HomeMy WebLinkAboutCHVAC LOADSFILE COP`
Harbor Insurance SCANNED
HVAC Load Analysis BY
for St. Lucie County
Harbor Insurance
Kitterman Plaza Units 6, 7 & 8
Port St. Lucie, FL
v CQLYTR4ERGI
H11AC LQAasD$
Prepared By:
Eric J. Svoboda, PE
Fort Pierce Engineering, Inc.
315 South 7th Street
Fort Pierce, FL 34950
772-672-4636
Sunday, December 19, 2010
Chvac- FullCommercial HVAC Loads Calculation Program
:�'
-
Elite Software Development, Inc'. I
"
A
Harbor
Insurance j
'
Page 2
Building Summary Loads
Building peaks in August at gam.
Bldg Load Area
Sett
%Tot
Lat
Sen
Net
%Net
Descriptions Quan.' _
Loss
'Loss
Gain
Gain
.. Gain
Gain
Roof 4,578
7,554
13.67
0
3,848
3,848
2.74
Wall 2,709
8,493
15.37
0
3,653
3,653
2.60
Glass 315
8,628
15.62
0
30,881
30,881
21.96
Floor Slab - 189
3,867
7.00
0
0
0
0.00
Skin Loads
28,541
51.66
0
38,382
38,382
27.29
Lighting 9,156
0
0.00
0
31,242
31,242
22.21
Equipment 4,578
0
0.00
0
15,621
15,621
11.11
People 39
0
0.00
7,708
9,635
17,343
12.33
Partition 0
0
0.00
0
0
0
0.00
Cool. Pret. 0
0
0,00
0
0
0
10.00
Heat. Pret. 0
0
0.00
0
0
0
0.00
Cool. Vent. 750
0
0.00
29,602
7,418
37,021
26.32
Heat. Vent. 750
26,706
48.34
0
0
0
0.00
Cool.lnfil. 0
0
0.00
0
0
0
0.00
Heat.Infil. 0
0
0.00
0
0
0
0.00
Draw-Thru Fan 0
0
0.00
0
1,029
1,029
0.73
Blow-Thru Fan 0
0
0.00
0
0
0
0.00
Reserve Cap. 0
0
0.00
0
0
0
0.00
Reheat Cap. 0
0
0.00
0
0
0
0.00
Supply Duct 0
0
0.00
0
0
0
0.00
Return Duct 0
0
0.00
0
0
0
0.00
Misc. Supply 0
0
0.00
0
0
0
0.00
Misc. Return 0
0
0.00
0
0
0
0.00
Building Totals
55,247
100.00
37,310
103,327
140,637
100.00
BuildingSen
_
/ooTof
Lat
'Sen
Net`,
%oNet i
Summary• Loss
Loss
Gain _
Gain
1Gain
Gain {
Ventilation 26,706
48.34
29,602
7,418
37,021
26.32
Infiltration 0
0.00
0
0
0
0.00
Pretreated Air 0
0.00
0
0
0
0.00
Zone Loads 28,541
51.66
7,708
94,880
102,588
72.94
Plenum Loads 0
0.00
0
0
0
0.00
Fan & Duct Loads 0
0.00
0
1,029
1,029
0.73
Building Totals 55.247
100.00
37,310
103,327
140,637
100.00
Check Fi ures
Total Building Supply Air (based on a 20°
TD):
4,297
CFM
Total Building Vent. Air (17.45% of Supply):
750
CFM
Total Conditioned Air Space:
4,578
Sq.ft
Supply Air Per Unit Area:
0.9387
CFM/Sq.ft
Area Per Cooling Capacity:
390.6
Sq.ft/Ton
Cooling Capacity Per Area:
0.0026
Tons/Sq.ft
Heating Capacity Per Area:
12.07
Btuh/Sq.ft
Total Heating Required With Outside Air:
55,247
Btuh
Total Cooling Required With Outside Air:
11.72
Tons
r
C:\Documents and Settings\Eric S\Desktop\Harbor Insurance\HVAC\Harbor Insurance.CHV Sunday, December 19, 2010, 06:31 PM
Chvac- FullCommercialHVAC Loads Calculation Program.
-
-
-
Elite Software Development, Inca
r
`
A
ce
Harbor ln Pane
Pae3�
Air Handler #1 - RTU 1 - Summary
Loads
Zn
Description
Area
Htg.Loss
Sen.Gain
Lat.Gain
Htg.O.A.
