HomeMy WebLinkAboutSPRINKLER PAPERWORKAutomatic Fire Sprinklers, Inc.
SCANNED
BY
St. Lucie Countv
Hydraulic Calculations
Wayne Automatic
Fire Sprinklers, Inc.
1500 S. Powerline Rd Unit A
Deerfield Beach, Florida 3344
954-917-3030
Job Name
Avalon Lot #6
Sheet Number
FP-3
Location
Ocean Estates Drive —Lot #6
Design Area
AREA #1
Contract
#95690
Data File
Area #1.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Wayne Automatic
Avalon Lot #6
Page 1
Date 6/7/2019
HYDRAULIC CALCULATIONS
for
Project name: Avalon
Location: Ocean Estates Drive —Lot #6
Drawing no: FP-3
Date: 6f7/2019
Design
Remote area number. AREA #1
Remote area location:, 2nd Floor Bedroom #2
Occupancy -classification: R-3
Density: .05=;Gpm/SgFt
Area of applicatiS)'Y it Head Desig - SgFt
Coverage per sprinkler. 400 - SgFt
Type of sprinklers calculated., Reliable (R3516) Semi -Recessed White Pendent
No. of sprinklers calculated. 1
In -rack demand: N/A - GPM
Hosestreams: -GPM
Total water required (including hose streams): 20.0 - GPM @ 54.7 - Psi
Type of system: Wet (NFPA 13D)
Volume of dry or preaction system: N/A - Gal
Water supply information
Date: 6/5/2019
Location: Ocean Estates Drive & A1A Blvd
Source: St. Lucie County Utlities
Name of contractor. Wayne Automatic Fire Sprinklers, Inc.
Address: 1500 S. Powerline Rd_Unit A Deerfield Beach, Florida 33442
Phone number: 954-917-3030
Name of designer. Michael Crawford
Authority havingjurisdiction: St. Lucie County
Notes: (Include peaking information for gridded systems here.)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
Wayne Automatic
Avalon Lot #6
Page 2
Date 6/7/2019
City Water Supply: Demand:
C1 - Static Pressure 65 D1 - Elevation 7.579
C2 - Residual Pressure: 25 D2 - System Flow : 20.024
C2 - Residual Flow 780 D2 - System Pressure 54.654
Hose (Demand)
D3 - System Demand : 20.0 44
Safety Margin 10.300
150
140
130
p 120
R 110
E 100
S 90
S 80
U 70
R 60
E 50
40
30
20
10
D1
100 200 300 400 500 600 700 800 900
FLOW (NA1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
Wayne Automatic Page 3
Avalon Lot #6 Date 6/7/2019
Fitting Legend
Abbrev. Name
% '/. 1 1% 1% 2
2%
3
3%
4
5
6
8
10
12
14
16
18
20
24
E
90' Standard Elbow
2 2 2 3 4 5
6
7
8
10
12
14
18
22
27
35
40
45
50
61
G
Generic Gate Valve
0 0 0 0 0 1
1
1
1
2
2
3
4
5
6
7
8
10
11
13
T
90' Flow Thru Tee
3 4 5 6 8 10
12
15
17
20
25
30
35
50
60
71
81
91
101
121
u*
CPVC 90' Elbow Tyco
0 4 5 6 7 9
12
13
0
0
0
0
0
0
0
0
0
0
0
0
v.
CPVC Tee Branch Tyco
0 3 5 6 8 10
12
15
0
0
0
0
0
0
0
0
0
0
0
0
Zig
Wilkins 375DA
Fitting generates a Fixed Loss Based on Flow
Zik
Wilkins 950XL
Fitting generates a Fixed Loss Based on Flow
Units Summary
Diameter Units
Inches
Length Units
Feet
Flow Units
US Gallons per Minute
Pressure Units
Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
Wayne Automatic
Avalon Lot #6
Page 4
Date 6/7/2019
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Reg.
s1
20.0 4.9
16.7 na
1
21.0
17.32 na
200
21.0
19.28 na
201
21.0
20.26 na
102
12.0
26.88 na
103
12.0
27.66 na
TR
12.0
28.59 na
BR
-2.5
41.35 na
UG2
-2.5
42.56 na
BF2
3.0
40.23 na
BF1
-2.5
53.63 na
UG7
-2.5
53.68 na
TEE
-2.5
56.82 na
TEST
2.5
54.65 na
20.02 0.05 400 16.7
The maximum velocity is 10.71 and it occurs in the pipe between nodes S1 and 1
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen -Williams
Wayne Automatic
Avalon Lot #6
Page 5
Date 6/7/2019
Hyd.
Qa Dia.
Fitting
Pipe
Pt
Pt
Ref.
..C.,
or
Ftng's
Pe
Pv `*`**'* Notes
Point
Qt Pf/Ft
Eqv. Ln.
Total
Pf
Pn
S1
20.02
0.874
U
4.0
1.000
16.700
K Factor = 4.90
to
150.0
0.0
4.000
-0.433
1
20.02
0.2100
0.0
5.000
1.050
Val = 10.71
0.0
20.02
17.317
K Factor = 4.81
1
20.02
0.874
V
3.0
6.333
17.317
to
150.0
0.0
3.000
0.0
200
20.02
0.2099
0.0
9.333
1.959
Val = 10.71
200
0.0
0.874
V
3.0
1.667
19.276
to
150.0
0.0
3.000
0.0
201
20.02
0.2100
0.0
4.667
0.980
Vel = 10.71
201
0.0
0.874
V
3.0
10.000
20.256
to
150.0
0.0
3.000
3.898
102
20.02
0.2099
0.0
13.000
2.729
Val = 10.71
102
0.0
1.101
0.0
11.333
26.883
to
150.0
0.0
0.0
0.0
103
20.02
0.0682
0.0
11.333
0.773
Val = 6.75
103
0.0
1.101
U
5.0
8.667
27.656
to
150.0
0.0
5.000
0.0
TR
20.02
0.0682
0.0
13.667
0.932
Val = 6.75
TR
0.0
1.101
Zik
0.0
10.000
28.588
to
150.0
0.0
0.0
12.080
' ' Fixed Loss = 5.8
BR
20.02
0.0681
0.0
10.000
0.681
Val = 6.75
BR
0.0
1.598
3U
21.0
80.000
41.349
to
150.0
V
8.0
29.000
0.0
UG2
20.02
0.0111
0.0
109.000
1.212
Vel = 3.20
UG2
0.0
2.067
E
5.0
6.000
42.561
to
120.0
0.0
5.000
-2.382
BF2
20.02
0.0047
0.0
11.000
0.052
Vel = 1.91
BF2
to
BF1
0.0
20.02
2.067
120.0
0.0048
E
Zig
5.0
0.0
0.0
6.000
5.000
11.000
40.231
13.342
0.053
* * Fixed Loss = 10.96
Val = 1.91
BF1
0.0
2.067
E
5.0
6.000
53.626
to
120.0
0.0
5.000
0.0
UG1
20.02
0.0048
0.0
11.000
0.053
Val = 1.91
UG1
0.0
1.827
G
0.828
15.000
53.679
to
150.0
T
8.284
9.112
3.000
` ` Fixed Loss = 3
TEE
20.02
0.0058
0.0
24.112
0.139
Vel = 2.45
TEE 0.0 6.34 2E 46.217 25.000 56.818
to 140.0 0.0 46.217 -2.166
TEST 20.02 0.0 0.0 71.217 0.002 Val = 0.20
0.0
20.02 54.654 K Factor = 2.71
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
i
Automatic Fire Sprinklers, Inc.
Hydraulic Calculations
Wayne Automatic
Fire Sprinklers, Inc.
1500 S. Powerline Rd Unit A
Deerfield Beach, Florida 3344
954-917-3030
Job Name
Avalon Lot 96
Sheet Number
FP-3
Location
Ocean Estates Drive —Lot #6
Design Area
AREA #2
Contract
#95690
Data File
Area #2.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Wayne Automatic
Avalon Lot #6
Page 1
Date 6f7/2019
HYDRAULIC CALCULATIONS
for
Project name: Avalon
Location: Ocean Estates Drive —Lot #6
Drawing no: FP-3
Date: 6/7/2019
Design
Remote area number: AREA #2
Remote area location: Kitchen
Occupancy classification: R-3
Density. .05 - Gpm/SgFt
Area of application: 2 Head Desig - SgFt
Coverage per sprinkler. 324 - SgFt
Type of sprinklers calculated: Reliable (R3516) Semi -Recessed White Pendent
No. of sprinklers calculated: 2
In -rack demand: N/A -GPM
Hose streams: -GPM
Total water required (including hose streams): 34.5 - GPM @ 59.3 -Psi
Type of system: Wet (NFPA 13D)
Volume of dry or preaction system: N/A - Gal
Water supply information
Date: 6/5/2019
Location: Ocean Estates Drive & A1A Blvd
Source: St. Lucie County Utlities
Name of contractor: Wayne Automatic Fire Sprinklers, Inc.
Address: 1500 S. Powerline Rd_Unit A Deerfield Beach, Florida 33442
Phone number: 954-917-3030
Name of designer. Michael Crawford
Authority having jurisdiction: St. Lucie County
Notes: (Include peaking information for gridded systems here.)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
Wayne Automatic
Avalon Lot #6
Page 2
Date 6/7/2019
City Water Supply: Demand:
C1 - Static Pressure 65 D1 - Elevation 3.681
C2 - Residual Pressure: 25 D2 - System Flow : 34.506
C2 - Residual Flow 780 D2 - S stem Pressure 59.317
Hose IS
D3 - System Demand : 34.506
Safety Margin 5.558
150
140
130
p 120
R 110
E 100
S 90
S 80
U 70
R 60
E 50
40
30
20
10
100 200 300 400 500 600 700 800 900
FLOW N^1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
Wayne Automatic Page 3
Avalon Lot #6 Date 6/7/2019
Fitting Legend
Abbrev. Name Y 3/1 1% 1'/: 2 2%a 3 3% 4 5 6 8 10 12 14 16 18 20 24
E
90' Standard Elbow
2 2 2 3 4 5
6
7
8
10
12
14
18
22
27
35
40
45
50
61
G
Generic Gate Valve
0 0 0 0 0 1
1
1
1
2
2
3
4
5
6
7
8
10
11
13
T
90' Flow Thru Tee
3 4 5 6 8 10
12
15
17
20
25
30
35
50
60
71
81
91
101
121
u.
CPVC 90' Elbow Tyco
0 4 5 6 7 9
12
13
0
0
0
0
0
0
0
0
0
0
0
0
V•
CPVC Tee Branch Tyco
0 3 5 6 8 10
12
15
0
0
0
0
0
0
0
0
0
0
0
0
Zig
Wilkins 375DA
Fitting generates a Fixed Loss Based on Flow
Zik
Wilkins 950XL
Fitting generates a Fixed Loss Based on Flow
Units Summary
Diameter Units
Inches
Length Units
Feet
Flow Units
US Gallons per Minute
Pressure Units
Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
Wayne Automatic
Avalon Lot #6
Page 4
Date 6/7/2019
Node
No.
Elevation
K-Fact
Pt
Actual
Pn
Flow
Actual
Density
Area
Press
Reg.
S2
11.0
4.9
12.0
na
16.97
0.05
324
12.0
S3
10.0
4.9
12.8
na
17.53
0.05
324
12.0
3
12.0
12.76
na
2
12.0
12.34
na
100
12.0
14.02
na
101
12.0
21.58
na
102
12.0
22.17
na
103
12.0
24.29
na
TR
12.0
26.84
na
BR
-2.5
41.92
na
UG2
-2.5
45.23
na
BF2
3.0
43.0
na
BF1
-2.5
57.95
na
UG1
-2.5
58.1
na
TEE
-2.5
61.48
na
TEST
2.5
59.32
na
The maximum velocity is 18.45 and it occurs in the pipe between nodes 100 and 101
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen -Williams
Wayne Automatic
Avalon Lot #6
Page 5
Date 6/7/2019
Hyd.
Oa Dia.
Fitting
Pipe
Pt
Pt
Ref.
"C"
or
Ftng's
Pe
Pv **•*' • Notes •'*`**
Point
Qt Pf/Ft
Eqv. Ln.
Total
Pf
Pn
S2
16.97
0.874
U 4.0
1.000
12.000
K Factor = 4.90
to
150.0
0.0
4.000
-0.433
2
16.97
0.1546
0.0
5.000
0.773
Vel = 9.08
0.0
16.97
12.340
KFactor= 4.83
S3
17.53
0.874
V 3.0
2.000
12.802
K Factor = 4.90
to
150.0
0.0
3.000
-0.866
3
17.53
0.1642
0.0
5.000
0.821
Vel = 9.37
0.0
17.53
12.757
K Factor = 4.91
3
17.53
0.874
V 3.0
4.667
12.757
to
150.0
0.0
3.000
0.0
100
17.53
0.1641
0.0
7.667
1.258
Val = 9.37
0.0
17.53
14.015
K Factor = 4.68
2
16.97
0.874
0.0
10.833
12.340
to
150.0
0.0
0.0
0.0
100
16.97
0.1546
0.0
10.833
1.675
Vel =
9.08
100
17.54
0.874
V
3.0
10.167
14.015
to
150.0
0.0
3.000
0.0
101
34.51
0.5745
0.0
13.167
7.565
Vel =
18.45
101
0.0
1.101
0.0
3.167
21.580
to
150.0
0.0
0.0
0.0
102
34.51
0.1866
0.0
3.167
0.591
Val =
11.63
102
0.0
1.101
0.0
11.333
22.171
to
150.0
0.0
0.0
0.0
103
34.51
0.1866
0.0
11.333
2.115
Val =
11.63
103
0.0
1.101
U
5.0
8.667
24.286
to
150.0
0.0
5.000
0.0
TR
34.51
0.1867
0.0
13.667
2.551
Vel =
11.63
TR
0.0
1.101
Zik
0.0
10.000
26.837
to
150.0
0.0
0.0
13.216
• Fixed Loss = 6.936
BR
34.51
0.1866
0.0
10.000
1.866
Vel =
11.63
BR
0.0
1.598
3U
21.0
80.000
41.919
to
150.0
V
8.0
29.000
0.0
UG2
34.51
0.0304
0.0
109.000
3.315
Val =
5.52
UG2
0.0
2.067
E
5.0
6.000
45.234
to
120.0
0.0
5.000
-2.382
BF2
34.51
0.0132
0.0
11.000
0.145
Vel =
3.30
BF2
0.0
2.067
E
5.0
6.000
42.997
to
120.0
Zig
0.0
5.000
14.812
* • Fixed Loss = 12.43
BF1
34.51
0.0131
0.0
11.000
0.144
Vel =
3.30
BF1
0.0
2.067
E
5.0
6.000
57.953
to
120.0
0.0
5.000
0.0
UG1
34.51
0.0131
0.0
11.000
0.144
Vel =
3.30
UG1
0.0
1.827
G
0.828
15.000
58.097
to
150.0
T
8.284
9.112
3.000
* Fixed Loss = 3
TEE
34.51
0.0158
0.0
24.112
0.382
Vel =
4.22
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen -Williams
Wayne Automatic
Page
6
Avalon Lot #6
Date
6/7/2019
Hyd. Qa
Dia.
Fitting
Pipe
Pt Pt
Ref.
"G.
or
Ftng's
Pe Pv
*"'***
Notes
Point Qt
Pf/Ft
Eqv. Ln.
Total
Pf Pn
TEE 0.0
6.34
2E 46.217
25.000
61.479
to
140.0
0.0
46.217
-2.166
TEST 34.51
0.0001
0.0
71.217
0.004
Vel = 0.35
0.0
34.51
59.317
KFactor=
4.48
Computer Programs by Hydratec Inc. Route I I I Windham N.H. USA 03087
Automatic Fire Sprinklers, Inc.
Hydraulic Calculations
Wayne Automatic
Fire Sprinklers, Inc.
1500 S. Powerline Rd Unit A
Deerfield Beach, Florida 3344
954-917-3030
Job Name
Avalon Lot #6
Sheet Number
FP-3
Location
Ocean Estates Drive —Lot #6
Design Area
AREA #3
Contract
#95690
Data File
Area #3.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Wayne Automatic Page 1
Avalon Lot #6 Date 6/7/2019
HYDRAULIC CALCULATIONS
for
Project name: Avalon
Location: Ocean Estates Drive —Lot #6
Drawing no: FP-3
Date: 6/72019
Design
Remote area number. AREA #3
Remote area location: Master Bedroom
Occupancy classification: R-3
Density: .05 - Gpm/SgFt
Area of application: 2 Head Desig - SgFt
Coverage per sprinkler. 256 - SgFt
Type of sprinklers calculated: Reliable (R3516) Semi -Recessed White Pendent
No. of sprinklers calculated., 2
In -rack demand: NIA -GPM
Hose streams: - GPM
Total water required (including hose streams): 35.0 - GPM @ 56.0 - Psi
Type of system: Wet (NFPA 13D)
Volume of dry or preaction system: N/A - Gal
Water supply information
Date: 6/5/2019
Location: Ocean Estates Drive & A1A Blvd
Source: St. Lucie County Utlities
Name of contractor. Wayne Automatic Fire Sprinklers, Inc.
Address: 1500 S. Powerline Rd —Unit A Deerfield Beach, Florida 33442
Phone number: 954-917-3030
Name of designer: Michael Crawford
Authority having jurisdiction: St. Lucie County
Notes: (Include peaking information for gridded systems here.)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
Wayne Automatic Page 2
Avalon Lot #6 Date 6/7/2019
City Water Supply: Demand:
Cl - Static Pressure 65 D1 - Elevation 3.537
C2 - Residual Pressure: 25 D2 - System Flow : 34.994
C2 - Residual Flow 780 D2 - System Pressure 56.035
Hose ( Demand)
D3 - System Demand : 34.994
Safety Margin 8.836
150
140
130
p 120
R 110
E 100
S 90
S 80
U 70
R 60
E 50
40
30
20
10
100 200 300 400 500 600 700 800 900
FLOW( NA1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
Wayne Automatic
Avalon Lot #6
Page 3
Date 6/7/2019
Fitting Legend
Abbrev. Name '/_ '% i 1'/. 1'/: 2 2% 3 3% 4 5 6 8 10 12 14 16 18 20 24
E
90' Standard Elbow
2 2 2 3 4 5
6
7
8
10
12
14
18
22
27
35
40
45
50
61
G
Generic Gate Valve
0 0 0 0 0 1
1
1
1
2
2
3
4
5
6
7
6
10
11
13
T
90' Flow Thru Tee
3 4 5 6 8 10
12
15
17
20
25
30
35
50
60
71
81
91
101
121
u'
CPVC 90' Elbow Tyco
0 4 5 6 7 9
12
13
0
0
0
0
0
0
0
0
0
0
0
0
V'
CPVC Tee Branch Tyco
0 3 5 6 8 10
12
15
0
0
0
0
0
0
0
0
0
0
0
0
Zig
Wilkins 375DA
Fitting generates a Fixed Loss Based on Flow
Zik
Wilkins 950XL
Fitting generates a Fixed Loss Based on Flow
Units Summary
Diameter Units
Inches
Length Units
Feet
Flow Units
US Gallons per Minute
Pressure Units
Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
Wayne Automatic
Page
4
Avalon Lot #6
Date
6/7/2019
Node Elevation K-Fact
Pt
Pn
Flow
Density
Area
Press
No.
Actual
Actual
Reg.
S4 10.667 4.4
13.3
na
16.05
0.05
256
13.3
S5 10.0 4.9
14.95
'na
18.95
0.05
256
7.0
4 12.0
14.62
na
5 12.0
15.03
na
103 12.0
20.78
na
TR 12.0
23.4
na
BR -2.5
38.53
na
UG2 -2.5
41.93
na
BF2 3.0
39.7
na
BF1 -2.5
64.66
na
_
UG1 -2.5
54.81
na
TEE -2.5
58.2
na
TEST 2.5
56.04
na
The maximum velocity is 11.79 and it occurs in the pipe between nodes 5 and 103
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen -Williams
Wayne Automatic
Avalon Lot #6
Page 5
Date 6/7/2019
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv .... Notes "•"•
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
S4 16.05 0.874 21_1 8.0 2.583 13.300 K Factor = 4.40
to 150.0 V 3.0 11.000 -0.577
4 16.05 0.1394 0.0 13.583 1.893 Val = 8.58
0.0
16.05
14.616
K Factor = 4.20
S5
18.95
0.874
V
3.0
2.000
14.952
K Factor = 4.90
to
150.0
0.0
3.000
-0.866
5
18.95
0.1896
0.0
5.000
0.948
Val = 10.13
0.0
18.95
15.034
K Factor= 4.89
4
16.05
0.874
0.0
3.000
14.616
to
150.0
0.0
0.0
0.0
5
16.05
0.1393
0.0
3.000
0.418
Val = 8.58
5
18.94
1.101
V
5.0
25.000
15.034
to
150.0
0.0
5.000
0.0
103
34.99
0.1915
0.0
30.000
5.746
Val = 11.79
103
0.0
1.101
U
5.0
8.667
20.780
to
150.0
0.0
5.000
0.0
TR
34.99
0.1916
0.0
13.667
2.618
VeI = 11.79
TR
0.0
1.101
Zik
0.0
10.000
23.398
to
150.0
0.0
0.0
13.216
` ` Fixed Loss = 6.936
BR
34.99
0.1915
0.0
10.000
1.915
VeI = 11.79
BR
0.0
1.598
31_1
21.0
80.000
38.529
to
150.0
V
8.0
29.000
0.0
UG2
34.99
0.0312
0.0
109.000
3.402
Val = 5.60
UG2
0.0
2.067
E
5.0
6.000
41.931
to
120.0
0.0
5.000
-2.382
BF2
34.99
0.0135
0.0
11.000
0.148
Val = 3.35
BF2
0.0
2.067
E
5.0
6.000
39.697
to
120.0
Zig
0.0
5.000
14.812
` ` Fixed Loss = 12.43
BF1
34.99
0.0135
0.0
11.000
0.149
Val = 3.35
BF1
0.0
2.067
E
5.0
6.000
54.658
to
120.0
0.0
5.000
0.0
UG1
34.99
0.0135
0.0
11.000
0.148
VeI = 3.35
UG1.
