HomeMy WebLinkAboutEVALUATION REPORTMEMO I etc. SCANNED Certificate of Authorization#32455 BY 353 Christian Street, Unit #13 St. Lucie County Oxford, CT 06478 (203) 262-9245 ENGINEER EVALUATE TEST CONSULT CERTIFY EVALUATION REPORT Polyglass USA, Inc. Evaluation Report P12060.02.09-R24 1111 West Newport Center Drive FL5259-R28 Deerfield Beach, FL 33442 Date of Issuance: 02/24/2009 (954)233-1230 Revision 24:01/24/2018 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the lit' Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: Polyglass Roof Underlayments LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the product(s), the Quality Assurance or the production facility location(s). NEMOIetc. requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMO)etc. Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 14. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DCA ANE1983 The facsimile seal appearing was authorized by Robert Nieminen, P.E. on 01/24/2018. This does not serve as an electronically signed document. CERTIFICATION OF INDEPENDENCE: 1. NEM01etc. does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. NEMOI etc. is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. 5. This is a building code evaluation. Neither NEMOletc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. NNEMO[etc. ROOFING COMPONENT EVALUATION: 1. SCOPE: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: Roof Underlayments, as produced by Polyglass USA, Inc., have demonstrated compliance with the following sections of the 6t6 Edition (2017) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Property Standard Year 1504.3.1 Wind Uplift FM 4474 2011 1504.3.1 Wind Uplift UL1897 2012 1507.2.3 / 1507.1.1 Physical Properties ASTM D226 2009 1507.2.4 / 1507.1.1, 1507.2.9.2 Physical Properties ASTM D1970 2015 1507.3.3 Physical Properties FRSA/TRI April 2012 2012 1507.11.2 Physical Properties ASTM D6164 2011 1507.11.2 Physical Properties ASTM D6222 2011 TAS 110 Accelerated Weathering ASTM D4798 2011 3. REFERENCES: 9nKne Examination Reference Date FM Approvals (TST 1867) Wind Uplift 3004091 01/12/2000 PRI (TST 5878) Physical Properties PRI01111 04/08/2002 PRI (TST 5878) Physical Properties PUSA-005-02-01 O1/31/2002 PRI (TST 5878) Physical Properties PUSA-013-02-01 12/23/2002 PRI (TST 5878) Physical Properties PUSA-013-02-02 12/23/2002 PRI (TST 5878) Physical Properties PUSA-013-02-03 12/23/2002 PRI (TST 5878) Physical Properties PUSA-018-02-01 07/14/2003 PRI (TST 5878) Physical Properties PUSA-028-02-01 07/13/2005 PRI (TST 5878) Physical Properties PUSA-033-02-01 01/12/2006 PRI (TST 5878) Physical Properties PUSA-035-02-01 09/29/2006 PRI (TST 5878) Physical Properties PUSA-055-02-02 12/10/2007 PRI (TST 5878) Physical Properties PUSA-061-02-02 01/28/2008 PRI (TST 5878) Physical Properties PUSA-076-02-01 02/22/2008 PRI (TST 5878) Physical Properties PUSA-083-02-01 04/14/2008 PRI (TST 5878) Physical Properties PUSA-088-02-01 07/29/2009 MITI (TST 2508) Physical Properties JX20H7A 04/01/2008 MTI (TST 2508) Physical Properties RX14E8A O1/29/2009 ERD (TST 6049) Physical Properties 11752.09.99-1 02/08/2000 ERD (TST 6049) Wind Uplift 11757.08,01-1 08/13/2001 ERD (TST 6049) Wind Uplift 11776.06.02 01/16/2003 ERD (TST 6049) Physical Properties 02200.07.03 07/14/2003 ERD (TST 6049) Wind Uplift P1740.01.07 01/04/2007 ERD (TST 6049) Physical Properties P5110.04.07-1 04/11/2007 ERD (TST 6049) Wind Uplift P9260.03.08 03/21/2008 ERD (TST 6049) Physical Properties P33450.08.09 08/13/2009 ERD (TST 6049) Wind Uplift P30540.11.09-R1 11/30/2009 ERD (TST 6049) Physical Properties P11030.11.09-1 11/30/2009 ERD (TST 6049) Wind Uplift P11030.11.09-2 11/30/2009 ERD (TST 6049) Physical Properties P11030.11.09-3 11/30/2009 ERD (TST 6049) Physical Properties P33360.06.10 06/25/2010 ERD (TST 6049) Physical Properties P33370.03.11 03/02/2011 ERD (TST 6049) Physical Properties P33370.04.11 04/26/2011 ERD (TST 6049) Physical Properties P37300.30.11 10/19/2011 NEMO ETC, U.C. Evaluation Report P32060.02.09-R24 Certificate of Authorization #32455 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FLS2S9-R28 Polyglass Roof Underlaynnents; (954) 233-1230 Revision 24: 01/24/2018 Page 2 of 14 119 ONEMOjetc. 