EVALUATION REPORT
GAF r R E C
FILE COPY
EXTERIOR RESEARCH €& DESIGN, I.I.C.
Certificate of Authorization #9503
353 CHRISTIAN STREET, UNIT#13
OXFORD, CT 06478
(203)262-9245
Evaluation Report 01506.01.UH-R22
1 Campus Drive FL10224-R20
Parsippany, NJ 07054 L5T,-Uc:0
R 1 `� �019 Date of Issuance: 01/03/2005
(800) 766-3411 Revision 22: 09/20/2017
County, Permitting
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the a Edition (2017) Florida Building Code
sections noted herein.
DESCRIPTION: GAF Asphalt Roof Shingles
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein and FBC 1507.2.7.1 / R905.2.6.1.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the
referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change.
Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the
product changes or the referenced Quality Assurance documentation changes. Trinity)ERD requires a complete
review of this Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity[ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at thejob site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 6.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The fzoimileseal appearing was aWhodred by Robert Nieminen,
Pmanai/20/2017. This dam not..rc..,an eleavom.1iysigned
domment
CERTIFICATION OF INDEPENDENCE:
1. Trinityl ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinityl ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity l ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
1 i{,, -
"' ' TRIMY J ERD
I
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Asphalt Shingles
Compliance Statement: GAF Asphalt Roof Shingles, as produced by GAF, have demonstrated compliance with the
following sections of the 6th Edition (2017) Florida Building Code and Florida Building Code, Residential Volume
through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements
and Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section
Property
Standard
Year
1507.2.4/1507.1.1,
Physical Properties
ASTM D1970
2015
R905.2.3 / R905.1.1
1507.2.5, R905.2.4
Physical Properties
ASTM D3462
2010
1507.2.7.1, R905.2.6.1
Wind Resistance
ASTM D3161
2016
1507.2.7.1, R905.2.6.1
Wind Resistance
ASTM D7158
2011
1507.2.7.1, R905.2.6.1
Wind Resistance
TAS 107
1995
3. REFERENCES:
99tiv
Examination
Reference
Date
GAF (PDM 1915)
Letter of Equivalency
Seal -A -Ridge Impact Resistant IR
01/13/2012
PRI (TST 5878)
Physical Properties
GAF-025-02-01
03/27/2002
PRI (TST 5878)
ASTM D3462
GAF-059-02-01
09/02/2004
PRI (TST 5878)
ASTM D3462
GAF-080-02-01
05/25/2005
PRI (TST 5878)
Physical Properties
GAF-324-02-01
12/01/2011
PRI (TST 5878)
Wind Driven Rain
GAF-407-02-01
01/21/2013
UL (TST 1740)
ASTM D3462
93NK6295
11/29/1993
UL (TST 1740)
ASTM D3462
99NK43835
01/12/2000
UL (TST 1740)
TAS 107
94NK9632
03/29/2000
UL (TST 1740)
ASTM D3462
OINK06632
02/02/2001
UL(TST 1740)
ASTM D3161, TAS 107
OINK9226
05/21/2001
UL (TST 1740)
ASTM D3161
OINK37122
12/18/2001
UL (TST 1740)
ASTM D3462
O1NK37122
12/19/2001
UL (TST 1740)
ASTM D3161, TAS 107
02NK12980
04/10/2002
UL (TST 1740)
ASTM D3161, TAS 107
02NK30871
09/09/2002
UL (TST 1740)
ASTM D3161
03CA5357
03/11/2003
UL (TST 1740)
ASTM D3462
03NK26444
10/17/2003
UL (TST 1740)
ASTM D3462
04NK13850
06/07/2004
UL (TST 1740)
ASTM D3161
04NK13850
06/23/2004
UL (TST 1740)
ASTM D3161
04NK30546
03/10/2005
UL (TST 1740)
ASTM D3462
04NK22009
05/06/200S
UL (TST 1740)
ASTM D3161
04NK22009
05/09/2005
UL(TST1740)
ASTM D3462
05NK27924
02/10/2006
UL (TST 1740)
ASTM D3161
05NK27924
02/11/2006
UL (TST 1740)
ASTM D3161,D3462
06CA18077
06/05/2006
UL (TST 1740)
ASTM D3161, D3462
OGCA18074
06/16/2006
UL (TST 1740)
