM 4470/4474 3030668 09/12/2007 FM-Approvals(TST1867) FM4470/4474 3032172 06/12/2009 PRI (TST5878) Physical Properties PUSA-062-02-01 12/04/2007 PRI (TST5878) Physical Properties PUSA-061-02-02 01/28/2008 PRI(TSF5878) Physical Properties PUSA-064-02-02 02/27/2008 PRI (TST5878) Physical Properties PUSA-062-02-02 12/04/2008 Miami -Dade (CER1592) HVHZ Compliance Various NOAs Various Miami-Dade(CER1592) Proposal for Review 10-0823 10/12/2010 UL LLC (QUA9625) Quality Control MI -Agreement 02/27/2012 UL LLC(QUA9625) Quality Control ML Correlation, R27202 08/20/2012 UL LLC (QUA9625) Quality Control Service Confirmation, R14571 Exp. 10/06/2018 4. PRODUCT DESCRIPTION: This Evaluation Report covers TRI-BUILT Modified Bitumen Roof Systems installed in accordance with TRI-BUILT Materials Group, LLC published installation instructions and the Limitations / Conditions of Use herein. The following membranes make up the subject systems. Table;l:.Roll-Goods for TRI-BUILT-Mollified Bitumen Roof Systems Type. Product Specification Reference Grade Type SBS Membranes TriBuilt SA SBS Base ASTM D6163, Table 2 5 I TriBuilt SBS Granular ASTM D6164 G I TriBuilt SA SBS Cap ASTM D6164 G I APP Membranes TriBuilt APP Smooth ASTM D6222 5 I TriBuilt APP Granular ASTM D6222 G I TriBuilt SA APP Cap ASTM D6222 G 1 5. LIMITATIONS: 5.1 This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation.Report is not for use in FBC HVHZ jurisdictions. 5.3 Refer to a current. Approved Roofing Materials Directory for fire ratings of this product. 5.4 For steeldeckinstallations, foam plastic insulation shall be separated from the building interior in accordance with FBC 2603.4 unless the exceptions stated in FBC 2603.4.1 and 2603.6 apply. 5.5 The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. 5.6 For recover installations, the existing roof shall be examined in accordance with FBC 1511. 5.7 For mechanically attached insulation or membrane or strip -bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16. Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI VIDl, FM Loss Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk' carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. Exterior Research and Design, I.I.C. Evaluation Report A42970.10.12-R2 Cemfrote of Awhorkadon#9503 6TMEDITION 12017)FBC NON-HVHZ EVALUATION FL16027-R2 TRI-BUILT Modified Bitumen Roof Systems, (800)S16d485 Revision 2:09/25/2017 Page 3 of 4 TRINITY ERD 5.8 For assemblies with all components fully bonded in place, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 26. No rational analysis is permitted for these systems. 5.9 For mechanically attached insulation or membrane over existing roof decks, fasteners shall be tested in the existing deck for withdrawal resistance: A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105. 5.10 For bonded insulation or membrane over existing substrates in a re -roof (tear off) or recover installation, the existing deck or existing roof surface shall be examined for compatibility with the adhesive to be Installed. If any surface conditions exist that bring system performance into question, field uplift testing in accordance with ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124 shall be conducted on mock-ups of the proposed new roof assembly. 5.11 For bonded insulation or membrane over existing substrates in a recover installation, the existing roof system shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with ASTM E907, FM Loss Prevention. Data Sheet 1-52 or Testing Application Standard TAS 124. 5.12 Metal edge attachment (except gutters), shall be designed and installed for wind loads in accordance with FBC Chapter 16:and tested for resistance in accordance with ANSI/SPRI ES-1 or Roofing Application Standard RAS 111, except the basic wind speed shall be determined from FBC Figure 1609.3(1), 1609.3(2) or 1609.3(3). 5.13 All products in the roof assembly shall have quality assurance in accordance with FAC Rule 61G20-3. 6. INSTALLATION: 6.1 TRI-BUILT Modified Bitumen Roof Systems shall be installed in accordance with TRI-BUILT Materials Group, LLC published installation instructions,subject to the Limitations / Conditions of Use noted below. 6.2 System attachment requirements for wind load resistance are set forth in Appendix 1. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FBC 1609 for determination of design wind loads. 7. BUILDING PERMIT REQUIREMENTS:, As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. 8. MANUFACTURING PLANTS: Contact the noted QA agency for information on product locations covered for -F.A.C. Rule 61G20-3 CIA requirements. 9. QUALITY ASSURANCE ENTITY: UL LLC— QUA9625; (314) 578-3406, k.chancellor@us.ul.com - THE26-PAGES THAT FOLLOW FORM PART OF THIS EVALUATION REPORT - Exterior Research and Design, U.C. Evaluation Report A42970.10.12-R2 certiifwte afAuthorirodoo 495d3 6oEDITION (2017) FBCNON-HVHZ EVALUATION FL16027-RZ TRI-BUILT Modified Bitumen Roof Systems; (800) S16-1495 Revision 2:09/25/Z017 Page 4 of 4 \! I KINIlY I ERD Table Deck Application Type Description Page 1A-1 Wood New or Reroof (Tear -Off) A-2 Mech. Attached AnchorSheet, Bonded Insulation, Bonded Roof Cover 4 2A Steel or5tructural concrete New. Reroof (Tear-Offl or Recover B Mech. Attached Base Insulation. Bonded Too Insulation. Bonded Roof Cover 9 3A Structural concrete New or Reroof (Tear -Off), A-1 Bonded Insulation, Bonded Roof Cover 11-14 3B Structural concrete New or Reroof (Tear -Off) F Non -Insulated, Bonded Roof Cover 14 4A LWIC New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded,Roof Cover 15-16 48 LWIC .New or Reroof (Tear -Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 16 4C LWIC New or Reroof (Tear -Off) - - E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 17-19 5A CWF New or Reroof(Tear-Off) A-1 Bonded Insulation, Bonded Roof Cover 20 SB CWF New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 21 5C CWF New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 22 SD CWF New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 22 SE CWF New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 22 6A Gypsum New or Reroof (Tear-Ofo A-1 Bonded Insulation, Bonded Roof Cover 23 6B Gvosum New. Reroof (Tear-Offlor Recover A-2 Mech. Attached Anchor Sheet. Bonded Insulation. Bonded Roof Cover 24 6D Gvosum New, Reroof (Tear -Off) or Recover E Non-Insulated-Mech. Attached Base Sheet, Bonded Roof Cover 24 25-26 7B Various Recover F Non -Insulated, Bonded Base Sheet Bonded Roof Cover 26 The following notes aooly to the systems outlined herein: 1. The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall be In accordance with FBC requirements to the satisfaction of the Authority' Having Jurisdlctlon, Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. 2. Insulation / base sheet fasteners shall be of sufficient length for the following deck engagement: D Wood: Minimum 0.75-Inch penetration. D Steel: Minimum 0.75-Inch penetration and engage the top flute of the steel deck. D Structural concrete: Minimum 1-Inch embedment Into pilot hole in accordance with fastener manufacturers published Installation Instmcticns. 