HomeMy WebLinkAboutELECTRICAL LOAD CALCULATION=RECEIVED
Matula Electric 1010 W Midway Road -tv god od ^ vt�l I
Ft. Pierce, FI. 34982
772-461-8328
ELECTRICAL LOAD CALCULATION
1987 S.F. LIVING@VA 5961VA
(2) 20 AMP APPLIANCE CIRCUITS 3000VA
RANGE 8000VA
REFRIGERATOR 1200VA
LAUNDRY 1500VA
DRYER 5000VA
WATER HEATER 3600VA
WELL 4500V
AR
misc. 750OVA
A/C HEAT @ 100%--15000VA
TOTAL
25261VA
25261VA = 105 AMPS
240
LOAD SHED 15,000W AC HEAT
USE 200 AMP SERVICE
SCANNED
BY
St. Lucie County
BT.LUCIE COUNTY
PLAN REVIEW
BLDG:
DATE:
ELE('Vg: -76 DATE� '
PLUMB:
DATE:
MECH:
DATE: