HomeMy WebLinkAboutPOOL PLANSPOOL -BOND PB-2008 WATER ELECTRICAL DIAGRAM AND ELECTRICAL DIAGRAM N.T.S. GFI OUTLET PER 2014 NEC HEAT PUMP WITH JANDY TRUE (3) #6 CU & (1) #10 CLEAR SALT MANUAL MOTOR STARTER CU GROUND IN 1" I / SWITCH DECK (1) #5 REBAR OR (2) # 3 REBAR 0 8" NO SCALE GRID LOCATION OF WATER BOND CONDUIT \ 1HP VARIABLE SPEED JANDY i, PUMP MOTOR WITH BUILT-IN POOL PANEL WI 80 AMP OVERLOAD SWITCH Wl3- #10 THHN BRKR & (2)-#4 & (2) #10 GND CU WITHIN %" MIN. CONDUIT (GFCI THHN CU IN 1" RPVC CONDUIT PROTECTED) S.P.S.T. TOGGLE SWITCH (2) POOL LIGHTS (GFI NOT REQUIRED) / JUNCTION BOX PUMP1PUMP BONDED BACK TO POOL TIME CLOCK W. P. DISCONNECT 12 VOLT TRANSFORMER ALL ELECTRICAL TO COMPLY WITH 2O14 NATIONAL ELECTRIC CODE. ELECTRICAL CONTRACTOR TO ERIFY ADEQUATE CAPACITY AT POINT OF CONNECTION 3412 THHN CU WITHIN %" MIN. CONDUIT FOR POOL LIGHT(S) GROUND ALL BOXES, LIGHTS, MOTORS, ETC. w/#8 SOLID, BARE COPPER. PROVIDE W.P.G.F.I. OUTLET 10' MIN. -20' MAX. FROM WATER'S EDGE. ALL POOL PUMPS TO BE GFCI PROTECTED PER NEC 680.22(B) IPMENT LAYOUT N.T.S. 1.5" VACUUM LINE 2X" POOL MAIN DRAIN 2" SKIMMER LINE 2" POOL RETURN LINE TO FIRST TEE, 1.5" TO POOL JANDY TRUE CLEAR SALT SYSTEM 1.5" TO WASTE OR DISCHARGE TO GROUND 1HP JANDY VARIABLE FHPM PUMP WITH W/APPR HAIR AND LINT STRAINER CARTRIDGE FILTER W/ PRESSURE GAUGE AND AIR RELIEF VALVE INSTALL PERMA-CAST WATER BOND OR APPROVED EQUAL TIED TO PUMP ROUND W/ #8 SOLID COPPER & APPROVED LUG (MIN. 9 SQ. IN SURFACE AREA (POSED TO WATER) PER MFGR'S SPECS (FIELD VERIFY LOCATION) HEAT PUMP W/INTERNAL BY-PASS VALVES wa,..",yna.�weunenmV4Blao. 64018XXV Ntlpryl of pLAE�1i198 +rvi A5MEP11259Ea]WB as4efin¢d f �' T dSCMIer I. uE NN6M T Cmifietlb(IavbwfierslzMnlw45,N4 SI6E mqN XYfrvay Sv=tm.&e�.G9]IISA]9. U.. Mrxa OT.,®mrnrOmw a vN 'M-avWvaFbaYv�vm •y.eM.rs-rwswsY .'Ys 4 _ _ _ ✓�r��•v--"F• �� 'aa oiY,.wWW,�.fa mw __ MP C r AHM 4 ib d m 55I5 wvav rvaamnwA CHILD SAFETY I BARRIER FENCE NO CLOSER THAN 20" FROM WATERLINE *LOCATION OF GFI RECEPTACLE EQ TO BE DETERMINED IN FIELD PER NEC 680 QUIPMENI VERIFY PAD EXACT PER FBC LOCATION IN R4501.22 FIELD WITH SUPERVISOR POOL DETAILRESIDENTIAL APPROVED AND THE ANSUAPSP-72D06 FOR SUCTION ENTRAPMENT AVOIDANCE I APPROVEDMAIN➢RAIN FRAMES AND GRATES PER V.G.& ASA ANSI 112.19.