Clg.O.A.
No
Zone Peak Time
People
'Htg.CFM
CIg.CFM
S.Exh
Req.CFM
Req.CFM
-
volume,
CFM7S ft
CFM/S ft
W.Exh
Act.CFM
Act.CFM
1
Conference
297
4,944
16,718
2,000
Direct
Direct
8am August
10
229
692
0
56
56
4,158
0.77
2.33
0
145
131
2
File Area
666
1,523
9,533
888
Direct
Direct
3pm August
4
71
395
0
126
126
9,324
0.11
0.59
0
45
75
3
Office 7
72
119
1,017
96
Direct
Direct
3pm August
0
6
42
0
14
14
1,008
0.08
0.58
0
3
8
4
Office 8
72
119
1,017
96
Direct
Direct
3pm August
0
6
42
0
14
14
1,008
0.08
0.58
0
3
8
5
Break Room
154
1,243
2,545
205
Direct
Direct
7pm August
1
58
105
0
29
29
2,156
0.37
0.68
0
36
20
6
Toilet
56
587
1,003
75
Direct
Direct
9pm August
0
27
42
0
11
11
784
0.49
0.74
0
17
8
Zone Peak Totals:
1,317
8,533
31,832
3,360
Total Zones: 6
17
395
1,318
0
250
250
Unique Zones: 6
18,438
0.30
1.00
0
250
250
C:\Documents and Settings\Eric S\Desktop\Harbor Insurance\HVAC\Harbor Insurance.CHV Sunday, December 19, 2010, 06:31 PM
Chvad• Full Commercial Loads Calculation Program
-
-
Elite Software Develbpment,,lnc. I
•
APae4!
Harbor Insurance i
'
Air Handler #1 - RTU 1 - Total Load Summar
Air Handler Description: RTU 1 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of
0.12 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.90
--- This system occurs 1 time(s) in the building. ---
Air System Peak Time: gam in August.
Outdoor Conditions: 84° DB, 76° WB, 119.72 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 8,533 Btuh
Infiltration sensible loss: 0 Btuh
0
CFM
Outside Air sensible loss: 8,902 Btuh
250
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
17,435 Btuh
Heating Supply Air: 8,533 / (.999 X 1.08 X 20) =
395
CFM
Winter Vent Outside Air (63.2% of supply) =
250
CFM
Zone space sensible gain: 30,106 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 316 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
30,421 Btuh
Cooling Supply Air: 30,421 / (.999 X 1.1 X 21) =
1,318
CFM
Summer Vent Outside Air (19.0% of supply) =
250
CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 2,473 Btuh
250
CFM
Blow-thru fan sensible gain: 0 Btuh .
Total sensible gain on return side of coil:
2,473 Btuh
Total sensible gain on air handling system:
32.894 Btuh
Zone space latent gain: 3,360 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 9,867 Btuh
Total latent gain on air handling system:
13,227 Btuh
Total system sensible and latent gain:
46,121 Btuh
Check Fi ures
Total Air Handler Supply Air (based on a 21 ° TD):
1,318
CFM
Total Air Handler Vent. Air (18.97% of Supply):
250
CFM
Total Conditioned Air Space:
1,317
Sq.ft
Supply Air Per Unit Area:
1.0008
CFM/Sq.ft
Area Per Cooling Capacity:
342.7
Sq.ft/Ton
Cooling Capacity Per Area:
0.0029
Tons/Sq.ft
Heating Capacity Per Area:
13.24
Btuh/Sq.ft
Total Heating Required With Outside Air:
17,435
Btuh
Total Cooling Required With Outside Air:
3.84
Tons
C:\Documents and Settings\Eric S\Desktop\Harbor Insurance\HVAC\Harbor Insurance.CHV Sunday, December 19, 2010, 06:31 PM
Chvac- FullCommercial HVAC Loads Calculation Program-
---,
- - -'
Elite Software Development, Inc. I
�,
- •
'Harbor'Insurance
Air Handler #2 - RTU 2 - Summaty
Loads
Zn
, Description ?
.Arbal Htg Loss.
Sen.Gain .
Lat.Gain
Htg.o,A.