912!!bf Examination Reference Date ERD (TST 6049) Physical Properties P40390.08.12-1 08/06/2012 ERD (TST 6049) Physical Properties P40390.08.12-2 08/07/2012 ERD (TST 6049) Physical Properties C41420.09.12-3 09/11/2012 ERD (TST 6049) Wind Uplift P39680.03.13 03/04/2013 ERD (TST 6049) Physical Properties P45370.04.13 04/26/2013 ERD (TST 6049) Wind Uplift P1738.02.07-R2 04/29/2013 ERD (TST 6049) Wind Uplift 11757.04.01-1-R1 04/30/2013 ERD (TST 6049) Wind Uplift P41630.08.13 08/06/2013 ERD (TST 6049) Wind Uplift P11751.05.03-R1 11/26/2013 ERD (TST 6049) Wind Uplift P31781.11.03-R1 11/26/2013 ERD (TST 6049) Physical Properties P45270.05.14 05/12/2014 ERD (TST 6049) Physical Properties 6020.07.14-1 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-2 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-3 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-4 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-5 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-6 09/08/2014 ERD (TST 6049) Physical Properties P46520.10.14 10/03/2014 ERD (TST 6049) Physical Properties P43290.10.14 10/17/2014 ERD (TST 6049) Physical Properties PLYG-SC7550.03.15 03/24/2015 ERD (TST 6049) Physical Properties P40390.04.15 04/03/2015 ERD (TST 6049) Physical Properties P44360.10.14-R1 05/18/2015 ERD (TST 6049) Physical Properties PLYG-SC8080.05.15-1 05/20/2015 ERD (TST 6049) Wind Uplift PLYG-SC8905.05.16-1 . 05/17/2016 ERD (TST 6049) Physical Properties PLYG-SC8080.07.16 07/16/2016 ERD (TST 6049) Wind Uplift PLYG-SC12025.10.16 10/12/2016 ERD (TST 6049) Physical Properties PLYG-SC33040.12.16 12/27/2016 ERD (TST 6049) Physical Properties PLYG-SC11900.03.17 03/10/2017 ERD (TST 6049) Physical Properties PLYG-SC12115.08.17 08/08/2017 ICC-ES(EVL 2396) IBCCompliance ESR-1697 11/01/2014 Miami-Dade(CER 1592) HVH2 Compliance NOA 14-0717.08 01/22/201S Polyglass USA Manufacturing Affidavit Products Current 02/18/2009 Polyglass USA P/LAffidavit Mule -Hide Cross Ltg 03/01/2008 Polyglass USA Materials Affidavit Polystick SA Compound 08/18/2011 UL, LLC.(QUA9625) Quality Control Service Confirmation Exp.10/05/2018 PRODUCT DESCRIPTION: 4.1.1 Elastobase is a fiberglass reinforced, SBS modified bitumen base sheet. 4.1.2 Elastobase P is a polyester -reinforced, SBS modified bitumen base sheet. 4.1.3 Polyglass G2 Base is a fiberglass -reinforced, asphaltic base sheet. 4.1.4 Polyglass APP Base is a fiberglass -reinforced, APP modified bitumen base sheet. ,4.2 Self-AdheringUnderlayments: _...IQ -- - 4.2.1 Polystick MTS or Polystick MTS PLUS is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, surfaced with polyolefinic film surface; meets FRSA/TRI April 2012. 4.2.2 Polystick IR-Xe is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an aggregate surface; meets ASTM D1970. 4.2.3 Polystick TU Plus is a nominal 80-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. NEMO ETC, U.C. Evaluation Report P32060.02.09-R24 Certificate of Authorization N32455 6' EDITION (2017) FBC NON-HVH2 EVALUATION FL5259-R28 Polyglass Roof Underlayments; (954) 233.1230 Revision 24: 01/24/2018 Page 3 of 14 NNEM0 I etc. 4.2.4 Polystick TU P is a nominal 130-mil thick rubberized asphalt waterproofing membrane, glass-fiber/polyester reinforced, with a granular surface; meets FRSA/TRI April 2012. 4.2.5 Polystick TU Max is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 190 g/m2 polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. 4.2.6 Polyflex SAP, Polyflex SAP FRI, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FIR) are polyester reinforced, APP modified bitumen cap sheets; meet FRSA/TRI April 2012, 4.2.7 Polystick Dual ProTM is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyester fabric surface; meets ASTM D1970. 4.2.8 Polystick Tile ProTM is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyester fabric surface; meets ASTM D1970 and FRSA/TRI April 2012. 4.2.9 Polystick MU-X is a nominal 54-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polypropylene film surface; meets AC188 and physical requirements of ASTM D1970 (See Section 5.8). 4.3.1 Elastoflex G TU is a polyester reinforced, modified bitumen tile underlayment composed of a sand -surfaced SBS modified bitumen back -side and granule -surfaced APP modified bitumen top -side. Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing' (ASTM D6380, Class M) in the "Single Ply System' from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. 4.3.2 Elastoflex S6 G and Elastoflex 56 G FIR are polyester reinforced, SBS modified bitumen cap sheets; meet ASTM D6164. Elastoflex S6 G and Elastoflex S6 G FIR are for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. Elastoflex S6 G is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Elastoflex S6 G FIR is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. 