19LOWER DOOR" PE5 a FORM
NED
Clouse Infiltration zest Cert)fleation SCAT Y
1°MSCr1Psive and Perf®rmanCe Method ,t. Lucie County
Date: 1 Z o z_o
Permit #: —_ C a S - 0 -7 S8
Contractor: �-rQ (�� /n e . (- _ -1 1
.lob Address: — S if 3
l—+ �� FL 3 k 4 Construction: (V") iMevv Construction - Colbtplete
( ) Erisiing- After Addition
House Infiltration Test Results
CFM (50) _ 6 SLC Climate Zone 2
Volume = Test Dare:
ACH (50) = CFM (50) n GO j Volume = .3 S
Passing results must be a ACH (50) or less Mechanical Ventilation required less than 3 ACH
(✓) Pass ( ) Fail
FBC,Energy I
The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes per
hour in Climate Zone 1, 2 and 3 air changes per hour in Climate Zones 3 through 8. Testing shall be conducted with a
blower door at a pressure of 0.2 Inches w. g. (50 Pascals). Testing shall be conducted by either individuals as defined in
Section 553.993(5) or (7), Florida Statutes or individuals licensed as set forth In Section 489.105 (3)(f), (g) or (1) or an
approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to the code official. Testing shall be performed at anytime after creation of all penetrations of the building
them, al envelope.
16C, Residential
Where the air infiltration rate of a dwelling unit is less than !air changes per hour when tested with a blower door at a
Pressure of 0.2 inch w. c. (50 Pa) in accordance with Section R402.4.1.2 of the Florida Building Code, Energy Conservation
the dwelling unit shall be provided with whole -house mechanical ventilation in accordance with Section M1507.3.
Taw. nE Camnany
Company Name: Pro -Duct SerV10eS
Address: •1915 Rio Vista Drive, Ft. Pierce, FL 34949
I hereby certify that the above House Infiltration results demonstrate compliance with FBC Energy Conservation
requirements in accordance wit"ection R402.4.1.2 Climate Zone 2.
Signatu re:
Printed Name: Martin Kiehl
License/Certification#: 5061633