CIg.O:A
No
Zone Peak•Tinne•
People
„•Htg CFM,,,
Clg.CFM
S.Exh
Req.CFM
Req.GFM I
,
Volume =" CFM/S 'k y.-
CFM/S ft
W.Exh
Act.CFM
' _ 'Act.CFM i
7
Spare Office
144
1,594
4,124
192
Direct
Direct
9am August
1
74
178
0
22
22
2,016
0.51
1.24
0
41
30
8
Reception
144
2,104
6,221
192
Direct
Direct
Sam August
1
97
269
0
22
22
2,016
0.68
1.87
0
54
45
9
Office 1
110
1,977
5,780
147
Direct
Direct
8am August
1
92
250
0
17
17
1,540
0.83
2.27
0
50
42
10
Work / File Area
980
1,617
13,836
1,307
Direct
Direct
3pm August
' 7
75
598
0
148
148
13,720
0.08
0.61
0
41
100
11
Server
121
976
2,000
161
Direct
Direct
7pm August
1
45
86
0
18
18
1,694
0.37
0.71
0
25
14
12
Closet / Hall
108
1,026
1,871
144
Direct
Direct
9pm August
1
48
81
0
16
16
1,512
0.44
0.75
0
26
13
13
Women
48
503
860
64
Direct
Direct
9pm August
0
23
37
0
7
7
672
0.49
0.77
0
13
6
Zone Peak Totals:
1,655
9,797
34,692
2,207
Total Zones: 7
11
454
1,501
0
250
250
Unique Zones: 7
23,170
0.27
0.91
0
250
250
C:\Documents and Settings\Eric S\Desktop\Harbor Insurance\HVAC\Harbor Insurance.CHV Sunday, December 19, 2010, 06:31 PM
Chvac - Full IIommercial HVAC Loads Calculation Program:.
-
-
Elite SoftwareDevelopment, Inc.:
Harbor Insurance,
Page
Air Handler #2 - RTU 2 - Total Load Summary
Air Handler Description: RTU 2 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of
0.14 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.94
--- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 9am in August.
Outdoor Conditions: 84° DB, 76° WB, 119.72 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 9,797 Btuh
Infiltration sensible loss: 0 Btuh
0
CFM
Outside Air sensible loss: 8,902 Btuh
250
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
18,699 Btuh
Heating Supply Air: 9,797 / (.999 X 1.08 X 20) =
454
CFM
Winter Vent Outside Air (55.1 % of supply) =
250
CFM
Zone space sensible gain: 32,624 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 359 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
32,983 Btuh
Cooling Supply Air: 32,983 / (.999 X 1.1 X 20) =
1,501
CFM
Summer Vent Outside Air (16.7% of supply) =
250
CFM
Return duct sensible gain: 0 Stuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 2,473 Btuh
250
CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
2,473 Btuh
Total sensible gain on air handling system:
35,456 Btuh
Zone space latent gain: 2,207 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 9,867 Btuh
Total latent gain on air handling system:
_
12,074 Btuh
Total system sensible and latent gain:
47,530 Btuh
Eheck Fi Gres ,__ .. • , e ._
... „... ;,
Total Air Handler Supply Air (based on a 200 TD):
1,501
CFM
Total Air Handler Vent. Air (16.66% of Supply):
250
CFM
Total Conditioned Air Space:
1,655
Sq.ft
Supply Air Per Unit Area:
0.9067
CFM/Sq.ft
Area Per Cooling Capacity:
417.8
Sq.ft/Ton
Cooling Capacity Per Area:
0.0024
Tons/Sq.ft
Heating Capacity Per Area:
11.30
Btuh/Sq.ft
Total Heating Required With Outside Air:
18,699
Btuh
Total Cooling Required With Outside Air:
3.96
Tons
C:\Documents and Settings\Eric S\Desktop\Harbor Insurance\HVAC\Harbor lnsurance.CHV Sunday, December 19, 2010, 06:31 PM
Chvac - Full Commercial HVAC'Loads Calculation Program
--- -
Elite Software Development, Inc.
Harbor Insurance
'
`-'-
Pace,7
Air Handler #3 - RTU 3 - Summary
Loads
Zn
Description
Area
Htg Loss
Sen.Gain
Lat.Gain
Htg.O.A
Clg.O.A.
No .
