EVALUATION REPORT
TRI-BUILT Materials Group, LLC
EXTERIOR RESEARCH & DESIGN, I.I.C.
Certificate ofAuthori2ation #9503
353 CHRISTIAN STREET, UNIT#13
OXFORD, CT 06478
(203)262-9245
Evaluation Report A42960.10.12-R6
PO Box 70 FL36048-116
Rutherford, NJ07070 Date of Issuance:10/2S/2012
(800) 516-1485 Revision 6: 09/2S/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the Gbh Edition (2017) Florida Building Code
sections noted herein.
DESCRIPTION: TRI-BUILT Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity) ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity IERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 6.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The halmge seal appearing waz authorized by Robert Nieminen,
P.E. on 09/25/201). This does not nerve asan eleamnizaily signed
document.
CERTIFICATION OF INDEPENDENCE:
1. Trinity[ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinity[ ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Underlayment
Compliance Statement: TRI-BUILT Roof Underlayments, as produced by TRI-BUILT Materials Group, LLC, have
demonstrated compliance with the following sections of the 6`h Edition (2017) Florida Building Code through testing
in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations /
Conditions of Use set forth herein.
2. STANDARDS:
Section
Property
Standard
Year
1504.3.1
Wind Resistance
FM 4474
2011
1504.3.1
Wind Uplift
UL 1897
2012
1504.6
Accelerated Weathering
ASTM G155
2005
1507.2.4 / 1507.1.1, 1507.2.9.2
Physical Properties
ASTM D1970
2015
1507.3.3
Physical Properties
FRSA/TRI April 2012 (04-12)
2012
3. REFERENCES:
Entity
Examination
Reference
Date
ERD (TST6049)
Physical Properties
540540.02.13-1
02/19/2013
ERD (TST6049)
Physical Properties
540540.11.13
11/19/2013
ERD (TST6049)
Physical Properties
540540.03.14
03/26/2014
ERD (TST6049)
Physical Properties
S44870.04.14-2
04/02/2014
ERD (TST6049)
Physical Properties
544870.04.14-3
04/02/2014
ERD (TST6049)
Physical Properties
S44870.04.14-1
04/10/2014
ERD (TST6049)
Physical Properties
S44870.04.14-4
04/10/2014
ERD (TST6049)
Physical Properties
S43530.02.14-1-R1
05/14/2014
ERD (TST6049)
Physical Properties
S43530.05.14
05/28/2014
ERD (TST6049)
Physical Properties
S40540.30.14
10/31/2014
ERD (TST6049)
Physical Properties
SC7645.02.15
02/13/2015
ERD (TST6049)
Accelerated Weathering
SC8520.04.15
05/27/2015
ERD (TST6049)
Wind Resistance
SC14045.05.17-R1
06/07/2017
UL, LLC. (QUA9625)
Quality Control
Multiple -Listing R16814
12/10/2015
UL, LLC. (QUA9625)
Quality Control
Service Confirmation
Exp. 07/18/2020
4. PRODUCT DESCRIPTION:
4.1 Tri-Built Sand-R SA Shingle Underlayment is a self -adhering, glass -mat reinforced, sand -surfaced, SBS
modified bitumen roof underlayment, with a 36-inch sheet width; meets ASTM D1970.
4.2 Tri-Built S/A HT TU Underlayment is a self -adhering, non -woven polyester fabric surfaced, SBS modified
bitumen roof underlayment; meets ASTM D1970 and FRSA/TRI April 2012.
4.3 Tri-Built Smooth HT S/A Underlayment is a self -adhering, glass -mat reinforced, film -surfaced, SBS
modified bitumen roof underlayment; meets ASTM D1970.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity) ERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials
Directory for fire ratings of this product.
Exterior Research and Design, U.C. Evaluation Report A42960.10.12-R6
Certificate oJAuthorkation rl9503 6r" EDITION (2017) FBC NON-HVHZ EVALUATION F1.36048-R6
TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6: 09/25/2017
Page 2 of 6
5.4 TRI-BUILT Roof Underlayments may be used with any prepared roof cover where the product is
specifically referenced within FBC approval documents. If not listed, a request may be made to the
Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the
prepared roof covering.
