HomeMy WebLinkAboutEVALUATION REPORTEXTERIOR RESEARCH & DESIGN,LLC. Certificate o/Authorimdon #9503 353 CHRISTIAN STREET, UNIT013 OXFORD, CT 06478 PHONE: (203) 262-9245 FAX: (203) 262-9243 Evaluation Report E10240.08.08-R4 SCANNED FL5374-114 BY Date of Issuance:09/03/2008 St. Lucie County Revision 4: 03/17/2015 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations .governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 51h Edition (2014) Florida Building Code sections noted herein. DESCRIPTION: East Coast Metals Channel Metals LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. Trinity IERD requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity)ERD Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INsPErnoN: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 7. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DCA ANE1983 T.-Trki NITY HERD EVALUATION REPORT East Coast Metals, Inc. 2301 West 8 Lane Hialeah, FL 33010 The f e0eIIp seal appeuinr was authorized try Rpbea Nieminen, P,Em0 117N0n. TNsdmnW seneasanhIWmn4aWV,,r hI document WWI. sealed hatdwPles hauebeen tnnsntitted tptM! R d,hppror Mminktratarandto the wined scent CERTIFICATION OF INDEPENDENCE: 1. Trinity) ERD does not have, nor does It intend to acquire or will It acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. Trinity) ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being Issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial Interest in any other entity involved In the approval process of the product. S. This is a building code evaluation. Neither Trinity ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. ROOFING COMPONENT EVALUATION: %RINITYIERD 1. SCOPE: Product Category: Roofing . Sub -Category: Roofing Accessories that are an Integral Part of the Roofing System Compliance Statement: East Coast Metals Channel Metals, as produced by East Coast Metals, have demonstrated compliance With the following sections of the Florida Building Code through testing In accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Property Standard Year 1507.3.7 Installation, non-HVHZ FRSA/fRI April 2012 (04-12) 2012 1518.8.1 Installation, HVHZ RAS 118, 119 & 120 1995 1523.6.S.2.2 Static Uplift Resistance TAS 101 1995 1711.2.1 Static Uplift Resistance SBCCI SSTD 11 1997 3. REFERENCES: Erdlty Examination . Reference Date ERD(TST6049) Static Uplift Resistance E42730.08.13 08/23/2013 ERD(TST6049) Static Uplift Resistance ECM-SC6795.12.14-1 02/2712015 ERD(T5T6049) Static Uplift Resistance ECM-SC6795.12.14-2 02/27/2025 Florida TEC (TST7393) TAS 101 S10-62SR 10/27/2010 PRI(TST5878) TASI01 ECM-M-02-01 09/22/2001 PRI (TST5878) TAS 101 ECM-003-02-01 06/13/2008 PRI (TST5878) TAS 101 ECM-004.02-01 06/13/2008 PRI (TST5878) TAS 101 ECM-005.02-01 06/13/2008 PRI (TST5878) TAS 101 ECM-006-02-01 06/13/2008 PRI (TSF5878) TAS 101 ECM-007-02-01 06/13/2008 PRI(TST5878) TAS101 ECM-008-02-01 06/13/2008 Florida Building Code Attachment Requirements FRSA/rRI April 2012 (04-12) 04/2012 Florida Building Code -HVHZ Attachment Requirements RAS 118,119 and 120 1995 East Coast Metals Metal Quality MITI Certifications Various Architectural Testing (QUAIB44) Quality Control Participation Letter Exp. 12/31/2019- 4. PRODUCT DESCRIPTION: 4.1 Hip & Ridge Channel Metal: Pre -formed metal channel designed for use as a hip and ridge base to which roof tiles are bonded in FBC Approved roof tile adhesive. Hip & Ridge Channel Metal Is available in 119-3/8-Inch L+ 3/8-inch) length by 2.5, 3, 3.5, 4, 5, 6 or 7-Inch (13/8-inch) heights with 1.5-inch (t 1/16-inch) deck -flanges. Exterior Research and Design, U.C. Evaluation Report E10240.08.08-114 CertiflW a ofAuthorlmdun /9503 FL5374-R4 Revision 4: 03/17/2015 Page 2 of 7 T­TR JNITYjERD i. 4.2 Trim Lock Channel Metal: Pre -formed metal channel designed for use as a hip and ridge base to which roof tiles are bonded in FBC Approved roof tile. adhesive. Trim Lock Channel Metal is characterized by its profiled and perforated upper horizontal flange designed to receive and allow for interlock with the overlying tile adhesive. Trim Lock Channel Metal is available in 119-3/8-inch L 3/8") length by 3, 3.5, 4, 5 or 6-inch I± 3/8-inch) heights with 1.5-inch (± 1/16-inch) deck -flanges: 4.2 Trim Lock Plus Channel Metal: Pre -formed metal channel designed for use as a hip and ridge base to which roof tiles are bonded in FBC Approved roof tile adhesive. Trim Lock Plus Channel Metal Is characterized by its profiled and perforated upper horizontal flange designed to receive and allow for interlock with the overlying tile adhesive and its perforated deck flanges, designed for installation atop the roof underlayment via placement in FBC Approved roof tile adhesive, which flows -through and interlocks with the underlying adhesive. Trim Lock Plus Channel Metal is available in 119-3/8-inch (± 3/8") length by 3, 3.5, 4, 5 or 6-inch (± 3/8-inch) heights with 1.5-inch (± 1/16-inch) deck -flanges. 4.4 East Coast Metals Channel Metals are fabricated of the following. metals: > Galvanized Steel: Min. 0.019±0.0024nch, ASTM A653 (G-90), min. 33 KSI. ➢ Galvalume.Steel: Min. 0.019±0.002-Inch, ASTM A702, AZ55, min. 35 KSI. > Aluminum: Min. 0.032±0.002-inch, ASTM B209, 3003-I114, min. 21 KSI. > Stainless Steel: Min. 0.019±0A02-inch, ASTM A240/A480, T304, min. 35 KSI. 5. LIMRATIoNs: 5.1 This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. Exterior Research and Design, I.I.C. Evaluation Report E102A0.08.08-R4 Rrtrjrmff OfAutharizattan 05e3 FL5374-114 Revision 4:03/17/2015 Page 3 of 7 '\JTRINITY ERD 5.2 FOR HVHZ JURISDICTIONS: 5.2.1 For Hip & Ridge Channel Metal or Trim Lock Channel Metal, refer to FBC RAS 118, Drawing 13, Detail 3, RAS 119, Drawing 12,. Detail 3; or RAS 120, Drawing 15, Detail 3. For Trim Lock Plus Channel Metal, refer to the installation instructions herein. 