HomeMy WebLinkAboutSCREEN ENCLOSURE DETAILSa Gene/tii Notes and Specifications: 1. Contractor shalt field verify all dimensions before construction and shall notify engineer of discrepancies for immediate consideration. 2. Concrete shall be minimum 28 day compressive strength of f'c=2500 psi, and be in accordance with the requirements of ACI 318. Reinforcing steel shall have a min. yield strength of 40,000 psi (grade 40) and be provided with cover in accordance with ACI 318. 3. All dimensions are provided by contractor, DO Kim & Associates, LLC have made interpretations where necessary. 4. The following structures are designed to be attached to block and wood frame structures of adequate structural capacity. The contractor shall verify that the host structure is in good condition and of sufficient strength to hold the proposed addition. If there is a question about the host structure, the owner (at his own expense) shall hire an architect or engineer to verify host structure capacity. 5. Screen densityshall be a maximum of 18 x 14 x 0.013" mesh. Aluminum shall be7005-T53 Alloy, 6005-T5 Alloy; for secondary components 6063-T6, Alloy based on industry standard shapes, thicknesses, and tolerances unless otherwise noted. 6. Unless otherwise noted, SMB shall be stitched with #100/4" SMS at 24"o.c., top and bottom. 7. Connections using screw bosses shall have minimum (4)41W" per connection unless shown otherwise. B. Unless otherwise shown, screws shall have minimum edae distance and center -to -center distances as shown in this table. C-ID22 Low Carbon Steel SMS & Self -Drilling (TEK) Screws (Industry Standard Screws) Screw Nominal Screw Diameter (in) Minimum Edge Distance Minimum Center to Center Distance #10 0.1B8 #14 (1/4") 0.250 14" 9. Structure has been designed to meet the 6" Edition FBC (2017 FBCI. Project is sited where the ultimate design wind speed, Vd, is 150 mph (3-sec gust)for risk category I buildings and other structures. Exposure B. Design pressures are from Table 2002.4. 2017 FBC reduced by 0.88 for screen mesh factor, 0.6 for allowable stress design (ASD). 10. Concrete anchors may be "Large Diameter Tapcons" (LTDsl. Tapcon concrete screws, Simpson Strong -Tie Anchors or Titian Screws or approved equal. 