5.5 Allowable Roof Covers:
'TABLE I: ROOFC0VEROPTION5 -
Underlayment
Asphalt
Nail -On Tile
Foam -On Tile
Metal
Wood Shakes
Slate
Shingles
& Shingles
Tri-Built Sand-R SA Shingle
yes
No
No
No
Yes
Yes
Underlayment
Tri-Built S/A HTTU
Yes
Underlayment
Yes
Yes
See 5.5.1
Yes
Yes
Yes
Tri-Built Smooth HT S/A
Underlayment
Yes
No
No
Yes
Yes
Yes
5.5.1 "Foam -On Tile" is limited to use of the following Approved tile adhesives / underlayment combinations.
- TABLE 1A: ALLOWABLE TILE ADHESIVE/ UNDERLAYMENT COMBINATIONS1 a
Adhesive
Florida Product Approval
Underlayments
ICP Adhesives Polyset® AH-160
FL6332
Tri-Built S/A HT TU Underlayment
Dow TileBond'"
FL22525
Tri-Built S/AHTTU Underlayment
5.6 Allowable Substrates:
5.6.1 Direct -Bond to Deck:
Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
➢ Plywood; ASTM D41 primed plywood; OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41
primed Southern Yellow Pine; ASTM D41 primed structural concrete.
While not required over plywood, OSB or Southern Yellow Pine substrates, TRI-BUILT Materials Group, LLC
recommends priming the deck if the final roof cover is not slated for installation within 24 hours. Note:
TRI-BUILT Materials Group, LLC requires tongue -and -groove board decking be covered with plywood or
OSB prior to installation of the self -adhering underlayment.
5.6.2 Bond -to -Insulation:
Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
➢ Dens Deck Prime; SECUROCK Gypsum -Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per
minimum requirements of the prepared roof covering manufacturer's Product Approval. For installations
under foam -on tile systems (Tri-Built S/A HT TU Underlayment only), insulation attachment shall be
designed by a qualified design professional and installed based on testing of the insulation/underlayment
system in accordance with FM 4474, Appendix D orTAS 114, Appendix J.
' Refer to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
Exterior Research and Design, I.I.C. Evaluation Report A42960.10.12-R6
Certificate ofAuthoritation#9503 e EDITION (2017) FBC NON-HVHZ EVALUATION FL16048-RG
TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6: 09/25/2017
Page 3 of 6
TRINITY ERD
5.6.3 Bond to Mechanically Attached Base Laver:
Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment or Tri-Built Smooth HT S/A
Underlayment applied to:
D ASTM D226, Type I or II felt.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per
minimum codified requirements. For installations under foam -on tile systems (Tri-Built S/A HT TU
Underlayment only), base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04-
12).
5.6.4 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12)
does not address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where
the underlayment forms part of the load -path. The following wind uplift limitations apply to direct -deck
underlayment systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile
applications. Maximum Design Pressure is the result of testing for wind load resistance based on
allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety
per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-12), Appendix A, Table 3A or
FBC 1609 for determination of design wind pressures.
#1 Maximum Design Pressure=-45.0 Dsf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Primer: (Optional) ASTM D41 or RESISTO EXTERIOR PRIMER
Underlayment: Tri-BuiltS/A HTTU Underlayment, self -adhered.
#2 Maximum Design Pressure=-67.5 psf:
Deck: Structural concrete to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Primer: Soprema Elastocol 600c
Underlayment: Tri-BuiltS/A HTTU Underlayment, self -adhered.
#3 Maximum Design Pressure = -150.0 Dsf:
Deck:
Min. 15/32-inch APA-rated BCX plywood (may be installed C-side up) to meet project
requirements to satisfaction of Authority Having Jurisdiction.