Zone Peak Time
Htg.CFM
Cl9.CFM
S.Exh
Req.CFM
Req.CFM
'Peopler
Volume
CFM/S ft_
CFM/Soft
W.Exh
ACt.CFM
Act.CFM
14
Men
48
503
860
64
Direct
Direct
9pm August
0
23
37
0
7
7
-
672
0.49
0.77
0
12
6
15
Office 2
110
1,977
5,780
147
Direct
Direct
Sam August
1
92
249
0
17
17
1,540
0.83
2.27
0
48
42
16
Office 3
110
107
5,780
147
Direct
Direct
Sam August
1
92
249
0
17
17
1,540
0.83
2.27
0
48
42
17
Office 4
110
1,468
3,680
147
Direct
Direct
Sam August
1
68
159
0
17
17
1.540
0.62
1.44
0
36
27
18
Hall
114
188
1,610
152
Direct
Direct
3pm August
1
9
69
0
18
18
1,596
0.08
0.61
0
5
12
19
Work Area
150
248
2,118
200
Direct
Direct
3pm August
1
11
91
0
23
23
2,100
0.08
0.61
0
6
15
20
File Area
120
198
1,694
160
Direct
Direct
3pm August
1
9
73
0
19
19
1,680
0.08
0.61
0
5
12
21
Hall
114
188
1,610
152
Direct
Direct
3pm August
1
9
69
0
18
18
1,596.
0.08
0.61
0
5
12
22
Work / File Area
378
624
5,337
504
Direct
Direct
3pm August
3
29
230
0
59
59
5,292
0.08
0.61
0
15
39
23
Rear Hall
110
888
1,818
147
Direct
Direct
7pm August
1
41
78
0
17
17
1,540
0.37
0.71
0
22
13
24
Office 5
121
976
2,000
161
Direct
Direct
7pm August
1
45
86
0
19
19
1,694
0.37
0.71
0
24
15
25
Office 6
121
976
2,000
161
Direct
Direct
7pm August
1
45
86
0
19
19
1,694
0.37
0.71
0
24
15
Zone Peak Totals:
1,606
10,211
34,285
2,141
Total Zones: 12
11
473
1,479
0
250
250
Unique Zones: 12
22,484
0.29
0.92
0
250
250
C:\Documenls and Settings\Eric S\Desktop\Harbor Insurance\HVAC\Harbor Insurance.CHV Sunday, December 19, 2010, 06:31 PM
Chvac -Full Commercial HVAC,Loads Calculation Program
Elite Software Development, Inc.
-
Harbor Insurance I
` '
-
Page 8
Air Handler #3 - RTU 3 - Total Load Summary
Air Handler Description: RTU 3 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of
0.14 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.94
--- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 9am in August.
Outdoor Conditions: 84° DB, 76° WB, 119.72 grains
Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air.
Zone Space sensible loss: 10,211 Btuh
Infiltration sensible loss: 0 Btuh
0
CFM
Outside Air sensible loss: 8,902 Btuh
250
CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss:
19,113 Btuh
Heating Supply Air: 10,2111 (.999 X 1.08 X 20) =
473
CFM
Winter Vent Outside Air (52.8% of supply) =
250
CFM
Zone space sensible gain: 32,150 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 354 Btuh
-
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil:
32,504 Btuh
Cooling Supply Air: 32,504 / (.999 X 1.1 X 20) =
1,479
CFM
Summer Vent Outside Air (16.9% of supply) =
250
CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 2,473 Btuh
250
CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil:
2,473 Btuh
Total sensible gain on air handling system:
34,977 Btuh
Zone space latent gain: 2,141 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 9,867 Btuh
Total latent gain on air handling system:
12,009 Btuh
Total system sensible and latent gain:
46,986 Btuh
CheckFi ure5
Total Air Handler Supply Air (based on a 200 TD):
1,479
CFM
Total Air Handler Vent. Air (16.91 % of Supply):
250
CFM
Total Conditioned Air Space:
1,606
Sq.ft
Supply Air Per Unit Area:
0.9208
CFM/Sq.ft
Area Per Cooling Capacity:
410.2
Sq.ft/Ton
Cooling Capacity Per Area:
0.0024
Tons/Sq.ft
Heating Capacity Per Area:
11.90
Btuh/Sq.ft
Total Heating Required With Outside Air:
19,113
Btuh
Total Cooling Required With Outside Air:
3.92
Tons
C:\Documents and Settings\Eric S\Desktop\Harbor Insurance\HVAC\Harbor lnsurance.CHV Sunday, December 19, 2010, 06:31 PM
Construction
Florida Department' of Commu'nfty Affairs
€nergyG'auge' Summits Fla/Com-2008, Effective;. March 1, 2000 -- Form 40OA-2008
Method -A -Whole Build! nd,'Perfdrmance, Method,,for Commercial Buildings
PROJECT SUMMARY OLANIV1--D
BY
St. Luria CountV
Short Desc: Harbor Insurance Description: Harbor Insurance
Owner: Harbor Insurance
Address]: Kitterman Plaza Units 6, 7 & 8 City: Port St. Lucie
Address2: State: FL
Zip: 0
Type: Office Class: New Finished building
Jurisdiction: PORT ST LUCIE, ST LUCIE COUNTY, FL (661200)
Conditioned Area: 4560 SF Conditioned & UnConditioned Area:
No ofStories: 1 Area entered from Plans
Permit No: 0 Max Tonnage
If different, write in:
4560 SF
0 SF
4
�uuunq
%%
N �:
8 882
o a
STA E OF :•Q.
