EVALUATION REPORT
TRI-BUILT Materials Group, LLC
PO Box 70
Rutherford, NJ 07070
(800)516-1485
EXTERIOR RESEARCH & DESIGN, LLC.
Certificate of Authorization #9503
SCANNED 353 CHRISTIAN STREET, UNIT#13
BY OXFORD, CT 06478
>pt. Lucie `roUP)QS/ (203) 262-9245
Evaluation Report A42960.10.12-R6
FL16048-R6
Date of Issuance:10/25/2012
Revision 6: 09/25/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products desceibed herein have been evaluated for compliance with the 6" Edition (2017) Florida Building Code
sections noted herein.
DESCRIPTION: TRI-BUILT Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity) ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity IERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 6.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appeanngma authorized by Robert Nieminen,
P.E on MM/2017. This does not serve as an electmnimlly signed
doamenL
CERTIFICATION OF INDEPENDENCE:
1. Trinity I ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity I ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are beingissued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
S. This is a building code evaluation. Neither TrinitylERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose. -
TRINITY ERD
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Underlayment
Compliance Statement: TRI-BUILT Roof Underlayments, as produced by TRI-BUILT Materials Group, LLC, have
demonstrated compliance with the following sections of the 6" Edition (2017) Florida Building Code through testing
in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations /
Conditions of Use set forth herein.
2. STANDARDS:
Section
Property
Standard
year
1504.3.1
Wind Resistance
FM 4474
2012
2005
1504.3.1
Wind Uplift
UL 1897
20
1504.6
Accelerated Weathering
ASTM G155
1507.2.4 / 1507.1.1, 1507.2.9.2
Physical Properties
ASTM D1970
FRSA/TRI April 2012 (04-12)
2015
2012
1507.3.3
Physical Properties
3. REFERENCES:
Entity
Examination
Reference
Date
02/19/2013
ERD (TST6049)
Physical Properties
S40540.02.13-1
11/19/2013
ERD (TST6049)
Physical Properties
S40540.11.13
03/26/2014
ERD (TST6049)
Physical Properties
S40540.03.14
S44870.04.14-2
64/02/2014
ERD (TST6049)
Physical Properties
544870.04.14-3
04/02/2014
ERD (TST6049)
Physical Properties
Physical Properties
S44870.04.14-1
04/10/2014
ERD (TST6049)
ERD (TST6049)
Physical Properties
S44870.04.144
04/10/2014
ERD (TST6049)
Physical Properties
S43530.02.14-1-R1
05/14/2014
05/29/2014
ERD (TST6049)
Physical Properties
S43530.05.14
10/31/2014
ERD (TST6049)
Physical Properties
S40540.10.14
02/13/2015
ERD (TST6049)
Physical Properties
SC7645.02.15
05/27/2015
ERD (TST6049)
Accelerated Weathering
SC8520.04.15
06/07/2017
ERD (TST6049)
Wind Resistance
Quality Control
SC14045.05.17-R1
Multiple -Listing R16814
12/10/2015
UL, L-C. (QUA9625)
Quality Control
Service Confirmation
Exp. 07/18/2020
UL, L-C. (QUA9625)
4. PRODUCT DESCRIPTION:
4.1 Tri-Built Sand-R SA Shingle Underlayment is a self -adhering, glass -mat reinforced, sand -surfaced, SBS
modified bitumen roof underlayment, with a 36-inch sheet width; meets ASTM D1970.
4.2 Tri-Built S/A HT TU Underlayment is a self -adhering, non -woven polyester fabric surfaced, SBS modified
bitumen roof underlayment; meets ASTM D1970 and FRSA/TRI April 2012.
4.3 Tri-Built Smooth HT S/A Underlayment is a self -adhering, glass -mat reinforced, film -surfaced, SBS
modified bitumen roof underlayment; meets ASTM D1970.
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity I ERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials
Directory for fire ratings of this product.
Evaluation Report A4Z960.10.12-R6
Exterior Research and Design, U.C. FL16048-R6
Certificate of Authorization #9503 EP EDITION (2017) FBC NON-HVHZ EVALUATION
TRI-BUILT Roof Underlayments;(800)516.1485 Revision 6: 0Page 2 of 2of6
Page 6
TRINITY ERD
5.4 TRI-BUILT Roof Underlayments may be used with any prepared roof cover where the product is
specifically referenced within FBC approval documents. If not listed, a request may be made to the
Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the
prepared roof covering.