2.3 PURUN (MAYBE SLOPEDIOR FIAT)-'- . S.M.S. THRU. IX2 PURUN SCREW 2x2 FASTENED TO SUPERGUTIER W/ /14z2' S.M.S. O 24' D.C. AND O EACH SIDE OF PURUN CTLstCOPY DO KIM ASSOCIATES, LLC t_ CONSULTING N 4_ STRUCTURAL i1 is ENGINEERS E x� - PO Box 10039 Tampa, FL 33679 Tel: (813) 374-0321 ATTACH SUPER GUTTER W/ (2) )4wex2Y2* -LAG SCREW O EACH PURUN AND (1)-B14x2' LG. S.M.S O 12' O.C. MAX. THE-ENORE LENGTH OF SUPER GUTTER 'f--PURLIN'.T O--SUPER'GUTTER (2) 014A7 S.M.S., EACH LEG AND 4 #144" S.M.S. CHANNEL TO BEAM 8 SCREW TOTAL 11. Screen enclosure structure shall meet Section 454.2.17 Residential Swimming Barrier Requirements and the screen enclosure per 1.1,9' BY 2' LONG 454.2.17.1.11. if enclosing a pool. ANGLE. EACH SIDE (TYP.) x 2 1/8" x 1' x 2" I.C. (4) B141V' S.M.S.. 2 SCREWS EACH LEG (TYP.) HOLLOW POST BEAM STITCHING O 24' O.C. M. TOP AND BOTTOM OF SUB SEE TABLE FOR SIZES) 1xlx%' BY 2' LONG ANGLE, EACH SIDE (TYP.) LEG (4) TOTAL (TYP.) PURLIN TO BEAM CONNECTION -- =-=` CHAIR RAIL / GIRT TO POST CONNECTION DETAIL 2x3z0.045 EAVERML ATTACHED TO _ +' i= BEAMS WITH (3)—Q10z2' S.M.S. � INTO SCREW BOSS. _ „_ - -- , - 61 -� MAY BE SLOPED OR FIAT . ,/ • 2x2 - 2. PURUN (MAY BE SLOPED ,..: -: (SEE PLAN FOR SIZE) -• ') )y0x2Ya' LG:,L"AG SCREW OR FLAT) (2) B10z4' S.M.S. IHRU. 2.3 INCH SIDE SIDE !>FHEAN (TYP.) FAVE RAIL INTO PURUN SCREW 2x5z.125 ANGLE-2' WIDE.WRN-% _ f FACIA TO BE 2x6 (HIM.) (4) B1403 4' S.M.S. BOSSES (2)-114x1' INTO BEAM &.-(2)—Bt4x1' IMO UPRIGHT. z (�') � USE B10xi)S' S.M.S. O 24' O.C. — — — za % Y � TO CONNECT TO 1x2 O.B. TO 2x3. � �2]/�/ ROOF BEAN USE BIOXIY2' S.M.S. O 24' O.C. (FIAT OR SLOPED) SECURE FASCIA TO EACH RAFTER TAIL / TO CONN[T TO 1.2 O.B. TO 2.3. V/ (1) K'0x4' LONG PAN HEAD LAG SCREWS / — — _ _ _ )I BEFORE ATTACHING SUPER GUTTER / IX2 O.B. FASTENED TO COLUMN/POST PURUN FASTENED TO COLUMN/POST W/(2) B10x Dj' S.M.S. INTO B WOH (J4)) B12x1' S.M.S. (EACH LEG) EEEEEE ' OF)I.QEAM ' S)•Q.R�H SIDE )S' EASCREW CH TYPE) USINGBST MIN., 3 Ye' STEAX. ERS (6)B12xii S.M.S. EACH SIpE SPACING (IF FASTENERS (TYP.) 2x2rJ6' ANGLE, EACH SIDE TO (60831C T6 AUA )7 OF BEAM FOR 2.5 COLUMN TO OYPJa 4 -1 t �v COLUMN/POST 2x5 BEAM / Ya• MIN. BEAM EDGE DISTANCE (TYPJ r /Lp1NO (8) S.M.S., (4) SCREW �,^" 1`., COLUMN/POST J EACH LEG?OYPJ I LEG,'4 E3 CARRIEFf BEAM TO FASCIA CONNECTION DETAIL 7 ,. S4lucie(301 -. - _ SIDEWALL POST COLUMN TO PURLIN - MAIN=PO$T / COLUMN TO ROOF BEAM- - CONNECTION DETAIL CONECTION-DETAIE`"i - �9rxo-O� f c LU W of O U O � J U z W a) LLI ULI C Z Of a g = J WLU a U ❑ DO PEON KIM, P.E. FLA. REG. NUMBER 49497 DO KIVAS.S CIATES,LLC 887 0039 33679 6,N9 i Drawing No. - 060811 i 1 OF2 - a-3 PURUN SUPFO -s _ - - - _ .4 - — COLVMN/P.OS'{ ._' .. y- ANOIE. EACH SIOE (TPJ /^� �- x Y LG..M.S S.M.S. WITH MIN.' i6'0' ANCHOR q W/ (4)8' W/ 1112a3/4' S.M.S EDGE DISTANCE kEMBETE tENBEDONCR H (EACH slDLy STRU smumuR�oxcaETE (TYPJ TE ( \� %-0 CONCRETE ANCHOR 1'd' D.B. SOLE.PLATE O O RUCT M. CONCR INTO ST S (EACH MO) CONCRETE Z 7j ^�•W