0.0
1.827
G
0.828
15.000
54.806
to
150.0
T
8.284
9.112
3.000
` • Fixed Loss = 3
TEE
34.99
0.0163
0.0
24.112
0.392
VeI = 4.28
TEE
0.0
6.34
2E
46.217
25.000
58.198
to
140.0
0.0
46.217
-2.166
TEST
34.99
0.0
0.0
71.217
0.003
VeI = 0.36
0.0
34.99
56.035
K Factor = 4.67
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
\V4gWA2Y2NrE
Automatic Fire Sprinklers, Inc.
PRODUCT DATA
SUBMITTALS
for
Avalon Lot #6
St. Lucie County, FL
WAFS JOB #95690
June 7, 2019
CONTENTS
1.
Sprinklers
2.
Pipe
3.
Fittings
4.
Hangers
5.
Miscellaneous
SCANNED
St. Lucie Coo*
WAYNE AUTOMATIC FIRE SPRINKLERS, INC.
1500 S. Powerline Road Suite A - Deerfield Beach, FL 33442
17 TEL (954) 9-3030 or FAX (954) 917-9424
Bulletin 135 Rev. J
i� Model F1
Residential Sprinklers for
labld Design Density of .05 gpmfft2
�„ Il�lbah.'1, c��.:RGF I ��� .
Il�odel 4 Res Slinnklers engineered for the lowest flows
to meet the minimum design density of .05 gpm/ftz
Types:
1. F1 Res 30 Pendent
2. F1 Res 30 Recessed Pendent/1`2
3. F1 Res 30 Recessed Pendent/FP
4. F1 Res 49 Pendent
5. F1 Res 49 Recessed PendenVF1
6. F1 Res 49 Recessed Pendent/FP
7. F1 Res 58 Pendent
8. F1 Res 58 Recessed Pendent/F1
9. F1 Res 58 Recessed Pendent/FP
10. F1 Res 76 Pendent
11. F1 Res 76 Recessed Pendent/F1
12. F1 Res 76 Recessed PendenVFP
13. F1 Res 30 CCP Pendent
14. F1 Res 49 CCP Pendent
15. F1 Res 58 CCP Pendent
16. F1 Res 76 CCP Pendent
17. F1 Res 44 HSW
18. F1 Res 44 Recessed HSW/F2
19. F1 Res 58 HSW
20. F1 Res 58 HSWX
21. KRes58 HSWX
22. F1 Res 58 HSW Recessed HSW/F2
23. F1 Res 44 SWC
(Ov I
F1 Res 30, 49,58 & 76
Recessed Pendent / F1
F1 Res 30, 49, 58 & 76
Recessed Pendent/FP
J■r
F1 Res 30, 49,58 & 76 F1 Res 44 & 58 F1 Res 44 SWC
CCP Pendent Recessed HSW/F2
Listings & Approvals
1. Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus)
2. NYC MEA 258-93-E
Slope Ceiling Approvals: Refer to Bulletin 035
Sprinklers for .10 Density: Refer to Bulletin 176
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents
US Patent No. 6,516,893 applies to the Model F1 Res 49
& 58 Pendent Sprinklers
US Patent No. 7,353,882 applies to Model F1 Res 44 & 58
HSW Sprinklers
US Patent No. 7,784,555 applies to Model F1 Res 44 SWC
Sprinklers
Product Description
Model F1 Res Pendent sprinklers (Figs. 1, 2, 3, & 4) are fast
response sprinklers combining excellent durability, high sensitiv-
ity glass -bulb and low profile decorative design. The F1 Res
Horizontal Sidewall sprinklers (Figs. 5, 6 & 7) are equally attrac-
tive when above ceiling piping cannot be used.
The 3mm glass -bulb pendent sprinklers permit the efficient use
of residential water supplies for sprinkler coverage in residential
fire protection design.
The low flow F1 Res sprinklers are specially engineered for fast
thermal response to meet the sensitive fire protection applica-
tion needs of the latest residential market standards (UL 1626
Standard). Upon fire conditions, rising heat causes a sprinklers
heat -sensitive element, glass bulb or link to actuate, releasing the
waterway for water flow onto the deflector, evenly distributing the
discharged water to control a fire.
Technical Data:
• Thermal Sensor: Soldered Element (Link) or Nominal
3mm glass -bulb
• Sprinkler Frame : Brass Casting
• Sprinklers' Pressure Rating : 175 psi
Factory Hydrostatically Tested to 500 psi
• Thread Size: 1/2" NPT (R1/2)
• K-Factor: 3.0 (Actual) - F1 Res 30 Pendent Sprinkler
4.9 (Actual) - F1 Res 49 Pendent Sprinkler
5.8 (Actual) - F1 Res 58 Pendent & HSW Sprinkler
7.6 (Actual) - F1 Res 76 Pendent Sprinkler
4.4 (Actual) - F1 Res 44 HSW Sprinkler
• Density: Minimum 0.05 gpm/ft2
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
m
c
CO
Application
Model F1 Res Sprinklers are used for Residential Fire Pro-
tection according to UL 1626 Standard*., Be sure that ori-
fice size, temperature rating, deflector style and sprinkler
type are in accordance with the latest published standards
of The National Fire Protection Association or the approving
authority having jurisdiction.
Installation
Models F1 Res sprinklers are to be installed as shown.
Model F1, F2 and FP Escutcheons, illustrated herewith,
are the only recessed escutcheons to be used with Model
F1 Res sprinklers. Use of any other recessed escutcheon
will void all approvals and warranties. For installing Model
F1 Res Pendent sprinklers use only the Model D sprinkler
Wrench; for installing Models F1 Res Recessed Pendent,
CCP & SWC sprinklers use only the Model GFR2 sprinkler
moaei rt Res 3u, 49, 5s & 75 Pende
wrench; for installing Model F1 Res Recessed HSW sprin-
klers use only the Model GFR2 Sprinkler Wrench. Use of
wrenches other than those specified may damage these
sprinklers. Install F1 Res 44 with a ceiling to deflector dis-
tance of 4" - 12". Flow arrow on deflector must point away
from near wall and "Top" marking must face ceiling.
Escutcheon*, F1 or F2, Data:
Adjustment
"A"
Face of fitting
Type
Inch (mm)
Inch (mm)
to ceiling
Inch mm
F1
3/4(19.0)
Min.-'14" (19.1)
3/16-15/16
Max: 11/2" 38.1
(4.7 - 24.0
F2
1/2(12.7)
Min: 151%"(23.8)
'/18-11h6
Max: 1112" 38.1
(4.7 - 17.4
Note: Escutcheons Ft or F2 may be used with
Model Ft Res 49, 58 & 76 Recessed Pendent Sprinkler
• Model F1 Res 30 Recessed Pendent/ F2
nt • Model F1 Res 49, 58 & 76 Recessed Pendent / F1
escutcheon, 3/4" (19mm) adjustment
N+-1
—T—
,,,mom•
I
1N
sn•-��n• m mm<°0
I
I
rm.y a•
•ssma
I
1[ia�w�j
Fig. 2
Technical Data: F1 Res 30 Pendent and Recessed Pendent (SIN R3511)
Thread
Nominal Orifice
Max.
Sprinkler
Max.
Actual
Sprinkler
Size
Inch (mm)
Pressure
Tem . Retina
Ambient Temp.
K
Length
°F
°C
°F
°C
Ds! bar
Factor
Inch mm
''A" NPT
R'/z
21/," (8.2)
175 (12)
155
175
68
79
100
38
3.0
2.25 (57)
Ordinary Temp. Rating
Intermediate Temp. Rating
Top of Deflector
Minimum
Max Coverage area
May -Spacing
155°F/680C
1750F/79°C
to Ceiling
Spacing
Flow
Pressure
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
GPM Umin
PSI bar
GPM Umin
PSI bar
Inch (mm)
Ft (m)
12 x 12 (3,6 x 3,6)
12(3,6)
8(30.3)
7.0 (0,48)
8(30,3)
7.0 (0,48)
1 to 4 (25 to 100);
%2 recessed using
8 (2,4)
14 x 14 (4,3 x 4,3)
14(4.3)
10 (37,8)
11 (0,76)
10 (37,8)
11 (0,76)
12 escutcheon
For Ceiling types refer to NFPA 13, 13R or 13D
2.
Technical Data: F1 Res 49 Pendent and Recessed Pendent (SIN R3516)
Max
Sprinkler
Max
Actual
Sprinkler
Thread
Nominal Orifice
Pressure
Tem . Ratilno
Ambient Tem .
K
Length
Size
Inch (mm)
i bar
Factor
Inch mm
°F
°C
°F
°C
'h" NPT
R/2
7/16" (11)
175 (12)
155
175
68
79
100
150
36
fifi
4.9
2.25 (57)
Max Coverage area
Ft x Ft (m x m)
Max Spacing
Ft (m)
Ordinary Temp. Rating
1550F/68°C
Intermediate Temp. Rating
175'F/79°C
Top of Deflector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)
Flow
GPM Umin
Pressure
PSI bar
Flow
GPM Umin
Pressure
PSI bar
12 x 12 (3,6 x 3,6)
12(3,6)
13 (49)
7,0 (0,48)
13 (49)
7.0 (0,48)
1 to 4 (25 to 100):
%2(13)recessed
using F2 escutcheon,
3/4 (19) recessed
using F1 escutcheon
8(2,4)
14 x 14 (4,3 x 4,3)
14(4,3)
13 (49)
7.0 (0,48)
13 (49)
7.0 (0,48)
16 x 16 (4,9 x 4,9)
16(4,9)
13 (49)
7.0 (0,48)
13 (49)
7.0 (0,48)
18 x 18 (5,5 x 5,5)
18(5.5)
17 (64,3)
12 (0,83)
17 (64,3)
12 (0,83)
20 x 20(6,1 x6,1)
20(6,1)
20(75,7)
16.7(1,14)
20(75,7)
1 16,7(1,14)
For Ceiling types refer to NFPA 13, 13R or 13D
Ordinary Temp. Rating
Intermediate Temp. Rating
Top of Deflector to
Minimum
Max Covemge area
Max. Spacing
155°F/680C
175017/790C
Ceiling
Spacing
Flow
Pressure
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
GPM (Umin)
PSI bar
GPM (Umin)
PSI bar
12 x 12 (3,6 x 3,6)
12(3,6)
15 (57)
9.4 (0,65)
15 (57)
9.4 (0,65)
4 to 8 (100 to 203);
%z(13)recessed
14 x 14 (4,3 x 4,3)
14(4.3)
16 (60,5)
10.6 (0,73)
16 (60,5)
10.6 (0,73)
16 x 16 (4,9 x 4,9)
16(4.9)
17 (64,3)
12.0 (0,83)
17 (64,3)
12.0 (0,83)
using F2 escutcheon,
3/4 (19) recessed
8(2,4)
18 x 18 (5,5 x 5,5)
18(5,5)
19 (72)
15.0 (1,0)
19 (72)
15.0 (1,0)
using Ft escutcheon
20x 20(6,1 x6, 1)
20(6,1)
22(83,2)
20.2(1,4)
22(83,2)
1 20.2(1,4)
*Note: The Ft Res 49 pendent and recessed pendent residential sprinklers can be installed per NFPA 13, NFPA 13R and NFPA 13D in beamed
ceilings meeting the following criteria:
1. Maximum beam depth = 7" (178mm)
2. Beam spacing at or greater than 7.5 ft. (2.3m) on center.
Technical Data: F1 Res 58 Pendent and Recessed Pendent (SIN R3513)
Thread
Nominal Orifice
Max
Sprinkler
Max
Actual
Sprinkler
Size
Inch (mm)
pressure
Temp. RatingAmbient
Tem .
K Factor
Length
°F
°C
°F
°C
i (bar)
Inch mm
'h" NPT
+�" (13)
175 (12)
155
68
100
38
5.8
2.25 (57)
RY2
175
79
150
66
Ordinary Temp. Rating
Intermediate Temp. Rating
Top of Deflector to
Minimum
Max Coverage area
Max Spacing
155°F/68°C
1750F/79°C
Ceiling
Spacing
Flow
Pressure
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
GPM Umin
PSI bar
GPM Umin
PSI bar
(Far
12 x 12 (3,6 x 3,6)
12(3.6)
16 (61)
7.6 (0,53)
16 (61)
1 to 4 (25 to 100):
'/2 (13) recessed
14 x 14 (4,3 x 4,3)
14(4,3)
16 (61)
7.6 (0,53)
16 (61)
7.6 (0,53)
16 x 16 (4,9 x 4,9)
16(4.9)
16 (61)
7.6 (0,53)
16 (61)
7.6 (0,53)
using F2 escutcheon,
'/4 (19) recessed
8(2,4)
18 x 18 (5,5 x 5,5)
18(5.5)
19 (72)
10.8 (0,75)
19 (72)
10.8 (0,75)
using Ft escutcheon
20x 20(6,1 x6, 1)
20(6,1)
22(83,3)
14.4(1,0)
22(83,3)
14.4(1,0)
For Ceiling types refer to NFPA 13, 13R or 13D
9
Technical Data: F1 Res 76 Pendent and Recessed Pendent (SIN R7618)
Thread
Nominal Orifice
Max.
Sprinkler
Max
K
Sprinkler
Size
Inch (mm)
Pressure
Temp. a ng
Amblent Tem
Factor
Length
°F
°C
°F
°C
psi bar
Inch mm
3/4° NPT
n/u° (13.5)
175 (12)
155
68
100
36
7.6
2.25 (57)
R%z
175
79
150
66
Ordinary Temp. Rating
Intermediate Temp. Rating
Max Coverage area
Max Spacing
155°F/680C
175°F/79'C
Top of Deflector to
Minimum
Ft x Ft (m x m)
Ft (m)
Ceiling
Spacing
Flow
Pressure
Flow
Pressure
GPM Umin
PSI bar
GPM Umin
PSI bar
Inch(mm)
Ft(m)
12 x 12 (3,6 x 3,6)
12(3.6)
21 (79,5)
7.6 (0,53)
21 (79,5)
7.6 (0,53)
1 to 4 (25 to 100);
%2(13)recessed
14 x 14 (4,3 x 4,3)
14(4.3)
21 (79,5)
7.6 (0,53)
21 (79,5)
7.6 (0,53)
16 x 16 (4,9 x 4,9)
16(4.9)
21 (79,5)
7.6 (0,53)
21 (79,5)
1.6 (0,53)
using F2 escutcheon,
3/4 (19) recessed
8(2.4)
18 x 18 (5,5 x 5,5)
18(5,5)
21 (79,5)
7.6 (0,53)
21 (79,5)
7.6 (0,53)
using F1 escutcheon
20 x 20(6,1 x6,1)
20(6,1)
23(87,1)
9.2(0,63)
23(87,1)
9.2(0,63)
For Ceiling types refer to NFPA 13. 13R or 13D
Model F1 Res 30, 49, 58 & 76 CCP Pendent Model F1 Res 30, 49, 58 & 76
Recessed Pendent/FP
2 5/8- [66.2mm] VA
2 5/15- DA HOLE IN CEIUNO
[56.7 m]
CUP - �-
j 1.112' REDUCER
CUP j
CE UNC
11/4' J1.Smm]
MAY. FACE OF 1 NNO TO OF CU UNC
0/MENSION
A'
COV ADJUSNAENr I HEIGHT
I
J 5/16- DLL
135F004D [84.1mm]
F1 RES 30, 49, 58 & 76 CCP PEND.
Fig. 3
Note: The 171 Res 76 will use a 1" x 3/4" reducer.
4.
FP push-on/thread-off escutcheon
Flg. 4
Technical Data: F1 Res 30 CCP Pendent and Recessed Pendent/FP (SIN R3511)
Nominal
Max. I
CCP Assembly
Max.
K
Sprinkler
Thread
Orifice
Pressure
Temp. Ratin
AmbientTem
Length
Size
inch mm
si bar
Factor
Inch mm
"F
°C
°F
eC
'/z NPT
21/6." (8.2)
175 (12)
135
57
100
38
3.0
2.25 (57)
Ordinary Temp. Rating
Top of Deflector
Minimum
Max. Coverage area
Max. Spacing
155°F/68°C
to Ceiling
Spacing
Flow
I
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
GPM in
PSI bar
12 x 12 (3,6 x 3,6)
12(3,6)
8(30.3)
7.0 (0,48)
1 to 4 (25 to 100);
Yz (13mm) recessed
8(2.4)
14 x 14 (4,3 x 4,3)
14(4,3)
11 (37,8)
13.4 (0,92)
using FP escutcheon
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data:
F1 Res 49
CCP Pendent and Recessed Pendent(FP (SIN 3516)
Nominal
Max
CCP Max Sprinkler
Assembly
Thread Orifice
Pressure
Ambient K Length
Temp.
Size Inch
Psl (bar)
Temp. Factor
Ratio
Inch
(mm)
°F °C °F °C
(mm)
W NPT 7/4' (11)
175 (12)
135 57 100 38 4.9 2.25 (57)
R'lh
Max Coverage
Ordinary Temp. Rating
Top of Deflector to
Minimum
area
Max. Spacing
155°F/68°C
Ceiling
Spacing
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
GPM Umin
PSI bar
12 x 12 (3,6 x 3,6)
12(3,6)
13 (49)
7.0 (0,48)
1 to 4 (25 to 100);
14 x 14 (4,3 x 4,3)
14(4,3)
13 (49)
7.0 (0,48)
16 x 16 (4,9 x 4,9)
16(4.9)
14 (53)
8.2 (0,56)
'/i (13) recessed
using FP escutcheon
8(2.4)
18 x 18 (5,5 x 5,5)
18(5.5)
18 (68,1)
13.5 (0,93)
20x 20(6,1 x6, 1)
20(6,1)
20(75,7)
16.7(1,14)
CCP Options Data:
"A„
"B„
Cover Adjustment
CCPHeight
Inch mm
Inch mm
1/212.7
11,6 24)
5/16(7.9)
31. (19)
FP Data "A":
A
FP Position
Inch mm
Max. Recessed
7/,6 11
Min. Recessed
15/,6 24)
Note: Sprinklers shown in Fig.
3 and Fig. 4 are not
suitable for installation
in ceilings which have
positive pressure in the
space above.
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent(FP (SIN R3513)
Nominal
Max.
CCP Assembly
Max
K
Sprinkler
Thread
Size
Orifice
Pressure
Tern Rating
AmbientTem .
Factor
Length
°F
^C
^F
eC
Inch (mm)
psi bar
Inch mm
Yz" NPT
,/z" (13)
175 (12)
135
57
100
38
5.8
2.25 (57)
R'/z
Max Coverage
Max Spacing
Ordinary Temp. Rating
155°F/68°C
Top of Deflector to
Minimum
area
Ft (m)
Ceiling
Spacing
Flow
Pressure
Ft x Ft (m x m)
GPM Umin
PSI(bar)Inch
(mm)
Ft (m)
12 x 12 (3,6 x 3,6)
12(3.6)
16 (61)
7.6 (0,53)
1 to 4 (25 to 100);
14 x 14 (4,3 x 4,3)
14(4,3)
16 (61)
7.6 (0,53)
16 x 16 (4,9 x 4,9)
16(4.9)
16 (61)
7.6 (0,53)
'/2 (13) recessed
using FP escutcheon
8(2,4)
18 x 18 (5,5 x 5,5)
18(5,5)
19 (72)
10.8 (0;75)
20x 20(6,1 x6,1)
20(6,1)
22(83,3)
14.4(1,0)
For Ceiling types refer to NFPA 13, 13R or 13D
5.
Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP (SIN R7618)
Thread
Nominal
Max.
CCP Assembly
Max.
K
Sprinkler
Size
Orifice
Pressure
Tem .Ratan
Ambient Tem .
Factor
Length
°F
°C
°F
°C
Inch (mm)
psi (bar)
Inch (mm)
3/<" NPT
R /a)
n/u" (13.5)
175 (12)
135
57
11,50(o)
38
66
7.6
2.25 (57)
Max. Coverage
Ordinary Temp. Rating
Top of Deflector to
Minimum
area
Max. Spacing
155°F/68°C
Ceiling
Spacing
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
(mm)
Ft (m)
GPM Umin
PSI(bar)Inch
12 x 12 (3,6 x 3,6)
12(3.6)
21 (79,5)
7.6 (0,53)
1 to 4 (25 to 100);
14 x 14 (4,3 x 4,3)
14(4.3)
21 (79,5)
7.6 (0,53)
16 x 16 (4,9 x 4,9)
16(4.9)
21 (79,5)
7.6 (0,53)
112 (13) recessed
using escutcheon
FP
8(2.4)
18 x 18 (5,5 x 5,5)
18(5.5)
22 (83,3)
8.4 (0,58)
20 x 20(6,1 x6, 1)
20(6,1)
25(94,6)
1 10.8(0,74)
For Ceiling types refer to NFPA 13, 13H or 13D
FACE OF FITRNG TO
WALL DIMENSION
1 114- MIN.
2 1/4- HOLE DA. (J I.Bmm] A
(SL2mm] I - 1�8 CEILING TO
(J.2mm] DEFLECTOR
I - X 1/2" REDUCER DIMENSION
1 15116" DA
2 21/32- DMA
�I� m [72.2mm]
L— �J 11I1
1
TURN COLLAR UNR
RGHr NST SPRINKLER
MENCH BOSS
11YL06-R 1AADJUSTMENT
F1 RES 58 & 44 HSW/F2
Fig. 5
Technical Data: F1 Res 44 HSW & HSW/F2 (SIN R3531)
Model F1 Res 44 & 58 Recessed HSW/F2
Thread
Nominal
Max
Sprinkler
Max
Ambient
K
Sprinkler
Size
Orifice
Pressure
Temp. Rating
Temp.
