HomeMy WebLinkAboutPLANSGeneral Notes ` A. CONCRETE & FOUNDATION DESIGN: 1. ALL CONCRETE GRADE BEAMS AND FOOTINGS SHALL BE 3000 PSIMINIMUM. 2. ALL CONCRETE FILLED SUPPORTED SLABS SHALL BE 2500 PSI MINIMUM, 3 1/2' NOMINAL THICKNESS. 3. FIBERMESH (3/4" PER CUBIC YARD MIN.) MEETING APPROPRIATE ACI AND ASTMREQUIREMMUS MAY BE USED INLIEU OF WELDED WIRE MESH 4. ALL SLABS ON GRADE SHALL BE 4" THICK WITH FIBERMESH 5. ALL REINFORCING SHALL CONFORM TO ASTM A615, BE GRADE 60 (60 KSI MIN.) DEFORMED BARS, 43 BARS MAY BE GRADE 40 6. ALL OVER POUR CONCRETE FILLED SUPPORTED SLABS SHALL BE 3000 PSI MIN., 2" MINIMUM THICKNESS. 7. SOIL BEARING PRESSURE SHALL BE A MINIMUM OF 1500 PSF. 8, THE CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING: OPC (PORTLAND CEMENT TYPE 1,-ASTM C 150). AGGREGATES -#6 STONE , ASTM C 33 SIZE NO. 67 LESS THAN 314". AIR ENTRAINING +/- 1% -ASTM C 260. WATER REDUCING AGENT - ASTM C494. CLEANPOTABLE WATER OTHER ADMIXTURES SHALL NOT BE PERMITTED. 9. METAL WELDED WIRE SHALL CONFORM TO ASTM A 185. 10. PREPARE & PLACE CONCRETE ACCORDING TO AMERICAN CONCRETE INSTTFUTE MANUAL STANDARD PRACTICE, PART 1, 2, & 3 ALONG WITH HOT WEATHER CONDITIONS RECOMMENDATIONS. 11. IF UTILIZING EXISTING CONCRETE FOR FOUNDATION, CONCRETE SHALL BE A MINIMUM OF 4" IN THICKNESS, VISIBLY FREE OF ANY STRUCTURAL EXCESSIVE CRACKING, SPALI.ING OR OTHER DETERIORATION. B. MASONRY: 1. CONCRETE MASONRY UNITS (CMU SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR 2 ALL MORTAR SHALL BE OF TYPE M OR S. 3.ALL GROUT SHALL BE 2000 PSI I IU14UMAN D HAVE MAXIMUM COARSE AGGREGATE SIZE OF SO% 4.PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS T-0" IN HEIGHT. C. ALUMINUM: 1. ALL STRUCTURAL ALUMINIUM SHALL CONFORMTO THE MI IMUMREQUIREMENIS OF 6005-T5 FOR ALLOY WITH A MININNMTHICKNESS OF 0.040" FOR SUPPORTING MEMBERS. 2. WEERE RICK PLATES ARE USED A MINIMUMTHICKNESS OF 0.024' SHALL APPLY, 3. STRUCTURAL ALUMINUM DESIGN CONFORMS TO "PART 1-A - SPECIFICATIONS FOR ALUMINUM STRUCTURES -ALLOWABLE STRESS DESIGN" OR "PART 1-B - SPECIFICATIONS FOR ALUMINUM STRUCTURES - BUILDING LOAD AND RESISTANCE FACTOR DESIGN' OF TEE ALUMINUM DESIGN MANUAL PREPARED BY THE ALUMINUM ASSOCIATION, INC. WASHINGTON D.C. TBE FLORIDA BUILDING? CODB 6lh EDITION ( CHAPTER 16 STRUCTURAL DESIGN & CHAPTER 20 4. ALUMINUM, ALUMINUM COMES INTO CONTACT WITH STEEL, OR PRESSURE TREATED LUMBER PROVIDE DIELECTRIC SEPARATION. 