Deck Preparation:
Plywood shall be thoroughly cleaned to remove dust and debris that may inhibit
adhesion. All sheathing fasteners shall be driven flush with the surface. All sharp
splinters and wood projections shall be removed/sanded.
Primer:
(Optional) RESISTO EXTERIOR PRIMER
Underlayment:
Tri-Built S/A HT TU Underlayment, self -adhered, shall be thoroughly roll using hand
roller and/or weighted roller to ensure there are no voids, and ensure there are no
voids/bridging at side and end -laps.
#4 Maximum Design Pressure=-60.0 Dsf:
Deck:
Min. 19/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Base Sheet:
Soprema Sopra-G or Modified Sopra-G mechanically attached with nails (FBC 1517.5.1)
and tin caps (FBC 1517.5.2) spaced 6-inch o.c. at the 4-inch laps and 6-inch o.c. in three,
equally spaced rows in the center of the sheet.
Underlayment:
Tri-BuiltS/A HT TU Underlayment, self -adhered.
Exterior Research and Design, LLC. Evaluation Report A42960.10.12-R6
Certificate cfAuthoritation #9503 6T" EDITION (2017) FBC NON-HVH2 EVALUATION FL36048-RG
TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6: 09/25/2017
Page 4 of 6
"� INITY ERD
5.6.4.1 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet
or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1
design pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an
attachment density designed by a qualified design professional to resist the elevated pressure criteria.
Commonly used methods are ANSI/SPRI WD3, FM Loss Prevention Data Sheet 1-29 and Roofing
Application Standard RAS 117. Assemblies marked with an asterisk" carry the limitations set forth in
Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements.
5.7 Exposure Limitations:
Tri-Built Sand-R SA Shingle Underlayment or Tri-Built Smooth HT S/A Underlayment shall not be left
exposed for longer than 30-days after installation
Tri-Built S/A HTTU Underlayment shall not be left exposed for longer than 180-days after installation.
5.8 Tile Slippage Limitations RAS 103 per FRSA/TRI April 2012 (04-12)):
When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall
be as follows. These slope limitations can only be exceeded by using battens during loading of the roof
tiles.
TABLE Z;-TILESLIPPAGE.LIMITATIONS FOR DIRECT
-DECK TILE INSTALLATIONS
Underlayment
Tile Profile
Staging Method
Maximum
Slope
Flat
Max. 10-tile stack
6:12
Lugged
Max. 10-tile stack
5:12
Max. 10-tile stack (bottom 2-tile stack
shall be inverted, followed by 8 tiles high
6:12
on slope, as shown below)
Tri-Built S/A HT TU
Underlayment
Lugged
Exterior Research and Design, U.C. Evaluation Report A42960.10.12-R6
Certificate ofAuthorization#9503 6'"EDITION (2017)FBC NON-HVHZ EVALUATION FL1604&R6
TRI-BUILT Roof Underiayments; (800) 516-140S Revision 6: 09/25/2017
Page 5 of 6
\t I RINITif ERD
6. INSTALLATION:
6.1 TRI-BUILT Roof Underlayments shall be installed in accordance with TRI-BUILT Materials Group, LLC
published installation requirements subject to the Limitations set forth in Section 5 herein and the
specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly
to remove any dust and debris prior to application, and prime the substrate (if applicable).
6.3 Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underla iment or Tri-Built Smooth HT S/A
Underlayment:
6.3.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
6.3.2 Non -Tile applications:
While priming is optional, TRI-BUILT Materials Group, LLC recommends priming the deck if the final roof
cover is not slated for installation within 24 hours.
Apply sheet parallel to the roof edge. Roll out approximately 10 ft of membrane and peel back the first 3
ft of release film.
Adhere the exposed part to the substrate and unroll the remaining membrane as far as possible.
Once the entire length of membrane is in place, peel -off the release film diagonally while holding the
membrane tight. Firmly roll, broom or hand -press the membrane into place to achieve a bond.
Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6-
inches and staggered not less than 2-ft from vertical seams in the course below, sealed in accordance with
TRI-BUILT Materials Group, LLC requirements.