4.3.3 Polyflex G and Polyflex G FIR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222! Polyflex G is for use as an alternate to Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Polyflex G FIR is for use as an alternate to Heat Applied "Cap Sheet" in the'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. 5. LIMITATIONS:^ 5.1 This is a building code evaluation. Neither NEMOI etc. nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in the HVHZ. 5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of this product. 5.4 Polyglass Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. NEMO ETC, LLC. Evaluation Report P32060.02.09-R24 Certificate of Authorization#32455 6'"EDITION(2017) FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 4 of 14 NNEMOjetc. 5.5 Allowable Roof Covers: TABLE 1:-ROOF COVER OPTIONS Underlayment Asphalt Shingles Nail -On Tile Foam -On Tile Metal Wood Shakes &Shingles Slate Elastobase Yes Yes (Base Sheet in] -ply system) Yes (Base Sheet in 2-ply system) Yes Yes Yes Elastobase P Yes Yes (Base Sheet in 2-ply system) yes (Base Sheet in 2-ply system) Yes Yes Yes Polyglass G2 Base No Yes (Base Sheet In 2-ply system) Yes (Base Sheet in 2-ply system) No No No Polyglass APP Base No - Yes (Base Sheet in 2-ply system) Yes (Base Sheet in 2-ply system) No No No Po ystitM¢fiS0",Tylis`F Palystic es �Yes� No o�Q es a es Yes i(e Yes No No �Ye Polystick TUP No Yes Yes (See 5.5.1) No No No Polystick TU Plus Yes Yes Yes (See 5.5.1) Yes Yes Yes Polystick TU Max No Yes Yes (See 5.5.1) Yes No No Polystick Dual Pro Yes No No Yes Yes Yes Polystick Tile Pro Yes Yes Yes (See 5.5.1) Yes Yes Yes Polystick MU-X Yes No No Yes Yes Yes Elastoflex S6G Yes Yes Yes (See 5.5.1) No Yes Yes Elastoflex S6 G FR Yes Yes No No Yes Yes Elastoflex G TU Yes Yes Yes (See 5.5.1) No Yes Yes Polyflex G Yes Yes Yes (See 5.5.1) No Yes Yes Polyflex G FR Yes Yes No No Yes Yes Polyflex SAP or SAP FR Yes Yes Yes (See 5.5.1) No Yes Yes Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) yes Yes Yes (See 5.5.1) No Yes Yes 5.5.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combinations. - . TABLE 1A: ALLOWABLE TILE ADHESIVE/ UNDERIAYMENT COMBINATIONS'_ Adhesive Florida Product Urderlayments Approval DAP Foam Touch'n Seal StormBond Roof Tile Adhesive FL14S06 Polystick TU Plus, Polystick TU Max Dow TileBond" FL22525 Polystick TU P, Polystick TU Plus, Polyflex SAP or Tile Pro Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, ICP Adhesives Polyset® AH-160 FL6332 Elastoflex G TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, ICP Adhesives Polyset® RTA-1 FL6276 Elastoflex G TU, Elastoflex 56 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-AlP Cap Sheet (FR) r Refer to Tile Manufacturers orAdhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance. NEMO ETC, U.C. Evaluation Report P12060.02.09-R24 Crrtifimte ofAuthoriaotion #32455 15m EDITION (2017) FBC NON-HVH2 EVALUATION F1.5259-1128 Polyglass Roof Underlayments; (954) 233-1230 Revision 24:01/24/2018 Page 5 of 14 NNEMO I etc. 5.6 Allowable Substrates: 5.6.1 Direct -Bond to Deck: Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: D New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing plywood; New or existing, unprimed OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern Yellow Pine; ASTM D41 primed structural concrete; Huber Engineered Woods "ZIP System" Panels (designed and installed to meet wind loads for project). Note: Polyglass does not require priming of new or existing plywood or OSB sheathing. New or existing plywood or OSB sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ ASTM D41 primed structural concrete. Polyflex G or Polyflex G FR torch -applied to: ➢ ASTM D41 primed structural concrete. 5.6.2 Bond -to -Insulation: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: ➢ ASTM C1289, Type II, Class 1 polyisocyanurate or Type V polyisocyanurate-composite insulation; Dens Deck DuraGuard; Dens Deck Prime; or SECUROCK Gypsum -Fiber Roof Board. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. Polyflex G or Polyflex G FR torch -applied to: ➢ ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations under foam -on tile systems, insulation attachment shall be designed by a qualified design professional and installed based on testing of the insulation/underlayment system in accordance with FBC Section 1504.3.1. 