BLOWER DOOR TEST FORM
House Infiltration Test Certification
SEP 13 2019
Prescriptive and Performance Methop Permitting Department
�( St. Lucie County, FL
Date: 09/13/2019 Permit #: f qot v_ ...__
F Contractor:
Job Address: 5215
Construction:
House Infiltration Test Results
Lake Circle
Construction —Complete ( )Existing — AfterAddition-
CFM (50) = 1603
Volume = 1498f
ACH (50) = CFM (50) x 60 / volume = 6_4
Passing results must be & ACH (50) or less
SLC Climate Zone 2
Test Date:
Mechanical Ventilation required less than 3 ACH
( ) Pass ( ) Fail
FBC, Energy
The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes per
hour in Climate Zone 1, 2 and 3 air changes per hour in Climate Zones 3 through 8. Testing shall be conducted with a
blower door at a pressure of 0.2 inches w. g. (50 Pascals). Testing shall be conducted by either individuals as defined in
Section 553.993(5) or (7), Florida Statutes or individuals licensed as set forth in Section 489.105 (3)(f), (g) or (i) or an
approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building
thermal envelope.
FBC, Residential
Where the air infiltration rate of a dwelling unit is less than 3 air changes per hour when tested with a blower door at a
pressure of 0.2 inch w. c. (50 Pa) in accordance with Section R402.4.1.2 of the Florida Building Code, Energy Conservation
the dwelling unit shall be provided with whole -house mechanical ventilation in accordance with Section M1507.3.
Testing Company
Company Name: PEG LLC
I hereby certify that the
requirements in accord
Signature:
Printed Name: 01uwafeml Benedict
License/Certification #: 0453377
Address: 3975 Fair Ridge Drive
ilts demonstrate compliance with FBC Energy Conservation
Climate Zone 2.