Factor
Length
Inch (mm)
mm
psi (bar)
Inch (mm)
°F
°C
,F
°C
W NPT
3/e" (10)
175 (12)
155
68
100
38
4.4
2.45 (62)
(RYz)
175
79
150
66
1.1
F2 escutcheon,
112" (13mm) adjustment
Escutcheon, F2, Data:
Face
T
Type
Adjustment
Inch (mm)
oof Fitting
ll
Inch (mm)
(4.7 - 17.4)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
155°F/66°C
Intermediate Temp. Rating
175°F/79°C
Top of Deflector to
Ceiling
Inch(mm)
Minimum
Spacing
Ft (m)
Flow
GPM Umin
Pressure
PSI bar
Flow
GPM Umin
Pressure
PSI bar
12 x 12 (3,6 x 3,6)
12(3,6)
12 (45,4)
7.5 (0,52)
12 (45,4)
7.5 (0,52)
4 to 6 (100 to 152);
'h (13) recessed
using F2 escutcheon
8(2,4)
14 x 14 (4,3 x 4,3)
14(4,3)
14 (53,0)
10.2 (0,71)
14 (53,0)
10.2 (0,71)
16 x 16 (4,9 x 4,9)
16(4,9)
16 (60,6)
13.3 (0,92)
16 (60,6)
13.3 (0,92)
16 x 18 (4,9 x 5,5)
16(4,9)
18 (68,1)
16.8 (0,53)
18 (68,1)
16.8 (0,53)
18 x 18 (5,5 x 5,5)
18(5,5)
19 (72,0)
18.7 (1,29)
19 (72,0)
18.7 (1,29)
16 x 20(4,9 x 6, 1)
16(4,9)
23(87,1)
27.4(1,89)
23(87,1)
27.4(1,89)
12 x 12 (3,6 x 3,6)
12(3.6)
14 (53,0)
10.2 (0,71)
14 (53,0)
10.2 (0,71)
6 to 12 (152 to 305);
'h (13) recessed
using F2 escutcheon
14 x 14 (4,3 x 4,3)
14(4.3)
16 (60,6)
13.3 (0,92)
16 (60,6)
13.3 (0,92)
16 x 16 (4,9 x 4,9)
16(4.9)
17 (64,4)
15.0 (1,04)
17 (64,4)
15.0 (1,04)
16 x 18 (4,9 x 5,5)
16(4.9)
20 (75,7)
20.7 (1,43)
20 (75,7)
20.7 (1,43)
16 x20(4,9 x 6,1)
16(4,9)
23(87,1)
27.4(1,89)
23(87,1)
27.4(1,89)
For Ceiling types refer to NFPA 13, 13R or 13D
Nominal
Max
Sprinkler
Max.
Sprinkler
Thread
Orifice
Pressure
Temp. Rating
Ambient
K
Length
Size
Inch
psi(bar)
Temp.
Factor
Inch(mm)
°F
I °C
°F
°C
(mm
'h" NPT
1/2" (13)
175 (12)
155
68
100
38
5.8
2.45 (62)
R/z
175
79
1,
66
:scutcheon, F2, Data:
TYPe Adjustment Fare owaolFitting
Inch (mm) Inch (mm)
is- 16
(4.7 - 17.4)
Max Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
155°F/66°C
Intermediate Temp. Rating
175°F/79°C
Top oCeilin Deflector to
Ceiling
Inch(mm)
Minimum
Spacing
Ft (m)
Flow
GPM Umin
Pressure
PSI bar
Flow
GPM Umin
Pressure
PSI bar
12 x 12 (3,6 x 3,6)
12(3,6)
16 (60,6)
7.6 (0,53)
16 (60,6)
7.6 (0,53)
4 to 6 (100 to 152);
Y2 (13) recessed
using F2 escutcheon
8(2,4)
14 x 14 (4,3 x 4,3)
14(4.3)
18 (68,2)
9.7 (0,69)
18 (68,2)
9.7 (0,69)
16 x 16 (4,9 x 4,9)
16(4.9)
21 (79,5)
13.2 (0,91)
21 (79,5)
13.2(0,
16 x 18 (4,9 x 5,5)
16(4.9)
25 (94,7)
18.6 (1,28)
25 (94,7)
18.6 (1,28)
16 x 20 (4,9 x 6,1)
16(4,9)
29 (109,8)
25.0 (1,73)
29 (109,8)
25.0 (1,73)
12 x 12 (3,6 x 3,6)
12(3,6)
22 (83,3)
14.4 (1,0)
22 (83,3)
14.4 (1,0)
6 to 12 (152 to 305);
'h (13) recessed
using F2 escutcheon
14 x 14 (4,3 x 4,3)
14(4.3)
22 (83,3)
14.4 (1,0)
22 (83,3)
14.4 (1,0)
16 x 16 (4,9 x 4,9)
16(4.9)
26 (98,4)
20.1 (1,39)
26 (98,4)
20.1 (1,39)
16 x 18 (4,9 x 5,5)
16(4.9)
31 (117,4)
28.6 (1,97)
31 (117,4)
28.6 (1,97)
For Ceiling types refer to NFPA 13, 13R or 13D
7.
Model F1 Res 44 SWC
N 12'
[I6Lfiam, r
I
r/r• lJxJsmm/ �+�+�w�
Jw.m„m(
rm.. a n, r�
ro Pon Wm
Haul av firnu¢ rax
N YM6r 4xlR
AyWr AfNASr ryNL
Remnmen✓al
,1
-••,
rurav muarz wim
•' �
1�
Mi/r A64Nsr 5FRW%(ER
I:r/Jz-
Inrmr
+I r/z•pzmmml
Ae'Y. -e
171 RES 44 SWC
Fig.
6
Technical Data: F1 Res 44 SWC (SIN R35311
Nominal
Max.
Cover
Max.
Sprinkler
Thread
Orifice
Pressure
Temp.
Ambient
K
Length
Size
Inch(mm)
psi (bar)
Ratin
Temp.
Factor
Inch(mm)
'F
,C
,F
,C
'/2' NPT
R%z
3/e° (10)
175 (12)
135
57
100
38
4.4
2.45 (62)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
155°F/680C
Top of Deflector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)
Flow
GPM Umin
Pressure
PSI bar
12 x 12 (3,6 x 3,6)
12(3,6)
13 (49,2)
8.7 (0,60)
4 to 6 (100 to 152);
r/I (13) recessed
using F2 escutcheon
8(2,4)
14 x 14 (4,3 x 4,3)
14(4,3)
14 (53,0)
10.2 (0,71)
16 x 16 (4,9 x 4,9)
16(4,9)
17 (64,3)
15.0 (1,1)
16x 18(4,9 x5,5)
16(4,9)
19(71,8)
18.7(1,13)
16x 20(4,9 x 6, 1)
16(4,9)
23(87,1)
27.4(1,89)
12 x 12 (3,6 x 3,6)
12(3,6)
14 (52,9)
10.2 (0,71)
6 to 12 (152 to 305);
Yz(13)recessed
using F2 escutcheon
14 x 14 (4,3 x 4,3)
14(4.3)
15 (56,7)
11.7 (0,81)
16 x 16 (4,9 x 4,9)
16(4,9)
18 (68,1)
16.8 (1,16)
16 x 18 (4,9 x 5,5)
16(4,9)
20 (75,6)
20.7 (1,43)
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1 Res 58 HSWX (SIN RA3533)
Thread
Nominal
Max
Sprinkler
Max
Ambient
K
Sprinkler
Sprinkler
Size
Orifice
Pressure
Temp. Rating
Temp.
Factor
Length
Identification
Inch (mm)
Pat (bar)
Inch (mm)
Number (SIN)
°F
°C
°F
°C
Bulb
11" NPT
(Rh)
lb- (13)
175 (12)
155
175
68
79
100
150
38
66
5.8
2.45 (62)
RA3533
Max Coverage area
Ft x Ft (m x m)
Max Spacing
Ft (m)
Ordinary Temp. Rating
155'FM'C
Intermediate Temp. Rating
175'Fl79°C
Top of Deflector to
Ceiling
inch (mm)
Minimum
Spacing
Ft (m)
Flow
GPM Umin
Pressure
PSI bar
Flow
GPM Umin
Pressure
PSI bar
18 x 20(5,5 x6,1)
18(5,5)
30(114)
26.8(1,85)
30(114)
26.8(1,85)
4 to 6 (100 to 152);
Yz (13) recessed
using F2 escutcheon
8(2.4)
20 x 20(6,1 x6,1)
20(6,1)
30(114)
26.8(1,85)
30(114)
26.8(1,85)
16 x 22 (4,9 x 7,3)
16(4,9)
33 (125)
32.4 (2,23)
33 (125)
32.4 (2,23)
16 x 24 (4,9 x 7,3)
16(4,9)
38 (144)
42.9 (2,96)
38 (144)
42.9 (2,96)
14 x 26 (4,3 x 7,9)
14(4,3)
42 (160)
52.4 (3,75)
42 (160)
52.4 (3,75)
18 x 20 (5,5 x 6,1)
18(5.5)
35 (133)
36.4 (2,5)
35 (133)
36.4 (2,5)
6 to 12 (152 to 305);
'h (13) recessed
using F2 escutcheon
16 x 22 (4,9 x 6,7)
16(4,9)
38 (144)
42.9 (2,96)
38 (144)
42.9 (2,96)
16 x 24 (4,9 x 7,3)
16(4.9)
42 (160)
52.4 (3,6)
42 (160)
52.4 (3,6)
14 x 26 (4,3 x 7,9)
14(4,3)
46 (174)
62.9 (4,34)
46 (174)
62.9 (4,34)
For Ceiling types refer to NFPA 13, 13R or 13D
FACE OF FITRNC TO
WALL DIMENSION
i II/I D" MIN.
(J I. mm]
2 iHOLE OlA
t. N
(57.2mm]
[57
CENNC TO
(S2mm]
OEfZECTOR
I - N 1/2- REDUCER
it
DIMENSION
it
-
-
(49.2mm]
2 27/J2" Dk.
i
[72.2mm]
TURN COLLAR UNTIL
SPRINKLER
\YL
WRENCH BOSS
1/2' [IJmm]
IesTcoe
ADJUSTMENT
F1 RES
58
HSWX
Fig. 7
91
Technical Data: KRes58 HSWX (RA3593)
Thread
Nominal
Max.
Ambient Max.
K
Sprinkler
Sprinkler
Size
Orifice
Pressure
Tem .
Factor
Length
Ident'rfipUon
Inch (mm)
psi (bar)
Inch (mm)
Number (SIN)
,F
Link
I RNPT
1/2" (13)
175 (12)
100
38
5,8
2.45 (62)
RA3593
Ordinary Temp. Rating
Top of Deflector to
Minimum
Max Coverage area
Max. Spacing
165°F/74°C
Ceiling
Spacing
Flow
Pressure
Ft x Ft (m x m)
Ft (m)
Inch (mm)
Ft (m)
GPM Umin
PSI bar
18 x 20 (5,5 x 6,1)
18(5.5)
29 (109)
25 (1,72)
4 to 6 (100 to 152);
20 x 20(6,1 x6,1)
20(6,1)
30(114)
26.8(1,85)
16 x 22 (4,9 x 7,3)
16(4,9)
33 (125)
32.4 (2,23)
'/z (13) recessed
using F2 escutcheon
16 x 24 (4,9 x 7,3)
16(4.9)
38 (144)
42.9 (2,96)
8(2,4)
14 x 26 (4,3 x 7,9)
14(4.3)
42 (160)
52.4 (3,75)
18 x 20 (5,5 x 6,1)
18(5.5)
35 (133)
36.4 (2,5)
6 to 12 (152 to 305);
11 (13) Recessed
16 x 22 (4,9 x 6,7)
16(4.9)
38 (144)
42.9 (2,96)
16 x 24 (4,9 x 7,3)
16(4.9)
42 (160)
52.4 (3,6)
using F2 escutcheon
14 x 26 (4,3 x 7,9)
14(4.3)
46 (174)
62.9 (4,34)
For Ceiling types refer to NFPA 13, 13R or 13D
Maintenance
Model F1 Res 30, 49, F1 Res 58, F1 Res 76 and F1
Res 44 Sprinklers should be inspected quarterly, and the
sprinkler system maintained in accordance with NFPA
25, 13, 13D, and 13R. Do not clean sprinkler with soap
and water, Ammonia or any other cleaning fluids. Remove
dust by using a soft brush or gentle vacuuming. Remove
any sprinkler which has been painted (other than factory
applied) or damaged in any way. A stock of spare sprin-
klers should be maintained to allow quick replacement
of damaged or operated sprinklers. Prior to installation,
sprinklers should remain in the original cartons and pack-
aging until used. This will minimize the potential for dam-
age to sprinklers that could cause improper operation or
non -operation.
Model F1 Res 30, 49 & 58 Pendent
Sprinkler Specifications
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential pendent sprin-
klers engineered to provide a minimum design density of
0.05 gpm/ftz over the listed coverage area. Listed flows
as specified by the manufacturer's technical data sheets
are to be used. Residential sprinklers shall be installed
in conformance with the manufacturer's installation guide-
lines and the applicable installation standard. Where
pendent residential sprinklers are installed under sloped
ceilings having a pitch from [4/12] to [8/12], the sprinklers
10.
shall be listed for such use. Deflector -to -ceiling distance
listing shall be 1" to 8" maximum. Sprinkler frame and
deflector shall be of bronze frame construction having
a 1/2" NPT thread. Water seal assembly shall consist of
a Teflon -coated Belleville spring washer with top -loaded
extruded or cold head cup with 3 mm glass bulb con-
taining no plastic parts, and having a temperature rating
of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have
a nominal K-factor of 3.0, 4.9 and 5.8. Standard finish:
[Bronze] [Chrome -plated] [White Polyester] [Special fin-
ish— specify]. Residential pendent sprinklers shall be Re-
liable Model F1 Res 30, 49 & 58, SIN R3511, R3516 &
R3513 (Bulletin 135).
Model F1 Res 49 & 58 Recessed Pendent/171,
Model F1 Res 30, 49 & 58 Recessed Pendent/
F2,
Model F1 Res 30, 49 & 58 Recessed Pendent/
FP
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential recessed pen-
dent sprinklers engineered to provide a minimum design
density of 0.05 gpm/ftz over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer's instal-
lation guidelines and the applicable installation standard,
Where pendent residential sprinklers are installed under
sloped ceilings having a pitch from [4/12] to [8/12], the
sprinklers shall be listed for such use. Deflector -to -ceil-
ing distance listing shall be 1" to 8" maximum. Sprinkler
frame and deflector shall be of bronze frame construction
having a 1/2" NPT thread. Water seal assembly shall con-
sist of a Teflon -coated Belleville spring washer with top -
loaded extruded or cold head cup with 3 mm glass bulb
containing no plastic parts, and having a temperature
rating of [155°F (680C)] [175°F (79°C)]. Sprinklers shall
have a nominal K-factor of 3.0, 4.9 & 5.8. Standard fin-
ish: [Bronze] [Chrome -plated] [White Polyester] [Special
finish— specify]. Recessed escutcheon assembly shall
be a steel, two-piece escutcheon [with 1/2" adjustment
(Model F2)] [with 3/4" adjustment (Model F1)] [of push -on
and thread off design with 1/2" adjustment (Model FP)].
Standard finish shall be [brass][bright chrome] [white
painted]. Residential recessed pendent sprinklers shall
be Reliable [Model F1 Res 30, 49 & 58 Recessed Pen-
denUF11 [Model F1 Res 30, 49 & 58 Recessed Pendent/
F2] [Model F1 Res 30, 49 & 58 Recessed Pendent/FP]
SIN R3511, R3516 & R3513 (Bulletin 135).
Model F1 Res 30, 49 & 58 CCP Pendent (Con-
cealed)
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential concealed
sprinklers engineered to provide a minimum design den-
sity of 0.05 gpm/ftz over the listed coverage area. Listed
flows as specified by the manufacturer's technical data
sheets are to be used. Residential sprinklers shall be in-
stalled in conformance with the manufacturer's installa-
tion guidelines and the applicable installation standard.
Where pendent residential sprinklers are installed under
sloped ceilings having a pitch from [4/12] to [8/12], the
sprinklers shall be listed for such use. Sprinkler frame and
deflector shall be of bronze frame construction having a
1/2" NPT thread. Water seal assembly shall consist of a
Teflon -coated Belleville spring washer with top -loaded
extruded or cold head cup with 3 mm glass bulb contain-
ing no plastic parts, and having a temperature rating of
155°F (68°C). Cover plate assembly shall consist of a
brass cover plate and copper alloy retainer flange. Meth-
od of attaching the cover plate to the sprinkler cup shall
be a push -on and thread -off design allowing a'/2" cover
plate adjustment. Cover plate temperature rating shall be
135°F (57°C). A plastic protective cap shall be provided
and factory installed inside the sprinkler cup to protect
the sprinkler from damage, which could occur during
construction before the cover plate is installed. Standard
cover plate finish: [White] [Custom Color— specify]. ].
Concealed pendent sprinklers shall be Reliable Model F1
Res 30, 49 & 58 CCP, SIN R3511, R3516 & R3513 (Bul-
letin 135).
Model F1 Res 44, F1 Res 58 Horizontal Side -
wall, F1 Res 58 HSWX & KRes58 HSWX Resi-
dential Sprinkler Specifications
Sprinklers shall be [cULus Listed] low flow residential
horizontal sidewall sprinklers engineered to provide a
minimum design density of 0.05 gpm/ft2 over the listed
coverage area. Listed flows as specified by the manu-
facturer's technical data sheets are to be used. Residen-
tial sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Where horizontal sidewall residen-
tial sprinklers are installed under sloped ceilings having a
pitch from [4/12] to [8/12], the sprinklers shall be listed for
such use. Sprinkler frame and deflector shall be of bronze
frame construction having a 1/2" NPT thread. Water seal
assembly shall consist of a Teflon -coated Belleville spring
washer with top -loaded extruded or cold head cup with 3
mm glass bulb containing no plastic parts, and having a
temperature rating of [155°F (68°C)] [175°F (79°C)]. The
solder element (Link) version, the water seal consist of a
cap with a bellville spring washer and a temperature rat-
ing of 165°F (74°C). The recessed assembly forthe HSWX
(Bulb & Link) should be a steel two pieces escutcheon
with 1/2" adjustment (Model F2) standard finish should be
Bright Chrome and white painted. The 171 Res 58 HSW is
also available with low lead frame. F1 Res 58 HSW and
HSWX sprinklers shall have a nominal K Factor of 5.8
and F1 Res 44 a nominal K factor of 4.4. Standard fin-
ish: [Bronze] [Chrome -plated] [White Polyester] [Special
finish— specify]. Residential horizontal sidewall sprinklers
shall be Reliable Model F1 Res 44, F1 Res 58, F1 Res 58
HSWX & Model KRes58 HSWX, SIN R3531, RA3533 &
RA3593 (Bulletin 135).
Model F1 Res 44 Recessed
Horizontal Sidewall Sprinkler
Use description for the Model F1 Res 44 horizontal side -
wall sprinkler with the following modifications: Replace
"horizontal sidewall sprinkler" with "recessed horizontal
sprinkler." Add: Recessed escutcheon assembly shall be
a steel, two-piece escutcheon with'/2" adjustment (Model
F2). Standard finish shall be [brass][bright chrome] [white
painted] [Special finish— specify]. Residential recessed
horizontal sidewall sprinklers shall be Reliable Model F1
Res 44/F2, SIN R3531 (Bulletin 135).
Model F1 Res 76 Pendent
Sprinklers shall be [cULus Listed] low flow residential
pendent sprinklers engineered to provide a minimum de-
sign density of 0.05 gpm/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer's in-
stallation guidelines and the applicable installation stan-
dard. Sprinkler frame and deflector shall be of bronze
frame construction having a 3/4" NPT thread. Water seal
assembly shall consist of a Teflon -coated Belleville spring
washer with machined or cold head cup with 3 mm glass
bulb containing no plastic parts, and having a tempera-
ture rating of [155°F (68°C)] [175°F (790C)]. Sprinklers
shall have a nominal K-factor of 7.6. Standard finish:
[Bronze] [Chrome -plated] [White Polyester] [Special fin-
ish —specify]. Residential pendent sprinklers shall be Reli-
able Model F1 Res 76, SIN R7618 (Bulletin 135).
Model F1 Res 76 Recessed Pendent/F1,
Model F1 Res 76 Recessed Pendent/F2,
Model F1 Res 76 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] low flow residential
recessed pendent sprinklers engineered to provide a
minimum design density of 0.05 gpm/ft2 over the listed
coverage area. Listed flows as specified by the manu-
facturer's technical data sheets are to be used. Residen-
tial sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall
be of bronze frame construction having a 3/4" NPT thread.
Water seal assembly shall consist of a Teflon -coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and hav-
ing a temperature rating of [1550F (680C)] [1750F (790C)].
Sprinklers shall have a nominal K-factor of 7.6. Standard
finish: [Bronze] [Chrome -plated] [White Polyester] [Spe-
cial finish— specify]. Recessed escutcheon assembly
shall be a steel, two-piece escutcheon [with 1/2" adjust-
ment (Model F2)] [with 3/4" adjustment (Model F1)] [of
push -on and thread off design with'/2" adjustment (Mod-
el FP)]. Standard finish shall be [brass][bright chrome]
[white painted]. Residential recessed pendent sprinklers
shall be Reliable [Model F1 Res 76 Recessed PendenU
F1] [Model F1 Res 76 Recessed Pendent/F2] [Model F1
Res 76 Recessed Pendent/FP] SIN R7618 (Bulletin 135).
Model F1 Res 76 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] low flow residential
concealed sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential sprin-
klers shall be installed in conformance with the manufac-
turer's installation guidelines and the applicable instal-
lation standard. Sprinkler frame and deflector shall be
of bronze frame construction having a 3/a" NPT thread.
