HomeMy WebLinkAboutEVALUATION REPORTEVALUATION REPORT OF
METAL SALES MANUFACTURING CORPORATION
'26 GA. 5V-CRIMP PANEL'
SCANNLD
BY
St. Lucie County
FLORIDA BUILDING CODE 6TH EDITION (2017)
FLORIDA PRODUCT APPROVAL
FL 14645.4-R3
ROOFING
METAL ROOFING
Prepared For:
Metal Sales Manufacturing Corporation
545 South 3rd Street, Suite200
Louisville, KY 40202
Telephone: (502) 855-4300
Fax: (502) 8554290
Prepared By:
Bala Sockalingam, Ph.D., P.E.
Florida Professional Engineer #62240
1216 N Lansing Ave., Suite C
Tulsa, OK 74106
Telephone: (918) 492-5992
FAX: (918) 493-3568
This report consists of
Evaluation Report (3 Pages including cover) %11111 �I!
Installation Details (1 Page) `�%%% SOCKA.QN ....
Load Span Table (1 Page) JP�P.•�OENSF ('qy•�
Report No. C21824
Date: 9.9.17
No 62240
rc
O• STATE OF '�
�.
e.Q..... . •aC? ��
g,g, 201�7
FL 14645.4-R3
C2182-4
9.9.17
Page 2 of 3
Manufacturer: Metal Sales Manufacturing Corporation
Product Name: 5V-Crimp
Panel Description: 24" wide coverage with (5) 1/2" high ribs
Materials: Min. 26 ga., 50 ksi steel. Galvanized coated steel (ASTM A653) or
Galvalume coated steel (ASTM A792) or painted steel (ASTM A755).
Deck Description: Min. 7/16" thick OSB or min. 15/32" thick plywood or min. V thick
wood plank. (min SG of 0.42) for new and existing constructions.
Designed by others and installed as per FBC 2017.
Deck Attachment: 8d x 2.51' long ring shank nails or #8 x 2" long wood screws @ 6" o.c.
(Minimum) in the plywood field and edges. Designed as per FBC 2017.
Underlayment: Minimum underlayment as per FBC 2017 Section 1507.4.5.1.
Slope: 1/2:12 or greater in accordance with FBC 2017 Section 1507.4.2.
Requires applied lap sealant for roof slopes less than 3:12.
Design Uplift Pressure: 30.0 psf @ fastener spacing of 36" o.c.
(Factor of Safety = 2) 172.5 psf @ fastener spacing of 6" o.c.
Fastener Pattern:
Type: #9-16 or #10-14 hex head wood screws with sealed washer. Fastener
shall be of sufficient length to penetrate through the deck a minimum
of 3/8 and installed as per Metal Sales current installation procedure.
At panel ends @ 6" o.c. across panel width
At intermediate @ 12" o.c. across panel width
Test Standards: Roof assembly tested in accordance with UL580-06 `Uplift Resistance
of Roof Assemblies' & UL1897-04 `Uplift Tests for Roof Covering
Systems'.
Test Equivalency: The test procedures in UL 1897-04 comply with test procedures
prescribed in UL 1897-12.
Code. Compliance: The product described herein has demonstrated compliance with FBC
2017 Section 1507.4.
Product Limitations: Design wind loads shall be determined for each project in accordance
with FBC 2017 Section 1609 or ASCE 7-10 using allowable stress
design. The maximum fastener spacing listed herein shall not be
exceeded. The design pressure for reduced fastener spacing may be.
dirP�tnry or ASTM E108/UL790 report from an accredited laboratory
for ratings of this product.
Supporting Documents: UL580 & 1897 Test Reports
PRI Construction Materials Technologies
MSMC-017-02-01, Reporting Date 9/20/13
FL 14645.4-R3
C2182-4
9.9.17
Page 3 of 3
computed using rational analysis prepared by a Florida Professional
Engineer or based on Metal Sales load span table. This evaluation
report is not applicable in High Velocity Hurricane Zone. Fire
classification is not within scope of this Evaluation Report. Refer to
FBC 2017 Section 1505 and current approved roofing materials
PANEL OVERLAP'v"
p
5V-CRIMP FASTENER AT PANEL FLAT
SEE DETAIL 2
/ SEE DETAIL 1
REQU
ENDSIOENLY.OR PANEL
a
u �
u
�-
S- NEL FAST // /
PAENER PER UPLIFT
MINIMUM ATTACHMENT: LOAD TABLE
8d x 2.5' LONG RING SHANK NAIL
UNDERLAYMENT
SHALL BE INSTALLED
OR 88 x 2' LONG WOOD SCREWS
$
AS PER MANUFACTURER'S INSTALLATION SPACED 0 6' O.C. IN THE FIELD
` GUIDELINES
& AT EDGES
MIN, 2X— WOOD RAFTER/JOIST/
TRUSS. AT MAX. 2e D.C.