5.5 Allowable Roof Covers:
TABLE 1: ROOF COVER OPTIONS
Asphalt Wood Shakes Slate
Underlayment Nail -On Tile Foam -on Tile Metal &Shingles
Shingles
Tri-Built Sand-R SA Shingle Yes No No No Yes Yes
Underlayment
Yes Yes Yes Yes
Tri-Built S/A HT TU
Yes Yes See 5.5.1
Underlayment
Tri-Built Smooth HT S/A Yes No No Yes Yes Yes
Underlayment
5.5.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combinations.
Adhesive Florida Product Approval
ICP Adhesives Polyset® AH 160 FL6332 Tri-Built S/A HT TU Underlayment
Dow TdeBond TM FL22525 Tn Bwlt S/AHTTUUncierlayment
5.6 Allowable Substrates:
5.6.1 Direct -Bond to Deck:
Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
➢ Plywood; ASTM D41 primed plywood; OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41
primed Southern Yellow Pine, ASTM D41 primed structural concrete.
While not required over plywood, OSB or Southern Yellow Pine substrates, TRI-BUILT Materials Group, LLC
recommends priming the deck if the final roof cover is not slated for installation within 24 hours. Note:
TRI-BUILT Materials Group, LLC requires tongue -and -groove board decking be covered with plywood or
OSB prior to installation of the self -adhering underlayment.
5.6.2 Bond -to -Insulation:
Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
➢ Dens Deck Prime; SECUROCK Gypsum -Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per
minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations
under foam -on tile systems (Tri-Built S/A HT TU Underlayment only), insulation attachment shall be
designed by a qualified design professional and installed based on testing of the insulation/underlayment
system in accordance with FM 4474, Appendix D or TAS 114, AppendixJ.
1 Refer to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
Evaluation Report A42960.10.12-R6
Exterior Research and Design, U.C. FL16048-R6
Certificate of Authorization #9503 6r" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 6:09/7512017
TRI-BUILT Roof Underiayments; (800) 516-1485 Page 3 of 6
TRINITY ERD
5.6.3 Bond to Mechanically Attached Base Laver:
Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
➢ ASTM D226, Type I or If felt.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per
minimum codified requirements. For installations under foam -on tile systems (Tri-Built S/A HT TU
Underlayment only), base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04-
12).
5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12)
does not address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where
the underlayment forms part of the load -path. The following wind uplift limitations apply to direct -deck
underlayment systems that are not addressed in FRSA/TRI April 2022 (04-12) and are used in foam -on tile
applications. Maximum Design Pressure is the result of testing for wind load resistance based on
allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety
per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-12), Appendix A, Table 1A or
FBC 1609 for determination of design wind pressures.
#1 Maximum Design
Pressure=-45.0 psf:
Deck:
Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Primer:
(Optional) ASTM D41 or RESI5TO EXTERIOR PRIMER
Underlayment:
Tri-Built S/A HTTU Underlayment, self -adhered.
#2 Maximum Design Pressure =-67.5 psf:
Deck:
Structural concrete to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Primer: Soprema Elastocol 600c
Underlayment: Tri-Built S/A HTTU Underlayment, self -adhered.
#3 Maximum Design Pressure = -150.0 osf
Deck: Min. 15/32-inch APA-rated BCX plywood (may be installed C-side up) to meet project
requirements to satisfaction of Authority Having Jurisdiction.
Deck Preparation: Plywood shall be thoroughly cleaned to remove dust and debris that may inhibit
adhesion. All sheathing fasteners shall be driven flush with the surface. All sharp
splinters and wood projections shall be removed/sanded.
Primer: (Optional) RESISTO EXTERIOR PRIMER
Underlayment: Tri-Built S/A HT TU Underlayment, self -adhered, shall be thoroughly roll using hand
roller and/or weighted roller to ensure there are no voids, and ensure there are no
voids/bridging at side and end -laps.
#4 Maximum Design Pressure =-60.0 psf:
Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Base Sheet: Soprema Sopra-G or Modified Sopra-G mechanically attached with nails (FBC 1517.5.1)
and tin caps (FBC 1517.5.2) spaced 6-inch D.C. at the 4-inch laps and 6-inch o.c. in three,
equally spaced rows in the center of the sheet.