ASTM D3161,D3462
06CA35251
10/18/2006
UL (TST 1740)
ASTM D3462
06CA31603
12/01/2006
UL (TST 1740)
ASTM D3161,D3462
OGCA41095
12/27/2006
UL (TST 1740)
ASTM D3161
071\11(05228
03/13/2007
UL (TST 1740)
ASTM D3161
06CA31611
04/04/2007
UL (TST 1740)
ASTM D3161
06CA61148
04/09/2007
UL (TST 1740)
ASTM D3161, D3462
07CA31742
11/08/2007
UL (TST 1740)
ASTM D3161, D7158, D3462
OSCA06200
03/13/2008
Eiderior Research and Design, I.L.C. Evaluation Report 01506.01.08-1122
Certtfimte of Authodzutlan#9503 dn' EDITION (2017) FBC NON-HVHZ EVALUATION F1.10124-1120
GAF Asphalt Roof Shingles Revision 22: 09/20/2017
Page 2 of 6
T �M Eta
Katky
Examination
Reference
Date
UL (TST 1740)
ASTM D3161, D3462
07CA55908
04/01/2008
UL (TST 1740)
ASTM D3161, D3462
09CA10592
03/26/2009
UL (TST 1740)
ASTM D3161, D3462
09CA06856
05/15/2009
UL (TST 1740)
ASTM D3161, D7158, D3462
09NK06647
08/01/2009
UL (TST 1740)
ASTM D3161, D7158, D3462
09CA27281
08/27/2009
UL (TST 1740)
ASTM D3161, D7158, D3462
10CA35554
03/05/2010
UL (TST 1740)
ASTM D3161, D7158, D3462
10CA13686
05/15/2010
UL (TST 1740)
ASTM D3462
IOCA07264
05/27/2010
UL (TST 1740)
ASTM D3462
IOCA11953
10/29/2010
UL (TST 1740)
ASTM 63161, D7158, D3462
10NK11951
10/30/2010
UL (TST 1740)
ASTM D3161, D7158, D3462
1ONK12070
11/04/2010
UL (TST 1740)
ASTM D3161, D7158, D3462
08CA06100
01/30/2010
UL (TST 1740)
ASTM D3161, D7158, D3462
10CA53934
03/31/2011
UL (TST 1740)
ASTM D3161, D7158, D3462
11CA48924
10/22/2011
UL (TST 1740)
ASTM D3161, D7158, D3462
11CA47919
12/03/2011
UL (TST 1740)
ASTM D3161, D7158, D3462
11CA48408
12/08/2011
UL(TST1740)
ASTM D3161, D7158, D3452
11CA48725
12/09/2011
UL, LLC.(TST 9628)
ASTM D3462
12CA34891
10/12/2012
UL, LLC. (TST 9628)
ASTM D3161, D7158, D3462
12CASS151
02/15/2013
UL, LLC.(TST9628)
ASTM D3161
12CA38083
02/26/2013
UL, LLC. (TST 9628)
ASTM D3161
13CA32332
06/18/2013
UL, U.C. (TST 9628)
ASTM D3161
13CA37934
08/02/2013
UL, LLC. (TST 9628)
ASTM D3161, WISE, D3462
4786875675
07/17/2015
UL, LLC.(TST 9628)
ASTM D3161, D7158, D3462
4787434542
05/17/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Mobile, AL
10/25/2016
UL, U.C. (QUA 9625)
Quality Control
Inspection Report, R21, Myerstown, PA
10/20/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Tuscaloosa, AL
11/11/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Michigan Cty, IN
11/01/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Shaffer, CA
11/17/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Savannah, GA
11/11/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Minneapolis, MN
10/25/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Mt. Vernon, IN
10/2512016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Baltimore, MD
10/21/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Tampa, FL
11/17/2016
UL, LLC. (QUA 9625)
Quality Control
Inspection Report, R21, Dallas, TX
11/04/2016
UL, LLC. (QUA 9625)
QualityControl
Inspection Report, R21, Ennis, TX
11/03/2016
UL, LLC. (QUA 9625)
QualityControl
Inspection Report, R21, Fontana, CA
11/01/2016
4. PRODUCT DESCRIPTION:
4.1 Asphalt Shingles:
4.1.1 Marquise WeatherMax®, Royal Sovereign® and Sentinel® are a fiberglass reinforced
3-tab asphalt roof
shingles.
4.1.2 Camelot®, Camelot® II, FortitudeT , Glenwoodl°,
Grand Canyon®, Grand Sequoia®, Grand Sequoia° IR,
Grand Sequoia°
ArmorShielcl ", Monaco®, Sienna®, Timberline° American Harvest®, Timberline®
ArmorShieldT" 11, Timberline® Natural Shadow®, Timberline HD®, Timberline® Cool Series®, Timberline Ultra
HD® and Woodland° are fiberglass reinforced, laminated asphalt roof shingles.
4.1.3 Slateline° is a fiberglass reinforced 5-tab asphalt roof
shingle.