When installing at slopes above 8:12, TRI-BUILT Materials Group, LLC recommends back -nailing in the
overlap area at the top of the sheet at 12-inch o.c.
For Valleys and Ridges: Cut underlayment into 4 to 6 foot lengths. Peel the release paper and center sheet
over valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge in
each direction. For valleys, apply the sheet starting at the lowest point and work upward.
6.3.3 Tile Applications (Tri-Built S/A HT TU Underlayment only):
Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the
instructions noted above as a guideline.
For foam -on tile applications, reference is made to Section 5.6.4 herein for wind resistance limitations that
fall outside the scope of FRSA/TRI April2012 (04-12).
Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the
underlayment. See Table 2 herein, and TRI-BUILT Materials Group, LLC published requirements for tile
staging.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
8. MANUFACTURING PLANTS:
Gulfport, MS
9. QUALITY ASSURANCE ENTITY:
UL, LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com
- END OF EVALUATION REPORT -
Exterior Research and Design, U.C. Evaluation Report A42960.10.12-R6
Cert(f,cate of Authorization a9SO3 6`H EDITION (2017) FBC NON-HVHZ EVALUATION FL16048-RG
TRI-BUILT Roof Underlayments; (800) 516-1485 Revision 6: 09/25/2017
Page 6 of 6
SCANNED
rTRINITYIERD
( BY
EVALUATION REPORT St. Lucie County
EXTERIOR RESEARCH & DESIGN, LLC.
Certificate of Authorization #9503
353 CHRISTIAN STREET, UNIT#13
OXFORD, CT 06479
(203)262-9245
Owens Corning: �--;r Evaluation Report 037940.02.12-118
One1Owens Corning Oii:L y��"--� � �-- FL10674-R13
oIT ed OH 43659 Date of Issuance: 02/06/2012
(740) 404-7829 Revision 8: 10/09/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building —Code _fIesidentlal Volume The
products described herein have been evaluated for compliance with the 6u'' dition-(20,17_)IFI B i)ding Code
sections noted herein. `
DESCRIPTION: Owens Corning Asphalt Roof Shingles
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein and FBC 1507.2.7.1 / R905.2.6.1.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the
referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change.
Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the
product changes or the referenced Quality Assurance documentation changes. TrinitylERD requires a complete
review of this Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinityl ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through B.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert
Nieminen, P.E. on 10/09/2017. This does not some as an
electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. TrinitylERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. TrinitylERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
FYD
jNITY j ERD
I
5.4 Wind Classification:
5.4.1 All Owens Corning asphalt shingles noted herein are Classified in accordance with FBC Tables 1507.2.7.1
and R905.2.6.1 to ASTM D3161, Class F and/or ASTM D7158, Class H, indicating the shingles are acceptable
for use in all wind zones up to Va,d = 150 mph (V„„ = 194 mph). Refer to Section 6 for installation
requirements to meet this wind rating.
5.4.2 All Owens Corning hip & ridge shingles, Starter Strip Shingle and Starter Strip Plus noted herein are
Classified in accordance with FBC Tables 1507.2.7.1 and R905.2.6.1 to ASTM D3161, Class F, indicating the
shingles are acceptable for use in all wind zones up to Vs,d = 150 mph (VI, = 194 mph). Refer to Section 6 for
installation requirements to meet this wind rating.
5.4.3 Classification by ASTM D7158 applies to exposure category B or C, as defined in FBC 1609.4.3, and a mean
roof height of 60 feet or less. Calculations by a qualified design professional are required for conditions
outside these limitations. Contact the shingle manufacturer for data specific to each shingle.
5.4.4 Refer to Owens Corning published information on wind resistance and installation limitations.
5.5 All products in the roof assembly shall have quality assurance audit in accordance with F.A.C. Rule 61G20-3.
6. INSTALLATION:
6.1 Underlavment:
6.1.1 Underlayment shall be acceptable to Owens Corning and shall hold current Florida Statewide Product
Approval, or be Locally Approved per Rule 611320-3, per FBC 1507.2.3, 1507.2.4 or R905.2.3.