Underlayment: Tri-BuiltS/A HT TU Underlayment, self -adhered.
Exterior Research and Design, LLC. Evaluation Report A42960.10.12-R6
Certificate of Authorization #9503 6'a EDITION (2017) FBC NON-HVHZ EVALUATION FL16048-116
TRI-BUILT Roof Underlayments; Iwo) 516-1485 Revision 6: 09/Z5/2017
Page 4 of 6
TRINITY ERD
5.6.4.1 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet
or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1
design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an
attachment density designed by a qualified design professional to resist the elevated pressure criteria.
Commonly used methods are ANSI/SPRI WDS, FM Loss Prevention Data Sheet 1-29 and Roofing
Application Standard RAS 117. Assemblies marked with an asterisk' carry the limitations set forth in
Section 2.2.10.1 of FM Loss Prevention Data Sheet 149 (January 2016) for Zone 2/3 enhancements.
5.7 Exposure Limitations:
Tri-Built Sand-R SA Shingle Underlayment or Tri-Built Smooth HT S/A Underlayment shall not be left
exposed for longer than 30-days after installation
Tri-Built S/A HT TU Underlayment shall not be left exposed for longer than 180-days after installation.
5.8 Tile Slippage Limitations RAS 103 per FRSA/TRI April 2012 (04-12)):
When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall
be as follows. These slope limitations can only be exceeded by using battens during loading of the roof
tiles.
TABLE 2: TILE SLIPPAGE LIMITATIONS FOR DIRECT
DECKTII! INSTALLATIONS
Underlayment
Tile Profile
Staging Method
Maximum
Slope
Flat
Max. 10-tile stack
6:12
Lugged
Max. 10-tile stack
5:12
Max. SO -tile stack (bottom 2-tile stack
shall be inverted, followed by R tiles high 6:12
on slope, as shown below)
Tri-Built S/A HT TU
J t
Underlayment
-
Lugged
Exterior Research and Design, LLC. Evaluation Report A42960.10.12-R6
Certiflcate of Authorization H9503 a EDITION (2017) FBC NON-HVHZ EVALUATION FL36048-116
TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6: 09/25/2017
Page 5 of 6
TRINITY ERD
6. INSTALLATION:
6.1 TRI-BUILT Roof Underlayments shall be installed in accordance with TRI-BUILT Materials Group, LLC
published installation requirements subject to the Limitations set forth in Section 5 herein and the
specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly
to remove any dust and debris prior to application, and prime the substrate (if applicable).
6.3 Tri-Built Sand-R SA Shingle Underlavment, Tri-Built S/A HT TU Underlavment or Tri-Built Smooth HT S/A
Underlavment:
6.3.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
6.3.2 Non -Tile applications:
While priming is optional, TRI-BUILT Materials Group, LLC recommends priming the deck if the final roof
cover is not slated for installation within 24 hours.
Apply sheet parallel to the roof edge. Roll out approximately 10 ft of membrane and peel back the first 3
ft of release film.
Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible.
Once the entire length of membrane is in place, peel -off the release film diagonally while holding the
membrane tight. Firmly roll, broom or hand -press the membrane into place to achieve a bond.
Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6-
inches and staggered not less than 2-ft from vertical seams in the course below, sealed in accordance with
TRI-BUILT Materials Group, LLC requirements.
When installing at slopes above 8:12, TRI-BUILT Materials Group, LLC recommends back -nailing in the
overlap area at the top of the sheet at 12-inch o.c.
For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet
over valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge in
each direction. For valleys, apply the sheet starting at the lowest point and work upward.
6.3.3 Tile Applications (Tri-BuiltS/A HTTU Underlavment only):
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the
instructions noted above as a guideline.
For foam -on the applications, reference is made to Section 5.6.4 herein for wind resistance limitations that
fall outside the scope of FRSA/TRI April 2012 (04-12).
Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the
underlayment. See Table 2 herein, and TRI-BUILT Materials Group, LLC published requirements for tile
staging.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
S. MANUFACTURING PLANTS:
Gulfport, MS
9. QUALITY ASSURANCE ENTITY:
UL, LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com
- END OF EVALUATION REPORT -
Exterior Research and Design, LLC. Evaluation Report A42960.30.12-R6
Certificate of Authorization #9503 6r" EDITION (2017) FBC NON-HVHZ EVALUATION FL16048-116
TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6: 09/25/2017
Page 6 of 6
CREEK Certificate of Authorization No. 29824
17520 Edinburgh Dr
Tampa, FL 33647
TECHNICAL SERVICES, LLC (813) 480-3421
EVALUATION REPORT
FLORIDA BUILDING CODE, C EDITION (2017)
Manufacturer: TAMKO BUILDING PRODUCTS
Issued September 25,2017
220 West a Street
Joplin, MO 64801
(417)624-6644
Manufacturing Plants: Joplin, MO
SCANNED
Phillipsburg, KS
BY
Frederick, MD
St. Lucie County
Tuscaloosa, AL
Quality Assurance: UL LLC (QUA9625)
SCOPE
Category: Roofing
Subcategory: Asphalt Shingles
Code Sections: 1504.1.1, 1507.2.5, 1507.2.7.1, 1523.6.5.1
Properties: Physical properties, Wind Resistance, Wind Driven Rain
REFERENCES
Entity
Report No.
Standard
Year
PRI Construction Materials Technologies (TST5878)
TAP-043-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-051-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-054-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-114-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-117-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-130-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-131-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-165-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-280-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-303-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-307-02-01
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP314-02-01 Rev 2
TAS 100
1995
PRI Construction Materials Technologies (TST5878)
TAP-315-02-01
ASTM D 6381
2008(2013)et
PRI Construction Materials Technologies (TST5878)
TAP-317-02-01
TAS 100
1995
UL LLC (TST9628)
02NK9507
ASTM D 3161
2016
UL LLC (TST9628)
04NK24366
ASTM D 3462
2010A
ULLLC(TST9628)
05NK28006
ASTM D 6381
2008(2013)et
UL 2390
ASTM D 7158
2011
UL LLC (TST9628)
06NK03898
ASTM D 3161
2016
ASTM D 3462
201
UL LLC (TST9628)
08CA59132
ASTMD 3161
2016A
UL LLC (TST9628)
09NK07896
ASTM D 3161
2016
ASTM D 62
2010A
UL LLC (TST9628)
10CA50498
ASTMD 3462
2010A
UL LLC (TST9628)
1 OCA64882
ASTM D 3161
2016
UL LLC (TST9628)
11 NK14014
ASTM D 3161
2016
ASTM D 3462
2010A
UL LLC (TST9628)
12CA24551
ASTM D 3161
2016
UL LLC (TST9628)
4786110543
ASTM D 6381
2008(2013)el
UL LLC (TST9628)
4787043752
ASTM D 3161
2016
UL LLC (TST9628)
478714874E
ASTM D 7158
2011
ASTM D 3161
2016
ASTM D 3462
2010A
CREEK Technical Services LLC (ANE11669)
TBP15001.3
Calculations
2017
TBP15001.4
FL18355-R4
Page 1 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
TAMKO BUILDING PRODUCTS
Asphalt Shingles
Elite Glass:Joplin
al@ 12-1/4" x 36", ASTM D 3161, Class F and ASTM D 7158, Class H self-sealing, 3-tab
Frederick, asphalt shingle with fiberglass mat coated on both sides with asphalt and surfaced with
loosceramic granules complying with ASTM D 3462.
Glass -Seal 12-1/4" x 36", ASTM D 3161, Class F and ASTM D 7158, Class H self-sealing, 3-tab
(Frederick & asphalt shingle with fiberglass mat coated on both sides with asphalt and surfaced with
Tuscaloosa) ceramic granules complying with ASTM D 3462.
Glass -Seal 12-1/4" x 36", ASTM D 7158, Class H self-sealing, 3-tab asphalt shingle with fiberglass
(Joplin) mat coated on both sides with asphalt and surfaced with ceramic granules complying
with ASTM D 3462. Shingles shall be used in the non-HVHZ only.