4.2 Hip & Ridge Shingles:
4.2.1 Seal -A -Ridge® Ridge Cap Shingles, Seal -A -Ridge®
IR Impact -Resistant Ridge Cap Shingles, Seal -A -Ridge®
ArmorShieldT°" Ridge Cap Shingles and Timbertex® Premium Ridge Cap Shingles are fiberglass
reinforced, hip
and ridge asphalt roof shingles.
Etderior Research and Design, LLC- Evaluation Report 01506.01.08-R22
CertiJlcote o/Authodzodon#9503 6'a EDITION (2017) FBC NON-HVHZ EVALUATION FL10124-R20
GAF Asphalt Roof Shingles Revision 22: 09/20/2017
Page 3 of 6
JTRINIrTY I ERR
4.3 Accessary Starter Strips.
4.3.1 Pro -Start® Eave/Rake Starter Strip Shingles and WeatherBlockerTM Premium Eave/Rake Starter Strip Shingles
are starter strips for asphalt roof shingles.
4.3.2 QuickStart® Peel & Stick Starter Roll is a is a mineral -surfaced,, fiberglass -reinforced, self -adhering SBS
modified bitumen starter strip, nominal 9-inch x 33 ft roll, for use with asphalt shingles with exposure of 6-
inch or less.
4.3.3 StarterMatchTM Starter Strip Shingles are color -coordinated starter strips for use with Grand Canyon® and
Grand Sequoia° series asphalt shingles. StarterMatchTM' are installed as the second starter for Grand
Canyon® and Grand Sequoia® series installations.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity]ERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically forthat purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials
Directory for fire ratings of this product.
5.4 Wind Classification:
5.4.1 The GAF asphalt shingles noted in Section 4.1 are Classified in accordance with FBC Tables 1507.2.7.1 and
R905.2.6.1 to ASTM D3161, Class F and/or ASTM D7158, Class H, indicating the shingles are acceptable for
use in all wind zones up to Vasd =150 mph (Vast =194 mph). Refer to Section 6 for installation requirements
to meet this wind rating.
5.4.2 The GAF hip & ridge shingles noted in Section 4.2 are Classified in accordance with FBC Tables 1507.2.7.1
and R905.2.6.1 to ASTM D3161, Class F, indicating the shingles are acceptable for use in all wind zones up
to Vasd =150 mph (Vuit =194 mph). Refer to Section 6 for installation requirements to meet this wind rating.
5.4.3 Classification by ASTM D7158 applies only to exposure category B or C, as defined in FBC 1609.4.3, and a
mean roof height of 60 feet or less. Calculations by a qualified design professional are required for
conditions outside these limitations. Contact the shingle manufacturer for data specific to each shingle.
5.5 All products in the roof assembly shall have quality assurance audit in accordance with F.A.C. Rule-61G20-3.
6. INSTALLATION:
6.1 Underlavment:
6.1.1 Underlayment shall be acceptable to GAF and shall hold current Florida Statewide Product Approval, or be
Locally Approved per Rule 61G20-3, per FBC 1507.2.3, 1507.2.4 or R905.2.3.
6.2 Starter ShinelesorStarterStrip:
5.2.1 Installation of Pro -Start Eave/Rake Starter Strip Shingles, Weather13locker Premium Eave/Rake Starter Strip
Shingles and QuickStart Peel & Stick Starter Roll shall comply with the GAF current published instructions.
6.3 AsphaltShinzles:
6.3.1 Installation of asphalt shingles shall comply with the GAF current published instructions, using minimum four
(4) nails per shingle in accordance with FBC 1507.2.7 or R905.2.6, with the following exceptions:
➢ Camelot, Camelot II, Grand Canyon, Grand Sequoia, Grand Sequoia IR, Grand Sequoia ArmorShield,
and Woodland require minimum five (5) nails per shingle.
➢ Slateline requires minimum six (6) nails per shingle.
6.3.2 Fasteners shall be in accordance with manufacturer's published requirements, but not less than FBC 1507.2.6
orR905.2.5. Staples are not permitted.
6.3.3 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are
required. Contact the GAF for details.
Exterior Research and Design, I.I.C. Evaluation Report 01506.01.08-RZ2
rerttfimte ofAuthorizatron M03 6tvEDITION (2017)FBC NON-HVHZ EVALUATION F1.10124-1120
GAF Asphalt Roof Shingles Revision 22:09/20/2017
Page 4 of 6
w�
TRII+ERD
6.4 Hip & Ridge Shingles:
6.4.1 Installation of Seal -A -Ridge Ridge Cap Shingles, Seal -A -Ridge IR Impact -Resistant Ridge Cap Shingles and
Seal -A -Ridge ArmorShield Ridge Cap Shingles shall comply with the GAF current published instructions with
a minimum two (2) nails, minimum 3/8-inch head diameter, per shingle and nominal 0.25-inch diameter
beads of Henkel "Loctite PL S30 Roof & Flashing Sealant".