Water seal assembly shall consist of a Teflon -coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and having
a temperature rating of 155°F (68°C). Cover plate assem-
bly shall consist of a brass cover plate and copper alloy
retainer flange. Method of attaching the cover plate to the
sprinkler cup shall be a push -on and thread -off design
allowing a Y2" cover plate adjustment. Cover plate tem-
perature rating shall be 1350F (570C). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate
is installed. Standard cover plate finish: [White] [Custom
Color— specify]. ]. Concealed pendent sprinklers shall be
Reliable Model F1 Res 76 CCP, SIN R7618 (Bulletin 135).
Finishes (1)
Standard Finishes
Sprinkler
F1, F2, FP
Cover Plates
Escutcheons
Bronze
Brass
White Painted
Chrome Plated
Bright Chrome Plated
Chrome
While and Black Polyester
White Painted
Coated
Special Application Finishes
Sprinkler
Ft, F2,
Cover Plates
Escutcheons
Bright Brass
Bright Brass
Bright Brass
Black Plated
Black Plated
Black Plated
Black Paint
Black Paint
Black Paint
Off White
Off White
Off White
Satin Chrome
Satin Chrome
Satin Chrome
(') Other finishes and colors are available on special order.
Consult factory for details.
Note: Paint or any other coating applied over the factory finish will void
all approvals and warranties.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Temperature Rating
4. Sprinkler Finish
5. Escutcheon Finish
6. Cover Plate Finish
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United Slates, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc. AN Recycled
Reliabi (800) 431-Sales Offices newer
(800) 848-6051 6051 Sales Fax Revision lines indicate updated or new data,
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address Ee. Printed in U.S.A. 05113 PM 9999970235
Sprinkler Emergency Cabinets
• Model A4
Designed to carry an emergency supply of sprinklers
and a sprinkler wrench. Made of light weight steel with
holes for mounting. These compact cabinets are fin-
ished in attractive red enamel and are furnished with
knockouts to accommodate either 1/2" or 3/a" sprinkler
threads. The Model A4 Cabinets are available in the fol-
lowing sizes:
• 3 Capacity - For residential sprinklers in NFPA
13D and 13R systems
5" high x 7Y, long x 23/8" deep. .
Locate wrench separately.
• 6 Capacity Standard - For N and Y4" NPT
standard and large orifice sprinklers.
5" high x 14" long x 2Y8" deep.
• 6 Capacity Large - For ESFR, XLO and VELO
Sprinklers.
6y" high x 14" long x 3y" deep.
• 12 Capacity Standard - For V and Y4" NPT
standard and large orifice sprinklers.
5" high x 14" long x 4" deep.
• Model A3
Model A3 Cabinets are designed to carry an emergency
supply of decorative type sprinklers and an installation
wrench. They are able to accommodate 12 Reliable
Models G Recessed, G1, G4, G4FR, ZX or Model B
Flush Sprinklers, and up to 6 sprinklers with a V adjust-
able inlet.
Installation Data:
Size of Cabinet: 161%"long x 14Ya" high x 3t3Y16" deep.
Size of Mounting Holes: Ya diameter.
Spacing of Mounting Holes: 13Yz length -11" height.
Ordering Information
When ordering, specify Model (A4 or A3) and cabinet
capacity size and type (Standard or Large). Sprinklers
and sprinkler wrenches are to be ordered separately.
Sprinkler Escutcheons
These escutcheons enhance the appearance of instak
lations by covering exposed fittings of automatic sprin-
kler systems that are visible beyond finished ceilings
and walls. Furnished to accommodate APT male pipe
threads, escutcheons are held firmly in place by the
sprinklers. The finishes provided are decorative and in-
tended for indoor use.
Bulletin 204 Rev. V
•Sprinkler Emergency Cabinets CD
•Sprinkler Escutcheons o
A
m
Model A4
6 Capacity Standard
12 Capacity Standard
The Reliable Automatic Sprinkler Co., Inc.,103 Fairview Park Drive, Elmsford, New York 10523
Approvals
There are no ILL Listings or FM Approvals associated
with the Models A, B, and C one piece escutcheons or
the Model HB two piece escutcheon. They may be used
with any Reliable Sprinkler with the exception of re-
cessed sprinklers which are listed together with their re-
spective escutcheons. Refer to the appropriate
technical bulletins for this information.
• Model B - One Piece
Available in steel with satin
chrome, bright chrome and
brass plated and white painted
finishes. Inner fingers grip
tightly to the sprinkler. Also
available for 10mm sprinklers.
Diameter: 2'/e°; Depth:lya°;
y" NPT.
• Model C - One Piece
Available in steel with satin
chrome, bright chrome and
brass plated and white painted
finishes. Inner fingers grip
tightly to the sprinkler. Also
available for 10mm sprinklers
Diameter: 2%°; Depth: y
1/2" NPT.
Model HB - Two Piece
Telescoping design permits up
to 1" adjustment to compensate
for variations in the distance that
pipe couplings extend below
ceilings. Made of steel and
available in brass, chrome, satin
nickel and off-white finishes.
Diameter: 3y°; Depth: 2° Min, 3"
Max;'/2" and 3/a" NPT.
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified
and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588
Sales Offices
(800) 848-8051
Sales Fax
(914) 829-2042
Corporate Offices
wmv.reliablesprinkler.com
Internet Address
® necycled Paper
Revision lines indicate updated or new data.
PG. Printed in U.S.A. 12/07 PM 9999970035
This building contains a CPVC fire sprinkler system. This CPVC fire sprinkler system is a Life Safety
Assembly and must be treated carefully. Please read the following before any activity which could
contact this system:
CPVC piping components may be damaged by certain substances and construction practices.
• DO NOT stack, support, hang equipment, or hang flexible wire/cable, especially communications cable, or other material on the fire
sprinkler system.
• ONLY system compatible materials including, but not limited to solvent cements, caulks, sealants, cutting oils and thread pastes as
noted by the CPVC fire sprinkler piping system manufacturer's installation instructions should be used in contact with this system.
• DO NOT expose CPVC products to incompatible substances, such as cutting oils, non -water based paints, packing oils, traditional
pipe thread paste and dope, fungicides, termiticides, insecticides, detergents, building caulks, adhesive tape, solder flux, flexible wire/
cable (with special consideration for communications cabling), and non -approved spray foam insulation materials.
• DO NOT expose CPVC products to edible oils, solvents, or glycol -based anti -freeze fluids.
• DO NOT expose CPVC products to open flame, solder, and soldering flux.
• DO NOT handle CPVC products with gloves contaminated with oils (hydrocarbons) or other incompatible materials.
Failure to follow this notice may cause cracks or fractures to develop in CPVC products resulting in property damage due to
leaks or flooding. The presence of any visible cracks may require partial or full system replacement. For additional information
contact the general contractor or the fire sprinkler system installer.
� l
WdUl
MIN EEC � PI"EdIMER PRODUCTS
FOR ADDITIONAL INFORMATION CONTACT
SPEARS® MANUFACTURING COMPANY AT 1-800-862-1499
Rev. 3.0 Jan 2008
FGN-7-0108
Important Information with Regards to
Your CPVC Fire Sprinkler System
CONGRATULATIONS! This building contains a state-of-the-art FlameGuard® life safety system. Your CPVC fire sprinkler
system will enhance the safety and security of your building when properly cared for. CPVC Fire Sprinkler Products resist
attack from a wide range of chemicals that are corrosive to metallic piping. As with any piping material, there are certain
chemicals that can be detrimental to CPVC. Occasionally, some of these chemicals may be found in some construction
products, site preparations and building maintenance. There are certain things that you need to be mindful of in caring for or
working around your CPVC fire sprinkler system.
Keep your system clear from contact with the following products and chemicals unless
product labels state materials are compatible with CPVC:
NOTICE
Considerations
Cleaning Products/Detergents I Fungicides
Oils/Lubricants/Greases Mold Remedilion
Rubbery Materials Chemicals/Termiticides/Insecticides
For Hired Contractors & Do-It-Yot
Corrosion Inhibitors
Glycol -based antifreezes
Solder Flux
Thread Sealants
Flexible Cable/Wiring (especially communications cabling)
Caulks/Mastics
Adhesive Vinyl/Electrical Tape
Non -Water Based Paint
Paint Thinners
Wood Finishes/Varnishes
You should also avoid the following:
• Sitting, standing, hanging, leaning, or resting anything on the pipe, fittings, and
sprinkler heads
• Grounding electrical Wring to the pipe or fittings
• Ambient temperatures below 40•F/4°C where your fire sprinkler system is located.
(Unless an approved compatible antifreeze or insulation method is installed.)
• Hot work around the pipe, i.e. blow torches, soldering, etc.
Be certain this document is reviewed and understood by anyone working on or around your CPVC life safety
system. If you have any questions or need assistance on chemical compatibility with your CPVC fire sprinkler
system, contact the manufacturer listed on the pipe.
Proper care will help your CPVC fire sprinkler system provide protection for years to come.
I t l t FORADDITIONAL
`lie `�r'+�. '� ® INFORMATION CONTACT
SPE�fS�'[�'[F'a rrr 'fin SPEARS® MANUFACTURING
CPVC FORM SPRIMMUR PRODUCTS COMPANY AT 1-800-862-1499
CPVC Fire SprinWer' mover Document 06-20-16 FGT.7-0616
FlameGuard°
CPVC FIRE SPRINKLER
PIPING PRODUCTS
TECHNICAL INFORMATION
WE.ICHTS & DIMENSIONS
November 2015.�S-
SUPERSEDES ALL PREVIOUS-EDIV&S
"•``"�f %� ~ vim* 1�/C V/(%
I Y� OPC
r smvns '
Visit our web site:
f
'=i
Assessed to ISO 9001:'2008* ;�` - • '��'., ~' C
rG
Certificate, number 293 `'```--,
9
SPERNS
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
The information contained in this section is based on current information and Product design at the time of publication and is subject to change without notification. Our
ongoing commitment to product improvement may result in some variation. No representations, guarantees or warranties of any kind are made as to its accuracy, suitability
for particular applications or results to be obtained therefrom. Forverifcation of technical data or additional information not contained herein, please contact Spears® Technical
Services Department (West Coast: (818) 364-1611--East Coast: (678) 985-1263].
General Information
RECOMMENDATIONS FOR INSTALLERS AND USERS:
Plastic piping systems should be ENGINEERED, INSTALLED and OPERATED in accordance with ESTABLISHED DESIGN AND ENGINEERING STANDARDS AND
PROCEDURES for plastic piping systems. Suitability for the intended service application should be determined by the installer and/or user prior to installation of a plastic
piping system. All Installation and maintenance personnel should be trained in the proper handling and installation requirements and precautions of plastic piping systems.
PRIOR TO ASSEMBLY, all piping system components should be inspected for damage or irregularities. Mating components should be checked to assure that
tolerances and engagements are compatible. Do not use any components that appear irregular or do not fit properly. Contact the appropriate manufacturer of
the component product in question to determine usability. Consult all applicable codes and regulations for compliance prior to installation.
Installation must be made in accordance with Spearse Manufacturing Company
FlameGuard® CPVC Fire Sprinkler Piping Products Installation Instructions - FG-3
NOTE— Individual or group instruction in cored solvent welding procedures is available by contacting your local distributor or your servicing Spears° Regional Distribution
Center.
SOLVENT CEMENT CONNECTIONS — Spears® Manufacturing Company recommends the use of Spears® FS-5 One Step solvent cement for joining Spears°
products. Use of solvent cementing products not approved for CPVC fire sprinkler systems, or failure to follow installation instructions will automatically void
the warranty.
THREADED CONNECTION — Spears® Manufacturing Company recommends the use of Spears° BLUE 75- Thread Sealant. This product has been tested by Spears'
and the sealant manufacturer for compatibility with the Spears° CPVC fire sprinkler products. Consult the sprinkler head manufacturer before using this product. WARNING:
OTHER PIPE JOINT COMPOUNDS OR PASTES MAY CONTAIN SUBSTANCES THAT COULD CAUSE STRESS CRACKING IN THE CPVC OR OTHER FITTING
COMPONENTS. Care must be taken to avoid over torquing -generally i to 2 turns beyond finger tight is all that is required to make up a threaded connection. Factory testing
has indicated 10-25 ft. lbs. of torque is adequate to obtain a leak free seal.
GASKET SEALED THREAD CONNECTIONS —This type of connection can only be made with Spears@ TorqueSafeTMA, SofforqueTM or Quick-forqueT" style Gasket Sealed
Female Sprinkler Adapters. DO NOT USE ANY TYPE OF THREAD SEALANT WHEN INSTALLING THIS TYPE OF ADAPTER. Tape or paste may impair proper sealing
and function. Testing has shown that hand tight until snug for the TorqueSafeTM adapter and finger tight plus 1-turn is all that is needed to seal this special connection.
Sprinkler heads in these specialty fittings can then be additionally tightened clockwise to bring sprinkler frames into desired alignment without stressing the fif5ng. See
speck adapter instructions in package for details.
Gripl-ocTM CONNECTIONS —This type of connection can only be made with Spears@ GdpLocw Couplings or Repair Couplings. DO NOT USE ANY TYPE OF SOLVENT
CEMENT OR SEALANT WHEN INSTALLING THIS TYPE OF CONNECTION. Uses an internal stainless steel gripper ring with an internal elaslomer gasket seal.
Connection allows immediate system use. See specific instructions in package for details.
Installation Training Available - Contact Spasms Technical Services for Details
FlameGuard& Products must be installed in accordance with Spears° FlameGuard° CPVC Fire Sprinkler Piping Products Installation Instructions, National Fire Protection
Association Standards 13, 13R, 13D, and In accordance with local codes. Code requirements and field conditions may differ. It is the responsibility of the installing contractor
to insure that the product is suitable to meet these requirements.
Dimension Reference
G = (LAYING LENGTH) Intersection of center lines to bottom of socket4hread; 90` elbows, tees,
crosses; ± 1/32 inch. M = Outside diameter of socket/thread hub; t 1/16 inch.
H = Intersection of center lines to face of fitting; 90° elbows lees, crosses; ± 1/32 inch. N = Socket bottom to socket bottom; couplings; ± 1/16 inch.
J = Intersection of center lines to bottom of socket/thread; 45' elbows; ± 1/32 inch Q = Width of flats; ±1116 inch.
L = Overall length of fittings; ± 1116 inch. W = Height of cap; ± 1/16 inch.
CPVC FIRE SPRINKLER PIPE SDR 13.5 (ASTM F 442)
Pact Number
Nominal Size
Inches (mm)
Average O.D.
Inches (ram)
Average I.D.
Inches (ram)
Approx. Weight LbsJFt.
CP-007
3/4
(19.1)
1.050
(26.7)
.674
(22.5)
0.168
CP-010
1
(25.4)
1.315
(33.4)
1.101
(28.2)
0.262
CP-012
1-1/4
(31.8)
1.660
(42.2)
1.394
(35.6)
0.418
CP-015
1-1/2
(38.1)
1.900
(48.3)
1.598
(40.7)
0.548
CP-020
2
(50.8)
2.375
(60.3)
2.003
(50.9)
0,859
CP-025
2412
(63.5)
2.875
(73.0)
2.423
(61.5)
1,257
CP-030
3
(76.2)
3.500
(88.9)
2.950
(75.0)
1.067
"Lead Free low lead certification - unless other wise specified, all Spears° FlameGuard® finings specified here -in are certified by NSF International to ANSI/NSFe Standard 61,
Annex G and is in compliance with California's Health 8 Safety Code Section 116825 (commonly known asAB1953) and VernonlAcl 193. Weighted average lead content<=0.25%.
Spearse PVC and CPVC Pipe, Fittings and Valves have always been lead-free and Certified by NSF International for use in potable water systems. Spears® offers a wide range of
lead-free specialty fittings and transition adapters for plumbing applications. However, certain brass threaded adapter fillings for applications that are not intended to convey water
for human consumption through drinking or cooking are still produced and available.
SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS 1
SOCKET DIMENSIONS
SCH 40 -ASTM F438
���
SCH 80 -ASTM F439
A
Socket
Socket
SCH 40 Minimum
SCH 80 Minimum
Size
Entrance A
Bottom B
Tolerance
Socket Length C
Socket Length C
3/4
1.058
1.046
t .004
.719
1.000
1
1.325
1.130
t .005
.875
1.125
1-114
1.670
1.655
t.005
.938
1.250
1-112
1.912
1.894
t.006
1.094
1.375
2
2.387
2.369
t .005
1.156
1.500
2-12
2.889
2.868
t.007
1.750
1.750
3
3.516
3.492
t .008
1.875
1.875
TEE
Socket x Socket x Socket
I
M
�LG�
Part Number
Size
G
H
L
M
Approx. Wt. (Lbs.)
4201-007
3/4
9116
1-1/2
231132
15116
.11
4201-010
1
718
1-13116
3518
1-518
.20
4201-012
1-114
15132
2-3/32
4-7132
2
.29
4201-015
1-112
1-5132
2-9/16
53132
2-11132
.54
4201-020
2
1-13132
2-15116
5.7/8
2-718
.86
4201-025
2-12
1-23132
3-12
7
3.15132
1.62
4201-030
3
2-1116
331132
7-15/16
4-5132
2.53
REDUCING TEE
J"M1
Socket x Socket x Socket
M M H1
G1
N- G2 1
H H2
L
Part
Size
G
G1
G2
H
H1
H2
L
M
M1
M2
Number
VA.Approx.
Lbs.)
4201-102
3143141
314
3/4
314
1-11116
1-25/32
141116
3.13132
15116
1-21132
15/16
.13
4201-125
1014314
23/32
7/8
23132
1-25/32
1.13/16
1-21/32
3-7/16
1-19/32
1-11/32
1-5116
.16
4201-126
1x3/4x1
23132
23132
314
1-27132
1-27/32
13/4
3-19132
1518
15/8
15/16
.17
4201-131
ix1014
11/16
13116
11/16
1-13116
1-13116
1-13/16
3518
1518
1-5116
15/8
.17
4201-157
1-1141014
11/16
1-1132
11/16
1-15116
2-1/32
1-13/16
3-25/32
23132
1-13/32
1-23132
.32
MADE IN THE U.S.A.
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
REDUCING TEE (continued) r---fM1
Socket x Socket x Socket i
PL
Part Number
Size
G
G1
G2
H
H1
H2
L
M
M1
M2
Approx. Wt. (Lbs.)
4201-158
1-114xlxl
27132
29132
25132
2-1116
2-1132
1-29132
3-15116
131132
1-518
1-518
.24
4201-159
1-1141A11/4
31/32
W32
31132
2-7132
2-7B2
23132
4-11132
2-118
2-118
1.23132
.36
4201-167
1-1/4x1-1/4x314
21132
1
21/32
1-29132
2
1-29B2
3-13/16
2
15116
2
.22
4201-168
1-1/40-114A
13116
1
13116
2-1/16
2-1/8
21116
4-118
131132
1-21/32
1-31132
.24
4201-169
1-114z1-114x1-112
1-1/8
15116
1-1/8
2-318
2-11B2
2-3/8
OM
2332
2-11132
23132
.51
4201-201
1-112x1-1/4314
11/16
1
1/4
2-1116
2
1-15116
4
25/16
13/8
2-1116
.41
4201-202
1-12xl-1/41
27/32
1-1132
1 1
2-7132
25B2
1 2-1/4
4-15132
2-5116
1 1-11116
2-1116
.42
4201-210
14/2xl-10314
11/16
1-1/32
11116
2.1116
2-1B2
2-1116
4-5/32
2-11/32
1-13B2
2-11132
.39
4201-211
1-12x1-112x1
13116
1.3132
13116
23116
2-1/4
2-3116
4-318
2-1162
13/4
2-11/32
.41
4201-212
1-112A-12x1-1/4
1-1/32
1-3/32
1-1/32
2-13132
2-11132
2.13132
4-13116
2-11132
2-1/8
2-11132
.49
4201-213
1-1/2x1-12x2
1-9/32
1-SB2
1.9132
2.21132
2-21132
2.21/32
5-11132
2-110
2.29132
2-11/32
.64
4201-248
2x2x3/4
11/16
1-13/32
11116
2-7132
2-7116
2-7132
4.7116
2.27/32
13/8
2-27B2
.52
4201-249
2x2x1
27B2
1-13/32
27132
2-11132
2-9116
2-11132
4-23132
2-78
13/4
2-7/8
.58
4201-250
2x2z1-1/4
1-1/32
1-11/32
1-1/32
2-17132
2-19132
2.17/32
5-3132
2-718
2-3132
2-78
.65
4201-251
2x2xl-12
1-5/32
1-7/16
1-5132
2-11/16
2-13B2
2-11/16
53/8
2-7/8
2-13132
2-718
.79
4201-289
2-11W.12A
27/32
1.23B2
27B2
2-5/8
2-27132
1 2-518
5.1/4
3.17B2
1 1-23132
3-17132
1.01
4201-290
2-1/2x2-1/20-1/4
1-3/32
1-23B2
1-1/32
2-13116
2-3W2
2-13116
5-21132
3-9116
2-3/32
3-9/16
1.13
4201-291
2-112x2-12x1-112
1.3116
12
13/16
2-15/16
1-7/8
2-15116
5-7/8
3-15/32
2-11B2
3-15132
1.26
4201-292
2-12x2-12x2
1-13132
1-58
1-13/32
33116
V/8
3.3/16
63/8
3-12
2-78
3-12
1.37
4201-335
3x3x1
7/8
115/16
718
2314
3-1116
23/4
6-15132
4-3116
1-23/32
43116
1.26
4201-336'
&M-1/4
1-318
WA
13/8
3-5116
3-1123-5116
6518
4-1/8
Via
4-118
1.94
4201-337
3x3xl-12
1-5132
2-1/16
1-SB2
3-1B2
3-7116
3-1B2
6.3/32
4-3116
23/8
43/16
1.46
4201-338
3x3x2
1-7116
1-1311fi
1-7/16
35I16
&5116
3.5116
6-19/32
4-3/16
2-7B
43116
1.69
4201-339
&M-112
1314
131132
1314
35B
323/32
3-5/8
7-114
4-3/16
3-17B2
4.3I16
2.11
• B2nch Met Sized with Bushing
TorqueSafeTM SPRINKLER HEAD TEE
Gasket Sealed Brass
Mt
Thread Insert Style
w
GlEiJ
Socket x Socket x Gasket Fipt
Hi
With Elastomer Seal - Use NO Thread Sealant
M
-- t --
M2
G
G2
H
H2
L
Part Number
Size
G
G1
G2
H
H1
H2
L
M
M1
M2
Approx. Wt. (Lbs.)