Heri ge@ 13-1/4" x 39-3/8", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
(Dal as, Frederick, reinforced, laminated architectural asphalt shingle surfaced with mineral granules
Joplin, Phillipsburg & complying with ASTM D 3462.
mereagela aremfum
13-1/4" x 39-3/8", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
(Dallas, Frederick,
reinforced, laminated architectural asphalt shingle surfaced with mineral granules
Phillipsburg &
complying with ASTM D 3462.
Tuscaloosa)
Heritage@ Premium
12" x 36", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass reinforced,
(Frederick)
laminated architectural asphalt shingle surfaced with mineral granules complying with
ASTM D 3462.
Heritage@ Vintage@
17-1/2" x 40", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass reinforced,
(Phillipsburg)
laminated architectural asphalt shingle surfaced with mineral granules complying with
ASTM D 3462.
Heritage@ Woodgate
13-1/4" x 39-318", ASTM D 3161, Class F and ASTM D 7158, Class H fiberglass
(Dallas & Frederick)
reinforced, laminated architectural asphalt shingle surfaced with mineral granules
complying with ASTM D 3462.
Heritage@ Woodgate
12" x 36-318", ASTM D 3161, Class F fiberglass reinforced, laminated architectural
(Frederick)
asphalt shingle surfaced with mineral granules complying with ASTM D 3462. Shingles
shall be used in the non-HVHZ only.
Hip and Ridge Shingles
12-1/4" x 12", ASTM D 3161, Class F fiberglass reinforced, hip and ridge asphalt
(Frederick & Joplin)
shingle surfaced with mineral granules complying with ASTM D 3462.
Vintage@ Hip and Ridge
12" x 12", ASTM D 3161, Class F fiberglass reinforced, hip and ridge asphalt shingle
(Phillipsburg)
surfaced with mineral granules complying with ASTM D 3462.
TBP15001.4 FL18355-R4 Page 2 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
INSTALLATION
TAMKO BUILDING PRODUCTS
Asphalt Shingles
Elite Glass -Seal®
Basic Wind Speed (Vw,):
Max. 194 mph
(Frederick, Joplin &
Basic Wind Speed (Vag):
Max. 150 mph'
Tuscaloosa)
Deck (HVHZ):
In accordance with FBC requirements;
&
Glass -Seal
Solidly sheathed min. 19132 in. plywood or wood plank for
(Frederick, Joplin (Non-
new construction; Min. 15/32 in. plywood existing
construction.
HVHZ) & Tuscaloosa)
Deck (Non-HVHZ):
In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7/16 in. OSB existing construction.
Undedayment:
In accordance with FBC requirements.
Min. slope:
2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12.
Installation (HVHZ):
Installed with 5-1/8 inch exposure in accordance with RAS
115 and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installation (Non-HVHZ):
Installed with 5-1/8-inch- exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either "4 Nail
Pattern" or "6 Nail Pattern" detailed below.
-7/8"
5-1 /8"
Butt Edge
Figure 1. Elite Glass -Seal & Glass -Seal
4 Nail Pattern (Non-HVHZ only)
M8'r
i-118"
Butt Edge
Figure 2. Elite Glass -Seal & Glass -Seal
6 Nail Pattern
TBP15001.4 FL18355-R4 Page 3 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G203. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
Heritage®
(Dallas, Frederick, Joplin,
Phillipsburg & Tuscaloosa)
Heritage® Premium
(Dallas, Frederick
Phillipsburg & Tuscaloosa)
Heritage® Woodgate
(Dallas & Frederick)
6-1
Basic Wind Speed (V u):
Basic Wind Speed (V,,a):
Deck (HVHZ):
Deck (Non-HVHZ):
Undedayment:
Min. slope:
Installation (HVHZ):
Installation (Non-HVHZ):
TAMKO BUILDING PRODUCTS
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7/16 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements. Refer to
the manufacturers application instructions when installing
shingles at slopes greater than 21:12.
Installed with 5-5/8 in. exposure in accordance with RAS
115 and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installed with 5-5/8 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either "4 Nail
Pattern" or "6 Nail Pattern" detailed below.