5.2.2 For HVHZ jurisdictions, Installations of Hip & Ridge Channel Metal and Trim Lock are prescriptive by RAS 118, 119 and 120, and the data in Tables lA and 1B is supplemental to these prescriptive allowances. Installations of Trim Lock Plus are limited to projects having a required moment resistance (M,J or uplift resistance (Fr), as determined in accordance with RAS 127, not greater than the following values. Referto the the adhesive manufacturers published Installation instructions for adhesive paddy placement details. Y "INDEPENDENT' paddy placement meanseach individual tile is bonded to the Channel Metal in its own, single foam paddy; the head laps are not bonded. This method is limited to 2-part the adhesives. Allowable performance data below for "INDEPENDENT" paddy placement already has a 2 to 1 margin of safety applied to ultimate performance. ➢ "INTERDEPENDENT" paddy placement means each individual tile Is bonded to the Channel Metal in a foam paddy, and a second foam paddy bonds the tile head lap, or two tiles are bonded to the Channel Metal using a single foam paddy. Allowable performance data below for "INTERDEPENDENT" paddy placement already has a 4 to 1 margin of safety applied to ultimate performance. 7 x'Y{ 7�.` g '1 t1{ TAME •Pt}(,R7#may t)>f r RM.WC p�� ti nnrATONS. VJIZ, PE D`'lirXY z%.3 : t.x,�tafApYRI17j.�e, t t Ut r +i� s+pb tg( p1gT}' ru s l °a¢ C4. iSfi�SS M.Ini"4s ,�.?dr'RtjliOs GBSY�s ANTS^# r1;Pd3(: lf'ifl xsF=.t�.r is Hip/Ridge Metal Tile Adhesive Allowable Performance Design MetalType Type PlacementM,(ft-lb0 Moment Based Uplift Based F'(Ibf) Hip & Ridge Channel Metal galvanized day or concrete 3M'" 2-Component Foam Roof Tile Adhesive AH-160 Independent p 127 169 Trim Lock galvanized, Galvalume•, clay or 3M- 2-Component Foam Independent 171 159 aluminum or stainless steel concrete Roof Tile Adhesive AH-160 Trim Lock Plus galvanized, Galvalumee, day or 3M-2-Component Foam Independent 177 165 aluminum or stainless steel concrete Roof Tile Adhesive AH•160 S ��q ,j {�qj ��� "rl f} Lr, tt �Rr9 }�ppryy1}};BJPER � EU1r�rf�ATON tiy��)$t�l��� � � x 3 {Y r,Fl£r HVH 'f ROE��HDPfO PA�OG',IA�py��"Nit aS FNi p�}( s� j( �� iCq�x, �rLu.a s•� �t Six .�}� �i�� � ,f{»{S�rft���(�f�}-Ya.° 2-,f-f�f f#Jci xtt fi4 3�.SYT. rs�r Ol'p�bk � 14 y�f�4..',ii �f �{r't�i�{�}��yui�dr�F� �3� �9. ! 4F 1� nGPJOh".LtfFT)'A1RfAL1YAP+YtflJ,.. t�IZk'(3t�i 3i23t"�.5., _j#nW �i.ia�.�u�d (a.F.Fa�hi`af„k Hip/Ridge Metal Tile Adhesive Allowable Performance Design MetalType Type Placement Moment Based Uplift Based M,(ft-Ibf) F'(Ibf) Trim Lock or Trim galvanized, Galvalumee, clay or 3M-2-Component Foam Lode Plus aluminum or stain less steel concrete Roof Tile Adhesive AH-I60 Interdependent 95 88 Trim Lock galvanized, Galvalume•, clay or 3M'" RoofTlle Adhesive Interdependent 99 94 stainless steel concrete RTA-1 Trim Lock aluminum day or 3M-Foam Roof Tile Interdependent 90 84 concrete Adhesive RTA-1 Trim Lock Pius galvanized, Galvalume-, day or 3M- Foam Roof Tile Interdependent 90 84 aluminum or stainless steel concrete Adhesive RTA-1 Trim Lock galvanized' Galvaiumee or day or TILE BOND -Roof Tile stainless steel concrete Adhesive Interdependent 123 117 Trim Lock aluminum day or TILE BOND -Roof Tile Interdependent 79 73 concrete Adhesive Trim Lock Plus galvanized, Galvalume^, day or TILE BOND- Roof Tile Interdependent 79 73 aluminum or stainless steel concrete Adhesive Trim Lock galvanized, Galvalume^or day or Touch'n Seat Starmeond Interdependent 14b 139 stainless steel concrete Roof Tile Adhesive Trim Lock Aluminum day or Touch'n Seal StormBond Interdependent 58 54 concrete Roof Tile Adhesive Trim Lode Plus galvanized, Galvalume•, day or Touch'n Seal StonnBond Interdependent 58 54 aluminumor stainless steel concrete Roof Tile Adhesive Exterior Research and Design, LLG Evaluation Report E30240.08.08-R4 Cert%fmte ofAuthorLmdon 49503 FL5374-R4 Revision 4:03/17/2015 Page 4 of 7 '1 TRINITY { ERD 5.3 FOR NON-HVHZ JURISDICTIONS: 5.3.1 For Hip & Ridge Channel Metal or Trim Lock Channel Metal, refer to FRSA/TRI April 2012 (04-12). For Trim Lock Plus Channel Metal, refer to the installation instructions herein 5.3.2 For non-HVHZ, Installations are limited to projects having hip and ridge design pressure requirements, determined in accordance with Table 1A of FRSA/TRI April 2012 (04-12), not greater than the following values. Refer to the the adhesive manufacturers published installation Instructions for adhesive paddy placement details. "INDEPENDENT" paddy placement means each individual tile is bondedtothe Channel Metal in its own, single foam paddy; the head laps are not bonded. This method Is limited to 2-part tile adhesives. This method is limited to 2-part tile adhesives. Allowable performance data below for "INDEPENDENT" paddy placement already has a 2 to 1 margin of safety applied to ultimate performance. D "INTERDEPENDENT" paddy placement means each individual tile is bonded to the Channel Metal in a foam paddy, and a second foam paddy bonds the tile head lap, or two tiles are bonded to the Channel Metal using a single foam paddy. Allowable performance data below for "INTERDEPENDENT" paddy placement already has a 4 to 1 margin of safetyapplied to ultimate performance. IA# F §l €'Fr(q^ .napp{;,r,roro¢��,I'fABLE}P FDRyhjANt(!6pNONi�}ifi, L Y'?f} (3-}6 {?vGHXSs,R+�,fi�^r J-S"1 i ,- f %I#:idra ii,1D M((rz pN xx r ro ti .h4ta s P tNDEVIMENT�0.3DJt1{ tt t n ENr,x'y.�f }{['a#3}hGf S �, {YL}RGINDr HfRfADVR !IOMrED�, `ii ?s+:°}'; ?Y�pfkiii lid lit F'..,r. 1, i i1 i n Hip/Ridge Metal TileAdhesive Allowable Uplift (Ps" Design Metal Type Type I Placement Hip &Ridge Channel Metal galvanized clay or concrete 3M"2-Component Foam Roof Tile Adhesive AH-160 Independent 169 Trim Lock galvanized, Galvalumee, aluminum or clay or 3M'"2-Component Foam Roof Independent 373 stainlesssteel concrete Tile Adhesive AH-260 Trim Lock Plus galvanized, Galvalumea, aluminum or clay or 3M"'2-Component Foam Roof Independent 178 stainless steel concrete Tile Adhesive AH-160 pr ':(s0flt3a)E YIOY'13;i'fhi01}-FIVp�,,fsY�v(MEROEOENDENr�A;Jpy:P.eAMENiI #�#k44Y,�. F�6tt'«r#1 r x�t4��.