4202-101 G
314x3/4x12
7/16
13116
7/16
1-7/16
1-7/16
1-17/32
2-29B2
1-3/8
1-318
1-318
.22
4202-124G
1x3/4112
7/16
1-11132
9116
1-9116
1-11116
1-9116
3-1/8
1-11/16
1-3/8
1-318
.26
4202-130G
1x1x1/2
7/16
1-11132
7116
1-9/16
1-11116
1-9/16
3-118
1.23132
1-3/8
1-23132
.28
4202-131 G
WA/4
17132
15/16
17132
1-11116
1518
1-11116
3.11132
1-23B2
1-9116
1-23132
.31
4202-166G
1-114xl-1/4xl2
7/16
15/8
7/16
Mills
1-15116
1-11116
3318
2-1/16
1-3/8
2-1116
.34
4202-209 G
1-191-1202
12
1-13116
112
1.718
2-3/32
1-718
3314
2.11/32
13/8
2-11132
.41
4202-247G
I 2x2xl2
1 12
1 2-1116
1 112
1 2
1 2-1152
1 2
1 4.1/32
1 2.27B2
1 1-3/8
1 2-27132
1 .54
Not intended to convey or dispense water for human consumption through ddnking or cooking
SPEARS® MANUFACTURING COMPANY
FlameGuard° CPVC FIRE SPRINKLER PIPING PRODUCTS
SPRINKLER HEAD TEE
Brass Thread Insert Style
G1
Socket x Socket x Fipt
H1
IM M
AHH
Part Number
Size
G
I G1
G2
H
I H1
H2
L
M
M1
M2
Approx. Wt. (Lbs.)
4202-010
1AM
1 21/31
1 1-118
21131
1-25/32
1 1-2M2
1-25132
3-19132
1-23/32
1-23132
1-23132
.37
Not intended to convey or dispense water for human consumption through drinking or cooking
Sofforque"14 SR REDUCING TEE
Gasket Sealed Special Reinforced Plastic Thread Style
Socket x Socket x SR Fipt
Mi
With Elaslomer Seal - Use NO Thread Sealant
I1 1
— M21�
H H22
L
Part Number
Size
G
G1
G2
H
H1
H2
L
M
M1
M2
Approx. Wt. (Lbs.)
4202-101GSR
3/43/412
7116
1-1/2
7/16
1 1318
1 1-78
13/8
2314
1 15/16
1 1318
1 15116
1 .16
4202-130GSR
1xlxl12
7/16
15/8
7116
1 1-1/2
1 2
1-112
3
1 1-518
1 1318
1 M/8
1 .20
SPRINKLER REDUCING HEAD TEE
Brass Thread Insert Style
Socket x Socket x Fipt
f H1
2
Gt
4HH
Part Number
Size
G
G1
G2
H
H1
H2
L
M
M1
M2
Approx. Wt. (Lbs.)
4202-101
31431412
7/16
1-1116
7116
1-15132
1-518
1-15/32
2-29132
1-13132
13116
1-13/32
.20
4202-124
14141/2
7116
1-11132
9/16
1.9116 '
1-11/16
1-9116
3-1/8
1.11116
W/8
13/8
.26
4202-130
UU112
7116
1-7/32
7/16
1-91%
1.25132
1-9116
3-1/8
1-314
13/16
1.3/4
.26
4202-156
1-114102
7116
1-7/16
9/16
1.11116
2-1132
1-11116
3.3/8
2-3/32
1.3116
1.23/32
.30
4202-166
1-114x1-1/4x112
7/16
1-15132
7/16
1.11116
2.1132
1-11/16
3-318
2-3132
13/16
23132
.31
4202-199
1-1/2x1-1/4x12
12
1518
9116
1-718
23116
1.13116
3.11116
2-11132
13116
2-1116
.37
4202-209
1-11261/2e12
12
1518
12
1-78
2-3/16
1-7/8
33/4
2-11/32
1-3/16
2.11132
.38
4202-237
2A-12A2
112
1-27132
17132
2
2-7/16
1-29132
3A6116
2.78
1-3/16
2-11'
.47
4202-247
2x2x1/2
12
1.718
112
2
2-7116
2
4-1/32
2-27132
1-3/16
2-27132
.50
Not intended to convey or dispense water for human consumption through ddnking or cooking
MADE IN THE U.S.A.
S\ PEARS
FlaRneUtll CPVC FIRE SPRINKLER PIPING PRODUCTS
SPRINKLER HEAD TEE
Special Reinforced
Plastic Thread Style G1 t
HI
Socket x Socket x SR Fipt
VHIH2
G2
Part Number Size G G1 G2 I H I H1 I H2 L I M M1 M2 Approx. Wt. (Lbs.)
4202-010SR 1x1x1 1 21/32 1 3/4 1 21132 1-25132 1-5/8 1-25132 3-19/32 1-23132 1-11116 1.23/32 .26
SPRINKLER REDUCING HEAD TEE
Special Reinforced
Plastic Thread Style
Socket x Socket x SR Fipt
N-M7-1
H1
MM2
G1
G22
;G�
Part Number
Size
G
G1
G2
H
H1
I H2
L
M
M1
M2
Approx. Wt. (Lbs.)
4202-101SR
3/43/41/2
19132
25/32
19/32
1-19132
1-7/16
1-19132
3-7132
1-13132
1-3116
1-13/32
.15
4202-124SR
1x3/4xl/2
7/16
29/32
9116
1-19132
1-5/8
1-9116
35/32
1-23/32
13116
1-17/32
.19
4202-130SR
1x1A/2
7/16
29132
7/16
1-9116
1-5/8
1-9116
3-1/8
1-23/32
1-3116
1-23/32
.20
4202-156SR
1-1/4xlxl/2
15132
1,02
19/32
1-23/32
1-7/8
1-23/32
3-13132
23132
13116
1-23132
.26
4202-166SR
1-1/4x1-1*1/2
7/16
1-1/8
7/16
1-11/16
1-27/32
1-11116
3-3/8
23/32
1-3116
23132
.26
4202-168SR
1-1/4x1-1/4x1
27132
1-1/32
27132
2-3132
1-29/32
23/32
4-7132
2-3132
1-11/16
23/32
.34
4202-199SR
1-1120-1/4x1/2
9116
1-9132
17132
1-15/16
2
1-25/32
3-23/32
2-11/32
1-3116
23132
.33
4202-209SR
1-1/20-112x112
1/2
1 1-1/4
1 112
1-7/8
131/32
1-7/8
1 33/4
2-11/32
1 13116
1 2-1V32
1 .35
4202-211SR
1-1/20-112A
27/32
1-7/32
27132
2-7112
2-1/8
L7/32
4-15/32
2-11/32
1-23/32
2-11132
.44
4202-237SR
2x1-1/2x1/2
23/32
1-9/16
3/8
2-7/32
2-9/32
1-3/4
3.31/32
2-718
13116
2-11/32
.45
4202-247SR
2x2x12
12
31132
12
2
1-11116
19/32
4
2-718
1-3116
2-7/8
.48
4202-287SR
2-1/2x2-1120/2
17132
1 1-3/4
1 17/32
1 2-9/32
2-1/2
1 2-9132
4-19132
1 3-1/2
1 1-7132
1 3-1/2
1 .78
SOFTORQUETM
SR SPRINKLER HEAD TEE
Gasket Sealed Special
Reinforced Plastic Thread StyleSocket
4H.
x SR Apt x SocketStainless
Steel Collar With Elastomer Seal - UseNO
Thread Sealant
Part Number
1 e
G
G1
G2
H
H7
H2
L
M
Nl
M2
Approx. Wt. (Lbs.)
4203-122GSR
1Sizx1/2x11
13/16
1 13/16
1 1-1/2
1 1-27132
1 1-27/32
I 1-31/32
3-13116
1 15/8
1 1-5/8
1 1-3/8
1 .22
5 SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS d
SPERNS
Torq ueSafeTM
SPRINKLER HEAD TEE
Gasket Sealed
Brass Thread Insert Style
Socket x Gasket Fipt x Socket
M _
H,
GI-1 Ij
_+__ Mz
With Elastomer Seal - Use NO Thread Sealant
G
G2
H
H2
L
PartNumberl
Size
I G
I G1
I G2
I H
1 1-11
1 H2
I L
I M
I M1
I M2
I Approx. Wt. Lbs.
4203-122G
I lx112x1
1 19132
1 13116
1 1-13/32
1 1-19132
1 1-27132
1 1-314
1 3-it132
1 1518
1 1-5/8
1 1-3/8
1 .25
Not intended to convey or dispense water for human consumption through drinking or cooking
SPRINKLER HEAD TEE
Brass Thread Insert Style
Socket x Fipt x Socket
r
I
IM
*GG2
�I
L
Part Number
FSize
I G
I G1
G2
I H
I H1
H2
L
I M
M1
M2
Approx. Wt. (Lbs.)
4203-122
1 1x1/2x1
1 23132
1 3/4
1-1/4
1 15/8
1 1-5/8
1-15/16
3-12
1 1-23132
1 1-23132
1 1-3116
.25
Not intended to conveyor dispense water for human consumption through drinking or cooking
SPRINKLER HEAD TEE
Special Reinforced
Plastic Thread Style
Socket x SR Fipt x Socket
PartNumber Size G G1 G2 H H1 H2 L M Mt M2 Approx. Wt (Lbs.)
4203-122SR 1x1/2x1 27/32 23132 1-3/32 1.23132 1-5/8 1-25/32 3-13132 1-3/4 1J/4 1-3116 .21
MADE IN THE U.S.A. 6
S\ PEARS
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
STREET TEE
Spigot x Socket x Socket
M1
M
o.
H1
G1
G
2
Part Number
Size
G
G1
G2
H
H1
H2
L
M7
M2
Approx. Wt. (Lbs.)
4244-007
314
13116
27132
27/32
1-13/16
1-7/8
1-7/8
3S/8
1-13132
1-13132
.16
4244-010
1
1-5132
1-1/32
1-1132
2-1/8
1-29132
1-29132
4-3/16
1-314
1-3/4
.27
4244-012
1-114
1-1/4
1
1
2-7116
2-9132
2-9132
4-27132
2-W2
2-3132
.42
4244-015
1-112
1-13/16
1-1/8
1-118
2-718
2-9116
2-9116
5-11132
2-1152
2-11/32
.56
4244-020
2
1-23/32
1-7116
1-13132
3-114
2-15116
2-15/i6
6-5132
2-718
2-7/8
.84
900 ELBOW
Socket x Socket
G
H
Part Number
Size
G
H
M
Approx. Wt (Lbs.)
4206-007
314
9116
1-112
1-5116
.07
4206-010
1
314
1.518
1518
.11
4206-012
1-1/4
15116
2J/16
2
.22
4206-015
1-1/2
1-W2
2-17132
2-318
.41
4206e20
2
1-13/32
2-29132
2-78
.62 -
4206-025
2-112
1-102
3-318
3-112
1.15
4206-030
3
15132
3-3/32
4-3/16
1.83
SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
SIDE OUTLET ELBOW
Socket x Socket x Socket
tG
H
Part Number
Size
G
H
M
Approx. Wt (Lbs.)
4213-007
314
27132
1-19132
1-5116
.09
4213-010
1
13116
1-718
1-518
.18
REDUCING 900 ELBOW
&Hl-jSocket x SocketG
H
M
Part Number Size G G1 H H1 M M1 Approwt. Lbx.s.
4206131 tz314 21/32 13116 1-25132 1-13116 1-19M 1-5116 .11
TorqueSafe Ton 900 SPRINKLER HEAD ELBOW
Gasket Sealed Brass Thread Insert Style
Socket x Gasket Rpt
With Elaslomer Seal - Use NO Thread Sealant
H1
G1
G
M1
M
Part Number
Size
G
G1
H
H1
M
M1
Approx. Wt (Lbs.)
4207-101 G
314XI2
9116
1-7132
1-13/32
11-17/32
1-1382
1-318
.19
4207-130G
1z12
7116
1-3116
1-9116
1-111i6
1-23/32
1-38
23
4207-166 G
1-11412
1 15132
1-19132
1 1.15116
1 1-11116
1 2J/32
1-38
1 .25
Not intended to wnvey or dispense water for human consumption through drinking or cooking
MADE IN THE U.S.A.
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS 3
SPRINKLER HEAD 900 ELBOW
Brass Thread Insert Style
Socket x Apt
PHI
M1
Part Number
Size
G
G1
' H
I
H1
M
M1
Approx. WL (Lbs.)
4207-101
3/4zt12
112
1-3132
1-112
1518
1-13132
1-3116
.17
4207-130
1z112
7116
1-7/32
1-19132
1-25132
1-23112
1-3111
.21
4207-131
1x3/4
17/32
1-11132
1-21132
1 J1/32
1-23132
1Jl8
.25
4207-166
1-1/4x1/2
I 15132
1-17/32
1-11116
1
1-15116
1 2-3132
1 147/32
.33
Not intended to convey or dispense water for human consumption through ddnking or cooking
SofTorqueTM SR 900 ELBOW SPRINKLER HEAD ADAPTER
Gasket Sealed Special Reinforced Plastic Thread Style
Socket x SR Apt
IH
With Elaslomer Seal - Use NO Thread Sealant G1
M1
fH
Part Number
Size
G
G1
H
H1
M
Mt
Approx. WL (Lbs.)
4207-101GSR
31412
7116
1-17132
1-318
1-27132
1
1.11/32
1-38
.17
4207-130GSR
IA2
7116
1-11M6
1 1-112
2
1-21132
1-3/8
.19
4207-166GSR
1-1141/2
1 7116
1-718
1 1-11116
2-7/32
2
1-3/8
.22
SPRINKLER HEAD 900 ELBOW
Special Reinforced Plastic Thread Style
M1 ry
Socket x SR Hint
G1
G
-
_
jM1
H
1
M
Part Number
Size
G
G1
H
H1
M
M1
Approx. Wt. (Lbs.)
4207-101SR
314x112
11/32
13116
1-15132
1-112
1 1-13132
1-3116
.14
4207-130SR
1x112
7116
718
1-9116
1-5/8
1-23132
1-3/8
.20
4207-131SR
1x3/4
112
718
1-5/8
1-9/16
1-23132
1-3/8
.16
4207-166SR
1-1/41/2
13132
1-1/32
1-21132
1-23132
2-3/32
1-7/32
.19
SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
900 STREET ELBOW
Spigot x Socket
H,�
G1
M1
HqG
I
L
�--.�- PIPE O.D.
Part Number
Size
G
G1
H
H1
M1
Approx. Wt. (Lbs.)
4209-007
314
29132
19132
1-15116
1-11116
1-13/32
.12
4209-010
1
1-9/32
23132
2-13132
1-27/32
1-3/4
.21
4209-012
1-1/4
1-9116
27132
2-13116
2-3/32
2-3132
.32
4209-015
1-1/2
1-15132
1416
2-27132
2-9116
2-11/32
.42
4209-020
2
1-23/32
1-318
3-7132
2-15/16
2-27132
.65
22-1120 ELBOW
Socket x Socket
J
1 I
M
Part Number
Size
H
J
M
Approx. Wt. (Lbs.)
4216-007
3/4
1-M
7/32
1-13132
.09
4216-010
1
1-318
9/32
1-25132
.14
4216-012
1-1/4
1-1/2
5t16
2-3132
.20
4216-015
1-1/2
1-7116
13132
1-3/8
.19
4216-020
2
1-7/8
318
2-27132
.43
4216.030
1 3
1 2-3/8
1 1/2
1 4-5132
1 1.00
22.1/20 STREET ELBOW
Spigot x Socket
H, A
VH J I
L-
I; •I -PIPE O.D.
Part Number
Size
H
H1
J
J7
M1
Approx. Wt. (Lbs.)
4242-007
314
1-1/4
1-1/2
114
112
1-318
.08
4242-010
1
1-7/16
1-11132
5116
7132
1-23132
.14
4242-012
1-1/4
1-9/16
V25132
17/32
11/16
2-1116
.21
4242-015
1-1/2
1-13/32
1-23132
112
11132
2-11132
.28
4242-020
2
1-29/32
2-1/8
7/32
5/8
2-7/8
.42
4242-025
2-112
2-1/8
2-1/4
13132
1/2
3-112
.68
4242-030
3
2-13/32
243132
9/16
17/32
4-5132
.99
MADE IN THE U.S.A. 10
FlameGuardO CPVC FIRE SPRINKLER PIPING PRODUCTS
450 ELBOW
Socket x Socket
3
IL
ISM--I
Part Number
Size
H
J
M
Approx. Wt. (Lbs.)
4217-007
314
1-5/16
5116
1-5/16
.07
4217-010
1
1-13132
3/8
15/8
.11
4217-012
1-1/4
15/8
3/8
2-5/32
.21
4217-015
1-1/2
1-27/32
15132
2-11/32
.32
4217-020
2
2-1/8
21/32
2-7/8
.48
4217-025
2-1/2
2-17132
314
3-112
.88
4217-030
3
2-29/32
29/32
4-5/32
1.17
CROSS
Socket x Socket x
Socket x Socket
�t
I
M
L H1
L
Part Number
Size
G
G1
H
H1
L
L1
M
Approx. Wt. (Lbs.)
4220-007
314
518
518
1-21132
1-21132
3-5/16
3-5/16
1-13/32
.22
4220-010
1
314
3/4
1-5/8
1-5/8
3-1/4
3-1/4
1-23132
.20
4220.012
1•1/4
1-118
1-1/8
2-3/8
2-3/8
4-3/4
4-3/4
2-3/32
.63
4220-015
1-1/2
1-7132
1-7/32
2-5/8
2-5/8
5-7132
5-7132
2-3/8
.80
4220.020
2
1-112
1-1/2
3
3
6
6
3
t43
4220-025
2-112
1-11111
1-11111
3-7116
3.7/i6
6.7/8
6.718
3-17132
2.16
4220.030
3
2-3132
2-3132
3-31132
3-31/32
7-15/16
7-15116
4-7116
3.37
11 SPEARS® MANUFACTURING COMPANY
Flgl'Y1EGuar O CPVC FIRE SPRINKLER PIPING PRODUCTS
450 STREET ELBOW
Spigot x Socket
H1J1 Mt
il
H�
I— .I PIPE OR
Pan Number
Size
H
Hl
J
JI
MI
Approx. s.
4227-010
1
1-1/2
1-5116
112
114
1-5/8
.10
4227-012
1-1/4
1-25/32
1-9116
9/16
11132
1-31/32
.15
4227-015
1-112
2-1132
2418
19132
25132
2-11132
.29
4227-020
2
2-5116
1-15116
25132
13/32
2-7/8
.44
M1
Socket x Socket
x Socket x Socket
L1
Lt
Part Number
Size
G
G1
H
H1
L
L1
M
M1
Approx. Wt. (Lbs.)
4220-131
lx3/4
23/32
5/8
1-5/8
1-5/8
3-1/4
3-1/4
1-7/8
1-1/2
.31
4220-167
1-1/4314
1-1116
23132
2-1116
1-31132
4-3/32
3-31132
2-1/16
1-13132
.35
4220-210
1-112014
11116
1-5132
2-3132
2-3116
4-3/16
4-11/32
2-318
1-13132
.42
4220.248
2414
11116
1-7116
2-7132
2-71M
4-13/32
4-7/8
2-29132
1-13/32
.56
4220.289
2-112x1
29/32
I-V
2-11116
2-718
5-11132
5-3/4
3-1/2
1-3/4
.98
COUPLING
Socket Socket
M
—_—
—_
N
Part Number
Size
L
M
N
Approx. Wt. (Lbs.)
4229-007
314
2-1/8
1-5116
3116
.05
4229-010
1
2-3116
1-518
3132
.08
4229.012
1-1/4
2-19132
2
3132
.13
4229-015
1-1/2
2-718
2-11/32
3132
.22
4229-020
2
3-1/8
2-7/8
1/8
.33
4229-025
2-1/2
3-11/16
3-15132
3116
.48
4229-030
3
4
4-3116
114
.89
MADE IN THE U.S.A. 12
S\ PERRS
FlameGuard° CPVC FIRE SPRINKLER PIPING PRODUCTS
REDUCER COUPLING
Socket x Socket
M —__FM1
N
L
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4229-131
1x3/4
2-3/8
1-23132
1-13/32
7/32
.10
4229-167
1-1143/4
2-19132
2-3132
1-5/8
11132
.17
4229-168
1-1/4x1
2-11116
2-3132
1-23132
5116
.18
4229-210
1-11204
2-13116
2-11132
1-13132
15/32
.19
4229-211
1-112x1
2-7/8
2-11132
1-15/16
318
.24
4229-212
1-112x1-1/4
2-13115
2-13132
2-118
5132
.23
4229-248
2014
3-3116
2-7/8
1-7/16
23/32
.32
4229-249
2xl
3-1/8
2-7/8
1-23/32
1/2
.31
4229-250
2xl-114
3-3/16
2-7/8
2-1/8
17132
.33
4229-251
2xl-112
3-3/16
2-27132
2-11/32
9/32
.31
4229-291
2-112x1-1/2
3-23/32
3-15132
2-11132
21/32
.51
422K92
2-112x2
3-21132
3-112
2-7/8
13132
.52
422M37
W-1/2
3-1/2
43116
23/8
7132
.71
4229-339
3x2-1/2
3-27/32
43116
3-1/2
3116
.80
GripLocTM COUPLING - LEAD FREE
w/EPDM 0-Ring Seals
L
175 psi Maximum
Internal Pressure @ 150-F
-----
----- ----- ------ M
L1�
WARNING:
DO NOT INSERT FINGERS.