FASTENERS NAIL ZON E
COMMON
BOND
EXPOSURE 5-5/8"
" 12-1 /2"--►-12-318" — ►�— 12-1 /2" h -1 "
Figure 3. Heritage% Heritage@ Premium, and Heritage@ Woodgate (Dallas)
4 Nail Pattern (non-HVHZ only)
NAIL ZONE
FASTENERS —�� �,
:6ka
EXPOSURE 5-5/8"
1"—►I �7-1l2"�-7-1/2"-� 7�8'�7-1P2"H�-7-1/2"� �f-1"
Figure 4. Heritage@ & Heritage@ Premium
6 Nail Pattern
TBP15001 A FL18355-R4 rage 4 or n
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
TAMKO BUILDING PRODUCTS
Asphalt Shingles
^r A n ZONEI
MON BOND
1" �7-112:�-7-1/2�7-318�-7-1/2�t7-112+�►� �..•1„
Figure 5. Heritage@ Woodgate
6 Nail Pattern
PAIN
LIN
7-71W
:] Common Bond
Figure 6. Heritage@, Heritage@ Premium, & Heritage@ Woodgate
Alternate 6 Nail Pattern
LOOATION
Figure 7. Heritage@ (Tuscaloosa)
Expanded Nail Zone
Nail patterns from Figures 3, 4, and 6 may be placed in the nail zone as described above
TBP15001.4 --------
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
Heritage® Premium Basic Wind Speed (V,,,,):
(Frederick) Basic Wind Speed (Vasa):
Deck (HVHZ):
Deck (Non-HVHZ):
Underlayment:
Min. slope:
Installation (HVHZ):
Installation (Non-HVHZ):
TAMKO BUILDING PRODUCTS
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7/16 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12. .
Installed with 5 in. exposure in accordance with RAS 115
and manufacturers published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installed with 5 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either "4 Nail
Pattem" or "6 Nail Pattern" detailed below.
NAIL ZONE/
'COMMON BOND
1211 --►�r-11"� 14-1"
Figure S. Heritage® Premium (Frederick)
4 Nail Pattern (non-HVHZ only)
FASTENERS
NAIL ZONE/
COMMON BOND
--IT
EXPOSURE 5"
91h" It-1 It
Figure 9. Heritage® Premium (Frederick)
6 Nail Pattern
TBP15001.4 FL18355-R4 Page 6 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEL{
TECHNICAL SERVICES, LLC
Heritage& Woodgate Basic Wind Speed (V ,,):
(Frederick) Basic Wind Speed (V.,d):
Deck (Non-HVHZ):
Undedayment:
Min. slope:
Installation (Non-HVHZ):
TAMKO BUILDING PRODUCTS
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7/16 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements. Refer to
the manufacturers application instructions when installing
shingles at slopes greater than 21:12.
Installed with 5 in. exposure in accordance with FBC
requirements and manufacturers published installation
instructions. Shingles shall be attached using either "4 Nail
Pattem" or "6 Nail Pattern" detailed below.
BOND
r--IT
EXPOSURE 5"
1J±
1'L1 �— 11""�r 11" -- 10-1"
Figure 10. Heritage@ Woodgate (Frederick)
4 Nail Pattern (non-HVHZ only)
ZONFJ
IdON BOND
T T
&1121 FEI(POSURE 5"
3 U ii 1
Figure 11. Heritage@ Woodgate (Frederick)
6 Nail Pattern
TBP15001.4 . FL18355-R4 Page 7 of 11
This evaluation report is provided for State of Florida product approval under Rule 61G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEL{
TECHNICAL SERVICES, LLC
Heritage® Vintage® Basic Wind Speed (Vic):
(Phillipsburg) Basic Wind Speed (Vasd):
Deck (HVHZ):
TBP15001.4
Deck (Non-HVHZ):
Underlayment:
Min. slope:
Installation (HVHZ):
Installation (Non-HVHZ):
TAMKO BUILDING PRODUCTS
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7/16 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements. Refer to
the manufacturer's application instructions when installing
shingles at slopes greater than 21:12.
Installed with 5 in. exposure in accordance with RAS 115
and manufacturer's published installation instructions.
Shingles shall be attached using "6 Nail Pattern" detailed
below.
Installed with 5 in. exposure in accordance with FBC
requirements and manufacturer's published installation
instructions. Shingles shall be attached using either "5 Nail
Pattem" or "6 Nail Pattern" detailed below.
Figure 12. Heritage@ Vintage@
5 Nail Pattern (non-HVHZ only)
Figure 13. Heritage@ Vintage®
6 Nail Pattern
FL18355-R4
AP..