5.6.3 Bond to Mechanically Attached Base Laver: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or Tile Pro self -adhered to: ➢ ASTM D226, Type I or II felt; Elastobase; Elastobase P or Mule -Hide Nail Base. Elastoflex G TU, Elastoflex 56 G or Elastoflex S6 G FR in hot asphalt to: ➢ ASTM D226, Type I or II felt; Elastobase; Elastobase P, Mule -Hide Nail Base or Polyglass G2 Base. Polyflex G or Polyflex G FR torch -applied to: ➢ Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass G2 Base or Polyglass APP Base. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under foam -on tile systems, base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested in accordance with FBC Section 1504.3.1. NEMO ETC, U.C. Evaluation Report P12060.02.09.R24 Certificate o)Authonratlm H32455 6'" EDITION (2017) F8C NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 6 of 14 NNE m' O I etc. 5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12) does not address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04- 12), Appendix A, Table SA or FBC 1609 for determination of design wind loads. #1 Maximum Design Pressure =-90 nsf Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: None Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #2 Maximum Design Pressure =-97.5osf• Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyfle: SAP FRI, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x 1Y.." ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch o.c. #3 Maximum Design Pressure =-105 psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: WB-3000 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x 1%" ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch o.c. #4 Maximum Design Pressure=-135 psf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: (Optional) PG100 or ASTM D41 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Joints: Min. 4-inch wide strips of Elastoflex SA-V over all plywood joints. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #5 Maximum Design Pressure=-315 osf: Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Tile Pro, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #6 Maximum Design Pressure=-622.5 osf: Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #7 Maximum Design Pressure=-30.0 osf': Deck: Min.15/32-inch OSB to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.25-inch long x 1-inch head diameter round metal cap nails Spacing: 6-inch o.c. at the 3-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. NEMO ETC, U.C. Evaluation Report P12060.02.09-R24 Certificate of Authorization#32455 6'"EDITION (2017)FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 7 of 14 NNEMO I etc. #8 Maximum Design Pressure=-37.5 osf*: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: it ga. x 1.25-inch longx 1-inch head diameter round metal cap nails Spacing: 6-inch o.c. at the 3-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #9 Maximum Design Pressure =-37.5 osf* Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: One (1) or two (2) layers ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-inch long x 1-inch head diameter round metal cap nails Spacing: 6-inch o.c. at the 3-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt. #10 Maximum Design Pressure=-45 osf*: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: One (1) layer ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 4-inch o.c. at the 2-inch wide side laps and 4-inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional; for use with self -adhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and - Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU, applied in full mopping of hot asphalt. #11 Maximum Design Pressure =-45 osf*: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Two (2) layers ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-inch long 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 9-inch o.c. at the 2-inch wide side laps and 9-inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional; for use with self -adhering underlayment only) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt. #12 Maximum Design Pressure=-45 osf Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 9-inch o.c. at the 2-inch wide side laps and 18-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #13 Maximum Design Pressure =-52.5 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 9-inch o.c. at the 2-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #14 