Part Number
Size
L
M1
N
Approx. Wt. (Lbs.)
GL4229-007
3/4
4
1-15/16
1-29132
.25
GL4229-010
1
4-5132
2
2-114
.34
13 SPEARS® MANUFACTURING COMPANY
FlameGuardO CPVC FIRE SPRINKLER PIPING PRODUCTS
GROOVED COUPLING ADAPTER
Groove x Socket
PIPE _ _ M1
O.D.
N
L
Part Number
Size
L
M1
N
Approx. Wt. (Lbs.)
4233-012
1-1/4
3-5/8
2-3132
2-11132
.72
4233-015
1-112
3-3/4
2-11132
2-11132
.83
4233-020
2
3-27132
2-27132
2-11/32
1.27
4233-025
2-1/2
4-3/16
3-15/32
2-7116
2.02
4233-030
3
4.5/16
4-1/8
2-7116
2.76
Not Intended to convey or dispense water for human consumption through drinking or cooking
FEMALE ADAPTER
Brass Thread Insert Style
Socket x Fipt
M
L
r
--
I+ L
M1
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4235-007
314
2
1-13/32
1-318
5/16
.23
4235-010
1
2-3116
1-314
1-11116
11132
.25
4235-012
1-1/4
2-3/8
2-N32
2-1116
3/8
.36
4235-015
1-112
2-17/32
2-318
2-7116
3/8
.47
4235-020
2
2-25/32
2-27132
3-3/16
7116
1.05
Not Intended to convey or dispense water for human consumption through drinking or cooking
FEMALE ADAPTER
Special Reinforced Plastic Thread Style
Socket x SR Fipt
1
M
--- M7
L��
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4235.007SR
314
1-7/8
1-13/32
1-3/8
3132
.OB
423RIOSR
1
2-5132
1-23132
1-7/8
3132
.22
4235-012SR
1-1/4
2-5116
2-1/8
2-1116
3/16
.20
MADE IN THE U.S.A. 14
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
FEMALE SPRINKLER HEAD ADAPTER
Special Reinforced Plastic Thread Style
Socket x SR Fipt
M
L
LA
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4235-10M
3141/2
1-29132
1-13132
1-3116
1/8
.08
4235-130SR
1xV2
1-31/32
1-23132
1-3/8
3/32
.16
4235-131SR
1x314
2-Y32
1-3/4
1-318
114
.13
FEMALE SPRINKLER HEAD ADAPTER
Special Reinforced Plastic Thread Style with Socket Wrench Flats
Socket x SR Apt
an
M
-----TN--
- �- `- M1
M = Flat -to -Flat Dimension
Part Number
Size
L
M
I M1
N
Approx. Wt. (Lbs.)
W4235-101SR
3140/2
2-9/32
1-13132
1 1-3116
17132
1 .09
W4235-130SR
1x1/2
2-9/32
1-3/4
1 1-3/16
13132
1 .12
16 SPEARS® MANUFACTURING COMPANY
FlameGuard° CPVC FIRE SPRINKLER PIPING PRODUCTS
SP\ EARS
SPIGOT FEMALE ADAPTER
Brass Thread Insert Style
Spigot x Fipt
PIPE
O.D. _____ M7
L
Part Number
Size
L
M1
N
Approx. Wt. (Lbs.)
4278-007
314
2-5132
1-318
17132
.15
4278-010
1
2-9132
1-11116
7116
.22
Not intended to convey or dispense water for human consumption through drinking or cooking
SPIGOT FEMALE ADAPTER
Special Reinforced Plastic Thread Style
!
Spigot x SR Fipt
PIPE —_—_
O.D.
�L
Part Number
Size
L
M1
N
Approx. Wt. (Lbs.)
4278-007SR
1 3/4
1 1-15116
1-318
11132
.08
4278-010SR
1 1
12-114
1-23132
13132
.13
TorqueSafeTm FEMALE SPRINKLER HEAD ADAPTER
Gasket Sealed Brass Thread Insert Style
Socket x Gasket Fipt
With Elastomer Seal - Use NO Thread Sealant
M - — - — - W
M1
N
L
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4235-101 G
314x112
1-718
1-13132
1-318
91i6
.15
4235-130GS
1x112
2-1132
1-IVi6
1-318
17/32
.17
4235-131 G
104
2
1-11116
1-9/16
9116
1 .18
Not intended to convey or dispense water for human consumption through drinking or cooking
MADE IN THE U.S.A. 16
SPEARS
FlameGuard° CPVC FIRE SPRINKLER PIPING PRODUCTS
FEMALE SPRINKLER HEAD ADAPTER
Brass Thread Insert Style
Socket x Fipt
M ----;Ij
In
t
N
L
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4235-101
3/4112
1-7/8
1-13/32
1-17132
15132
.19
4235-130
1x12
2-11/32
1-11/16
1-3116
518
.16
4235-131
1x314
2-5/16
1-11116
1-18
17132
.18
Not intended to convey or dispense water for human consumption through drinking or cooking
SofforqUeTM SR FEMALE SPRINKLER HEAD ADAPTER
Gasket Sealed Special Reinforced Plastic Thread Style
Socket x SR Fipt
With Elastomer Seal -Use NO Thread Sealant �
M __--
1
N
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4235-101GSR
314x12
2-5116
M/16
1-318
31132
.11
4235-130GSR
1xl2
2-13132
1-19132
1-9
31/32
.13
4235-131GSR
1414
2-13132
1-518
1-23732
1
.16
QuickTorqueTM
SR FEMALE SPRINKLER HEAD ADAPTER
Gasket Sealed Special Reinforced Plastic Thread Style
Socket x SR Metal Fipt
With Elastomer Seal - Use NO Thread Sealant L
r
Mt
MM ___ _ _��
_L
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4235-101GMR
31412
1.15116
W16
1.9116
13116
.17
4235-13OGMR
1x12
2-3116
1-19132
1-9116
15116
.19
17 SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
SPEAfl3
FEMALE SPRINKLER
HEAD ADAPTER
Brass Thread Insert Style M
with Long Body
Socket x Apt
M1
----
N
L
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
L4235-130
1x112
1 2-3/16
1-23/32
1 1-7132
ill
.19
Not intended to convey or dispense water for human consumption through drinking or cooking
FEMALE SPRINKLER HEAD ADAPTER
Brass Thread Insert Style
with Positioning Ring M
--- M1
Socket x Fipt
L
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
R4235-101
314x112
2-1132 1
1-7/16
1-3/16
15132
.15
Not intended to convey or dispense water for human consumption through drinking or cooking
FEMALE SPRINKLER HEAD ADAPTER
Special Reinforced Plastic Thread
Style with Positioning Ring
--�
Socket x SR Fipt L
M[:;
M1
Fes— L
Part Number_
Size
L
M
M1
N
Approx. Wt. (Lbs.)
R4235-101SR
3/4x1/2
1 1-15116
1-7/16
1-7132
1 7/32
.09
TorqueSafe`rm FEMALE SPIGOT SPRINKLER HEAD ADAPTER
Gasket Sealed Brass Thread Insert Style
Spigot x Gasket Fipt,
With Elaslomer Seal - Use NO Thread Sealant —
PIPE —_—_—_ Mt
O.D.
N
L
Part Number
Size
L
M
N
Approx. Wt. (Lbs.)
4238-101 G
314112
1-15116
1-3/8
21/32
.14
4238-130G
1x112
2-1/16
1-318
19/32
.15
Not intended to convey or dispense water for human consumption through drinking or cooking
MADE IN THE U.S.A. 18
FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS
SPIGOT FEMALE SPRINKLER HEAD ADAPTER
Brass Thread Insert Style
Spigot x Fipt
PIPE
O.D. ------ Mt
L
Part Number
Size
L
M1
N
Approx. Wt. (Lbs.)
4238-101
3/4x1 /2
1-15116
1-17/32
17132
.18
4238-130
1x1/2
2-1/4
1-3116
11132
.19
Not intended to convey or dispense water for human consumption through drinking or cooking
TorqueSafeTm BUSHING - GASKET SEALED
Brass Thread Insert Style
Spigot x Gasket FIPT
With Elastomer Seal - Use NO Thread Sealant PIP
L
Part Number
Size
L
Approx. Wt. (Lbs.)
4238-1308R G
1xi/2
1-7/32
.10
Not intended to convey or dispense water for human consumption through drinking or cooking
BUSHING with BRASS THREAD INSERT
Spigot x Fipt
0.0.
Part Number
Size
L
Approx. Wt. (Lbs.)
4238-130BR
1x1/2
1
.13
Not intended to convey or dispense water for human consumption through drinking or cooking
SPIGOT FEMALE SPRINKLER HEAD ADAPTER
Special Reinforced Plastic Thread Style
Spigot x SR Fipt
PIPE _____„�
O.D.
N
L
Part Number
Size
L
M7
N
Approx. Wt. (Lbs.)
4238-101SR
314112
1-29/32
1-7/32
118
.07
4238-130SR
1x1/2
2-1/32
1-7/32
7132
1 .09
19 SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
SPEARS
MALE ADAPTER
With CPVC Lined Thread Brass Insert
MiptxSocket
M1
---------
L
N
Part Number
Size
L
M1
N
Approx. Wt. (Lbs.)
4236-007
314
2-17132
1-13/32
13116
.26
4236-010
1
2-15/16
1-23/32
29132
.43
4236-012
1-1/4
3-1/8
2-3132
31132
.66
4236-015
1-112
3-9132
2-11132
31132
.80
4236-020
2
3-7/16
2-27/32
31132
1.00
ADJUSTABLE SPRINKLER HEAD ADAPTER
Special Reinforced Plastic Thread Style
Socket x SR Fipt
Q
N BM
L Widh
Part Number
Size
L
N
Q
Body Width
Approx. Wt. (L a.)
Min
Max
Min
Max
42001SR
3/41/2
6-9132
8
4-7/16
6-114
1-7116
2-3/16
.66
42011SR
1x112
6-13/32
8
4-1/2
6-1/8
1-7/16
2-1/8
.68
ADJUSTABLE SPRINKLER HEAD ADAPTER
Special Reinforced Plastic Thread Style
Spigot x SR Fipt
PIPE*'B
;�—INdth
L
N
Part Number
Size
Q
Body Width
Approx. Wt. (Lbs.)
Min
Max
Min
Max
42004SR
3/4112
5-1/32
6-5116
3-3/16
4-15/32
1-5116
2-118
.36
42014SR
1x112
6-7/16
8-1/8
4-7/16
6-1/4
1-7/16
2-3/16
.67
MADE IN THE U.S.A. 20
FlameGuard° CPVC FIRE SPRINKLER PIPING PRODUCTS
REDUCER BUSHING
Flush Style
Spigot x Socket PIPE
O.D.
L
N
-
L
Part Number
Size
L
N
Approx. Wt. (Lbs.)
4237-131
104
1-1/4
1/4
.D4
4237-167
1-1140/4
1-7116
7/16
.10
4237-168
1-114x1
1-13/32
9132
.06
4237-210
1-1/204
15/8
5/8
.19
4237-211
1-112x1
1-17/32
13/32
.13
4237-212
1-112XI-1/4
1-9116
5116
.07
4237-248
2x3/4
1-29/32
29132
.28
4237-249
2x1
1-23/32
9/16
.23
4237-250
20-1/4
1.11/16
7/16
.21
4237-251
2x1-1/2
1-11/16
5/16
.15
4237-290
2-100-1/4
2-5132
7/8
.41
4237-291
2-1/2x1-112
2-5/32
314
.39
4237-292
2-104
2-9132
3/4
.28
4237-338
3x2
2-7132
11116
.63
4237-339
3x2-1/2
2-5116
1/4
.42
TRANSITION BUSHING
IPS Spigot x CTS Socket
PIPE
O.ID.
L
Part Number
Size
L
N
Approx. Wt. (Lbs.)
4240-101
3/4112
14/8
518
.03
4240430
1x112
1-1/4
23132
.05
CAP
Socket
II
-
W
Part Number
Size
M
W
Approx. Wt. (Lbs.)
4247-007
3/4
15/16
1-5116
.04
4247-010
1
1-518
1-9116
.06
4247-012
1-1/4
2-M2
1-27132
.13
4247-015
1-112
2-11/32
2
.17
4247-020
2
2.27132
2-9132
.39
4247-1
2-112
311722
2-518
.50
4247-030
3
4-3I8
3
1.92
21 SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
B
TEST PLUG - 0-ring Sealed
Mipt - For Pressure Testing Only,
Not For use with Z4235 Series Adapters
L ---
F j
M1 — ----- M
1/2-14NPT
Part Number Size L I M M1 Approx. Wt. (Lbs.)
FTP-005 112 1-27132 1-15116 1-7132 .03
TEST PLUG for TorqueSafeTM
Gasket Sealed Head Adapters
Mipt - For Pressure Testing Only.
Use ONLY With Gasket Sealed Head Adapters
L
M1 O��
1/2-14NPf
Part Number Size L M M1 Approx. Wt. (Lbs.)
FTP-005GS 112 1-25132 2-1132 1-1/4 .05
TEST PLUG
(PVC White) Not UL Listed; For Pressure Testing Only,
Mipt
Part Number Size L Approx. Wt. (Lbs.)
4250.005 112 27132 .02
MADE IN THE U.S.A. 22
S\ PfARS
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
FLANGE - ONE PIECE
4 Bolt Holes,175 psi
Socket
M
L
�_j'—
R
N I tr- BOLT CIRCLE DIA �I
� MAX O.D.
No. of
Bolt
Min.
Part Number
Size
L
M
N
R
Bolt
Circle
Bolt
Bolt
Max.
Approx. Wt.
Size
O.D.
(Lbs.)
Holes
Dia.
Length
4251-007
314
1-5/32
1-1/2
118
17132
4
2-3/4
112
2
3-29/32
.31
4251-010
1
1.5/16
1-13/16
1/8
11116
4
3-1/8
1/2
2-1/4
4-9132
.35
4251-012
1-1/4
1-13132
2-7/32
5/32
11/16
4
3-1/2
112
2-1/4
4-5/8
.44
4251-015
1-1/2
1-19132
2-1/2
3/16
23/32
4
3-27/32
112
2-112
5-1116
.61
4251-020
2
1-27132
3
5116
27132
4
4.314
518
3
5-31132
.95
4251-025
1 2-1/2
1 2-7/32
1 3-1/2
1 7116
1-1132
1 4
5-1/2
518
3-114
7
1.50
BLIND FLANGE
4 Bolt Holes,175 psi
R
L—�I
{�- BOLT CIRCLE DIA-
MAXO.D.
Part Number
Size
R
Bolt
No. of Bolt
golf Size
Min. Bolt
Max. O.D.
Approx. Wt. (Lbs.)
Circle Dia.
Holes
Length
4253-007
314
17/32
2-V4
4
112
2
3-27/32
.30
42a010
1
23132
3-118
4
112
2-114
4-114
.35
4253-012
1-1/4
21/32
3-112
4
1/2
2-1/4
4-5/8
.40
4253-015
1-1/2
23/32
3-27132
4
112
2-1/2
5-1116
.52
4253-022
2
27/32
43/4
4
518
3
5-31/32
.86
4253-025
2-112
1-1132
5-112
4
518
3-114
6-15/16
1.70
4253-030
3
1-5/16
6
4
5/8
1 3-1/4
7-5/8
1.72
FLANGE - TWO PIECE
Van Stone Style, 4 Bolt Holes,175 psi
Socket
M
L rR
N "BOUCIRCLE DI� MAX O.D.
Bolt Circle No. of Bolt Min. Bolt
Part Number Size L M N R Dia. Holes Bolt Size Length Max, O.D. Approx. Wt. (Lbs.)
4254-030 3 2-1/8 4-1/4 9132 1-1132 6 4 5/8 3-1/4 7-15132 1.75
23
SPEARS® MANUFACTURING COMPANY
FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS
FLANGE - TWO PIECE
Van Stone Style, 4 Bolt Holes, 175 psi
PIPE 0..0.
Spigot
N
L
R 1F—BDLT CIRCLE DIAL
MAX OD.
Bolt
No. oBolt
Min. Bolt
Approx. WL
Part Number
Size
L
N
R
Bolt Size
O
Max.O.D.
Circle Dia.
Holes
Length
(Lbs.)
4256-007
3/4
1-15/16
13116
17132
MA
4
112
2
3-27r32
.30
4256010
1
2-7/32
1-1132
11/16
3-1/8
4
112
2-1/4
4.1/4
.41
4256-012
1-1/4
2-318
1
11/16
312
4
12
2-1/4
4-518
.50
4256-015
1-12
2.7116
1-3132
23/32
3-7/8
4
112
2-12
4.31132
.65
4256-020
2
2-314
1-5/32
25132
4-3/4
4
518
3
5-15/16
1.00
4256-025
2-1r2
3116
1-9732
1-1r32
5112
4
5/8
31/4
6-15/16
1.62
4256-030
3
3,3
T13/32
1-1132
6
4
5/8
3-114
7-9116
1.76
TRANSITION UNION
Brass Thread Insert Style
Socket x Fipt
175 psi
NUT _
M
O.D.
N
L
Part Number
Size
L
M
N
Nut O.D.
Approx. Wt. (Lbs.)
4259-010BR
1
2-13116
1-7/8
1-1/32
2-7/8
.52
4259-012BR
1-1/4
3
2-3116
1-1/8
3-9132
.98
4259-015BR
1-1/23-314
2-1/2
1-9116
3-17132
.93
4259-020BR
2
3-5/8
2-7/8
1-1/4
4-5/16
1.64
Not Intended to convey or dispense water for human consumption through drinking or cooking
UNION
Socket x Socket
175 psi
NUT M
_ _-
O.D.
N I
L r��III
Part Number
Size
L
M
N
Nut O.D.
Approx. Wt. (Lbs.)
4257-007
314
23/8
1-17132
318
2-12
.38
4257-010
1
2-9116
1-27r32
318
2-718
.41
4257-012
1-114
2.27/32
2-7132
11132
3.5116
.52
4257-015
1-12
3-118
2-12
318
3-17132
.63
4257-020
2
3-5/8
3-1132
9116
43116
1.09
MADE IN THE U.S.A. 24
S\ PFARS
FlameGuard" CPVC FIRE SPRINKLER PIPING PRODUCTS
SofTorqueTIM SR FEMALE SPIGOT SPRINKLER HEAD ADAPTER
Gasket Sealed Special Reinforced Plastic Thread Style
Spigot x SR Apt
With Elastomer Seal - Use NO Thread Sealant
PIPE M7
O.D.
L N
Part Number Size L Mt N Approx. Wt. (Lbs.)
4278-101GSR 3/412 2-1/4 1-H 1 .11
SHORT REPAIR COUPLING
Spigot x Socket
175
psi
L2
L1�
L3
S
Part Number
Size
1-1
L2
L3
M
S
Approx. Wt. (Lbs.)
SH118-07C0
1 314
1 4-13116
1 5-17/32
1 314
1 1-3/4
1 2-3116
1 .31
SH118-1000
11
4-3/4
1 5-518
1 31/32
1 2-1116
1 2-5/32
1 .40
GripLoCTm REPAIR COUPLING — LEAD FREE
w/EPDM 0-Ring Seals
175 psi Maximum
Pressure @ 150°F
WARNING: DO NOT INSERT FINGERS.
Part Number Size L L1 L2 M S Approx. Wt.
Lbs.
SG71&1o00 1 1.17/32 7-17/32 4-114 2-1/4 2-27132 .73
25 SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
FlameGuard® CPVC Drain & Swing Check Valves for NFPA 13D Applications Only
Application: FlameGuard® CPVC Orange Swing Check Valves and PVC/CPVC True Union Drain Valves are for use in configuring CPVC Fire
Sprinkler System connection to water supply (riser/drain assembly) in NFPA 13D installations only. These valves are not UL Listed and NOT for
use in any other locations within the fire sprinkler system.
TRUE UNION INDUSTRIAL DRAIN VALVES
CPVC Gray Valve with CPVC Orange End Connector
Socket Socket
E
I
D i
I
—
A
B
C
Part Number
Size
A
B
C
D
E
1822-007CFG
3/4
2-114
23/4
4314
2-7/8
33/8
1822-010CFG
1
2-1/2
2-7/8
5-1/8
3-1/8
3-7/16
1822-012CFG
14/4
3-1116
3-1/4
5-3/4
3-5/8
3-7/8
1822-015CFG
1-112
3-1/2
3-12
6-1/4
4
43/16
1822-020CFG
2
4-1/4
43/4
73/4
4-12
5-118
Not UL Listed
TRUE UNION DRAIN VALVES
PVC Valve with CPVC End Connector
Socket Socket
D I
4E
_L—
B
C
Part Number
Size
A
B
C
D
E
3622-007FG
3/4
2-1/4
23/4
43/4
2
3
3622-010FG
1
2-112
2-7/8
5.118
2-5116
3-7116
Not UL Listed
MADE IN THE U.S.A. 26
3PERRS
FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS
COMPACT 2000 DRAIN VALVE e
Socketx Socket
o
A
rWB
Part Number
Size
A
B
C
D
E
6622-007CO
314
1-13116
1-12
3-9116
2
3
6622-01000
1
2-1/16
W14
4
2-5/16
3-7/16
Not UL Listed
CPVC SWING CHECK VALVES
Socket Socket
._
A JB
C
Part Number
Size
A
B
C
D
Approx. Wt. (Lbs)
S1520-1000
1
1-11116
2-5/16
4-9116
2-518
.33
S1520.12C0
1-1/4
2-1/16
2-15116
5.1/2
3-318
A2
S1520.15C0
1-112
2-7116
3
5-5/8
3-3/8
.89
Not UL Usted
CPVC SPECIAL REINFORCED
THREAD INLET SWING CHECK VALVES
SR Rpt x Socket
A p
qB ip
C
Part Number
Size
A
B
C
D
Approx. WL (Lbs)
S152040FSRSC0
1
1-11/16
2-15/16
4-9116
2-518
.33
S1520-12FSRSCO
1-1/4
2-1/16
3-5/8
5Al2
3-318
.42
S1520-15FSRSCO
1-12
2-7116
3-11116
5518
3-3/8
.89
NotUL Listed
27 SPEARS® MANUFACTURING COMPANY
NOTES
NOTES
PRODUCT LIMITED LIFETIME WARRANTY
SPEARS
Except as otherwise specified for certain products, mandated by law or herein provided, Spears® Manufacturing Company ('Company") warrants
Standard Catalog Products ('Products") which have been directly manufactured by them to be free from defects in material and workmanship for as long
as the original intended end user of the Products ('End User') retains ownership and possession of the Products and complies with this Warranty
(°Warranty Period'). Each other person or entity acquiring or employing the Products, including buyers, contractors and installers ('Buyer") and End Users
('Buyer/End User) agrees that this Warranty shall be effective only during the Warranty Period so long as the Products are used solely for the normal purposes
for which they are intended and in conformance with industry established standards, engineering, installation, operating, and maintenance specifications,
recommendations and instructions including explicit instructions by the Company; the Products are properly installed, operated and used, and have not been
modified; and all the other terms of this Warranty are complied with. Anyviolation thereof shall void this Warranty and relieve Company from all obligations arising
from this Warranty and the Products.