6.2 Asphalt Shingles:
6.2.1 Installation of asphalt shingles shall comply with the Owens Corning current published instructions, using
minimum four (4) nails per shingle in accordance with FBC 1507.2.7 or R905.2.6, with the following
exceptions:
➢ Berkshire shingles require minimum five (5) nails per shingle.
➢ WeatherGuard HP shingles require minimum six (6) nails per shingle.
➢ Devonshirers' shingles require minimum six (6) nails per shingle.
➢ Starter Strip Shingle and Starter Strip Plus require minimum five (5) nails per strip.
Refer to Owens Corning published information on wind resistance and installation limitations.
6.2.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.2.4 Where the roof slope exceeds 21 units vertical in 12 units horizontal, special methods of fastening are
required. See figures below for details.
6.2.5 Minimum Nailing —Starter Strip Shingle and Starter Strip Plus:
Felt undedayment Deck
ered
Mathlac
underkryment
Drip—
Drip edge
9e
NAslecated
2° 3' from eays
Install first
Starter Strip
SeB�seeefing adhesive
shingle Vd
.� positioned along gave
.s
\
g'removed
Starter Snip shingle overhangs eaves and rakes h� -514'
Exterior Research and Design, U.C.
Certifie#te of Authorhation#9503 e'EDITION (2017)FBC NON-HVHZ EVALUATION
Owens Corning Asphalt Roof Shingles
SW.dh.M
weadxdoetU
ureledevnern
Ssxuxing ad6ewe
paAtloned abigem
Evaluation Report 037940.02.12-R8
FL10674-R13
Revision 8: 10/09/2017
Page 3 of 8
6.2.6 Minimum Nailing —Classic®&Supreme:
%4orenal Monsard or At" paw
yBrnl Ara r, Xt9h Wind ifaavanea y
Ater pnw riBntde n8rmelBa =8 vieMios fuema
mot• r
ll
Fttyoahidn
6.2.7 Minimum Nailing —Berkshire°:
Seahrn�rip
1athada sa5da
taat�ttt�r _
Standard Fastening Pattern
Normal aaaoit" or Ants pare.
Wind Aram High Wind' das"noury
Area Para visor" na atatao Areas. 'vient" fawrea:
` t r z• IB .p.
zt t
pah8 Eepoaure'
'Fnposholda
SeatiNsMp _
La ad8ffihda.
Mansard or Steep Slope Fastening Pattern
S.I.Mstrip
tatiradexaadw
Aa SW" lasr ' at2• .
r
6-Nail Fastening Pattern
Exterior Research and Design, U.C. Evaluation Report 037940.02.12-R8
Certificate of Authorization #9503 6'" EDITION (2017) FBC NON-HVHZ EVALUATION FL10574-R13
Owens Corning Asphalt Roof Shingles Revision 8:10/09/2017
Page 4 of 8
t
6.2.8 Minimum Nailing—Devonshirem:
Uposlcldndetiaidpu18 Ublmddndel sellador
i t KINITY ERD
i
Standard 6-Nail Fastening Pattern Mansard or Steep Slope Fastening Pattern
6.2.9 Minimum Nailing — Duration®, TruDefinition�Duration, Duration® Premium Cool & TruDefinition
Duration Designer Color Collection:
snwaaar�m�mawmm
Standard Fastening Pattern
'r»tenlne for Slop" Greater Thep 2f:f2
bma"aHSus4rtnevaa»
xarr,k,i
fY 1Y
61M SSW
..1!
rmrpwm�uwaeoomp rm.x
Mansard or Steep Slope Fastening Pattern
Exterior Research and Design, LLC. Evaluation Report 037940.02.12-RB
Certificate ofAuthorhation 1195a3 6r"EDITION(2017)FBC NON-HVHZ EVALUATION F1.10674-1113
Owens Corning Asphalt Roof Shingles Revision 8: 10/09/2017
Page 5 of 8
6.2.1 Minimum Nailing—TruDefinition"OakridgeO, OakridgeO:
4 Nail PaRom
&spina con 4lows
d<— r ►I I<— it —sl
66/0"ExPosure. rum 660 Expsure�
EryMIN6ide 3S�8DdB C40W Exwgddn do 6Gig pdg.