5. ALUMINUM MEMBERS SHALL BE STITCHED WITH NO LESS THAN#10 SMS 6" FROMTHE ENDS AND 12" ON CENTER, IF USING #12 SPACING MAYBE 24" ON CENTER 6. VINYL AND ACRYLIC PANELS SHALL BE REMOVABLE. THEY SHALL BE IDENTIFIED WITH A DECAL ESSENTIALLY STATING "REMOVABLE PANEL SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH. DECAL SHALL BE PLACED SOITIS VISIBLE WHENPANELISINSTALLED. 7. 1'X2"X0.045" NON-STRUCTURAL MEMBERS SHALL BE ATTACHED TO HOST WITH 1/4'0 X 1-3/4" EMBEDMENT & 24' O.C. MASONRY SCREW FOR CONCRETE & EQUIVALENT SIZE WOOD SCREW WBENINWOOD &#10X 112" EMBEDMENT SIAS OR TEK SCREWS INALUMINUM MEMBERS TYPICAL. D. FASTENERS: 1. ALL LAG BOLTS SHALL CONFORMTO STAINLESS STEEL TYPE 300 18-8, WITH STANDARD FLAT WASHER UNLESS MANUFACTURER GALVANIZES BOLTS SPECIFIES FOR USE WITH ACQ PRESSURE TREATED WOOD. 2. HEX BOLTS HAS TO B, M A 325, PLATED WITH STANDARD ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED FLAT WASHERS AND. i:_ HOME. - 3. ALL CONCRETE SCREWS SHALL BE, SIMPSON, HTLTI, RAWL, 2. IF ENCLOSURE CONTAINS A SWIMMING POOL OR SPA, THE TAPCON, REDHEAD, DYNABOLT, PORTECT OR APPROVED ENCLOSURE SHALL COMPLY WITH RESIDENTIAL SWIMMING EQUAL. BARRIER REQUIREMENTS OF THE FLORIDA BUILDING CODE 6th 4. ALL METAL TIES AND ASSOCIATED ACCESSORIES SHALL BE EDITION R 4501.17INITS ENTIRETY. HOT DIPPED GALVANIZED. 3. DOOR LOCATIONS MAY BE DETERMINED IN THE FIELD BY 5. ALL LAG BOLTS SHALL HAVE A MINIMUM EMBEDMENT OF 8X CONTRACTOR BOLT DIAMETER INTO STRUCTURAL FRAMING (G=.42 MIN.). 4. IF PAVERS ARE UNDER ALUMINUM MEMBERS THEY SHALL 6. LAG BOLTS AND SCREWS INTO WOOD FRAMING SHALL BE HAVE EPDXY ADHESIVE TO CONCRETE OR IF USING GROUT, PROVIDED WITH PILOT HOLESHAVING A DIAMETER NOT ENSURE BONDING AGENT IS USED FIRST. GREATER THM70 PERCENT OF THE THREAD DIAMETER OF 5. SCREENING MATERIAL SHALL BE 18X14X0.013 OR THE BOLT OR SCREW. ALL LAG BOLTS AND SCREWS SHALL BE EQUrVALENT DENSITY SCREENMESH ONLY UNLESS NOTED INSERTED IN PILOT HOLES B Y TURNING AND UNDER NO ONDRAWINGS-2. CIRCUMSTANCES BY DRIVING WITH AHAMM&R 6. PLEASE NOTE: 2x2(typ) DIAGONAL BRACING SHALL BE 7. ALL EXPANSION ANCHORS SHALL BE DESIGNED IN 2"X2"X0.055" MATERIAL, UNLESS OTHERWISE NOTED ON S-Z ACCORDANCE WITH THE SPECIFIC MANUFACTURER'S REQUIREMENTS AND ALLOWABLE LOADS AND SHALL ONLY BE APPLIED IN CONDITIONS ACCEPTABLE TO MANUFACTURER FASTENERS SHALL BE A IMMOM OF SAE GRADE #5 OR BETTER ZINC PLATED. DESIGN DATA: a. ALL FASTENERS CONNECTING ALUMINUM COMPONENTS OR 1. ULTIMATE DESIGN WIND SPEED Vult, (3 SECOND GUST): PRESSURE TREATED LUMBER ARE STAINLESS STEEL TYPE 300 NOMINANWIND SPEED Vasd: 18-8, UNLESS MANUFACTURER GALVANIZED BOLTS SPECIFIES FOR USE WITH ACQ PRESSURE TREATED WOOD. OR 2. RISK CATEGORYGORY: OTHERWISE NOTED ONPLANS. 