3. Unless otherwise noted, Insulation may be any one layer or combination of polylsocyanurate, polystyrene, wood fiberboard, perlite, gypsum -based roof board or mineral -wool roof board that meets the CA requirements of F.A.C. Rule 61G20.3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC Chapter 26, when Installed with the roof cover. Exterior Research and Design, LLC. d/b/a Trinityj ERD Evaluation Report A42970.10.12-R2 for FL36027-R2 Certlfiate of Authorization 99503 67H EDITI ON (2017) FBC NON-IJVH2 EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI•BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 1 of 26 `�! I KINM( ERD Minimum 200 psi, minimum 2-Inch thick lightweight. Insulating concrete may be substituted for rigid Insulation board for System Type D (mechanically attached base sheet; bonded roof cover), whereby the base sheet fasteners are Installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codlfled and/or FBC Approval documentation. S. Preliminary insulation attachment for System Type D: Unless otherwlse noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016). 6. Unless otherwise noted, insulation adhesive application rates are as follows.Ribbon or bead width Is at the time of application; the ribbons/beads shall expand as noted In the manufacturer's published Instructions. ➢ HA (HA): Full coverage at 2530lbs/square. ➢ Dow INSTA STIK Quik Set Insulation Adhesive (D-IS); Continuous 0.75 tot -inch wide ribbons, 12-Inch o.c. D Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-Inch wideribbons, 12-Inch c.c. D OMG OlyBond 500 (08500): Continuous 0.75 to 1-Inch wide ribbons, 12-Inch o.c. (PaceCart or SpotShot). Note. Olyliond Green may be used where 01yBond'500 Is referenced. ➢ OlyBond Classic (OB Classic): Full mverage at 1 gal/square.. ➢ ICP Adhesive & Sealants CR-20: Continuous 2.5-3.5-Inch wide ribbons, 12-Inch o.c. ➢Note: When multiplelayersfs) of Insulation and/or coverboard are Installed In ribbon-opplled adhesive; adhesive ribbons shall be smggeredfrom layer -to -layer a distance ofone-ho/ll ribbon spacing. D Note: The maximum edge distance from the adhesive ribbon to the edge of the Insulation board shall be not less than one-half the specified ribbons spacing. 7. Unless otherwise noted, all insulations are Rat stock or taper board of the minimum thickness noted. Tapered palyisoryanurate at the following thickness limitations may ba substituted with the following Maximum Design Pressure (MDP) limitations. In no case shall these values be used to 'Increase' the MDP listings In the tables; rather if MDP listing below meets or exceeds that listed fora particular system In the tables, then the thinner board listed below may be used as a drop -In for the equivalent thicker material listed In the table: D Millennium One Step Foamable Adhesive (M-OSFA): MDP -157.5 psf (Min. 0.5-Inch thick) ➢ OMG OlyBond 500 (08500): MDP -45.0 psf (MIn. 0.5-Inch thick Multi -Max FA-3) ➢ OMG OlyBand 500 (OB500): MDP -187.5 psf (Min. 0.5-Inch thick ISO 95+GL) ➢ OMG OlyBond 500 (OB500): MDP -315.0 psf (Min. 0.5-Inch thick ENRGY 3) ➢ OMG OlyBond 500 (OB500): MDP -487.5 psf (Min. 0.S-Inch thick ACFoam II) ➢ICP Adhesive & Sealants CR-20: MDP -117.5 psf (Min. 1.0-Inch thick). & Bonded polylsocyanurate Insulation boards shall be maximum 4 x4 ft 9. For mechanically attached components or partially bonded Insulation, the maximum design pressure for the selected assembly shall meet or exceed the. Zone 1 design pressure determined in accordance with FBC Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI%SPRI WDl, FM Loss Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk- carry the limitations set forth In Section 2.2.10.1 of FM Loss Prevention Data Sheet 1.29 (January 2016) for Zone 2/3 enhancements. 10. For fully bonded assemblies, the maximumdesign pressure for the selected assembly shall meet or exceed critical design pressuredetermined in accordance with FBC Chapter 16, and no rational analysis is permitted. 