Standard Fastening Pattern
ea.r•s�me.
6 Nail Pattoin
Esauema tots daLros
Mansard or Steep Slope Fastening Pattern
6.2.1 Minimum Nailing — WeatherGuardO HP:
�1 TRINITY ERD
rc '
66i4'.:Expaemla�,
'EVgsimdn de 661Bpd0..
6-Nail Fastening Pattern
•Inpb'"V4wt
hrftmf
Exterior Research and Design, U.C. Evaluation Report 037940.02.12-Rg
CeHilcote oJAuthorizadon R9503 61°EDITION(2017)FBC NON-HVHZ EVALUATION F110674-R13
Owens Corning Asphalt Roof Shingles Revision 8: 10/09/2017
Page 6 of 8
QOTRIN-ITYIERD
6_3 Hip .&.RidjWSM gl4 s:
6.3.1 Installation of Berkshire Hip and Ridge Shingles, High Ridge, WeatherGuard HP Hip and Ridge Shingles
and (Pr, oEdge,Hip'&, Ridge 3hingleVshal comply with the Owens Corning current published instructions,
using four (4) nails per rr shingle. Installation of CluraRidge'' Hip & Ridge Shingles shall comply with the
Owens Corning current published instructions, using two (2) nails per shingle. Refer to Owens Corning
published information on wind resistance and installation limitations, including the.use of hand -sealing for
wind warranties.
6.3.2 Fasteners shall be in accordance with the manufacturer's published requirements, but not less than FBC
1507.2.6 or R905.2.5. Staples are not permitted.
6.3.3 Minimum Nailing — Berkshire® Hip & Ridge and High Ridge:
jt_.: PRVu6i9KTd �
� roedwn �. c A I
r
I
I , I r
6.3.4 Minimum Nailing — WeatherGuard® HP Hip and Ridge:
Fig.A
t— tC,ectbn
cre 27tW
'..
�s _y
�� �\ ESp0.ture
Fig. G Hipp& Ridge Shinglg-Easienih
TopVhs-
�I
1
thiG Haile
I
� FSporure-------------------
Exterior Research and Design, U.C. Evaluation Report 037940.02.12-Rg
Certifimte of Authonz&ion#9503 6T"EDITION (2017)FBC NON-HVHZ EVALUATION FL10674-1113
Owens Corning Asphalt Roof Shingles Revision 8: 10/09/2017
Page 7 of 8
6.3.5 Minimum Nailing - ProEdge Hip & Ridge Shingles:
Prevailing
Wind Direction Sealant Strip
,ram 6-Exposure
C,5
Fasten 71h'M
Cam Exposed
Fosteoers with
:,- Rost cement
Standard wit•
Fastening
Pattern
12Sealant
.� 6° Expos
6.3.6 Minimum Nailing— DuraRidgenz Hip & Ridge Shingles:
Note: The drawings below pertain to minimum, as -tested attachment requirements. Refer to Owens Corning
published installation instructions for their minimum requirements.
Toot
v esera,
Vhtauperiat
7. LABELING:
7.1 Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
7.2 Asphalt shingle wrappers shall indicate compliance with one of the required classifications detailed in FBC
Table 1507.2.7.1 / R905.2.6.1.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
9. MANUFACTURING PLANTS:
Contact the named QA entity for information on which plants produce products covered by Florida Rule 9N-3 CIA
requirements.
10. QUALITY ASSURANCE ENTITY:
UL LLC— QUA9625 ; (631) 546-2458; Kanchi.Agrawala-Dokania@ul.com
- END OF EVALUATION REPORT -