3. WIND EXPOSURE: 9. ALL FASTENERS SHALL COMPLY WITH ASTM A153. 4. WIND LOADS: 10. ALL CONNECTORS SHALL COMPLY WITH ASTM A653 SCREENROOF: NTA CLASS G-185. SCREEN WALLS: 31 PSF 11. FOR SMS, THE MINIMUM CENTER -TO -CENTER SPACING SOLID ROOF (SCREEN WALL): 25 PSF SHALL BE 314' AND MIIIMUM CENTER -TO -EDGE SHALL BE 112" COMPONENTS AND CLADDING LOAD: +19.00/-25.7 PSF TTNI.FSSNCYrFTI (YMTzR WTCF. ' E. REFERENCE STANDARDS: ASTME 119 ASTME 1300 CURRENIASCE7 CURRENT ALUMINUM DESIGN MANUAL -AA ASM35, AND SPEC. FOR ALUMINUM PART 1-A, & I-B ASTMC94 ASTMC150 ASTMC33 ASTMC260 ASTM C494 ASTMA615 ASTMAI85 FLORIDA BUILDING CODE 61h ED17YON (CHAPTERS 16.20 & 23). F.ABBREVIATIONS: THE FOLLOWING LIST OF ABBREVIATIONS IS NOT INTENDED TO REPRESENT ALL THOSE USED ON THESE DRAWINGS, BUT TO SUPPLEMENT THE MORE COMMONABBREVIATIONS. 1. TYP -TYPICAL 2. SIM-SIMILAR 3. UON-UNLESS OTHERWISE NOTED 4. CONT--CONTINUOUS 5. VIF- VERIFY INFIELD G. RESPONSIBILITY: 1. ALL SITE WORK SHALL BE PERFORMED BY ALICENSED CONTRACTOR INACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDINANCES, ETC. 2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND DETAILS, NOTIFYING ENGINEER OF ANY DISCREPANCIES BETWEEN DRAWINGS, FABRICATED ITEMS, OR ACTUAL FIELD CONDITIONS. 3. THESE DRAWINGS REPRESENT THE ACCEPTABILITY OF THE 'SUNROOM ROOM ADDITION ELEMENTS AS PROVIDED BY THE CONTRACTOR- 4. ALL DETAILS ON THESE DRAWINGS ARE ENGINEERED. BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND MANUFACTURER 5. ANY DETAILS NOT SHOWNARE TO BE ENGINEERED BY A LICENSED P.E. IN ACCORDANCE WITH STANDARD ENGINEERING PRACTICES. H. MISCELLANEOUS: 1. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPARATE 4TH WALL SUPPORT SYSTEM MUST BE ENGINEERED SO THAT NO 150 MPH 116 MPH 1 B S FACTORAPPLIED TO SCREEN WIND LOADS FOR 18X14X0.013 OR EQUIVALENT DENSITY SCREEN MESH: 0.88 6. FACTOR APPLIED TO SCREEN WIND LOADS FOR ALLOWABLE STRESS DESIGN 0.6 7. LNELOAD: 3001b. VERTICAL DOWNLOAD ONPRIMARY SCREENENCLOSURE MEMBERS. 2001b. VERTICAL DOWNLOAD ON SCREENENCLOSURE PURLINS. 