$[E26YOaryM,fANCEsIIMR Li ¢ , ,� I 3> , Hip/Ridge Metal Tile Adhesive Allowable Uplift (Psf) Design Metal Type Type Placement Trim Lock or Trim galvanized, Galvalume', aluminum or clay or 3M"2-Component Foam Roof Interdependent 96 Lock Plus stainless steel concrete Tile Adhesive AH-160 Trim Lock galvanized, Galvalume" or stainless dayor 3M^ Foam Roof Tile Adhesive Interdependent 110 steel concrete RTA-1 Trim Lock aluminum clay or 3M'" Foam Roof Tile Adhesive Interdependent 93 concrete RTA-1 Trim Lock Plus galvanized, Gaiwlume•, aluminum or clay or 3M'" Foam Roof Tile Adhesive Interdependent 93 stainless steel concrete RTA-1 Trim Lock galvanized, Galvalume`or stainless clay or TILE SOND`"Roof Tile Adhesive Interdependent 152 steel concrete Trim Lock aluminum clayor TILE BOND"' Roof Tile Adhesive Interdependent 82 concrete Trim Lock Plus galvanized, Galvalume•, aluminum or clay or TILE BOND'" Roof Tile Adhesive Interdependent 82 stamlesssteel concrete Trim Lock galvanized, Galvalume• or stainless clay or Touch'n Seal StormBond Roof Interdependent 148 steel concrete Tile Adhesive Trim Lock Aluminum clay or Touch'n SealStorm Bond Roof Interdependent 61 concrete Tile Adhesive Trim Lock Plus galvanized, Gaivalume•, aluminum or clay or Touch'n Seal StormBond Roof Interdependent 61 stainless steel concrete Tile Adhesive Exterior Research and Design, U.C. Evaluation Report E1D240.08.08-R4 rardpcate ofAurbadzaden"SO FL5374-R4 Revision 4:03/17/201S Page S of 7 �J TKINIIY I ERD 6. INSTALLATION: 6.1 The roof deck shall be minimum 15/32-inch plywood (non-HVHZ) or minimum 19/32-inch plywood (HVHZ) attached In accordance with FBC Chapter 23 to the satisfaction of the AHJ. 6.2 Hip & Ridge Channel Metal and Trim Lock Channel Metal shall be installed using min. 11 ga. x 1144-Inch long x 3/8-inch head diameter galvanized annular ring shank nails spaced 6-Inch o.c. along both deck -flanges. Fasteners shall be positioned V inch from the outside edge of each deck -flange, set In a bed plastic roof cement. For FBC HVHZ, refer to FBC RA5118, Drawing 13, Detail 3; RA5119, Drawing 22, Detail 3; or RAS 120, Drawing 15, Detail 3. 6.3 Trim Lock Plus Channel Metal shall be installed atop the Approved roof underlayment in continuous 2-inch wide ribbons of tile adhesive centered beneath each 1.5-inch wide deck flange. Place the Trim Lock Plus Channel Metal Into the wet adhesive and allow it to set-up prior to installation of roof tiles. View of Polyset AH160 Placement for Trim Lock Plus Channel Metal Installation 6.3.1 It is critical that the bond between the Trim Lock Plus Channel Metal, the tile adhesive and the underlayment is not disturbed prior to or during placement of the ridge tiles. 6.3.2 Approved underlayments are the codified '30/90' system or other FBC Approved roof underlayments listing approved use of the subject tile adhesive. Exterior Research and Design, I.I.C. Evaluation Report E10240.08.08-R4 CeNfleate ofAuftdmdae 09503 FL537"4 Revision 4:03/17/2015 Page 6 of 7 ''��PTR INJTY ERD 6.4 Tile shall be installed atop the Channel Metal in accordance with the the adhesive manufacturer's Approved, published Installation Instructions, subject to the limitations outlined in Section 5 herein. The exposed edges shall be packed and pointed with Approved mortar or weather blocking adhesive in accordance with FRSA/TRI April 2012 (04-12) or RAS 118, RAS 119, RAS 120 requirements. Hip / Ridge Tile Tile Adhesive Trim Lack Plus Mortar or Weather Block Adhesive Tile Adhesive Vlew of Trim Lock Plus Channel Metal Installation after Weather Blocked 6.4.1 Channel Metal shall be free of dust, debris, oils or other bond -breaking substance prior to placement of adhesive. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the Installation of this product. 8. MANUFACTURING PLANTS: Contact the named CIA entity for manufacturing facilities covered by F.A.C. Rule 61G20-3 QA requirements. 9. QUALITY ASSURANCE ENTITY: Architectural Testing, Inc. — QLIA1844; (717) 764-7700 END OF EVALUATION REPORT - Exterior Research and Design, LLC. Evaluation Report E30240.08.08-R4 CeWficorec7Authorhodon 49503 FL5374-R4 Revision 4: 03/17/201S Page 7 of 7 CREEK TECHNICAL. SERVICES, LLC EVALUATION REPORT Manufacturer: Manufacturing Plants: Quality Assurance: SCOPE BORAL ROOFING LLC 7575 Irvine Center Drive Irvine, CA 92618 (800)669-8453 www.boralamedca.com Lake Wales, FL Okeechobee, FL Certificate of Authorization No. 29824 17520 Edinburgh Or SCANNED Tampa, FL33647 BY (813)480-3421 St. Lucie County FLORIDA BUILDINGCODE6'" EDITION (2017) PRI Construction Materials Technologies (QUA9110) Issued October 15, 2018 Category: Roofing Subcategory: Roofing Tiles Code Sections: 1507.3.5, 1507.3.7, 1523.6.5, 1523.6.5.2, 1523.6.5.2.2, 1523.6.6.2.3 Properties: Physical Properties, Attachment Requirements, Wind Driven Rain, Static Uplift Resistance REFERENCES Entity Report No. Standard Year American Test Lab of South Florida Inc (TST3782) RT0130.01-14 TAS 112 1995 ASTM C 1492 2003(2009) American Test Lab of South Florida Inc (TST3782) RT0426.01-14 TAS 112 1995 ASTM C 1492 2003(2009) American Test Lab of South Florida Inc (TST3782) RT0615.02-11 TAS 112 1995 ASTM C 1492 2003(2009) American Test Lab of South Florida Inc (TST3782) RT0615.03-11 TAS 112 1995 ASTM C 1492 2003(2009) American Test Lab of South Florida Inc (TST3782) RT0615.04-11 TAS 112 1995 ASTM C 1492 2003(2009) American Test Lab of South Florida Inc (TST3782) RT0617.02-16 TAS 112 1995 ASTM C 1492 2003(2009) American Test Lab of South Florida Inc (TST3782) RT0617.03-16 TAS 112 1995 ASTM C 1492 2003(2009) American Test Lab of South Florida Inc (TST3782) RT0617.04-16 TAS 112 1995 ASTM C 1492 2003(2009) American Test Lab of South Florida Inc (TST3782) RT0623.04-14 TAS 112 1995 ASTM C 1492 2003(2009) American Test Lab of South Flodda Inc (TST3782) RT0624.04-14 TAS 112 1995 ASTM C 1492 2003(2009) American Test Lab of South Florida Inc (TST3782) RT0624.05-14 TAS 112 1995 ASTM C 1492 2003(2009) American Test Lab of South Florida Inc (TST3782) RT1210.02-15 TAS 112 1995 ASTM C 1492 2003(2009) American Test Lab of South Florida Inc (TST3782) RT1210.03-15 TAS 112 1995 ASTM C 1492 2003(2009) Miami -Dade BCCO (CER1592) 14-0408.06 FBC (HVHZ) 2017 Miami -Dade BCCO (CER1592) 14-0416.12 FBC (HVHZ) 2017 Miami -Dade BCCO (CER1592) 15-0721.04 FBC (HVHZ) 2017 Miami -Dade BCCO (CER1592) 16-0112.07 FBC (HVHZ) 2017 Miami -Dade BCCO (CER1592) 16-0112.08 FBC (HVHZ) 2017 Miami -Dade BCCO (CER1592) 18-0609.16 FBC.