Upon receipt or discovery of any Products that appear questionable or defective each Buyer/End User shall promptly inspect and return any such Prod-
uct to the Company at 15853 Olden Street, Sylmar, California 91342, accompanied by a letter staling the nature of any problems. If the Prod-
ucts are determined by Company to be defective in materials or workmanship directly provided by Company, Company, at its sole option, may ei-
ther repair or replace the defective Products, or reimburse applicable Buyer/End User for the cost of such Products. The applicable Buyer/End
User shall bear all applicable shipping costs. THIS SHALL BE BUYERS/END USERS' SOLE REMEDY. EACH BUYERIEND USER AGREES
THAT COMPANY WILL NOT BE RESPONSIBLE FOR ANY OTHER OBLIGATIONS RELATING TO THE PRODUCTS, INCLUDING ANY OTH-
ER MATERIALS OR LABOR COSTS, LOSS OF USE OR ANY OTHER ITEM OR FOR ANY DELAYS IN COMPLYING WITH THIS WARRANTY
BEYOND COMPANY'S REASONABLE CONTROL.
COMPANY SHALL NOT BE LIABLE FOR, DOES NOT ASSUME, AND EXPRESSLY DISCLAIMS, ANY LIABILITY, RESPONSIBILITY AND
DAMAGES: DUE TO ANY BUYER/END USER'S FAILURE TO COMPLY WITH THIS WARRANTY, INCLUDING IMPROPER INSTALLATION,
USE OR OPERATION; USE WITH PRODUCTS FROM OTHER MANUFACTURERS THAT DO NOT MEET ASTM OR OTHER APPLICABLE PRODUCT
STANDARDS; IMPROPER CONTROL OF SYSTEM HYDRAULICS, IMPROPER WINTERIZATION PROCEDURES, IMPROPER VOLTAGE SUPPLY, CON-
TACT WITH INCOMPATIBLE MATERIALS OR CHEMICALS, EXCAVATION/DIGGING, EXCESSIVE WEIGHT, AND VANDALISM; DUE TO REASONABLE
WEARANDTEARAND DUE TOANYACTS OF NATURE, INCLUDING LIGHTNING, EARTHQUAKES, GROUND MOVEMENT, FROST HEAVE, OR FLOODS.
COMPANY EXTENDS ONLY THIS WARRANTYAND EXPLICITLY DISCLAIMSALL OTHER WARRANTIES, WHETHER IMPLIED OR OTHERWISE EXPRESSED,
WHETHER ORAL, STATUTORY OR OTHERWISE, INCLUDING ANY IMPLIED WARRANTIES ORAFFIRMATIONS FOR SUITABILITY, MERCHANTABILITY OR
FITNESS FORA PARTICULAR PURPOSE. NO AFFIRMATION BY COMPANY DRAW OF ITS REPRESENTATIVES, BYWORDS, CONDUCTOR OTHERWISE,
SHALL CONSTITUTEA WARRANTY. THIS WARRANTY MAY NOT BE TRANSFERRED, EXTENDED, ALTERED OR OTHERWISE MODIFIED IN ANY MANNER,
EXCEPT BY WRITTEN AGREEMENT SIGNED BY COMPANY.
BY ITS ACCEPTANCE OF THE PRODUCTS, EACH BUYERIEND USER EXPRESSLY WAIVES ALL OTHER LIABILITY OR OBLIGATION OF
ANY KIND OR CHARACTER OF COMPANY, INCLUDING LIABILITY PREDICATED UPON CONTRACT, TORT, STRICT LIABILITY OR OTHER
LEGAL OR EQUITABLE GROUNDS, AND ALL, IF ANY, DAMAGES AND LOSSES AS A RESULT THEREOF, INCLUDING ALL, IF ANY,
COMPENSATORY, GENERAL, SPECIAL, CONSEQUENTIAL, INCIDENTAL, OR PUNITIVE DAMAGES. WITH RESPECT TO SUCH WAIVERS,
EACH BUYERIEND USER EXPLICITLY WAIVES CALIFORNIA CIVIL CODE §1542 WHICH STATES 'A GENERAL RELEASE DOES NOT
EXTEND TO CLAIMS WHICH THE CREDITOR DOES NOT KNOW OR SUSPECT TO EXIST IN HIS FAVORAT THE TIME OF EXECUTING THIS RELEASE,
WHICH IF KNOWN BY HIM MUST HAVE MATERIALLY ADVERSELY AFFECTED HIS SETTLEMENT WITH DEBTOR" AND ALL OTHER SIMILAR STATU-
TORY, COMMON AND CASE LAW RIGHTS, DEFENSESAND LIMITATIONS.
Having previously independently inspected the Products, or a sample, as fully as desired, or having the opportunity to and having not done so,
upon acceptance of delivery of the Products, and except as otherwise herein explicitly provided, each Buyer/End User by acceptance or use of the Products
accepts them in their'AS IS" and 'WITH ALL FAULTS' condition without any otherwarranty, expressed, implied or otherwise, and accepts and assumes the entire
risk and cost of all servicing, remediation and consequences thereof. This Warranty shall be governed by California law and any unenforceable provisions severed
without affecting the remaining provisions. As used herein, 'including' includes 'without limitation."
It is the policy and objective of Spears® Manufacturing Company to produce a superior quality product suitable for its intended use, with
regard to functionality, structural integrity and conformance to established industry standards and practices. It is the commitment of this
Company to do so in a manner which provides consistency of product quality, optimum availability, and superior customer service, while
maintaining efficiency of operations and profitability necessary to perpetuate product improvement and customer satisfaction. Furthermore,
it is recognized that the attainment of these objectives is the responsibility of all Company operations and personnel according to their
respective functions.
The information contained in this publication is based on current information and product design at the time of publication and is subject to change without notification. Our ongoing
commitment to product improvement may result in some variations. No representations, guarantees or warranties of any kind are made as to its accuracy, suitability for particular
application orresults lobe obtained therefrom. For information not contained herein, please contact Spears® Technical Services Department [West Coast(818) 364-1611—East Coast:
(678) 985-12631. Reproduction of this publication in whole or in part is prohibited without the authorized consent of Spears° Manufacturing Company, Sylmar, California.
0 Copyright 2014 Spears® Manufacturing Company. All Rights Reserved. Printed in the United States ofAmerica.
EL
SPEARS® MANUFACTURING COMPANY
Corporate Office
SPEARS 15853 Olden Street •Sylmar, CA 91342
PO Box 9203 • Sylmar, CA 91392
(818) 364-1611 • hftp:llwww.spearsmfg.com
ins
®Copyright 2g15 Spears® Manufacturing Company. NI Rights Reserved. Printed In the United States of America 11115. - FG-4-1115 - ,.-
SCANNE®
BY
St. Lune Countv
7EP
FlameGuard°
CPVC fire Sprinkler Products
INSTALLATION INSTRUCTIONS
To Make Reliable Threaded Connections ...
Gasket Sealed Head Adapter
No Thread Sealant to be Used
Hand Tight + 10 to 25 ft-Ibs Torque to
Rotate for Sprinkler Head Alignment
For Other Thread Connections:
o
1. Use a compatible paste sealant. Spears® 17R -:
recommends BLUE 75TM, tested for
compatibility with CPVC products. BLUE
2. Apply sealant to male threads. Ja�
3. Install Sprinkler Heads or make metal THREAD SEALANT
pipe transitions, tighten as follows: U,
Adapterfor SR Plastic Metal
Metal Pipe Thread Thread
Transition
Hand tight Min. 5 ft-Ibs Min.15 ft-Ibs
+1.5 to 2 Max.10 ft-Ibs Max. 20 ft-Ibs
Turns Torque Torque
October 4, 2010 Pnnted01113 FG-3-1010
,Cn pptC pn A
Flalneduarde LIMITED LIFETIME WARRANTY
Except as otherwise specified for certain products, mandated by law or herein provided,
Sp.
Manufacturing Company r0ompanyT warrants Standard Catalog Products
('Proiuctsjwhich have been directly manufactured bythemto behee from defects in material
and workmanship for as long as the original intended end user of the Products ('End User]
retains ownership and possession of the Products and complies with this Warranty ('Warranty
Period'). Each other person or entity, acquiring or employing the Products, including buyers,
contractors and installers ('Buyer') and End Users r0uyer/End User) agrees that this
Warranty shall be effective only during the Warranty Period so long as the Products are used
solely for the normal purposes for which they are intended and in conformance with industry
established standards, engineering, installation, operating, and maintenance specifications,
recommendations and instructions including explicit instructions by the Company; the
Products are property installed, operated and used, and have not been modified; and all the
other terms of this Warranty are complied with. Any violation thereof shall void this Warranty
and relieve Company from all obligations arising from this Warranty and the Products.
Upon receipt or discovery of any Products that appear questionable or defective each Buyer/
End User shall promptly inspect and return any such Product to the Company at 15853 Olden
Street, Sylmar, California 91342, accompanied by a letter stating the nature of any problems.
If the Products are detemuned by Company to be defective in materials or workmanship
directly provided by Company, Company, at its sole option, may either repair or replace the
defective Products, or reimburse applicable Buyer/End User for the cost of such Products.
The applicable BuyerlEnd User shall bear all applicable shipping costs. THIS SHALL BE
BUYERSIEND USERS' SOLE REMEDY. EACH BUYER/END USER AGREES THAT
COMPANY WILL NOT BE RESPONSIBLE FOR ANY OTHER OBLIGATIONS RELATING
TO THE PRODUCTS, INCLUDING ANY OTHER MATERIALS OR LABOR COSTS, LOSS
OF USE OR ANY OTHER ITEM OR FOR ANY DELAYS IN COMPLYING WITH THIS
WARRANTY BEYOND COMPANY'S REASONABLE CONTROL
COMPANY SHALL NOT BE LIABLE FOR, DOES NOT ASSUME, AND EXPRESSLY
DISCLAIMS, ANY LIABILITY, RESPONSIBILITY AND DAMAGES: DUE TO ANY
BUYER/END USER'S FAILURE TO COMPLY WITH THIS WARRANTY. INCLUDING
WINTERIZATION PROCEDURES, IMPROPER VOLTAGE SUPPLY, CONTACT WITH
INCOMPATIBLE MATERIALS OR CHEMICALS, EXCAVATION/DIGGING, EXCESSIVE
WEIGHT, AND VANDALISM; DUE TO REASONABLE WEARAND TEARAND DUE TOANY
ACTS OF NATURE, INCLUDING LIGHTNING, EARTHQUAKES, GROUND MOVEMENT,
FROST HEAVE, OR FLOODS.
COMPANY EXTENDS ONLY THIS WARRANTY AND EXPLICITLY DISCLAIMS ALL
OTHER WARRANTIES, WHETHER IMPLIED OR OTHERWISE EXPRESSED, WHETHER
ORAL, STATUTORY OR OTHERWISE, INCLUDING ANY IMPLIED WARRANTIES OR
AFFIRMATIONS FORSUITABILITY, MERCHANTABILITYORFITNESS FORAPARTICULAR
PURPOSE. NO AFFIRMATION BY COMPANY OR ANY OF ITS REPRESENTATIVES,
BY WORDS, CONDUCT OR OTHERWISE, SHALL CONSTITUTE A WARRANTY. THIS
WARRANTY MAY NOT BE TRANSFERRED, EXTENDED, ALTERED OR OTHERWISE
MODIFIED INANY MANNER, EXCEPT BY WRITTEN AGREEMENT SIGNED BY COMPANY.
BY ITS ACCEPTANCE OF THE PRODUCTS, EACH BUYERIEND USER EXPRESSLY
WAIVES ALL OTHER LIABILITY OR OBUGATION OF ANY KIND OR CHARACTER OF
COMPANY, INCLUDING LIABILITY PREDICATED UPON CONTRACT, TORT, STRICT
LIABILITY OR OTHER LEGAL OR EQUITABLE GROUNDS, AND ALL, IF ANY, DAMAGES
AND LOSSES AS A RESULT THEREOF, INCLUDING ALL, IF ANY, COMPENSATORY,
GENERAL, SPECIAL, CONSEQUENTIAL, INCIDENTAL, OR PUNITIVE DAMAGES.
WITH RESPECT TO SUCH WAIVERS, EACH BUYERIEND USER EXPLICITLY WAIVES
CALIFORNIA CIVIL CODE §1542 WHICH STATES -A GENERAL RELEASE DOES NOT
EXTEND TO CLAIMS WHICH THE CREDITOR DOES NOT KNOW OR SUSPECT TO
EXIST IN HIS FAVORAT THETIME OF EXECUTING THIS RELEASE, WHICH IF KNOWN
BY HIM MUST HAVE MATERIALLY ADVERSELY AFFECTED HIS SETTLEMENT WITH
DEBTOR' AND ALL OTHER SIMILAR STATUTORY, COMMON AND CASE LAW RIGHTS,
DEFENSES AND LIMITATIONS.
Having previously independently inspected the Products, or a sample, as fully as desired, or
having the opportunity to and having not done so, upon acceptance of delivery of the Products,
and except as othervrise herein explicitly provided, each BuyerlEnd User by acceptance or
use of the Products accepts them in theh'AS IS' and 'NTH ALL FAULTS' condition without
any other warranly, expressed, implied or otherwise, and accepts and assumes the entire
risk and cost of all servicing, remediation and consequences thereof. This Warranty shall be
governed by California law and any unenforceable provisions severed without affecting the
remaining provisions. As used herein, mcluding'includes'without limitation."
TABLE OF CONTENTS
IMPORTANT INFORMATION............................................................................._...............4
Use of this Manual • Hazards & Information Definitions...............................................4
System Engineering, Installation & Maintenance..........................................................4
InstallerTmining............................................................................................................5
General Installation Safety Instructions ........ .._.............................................. __............. 5
Introduction_......................................................................................................................5
Handling& Storage .... _..... _......................................................................._..._.................6
Pipe& Fittings ...............................................................................................................6
One -Step Solvent Cement............................................................................................6
Listing. Approvals, Application & Use ...... _......................................................................7
Light Hazard Occupancies............................................................................................7
Residential Occupancies...............................................................................................7
Low Pressure Dry Pipe and Pre -action Systems..........................................................8
ConcealedInstallations.................................................................................................9
Combustible Concealed Installation with Specific Use Sprinklers .................................9
CombuslibleAttic Spaces with Specific Use Sprinklers ..............................................10
ExposedInstallations..................................................................................................10
Expanded Use with Light Hazard Extended Coverage and Residential Sprinklers .... 10
Unfinished Basement with Exposed Solid Wood Joist Installation..............................11
Extended Coverage Quick Response Sprinklers ........................................................14
Return Air Plenum Installation • Garage Installations..................................................15
Ambient Temperature Limitations • High Temperature Areas......................................15
Cold Temperature Areas............................................................................................. 15
Fire Sprinkler System Risers.......................................................................................16
Underground Fire Service • GUL Using Requirements.............................................18
FactoryMutual Approvals............................................................................................20
Loss Prevention Certification Board LPCB..................................................................20
NSFInternational........................................................................................................21
Penetrating Flre-related Walls & Panitions.................................................................21
Heal Sources & Open Ceiling Areas...........................................................................21
Use With Other Manufacturers' Pipes, Fillings & Solvent Cement .............................22
Installation& Joining ............. _............. ... .... _........................ ..................... _............... 22
Solvent Cement Welded Joints...................................................................................22
Solvent Cement Requirements...................................................................................27
Threaded Connections................................................................................................27
TorqueSafe'Gasket Sealed Thread Connections.......................................................29
Painting Pipe & Filings • Cleaning..............................................................................3D
Transition to Other Materials • Flanged Connections..................................................30
Flange Data & Bolt Torque • Grooved Coupling Adapters ...........................................31
Adjustable Sprinkler Head Adapter Installation...........................................................33
FlushingSystem.........................................................................................................34
System Acceptance Testing (Hydrostatic Pressure Test)..........................................34
Recommended Cut -in Procedures for Systems Modification or Repair......................35
EngineeringData ................ ... ... .................. _.............................. _..... _......................... 37
Pipe & Filling Specifications • Hydraulic Design.........................................................37
Allowance for Friction Loss in Filings.........................................................................38
Hanger& Supports......................................................................................................38
RiserSupport..............................................................................................................41
Exposed Installations • Earthquake Bracing • Trenching............................................42
SnakingMeflection of Pipe..........................................................................................43
Backfilling....................................................................................................................45
MaterialProperties......................................................................................................46
Expansion& Contraction.............................................................................................47
Expansion Loop &Offset Configurations....................................................................49
Review- Do's & Don'ts................... _.._.......................................................................... _52
Material Safety Data SheeL................... _......................................................................... 63
FG-3-1010 m 2013 Speare® Manufacturing Company Page 3
IMPORTANT INFORMATION
Please Read The Following section Before Proceeding
Use of this Manual
Spears® FlameGuard® CPVC Fire Sprinkler Products are approved for use in
combination with other listed manufacturers' products (see, "Use With Other
Manufacturers' Pipes, Fittings, and Solvent Cements" section). However,
specific application approvals may not be the same amongst manufacturers.
It is the installer's responsibility to verify suitability of products used in
combination according to each manufacturer's installation instructions.
Engineering data related to the installation and use of CPVC Fire Sprinkler
Pipe provided in this manual is based on product manufactured by Spears°
Manufacturing Co. (Spears° FlameGuard®), the Victaulic Company (Victaulic
FireLock") or Harvel Plastics, Inc. (Harvel BlazeMaster®), as designated
herein. If products other than Spears®, Victaulic or Harvel are used, follow
the appropriate manufacturers installation instructions. Contact Spears® if
questions on any application are not addressed in this manual.
This manual is intended for use by specifiers, installers, and users in the
selection, design, installation, and inspection of Spears® FlameGuard® CPVC
Fire Sprinkler Products for fire protection service. Due to the critical safety
and loss prevention uses of such systems, all information contained herein
is considered vital to obtain proper system performance and must be read
and understood carefully before starting the installation. The information
contained within this manual is accurate at the time of publication to the best
of our knowledge. It is not meant as a replacement for formal installer training.
We do not make any guarantees nor assume any liabilities arising out of its
use. If you need additional copies, or if you have any questions about the safe
installation and use of these products, contactSpears®Manufacturing Company,
P.O. Box 9203, Sylmar, CA 91392 or call (800) 862-1499. Additional copies
of this manual may be downloaded from our web site: www.spearsmfg.com.
Hazards & Information OeOnitlons
Definitions for identifying the various hazard levels are as follows:
• WARNING• The use of the word "WARN ING" identifies the presence of
hazards or unsafe practices that could result in severe personal injury
if instructions, including recommended precautions, are not followed.
• CAUTION -The use of the word 'CAUTION" identifies possible hazards or
unsafe practices that could result in personal injury, product damage, and/
or property damage if instructions, including precautions, are not followed.
• NOTICE -The use of the word 'NOTICE"identifies special instructions that
are highly Important but not related to hazards.
• Text information in bold print —Text in bold print Identifies additional
important information that may or may not be related to a hazard, according
to the topic and context.
System Engineering, Installation & Maintenance
CPVC Fire Sprinkler Systems must be engineered, installed and maintained
in accordance with local codes, standards and Spears® FlameGuard® CPVC
Fire Sprinkler Products Installation Instructions. Code requirements and field
conditions may differ. It is the responsibility of the installing contractorto insure
that the product is suitable for the Intended use and that all requirements have
been satisfied.
Page ©2013 Spears° Manufacturing Company FG-3-1010
Installer Training
Spears® Manufacturing Company recommends that installers receive proper
installation training and that training be renewed every two (2) years.
Training will be provided at no charge by contacting an authorized Spears®
FlameGuard® CPVC Fire Sprinkler Products distributor or your nearest
Spears° Regional Distribution Center.
General installation Safety Instructions
• Use only recommended accessories. Use of improper accessories or
unapproved system components in conjunction with Spears° FlameGuarda
CPVC Fire Sprinkler Products will void the warranty and may result in
improper operation of the system.
• CAUTION: Avoid dangerous environments. If utilizing electrically powered
tools for installation, be sure that the area is free of moisture or wetness
that could create an unsafe condition. Keep work area clean and well
illuminated. Allow sufficient space for measuring and system dry -fit to
accommodate proper installation.
• Prevent back injury. Always practice safe lifting and installation techniques.
• Use only tools specifically designed for plastic pipe and fittings.
• Inspect the products. Be sure that all parts are included and that you have
all necessary tools available to properly install the system.