11.5' Sealant
1" (292 mm) 1. Sellante
(ZS mm) (25 tpm) Enduit d 6tanch&6
�1
(905 Nall mm)
Clavo
65/8" _7518° Clouer
12'
(305 mm)
6.4.2 Installation of Timbertex Premium Ridge Cap Shingles shall comply with GAF current published instructions
with a minimum two (2) nails, minimum 3/8-inch head diameter, per shingle and beads of Sonneborn NP3
Gun Grade Polyurethane Sealant or Henkel PL Roofing and Flashing Sealant.
y� �d
NOR
C"r7 t
:aver (005 nun)
5
(229Imn1P
i —
17"
FSsT5 iixlll
6.4.3 Fasteners shall be in accordance with GAF published requirements, but not less than FBC 1507.2.6 or
R905.2.5. Staples are not permitted.
Exterior Research and Design, U.C. Evaluation Report 01506.01.08-R22
Certiftate afAuthonzatlon#9503 61eEDITION (2017)F13C NON-HVHZ EVALUATION FL10124.RZO
GAF Asphalt Roof Shingles Revision 22: 09/2O/2017
Page 5 of 6
ERD
J TRINITY
7. LABELING:
7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC
Table 1507.2.7.1 / R905.2.6.1.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9. MANUFACTURING PLANTS:
Contact the named QA entity for information on which plants produce products covered by Florida Rule 61G20-3 CA
requirements.
10. QUALITY ASSURANCE ENTITY:
UL LLC—QUA9625; (847) 664-3281
ENIb OF EVALUATION REPORT -
Exterior Research and Design, U.C. Evaluation Report 01506.01.08-R22
C'eniloate ofAothari:otion 09503 0 EDITION (2017) FBC NON-HVHZ EVALUATION FL10124-1120
GAF Asphalt Roof Shingles Revision 22: 09/20/2017
Page 6 of 6
U
ram
APR 12 "9'9
ST. Ludo County, Permitting
l�L � O I etc.
Certificate of Authorization #32455
353 Christian Street, Unit #13
Oxford, CT 06478
(203)262-9245
ENGINEER EVALUATE TEST CONSULT CERTIFY
o e
Soprema, Inc. Evaluation Report S18010.06.09-R12
1640 rue Haggerty SCANNED FL2569-R14
Drummondville, Quebec J2C SP8 Canada Date of Issuance: 06/15/2009
BY
(819) 478-2400 St. t' UC(e COun� Revision 12: 02/12/2018
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 6u' Edition (2017) Florida Building Code
sections noted herein.
DESCRIPTION: Soprema Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to
the product(s), the Quality Assurance or the production facility location(s). NEMOJetc. requires a complete review of
this Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMO Ietc. Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 8.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
�ufinger"",
T pO�cv`.
' Jo •..>�.. Qa,.{-;_ The facsimile seal appearing was authorized by Robert
•r'S''O�•�'''-' Nieminen, P.E. on 02/12/2018. This does not serve as an
��� N l��n\ electronicallysigned document.
CERFIFICATION OF INDEPENDENCE:
1. NEMO ETC, LLC does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMO ETC, LLC is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither NEMOI etc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
NNEMOJetc.
ROOFING COMPONENT EVALUATION:
v•
Product Category: Roofing
Sub -Category: Underlayment
Compliance Statement: Roof Underlayments, as produced by Soprema, have demonstrated compliance with the
following sections of the 6t6 Edition (2017) Florida Building Code through testing in accordance with the following
Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth
herein.