(HVHZ) 2017 Miami -Dade BCCO (CER1592) 18-0509.16 FBC (HVHZ) - 2017 Miami -Dade BCCO (CER1592) 18-0509.17 FBC (HVHZ) 2017 Tile Roof Institute Membership Confirmation TAS 100 1995 TAS 101 1995 TAS 102 & 102(A) 1995 BOR18003 FL28328 Page 1 of 12 This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. BOR CREEK AL ROOFING LLC Concrete Roof Tiles TECHNICAL SERVICES, LLC PRODUCT DESCRIPTION Bermuda (Okeechobee) Profile/Description: ASTM C 1492, TAS 112 Type 3a, Flat profile, interlocking, class III concrete roof file Allowable Applications: For mechanically fastened (direct deck or batten), mortar set or adhesive set applications Dimensions: 16" x 10" BOR18003 l i-16'——li Y11/T4—' I� 10' Y Figure 1. Bermuda FL28328 2 of 12 This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report Is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK BORALROOFING LLC Concrete Roof Tiles TECHNICAL SERVICES, LLC Plantation (Okeechobee) Profile/Description: ASTM C 1492, TAS 112 Type 3a, flat profile,. interlocking,. class Ill. concrete roof file Allowable Applications: For mechanically fastened (direct deck or batten), mortar set or adhesive set applications Dimensions: 16-1/2" x 13" Figure 2. Plantation Saxony 900 Slate, Shake and Split Shake (Lake Wales) Profile/Description: ASTM C 1492, TAS 112 Type 3a, flat profile, interlocking, class III concrete roof file Allowable Applications: For mechanically fastened (direct deck or batten), mortar set or adhesive set applications Dimensions: 17" x 13" x 1-5/32" (Slate) or 1-9/32" (Shake and Split Shake) XkM HOLES BOR18003 UNMERLOCF:. Figure 3. Saxony 900 Slate FL28328 wr-(Smm) COVF.RLOCA 3 of 12 This evaluation report is provided for Stale of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC NAIL HOLES NAIL HOLES LO BOR18003 Millil Figure 4. Saxony 900 Shake Figure 5. Saxony 900 Split Shake FL28328 BORAL ROOFING LLC Concrete Roof Tiles 497T(Slate) 4 of 12 This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for Which this report Is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. r- CD�C� BORAL ROOFING LLC I� �y Concrete Roof Tiles TECHNICAL SERVICES, LLC Estate "S" (Okeechobee) Profile/Description: ASTM C 1492, TAS 112 Type 1b, low profile,. interlocking, class III concrete roof file Allowable Applications: For mechanically fastened (direct deck or batten), mortar set or adhesive set applications Dimensions: 16-1/2" x 13" Nail Holes Figure 6. Estate Villa 900 (Lake Wales) Profile/Description: ASTM C 1492, TAS 112 Type 1b, low profile, interlocking, class III concrete roof tile Allowable Applications: For mechanically fastened (direct deck or batten), mortar set or adhesive set applications Dimensions: 17.0" x 13" x2-1/8" 1" Figure 7. Villa 900 12 Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. ING LLC CREEK BORA Concrete Roof Tiles TECHNICAL SERVICES, LLC Barcelona 900 (Lake Wales) Profile/Description: ASTM C 1492, TAS 112 Type la, high profile, interlocking, class III, 'S' shaped concrete roof tile Allowable Applications: For mechanically fastened (direct deck or batten), mortar set or adhesive set applications Dimensions: 17" x 13" x 3-5/8" 0 sre M Figure 8. Barcelona 900 Galena Spanish "S" (Okeechobee) Profile/Description: ASTM C 1492, TAS 112 Type 2a, high profile, interlocking, class III 'S' shaped concrete roof tile Allowable Applications: For mechanically fastened (direct deck), mortar set or adhesive set applications Dimensions: 17" x 10" x 2.7" Fastener Holes 17" 10" Figure 9. Galena Spanish "S" BOR18003 FL28328 Page 6 of 12 This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK BORAL ROOFING LLC Concrete Roof Tiles TECHNICAL SERVICES, LLC Spanish "S" Nuevo (Lake Wales) Profile/Description: ASTM C 1492,.TAS 112 Type 2a, high profile,. interlocking, class III 'S' shaped concrete roof tile Allowable Applications: For mechanically fastened (direct deck or batten), mortar set or adhesive set applications Dimensions: 17" x 9-3/4' x 2-27/32" Fastener Holes 17" 9-3/4" Figure 10. Spanish "S" Nuevo APPLICATION METHOD Installation Limited to slopes 3:12 or greater in the HVHZ; Outside the HVHZ, shall be in accordance Slope: with the recommendations of the FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Fifth Edition Revised or RAS 118, RAS 119, or RAS 120, as applicable. Solid or closely fitted min. 15/32-inch plywood sheathing for new and existing construction Roof Deck: at max. 24 in. span; In the HVHZ, new construction shall be min. 19/32 in. plywood at max. 24 in. span; Designed by others in accordance with FBC requirements. Underlayment: Installed in accordance with FBC requirements. In the HVHZ, the minimum underlayment shall be installed as described in RAS 118, RAS 119, or RAS 120, as applicable. BOR18003 FL28328 Page 7 of 12 This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC BORAL ROOFING LLC Concrete Roof Tiles Data for Attachment Calculations for Direct,to Deck Applications Nominal Weight(W) and Aerodynamic Restoring Moments due to Gravity - M9 (ft-lbf) ' Dimensions (I x w) Multipliers Direct Deck Roof Tile e A (fts ) W (lbf) • I (ft) w (tt) Direct Deck 3°:12" 4":12° 5":12" 6":12" >7°:12" Application Bermuda 9.7 1.33 0.833 0.205 6.97 6.86 6.71 6.54 6.35 Plantation 11.6 1.375 1.08 0.289 7.79 7.67 7.52 7.32 7.04 Saxony 900 10.9 1.417 1.08 0.315 7.62 7.5 7.34 7.16 6.95 Estate "S" 10.0 1.375 1.08 0.289 6.74 6.64 6.50 6.33 6.14 Villa 900 10.9 1.42 1.08 0.315 7.62 7.50 7.34 7.15 6.95 Barcelona 11.5 1.417 1.08 0.301 7.00 6.90 6.76 6.60 6.42 900 Galena Spanish "S" 8.5 1.42 0.833 0.235 6.13 6.03 5.89 5.74 5.57 Spanish "S" 8.95 1.417 0.8125 0.233 5.93 5.83 5.70 5.56 5.39 Nuevo Data for Attachment Calculations for Batten Applications Nominal Weight. (W) and Aerodynamic Multipliers Restoring Moments due to Gravity - M9 (ft-Ibf) Roof Tile Dimensions(Izw) A (fts ) Direct Deck W (lbf) I (ft) w(ft) Batten 3^;12" 4°:12° 5":12" 6°:12° >7":12° _ Application Bermuda 9.7 1.33 0.833 0.189 6.53 6.43 6.29 6.14 5.97 Plantation 11.6 1.375 1.08 0.267 6.85 6.75 6.61 6.44 6.26 Saxony 10.9 1.417 1.08 0.291 - 6.61 6.48 6.31 6.13 900 Estate "S" 10.0 1.375 1.08 0.267 5.91 5.82 5.70 5.56 5.40 Villa 900 10.9 1.42 1.08 0.291 - 6.56 6.42 6.26 6.08 Barcelona 11.5 1.417 1.08 0.286 6.19 6.19 6.06 5.92 5.76 900 Spanish 8.95 1.417 0.8125 0.215 5.30 5.21 5.09 4.96 4.82 S" Nuevo BOR18003 FL28328 Page 8 of 12 This evaluation report is provided for Stale of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC BORAL ROOFING LLC Concrete Roof Tiles Attachment Resistance Expressed as a Moment for Mechanically Fastened Applications .Tile Fastener, Roof Tile Direct Deck Direct Deck Type Count Size Shank? - Clip (min. 15132" (min.r19/32' Battens plywood) plywood) _, . Nail 2 10d Ring N/A 30.9 38.1 17.2 Nail 1 10d Smooth N/A 7.3 9.8 4.9 or