EnergyGauge Summit@ Fla/Com-2008. Effective: March 1, 2009
12/19/2010 Page I of 7
Compliance Summa
Component Design Criteria Result
Gross Energy Cost (in $) 3,192.0 3,397.0 PASSED
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
PASSES
None Entered
PASSES
None Entered
None Entered
None Entered
Yes/No/NA
IMPORTANT MESSAGE
Info 5009 -- -- -- An input report of this design building must be submitted along with this
Compliance Report
EnergyGauge Summit@ Fla1Com-2008. Effective: March 1, 2009
12/19/2010 Page 2 of 7
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation -are in compliance with the
Florida Energy Code
Prepared By: Eric J. voboda, PE
Building Official:
Date: 17 o -oo
Date:
I certify that this building is in compliance with the FLorida Energy Efficiency Code
Owner Agent:
Date:
If Required by Florida law, I hereby certify (') that the system design is in compliance with the FLorida
Energy Efficiency Code
Architect:
Reg No:
Electrical Designer:
Reg No:
Lighting Designer:
Reg No:
Mechanical Designer:
Reg No:
Plumbing Designer: -
Reg No:
(') Signature is required where Florida Law requires design to be performed by registered design
professionals.
EnergyGauge Summil0 Fla/Com-2008. Effective: March 1, 2009
12/19/2010 Page 3 of 7
Project: Harbor Insurance
Title: Harbor Insurance
Type: Office
(WEA File: FL ST LUCII
Building End Uses
1) Proposed
2) Baseline
Total
205.40
255.40
$3,192
$3,996
ELECTRICITY(MBtulkWh/$)
205.40
255.40
60226
74830
$3,192
$3,996
AREA LIGHTS
49.10
52.40
14394
15362
S763
S820
MISC EQUIPMT
68.40
68.40
20043
20043
$1,062
$1,070
PUMPS & MISC
0.00
0.10
13
21
$1
$1
SPACE COOL
67.40
66.00
19762
19326
$1,047
$1,032
SPACE HEAT
0.50
3.70
151
1080
$8
$58
VENT FANS
20.00
64.80
5863
18998
$311
$1,014
assing requires Proposed Building cost to be at most 85%
PASSES
f Baseline cost. This Proposed Building is at 79.9%
EnergyGauge Summit@ Fla/Com-2008. Effective: March 1. 2009
12/19/2010 Page 4 of 7
External Lighting Compliance
Description Category Tradable? Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
None
Project: Harbor Insurance
Title: Harbor Insurance
Type: Office
(WEA File: FL_ST
LUCIE CO_INTL.tm3)
.Lighting Controls Compliance
Acronym
Ashrae Description
Area Design
Min Compli-
ID
(sq.ft) CP
CP ance
PrOZolSpl
17 Office -Enclosed
4,560 20
2 PASSES
PASSES
Project: Harbor Insurance
Title: Harbor Insurance
Type: Office
(WEA File: FL_ST_LUCIE_CO_INTL.tm3)
System
Report Compliance
1Pr0Sy1 System 1
Constant Volume Packaged No. of Units
System
3
Component
Category Capacity Design Eff Design
IPLV Comp-
Eff Criteria IPLV
Criteria liance