Pb¢h
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
Hip & Ridge Basic Wind Speed (V u):
(Frederick & Joplin) Basic Wind Speed (Vase):
Deck (HVHZ):
Deck (Non-HVHZ):
Underlayment:
Min. slope:
Installation:
TAMKO BUILDING PRODUCTS
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 15/32 in. plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7/16 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements.
Installed with 5-1/8 inch exposure in accordance with the
FBC and manufacturer's published installation instructions.
The direction of the exposed end shall be away from the
prevailing wind.
Direction prevailing wind
exposure
Figure 1
nor
Figure Figure 2
Figure 14. Hip & Ridge (Frederick & Joplin)
TBP15001.4 FL
9xposure
9of11
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK
TECHNICAL SERVICES, LLC
Vintage® Hip & Ridge Basic Wind Speed (V,,,,):
(Phillipsburg) Basic Wind Speed (Vasd):
Deck (HVHZ):
Deck (Non-HVHZ):
Undedayment:
Min. slope:
Installation:
TAMKO BUILDING PRODUCTS
Asphalt Shingles
Max. 194 mph
Max. 150 mph
In accordance with FBC requirements;
Solidly sheathed min. 19/32 in. plywood or wood plank for
new construction; Min. 16132 in. plywood existing
construction.
In accordance with FBC requirements;
Solidly sheathed min. 15/32 in. plywood or wood plank for
new construction; Min. 7/16 in. OSB existing construction.
In accordance with FBC requirements.
2:12 and in accordance with FBC requirements.
Installed with 5 inch exposure in accordance with the FBC
and manufacturer's published installation instructions. The
direction of the exposed end shall be away from the
prevailing wind.
Direction of prevailing wind
exposure
Figure 1
1"
Fastener
Figure 2
Kposure
rigure s
Figure 15. Vintage@ Hip & Ridge (Phillipsburg)
TBP15001.4 FL18355-R4 Page 10 of 11
This evaluation report is provided for State of Florida product approval under Rule 61 G20-3. The manufacturer shall notify CREEK
Technical Services, LLC of any product changes or quality assurance changes throughout the duration for which this report is valid.
This evaluation report does not express nor imply warranty, installation, recommended use, or other product attributes that are not
specifically addressed herein.
CREEK TAMKO BUILDING PRODUCTS
Asphalt Shingles
TECHNICAL SERVICES, LLC
LIMITATIONS
1) Fire Classification is not within the scope of this evaluation.
2) The roof deck and the roof deck attachment shall be designed by others to meet the minimum design loads
established for components and cladding and in accordance with FBC requirements.
3) The mean roof height shall be restricted to a maximum 33 It in the HVHZ.
4) Classification to ASTM D 7158 applies to exposure B & C with a building mean roof height of 60-11 or less.
5) Deck substrates shall be clean, dry, and free from any irregularities and debris. All fasteners in the deck
shall be checked for protrusion and corrected prior to underlayment application.
6) Shingles shall be installed starting at the eave in horizontal layers such that the laps shed water from the
deck.
7) Installation of the evaluated products shall comply with this report, the FBC, and the manufacturer's
published application instructions. Where discrepancies exist between these sources, the more restrictive
and code compliant detail shall prevail.
8) All products listed in this report shall be manufactured under a quality assurance program in compliance with
Rule 61 G20-3.
COMPLIANCE STATEMENT
The products evaluated herein by Zachary R. Priest, P.E. have demonstrated compliance with the Florida Building
Code, 6v Edition (2017) as evidenced in the referenced documents submitted by the named manufacturer.
ti :. 2017 09 25
No 7402111:31:41
-04'00'
STATE OF
'.� n '• c( V?: �c��.� Zachary R. Priest, P.E.
Florida Registration No. 21
SS10NA ; �� ,, Organization E anization No. A ll669
CERTIFICATION OF INDEPENDENCE
CREEK Technical Services, LLC does not have, nor will it acquire, a financial interest in any company manufacturing or distributing
products under this evaluation.
CREEK Technical Services, LLC is not owned, operated, or controlled by any company manufacturing or distributing products under
this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any company manufacturing or distributing products
under this evaluation.
Zachary R. Priest, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
END OF REPORT