&20a/ MINIMUM Q SUCTION LINES PER PUMP 3_FT_. SEPARATION OR SEPARATE PLANES 3 FT. MIN. •2.5" LINE TO FIRST TEE. 1.5" TO POOL •A • • 3" SUCTION LINE MAX 181 G.P.M. TO FILTRATION PUMP 6 FPS MAX Is- MIN. ( ENTIRE PERIMETERI)e- W.L. BOND WIRE Wl APPR. CLAMPS (ONE ON EACH SIDE OF POOL 4 PER N.E.C. 2014 SEC. 680.26 (WHERE ADOPTED) M a, . 1 ALL STEPS AND SWIMOUT BENCH EDGES WILL HAVE 2X6 CAPTILE BORDER OF OPPOSITE COLOR OF GEM FINISH FOR VISIBILITY 2. HAND HOLD TO BE INSTALLED AT ARE WHERE DECK RAISED -6" < ABOVEPOOL 48" MAX WATER. FIr M DEPTH MA Y . . Y N.T.S. PLUMBING LINES FROM SUMP W13" TEE -� I( 8 GAUGE SOLID COPPER WIRE 1 I 1 I MINIMUM Is- MAX 7A" FROM EDGE OF POOL AROUND ENTIRE POOL PERIMETER BURIED 4" TO 6" DEEP #8GROUND WIRE STEPDETAIL 1. TREAD IS MIN. OF 10" WIDE. 2. RISER NOT GREATER THAN 12" EXCEPT IF MORE THAN (3) TREADS ARE USED. 3. ALL STEPS TO BE SOLID GUNITE 4000 PSI. OUTSIDE ANGLE OF REPOSE 6' AND FURTHER = e THICK WALLS W1#3 REBAR @ 12" O.C. EACH WAY 3' TO V - 6" THICK WALLS W1#3 REBAR @ 12" O.C. EACH WAY 0' TO Y = 8" THICK WALLS W1#3 REBAR @ 12" O.C. EACH WAY 9ft m m 3 fl. / / 0 / c a° / � o EXCAVATION INTO THE ANGLE OF REPOSE IS ALLOWABLE PROVIDED: SHORING IS INSTALLED AT EXCAVATION AND SHORING SHOULD BE SUFFICIENT TO SECURE SOILS FROM EROSION OR SETTLEMENT ' NO UNDERMINING OCCURS OR ENGINEER APPROVED IF ANY DOES ' COMPACTION TEST OF THE BACKFILLED MARTIAL ARE PROVIDED AT C.O. OF THE SWIMMING POOL 1 SWIMOUTS WHEN PROVIDED SHALL BE AT 20" MAX. BELOW THE WATERLINE 201' max. Per F.R.C. 4501.18 AND ANSI/ NSPI-5-2003 _SCHEMATIC MUST HOLD y355PSI FOR (NO SCALE) __aEAST ST 30 N RETURN LINE SEPARATE AINS 36" 'PRfSSU FILTER GAU HAIR & LIN' CATCHER 10NENT OF PUMP 1 Janay Pro Series VS Repro Series Pump VS-FHP2.0 Performance Curves IN 43 90 39 so 3s 10 30 0 3 a a . 60 28 a so zz v y j N E 4o 17 S MIArI 30 13 A 20 e 10 4 NO Pm 0 1 0 0 10 20 30 40 60 60 70 80 90 100 110 IM IN 140 IN 160 170 IN INFlow Rate, Gallons Per Minute. IGPMI 200 EQ. LAYOUT (NO SCALE) EQUIPMENT PAD 30"MIN. CLEARANCE PER FBC IN FRONT R4501.22 )F SUBPANEL LOCATION OF GFI U RECEPTACLE TOBE DETERMINED IN SALT MELD PER NEC 680 VERIFY FILTER EXACT LOCATION IN FIELD WITH HEATER SUPERVISOR • APPROVED WITH THE 2017 FLORIDA BUILDING CODE FOR RESIDENTIAL 6TH EDITION SPECIFICATIONS MAX. WIDTH 28' MAX. LENGTH 40' MIN. DEPTH 3.5' MAX. DEPTH 6' SHAPE CUST ELEVATION T.B.D FILL FROM EXCAVATION STOCKPILE TILE INTERIOR FINISH GEM FILTER