Section
Property
Standard
Year
1504.3.1
Wind Resistance
FM 4474
2011
1504.3.1
Wind Uplift
UL 1897
2012
1507.2.4 / 1507.1.1, 1507.2.9.2
Physical Properties
ASTM D1970
2015
1507.3.3
Physical Properties
FRSA/TRI April 2012
2012
FRSA/TRI April 2012 (04-12)
Physical Properties
ASTM D6163
2008
TAS 110
Accelerated Weathering
ASTM D4798
2011
Ent(
Examination
Reference
Date
ERD (TST6049)
ASTM D1970/TAS 110
2968.05.04-2
05/14/2004
ERD (TST6049)
Physical Properties
2757.02.05
02/03/2005
ERD (TST6049)
ASTM D1970 / TAS 110
2974.03.05-2
05/17/2005
ERD (TST6049)
Wind Resistance
2778.07.05
07/15/2005
ERD (TST6049)
Wind Resistance
2779.11.05-R1
04/18/2007
ERD (TST6049)
TAS 103 / TAS 110
S7120.11.07-2
11/02/2007
ERD (TST6049)
ASTM D1970/TAS 110
S13190.02.09-R1
04/01/2010
ERD (TST6049)
ASTM D1970/TAS 110
S31370.03.10-1-R1
04/07/2010
ERD (TST6049)
Physical Properties/ Tensile Adhesion
S11150.05.10-R1
09/09/2010
ERD (TST6049)
Physical Properties/ Tensile Adhesion
S11150.05.09-R2
10/05/2010
ERD (TST6049)
ASTM D1970
S37210.11.11
11/09/2011
ERD(TST6049)
ASTM D1970
S40540.02.13-1
02/19/2013
ERD (TST6049)
Physical Properties/Tensile Adhesion
S43530.02.14-1
02/21/2014
ERD (TST6049)
Physical Properties/ Tensile Adhesion
SOPC-SC7645.02.15
02/13/2015
ERD (TST6049)
Accelerated Weathering
SOPC-SC8520.14
04/17/2015
ERD (TST6049)
Wind Resistance
SOPC-SC14045.05.17-R1
06/07/2017
M-D(CER1592)
HVHZCompliance
15-0508.04
09/24/2015
]CC-ES(EVL2396)
20151BC Compliance
ESR-1524
03/01/2017
PRI (TST5878)
Physical Properties
SOP-064-02-01
12/03/2013
Soprema, Inc. (PDM3511)
Equivalency Declaration
SA SMOOTH PLY 40
06/29/2015
UL, LLC (QUA9625)
Quality Control
Service Confirmation
Exp. 07/18/2020
4.1 Lastobond TU HT is a self -adhering, non -woven polyester fabric surfaced, SBS modified bitumen roof
underlayment; meets ASTM D1970 and FRSA/TRI April 2012 (04-12).
4.2 Lastobond Shield is a self -adhering, woven polyethylene surfaced, SBS modified bitumen roof underlayment
available in two widths; 36 and 45 inch; meets ASTM D1970.
4.3 RESISTO SA SMOOTH PLY 40 is a self -adhering, woven polyethylene surfaced, SBS modified bitumen roof
underlayment; available in 3.3 ft x 65 ft rolls; meets ASTM D1970.
4.4 Lastobond Shield HT is a self -adhering, woven polyethylene surfaced, high temperature, SBS modified bitumen roof
underlayment; meets ASTM D1970.
NEMO ETC, LLC Evaluation Report 518010.06.09-R12
CertJjlcate DfA0hunzadan#32455 eEDmON(2017)FBC NON-HVHZ EVALUATION FL2569-R14
Soprema Roof Underlayments Revision 12: 02/12/2018
Page 2 of 8
ONEMOletc.
4.5 Lastobond Pro HT-N is a self -adhering, woven polyethylene surfaced, SBS modified bitumen roof underlayment
available in two widths; 36 and 45 inch; meets ASTM D1970.
4.6 Lastobond Pro HT-S is a self -adhering, woven polyethylene surfaced, high temperature, SBS modified bitumen roof
underlayment; meets ASTM D3970.
4.7 EnviroShield is a self -adhering, woven polyethylene surfaced, high temperature, SBS modified bitumen roof
underlayment; meets ASTM D1970. _
4.8 Lastobond 195 is a self -adhering, glass -mat reinforced, sand -surfaced, SBS modified bitumen roof underlayment;
meets ASTM D1970.
4.9 Lastobond Eaves Protection Sheet is a self -adhering, glass -mat reinforced, sand -surfaced, SBS modified bitumen
roof underlayment; meets ASTM D1970.
4.10 Lastobond Eco is a self -adhering, glass -mat reinforced, sand -surfaced, SBS modified bitumen roof underlayment;
meets ASTM D1970,
4.11 Lastobond Smooth Seal HT is a self -adhering, glass -mat reinforced, film -surfaced, SBS modified bitumen roof
underlayment; meets ASTM D1970.
4.12 RESISTO LB1236 is a self -adhering, glass -mat reinforced, sand -surfaced, SBS modified bitumen roof underlayment,
with a 36-inch sheet width; meets ASTM D1970.
4.13 PrimeSource Grip -Rite Eave & Valley Protector is a self -adhering, glass -mat reinforced, sand -surfaced, SBS
modified bitumen roof underlayment, with a 36-inch sheet width; meets ASTM D1970.