Cooling System
Air Conditioners Air Cooled
13.00 12.23 8.00
PASSES
< 65000 Btu/h Cooling
Capacity
Heating System
Electric Furnace
1.00 1.00
PASSES
Air Handling
Air Handler (Supply) -
0.30 0.90
PASSES
System -Supply
Constant Volume
Air Distribution
ADS System
6.00 3.50
PASSES
System
PASSES
EnergyGauge Summit@ Fla/Com-2008. Effective: March 1, 2009
12/19/2010 Page 5 of 7
Plant Compliance
Description Installed Size Design Min Design Min Category
No Eff Eff IPLV IPLV
Comp
Hance
None
Water Heater Compliance
Description Type Category Design Min Design
Eff Eff Loss
Max Comp
Loss Hance
None
Piping System Compliance
Category Pipe Dia Is Operating Ins Cond Ins
jinchesj Runout? Temp [Btu-in/hr Thick jinj
jFj SF.Fj
Req Ins Compliance
Thick linj
None
EnergyGauge Summit® Fla/Com-2008. Effective: March 1, 2009
12/19/2010 Page 6 of 7
A: Harbor Insurance
Harborinsurance
Office
File: FL_ST_LUCIE_CO_INTL.tm3)
Other Required Compliance
Category
Section Requirement (write N/A in box if not applicable)
Check
Report
13-101 Input Report Print -Out from EnergyGauge FlaCom attached
Operations Manual
13-102.1, Operations manual provided to owner
13-410,13-413
Windows & Doors
13-406.AB. 1. 1 Glazed swinging entrance & revolving doors: max. 1.0 cfm/ft'; all
other products: 0.4 cfm/ft'
Joints/Cracks
13-406.AB.1.2 To be caulked, gasketed, weather-stripped or otherwise sealed
Dropped Ceiling
13-406.AB.3 Vented: seal & insulated ceiling. Unvented seal & insulate roof &
❑
Cavity
side walls
System
13-407 HVAC Load sizing has been performed
❑
Reheat
13-407.13 Electric resistance reheat prohibited
El
HVAC Efficiency
13-407, 13-408 Minimum efficiences: Cooling Tables 13-407.AB.3.2.1A-D;
❑
Heating Tables 13-407.AB.3.2.1B, 13-407.AB.3.2. I D,
13-408.AB.3.2.1E, 13-408.AB.3.2F
HVAC Controls
13-407.AB.2 Zone controls prevent reheat (exceptions); simultaneous heating
and cooling in each zone; combined HAC deadband of at least 57
(exceptions)
Ventilation Controls
13-409.AB.3 Motorized dampers reqd, except gravity dampers OK in: 1)
❑
exhaust systems and 2) systems with design outside air intake or
exhaust capacity <300 cfm
ADS
13-410 Duct sizing and Design have been performed
❑
HVAC Ducts
13-410.AB Air ducts, fittings, mechanical equipment & plenum chambers
❑
shall be mechanically attached, sealed, insulated & installed per
Sec. 13-410 Air Distribution Systems
Balancing
13-410.ABA HVAC distribution system(s) tested & balanced. Report in
construction documents
Piping Insulation
13-41 LAB In accordance with Table 13-41 LAB.2
Water Heaters
13-412.AB Performance requirements in accordance with Table 13-412.AB.3.