Maximum Design Pressure =-52.5 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: Simplex Original Cap Nails Spacing: 6-inch o.c. at the 3-inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick NITS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. NEMO ETC, U.C. Evaluation Report P12060.02.09-R24 Certificate of Awhodzatlon#32455 6" EDITION (2017) FDC NON-HVHZ EVALUATION F1.5259-1128 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 8 of 14 NDEMO I etc. #15 Maximum Design Pressure =-52.5 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex Original Cap Nails Spacing: 6-inch o.c. at the 3-inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #16 Maximum Design Pressure =-60 osf: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: 11 ga. x 1.25-inch long 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 8-inch o.c. at the 4-inch wide side laps and 8-inch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex GTU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #17 Maximum Design Pressure =-60 osf: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: OMG #12 Standard Roofgrip with OMG Flat Bottom Metal Plates Spacing: 12-inch o.c. at the 4-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #18 Maximum Design Pressure =-67.5 osf: Deck:- Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment) Fasteners: 12 ga. x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 8-inch o.c. at the 4-inch wide side laps and 8-inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #19 Maximum Design Pressure=-75 osf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment) Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with OMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-inch Insulation Plates or Simplex MAXX Cap Fasteners Spacing: 30-inch o.c. at the 4-inch wide side laps and 10-inch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #20 Maximum Design Pressure=-90 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastabase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-inch o.c. at the 2-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #21 Maximum Design Pressure =-90 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal Plates Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #22 Maximum Design Pressure =-90 osf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface) Fasteners: Trufast#12 DP or Trufast#14 HD with Trufast 3" Metal Insulation Plates Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt. NEMO ETC, LLC. Evaluation Report P32060.02.09-R24 Certifirote of Authorization #32455 6r" EDITION (2017) FBC NON-HVH2 EVALUATION FLS2S9-R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 9 of 14 ONEMOletc. #23 Maximum Design Pressure=-90 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underfoyment) Fasteners: Dekfast #14 with Dekfast Hex plates, OMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with OMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-inch Insulation Plates or Simplex MAXX Cap Fasteners Spacing: 9-inch o.c. at the 4-inch wide side laps and 9-inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. #24 Maximum Design Pressure=-97.5 osf Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: it ga. x 1.25-inch"x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 4-inch o.c. at the 4-inch wide side laps and 4-inch o.c. at four (4) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS or Polystick MTS PLUS, self -adhered. Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. ' #25 Maximum Design Pressure=-105 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 6-inch o.c. at the 2-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #26 Maximum Design Pressure=-112.5 osf: Deck: Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at 1-S/8-inch diameter tin caps Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows. Primer: PG100 or ASTM D41 primer at all tin -caps Base Ply: Polystick MTS or Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. #27 Maximum Design Pressure =-120 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal Plates Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at five (5) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. #28 Maximum Design Pressure =-120 osf: Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface) Fasteners: Trufast #12 DP or Trufast #14 HD with Trufast 3" Metal Insulation Plates Spacing: 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at five (5) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt. 5.6.4.1 All other direct -deck, adhered Polyglass underlayment systems beneath foam -on tile systems carry a Maximum Design Pressure of-45 psf. NEMO ETC, LLC. Evaluation Report P12060.02.09-R24 Certificate of Authorization#32455 6'x EOI1I0N(2017)FBC NON-HVH2 EVALUATION FL5259-R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 10 of 14 NNEMID. I etc. 5.6.4.2 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. 