4.14 , RESISTO LB1244 is a self -adhering, glass -mat reinforced, sand -surfaced, SBS modified bitumen roof underlayment,
with a 44-inch sheet width; meets ASTM D1970.
4.15 Colphene FR GR is a self -adhering, fiberglass reinforced, granule -surfaced, SBS modified bitumen roof
underlayment; meets ASTM D1970 and FRSA/TRI April 2012 (04-12).
5.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting
or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this report; refer to current Approved Roofing Materials Directory for fire ratings of
this product.
5.4 Soprema Roof Underlayments may be used with any prepared roof cover where the product is specifically
referenced within FBC approval documents. If not listed, a request may be made to the Authority Having
Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering.
5.5 Allowable Roof Covers:
•m •
� .OPTIONS
Wood or
Slate or
Underlayment
Asphalt
Nail -On
Foam -On
Metal
Composite
Composite
Shingles
Tile
Tile
Shakes &
Slate
Shingles
Lastobond TU HT
Yes
Yes
Yes See .1
5.5
yes
Yes
_
Yes
Lastobond Shield/Pro HT-N/
Yes
No
No
No
Yes
Yes
RESIST' SA SMOOTH PLY 40
_
Lastobond Shield HT/ Pro HT-5
Yes
No
No
Yes
Yes
Yes
EnviroShield
Yes
No
No
Yes
Yes
Yes
NEMO ETC, LLC Evaluation Report 518010.06,09-1112
Certfjfcute ofAuthorizotion#32455 0 EDITION (2017) FBC NON.HVHZ EVALUATION F1.2569-1114
Supreme Roof Underlayments Revision 12: 02/3Z/2018
Page 3 of 8
NNEMO I etc,
TABLE
1: ROOFC6VEFC
o
Wood or
Slate or
-
Underlayment
Asphalt
Nail -On
Foam -On
Metal
Composite
Composite
Shingles
Tile
Tile
Shakes &
Slate
Shingles
Lastobond Eaves Protection Sheet /
yes
-- No: -- -
- - °=No-
No
Yes
- -Yes_
Lastobond 195
Lastobond ECO / RESISTO LB1236,
— --
- - -
-- - --
- -- -
- -
- ' —
Grip -Rite Eave & Valley Protector /
Yes
No
No
No
Yes
Yes
RESISTO LB1244
Lastobond Smooth Seal HT
Yes
No _
_ _ No. _
Yes
Yes
Yes
Colphene FR GR
Yes
Yes
Yes
No
Yes
Yes
See 5.5.1
5.5.1 "Foam -On Tile" is limited to use of following Approved tile adhesives / underlayment combinations.
TABLE
Adhesive
• �bHEtiVE,/ UNDERLAYMENT
Florida Product Approval
COMBINATIONS
Underlayments
Dow TileBond-
FL22525
Lastobond TU HT
ICP Adhesives Polyset® AH-160
FL6332
Lastobond TU HT or Colphene FR GR
5.6 Allowable Substrates:
5.6.1 Direct -Bond to Deck:
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT, Lastobond Pro HT-S,
EnviroShield, Lastobond TU HT, Lastobond Eaves Protection Sheet, Lastobond 195, Lastobond ECO, RESISTO
LB1236, Grip -Rite Eave & Valley Protector, RESISTO LB1244 or Lastobond Smooth Seal HT applied to:
➢ Plywood; ASTM D41 primed plywood; OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed
Southern Yellow Pine; ASTM D41 primed structural concrete.
Colphene FR GR applied to:
➢ Plywood; ASTM D41 primed plywood; ASTM D41 primed structural concrete.
Note:
➢ While not required over plywood, OSB or Southern Yellow Pine substrates, Soprema recommends priming
with Elastocol Stick or Elastocol 600c if the final roof cover is not slated for installation within 24 hours.
➢ Soprema requires tongue -and -groove board decking be covered with plywood or OSB prior to installation of
the self -adhering underlayment.
5.6.2 Bond -to -Insulation:
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT, Lastobond Pro HT-S,
EnviroShield, Lastobond TU HT, Lastobond Eaves Protection Sheet, Lastoband 195, Lastobond ECO, RESISTO
LB1236, Grip -Rite Eave & Valley Protector, RESISTO LB1244, Lastobond Smooth Seal HT or Colphene FR GR
applied to:
➢ Dens Deck Prime; SECUROCK Gypsum -Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum
requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on
tile systems (Lastobond TU HT only), insulation attachment shall be designed by a qualified design professional
and installed based on testing of the insulation/underlayment system in accordance with FM 4474, Appendix D,
Testing Application Standard TAS 114, Appendix J or UL1807.