Heat trap required
Swimming Pools
13-412.AB.2.6 Cover on heated swimming pools: Time switch (exceptions);
❑
Readily accessible on/off switch
Hot Water Pipe
13-41 LAB.3 Table 13-41 LAB.2 for circulating systems, first 8 feet of outlet
Insulation
pipe from storage tank and between inlet pipe and heat trap
Water Fixtures
13-412.AB.2.5 Shower hot water flow restricted to 2.5 gpm at 80 psi. Public
lavatory fixture how water flow 0.5 gpm max; if self -closing valve
0.25 gallon recirculating, 0.5 gallon non recirculating
Motors
13-414 Motor efficiency criteria have been met
Lighting Controls
13-415.AB Automatic control required for interior lighting in buildings
>5,000 s.f; Space control; Exterior photo sensor; Tandom wiring
with 1 or 3 linear fluuorescent lamps>30W
EnergyGauge Summit0 Fla/Com-2008. Effective: March 1, 2009
12/19/2010 Page 7 of 7
EnergyGauge Summit® v3.22
INPUT DATA REPORT
Proiect Information
Project Name: Harbor Insurance
Project Title: Harbor Insurance
Address: Kitterman Plaza Units 6, 7 & 8
State: FL
Zip: 0
Owner: Harbor Insurance
Orientation: North
Building Type: Office
Building Classification: New Finished building
No.of Stories: I
GrossArea: 4560 SF
Zones
No Acronym Description
Type
Area Multiplier
[sq
Total Area
[sf]
1 PrOZoI Zone I
CONDITIONED
4566.0 I
4560.0 ❑
Spaces
No Acronym Description
Type Depth Width
A [ftl
Height Multi Total Area
[ftl plier [sfI
Total Volume
tcfl
12/19/2010
EnergyGauge Summit@ v3.22
In Zone: PrOZol
1 PrOZoISPI
ZoOSPI Office - Enclosed
48.00
95.00
14.00
1 4560.0
63840.0 ❑
Lighting
No
Type Category
No. of
Watts per
Power
Control Type
No.of
Luminaires
Luminaire
[W]l
Ctrl pts
In Zone: Pr0Zo1'
In Space: PrOZo1Sp1
1
Compact Fluorescent General Lighting
1
4700
4700
Manual On/Off
20 ❑
Walls
No Description
Type Width H (Effec) Multi
Area DirectionConductance
Heat
Dens. R-Value
[ftl
[ftl plier
[sf]
[Btu/hr.
sf F]
Capacity
[lb/cf] [h.sf.F/Btul
[Btu/sf.Fl
In Zone: PrOZol
l PrOZOI Wa1
5/8" stucco 95.00
14.00 l
1330.0
East
0.2067
5.731
34.65 4.8 ❑
/8"CMU/3/4"ISO
BTWN24"oc/.5"
Gyp
2 PrOZol Wag
5/8" stucco 95.00
14.00 1
1330.0
West
0.2067
5.731
34.65 4.8 ❑
/8"CMU/3/4"ISO
BTWN24"oc/.5"
Gyp
Windows
No
Description Type Shaded
U SHGC Vis.Tra
W
H (Effec)
Multi
Total Area
[Btu/br sf Fl
[ft]
[ft]
plier
[s fl
In Zone: PrOZol
In Wall: East
I
Pr0Zo 1 Wa l W i 1 User Defined No
1.2500 0.82 0.76
3.00
7.00
16
336.0 EEJI
12/19/2010 EnergyGauge Summit® v3.22
Doors
No Description Type .Shaded? Width H (Effec) Multi Area Cond. Dens. Heat Cap. R-Value
IN [ft] plier [sf] [Btu/hr. sf. F] [Ib/ct] [Btu/sE F] [h.sf.FBtul
In Zone: PrOZo1
In Wall: West
I PrOZol Wa2Drl Solid core flush No 3.00 7.00 3 21.0 0.3504 0.00 0.00 2.85 ❑
(2.25)
Roofs
No Description
Type
Width H (Effec) Multi Area " Tilt Cond. Heat Cap
Dens. R-Value
IN N plier [sl]
[deg] [Btu/hr. SE F] [Btu/sE F]
[Ib/ct] [h.sEF/Btu]
In Zone: PrOZoI
I PCOZOIRfl
Mtl Bldg Roof/R-19
95.00 48.00 1 4560.0
0.00 0.0492 1.34
9.49 20.3
❑
Batt
Skylights
No Description Type
U SHGC Vis.Trans
W H (Effec) Multiplier
Area Total Area
[Btu/hr sf F]
[ft] [ft]
[Sf] [Sf]
In Zone:
In Roof:
Floors
No Description
Type.
Width H (Effec) Multi Area
Cond. Heat Cap. Dens.
R-Value
[ft] [ft] plier [sf]
[Btu/hr. sE F] [Btu/sE F] [lb/cf]
[h.sEF/Btu]
In one: PrOZol
I PrOZOI Fl l
I ft. soil, concrete
95.00 48.00 1 4560.0 0.2681 34.00 113.33
3.73
❑
floor, carpet and
rubber pad
12/19/2010 EnergyGauge Summit® v3.22
Systems
1Pr0Sy1 System 1
Constant Volume Packaged, System
No. Of Units 3
Component Category
Capacity
Efficiency IPLV
I Cooling System
2 Heating System
3 Air (Handling System -Supply
4 Air Distribution System
48000.00
24000.00
1440.00
13.00 8.00
1.00
0.30
6.00
❑
❑
Plant
Equipment
Category . Size
Inst.No Eff.
