DIVISION: 08 00 00—OPENINGS
SECTION: 08 95 43—VENTS/FOUNDATION FLOOD VENTS
REPORT HOLDER:
FLOOD FLAPS', LLC
POST OFFICE BOX 1003
SCANNED
BY
St. Lucie County
REVIEWED FOR
CODE COMPLIANCE
ST. LUCIE COUNTY
p�B ®CC
ISLE OF PALMS, SOUTH CAROLINA 29451
EVALUATION SUBJECT:
FLOOD FLAPS® AUTOMATIC FLOOD VENTS:
MODELS FFWF12; FFNF12; FFWF08; FFNF08; FFWF05; FFNF05
1CCC ICC ICC
10� �Ug) c D
Look for the trusted marks of Conformityl
"2014 Recipient of Prestigious Western States Seismic Policy Council
t (WSSPQ Award in Excellence"
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not
specifically addressed, nor are they to be. construed as an endorsement of the subject of the report or a
recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as V
uoncc noes
to any finding or other matter in this report, or as to any product covered by the report.
Copyright 0 2017 ICC Evaluation Service, LLC. All rights reserved.
v-va,uarlon rteport ESR-3560
Reissued September 2017
This report is subject to renewal September 2018.
www.fcc-es ora 1 (800) 423.6587 1 (562) 699-0543 A Subsidiary of the International Code Council®
DIVISION: 08 00 00—OPENINGS
Section: 08 95 43—Vents/Foundation Flood Vents
REPORT HOLDER:
FLOOD FLAPS®, LLC
POST OFFICE BOX 1003
ISLE OF PALMS, SOUTH CAROLINA 29451
(843) 881-0190
www.floodill corn
mfo(a�0ood0aos com
EVALUATION SUBJECT:
FLOOD FLAPS® AUTOMATIC FLOOD VENTS: MODELS
FFWF12; FFNF12; FFWF08; FFNF08; FFWF05; FFNF05
1.0 EVALUATION SCOPE
Compliance with the following codes:
■ 2015, 2012 and 2009 intemational Building Codee (IBC)
■ 2015, 2012 and 2009 International Residential Codes
(IRC)
Properties evaluated:
■ Physical operation
■ Water flow
■ Weathering
2.0 USES
Flood Flapse automatic flood vents are used to provide for
the equalization of hydrostatic flood forces on exterior
walls. Certain models also allow natural ventilation.
3.0 DESCRIPTION
3.1 General:
Flood Flaps® automatic flood vents are engineered
mechanically operated flood vents (FVs) that automatically
allow flood waters to enter and exit enclosed areas. The
FVs are constructed of ABS plastic which serves as the
FYs housing, and a front grill that contains an anodized
metal screen imbedded in polypropylene plastic. On
contact with rising flood water, the grill will disengage from
its secured position, allowing flood water and debris to flow
through in either direction. The IVs are available in two
series as described in Section 3.3.
The sealed series models contain two rubber flaps that
close the FV to the passage of air when using with
conditioned areas or sealed crawl spaces. In the same
manner as the grill, the two rubber flaps. are pushed open
by water pressure, allowing water and debris to flow
through the FV in either direction. See Figure 1 for an
illustration of the Flood Flaps® automatic FV.
3.2 Engineered Opening. -
The Flood Flaps® automatic FVs comply with the design
principle noted in Sections 2.7.2.2 and 2.7.3 of ASCE/SEI
24-14 [Section 2.6.2.2 of ASCE/SEI 24-05 (2012 and 2009
IBC and IRC)) for a rate of rise and fall of 5 feet per hour
(0.423 mm/s). In order to comply with the engineered
opening requirement of ASCE/SEI 24, Flood Flaps®
automatic FVs must be installed in accordance with
Section 4.0.
3.3 Flood Vent Series Models:
Flood Flapse automatic FVs are available in two series
with multiple models and sizes as described in Table 1.
The sealed series models, designated FFWF, include two
rubber flaps for the prevention of air flow. The multi-
purpose series, designated FFNF, omits the rubber flaps.
3.4 Natural Ventilation:
Flood Flaps® automatic FV models FFNF12, FFNF08,
FFNF05, and FFNF02 have metal screens with inch by
'/4 inch (6 mm bey 6 mm) openings and provide 37 square
inches (0.02 m) of net free opening to supply natural
ventilation for under -floor ventilation. Flood Flaps®
automatic FV models FFWF12, FFWF08, and FFWF05
have not been evaluated for use as openings for under-
floor ventilation.
4.0 DESIGN AND INSTALLATION
Flood Flaps® automatic FVs are designed to be installed
into walls of existing or new construction. Installation of
the FVs must be in accordance with the manufacturer's
instru® ons. the applicable code and this report. Flood
Flaps automatic FVs can be installed in wood, masonry
and concrete walls up to a thickness of 12 inches
(305 mm). In order to comply with the engineered opening
design principle noted in Sections 2.7.2.2 and 2.7.3 of
ASCE/SEI 24-14 [Section 2.62.2 of ASCE/SEI 24-05
(2012 and 2009 IBC and IRC)), the Flood Flaps® FVs must
be installed as follows:
■ With a minimum of two openings on different sides of
each enclosed area.