8. EXISTING SLAB AND OR FOOTING MEETS THE REQUIREMENTS TO RESIST THE UPLOADS FOR THE PROPOSED STRUCTURE, 9. SCREEN ROOF TYPE : NTA 10. SOMD ROOFTYPE: 3"X48"X0.032" ELITE EPS COMPOSITE PANEL ROOF In, FOA DENSITY, FLORIDA PRODUCT APPROVAL, FL 756 LR-4. ALUMINUM STRUCTURAL MEMBERS I HOLLOW SECTIONS 2 x 2------------------------------------2" x 2" x 0.044" 2 x 3:----------------------2" x 3" x 0.050" 2 x 4:----------------------2" x 4" x 0.050" 2 x 5----------------------------------------2„ x 5" x 0.050" 3 x 3:-----------------------------------3" x 3" x 0.125" OPEN BACK SECTIONS 1 x 2:-------------------- 1" x 2" x 0.040" 1 x 3:-------T-------------------------------- 1" x 3" x 0.045" SNAP SECTIONS 2 x 2 SMS: ---------------------------------- 2"x 2" x 0.045" 2 x 3 SM&--------------------------------2" x 3" x 0.072" 2 x 4 SMS:-------------------------------- 2" x 4" x 0.045" 3 x 3 SMS---------------------------------- 3" x 3"x 0.090" SELF MATING (SMB 2 x 4 SMB----------------------- 2"x 4" x 0.044" x 0.100" 2 x 5 SMB:---------------------- 2"x 5" x 0.050" x 0.118" 2 x 6 SMB---------------------- 2"x 6" x 0.050" x 0.120" 2 x 7 SMB---------------------- 2"x 7" x 0.057" x 0.120" 2 x 8 SMB=--------------------- 2"x 8" x 0.072" x 0224" 2 x 9 SMB----------------------- 2"x9" x 0.072" x 0224" 2 x 10 SMB-------------------- 2" x 10" x 0.092"x 0.374" TUBE SECTIONS 2 x 2---------------------------------------2" x 2" x 0.090" (GTo y 05 13 REIVIEWED FOR CODE COMPLIANCE ST. LUCIE COUNTY SCANNED BY St. Lucie County ENGINEER OF RECORD: David W. Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson P FLORIDA LICENSE 38654 Mark R. Dunn P.E. FLORIDA LICENSE: 73968 Joel Falardeau P.E. FLORIDA LICENSE 70667 Erik Stuart P.E. FLORIDA LICENSE 77605 FBC Plans & Engineering Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph#(813)788-5314 Fax# 1-(866)824-7894 E-mail-erb@lbcplans.com Website-www.lb cplans. com C.O.A: #29054 DATE: 4/16/2019 I DRAWN BY: TLK I IREVISION: I DATE 1 RO 1 R0 2 RO 3 RO 4 ADDRESS: 15 SOUTHERN PINES DR PIERCE, FL 34982 ]ONTRACTOR: K & S INDUSTRIES, INC. 1379 SW BILTMORE ST. PORT ST LUCIE, FLcU9I' NOTES S-1 D e 1x2 zxz/D,I N a :1 v N N 1x2 e / C' \ 1 c_n 1 I S-3 0 m 3" ELITE COMPOSITE ROOF m o ^� I I m O Z z w w N X N N CIA S S-3 2x3/tx2 EDGE BM 9.1/1'9 Pr1Gr ARA x m x ir 0. x N N Cy * a 2x2(typ) 2x2(typ) 0 1 x2 I. (ryPJ S-3 S-3 1x2 v`N * %_ F A ®L O° ....