Screw Nail 2 10d Smooth N/A 14.0 18.8 7.4 or Screw Screw 1 #8 N/A N/A 30.8 30.8 18.2 Bermuda, Screw 2 #8 N/A N/A 51.7 51.7 24.4 Plantation or Saxony 900 Nail 1 10d Smooth Field 24.3 24.3 24.2 or Screw Nail 1 10d Smooth Eave 19.0 19.0 22.1 or Screw Nail 2 10d Smooth Field 35.5 35.5 34.8 or Screw Nail 2 10d Smooth Eave 31.9 31.9 32.2 or Screw Nail' 2 10d Ring N/A 50.3 65.5 48.3 Nail 2 10d Ring N/A 27.8 37.4 28.8 Nail 1 10d Smooth N/A 8.8 11.8 4.1 or Screw Nail 2 10d Smooth N/A 16.4 21.9 7.1 or Screw Screw 1 #8 N/A N/A 25.8 25.8 22.9 Estate Villa 900 00 Screw 2 #8 N/A N/A 47.1 47.1 49.1 Nail 1 10d Smooth Field 24.3 24.3 24.2 or Screw Nail 1 10d Smooth Eave 19.0 19.0 22.1 or Screw Nail 2 10d Smooth Field 35.5 35.5 34.8 or Screw Nail 2 10d Smooth Eave 31.9 31.9 32.2 or Screw Estate "S" Nail' 2 10d Ring N/A 43.0 67.5 50.9 Continued on following page Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC BORAL ROOFING LLC Concrete Roof Tiles Attachment ResistanceExpressed as a Moment for Mechanically Fastened Applications Tile Fastener Mf (ft-lbf) Roof Tile Direct Deck'. Direct Deck Type Count Size. Shank Clip (min. 1613T (min. 19/32" : Battens plywood) plywood) Nail 2 10d Ring N/A 28.6 41.2 19.4 Nail 1 10d Smooth N/A 5.1 6.8 2.8 or Screw Nail 2 10d Smooth N/A 6.9 9.2 7.3 or Screw Screw 1 #8 N/A N/A 20.7 20.7 18.1 Barcelona 900, Galena or Screw 2 #8 N/A N/A 43.2 43.2 29.8 Spanish "S" Smooth Nuevo Nail 1 10d or Screw Field 23.1 23.1 19.0 Nail 1 10d Smooth Eave 29.3 29.3 24.0 or Screw Nail 2 10d Smooth Field 27.6 27.6 38.6 or Screw Nail 2 10d Smooth or Screw Eave 38.1 38.1 41.8 Nail' 2 10d Ring N/A 33.1 48.1 45.2 Notes: 1) Not for Saxony 900, Villa 900 or Barcelona 900. Installation with a 4" the headlap and fasteners are located a min. 2-1/2" from head of tile. 2) When using only one fastener, use the hole that is approximately 4-314" away from interlocking edge. 3) Direct Deck applications only. Attachment Resistance Expressed as a Moment for Adhesive or Mortar Set Roof Tile Adhesive" Product Approval Paddy Cunt Average Paddy - Weight (grams) Mf (ft-lbf) Dow Chemical TILE BONDM NOA 16-0222.01 2 13.9 31.3 Bermuda, Planation and Saxony 900 ICP Adhesives Polyset AH-160 NOA 17-0322.03 2 8 31.3 1 24 40.4 1 45 118.9 Saxony 900 DAP Foam Inc. Touch N' Seal® Storm Bond TM 2 Two -Component NOA 17-0829.12 2 8 59.0 1 24 45 1 45 93 Premix Marbletite, Inc. TILE-TITE NOA 17-1016.07 N/A N/A 43.9 Dow Chemical TILE BONDTM NOA 16-0222.01 2 11.4 26.1 Estate "S" or Villa 900 ICP Adhesives Polyset AH-160 NOA 17-0322.03 2 8 26.1 1 24 45.5 1 54 86.61 Premix Marbletite, Inc. TILE-TITE NOA 17-1016.07 N/A N/A 20.6 Villa 900 DAP Foam Inc. Touch N' Seal® Storm Bondi" 2iwo-Component NCA 17-0829.12 2 8 55 1 30 40 1 60 70 BOR18003 FL28328 Page 10 of 12 This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. CREEK TECHNICAL SERVICES, LLC BORAL ROOFING LLC Concrete Roof Tiles Attachment Resistance Expressed as a Moment for Adhesive, or Mortar Set Roof 'Tile Adhesive Produd Approval'' Paddy Count Average Paddy Weight (grams) Mf (Count Dow Chemical TILE BONDT°' NOA 16-0222.01 2 10.7 29.3 Barcelona 900, Galena Spanish "S° or Spanish "S° Nuevo ICP Adhesives PolysetAH-160 NOA 17-0322.03 2 8 29.3 1 24 38.7 1 63 66.5 Premix Marbletite, Inc. TILE-TITE NOA 17-1016.07 N/A N/A 24.5 Barcelona 900 DAP Foam Inc. Touch N' Seal® Storm Bond'TM 2 Two -Component NOA 17-0829.12 2 8 66.0 1 30 63 1 i 60 82 Notes: 1) See manufacturer's product approval for installation requirements. LABELING 1) All tiles shall bear the identifiable marking of the manufacturer's name or logo as follows: BOR18003 Manufactured in Lake Wales, FL Manufactured in Okeechobee, FL OR ENTEERA FL28328 12 This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. vFZZA BORAL ROOFING LLC CREEK Concretee Roof Roof Tiles TECHNICAL SERVICES, LLC LIMITATIONS 1) Fire Classification is not within the scope of this evaluation. 2) Installation of the evaluated products shall comply with FBC Section 1507.3, FRSAlfRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Fifth Edition Revised and the manufacturer's published application instructions. Installations in the HVHZ shall comply with RAS 118, RAS119 and RAS 120. 3) All products listed in this report shall be manufactured under quality assurance program in compliance with Rule 61020-3. 4) All product listed in this shall tested quarterly in accordance with TAS 112 Appendix A. 5) Installation of the evaluated products shall be limited to projects in areas subjected to weathering indices of 50 or greater as illustrated in ASTM C 1492-03, figure 1 (see below). so MODERATE WEATHERING SEVERE WEATHERING COMPLIANCE STATEMENT The products evaluated herein by Zachary R Priest P.E. have demonstrated compliance with the Florida Building Code, 6"' Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer. Iq t 11 ri, J P P G E N No 74021 2018.10.15 :� STATE OF : rLC/� 19:51:52 04'00' Zachary R. Priest, P.E. SiONA;p� % Florida Registration No. 74021 Organization No. ANE9641 CERTIFICATION OF INDEPENDENCE CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing products under this evaluation. CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under this evaluation. Zachary R. Priest, P.E. does not have, nor vdll acquire, a financial interest in any company manufacturing or distributing products under this evaluation. Zachary R. Priest, P.E. does not have, nor wiil acquire, a financial interest in any other entity involved in the approval process of the product. END OF REPORT FL28328 12 of 12 I nls evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid. This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not specifically addressed herein. NEORECta. SCANNED Certrficate of authorization#32455 BY 353 Christian Street, Unit #13 St. Lucie County oxford, CT 06478 (203) 262-9245 ENGINEER EVALUATE TEST CONSULT CERTIFY Boral Roofing 7575 Irvine Center Drive, Suite 100 Irvine, CA. 92618 (602)269-2288 Evaluation Report M35710.12.10-R11 FL14317-R10 Date of Issuance:12/21/2010 Revision 11:10/12/2018 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product underthe Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 61h Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: Boral Roof Underlayments LABELING: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the product(s), the Quality Assurance or the production facility location(s). NEMO ETC, LLC requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOIetc. Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 8 Prepared b m^^""."• Robert J.M. Nieminen P.E. The famimlle seal appearingwas authorized by Robert �•`'o Florida Registration No. 59166, Florida DG4 ANE1983 'x:n..:,,:,:::• Nieminen, 10/12/2018. This does not serve as an ' electronically signed document. CEFmncA'nON OF INDEPENDENCE: 1. NEMO ETC, LLC does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. NEMO ETC, LLC is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. S. This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. ONEMOletc. ROOFING COMPONENT EVALUATION: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: Boral Roof Underlayments, as marketed by Boral Roofing, have demonstrated compliance with the following sections of the 6'h Edition (2017) Florida Building Cade through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 1504.3.1 Wind Uplift UL 1897 �2012 1507.1.1, T1507.1.1, Physical Properties ASTM D1976 2015 1507.2.9.2 1507.3.3 Physical Properties FRSA/TRI April 2012 (04-12) 2012 ERD (TST 6049) Physical Properties M36790.07.11 09/30/2011 ERD (TST 6049) Physical Properties B40380.08.12 08/28/2012 ERD (TST 6049) Tensile Adhesion / LTA C41420.09.12-2 09/11/2012 ERD (TST 6049) Adhesion 341940.09.12 09/13/2012 ERD (TST 6049) Tensile Adhesion / LTA B47390.07.14-1 07/31/2014 ERD (TST 6049) Tensile Adhesion / LTA B47390.09.14 09/04/2014 OC(PDM1838) Physical Properties Equivalency statement 11/02/2017 PRI (TST 5878) ASTM D1970 NEI-031-02-02:REV 10/27/2010 PRI (TST 5878) ASTM D1970 NEI-029-02-01:REV 12/03/2010 PRI (TST 5878) Tensile Adhesion / LTA NEI-046-02-01REV 12/17/2010 PRI (TST 5878) FRSA/TRI April 2012 NEI-076-02-01 02/14/2011 PRI (TST 5878) ASTM D1970 NEI-034-02-02 01/29/2013 PRI (TST 5878) Wind Uplift BORR-001-02-01 03/17/2015 PRI (TST 5878) Wind Uplift BORR-005-02-01 06/24/2015 PRI (TST 5878) Tensile Adhesion / LTA DAPF-002-02-01 03/08/2018 PRI (TST 5878) ASTM D1970 (adhesion) OCF-443-02-01 10/11/2018 UL, U.C. (QUA 9625) Quality Assurance Service Confirmation Exp. 08/21/2020 4.1 Boral® TileSeal 50' is a nominal 50-mil thick, polyester -surfaced, self -adhering SBS modified bitumen roof underlayment; meets ASTM D3970. Yj4.2 BoralO TileSeaiw is a nominal 60-mil thick, polyester -surfaced, self -adhering SBS modified bitumen roof underlayment; meets ASTM D1970 and FRSA/TRI 04-12. 4.3 BoralO MetalSealw is a nominal 60-mil thick, polyester -surfaced, self -adhering SBS modified bitumen roof underlayment; meets ASTM D1970 and FRSA/TRI 04-12. 4.4 GatorSeal® is a nominal 55-mil thick, granular -surfaced, fiberglass reinforced, self -adhering SBS modified bitumen roof underlayment; meets ASTM D1970. CA4.5 Citadel® Plus is a nominal 48-mil thick, fabric -surfaced, fiberglass reinforced, self -adhering SBS modified bitumen roofing underlayment for use as a base -layer in multi -ply underlayment systems; meets ASTM D1970. NEMO ETC, LLC Evaluation Report M3S730.12.10-RSI CertijVw ofAuthorf:ation N324S5 6- EDITION (2017) FBC NON-HVHZ EVALUATION FL14317-RlD Boral Roof Underlayments: (602) 269-2288 Revision 11: 10/12/2018 Page 2 of 8 ONEMOletc. 5.1 This is a building code evaluation. Neither .NEMO-ETC, LLC nor Robert Nieminen,P.E. are, in anyway, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions. 5.3 Fire Classification is not part of this Laboratory Report; refer to current Approved Roofing Materials Directory for fire ratings of this product. 5.4 Boral Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. 5.5 Allowable Roof Covers: Table 1 pertains to use of each listed underlayment by -itself beneath the stated roof covers. Refer to the installation instructions for multi -ply underlayment options. TABLE I: ROOF COVER OPTIONS Undedayment Asphalt Nail -On Tile Adhesive -set.. Metal Wood Shakes Slate Shingles Tile &Shingles Boral Tile5eal 50w Yes No No Yes Yes Yes BoralTileSealw Yes Yes Yes Yes Yes Yes (See 5.5.1) Boral MetalSeaiw Yes Yes Yes Yes Yes Yes (See 5.5.1) GatorSeal Yes No No No Yes Yes 5.5.1 "Adhesive -set Tile" is limited to use of following Approved tile adhesives if underlayment combinations. TABLE IA: ALLOWABLE TILE ADHESIVE/ UNDERLAYMENT COMBINATIONS' Adhesive Florida Product Underlayments Approval DAP Foam Touch'n Seal StormBond Roof Tile Adhesive FL14506 Boral TileSeal"r or Boral MetalSeal"r DAP Foam Touch'n Seal StormBond 2Two-Component FL21374 Boral TileSeal"r or Boral MetalSeal"r Polyurethane Roof Tile Adhesive Dow TILE BOND— Roof Tile Adhesive FL22525 Boral TileSeal"r or Boral MetalSealRr ICP Adhesives Polyset® AH-160 FL6332 Boral TileSeal"r or Boral MetalSealw ICP Adhesives Polyset® RTA-1 FL6276 Boral TileSealw or Boral MetalSeal"r I Refer to rile Manufacturer's orAdhesive Manufacturers Florida Product Approval for Overturning Moment Resistance Performance. NEMO ETC, LLC Evaluation Report M35710.12.10-R11 Ceniflc a ofAorhonzation 02455 6- EDITION (2017) FBC NON-HVHZ EVALUATION FLM17-R10 Boral Roof Underlayments; (602) 269-2288 Revision 11: 10/12/2018 Page 3 of 8 NNEMOletc. 5.6 Allowable Substrates: 5.6.1 Direct -Bond to Deck: Citadel Plus, Boral TileSeal 50"T, Boral TileSeal"T, Boral MetalSeal"T or GatorSeal: ➢ Plywood (unprimed or primed with ASTM D41 primer). Boral TileSeal' or Boral MetalSeal"T: ➢ OSB (unprimed or primed with ASTM D41 primer). Note: Refer to Section 5.6.4 for uplift limitations associated with direct -deck underlayment installations where the overlying roof cover is adhesive -set tile roofing 5.6.2 Bond to Base Laver Underlayment: Citadel Plus, Boral TileSeal 50"T, Boral TileSealHT, Boral MetalSeal"T or GatorSeal: ➢ ASTM D226, Type II felt; Citadel Plus. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under adhesive -set tile systems, base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested in accordance with FBC 1504.3.1. 5.6.3 Bond to Other Substrate Types: Citadel Plus, Boral TileSeal 50HT I Boral TileSeal"T, Boral MetalSealHT or GatorSeal: ➢ ASTM D41 primed metal (e.g., flashing metal, valley metal, etc.). Boral TileSealHT: ➢ Huber Zip Deck (unprimed or primed with ASTM D41 primer); Dens Deck Prime. Note: For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum requirements of the prepared roof covering manufacturer's Product Approval. 5.6.4 Wind Resistance for Underlavment Systems in Adhesive -set Tile Applications: FRSA/TRI April 2012 (04-12) does not address wind uplift resistance of all underlayment systems beneath adhesive -set tile systems, where the underlayment forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in adhesive -set tile applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-12), Appendix A, Table 1A or FBC 1609 for determination of design wind loads #1 Maximum Design Pressure=-120.0 post: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: (Optional) ASTM D41 to the plywood deck Base Ply:. Citadel Pius, self -adhered Cap Sheet: BoralTileSeal"Tor Boral MetalSealHT, self -adhered, and back -nailed within the selvedge -edge side laps using 12 ga. x 1'/." ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch o.c. #2 Maximum Design Pressure=-142.5 psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Ply: None Cap Sheet: Boral TileSealw or Boral MetalSeal"T, self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x 1Y.." ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch o.c. NEMO ETC, LLC Evaluation Report M35710.12.10-RSI Certificate of Authuri:ation#32455 6- EDITION (2017) FBC NON-HVHZ EVALUATION FL14317-RlO Boral Roof Underlayments; (602) 269-2288 Revision 11: 10/12/2018 Page 4 of 8 ONEMOletc. #3 Maximum Design Pressure=-202.S psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of .Authority Having Jurisdiction. Primer: Tropical Roofing Products #410 Quick Dry Primer or other ASTM D41 primer to the plywood deck Base Ply: None Cap Sheet: Boral TileSealw or Boral MetalSeallr, self -adhered, and back -nailed within the selvedge -edge side laps using 12 ga. x 1Y4" ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch o.c. #4 Maximum Design Pressure = -210.0 psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: KARNAK #89 Sta-Tak Primer to the plywood deck Base Ply: None Cap Sheet: Boral TileSeal"T or Boral MetalSealn self -adhered, and back -nailed within the selvedge -edge side laps using 12 ga. x 1W ring shank nails through 32 ga.,1-5/8" diameter tin caps spaced 12-Inch o.c. #5 Maximum Design Pressure=-120.0 psf: Deck: Min. 2,500 psi structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: ASTM D41 to the concrete deck Base Ply: (Optional) Citadel Plus, self -adhered Cap Sheet: Boral TileSeal"DorBoral MetalSeallr,self-adhered 5.6.4.1 Note: For adhesive -set tile systems, if there is a base ply or mid -ply of Citadel Plus in the system, the project design pressure requirements may not exceed -120 psf. 5.7 Exposure Limitations: GatorSeal shall not be left exposed for longerthan 30-days after installation, prior to placement of final roof cover. Boral TileSeal SO"r, Boral TileSealw or Boral MetalSealw shall not be left exposed for longer than 180-days after installation, prior to placement of final roof cover. Citadel Plus, for use as a base -layer in a multi -ply underlayment system, shall not be left exposed for longer than 180-days after installation, priorto placement of subsequent underlayment layer. 5.8 Tile Slippage Limitations 1FRSA/TRI April 2012 (04-1211: When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. 6.1 Boral Roof Underlayments shall be installed in accordance with Boral Roofing published installation instructions subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application, and prime the substrate (if applicable). 6.3 Install self -adhering underlayment when ambient and surface temperatures are minimum 40"F and rising. NEMO ETC, LLC Evaluation Report M35710.12.10-R11 Certificate OfAuthanzanan M32455 0 EDITION (2017) FBC NON-HVHZ EVALUATION FL14317-RSO Boo] Roof Underlayments, (60Z) 269-2Z88 Revision 11: 10/12/2018 Page 5 of 8 ONEMOletc. 6.4 Citadel Plus: 6.4.1 Citadel Plus is limited to use as a base or mid -layer in multi -ply underlayment systems beneath Boral TileSeal 50"r, Boral TileSeal' or GatorSeal. 6.4.2 Slope limitations are those associated with the top -layer underlayment. 6.4.3 Direct to Deck: Cut the membrane into manageable lengths, typically 10 to 12 ft. Align the membrane parallel to the roof edge, extending over by %-inch. Fold the membrane away from the edge onto itself. Remove the release sheet. Place the membrane with the exposed rubberized asphalt onto the deck, pressing firmly into place. Roll into place with a weighted roller. Fasten the top edge of the sheet to the deck with corrosion resistant roofing nails, nails & tin -tags or 1-inch diameter plastic or steel cap nails spaced maximum 12-inch o.c. Overlap successive courses the entire width of the black -selvedge area, minimum 2 inches (horizontal lap) and minimum 6" end (vertical) laps. Install final underlayment layer atop Citadel Plus per 'direct -to -deck' instructions for Boral TileSeal 50HT, Boral TileSeal"', Boral MetalSealw or GatorSeal. 6.4.4 To Base Sheet: Install base sheet of ASTM D226, Type II felt in accordance with Code requirements or install base ply of Citadel Plus in accordance with Boral Roofing published installation instructions and Section 6.4.3 and when used as part of a multi -ply system. Install optional Citadel Plus as a mid -ply in accordance with Boral Roofing published installation instructions and Section 6.4.3. Install final underlayment layer atop Citadel Plus per 'direct -to -deck' instructions for Boral TileSeal 50HT, Boral TileSeal"' or GatorSeal. Note: For adhesive -set tile systems, if there is a base ply or mid -ply of Citadel Plus in the system, the project design pressure requirements may not exceed-120psf. 6.5 Boral TileSeal 50BT: 6.5.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table 1507.2.1 for the type of prepared roof covering to be installed. 6.5.2 Do not use Boral TileSeal 50HT on roof pitches less than 2:12. 