11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be In accordance with ANSI/SPR( FX-1 or Testing Application Standard TAS 105. 12. For existing substrates In a bonded recover or re -roof Installation, the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive, and the existing roof system (for recover) shall be capable of resisting project design pressures on Its own merit to the satisfaction of the AuthorityHaving Jurisdiction, as documented through field uplift testing in acmrdance with ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52orTesting Application Standard TA5124. 13. For Recover Applications using System Type D, the Insulation Is optional; however, the existing roof system shall be suitable fora recover application. 14. Lightweight Insulating Concrete (LWC) shall be cast In accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC Is referenced, refer to current LWC Product Approval for specific deck construction and limitations. For systems where specific LWC Is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top -coat thickness is 2-inches. For LWC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1. Exterior Research and Design, U.C. d/b/a Trinity IERD Evaluation Report A42970.10.12-R2 for FL36027-R2 Certificate of Authorization 119503 6rx EDITION (2017) FBC NON-HVHZ EVALUATION Revlslon 2:09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 2 of 26 QI' RINITY ERD 15. Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications. . TABLE I:TRI•BUILT ROOF. COVERS Reference Layer Material Application BP -AA Base Ply FBCApproved ASTM.D4601, Type 11 (Base and Ply sheets,Asphalt-Applled) 'HA at 20-40lbs/square Ply FBC Approved ASTM D2178, Type IV or VI (SBS, A , S B ISAsphalt-Applied) Cap Ply TriBuIIt SBS Granular HA at 20-40 lbs/square SBS-TA (SBS, Torch -Applied) Cap Ply TrIBUIIt S8S Granular Torch -Applied SBS-SA Base Ply TrlBullt SA SBS Base (SBS, Self-Adhedng) Cap Ply TrlBullt SASBS Cap Self -Adhering APP-TA Base Ply or Ply TrlBullt APP Smooth (APP, Torch -Applied) Torch -Applied' Cap Ply TrlBuilt APPSmooth, TrlBUilt APP Granular APP SA (APP, Self -Adhering) Cap Ply TriBuilt SA APP Cap Self -Adhering i 16. Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following Maximum Designse . Pressure (MDP) limitations. The lesr of the MDP listings belowvs. those In Table 3A applies: VAPOR BARWER OPTIONS; STRUCTURAL CON [RErE DEG, ADHERED INSUTAVON PER TABLE 3A. ,. I., Option g Pflmer Vapor Bawler Insulation Adhesive MDP(psf) Type Attach VB-1. ASTM D41 TriBuIIL SA SBS Base Self -Adhering Inta-Stlkor CR-20,12-inch o.c -60.0 VB-2. ASTM D41 TrIBUIlt SA SBS Cap Self -Adhering Insta-StIk, 12-inch o,c. -75.0 VB-3. ASTM D41 TrIBuIItSA SBS Cap Self -Adhering MillenniumOne Step Foamable Adhesive, 12-inch o.c -157.5 VB-4. ASTM D41 TriBuilt SA 5B5 Cap Self -Adhering CR-20, 12-Inch o.c. -270.0 VB-S. ASTM D41 TriBuilt SA SBS Base Self -Adhering Millennium One Step Foamable Adhesive, Millennium PG-1 Pump'Grade Adhesive, OlyBond 500 or CR-20,12-Inch o.c. -290.0 17. Dens Deck shall be Reld-primed with PG100 prior to self -adhering membrane application. Refer to tables herein for other priming requirements. 