1CGESEvalwhon Reports are not to be romtruedmmpremmingaesthetia orany odwattributernot +wl a
manendorsementofthesubjectofthereponorare mmwdwimferiame.7here&rmrva ,ybyICCQEvohmtronI,normelheylo be mratmed
to mryftndirrgororhermoaer in A& report, orm to ary product eove dhy the report, a C.
express or lmplin4 m
Copyright ® 20171CC Evaluation Service. L.L.C. All rights reserved.
a
Page 1 of 3
�a�v-CJ =valuation Kepor t ESR-3560
Reissued September2O17
This report is subject to renewal September2O18.
www.icc-es.orn 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the lntemational Mode Council®
DIVISION: 08 00 0o—OPENINGS
Section: 08 95 43=Vents%Foundation Flood Vents
REPORT HOLDER:
FLOOD FLAPS°, LLC
POST OFFICE BOX 1003
ISLE OF PALMS, SOUTH CAROLINA 29451
(843) 881-0190
www.floodfiaos coin
infoOfloodflaos com
EVALUATION SUBJECT:
FLOOD FLAPS® AUTOMATIC FLOOD VENTS: MODELS
FFWF12; FFNF12; FFWF08; FFNF08; FFWFOS; FFNF05
1.0 EVALUATION SCOPE
Compliance with the following codes:
■ 2015, 2012 and 2009 International Building Code® (IBC)
■ 2015, 2012 and 2009 International Residential Code®
(IRC)
Properties evaluated:
■ Physical operation
■ Waterflow .
■ Weathering
2.0 USES
Flood Flaps® automatic flood vents are used to provide for
the equalization of hydrostatic flood forces on exterior
walls. Certain models also allow natural ventilation.
3.0 DESCRIPTION
3.1 General:
Flood Flapse automatic flood vents are engineered
mechanically operated flood vents (FVs) that automatically
allow flood waters to enter and exit enclosed areas. The
FVs are constructed of ABS plastic which serves as the
Mrs housing, and a front grill that contains an anodized
metal screen imbedded in polypropylene plastic. On
contact with rising flood water, the grill will disengage from
its secured position, allowing flood water and debris to flow
through in either direction. The FVs are available in two
series as described in Section 3.3.
ri or remtmoenda mjorih ro& nere is
or arto anypro&ar vvdbythe report.
The sealed series models contain two rubber flaps that
close the. FV to the passage of air when using with
conditioned areas or sealed crawl spaces. In the same
manner as the grill, the two rubber flaps.are pushed open
by water pressure, allowing water and debris to flow
through the FV in either direction. See Figure 1 for an
illustration of the Flood Flaps® automatic FV.
32 Engineered Opening:
The Flood Flaps® automatic FVs comply with the design
principle noted in Sections 2.722 and 2.7.3 of ASCEISEI
24-14 (Section 2.622 of ASCE/SEI 24-05 (2012 and 2009
IBC and IRC)] for a rate of rise and fall of 5 feet per hour
(0.423 mints). In order to comply with the engineered
opening requirement of ASCE/SEi 24, Flood Flaps®
automatic FVa must be installed in accordance with
Section 4.0.
3.3 Flood Vent Series Models:
Flood Flaps® automatic FVs are available in two series
with multiple models and sizes as described in Table 1.
The sealed series models, designated FFWF, include two
rubber flaps for the prevention of air flow. The multi-
purpose series, designated FFNF, omits the rubber flaps.
3A Natural Ventilation:
Flood Flaps® automatic FV models FFNF12, FFNF08,
FFNF05, and FFNF02 have metal screens with '14Inch by
'la inch (6 min by 6 mm)openings and provide 37 square
Inches (0.02 m ), of net free opening to supply natural
ventilation for under -floor ventilation. Flood Flaps®
automatic FV models FFWF12, FFWF08, and FFWF05
have not been evaluated for use as openings for under-
floor ventilation.
4.0 DESIGN AND INSTALLATION
Flood Flaps® automatic FVs are designed to be installed
Into walls of existing or new construction. Installation of
the FVs must be in accordance with the manufacturer's
instructions, the applicable code and this report. Flood
Flaps® automatic FVs can be installed in wood, masonry
and concrete walls, up to a thicimess of 12 inches
(305 mm). In order to comply with the engineered opening
design principle noted in Sections 2.72.2 and 2.7.3 of
ASCEISEI 24-14 [Section 2.62.2 of ASCE/SEI 24-05
(2012 and 2009 IBC and IRC)], the Flood Flaps® FVs must
be installed as follows:
■ With a minimum of two openings on different sides of
each enclosed area.
nor ore duy ro be oorarmed
LLC erg r or Implied m
m's"
Page 1 of 3
Copyright® 201T ICC Evaluation Service, LLC. M rights reserved.