6.5.3 Non -Tile Applications, Direct to Deck: Cut the membrane into manageable lengths, typically 10 to 12 ft. Align the membrane parallel to the roof edge, extending over by X-inch. Fold the membrane away from the edge onto itself. Remove the release sheet. Place the membrane with the exposed rubberized asphalt onto the deck, pressing firmly into place. Roll into place with a weighted roller. Fasten the black selvedge edge to the deck with corrosion resistant roofing nails, nails & tin -tags or 1-inch diameter plastic or steel cap nails spaced maximum 24-inch o.c. for slopes below 7:12 and maximum 12-inch o.c. for slopes 7:12 and greater. Overlap successive courses the entire width of the black -selvedge area, minimum 3-inch. Seal under end (vertical) laps using approved mastic, or use Joined and Folded Seam or Inverted Sheet Seam method detailed in Boral Roofing published installation instructions. NEW ETC, LLC Evaluation Report M35730.12.10-R31 Certificate ofAuthorirotlan #32455 0 EDITION (2017) FBC NON-HVHZ EVALUATION FL14317-R10 Boml Roof Underlayments; (602) 269-2298 Revision 11: 10/12/2018 Page 6 of 8 ONEMOletc. 6.5.4 Non -Tile Applications. to Base Sheet: Install ASTM D226, Type II felt in accordance with Code requirements or install Citadel Plus in accordance with Boral Roofing published installation instructions and Section 6.4. Install Boral TileSeal 5V in accordance over ASTM D226, Type II felt or Citadel Plus with Boral Roofing published installation instructions and Section 6.5.3, except end (vertical) laps, described below. Apply SBS Mastic under all end (vertical) laps or any other laps where the self -adhering bituminous underside is in contact with the fabric top surface, rolling the interface into place with a weighted roller. 6.6 GatorSeal: 6.6.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table 1507.1.1 for the type of prepared roof covering to be installed. 6.6.2 Do not use GatorSeal on roof pitches less than 2:12. 6.6.3 Non -Tile applications. Direct to Deck: Cut the membrane into manageable lengths, typically SO to 12 ft. Align the membrane parallel to the roof edge, extending over by %-inch. Fold the membrane away from the edge onto itself. Remove the release sheet. Place the membrane with the exposed rubberized asphalt onto the deck, pressing firmly into place. Roll into place with a weighted roller. Fasten the black selvedge edge to the deck with corrosion resistant roofing nails, nails & tin -tags or 1-inch diameter plastic or steel cap nails spaced 24-inch o.c. for slopes below 7:12 and 12-inch o.c. for slopes 7:12 and greater. Overlap successive courses the entire width of the black -selvedge area, minimum 3-inch. Seal end (vertical) laps using SBS Mastic under all side (vertical) laps or any other laps where the self -adhering bituminous underside is in contact with the granular or mineral top surface, rolling the interface into place with a weighted roller, or using the Inverted Sheet Seam detailed in Boral Roofing published installation instructions. 6.6.4 Non -Tile Applications. to Base Sheet: Install ASTM D226, Type II felt in accordance with Code requirements or install Citadel Plus in accordance with Boral Roofing published installation instructions and Section 6.4. Install GatorSeal overASTM D226, Type II felt or Citadel Plus in accordance with Boral Roofing published installation instructions and Section 6.6.3 except end (vertical) laps, described below. Apply SBS Mastic under all side (vertical) laps or any other laps where the self -adhering bituminous underside is in contact with the granular top surface, rolling the interface into place with a weighted roller. 6.7 I' Boral TileSealHT or Boral MetalSeal"!: 6.7.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table 1507.1.1 for the type of prepared roof covering to be installed. 6.7.2 Do not use Boral TileSealHT or Boral MetalSeaF on roof pitches less than 2:12. 6.7.3 Non -Tile Applications. Direct to Deck: For OSB substrate, prime with ASTM D41 primer and allow to dry prior to installation. Cut the membrane into manageable lengths, typically 10 to 12 ft. Align the membrane parallel to the roof edge, extending over by X-inch. Fold the membrane away from the edge onto itself. Remove the release sheet. Place the membrane with the exposed rubberized asphalt onto the deck, pressing firmly into place. Roll into place with a weighted roller. Fasten the black selvedge edge to the deck with roofing nails, nails & tin -tags or 1-inch diameter plastic or steel cap nails spaced maximum 12-inch o.c. Overlap successive courses the entire width of the black -selvedge area, minimum 3-inch. Seal under all end (vertical) laps using approved mastic or use Inverted Sheet Seam method detailed in Boral Roofing published installation instructions. NEW ETC, LLC Evaluation Report M35710.12.10-R31 Certificate o7AuMorization #32455 6- EDITION (2017) FBC NON-HVHZ EVALUATION FU4317-R30 Dotal Roof Underlayments: (602) 269-2288 Revision 11: 10/12/2018 Page 7 of 8 ONEMOletc. 6.7.4 Non -Tile Applications. to Base Sheet: Install ASTM D226, Type II felt in accordance with Code requirements or install Citadel Plus in accordance with Boral Roofing published installation instructions and Section 6.4. Install Boral TileSeal' or Boral MetalSeal"r over ASTM D226, Type II felt or Citadel Plus in accordance with Boral Roofing published installation instructions and Section 6.7.3, except end (vertical) laps, described below. Apply SBS Mastic under all end (vertical) laps or any other laps where the self -adhering bituminous underside is in contact with the fabric top surface, rolling the interface into place with a weighted roller. 6.7.5 Tile Applications: Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions noted above as a guideline. For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12), Table 1. For adhesive -set tile applications, refer to Section 5.6.4 herein. Note: For adhesive -set tile systems, if there is a base ply or mid -ply of Citadel Plus in the system, the project design pressure requirements may not exceed -120 psf. Refer to Section 5.9 for tile staging limitations. Battens must be used for all tile installations atop Boral TileSeal"T or Boral MetalSeal"rwith roof pitches of 2%to less than 3:12. Boral Roofing's Elevated Batten System or counter battens are required. As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. 8. MANUFACTURING PLANTS: Brentwood, NH UL, LLC.—QUA9625; (631) 546-2458; Kanchi.Aerawala-DokaniaCdul.com - END OF EVALUATION REPORT - NEMO ETC, LLC Evaluation Report M35710.12.10-R31 Cerrijimre ofAud orizadon #32455 67' EDITION (2017) FBC NON-HVHZ EVALUATION FL14317-RSO Boral Roof Underlayments; (602) 269-2288 Revision 11: 10/12/2018 Page 8 of 8