U N
TYPICAL PANEL INSTALLATION X—SECTION
�Oo
aOZ
M
�'G A OR Q70-14 WO*AT
ow u"i
n7"li
WRH SELF SEAfJNG WAS
MAXIMUM SPACING OF 3
�N
N
7
NO
MIN CRIMP
MIN 26 GA
5
a
�� N
YI
}
GENERA NO C'
1. ARCHRECTURAL ROOF PANEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE
a
p
a
3
G
UNDERLAYMENi
(uINJ oR
FLORIDA BUILDING CODE (FBC).
2. ROOF PANEI5.5HALL BE MIN; 26 GA. (t 0.019'. EFFECTNE COVERING;7
a
DETAIL
7/i s' THICK
TN
PLYWOOD 15/32 ICK (MIN:)
WIDTH 0A PANEL = 24',
3. THE ROOF PANELS SHALL BE INSTALLED OVER SHEATHING &STRUCTURE AS
+
SPECI0 D ON THIS DRAWICA
4. RE0U1 ED DESIGN. WINO LOADS SHALL BE DETERMINED FOR EACH PROJECT. THIS
3
i
PANEL SYSTEM MAY NOT BE INSTACCALLED WHEN THE REQUIRED DESIGN WIND LOADS
e
$9-16 OR p10-tM1 WOODSCREWS
WITH SELF SEALING WASHER AT
UPLIFT PRE" URES'SP[CIFIEO ON TH6 DRAWING.
ARE GREATER THAN THE DESST BE INI0
M
S UM E FLORIDA
BEDYEEN THEDRAWIMINIM
-
MAXIMUM SPACING OF 3fi" O.C.
WIGN
BUILDING CODE. F A OIFFERENCER0 CURS
A
QUI NTS E OD E. TH CODE L CONTROL
RE REME
ND LOADS AS
To ST AND WIN
SES MU
6. RA D�ARE ETHE
RE EREDJFOR FACRHSIAPPLICATIIONBANDE RES ONSIBILM OF OTHERS.
MIN 26MGA:
-v 2182—
UNDERLAYMEM J OSB 7/16" THICK (MIN.) OR slap I
DETAIL 2 PLYWOOD 15/32' THICK (MIN.) ( of
METAL SALES MANUFACTURING CORPORATION
5V-Crimp Uplift Loads
(Min. 26 ga.)
Description
Fastener Spacing
along panel length
(in)
Allowable Uplift
Load
(psfl
Coverage width: 24"
Panel Fasteners
#9-16 or #10-14 hex head
wood screws with sealed
washer
6
172.5 _
9
120.0
15
72.0
18
60.0 _
21
51.4
24
45.0
27
40.0
30
36.0
33
32.7
36
30.0
Notes:
1. The bold numbers indicate design loads calculated from test data with safety factor of 2.
2. Panels must be installed as per Evaluation Report FL 14645.4 and Metal Sales current installation procedure.
3. Three or more spans condition.
1216 N Lansing Ave., Suite C
Tulsa, Ok 74106
918 492 5992
�Itltuuplt
%,����� gOCKg4�°°i�i
*: No 62240CC
0'. STATE OF
awl
° S � CN
11
Bala Sockalingam, Ph.D., P.E.
FL 62240
i
EXTERIOR RESEARCH & DESIGN, U.C.
Certificate of Authorization #9503
TRINITY 1 ERD SCANNED 353 CHRISTIAN STREET, UNIT #13
Q0BY OXFORD, CT 06478
478
(203) 262-9245
EVALUATION REPORT St. Lucie County
TRI-BUILT Materials Group, LLC Evaluation Report A42960.10.12-116
PO Box70 FL16048-116
Rutherford, NJ 07070 Date of Issuance:10/25/2012
(800)516-1485 Revision 6: 09/25/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 6Th Edition (2017) Florida Building Code
sections noted herein.