18. "MDP"= Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads. Exterior Research and Design, U.C. d/b/a Trinity I ERD Evaluation Report A42970.10.12-R2 for FL36027-RZ Certificate of Authoriration M9503 67" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2:09/25/2017 Prepared by: Robert Nleminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800I 516-1485 Appendix 1, Page 3 of 26 `J I RINITY ERD TABLE IA-1: WOOD DECKS —NEW CONSTRUCTION OR REROOF(TEAR=OFF) SYSTEMI TYPE A-2t MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER'` System Deck Anchor Sheet Base Insulation Top Insulation Roof Cover(Note.15) MOP No. (Note 1) Type Fasteners Attach Type Attach Type Attach Base Ply Ply 'Cap Ply IPsf) Min. 0.25-Inch Dens Polyglass G2 Base, B-Inch o.c. in 4- Deck, Dens Deck Prime, MIn. 19/32- CertalnTeed Glasbase, 32 Be., 1.5/8- Inch lap and8- (Optional) FBC SECUROCK Gypsum- Inchplywood Firestoneed Base,JM Inch diameter Inch o.c. in Approved, Fiber Roof Board, Min. (Optional) SBS-AA, W-1 at max. 24- Perma-Ply 28, Tamko tin caps with 11 three, equally ASTM C3289, HA 0.75-Inch FescaBoard HA BP -AA BP -AA SBS-TA, -60.0 Inch spans Glass Base or ga. annular ring spaced, type ll polylso- (homogeneous) or min. APP-TA GAFGLAS H75 shank nails staggered cyanurate 0.5-Inch Structodek center rows High Density Fiberboard Roof Insulation Polyglass G2 Base, 8-Inch o.c. In 4 Min. 19/32- CertalnTeed GI 32 32 ga., 1-5/8- Inch lap and 8- (Optional) FBC Min. 0.25-Inch.Dens (Optional) SBS-SA, Inch plywood Firestone MB Base, JM Inch diameter Inch o.c. in Approved, - Deck, Dens Deck Prime, One or W-2 Tamko .tin caps with 11 three, equally ASTM C3289, HA SECUROCK Gypsum- HA SBS-SA more SBS- SiS-TA, 505-TA or •60.0 In hspmaxans- Inch spans GlassBPerma-se or Glass Base or ga annular ring spaced, type ll polyiso- Fiber Roof Board SA or APP-TA GAFGLAS g75 shank nails staggered fig cyanurate APP-TA center rows 32 ga., 1-5/8- 6-Inch o.c. in 4- Inch lap and 6• Min. 2-Inch D-ES, OBS00, Min. 19/32- Polyglass Elastobase Inch diameter Inch o.c. In ACFoam II, III, CR-20 or M• MIn:0,25-Inch Dens 615; SBS-AA, W-3 Inch plywood or Polyglass tin caps with 12 four, equally OStenatop Deck, Dens Deck Prime 0, BP -AA (Optional) 565-TA, -60.0• Elastobase PolyShield �. annular ring spaced, ShieldH-ShlC , Ca fastener Gypsum- CR-2 r BP -AA APP-TA In h spans Inch spans shank nails staggered -Multi-Maz FA3 rows, 7-inch Fiber Roof Board er Roof Bo Fiber M-DSF M-OSFA center rows or ENRGY-3 oc 6-Inch o,c. in 4- Min. 2-Inch 0.15, OB500, Min. 19/32- 32 ga., 1-5/8- Inch lap and 6- ACFoam 11, III, CR-20 or M- D-IS, (Optional) SBS-SA, Inch plywood Polyglass Elastobase Inch diameter Inch o.c. in H-ShIeId, H- OSFA, atop (Optional) Additional 08500, One or APP-SA, W-4 or Polyglass On caps with 12 four, equally Shield CG, fastener layers of base Insulation CR-20 or SBS-SA more SBS- SBS-TA or -60-V In hspans- Inch spans Elastobase Poly ga. annular ring spaced, Muitl-Max FA3 rows, 7-Inch M-OSFA or APPTA shank nails staggered or ENRGY-3 oc AP APP-TA center rows Exterior Research and Design, U.C. d/b/a TrinityI ERD Evaluation Report A42970.10.12-R2 for F1.16027-112 Certificate of Authorization 89503 6rx EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nleminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) SM1485 Appendix 1, Page 4 of 26 `�! 1 KINITY J ERD TABLE1A-2: WOOD DECKS— NEW CONSTRUCTION, REROOP(TEAR-OFF)GR RECOVER - - - -SYSTEMTYPE'A-2r MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION; BONDED ROOF COVER System Deck Anchor5heet Base Insulation Top Insulation Roof Cover (Note 25) MDP No. (Note 1) Type Fasteners Attach Type. Attach Type- Attach Base Ply Ply Cap Ply (Psf) 12-Inch o.c. in 4- Min. 0.25-inch Dens Deck, Min. Polyglass OMG Flat Inch lap and 12- (Optional)FBC Dens Deck Prime, SECUROCK W-6 Inch I lywoo plywood p Elastobase or Polyglass Bottom Plates Inch o.c. in two, Approved, ASfM C3289, HA Gypsum -Fiber Roof Board, (Optional) SBS-AA,SBS- at max. 24 (square) with a uall s aced, y p Min. 0.75-Inch FescoBoard HA BP -AA BP -AA - TA, APP-TA -60.0 Inch spans Elastobase Roofgdp R32 staggered