ESR3560 I Mast WidelyAccepted and Trusted Page 2 of 3
With a minimum of one FV for every 220 square
feet (20 e) of enclosed area.
■ Below the base flood elevation.
■ With the bottom of the FV located a max(mum of
12 inches (305 mm) above grade.
5.0 CONDITIONS OF USE
The Flood Flaps® automatic flood vents described in this
report comply with, or are suitable alternatives to what is
specified In, those codes listed in Section 1.0 of this report,
subject to the following conditions:
5.1 The Flood Flaps® automatic FVs must be installed in
accordance with this report, the applicable code and
the manufacturers installation instructions. In the
event of a conflict, the instructions in this report
govern.
5.2 The Flood Flapse automatic FVs must not be used in
place of 'breakaway walls' in coastal high hazard
areas, but are permitted for use in conjunction with
breakaway walls in other areas.
6.0 EVIDENCE SUBMITTED
Data in accordance with the ICC-ES Acceptance Criteria
for Mechanically Operated Flood Vents (AC364), dated
August2015.
7.0 IDENTIFICATION
The Flood Flaps® models recognized in this report are
identified by a label bearing the manufacturer's name,
the model number, and the evaluation report number
(ESR3560).
TABLE 1—FLOOD FLAP AUTOMATIC FLOOD VENT MODEL SIZES
MODEL
NUMBER
MODEL
DESIGNATION
ROUGH OPENING
(Width X Height)
(inches)
VENT SIZE
(W X H X D)
(inches)
ENCLOSED AREA
COVERAGE
(fly)
NET FREE AREA
OPENING'
(in)
FFWF12
Sealed Series
16x8
1 /aX /,X12
220
NA
FFNF12
Multi -Purpose
16 x 8
1 /a X /. X 12
220
37
FFWFO8
Sealed Series
16 x 8
1 !a x /4 x 8
220
NA
FFNF08
Multi -Purpose
16 x 8
15 /e x 4 x e
220
37
FFWF05
Sealed Series
16x8
1 /ax714x5
220
NA
FFNF05
Multi -Purpose
16 x 8
1 /e x /. x 5
220
37
For S1:1 Inch = 25.4 mm;1 P` = 0.093 m'
'For under-floorventilation only_
Trusted
3of3
FFWF12
12" DEPTH
FIGURE 1—FLOOD FLAPS®AUTOMATIC FLOOD VENT
FFNF08
FIGURE 2—FLOOD FLAPS® AUTOMATIC FLOOD VENT SERIES MODELS
S" DEPTH 5" DEPTH
FIGURE 3—FLOOD FLAPS® AUTOMATIC FLOOD VENTS MULTIPLE DEPTH OFFERINGS
ESR3560 I Most WidelyAccepted and Trusted rage & ..,
•B' With a' minimum of one FV for every 220 square
feet (20 mz) of enclosed area.
■ Below the base flood elevation.
■ With the bottom of the FV located a maximum of
12 inches (305 mm) above grade.
5.0 CONDITIONS OF USE
The Flood Flaps® automatic flood vents described in this
report comply with, or are suitable alternatives to what is
specified in, those codes listed in Section 1.0 of this report,
subject to the following conditions:
5.1 The Flood Flaps® automatic FVs must be installed in
accordance with this report, the applicable code and
the manufacturer's installation instructions. In the
event of a conflict, the instructions in this report
govern.
5.2 The Flood Flaps automatic FVs must not be used in
place of "breakaway walls" in coastal high hazard
areas, but are permitted for use in conjunction with
breakaway walls in other areas.
6.0 EVIDENCE SUBMITTED
Data in accordance with the ICC-ES Acceptance Criteria
for Mechanically Operated Flood Vents (AC364), dated
August2015.
7.0 IDENTIFICATION
The Flood Flaps® models recognized in this report are
identified- by a label bearing the manufacturer's name,
the model number, and the evaluation report number
(ESR-3560).
TABLE 1—FLOOD FLAP AUTOMATIC FLOOD VENT MODEL SIZES
MODEL
NUMBER
MODEL
DESIGNATION
ROUGH OPENING
(Width X Height)
(inches)
VENT SIZE
(W X H X D)
(inches)
ENCLOSED AREA
COVERAGE
(fe)
NET FREE AREA
OPENING'
(in)
FFWF12
Sealed Series
16 x 8
15 /e X /4 X 12
220
NA
FFNF12
Multi -Purpose
16 x 8
15 /e X 7 /4 X 12
220
37
FFWFO8
Sealed Series
16 x 8
15 /. x /4 x 8
220
NA
FFNFO8
Multi -Purpose
16 x 8
15 /e x /4 x 8
220
37
FFWFO5
Sealed Series
16 x 8
1551, x 731, x 5
220
NA
FFNFO5
Multi -Purpose
16 x 8
15 /e x 714 x 5
220
37
For Sl:1 inch =25.4 mm;1=0.093m
'For under -floor ventilation only.