DESCRIPTION: TRI-BUILT Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity[ ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADvERTISEMENT: The Evaluation Report number preceded by the words 'Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
Its distributors and shall be available for inspection at thejob site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 6.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The fealm0eseal.,,ari .g amhmi by Robert Niemhun,
P8anM/25/2017. m6dmnotu easaneleamni=Wsi(ned
demanent
CERTIFICATION OF INDEPENDENCE:
1. Trinity]ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity] ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
f
QOTRINITYIERD
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Underlayment
Compliance Statement: TRI-BUILT Roof Underlayments, as produced by TRI-BUILT Materials Group, LLC, have
demonstrated compliance with the following sections of the 61h Edition (2017) Florida Building Code through testing
in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations /
Conditions of Use set forth herein..
2. STANDARDS:
Section
Property
Standard
Year
1504.3.1
Wind Resistance
FM 4474
2011
1504.3.1
Wind Uplift
UL 1897
2012
1504.6
Accelerated Weathering
ASTM G155
2005
1507.2.4/ 1507.1.1, 1507.2.9.2
Physical Properties
ASTM D1970
2015
1507.3.3
Physical Properties
FRSA/TRI April 2012 (04-12)
2012
3. REFERENCES:
End
Examination
Reference-
Date
ERD (TST6049)
Physical Properties
S40540.02.13-1
02/19/2013
ERD (TST6049)
Physical Properties
S40540.11.13
11/19/2013
ERD (TST6049)
Physical Properties
S40540.03.14
03/26/2014
ERD (TST6049)
Physical Properties
S44870.04.14-2
04/02/2014
ERD (TST6049)
Physical Properties
S44870.04.14-3
04/02/2014
ERD (TST6049)
Physical Properties
S44870.04.14-1
04/10/2014
ERD (TST6049)
Physical Properties
S44870.04.14-4
04/10/2014
ERD (TST6049)
Physical Properties
S43530.02.14-1-R1
05/14/2014
ERD (TST6049)
Physical Properties
S43530.05.14
05/28/2014
ERD (TST6049)
Physical Properties
540540.10.14
10/31/2014
ERD (TST6049)
Physical Properties
SC7645.02.15
02/13/2015
ERD (TST6049)
Accelerated Weathering
SC8520.04.15
05/27/2015
ERD (TST6049)
Wind Resistance
SC14045.05.17-R1
06/07/2017
UL„LLC. (QUA9625)
Quality Control
Multiple -Listing R16814
12/10/2015
UL, LLC.(QUA9625)
Quality Control
Service Confinnation
Exp.07/18/2020
4. PRODUCT DESCRIPTION:
4.1 Tri-Built Sand-R SA Shingle Underlayment is a self -adhering, glass -mat reinforced, sand -surfaced, SBS
modified bitumen roof underlayment, with a 36-inch sheet width; meets ASTM D1970.
4.2 Tri-Built S/A HT TU Underlayment is a self -adhering, non -woven polyester fabric surfaced, SBS modified
bitumen roof underlayment; meets ASTM D1970 and FRSA/TRI April 2012.
4.3 Tri-Built Smooth HT S/A Underlayment is a self -adhering, glass -mat reinforced, film -surfaced, SBS
modified bitumen roof underlayment; meets ASTM D3970.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity.) ERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials
Directory for fire ratings of this product.
Exterior Research and Design, LLC. Evaluation Report A42960.30.12-R6
Certificate afAuthorizatlan#9503 6'"EDITION (2017)FBC NON-HVHZ EVAWATION FL36048-R6
TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6: 09/25/2017
Page 2 of 6
QTRINI'jY1 ERD
5A TRI-BUILT Roof Underlayments may be used with any prepared roof cover where the product is
specifically referenced within FBC approval documents. If not listed, a request may be made to the
Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the
prepared roof covering.