° q ®0 ) . °°°LIC,(.' m N70 F o n 6 ® 0 ' 6j c 0. � TATF ®ohs `0RIopF PA®L Y�ENG fyII 1�<J0q SVL'�NN' ` EffR SEAL ENGINEER OF RECORD: David W. Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson RE FLORIDA LICENSE: 38654 Mark R. Dunn P.E. FLORIDA LICENSE 73968 Joel Falardeau P.E. FLORIDA LICENSE 70667 Erik Stuart P.E. FLORIDA LICENSE 77605 FBC Plans & Engineering Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph#(813)788-5314 Fax# 1-(866)824-7894 E-mail-erb@fbcplans.com Website-www.fb cplans.com C.OA-#29054 DATE: 4/16/2019 DRAWN BY: TLX :VISION: DATI-- ) 1 )2 )3 )4 .OJECT ADDRESS: ISENBIGLER 6 SOUTHERN PINES DR PIERCE, FL 34982 ]ONTRACTOR: K & S INDUSTRIES, INC. 1379 SW BILTMORE ST�y PORT ST LUCIE_FI604 OOR PLAN S2 ORINPARftlFH077 (4) # 10 SMS W/ 3/4" WASHERS PER 12" PANEL #SOX 1" LONGER THAN PANEL DEPTH SMS W/ 1-1/4" NEOPRENE COMPOSITE WASHER 0)8" O.C. PER PANEL(FOR-\ PANEL PAN ROOF SEE DETAIL C2) 2X_PB OR SMB EDGE BEAM (EDGE BEAM SHALL BE PLACED ATOP EACH UPRIGHT. MATCH POST SIZE W/ EDGE BEAM SIZE SEE SHEET FOR SIZE) C2 # SOX 3" INTO (SEE SHEET S-2 �\ ------- V— ( �ROOFPANELTOEDGEBEAMCONNECI'IONDETAIL S_3 SCALE:NTS 2" x _ END BEAM (SEE SHEET 3-2 FOR SIZE) 2" x_" END BEAM ATTACHED TO 1"x2"OPEN BACK W/ (4) # 10 x 2" THRU SCREW BOSS EXISTING MASONRY WALLGROUTED SOLID 0 CONNECTION 1/4"OX2-3/4" EMBEDMENT MASONRYSCREW3"FROM END &. 0 24" O.C. '=" OPEN BACK NOTE: WHEN ATTACHING TO WOOD STRUCTURE$ WOOD LAG SCREW ANCHOR DESIGNS SHALL BE OF IDENTICAL SIZE AND EMBEDMENT AS THAT OF MASONRY ANCHOR SCREWS, SZ] END BEAM TO HOST STRUCTURE DETAIL S-J SCALE: NTS (4) # 10 X 3/4" SMS FASTENING SECONDARY ANGLE TO COLUMN (TYP' EACH SIDE) (B)- CONCRETE SCREW / ANCHOR INTO SECONDARY I ANGLE(TYP EACH SIDE) (SEE TABLE) 00 ANCHORSPA (MIN) (T)(P)(SEE Ti Column Size 1/4"& 3/8" 0 Concrete Screw Anchor B Min. Spa 4 0 x4-1 1 3 2x6-3 8"1 4 2x-3 8'1 S 2x8-3 8" 2 3 2x9-3 8' 2 4" 2x10-3 8' 2 .5" HINGE 2" x 2" HINGE LOCATION 1 INWIIPIN.MYLi; SECONDARYANGLE MIN 0.125" THICK (NOT REQ.0 IRED FOR 2X3 PRIMARY 2" X 2" X 0.125" ANGLE (2) #SOX 3/4"SMS FASTENING COLUMN TO PRIMARY ANGLE (Tl'P EACH SIDE) 1" X2"BASE MEMBER TYP EACH SIDE) SEE TABLE) ANCHOR SCREW (IM i III��d 114\\ TABLE)ANCHORIN7YI PRIMARY ANGLE AND @ 1/4" 0 CONCRETE 3" (MIN) SCREWANCHOR0 24" O.C. BETWEEN COLUMNS (TYP EACH SIDE) NOTES: 1. NUMBER OF ANCHORS"B" IS EACH SIDE INTO THE SECONDARY ANGLE AND DOES NOT INCLUDE THE ANCHOR INTO THE IX2. 