center type ll polyiso- (homogeneous) or min. 0.5- Poly cyanurate Inch S[ructodek High Density rows Fiberboard Roof Insulation MIn.19/32- Pol lass YB OMG Flat 12-Inch o.c. in 4- Inch lap and 12- (Optional) FBC (Optional) Inch plywood Elastobase or Bottom Plates Inch two, Approved, Min. 0.25-Inch Dens Deck, One or SBS•SA, APP. W-6 Polyglass (square) with equally spaced, equally ASTM C3289, HA Dens Deck Prime, SELUROCK HA S85-SA more SBS- SA, SBS-TA -60.0 Iat nch spans inch spans Elastobase Roofgdp R32 staggered center type ll polyiso- Gypsum -Fiber Roof Board SA or APP- or APP-TA PolyI cyanurate TA rows TABLE 10: WOOD DECKS. -NEW CONSTRUCTION, REROOF,(TEAR-OFF) okRECOVER ' " -' SYSTEM TYPES: MECHANICALLYATTACHEDBASE INSULATION, BONDED TOP,INSUL_A_TION; BONDED ROOF COVER - System Deck (Note 1) Base Insulation Layer Top Insulation layer Roof Cover (Note 15) _ MDP No. Type Fasteners Attach Type Attach Base Ply Ply Cap Ply (psf) min. 19/32-Inch Min. 1.5-Inch Dekfast Hex with Min. 0.75-Inch FescoBoard (Optional If (Optional if using W-7 plywood at max. 24-Inch ENRGY 3; H-Shleld Dekfast Hl2 orTruFast 1 per (homogeneous) or min: 0.5-Inch HA using AA Ply) AA Base) One or SBS-AA,'SBS-TA, -60.0 spans or Polytherm MP-3 with TruFast DP 1.33 ft' Structodek High Density Fiberboard BP AA more BP -AA or APP-7A Roof Insulation APP-TA Exterfor Research and Design, I.I.C. d/b/a Trinity IERO Evaluation Report A42970.10.12-R2 for FL16027-R2 Certificate of Authorization.09503 Gr" EDITION (2017) FBC NON-HVH2 EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 5 of 26 � r KINITY ERD TABLE IC;WOOD DECKS -NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER-,'- ' :SYSTEMTYPEC: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER' System Deck (Note 11 Base Insulation Top Insulation Layer - Roof cover (Note IS) MOP Type Fasteners Attach Base Ply Ply Cap Ply No. Layer (Psf) W-8 Min. 19/32-Inch (Optional) One or more layers, Min.0.5-Inch Structodek High Density Fiberboard Roof insulation or min. 0.25- Dekfast Galvalume S.per 1.33 (Optional if (P (Optional if using AA SBS-AA, 585-TA,APP- plywood at maz any combination, Inch Dens Deck, Dens Deck Prime or Steel Hex with r ft using AA Ply) Base) One or more BP -AA TA -82.5 24-Inch s p ans loose laid SECUROCK Gypsum -Fiber goof Board Dekfast #12 DP BP -AA or APP-TA (Optional) Dekfast Galvalume W-9 Min. 19/32-Inch plywood at max Ohe of more layers, Min. 1.5-Inch ENRGY 3, H-Shield or Steel Hex with Dekfast #12 DP or 1 per 1.33 5B5-SA (Optional) One or more SBS-SA, APP-SA, SBS- 24-Inch spans any combination, Polythenn TruFast MP-3 with SBS-SAor APP-TA TAor APPTA 82 5 loose laid TruFast DP - TABLE ID: WOOD DECKS —NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER — SYSTEM TYPED: PRELIMINARILY ATTACHED SULATION,.MECHANICALLYATTACHED BASE SHEET, BONDED ROOF COVER i • , • <' ��- System Deck (Note 11 Insulation Layer(s) Base Sheet Roof [over (Note 1S) MOP No. Type Attach Base Fasteners Attach Base Ply Cap Ply ji Ipsf) Polyglass Elastobase, Polyglass OMG Flat Bottom Plates Min. 19/32-Inch One or more layers, Prelim. Elastobase Poly, Polyglass G2 Base, (square) with Roofgrip 12-Inch o.c. in 4-Inch lap and 12- (Optional) One SBS-AA, W-10 plywood at max, , any combination Attached CertainTeed Glasbase, Firestone MB 414, Dekfast Hex with inch o.c. In two, equally spaced, or more BP -AA SBSTA, -52.5 24-inch spans Base, JM Perma-Ply 28, Tamko Glass Dekfast#14 or TruFast staggered center rows or APP-TA APP-TA Base or GAFGLAS#75 MP-3 with TruFast HD W-11 Min. 19/32-Inch One or more layers, Prelim. Polyglass Elastobase or Polyglass Dekfast Hex with Dekfast 12-Inch o.c. in 4-Inch lap and 12- One or more