I Refer to Tile Manufacturers or Adhesive Manufacturer's Florida Product Approval for overturning Moment Resistance Performance.
NEMO ETC, LLC Evaluation Report 518010.06.09-1112
Certificate of AuthofizaVan#32455 ErnEDITION (2017) FBC NON-HVHZ EVALUATION FL2569-R14
Soprema Roof Underlayments Revision 12:02/12/2018
Page 4 of 8
NNEMO etc.
5.6.3 Bond to Mechanically Attached Base Laver:
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT, Lastobond Pro HT-S,
EnviroShield, Lastobond TU HT, Lastobond Eaves Protection Sheet, Lastobond 195, Lastobond ECO, RESISTO
LB1236, Grip -Rite Eave & Valley Protector, RESISTO LB1244, Lastobond Smooth Seal HT or Colphene FR GR
applied to:
ASTM D226, Type I or II felt; Sopra-G; Modified Sopra-G.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum
codified requirements. For installations under foam -on tile systems (Lastobond TU HT only), base layer shall be
attached in accordance with FRSA/TRI April 2012 (04-12).
5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-22) does not
address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the
underlayment forms part of the load -path. The following wind uplift limitations apply to underlayment systems
that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile applications. Maximum
Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the
ultimate passing pressure divided by 2 (the 2.to 1 margin of safety per FBC 1504.9 has already been applied).
Refer to FRSA/TRI April 2012 (04-12) or FBC 1609 for determination of design wind pressures.
#1 Maximum Design Pressure = -45.0 osf
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Primer: (Optional) Elastocol Stick, Elastocol 600c or RESISTO EXTERIOR PRIMER
Underlayment: Lastobond TU HT or Colphene FR GR, self -adhered.
#2 Maximum Design Pressure =-67.5 psf:
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Primer: Elastocol600c
Underlayment: Lastobond TU HT or Colphene FR GR, self -adhered.
#3 Maximum Design Pressure=-150.0 psf:
Deck: Min. 15/32-inch APA-rated BCX plywood (may be installed C-side up) to meet project
requirements to satisfaction of Authority Having Jurisdiction.
Deck Preparation: Plywood shall be thoroughly cleaned to remove dust and debris that may inhibit adhesion. All
sheathing fasteners shall be driven flush with the surface. All sharp splinters and wood
projections shall be removed/sanded.
Primer: (Optional) RESISTO EXTERIOR PRIMER
Underlayment: Lastobond TU HT, self -adhered, shall be thoroughly roll using hand roller and/or weighted
roller to ensure there are no voids, and ensure there are no voids/bridging at side and end -
laps.
#4 Maximum Design Pressure =-60.0 psf:
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Base Sheet: Sopra-G or Modified Sopra-G mechanically attached with nails (FBC 1517.5.1) and tin caps (FBC
1517.5.2) spaced 6-inch o.c. at the 4-inch laps and 6-inch o.c. in three (3), equally spaced rows
in the center of the sheet.
Underlayment: Lastobond TU HT or Colphene FR GR, self -adhered
5.6.4.1 All other direct -deck, adhered Soprema underlayment systems beneath foam -on tile systems carry a Maximum
Design Pressure of -45 psf.
NEMO ETC, LLC Evaluation Report S18010.06.09-R32
Certificate of Authadutfon#32455 6mEDITION (2017)FBC NON-HVHZ EVALUATION FL2569-R14
Soprema Roof Underlayments Revision 12: 02/12/2018
Page S of 8
ONEMOletc.
5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or
exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table IA.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design
pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment
density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used
methods are ANSI/SPRI WD3, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117.
Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention
Data Sheet 1-29 (January 2016) for tone 2/3 enhancements.
5.7 Exposure Limitations:
Lastobond Eaves Protection Sheet, Lastobond 195,Lastobond Eco, Lastobond Smooth Seal HT, RESISTO LB1236,
Grip -Rite Eave & Valley Protector or RESISTO LB1244 shall not be left exposed for longer than 30-days after
installation.
Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT or Lastobond Pro HT-
S, EnviroShield shall not be left exposed for longer than 90-days after installation.
Lastobond TU HT or Colphene FR GR shall not be left exposed for longer than 180-days after installation.
5.8 Tile Slippage Limitations (TAS 103 per FRSA/TRI April 2012 (04-12)):
When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall be as
follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles.