2, MINIMUM EMBEDMENT OF ANCHORS INTO CONCRETE FOOTING SHALL BE 2-3/4" AT AT ALL UPRIGHT LOCATIONS. ALL SCREW LENGTHS AT UPRIGHT CONNECTIONS SHALL BE OF SUFFICIENT LENGTH FOR REQUIRED EMBEDMENT INTO CONCRETE FOOTING WHEN A PAVER DECK IS PRESENT. 3, CONCRETE SCREW ANCHOR DESIGNS ARE BASED ON THOSE LISTED ON S-1, D.FASTENERS, OTHER BRAND&.TYPE SHALL BE APPROVED BYENGINEER 4.2X3W/IX2 CORNER POST SHALL REQUIRE SAME BASE CONNECTIONS AS 2X4 SHOWN IN TABLE. DOOR " x 2" EXTRUSION NOTES: 1. HINGES SHALL BE ATTACHED TO STRUCTURE W/ (3) #10 a5/8" SMS MINIMUM. 2. DOORSHALL BE ATTACHED TO ENCLOSURE w/(2) HINGES MINIMUM. 3, HINGES SHALL BE ATTACHED TO DOORWITH(3)#10 x5/8"SMS. FASTEN 1" x 2" x 0.044" TO UPRIGHT W/#12 x 1" SMS Q 12" O.C. AND WITHIN 3" FROM END OFTHE UPRIGHT. F TYPICAL SCREEN DOOR CONNECTION DETAIL S_ 3 SCALE MS F A t LIC I$ : NO F ®v�• �Os =ym ®� �•T qTF OF • � I I o® tp .•.�R/DA � e� OPTION #1 I •• / O °p•••••OO �. �q 0� `s I L ENG� (4)#10x IX"SMS INTO I OPTIC N#2 �� I8H11 SCREWBOSSES PR S DNA E GI HER SEAL ORD: _ David W. Smith P.E. 2"X2" OR 2'X3" I 0.062" ALUMINUM INTERNAL OR FLORIDA LICENSE: 53608 MEMBER EXTERNALRECEIVINGCHANNEL Thomas L. Hanson P.E I W/(4) #1OX3/4" INTO INTO I I BHAM ORUPRIGHT, (2)#14X3/4" FLORIDA LICENSE: 38654 EA LEG INTO GIRT OR PURLIN - Mark R. Dunn P.E. #14x3/AN/ (2) I SMS EALEG) FLORIDA LICENSE 73968 Joel Falardeau P.E. UPRIGHT OR BEAM -SNAP R SELF MATING ORFLORIDA LICENSE: 70667 HOLLOW H Erik Stuart P.E. PURLIN OR GIRT TO BEAM OR POST DETAIL S 3 SCALE: NTS FLORIDA LICENSE 77605 HOSTSTRUCTURE BREAK FORM HEADER OR IRECEIVING CHANNEL # SO SMS AT EACH RISER RPAN OR#IOSMS11 8" O.C. FOR COMPOSITE PANEL SOLID ROOF 1-1/4'J \#1OSMS08"O.C. ' (MIN) FOR COMPOSITE PANEL (2) #10 SCREWS PER 12" WIDTH CONNECTING PANTO HEADERCBOTTOM OR BACK OF PAN) /2)#0X2" SCREWS PER 12" WIDTH CONNECTING HEADER OR CHANNEL TO FASCIA S1 ROOF PANEL TO FASCIA CONNECTION DETAILS S_3 SCALE: NTS FBC Plans & Engineering Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 PhN(813)788-5314 Fax# 1-(866)824-7894 E-mail-erb@fbcplans.com Website-www.fb cplans. com C.O.A: #29054 DATE: 4/16/2019 DRAWN BY: TLK REVISION: DATE: RO 1 RO 2 R03 RO 4 Job# 19_0408_38 PROJECT ADDRESS: LINSENBIGLER 3495 SOUTHERN PINES DR -T PIERCE, FL 34982 K & S INDUSTRIES, INC. 1379 SW BILTMORE ST. PORT ST LUCIE, FL 3498p C® AILS S-3 BE REPRODUCED IN