SBS-SA, APP-SA, plywood spat ans 24-lochs ans any combination Attached Elastohase Poly with poly top surfaceInch st MP-3 with spaced, SBS-SA 5B5-TA -52.5' P TruFast TruFast HD HD staggered center rows staggered center rows APP-TA W-12 Min. 19/32-Inch plywood at max One or mom layers, Prelim. Polyglass Elastobase or Polyglass OMG Flat Bottom Plates 12-Inch o.c. In 4-Inch lap and 12- (Optional) One SBS-AA, 24-Inchs any combination Attached Elastobase Poly (square) with Roofgdp 412 Inch o.c In two, equally spaced, or more BP -AA 5B5-TA, -60.0 spans P staggered center rows or APP-TA APPTA Wd3 Min. 19/32-Inch plywood at max One or more layers, Prelim. Polyglass Elastobase or Polyglass OMG Flat Bottom Plates 12-Inch o.c. In 4-Inch lap and 12- Inch o.c )olio, equally spaced, One or more SBS-SA, APP-SA, 24-Inch spans any combination Attached Elastobase Polywith poly top surface (square with Roofgrip#12 staggered center rows SBS-SA SBS-TA -60,0' APPTA Exterior Research and Design, I.I.C. d/b/a Trinity) ERD Evaluation Report A42970.30.12-R2 for FL36027-R2 Certificate of Authorization #9503 6r"EDITION (20171 FBC NON-HVHZ EVALUATION Revision 2:09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof System; (8001516-1485 Appendix 1, Page 6 of 26 NINITY I ERD . TABLE IE-1:;WOOD DtEKS—. N,EW CONSTRUCTION OR REROOF (TEnR-OFF) SYSTEMTYPE E: NON-INSULATED,:MECHANICALLY ATTACHED BASE SHEET; BONDED ROOF COVER System Deck (Note 3) Base Skeet Roof Cover (Note 15) MOP No. Base Fasteners Attach Base Ply Cap Ply (Psf) W14 Mtn. plywood at Inch max, 24- Polyglass Elastobase SlmplexMA%X Cap 9-inch o.c. at 2-inch la and 18-Inch o.c. in two, P (Optional) or -45.0• Inch spars Inch spans equally spaced, staggered center rows APRTA orAPP-,585-TA or APP TA W-15 Min. plywood at inch man. 24- max Polyglass Elastobase Simplex MAX%Cap 9-Inch o.c. at 2-Inch la and 12-Inch o.c. In two, P (Optional) BP -AA or . -52.5 Inch spans Inch spans equally spaced, staggered center rows APP-TA orAPP-,SB5-TA orAPP-TA Min. 19/32-Inch Polyglass Elastobase, Polyglass Elastobase (Optional) One or W-16 PYvr plywood at max. Poly, Polyglass G2 Base, CertalnTeed 32 ga., 1-5/8-Inch diameter tin caps 8-Inch o.c. In 4-Inch lap and 8-inch o.c. in three, more BP -AA or SBS-AA, SB5- -60.0 24-Inch spans Firestone JIMAF Parma- with 31 ga. annular ring shank nails equally spaced, staggered center rows APP-TA TA, APP-TA Pl 28, T, BMID aseorBase, Ply 28, TamkaGlass Base or GAFGLAS q75 W-17 Min. 19/32-Inch at maz. Polyglass Elastobase or Polyglass 32 ga., 1-5/8-inch diameter tin caps 8-Inch o.c. in 4-Inch lap and 8-Inch o.t%in three, (Optional) One or SBS-SA, APP- plywood Elastobase Pely with poly top surface with 11 ga.. annular ring shank nails equally spaced, staggered center rows more SBS-SA or SA,SBS-TA or -60.0 24-Inch -Inchspans APP-TA APP-TA W-18 Min. 15/32-Inch plywood at max. 24- Polyglass Elastobase Simplex MA%%Lap 6-Inch o.c. at 2-inch lap and 6-Inch c.c. in two, (Optional) BP -AA or sas-AA, SSS-TA .90.0 Inch spans equally spaced, staggered center rows APP-TA or APP-TA W-19 Min. 19/32-Inch Plywood at max. P Y Polyglass Elastobase or Polyglass ga., annul diameter tin caps o.c. in 4-Inch lap and o.c, in four, (Optional)One or SBS-SA,APP- 24-Inch 'Elastobase Poly with poly top surface with ga. with lL.ga. annular ring shank nails. equally equally spaced, staggered center rows enter r more SBS-SA or SA, SBS-TA or -97.5 spans P APP-TA APP-TA MIn, Inch W-20 max. 24- plywood at max Polyglass Elastobase Simplex MAX%Cap 6-Inch O.C.at 2-Inch lap and 6-Inch o.c. in three, (Optional)BP-AA or SBS-AA, SBS-TA -105.0 Inch spans Inch spans equally spaced, staggered center rows APP-TA or APP-TA W-21 Min. 19/32-Inch at max. Polyglass Elastobase or Polyglass 32 ga., 1-5/8-Inch diameter tin caps 6-Inch o.c. In 4-Inch lap and 6-Inch o.c. in four, (Optional) One or SB5-AA, SBS- plywood 24-Inch Elastobase Poly with 11 ga. annular ring shank nails equally spaced, staggered center rows more BP -AA or TA, APP-TA -1125 spans gpp_Tq Min. 19/32-Inch 2-Inch 32ga.,:1-5/g-Inch diameter tin caps SBS-SA, APP- W-22 plywood P Polyglass Elastobase or Polyglass with 11 ga. annular ring shank nails. 