ST. _.1JCIE COUNTY
PAUL WELCH INC.
Mechanical * Electrical * Civil Engineering
1984 S.W. Biltmore St. Suite#114
Port Saint Lucie, FL 34984
BOCC
Phone (772) 785 - 9888 RECEIVED
Email pwelchinc@aol.com
April 1, 2019
RE: SHAT POST SCANNED
255 NETTLES BLVD, BY
JENSEN BEACH, FL St. Lucie County
SCOPE OF WORK
- INSTALL POSTS FOR REMOVABLE AWNING.
APR 0 2 9019
ST. Lucie county,_Parmitting
FILE COPY
NOTES:
I) THE CONTRACTOR, SUBCONTRACTOR, SUPPLIER, ECT. SHALL VERIFY ALL DIMENSIONS,
CONDITIONS AT JOB SITE, PLANS, SPECIFICATIONS, ECT.
2) STRUCTURAL FEATURES NOT DETAILED ON THESE PLANS WILL BE ADDRESSED BY THE ENGINEER
AS CONSTRUCTION PROGRESSES.
3) ALL WRITTEN DIMENSIONS ON THESE DRAWINGS TAKE PRECEDENCE OVER SCALED DIMENSIONS.
4) ALL CONSTRUCTION MUST COMPLY WITH THE FLORIDA BUILDING CODE (FBC) 2017, FBC 2017
RESIDENTIAL, FBC 2017 PLUMBING CODE, FBC 2017 MECHANICAL CODE, FBC 2017 ENERGY
CONSERVATION, AND THE NEC (NFPA 70) 2014 EDITION.
5) RESIDENCE LOCATED IN NEGLIGIBLE WEATHERING AREA, AND IN VERY HEAVY TERMITE
INFESTATION AREA PER FRC 301.
STRUCTURAL NOTES
1) DESIGN LOADS IN ACCORDANCE WITH ASCE7-10.
2) SOIL BEARING CAPACITY: 2000 PSF (MIN.).
3) SLAB / FOOTINGS TO BE CONCRETE WITH A MINIMUM 2500 PSI COMPRESSIVE STRENGTH
AT 28 DAYS. SEE PLAN FOR SIZES & STEEL REQUIREMENTS.
4) MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS:
FOOTINGS: 3" BEAMS: 1 'h" SUSPENDED SLABS: 1 'h"
5) ALL LUMBER SHALL BE PRESSURE TREATED.
6) SPLITING OR CRACKING OF STRUCTURAL COMPONENTS DUE TO INSTALATION OF
HARDWARE IS NOT PERMITED.
7) UNLESS OTHERWISE NOTED, THE INSTALLATION OF SPECIFIED HARDWARE SHALL
CONFORM TO THE MANUFACTURES INSTRUCTIONS AND STANDARD PRACTICIES.
PAULCH MC.
b1EC4ffiggaQ�
IMBILTMOREST. M
PORT ST. UJC1E, FL
PAID WELCH, P.E. FLA REG 2M
APR 0 12019