• ••
Tile Profile
DIIkECT-[DECKTILE INSTALLATIONS
Staging Method
Maximum
Slope
Underlayment
Flat
Max. 10-tile stack
6:12
Lugged
Max. 10-tile stack
5:12
Max. 30-tile stack (bottom 2-tile stack
shall be inverted, followed by 8 tiles high
6:12
on slope, as shown below)
Lastobond TU HT
Lugged
Flat
Max.10-tile stack
5:12
Colphene FR GR
Lugged
Max. 10-tile stack
6:12
NEMO ETC, LLC Evaluation Report S38030.06.09-R12
Certificate ofAuthorizotton N32455 6P EDITION (2017) FBC NON-HVHZ EVALUATION FL2569-1114
Soprema Roof Underlaymems Revision 22: 02/12/2018
Page 6 of 8
NNEMO I etc,
6.1 Soprema Roof Underlayments shall be installed in accordance with Soprema published installation requirements
subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to
remove any dust and debris prior to application, and prime the substrate with Elastocol Stick, Elastocol 600c or
RESISTO EXTERIOR PRIMER (if applicable).
6.3
6.3.1
Lastobond TU HT, Lastobond Shield, Lastobond Pro HT-N, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT,
Lastobond Pro HT-S, EnviroShield, Lastobond Eaves Protection Sheet, Lastobond 195, Lastobond Eco, Lastobond
Smooth Seal HT, RESISTO LB1236, Grip -Rite Eave 8, Valley Protector, RESISTO LB2244 or Colphene FR GR:
Shall be installed in comoliance with the requirements for ASTM D1970 underlavment in FBC Table 1507.1.1 for
the type of prepared roof covering to be installed.
6.3.2 Non -Tile Applications.,
While priming is optional, Soprema recommends priming with Elastocol Stick, Elastocol 600c or RESISTO EXTERIOR
PRIMER if the final roof cover is not slated for installation within 24 hours.
Apply sheet parallel to the roof edge. Roll out approximately 30 ft of membrane and peel back the first 3 ft of
release film.
Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible.
Once the entire length of membrane is in place, peel -off the release film diagonally while holding the membrane
tight. Firmly roll the membrane into place to achieve a bond.
Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6-inches and
staggered not less than 2-ft from vertical seams in the course below. All over -granule end -laps shall be sealed
using either heat -welding or hot air welding techniques.
When installing at slopes above 8:12, Soprema recommends back -nailing in the overlap area at the top of the
sheet at 12-inch o.c.
For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet over
valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge in each direction.
For valleys, apply the sheet starting at the lowest point and work upward.
6.3.3 Tile Applications (Lastobond TU HT or Colphene FR GR only):
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions
noted above as a guideline.
For foam -on tile applications, reference is made to Section 5.6.4 herein for wind resistance limitations that fall
outside the scope of FRSA/TRI April 2012 (04-12).
Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment. See
Table 2 herein, and Soprema published requirements for tile staging.
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
MEMO ETC, LLC Evaluation Report S38010.06.09-1112
Certifimte ofAvthorizadonN32455 0 EDITION (2017) F8C NON-HVHZ EVALUATION FL2569-R14
Soprema Roof Underlayments Revision 12:02/12/2018
Page 7 of 8
M(
NEMiO etc.
Contact the noted QA agency for information on product locations covered for F.A.C. 61G20-3 QA requirements.
The following plants have qualified products under their respective physical properties specifications.
Plant
Specification
Products)
Lastobond Shield, RESISTO SA SMOOTH PLY 40, Lastobond Shield HT,
LastobondProHT-N, Lastobond Pro Hi EnviroShield, Lastobond 195,
Drummondville,
ASTM D1970
Lastobond Eaves Protection Sheet, Lastobond Eco, Lastobond Smooth
QC (Canada)
Seal HT, RESISTO L61236, PrimeSource Grip -Rite Eave & Valley
Protector, RESISTO LB1244
ASTM D1970 & FRSA/fRI 04-12
Colphene FR GR
Wadsworth, OH
Lastobond 195, Lastobond Eaves Protection Sheet, Lastobond Eco,
ASTM D1970
Lastobond Smooth Seal HT, RESISTO LB3236, PrimeSource Grip -Rite
Eave & Valley Protector, RESISTO LB1244
ASTM D1970 & FRSA/TRI 04-12
Lastobond TU HT; Colphene FR GR
Lastobond 195, Lastobond Eaves Protection Sheet, Lastobond Eco,
Gulfport, MS
ASTM D1970
Lastobond Smooth Seal HT, RESISTO LB1236, PrimeSource Grip -Rite
Eave & Valley Protector, RESISTO LB1244
UL, LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com
- END OF EVALUATION REPORT -
NEMO ETC, LLC Evaluation Report S18010.06.09-R32
Certflfla of Awhorization#32455 11 EDITION(2017) W NON-i EVALUATION F1.2569-R14
Soprema Roof Underlayments Revision 12: 02/12/2018
Page 8 of 8