IPLV
El
Water Heaters
W-Heater Description
CapacigCap.Unit I/P Rt.
Efficiency
Loss
El
Ext-Lighting
Description Category No. of Watts per Area/Len/No. of units Control Type Wattage
Luminaires Luminaire [sVft/No] [W]
12/19/2010 EnergyGauge Summit® v3.22
Piping
No Type Operating Insulation Nomonal pipe Insulation Is Runout?
Temperature Conductivity Diameter Thickness
(F[ [ Btu-in/h.sf.F[ [in[ [in[
uJ
Fenestration Used
Name Glass Type No. of Glass SHGC VLT
Conductance
Panes
[Btu/h.sf.F[
ASHULSgICIrAI User Defined 1 1.2500 0.8200 0.7600 ❑
IFrm
Materials Used
Mat No Acronym Description Only R-Value RValue Thickness Conductivity Density SpecificHeat
Used [h.sf.F/Btuj IN lBtu/h.ft.F[ [Ib/ct] [Btu/Ib.FJ
187
MatII87
6YP OR PLAS
No
.
BOARD,1 /2IN
178
Mat1178
CARPET W/RUBBER PAD
Yes
1.2300
❑
265
Matl265
Soil, I fl
No
2.0000
1.0000
0.5000
100.00
0.2000
❑
48
Mat148
6 in. Heavyweight concrete
No
0.5000
0.5000
1.0000
140.00
0.2000
❑
268
Mat1268
0.625"stucco
No
0.1302
0.0521
0.4000
16.00
0.2000
❑
42
Mat142
8 in. Lightweight concrete
No
2.0212
0.6670
0.3300
38.00
0.2000
❑
block
1
269
Mat1269
.75" ISO BTWN24" oc
No
2.2321
0.0625
0.0280
4.19
0.MOO
❑
23
Matl23
6 in. Insulation
No
20.0000
0.5000
0.0250
5.70
0.2000
❑
94
Mat194
BUILT-UP ROOFING,
No
0.3366
0.0313
0.0930
70.00
0.3500
❑
3/8IN
12/19/2010 1 EnergyGauge Summit® v3.22 5
Constructs Used
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.Fl
lBtu/sfF)
lib/cfl
[h.sf.FBtu)
1011
5/8" stucco /8"CMU/3/4"ISO No
No 0.21
5.73
34.65
4.8
❑
BTWN24"oc/.5"
Gyp
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
268
0.625" stucco
0.0521
0.000
❑
2
42
8 in. Lightweight concrete block.
0.6670
0.000
❑
3
269
.75" ISO BTWN24" oc
0.0625
0.000
❑
4I
187
GYP OR PLAS BOARD,1/21N
0.0417
0.000
❑
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cfl
[h.sf.FBtul
1056
Mtl Bldg Roof/R-19 Batt
No
No 0.05
1.34
9.49
20.3
❑
Layer
Material
Material
Thickness
Framing
No.
[ft)
Factor
1
94
BUILT-UP ROOFING, 3/8IN
0.0313
0.000
❑
2
23
6 in. Insulation
0.5000
0.000
❑
No
Name
Simple
Massless - Conductance Heat Capacity
Density
RValue
Construct
Construct lBtu/h.sf.Fl
[Btu/sf.Fl
[Ib/cfl
[h.sf.F/Btul
1057
1 ft. soil, concrete floor, carpet and rubber No
No 0.27
34.00
113.33
3.7
❑
pad
Layer
Material
Material
Thickness
Framing -
No.
lftl
Factor
1
265
Soil, I ft
1.0000
0.000
❑
2
48
6 in. Heavyweight concrete
0.5000
0.000
❑
3
178
CARPET W/RUBBER PAD
0.000
❑
12/19/2010 EnergyGauge Summit@ v3.22
No Name Simple Massless Conductance Heat Capacity Density RValue
Construct Construct [Btu/h.sf.F] [Btu/sf.F] [lb/cf] jh.sf.FBtu[
1058 Solid core flush (2.25) No Yes 0.35 2.9 ❑
Layer Material Material Thickness Framing
No. (f[j Factor
1 279 Solid core flush (2.25") 0.000 ❑
12/19/2010 EnergyGauge Summit@ v3.22