5.5 Allowable Roof Covers:
•.,TABLE T: ROOFCOVFR.0013ONS - -
Underlayment
Asphalt
Shingles
Nail -On Tile
Foam -On Tile
Metal
Wood Shakes
Slate
& Shingles
Tri-Built Sand-R SA Shingle
Underlayment
Yes
No
No
No
Yes
Yes
Tri-Built S/A HT TU
Yes
Underlayment
Yes
Yes
See 5.5.1
.Yes
Yes
Yes
;.T[eBu ilt Smooth 1HT-S�A t
fY�-�'
nderlaymment j
No
No
�Y
Yes
Cy�,1
5.5.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / undprlavmpnt rnmhinat;nnc
- TABLE TAIALLOWABLE TILE ADHESIVE/UNDERLAYMENT COMBINATLON51
Adhesive
Florida Product Approval
Underlayments
ICP Adhesives Polysete AH-160
FL6332
Tri-Built S/A HT TU Underlayment
DOWTileBond"'
FL22525
Tri-Built S/A HT TU Underlayment
5.6 Allowable Substrates:
5.6.1 Direct -Bond to Deck:
Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
➢ Plywood; ASTM D41 primed plywood; OSB; ASTM D41 primed 0SB; Southern Yellow Pine; ASTM D41
primed Southern Yellow Pine; ASTM D41 primed structural concrete.
Whilenot required over plywood, OSB or Southern Yellow Pine substrates, TRI-BUILT Materials Group, LLC
recommends priming the deck if the final roof cover is not slated for installation within 24 hours. Note:
TRI-BUILT Materials Group, LLC requires tongue -and -groove board decking be covered with plywood or
OSB prior to installation of the self -adhering underlayment.
5.6.2 Bond -to -Insulation:
Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
➢ Dens Deck Prime; SECUROCK Gypsum -Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per
minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations
under foam -on tile systems (Tri-Built S/A HT TU Underlayment only), insulation attachment shall be
designed by a qualified design professional and installed based on testing of the insulation/underlayment
system in accordance with FM 4474, Appendix D or TAS 114, Appendix J.
I Refer to rile Manufacturers or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
Exterior Research and Design, LLC. Evaluation Report A42960.10.12-R6
Certifitate ofAutbor¢a0on#9503 6'"EDmoN 12017)FBC NON-HVHZ EVALUATION FL16048-R6
TRI-BUILT Roof Underlayments; (800) 526-1485 Revision 6: 09/25/2017
Page 3 of 6
t
5.6.3
5.6.4
#1
Bond to Mechanically Attached Base Laver:
QOTRINITYIERD
Tri-Built Sand -RSA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
➢ ASTM D226, Type I or II felt.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per
minimum codified requirements. For installations under foam -on tile systems (Tri-Built S/A HT TU
Underlayment only), base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04-
12).
vvnlu neslsiance Tor unaerlayment systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12)
does not address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where
the underlayment forms part of the load -path. The following wind uplift limitations apply to direct -deck
underlayment systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile
applications. Maximum Design Pressure is the result of testing for wind load resistance based on
allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to S margin of safety
per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-12), Appendix A, Table 1A or
FBC 1,609 for determination of design wind pressures.
Maximum Design Pressure =-45 0 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Primer: (Optional) ASTM D41 or RESISTO EXTERIOR PRIMER
Underlayment: Tri-Built S/A HT TU Underlayment, self -adhered.
#2 Maximum Design Pressure =-67 5 osf:
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Primer: Soprema Elastocol 600c
Underlayment: Tri-Built S/A HT TU Underlayment, self -adhered.
#3 Maximum Design Pressure =-1500nsf:
Deck: Min. 15/32-inch APA-rated BCX plywood (may be installed C-side.up) to meet project
requirements to satisfaction of Authority Having Jurisdiction.
Deck Preparation: Plywood shall be thoroughly cleaned to remove dust and debris that may inhibit
adhesion. All sheathing fasteners shall be driven flush with the surface. All sharp
splinters and wood projections shall be removed/sanded.
Primer: (Optional) RESISTO EXTERIOR PRIMER
Underlayment: Tri-Built S/A HT TU Underlayment, self -adhered, shall be thoroughly roll using hand
roller and/or weighted roller to ensure there are no voids, and ensure there are no
voids/bridging at side and end -laps.
#4 Maximum Design Pressure=-600Psf:
Deck: Min. 19/32-Inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Base Sheet: Soprema Sopra-G or Modified Sopra-G mechanically attached with nails (FBC 1517.5,1)
and tin caps (FBC 1517.5.2) spaced 6-inch o.c. at the 4-inch laps and 6-inch o.c. in three,
equally spaced rows in the center of the sheet.