6-Inch o.c. In 4-Inch lap and 6-inch o.c. In four, (Optional)One or 5A, SBS-TA or -112.5 24-Inch spans Elastobase Poly with poly top surface Note: Tin caps are to be primed with equally spaced, staggered center rows mare APP-TA APP-TA ASTM D41prlmer. Exterior Research and Design, I.I.C. d/b/a Trinity IERD Evaluation Report A42970.10.12-R2 for FL16OZ7-RZ Certificate of Authorization g9503 6m EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2:09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 7 of 26 rTRINIl1( I ERD TABLE3E2: WOOD DECKS-NEW;CONSTRUCTION, REROOF,,(TEAR-OFF)DR'RECOVER ; •„ SYSTEMTYPE'E NON -INSULATED, MECHANICALLY ATTACHED BASESHEET, BONDED ROOFCOVER System Base Sheet 'Roof Cover (Note 15) MDP No. Deck (Nate 3) Base Fasteners Attach Base Ply Cap Ply (Psf) Min. 19/32-Inch Polyglass Elastobase; Polyglass Elastobase Poly, Polyglass G2 Base, CertalnTeed OMG Flat Bottom Plates (square) with 12-Inch o.c. in 4-Inch lap and12-inch (Optional) One or SBS-AA, SBS- W-1 plywood Glasbase; Firestone MB'Base, JIMPerma- 1p ft with Dekfast 014 two, equally spaced, staggered more BP -AA or TA, APP-TA •5215 pansat 241nch spans Ply 28, Tamko Glass Base or GAFGLAS 475 ruFasex or TruFast MP-3.wi[h TruFast HD or Tru MP-3 with centerrows center a APP-TA Min. 19/32-Inch Polyglas; Elastobase or Polyglass Dekfast Hex with Dekfast 914 or TruFast MP- 12-Inch o.c. In 4-Inch lap and:12-Inch DneormoreSBS- SBS-SA, APP- W-2 plywood at max. Elastobase Poly with poly top surface 3wRh TruFast HD o.c. In two, equally spaced, staggered SA SA; SBS-TA or -52.5" 7A-Inch spans centerrows APP-TA W-3 Min. 19/32-Inch plywood at max. Polyglass Elastobase or Polyglass OMG�FIat Bottom Plates (square) with 12-Inch o.c. In 4-Inch lap and 12-Inch O.C. In two, equally spaced, staggered (Optional) One or more BP -AA or -TA, -60.0 24-Inch spans Elastobase Poly Roofgrip 412 center rows - APP-TA TA, APP-TA AP -TA Min. 19/32-Inch 'plywood PolyglassElastobaseorPolyglass OMG Bottom Plates (square) with 12-Inch o.c. in 4-Inch lap and 12-Inch One or more SBS- SBS-SA, APP- W-4 at max. Elastobase with poly top surface Roofgrip ql2 o.c. In two, equally spaced, staggered SA I SA, SBS-TA or -60.0• 24-inch spans center rows APP-TA TABLE IF:. WOOD DECKS -.NEW cONSTRUCTIONOR REROOF(TEAR-OFF) ` I a „ j - 'SYSTEM TYPE Fr NON -INSULATED, BONDEDROOFCOVER System Deck Primer Roof Cover (Note 15) -MDP Joint Treatment Base Ply Ply [ap ply No. (PA Cw_5.� _MIn 15/32sinch plywoodr I s(OpHonal)ASTM;D41) No~ rie_) SBS=SA f(Optlonal)SB5=5A;arj( SBS SA;-APP-SA; SBS-TA+<(--90:d—_ i lat max 24-inch.spansi `---. 'APP_TA...3 ,or APP_TA0 W-6 MIn. 15/32-Inch plywood (Optional) ASTMD41 Plywood joints are covered with 4-inch wide strips ofTriBuilt SA TriBuilt SA SBS Base (Optional) SBS75A or SBS-SA, APP-SA', SBS-TA - -97.5 at maz,241nch spans SBS Base, rolled Into to create continuous bond. APP•TA or APP-TA Exterior Research and Design, I.I.C. d/b/a Trinity( ERD EvaluationReportA42970:30.12-R2 for FL16027-RZ Certificate of Authorization 09503 6rH EDITION (2017) F13C NON-HVHZ.EVALUATION Revislon 2: 09/25/2017 Prepared by: Robert Nleminen, PE-59166 TRI•BUILT Modified Bitumen Roof Systems; (800) 516.1485 Appendix 1, Page 8 of 26