CS200 PUMP MAKE PER FBC 4601.20 PUMP HP: POOL FLOPRO VAR 2hp SPA NA FILTRATION PUMP COMPLIANT WITH ANSI1APSP/ICC-1S 2011 LIGHTS POOL 2 CLR LED SPA NA TRNFORM: POOL 100 WATT SPA NA MAIN DRAIN: POOL 2 SPA NA SKIMMER (1) _ RETURNS: POOL 3 SPA NA JETS: POOL NA_ SPA NA VALVED VAC LINE INCL FILL LINE NA DISCHARGE LINE TO GROUND CHLORINATOR TRU CLEAR SALT SYSTEM LADDER NA DIVING BOARD NA SLIDE NA HEATER RHE_EM8460 VACUUM HEAD INCL POLE INCL VACUUM HOSE INCL BRUSH INCL LEAF SKIMMER INCL TEST KIT INCL TREE / STUMP REMOVAL NA CHILD BARRIER FENCE INCL. SCREEN NA HANDRAIL NA ELECTRICAL INCL POOL PATIO CONCRETE FLOCRETE EXISTING PATIO NA DECK DRAIN NA GALLON CAPACITY -POOL 31,266 GAL. GALLON CAPACITY SPA- NA GAL. NA TURN -OVER RATE 6 hm TERMITE TREAT INC BARRIER INCL MAX. WATER VELOCITY - 6 WS FROM TRUNK LINES TO 8 k./S SUCTION LINES IMPS MAX RETURN LINE SKIMMER MIN. FLOW 25 GPM SURFACE AREA OF POOL —880 SO. FT 136 LN FT ESPINAL NAVION DRIVE JOB NAME: TREASURE COAST ADDRESS: AIRPARK LOT 99 PERMIT NO.: DATE DRAWN: MARCH 27, 2019 DRAWN BY: DAVE CURLAND DESIGNER APPROVAL: CUSTOMER APPROVAL: SCALE: 1/4" = V RAY REINHARD PE # 47041 1010 EASTER LILLY LANE UNIT 203 VERO BEACH 3296CD CD CONCRETE P:�PPOOLS, INC. ICRETE DECK POOL PATIO NOTE: REMOVE GRATE & DECK-1 1 ROW OF WATERLINE TILE WATER LEVEL WELL POINT PLUG FROM MAIN OVERPOUR BEND INTO D CK @ 48" O.C. MAX. - DRAIN &ATTACH AUX. PUMP (IH NE WHEN EMPTYING POO O . WATERLINE A4'/:" THICK _ FROM 6"X64" SLAB R w LIGH 00 POWER 2500 FIBE v/Ai_Ls 1" LIGHT #3 STEEL @ 12" O/C E.W. 6' Z SUPPLY GRATE SHALL TYPICAL WALL SHALL CONDUIT BE SECURED IN /2" TYP. FLOOR SLID N0 uNDERWATE UNDERWATER WALL SECTION & FLOOR9 LOPES SHALL BE 6"THICK SLOPE r PLACE SOWELL POINT FLOOR UNIFORM AND NO c zrA: r_ LIGHT LIG__HTDE7AIL THAT TOOLS1 cGMPLYwninncLEssc.1NICHE \ NvscALE/ THAN'11( ) ARE REQUIRED HRU 6.6NO SCALEAPPROVED FOR R MOVALSTEEL-TEX FORM CYCOLAC MAIN DRAIN -A GROUND CLAMP 6'R KRAFT WALLTHE SL(PE OF THE FLOOR FROM 3FLTHEWALLOW END WALL #3 @ 12" O.C.B.W.TOWARG THE DEEP AREA SMALL CONTINUOUS BOND WIRE THREADENOTE: FOR DEPTHS NorEE EF01FOOTiN7FOOCOMMON TO POOL STEEL, PLUG EATER THAN T ADD 1- POOL FINISH RAILS & EQUIPMENT AR @ 6" O.C. TO PUMP—► TYPICAL SECTION THRU POOL GRAVEL BED - - NO SCALE) FILE C.Y I C 04+- c053 REVIEWED FOR CODE COMPLIANCIL ST. LUCIE COUNTY BOCC SCANNED BY St. Lucie County 1aou- m53