J' MIN. (TM,. ,) fiq awY•0z2Y' CONCRETE J �pw z;'i SCREW ANCHOR 0 24" OC AND 9' FROM POsF (1YP.) ` w yU \ SEE PUN FOR SZE O.B. FASTENED TO COMESE SECTION WITH /14z1Yy' S.M.S.N 24' O.C. U) 2x2d'0' ANGLEI2LONG (EACH W/(2, �14�' S.M.S. TO POS § 3 0 H.D. GALV. UP. 801 W/ 2 1/2' MIN. EMBEDMENT S.M.5. WITH MIN. ' K ANGLE EACH SIDE (TVP.) EDGE. DISTANCE %"0 CONCRETE ANCHOR W/2)6' EMBEDMENT IN10 STRUCTURAL CONCRETE OW.) . X . 1'x2' O.B. SOLE PLATE •J } �CF tVV I irc'd U OF CONCRETE PLAN VIEW 44 3- MIN. (TYP.) ,1 ,1 E PLATE O.B. SOLE PLATE 4 :TYP.) ) ,, 2500 PSI MIN. CONCRETE STRENGTH '° a D ❑ K I M 'ROXIMATE •.. . GRADED I _ IICq�/ [� ® REVIEWED FOR & ASSOCIATES, LLC ° °' d' ° CODE COMPLIANCE CONSULTING 1 ° ST. LUCIE COUNTY STRUCTURAL ��� I °' � � ' , p I I � COMPACTED OR I UNDISTURBED SOIL/S4ND B®CC ENGINEER S ° (1)-#5 REBAR, CONTINUOUS PO Box 10039 I ' ' I — I 3" MIN. CONC. COVER, 36" MIN. Tampa, FL 33679 I�I I. 1I II TTT IT�)T� _ LAP SPLICE Y.'mxDs' LAG ScaEW o- 12' O.C.. (1) WITHIN 3. OF EDGES (M.) Tel: (813) 374-0321 12' MIN.* 1-x - D.B. (M.) ReviDatel Descri lion zo, em 201> ISSUED NOTE: STUD MIN. CONTINUOUS PERIMETER FOOTING FOR BLOCK FRAMED HOUSES USE /14x271 CONCRETE SCREW WOOD FRAME WALL O Is, D.C.. 1 WITHIN 3' OF EDGES CYPJ 0 0 TYPICAL SCREEN EDGE TO STRUCTURE CONNECTION DETAIL POST � U2 O.B. TOP FRAME 1.3 03. FASTENED TO CORNER CORNER POST SECTION WITH #10.2' S.M.S. W/ W DIA WASHER O 18- O.C. Ix O.B. SIDE WALL CORNER UPRIGHT ELEVATION VIEW BEAM SUPPORT CORNER POST/ COLUMN COLUMN/POST 2a21 1/a' a 2, Lc ANGLE UPRIGHT DETAIL W/ (4) /12a3/4' S.M.S (EMH SIDE) POST 4' NOMINAL CONCRETE SUB (25GO PSI, MIN.) W/6x6XIO/l0 W.W.M. OR FIBER REINFORCED [MI.WROPDENE RISER - 1.5 FOUND (NIN.)PFR C.Y.] °°.. • ' •e .• • • UNDISTURBED SOIL OR COMPACTED CRUSHED UMEROCK (90R PROCTOR) MIN. (1)-15 REBAR CONTINUOUS, SPLICE MUST OVERLAP 20' MIN. 3' COVER (TYP.) FOUNDATION/SLAB DETAIL 1x2 O.B. OR 2x2 FASTENED TO WA LL - CO CONCRETE SCREWS 024' O.C. 1, W/ d14a2ON MAX. DISTANCE FROM (OPTIONAL) BEAM EDGE TiP. 2x2 Y- MIN. THICK ANGLE (EACH SIDE) F (ANGLE LENGTH - DEPTH OF BEAM) W ROOF BENT C O (SEE PUN FOR SIZE) (5)-@14�' S.N.S. (EACH SIDE OF BEAM) W - � O Q U d 0) 0 VZ N W a HOST STRUCTURE ANCHORS U) Z W EQUALLY SPACED (TYP.) C C ULI Z R' O 0 ((\\ d (2) Y' 0 x 2Y• LONG WOOD LAG SCREW OR F 1 2' MIN. E wl (2) Y' 0 z 24' LONG MASONRY ANCHORS Q SPACED (TIP.) Z U HOST STRUCTURE (MASONRY OR WOOD) W _U fi O_ J W } U ❑ T- BEAM TO HOST STRUCTURE DETAIL DRAWN BY. DO YEON KIM, P.E. FLA, REG. NUMBER 49497 DO KIW&CLATES, LLC 8870039 Tampa, FL 33679 6,1-t I Drawing No. - 060811 SHEET 2OF2 I. �iia� ��sc a I I