5.7 Exposure Limitations: Elastobase, Elastobase P, Polyglass G2 Base or Polyglass APP Base shall not be left exposed for longer than 30-days after installation. Polystick IR-Xe or Polystick MU-X shall not be left exposed for longer than 90-days after installation. Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Dual Pro, Tile Pro or Elastoflex G TU shall not be left exposed for longer than 180-days after installation. ` Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure. limitation, unless the prepared roof covering is to be adhesive -set tile, in which case the maximum exposure is 30 days. Elastoflex S6 G or Elastoflex 56 G FR or Polyflex G or Polyflex G FR does not have an exposure limitation, unless the prepared roof covering is to be adhesive -set tile (Elastoflex S6 G or Polyflex G only), in which case the maximum exposure is 180 days. 5.8 Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226 roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as set forth in Section 4.3, Note 1 of ASTM D1970-15, should be established as to slip resistance. 5.9 Tile Slippage Limitations (FRSA/TRI April 2012 (04-12)): When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall be as follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles. TABLE 2: TILE SLIPPAGE LimITATIONS FOR DIRECT -DECK TILE INSTALLATIONS - x Underlayment Tile Profile Staging Method Maximum Slope Elastoflex G TU Flat 10-tile stack 7:12 Lugged 8-tile stack (6 over 2) 6:12 Elastoflex S6 G or S6 G FR Flat or Lugged 6-tile stack (4 over 2) 4:12 Polystick NITS or NITS PLUS Flat 6-tile stack (4 over 2) 5:12 Lugged 6-tile stack (4 over 2) 4:12 Polystick Tile Pro Flat or Lugged 6-tile stack (4 over 2) 7:12 Polystick TU Max Flat 6-tile stack (4 over 2) or 10-tile stack 7:12 Lugged 6-tile stack (4 over 2) 7:12 Lugged 10-tile stack 6:12 Polystick TU P Flat 6-tile stack (4 over 2) 6:12 Lugged 6-tile stack (4 over 2) 4:12 Polystick TU Plus Flat or Lugged 6-tile stack (4 over 2) 7:12 Flat or Lugged 10-tile stack 6:12 Polyflex G or G FR Flat or Lugged 6-tile stack (4 over 2) 4:12 Polyflex SA P or SA P FR Flat or Lugged 6-tile stack (4 over 2) 4:12 NEMO ETC, U.C. Evaluation Report P12060.02.09-R24 Certificate of Authorization#3Z455 6'" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259-R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 11 of 14 NNEMOletc. 6. INSTALLATION: 6.1 Polyglass Roof Underlayments shall be installed in accordance with Polyglass published installation requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris priorto application, and prime the substrate (if applicable). 6.3.1 Shall be installed in compliance with the codified requirements for ASTM D226, Type II underlayment in FBC Table 1507.1.1 for the type of prepared roof covering to be installed. Elastobase, Elastobase P or Mule -Hide Nail Base may be covered with a layer of Polystick, Polyflex SAP, Poly0ex SA P FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FRI, self -adhered, Elastoflex G TU, Elastoflex S6 G or Elastoflex 56 G FR in hot asphalt or Polyflex G or Polyflex G FR, torch applied. Roof cover limitations are those are those associated with the top -layer underlayment, as set forth in Table 1. 6.3.2 Tile Applications: Elastobase, Elastobase P or Mule -Hide Nail Base are limited to use as a mechanically attached base sheet in the "Two Ply System" from FRSA/TRI April 2022 (04-12). Reference is made to Table 1 and Section 5.6.4 herein, coupled with FRSA/TRI April 2012 (04-12) Installation Manual. 