Underlayment: Tri-BuiltS/A HTTUUnderlayment, self -adhered.
Exterior Research and Design, LLC. Evaluation Report A42960.10.12-R6
Certijcate of Authorization a95o.9 6'"EDITION (2017) FBC NON-HVHZ EVALUATION FL26D48-R6
TRI-BUILT Roof Underlayments;.(800) 516-1485 Revision 6: 09/2S/2017
Page 4 of 6
8
QTRININ ERD
5.6.4.1 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet
or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1
design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an
attachment density designed by a qualified design professional to resist the elevated pressure criteria.
Commonly used methods are ANSI/SPRI WDi, FM Loss Prevention Data Sheet 1-29 and Roofing
Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in
Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements.
5.7 Exposure Limitations:
Tri-Built Sand-R SA Shingle Underlayment or Tri-Built Smooth HT S/A Underlayment shall not be left
exposed for longer than 30-days after installation
Tri-Built S/A HT TU Underlayment shall not be left exposed for longer than 180-days after installation.
5.8 Tile Slippage Limitations (TAS 103 Per FRSA/TRI April 2012 (04 12))•
When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall
be as follows. These slope limitations can only be exceeded by using battens during loading of the roof
tiles.
`TABLE 2: TIL SUPPAGE:LIMITATIONS FOR DIREOr-DECK TILE INSTALLATIONS
Underlayment
Tile Profile
Staging Method
Maximum
Slope
Flat
Mm 10-tile stack
6:12
Lugged
Max 10-tile stack
5:12
Max. 10-tile stack (bottom 2-tile stack
shallbe inverted, followed by 8 tiles high 6:12
on slope, as shown below)
Tri-Built 5/A HT TU
Underlayment
Lugged
v
Werior Research and Design, U.C. Evaluation Report A42960.10.12-R6
Certiftcate of Authorizabron#9503 6TM EDITION (2017) FBC NON-HVHZ EVALUATION FL36048-R6
TRI-BUILT Roof Underlayments, (800) 516-1485 Revision 6:09/2512017
Page 5 of 6
QOTRINi-rYIERD
6. INSTALLATION:
6.1 TRI-BUILT Roof Underlayments shall be installed in accordance with TRI-BUILT Materials Group, LLC
published installation requirements subject to the Limitations set forth in Section 5 herein and the
specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly
to remove any dust and debris prior to application, and prime the substrate (if applicable).
6.3 Tri-Built Sand-R SA Shingle Underlavment Tri-Built S/A HT TU Underlavment or Tri Built Smooth HT S/A
Underlavment• -
6.3.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
6.3.2 Non -Tile applications:
While priming is optional, TRI-BUILT Materials Group, LLC recommends priming the deck if the final roof
cover is not slated for installation within 24hours.
Apply sheet,parallel to the roof edge. Roll out approximately 10 ft of membrane and peel back the first 3
ft of release film.
Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible.
Once the entire length of membrane is in place, peel -off the release film diagonally while holding the
membrane tight. Firmly roll, broom or hand -press the membrane into place to achieve a bond.
Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6-
inches and staggered not less than 2-ft from vertical seams in the course below, sealed in accordance with
TRI-BUILT Materials Group, LLC requirements.
When installing at slopes above 8:12, TRI-BUILT Materials Group, LLC recommends back -nailing in the
overlap area at the top of the sheet at 12-inch o.c.
For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet
over valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge in
each direction. For valleys, apply the sheet starting at the lowest point and work upward.
6.3.3 Tile Applications (Tri-Built S/A HTTU Underlavment only):
Reference is made to FRSA/TRI April. 2012 (04-12) Installation Manual and Table 1 .herein, using the
Instructions noted above as a guideline.
For foam -on tile applications, reference is made to Section 5.6.4 herein for wind resistance limitations that
fall outside the scope of FRSA/TRI April 2012 (04-12).
Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the
underlayment. See Table 2 herein, and TRI-BUILT Materials Group, LLC published requirements for tile
staging.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
B. MANUFACrURING PLANTS:
Gulfport, MS
9. QUALITY ASSURANCE ENTITY:
UL, LLC —QUA9625; (314) 578-3406; k.chancellor@us.ul.com
- END OF EVALUATION REPORT -