6 4P Poly'stick.MTS "MTS PLUS, IR Xe; TU P, TU;Plusj TU Miix;IDual Pro Tile Pro or%,MU-X.or Polyflex SAP Pofyilex SAP �Rj; Mule -Hide SA=APP Cap Shee'foT:Mule,Hide SiA ARP.t?ap;Sheet a I' 6.4.1 Shall be installed in compliance with the codified requirements for ASTM D1970 (except Polystick TU P) underlayment 6.4.2 in FBC Table 1507.1.1 forthe type of prepared roof covering to be installed. Direct -to -Deck with Mechanically Fastened Roof Covers: All self -adhering materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) should be back -nailed in selvage edge seam in accordance with Polyglass / Mule - Hide back nailing guidelines. Nails shall be corrosion resistant, 11 gauge ring -shank type with a minimum 1-inch diameter metal disk or Simplex -type metal cap nail, at a minimum rate of 12" o.c. Polystick TU Plus should be back - nailed using the above noted fasteners and spacing, in area marked "nail area, area para clavar" on the face of membrane. The head lap membrane is to cover the area being back -nailed. All seaklap seams (selvage laps) must be i firmly rolled with a minimum 28 lb. hand�� roller to ensure full contact and adhesion.,++'"��_ _ For Dual Pro and Tile Pro, align the edge of the top sheet to the end of the glue pattern (the sheet will overlap the fabric). View of Ovelap Seam of Dual Pro and Tile Pro All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PG500 Modified Cement applied in between the application of the lap. Polystick TU Plus, Dual Pro and Tile Pro may not be used in any exposed application such as crickets, exposed valleys, or exposed roof to wall details NEMO ETC, LLC. Evaluation Report P12060.02.09-R24 certificate of Authorization#32455 6'" EDITION (2017) FBC NON-HVHZ EVALUATION FL5259.R28 Polyglass Roof Underlayments; (954) 233-1230 Revision 24: 01/24/2018 Page 12 of 14 i MEMO I etc. Repair of Polystick membranes is to be accomplished by applying Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PG500 Modified Cement to the area in need of repair, followed by a minimum 6 x 6 inch patch of the Polystick material of like kind, set and hand rolled in place over the repair area. Patch laps, if needed, shall be installed in a water shedding manner. All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a minimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom with approximately 40-lbs of load applied for the field membrane. Hand rollers are acceptable for rolling of patches, laps (min. 28 lb roller) or small areas of the roof that are not accessible to a large roller or broom. 6.4.3 riileApplications (not allowed for Polystick Dual Pro, IR-XeorPolystick MU-X): Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions noted above as a guideline. For mechanically fastened tile roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12), Table 1. For adhesive -set tile applications, refer to Section 5.6.4 herein. 6.4.4 Two (2) Ply Underlavment Systems: Polystick MTS or MTS PLUS followed by Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Tile Pro, MU-X or Polyflex SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with the top -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired. Polystick MTS or MTS PLUS followed by Polystick TU P, TU Plus, TU Max, Tile Pro or Polyflex SAP is allowable for use under foam -on tile systems. Limits of use are those associated with the top -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired. 6.5. Elastoflex G:TU, Elastoflex S6:.G.oy Elastoflex.66 G: FR: 6.5.1 Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be installed in compliance with current Polyglass published installation requirements. For use in tile applications: ✓ Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing' (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G FR is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. 6.5.2 For hot -asphalt -applications, Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be fully asphalt -applied to the substrates noted in Section 5.6. Side laps shall be minimum 3-inch and end -laps minimum 6-inch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully adhered in a complete mopping of hot asphalt with asphalt extending approximately 3/8-inch beyond the lap edge. 6.6 Polyflex G or Polyflex G FR: 6.6.1 Polyflex G or Polyflex G FR shall be installed in compliance with current Polyglass published installation requirements. For use in tile applications: ✓ Polyflex G is for use as an alternate to the Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems (Base Sheet Limited per 5.6.3). ✓ Polyflex G FR is for use as an alternate to the Heat Applied "Cap Sheet' in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems (Base Sheet Limited per 5.6.3). NEMO ETC, U.C. Evaluation Report P12060.02.09-R24 Certificate of Authorization#32455 e" EDITION (2017) FBC NON-HVH2 EVALUATION FL52S9-R28 Polyglass Roof Underlayments; (9541233-1230 Revision 24: 01/24/2018 Page 13 of 14