CAUTION: Follow all workplace safety requirements. Wear safety glasses,
hardhat, and safety footwear. Always practice safety first.
When solvent cementing, always work in a well-venfilated area. Avoid
sources of heat or open games. DO NOT smoke. Wear protective gloves.
PVA-coated protective gloves are recommended for use while solvent
cementing. If hands come in contact with solvent cement, use a waterless,
abrasivesoap.
Wear ear protection. Protect your hearing if you are exposed to long periods
of very noisy job -site operations.
INTRGGGCHON
Spears® FlameGuard® CPVC Fire Sprinkler Products are manufactured
from high quality, Post -Chlorinated Poly Vinyl Chloride (CPVC), a specialty
thermoplastic material tested and approved by certifying agencies for use
in CPVC fire sprinkler systems. Spearsm FlameGuard° CPVC Fire Sprinkler
Products provide unique advantages over traditional metal fire sprinkler
systems through superior hydraulics, ease of installation and handling and
quick assembly using readily available, inexpensive tools.
FG-3-1010 02013 Spears® Manufacturing Company Page 5
Handling & Storage
Pipe & Fillings
Spears® FlameGuard®CPVC Fire Sprinkler Products resist attack from a large
group of chemicals that are corrosive to metallic piping. However, care must
be taken to avoid contact with chemicals that are harmful to CPVC including
those found in some common construction products. Specific chemicals or
chemical vapors that contact CPVC can weaken or severely damage the
system. Consultwith the chemical manufacturer or Spears® before use.
WARNING: DO NOT expose Spears' FlameGuard' CPVC Fire Sprinkler
Products to edible oils, esters, ketones, or petroleum -based products,
such as cutting oils, packing oils, traditional pipe thread paste or
dopes, and some lubricants. Do not store or install CPVC products in
direct contact with plasticizer containing materials such as electrical
tape or certain wire and cable insulations. Consult with the chemical
manufacturer for compatibility with CPVC or Spears' before use.
Contact with incompatible chemicals could cause serious personal
injury, property damage, and product damage.
Spears® FlameGuard® CPVC Fire Sprinkler Pipe should be stored indoors
with a maximum storage temperature of 110° F (43' C). If storing outdoors,
the products must be covered with a non -transparent material to prevent
extended exposure to sunlight. Brief exposure to direct sunlight on the job
site may result in color fade, but it will not affect the physical properties.
Spears® FlameGuard® CPVC Fire Sprinkler Fittings should be stored indoors
in their original containers to keep them free from dirt and to help reduce the
possibility of damage.
WARNING; Spears' FlameGuard' CPVC Fire Sprinkler Products must
not be subjected to prolonged sunlight exposure. The use of pipe and
Fittings that have been damaged due to improper storage could cause
serious personal injury, property damage, and product damage.
Reasonable rare must be exercised in handling Spears° FlameGuard® CPVC
Fire Sprinkler Products. DO NOT drop the products or drop anything on them.
If improper handling results in scratches, splits, or gouges, the damaged fitting
or section of pipe must be discarded.
WARNING: DO NOT install Spears' FlameGuard' CPVC Fire Sprinkler
Products that have been scratched, split, or gouged. The use of pipe and
fittings that have been damaged due to improper handling could cause
serious personal injury, property damage, and product damage.
One -Step Solvent Cement
Spears® FS-5 One -Step Low VOC Solvent Cement must be stored out of
direct sunlight in an ambient temperature between 40' F (4' C) and 90' F
(32' C). The solvent cement may be used for a period of two years from the
date stamped on the container. Expired solvent cement must be discarded in
an environmentally friendly fashion, in accordance with local regulations. To
prolong the life of the cement, the containers must be kept tightly closed when
not in use and covered as much as possible when in use.
WARNING:
• Spears'FS-5 One -Step Low VOC Solvent Cement is highly flammable.
Eliminate all ignition sources.
• Avoid breathing vapors. Use only with adequate ventilation.
Explosion -proof, general mechanical ventilation or local exhaust is
recommended to maintain vapor concentrations below recommended
exposure limits. In confined or partially enclosed areas, a NIOSH
approved organic vapor cartridge respirator with a full face -piece is
recommended. Avoid frequent contact with skin. It is recommended
that you wear PVA coated gloves and an impervious apron.
Page 6 © 2013 Spears° Manufacturing Company FG-3.1010
• Avoid contact with eyes. Splash -proof chemical goggles are
recommended.
• Review the Material Safety Data Sheet (MSDS) and the important
product information provided on the label for Spears' FS-5 One -Step
Low VOC Solvent Cement.
Failure to follow the above recommendations could result in death or
serious personal injury.
Listings, Approvals, Application & Use
Spears° FlameGuard® CPVC Fire Sprinkler Products are fully tested
and approved for use in wet pipe fire sprinkler systems by Underwriters
Laboratories Inc., FM Global, and the Loss Prevention Certification Board.
Spears® FlameGuard® CPVC Fire Sprinkler Products are approved for
use In low pressure dry pipe or pre -action systems by Underwriters
Laboratories Inc. Spearse FlameGuard® CPVC Fire Sprinkler Products are
listed by NSF Intemational for use in potable water systems. For specific
listing information not covered in this manual concerning Factory Mutual, The
Loss Prevention Certification Board or NSF International, please contact your
nearest Spears® Regional Distribution Center.
NOTICE: National Fire Protection Association (NFPA) Standards 13, 13R,
and 13D must be referenced for design and installation requirements in
conjunction with this manual and all local codes.
CAUTION: Spears® FlameGuard° CPVC Fire Sprinkler Products are NOT
listed for outdoor applications. Outdoor installation could result in product
failure and property damage and will not be covered under the Spearse
FlameGuard® CPVC Fire Sprinkler Products warranty.
CAUTION: Spearse FlameGuard® CPVC Fire Sprinkler Products are to be
used in wet pipe systems only, except as provided for dry pipe or pre -action
systems in this manual. A wet pipe system is one that contains water and
is connected to a voter supply system so that the water will discharge
immediately when the sprinkler is opened. A low pressure dry pipe or pre -
action system is a piping system containing air or nitrogen under pressure that
is release with the opening of a spdnklerwhich activates a special dry pipe valve
allowing water to flow into the piping system and to the open sprinkler.
WARNING: Spearse FlameGuard® CPVC Fire Sprinkler Products must never
be used for distribution of compressed air or other gases except as provided
for under Low Pressure Dry Pipe and Pre -action Systems specified in this
manual. Failure to follow this warning could result in product failure, property
damage and severe personal injury or death.
Light Hazard Occupancies
Spearse FlameGuard® CPVC Fire Sprinkler Products are UL Listed for use in
Light Hazard Occupancies, as defined in the NFPA 13.
In accordance with NFPA 13, 2002 Edition paragraph 6.3.6.2, "Pipe ortube listed
for light hazard occupancies shall be permitted to be installed in ordinary hazard
rooms of othewise light hazard occupancies where the room does not exceed
400 square feet'. NOTICE: Local jurisdictions must approve of this exception.
Residential Occupancies
Spearse FlameGuard® CPVC Fire Sprinkler Products are UL Listed for use in:
Residential occupancies up to and Including fourstories in height, as defined
in NFPA 13R.
Residential occupancies, as defined in the Standard for the Installation
of Sprinkler Systems in One and Two Family Dwellings and Manufactured
Homes, NFPA 13D.
FG-3-1010 02013 Spears° Manufacturing Company Page 7
Low Pressure Dry Pipe and Pre -action Systems
In accordance with the UL° Listing, Spears® FlameGuarde CPVC Fire Sprinkler
Products may be used in Low Pressure Dry Pipe and Pre -action System
applications in Light Hazard and Residential occupancies in accordance with
NFPA 13, 13D and 13R when subject to the following additional limitations:
A CPVC Low Pressure Dry Pipe or Pre -action System is a piping system
intended for use where piping could be subjected to freezing temperatures and
water filled pipe cannot be utilized. The minimum rated temperature is -20' F
(-29° C). Low Pressure Dry Pipe systems contain compressed air or nitrogen
(gas) having an internal gage pressure of not more than 15 psig (105 kPa).
These specially designed systems require separate control valve mechanisms
for this application (supplied by others) that activate to release water into the dry
piping section and to the sprinkler heads. The water -filled portion of the system
control device must be in an area protected from freezing. It is the installer's
responsibility to be sure the system is installed in accordance with the limitations
of this manual and specifications of a Dry Pipe or Preadion Fire Sprinkler
System design Engineer for proper control devices, pipe sizing, and other
impodanldesign and maintenance criteria applicable to each project. CPVC dry
systems must be designed with NefolloWng maximumwaterdeliverytime delay.
Occupancy Hazard'
Remote Sprinklers
Open
Water Delivery
Delay, sec.
Residential
1
15
Light
1
60
'As desoitied in NFPA 13, Standard for the Installation of Sprinkler Systems.
Spears® FlameGuar& CPVC Fire Sprinkler Products are UL® Listed for use in
Dry Pipe or Pre -action type systems when installed with UL® Listed Spears®
FlameGuard® or BlazeMaster® brands of CPVC Fire Sprinkler Products that are
also Listed for this application.
CPVC installation in a Dry Pipe or Pre -action sprinkler system must be
concealed (protected) by either.
(1) A 318 in. Nick or thicker gypsum wallboard;
(2) Asuspended membrane ceiling with lay -in panels or tiles having a weight of
not less than 0.35 IbNt' when installed with metallic support gdds; or
(3)112 in. plywood soffits.
CPVC pipe and finings used in a Dry Pipe or Pre -action System are not for use
in combustible concealed spaces where sprinklers are required by NFPA 13,
13D and 13R.
Pipe and fittings are for indoor use only, down to a minimum temperature of
-20° F (-29- C).
CPVC pipe in Dry Pipe or Pre -action Systems must be installed with proper pitch
to allow system drainage for removal of water. NFPA 13 requires a minimum
pitch of 112 inch per 10 feel (4 mnJm) for main lines and branch lines in areas
subject to freezing.
The following types of sprinklers and arrangements shall be permitted for dry
pipe systems, current NFPA 13:
(1) Upright sprinklers;
(2) *Listed dry sprinklers;
(3) Pendent sprinklers and sidewall sprinklers installed on return bends, where
the sprinklers, return bend, and branch line piping are in an area maintained at
or above 40' F (4° C);
(4) Horizontal sidewall sprinklers installed so that water is not trapped;
Page 8 02013 Spears® Manufacturing Company FG-3-1010
(5) Pendent sprinklers and sidewall sprinklers, where the sprinklers and branch
line piping are in an area maintained at or above 40° F (4' C), the water supply
is potable, and the piping for the dry pipe system is copper or CPVC specifically
listed for dry pipe applications.
Residential sprinklers used in CPVC Dry Pipe Systems shall be specifically
listed for such use.
Low Pressure Dry Systems have a maximum installed air pressure of 15 psi (1
BAR). Air (or Nitrogen) supply for charging the system must be filtered, clean,
oil -free, and must be pressure regulated to assure that the 15 psi (1 BAR)
pressurization is not exceeded.
WARNING - Oil in the air (or Nitrogen) supply can cause environmental
stress cracking in CPVC materials.
WARNING- Over pressurization can result in system damage or serious
injury.
The system must be hydrostatically tested in accordance with System
Acceptance Testing (Hydrostatic Pressure Test) as specified in this manual.
Concealed Installations
In concealed installations, the minimum protection shall be one layer of 3/8-
inch gypsum wallboard, 1/2-inch plywood soffits, or a suspended membrane
ceiling with lay -in panels or tiles having a minimum weight of not less than
0.35 Ibs/d' when installed with metal support grids. The minimum protection
for residential occupancies, defined In NFPA 13D and 13R, may consist of one
layer of 1/2-inch plywood.
Spears® FlameGuard® CPVC Fire Sprinkler Products must be used in spdnkler
systems employing sprinkler heads rated at 225° F (107' C) or lower.
NOTICE
• Spears®FlameGuard® CPVC Fire Sprinkler Products CANNOT be installed
in spaces designated by NFPA 13 as combustible, concealed spaces that
require sprinklers, unless the space is protected by spdnkers that are
specifically Listed for the application.
• NFPA 13D and NFPA 13R permitthe omission ofspdnklers in combustible,
concealed spaces. Spears® FlameGuard° CPVC Fire Sprinkler Products
can be installed in these areas when sprinkling residential occupancies in
accordance with these standards.
Combustible Concealed Installations with Specific Use Sprinklers
InaccordanceWthULLisfing, SpearsaFlameGuard®CPVCFire SpdnklerProducts
can be used in specific light -hazard, combustible concealed and noncombustible
concealed spaces that require sprinkler protection when installed with UL
Listed VictauGc Model V2502, Tyco Fire Products Model CC1- 2.8 K-Factor or
Model CC2- 5.6 K-Factor Combustible Concealed Space Sprinklers, Specific
Application Upright, or UL Listed Viking Microfaste COINTM Quick Response
Combustible Interstitial Space Upright Sprinklers for Specific Application.
The system must be installed in accordance with the applicable sprinkler
manufacturer's information contained in Victaulic Model V2502, Submittal
40.09, Tyco Fire Products Model CCi - 2.8 K-Factor Combustible
Concealed Space Sprinkler Technical Data Sheet (dated July 2004), Tyco
Fire Products Model CC2 - 5.6 K-Factor Combustible Concealed Space
Sprinkler Technical Data Sheet (dated July2007) or Viking Microfase C0IN1°
Quick Response Upright Sprinkler SIN VK900 (SpecificApplication) Technical
Data Sheet (dated February 2, 2007).
NOTICE: When installing Spears° FlameGuarda CPVC Fire SprinklerProducts
in combustible concealed areas where sprinklers are required, the specific
application spdnklermust be used in accordance with the UL Listing. Contact the
local authority having jurisdiction with questions concerning code requirements.
FG-3-1010 © 2013 Spears® Manufacturing Company Page 9
Combustible Attic Spaces with Specific Use Sprinklers
Product Description
In accordance with the UL Listing, Spears° FlameGuard° CPVC Fire Sprinkler
Products may be installed within the attic space provided the attic space
is protected with UL Listed Tyco Fire Products Specific Application Attic
Sprinklers. Specific Application Attic Sprinklers are sprinklers designed
to provide protection of specific light hazard combustible, as well as non-
combustible, attic spaces requiring sprinkler protection.
Installation Requirements
When using the Specific Application Attic Sprinklers, Spears® FlameGuard®
CPVC Fire Sprinkler Products may be installed to feed the wet system
sprinklers below the ceiling and exposed to feed wet system specific
application attic sprinklers provided the system is installed in accordance with
the Tyco Fire Products' Technical Data Sheet TFP610 (dated May 2008) for
Specific Application Attic Sprinklers.
Exposed Installations
Spears® FlameGuard® CPVC Fire Sprinkler Products are UL Listed for use in
installations without protection (exposed), with the following restrictions:
Exposed CPVC Fire Sprinkler piping is installed below a smooth, flat,
horizontal ceiling construction utilizing UL Listed support devices.
• Listed, Quick -Response, ordinary temperature -rated pendent sprinklers
having deflectors Installed within 8 inches from the ceiling. Listed,
Residential, ordinary temperature -rated, pendent sprinklers located in
accordance with their Listing. The maximum distance between sprinklers
must not exceed 15 feet. The piping must be mounted directly to the ceiling.
• Listed, Quick -Response, ordinary temperature -rated horizontal sidewall
sprinklers having deflectors installed within 6 inches from the ceiling and
within 4 inches from the sidewall. Listed, Residential, ordinary temperature
rated horizontal sidewall sprinklers located In accordance with their Listing.
The maximum distance between sprinklers must not exceed 14 feet. The
piping must be mounted directly to the sidewall.
• Listed, Quick -Response, upright sprinklers having a maximum temperature
rating of 155° F (68° C) must be installed so that the deflectors are a
maximum of 4' from the ceiling. The maximum distance from the ceiling to
the centedine of the main run of pipe must be 7-1/2'. The distance from the
centedine of a sprinkler head to a hanger must be 3'. Rigid pipe hangers
secured to the ceiling must be used.
Expanded Use with Light Hazard Extended Coverage and Residential
Sprinklers
In accordance with the UL Listing, Spearse CPVC Fire Sprinkler products
may be installed without protection (exposed) when subject to the following
additional limitations.
The following installations shall be below a smooth, flat, horizontal ceiling
construction and require the use of FS-5 one step solvent cement. The piping
shall be mounted directly to the sidewall.
Listed quick response, 200' F (93' C) maximum temperature rated, horizontal
sidewall sprinklers having deflectors installed within 12 inches (304 mm)
from the ceiling and within 6 inches (152 mm) from the sidewall or Listed
residential, 200" F (93° C) maximum temperature rated, horizontal sidewall
sprinklers located in accordance with their Listing and a maximum distance
between sprinklers not to exceed 14 feet (4.27 m).
The following installations shall be below a smooth, flat, horizontal ceiling
construction, are limited to unobstructed construction, require the use of
Schedule 80 fittings for sizes 1-1/2 in. and greater, and require the use of FS-5
one step solvent cement. The piping shall be mounted directly to the sidewall.
Page 10 © 2013 Spears® Manufacturing Company FG-3-1010
• Listed light hazard, extended coverage, quick response,175' F (79° C)
maximum temperature rated, horizontal sidewall sprinklers having
deflectors installed within 12 inches (304 mm) from the ceiling and within
6 inches (152 mm) from the sidewall, a maximum distance between
sprinklers not to exceed 16 feet (4.87 m), and an application density not
less than 0.10 gpm/ft' (4.08 mm/min).
• Listed residential, 165' F (74° C) maximum temperature rated, horizontal
sidewall sprinklers having deflectors installed within 12 inches (304
mm) from the ceiling and within 6 inches (152 mm) from the sidewall, a
maximum distance between sprinklers not to exceed 18 feet (5.48 m), and
an application density not less than 0.10 gpm/d' (4.08 mm/min).
• Listed light hazard, extended coverage, quick response 165° F (74° C)
maximum temperature rated, horizontal sidewall sprinklers having
deflectors installed within 12 inches (304 mm) from the ceiling and within
6 Inches (152 mm) from the sidewall, a maximum distance between
sprinklers not to exceed 18 feet (5.48 m), and an application density not
less than 0.10 gpm/ft' (4.08 mm/min).
• Listed light hazard, extended coverage, quick response,155° F (68° C)
maximum temperature rated, horizontal sidewall sprinklers (manufactured
by Reliable Automatic Sprinkler Co. Inc. SIN R40362) having deflectors
Installedwithin 12 inches (304 mm) from the ceiling and within 6 inches (152
mm)fromthesidewall,a maximum distancebetweensprinklers nolloexceed
24 feel (7.31 m), and a flow not less than 40 gpm (152 Umin) per sprinkler.
Spears® FG-3 Installation instructions must be referenced for complete
information regarding installation. Additional requirements may be listed in
NFPA 13,13D and 13R.
Unfinished Basements with Exposed Solid Wood Joist Installations
NOTICE: Use of Spears® FlameGuard® CPVC Fire Sprinkler Products is
limited to basements where the quantity and combustibility of contents is
low and fires with relatively low rates of heat release are expected. Refer to
NFPA 13D,'Standard for Installation of Sprinkler Systems in One and Two
Family Dwellings and Manufactured Homes', for more information regarding
installation in unfinished basements with exposed, solid woad joists.
Spears® FlameGuard® CPVC Fire Sprinkler Products can be installed in
unfinished basements with exposed, solid wood joists with the following
limitations:
1. The ceiling shall be horizontal and constructed utilizing nominal in. x 10 in.
solid wood joists on 16 in. centers.
OR
The ceiling must be horizontal and constructed utilizing nominal in. x 12 in.
solid wood joists on 16 in. centers. When installing Spears® FlameGuarda
CPVC Fire Sprinkler Products In conjunction with 2 in. x 12 in. solid wood
joists, the maximum system working pressure under floWng conditions must
not exceed 100 psi and the maximum system working pressure under non -
flowing conditions must not exceed 175 psi.
2. Schedule 80 fittings are required for installations involving 1-1/2' through 3'
piping.
3. The distance from the floor to the bottom of the solid wood joists must be
between 7 it and 8 it
4. All system mains shall be run perpendicular to the joists. All branch lines
shall be run parallel to the joists.
5. When the total protected area exceeds 1,000 square feet, blocking shall be
utilized to divide the area into individual compartments not exceeding 1,000
square feet.
FG-3-1010 m 2013 Spears• Manufacturing Company Page 11
6. The maximum length along the joist must not exceed 32 feel. When the
length exceeds 32 feet, blocking must be utilized. The blocking must be
constructed of minimum 1/2 in. plywood and shall be the full depth of the
wood joists. Refer to drawing below.
Sdid W.d
Center Wall Riser with Center Room Main
Center Wall Riser with Main at Wall
Riser In Corner
7. Listed residential pendent sprinklers with a maximum temperature rating
of 155' F and a minimum K-factor of 3.0 must be used for this type of
installation. NOTE:The maximumsprinklerspacing shall notexceed 12feet.
The system must be designed to ILL Listed flows for the sprinklers being
used. However, the flow must not be less than 11 gpm per sprinkler.
Sprinklers must be installed with the deflectors below the solid wood
joists for future Installation of a finished ceiling. However, deflector
placement must not exceed 1-3/4 inches below the solid wood joist (refer
to following Figures W and V). For more information, refer to NFPA
131), "Standard for Installation of Sprinkler Systems in One and Two
Family Dwellings and Manufactured Homes'.
mg
14 Joist
Depth Max.
PlP
Max.
FG-3-1010 02013 Spears® Manufacturing Company Page 13
9. When installing Spears® FlameGuard® CPVC Fire Sprinkler Products
perpendicular (system mains) to the solid wood joists, UL Listed support
devices for thermoplastic sprinkler piping or other UL Listed support
devices shall be used which mount the piping directly to the bottom of the
solid wood joists. In addition, It is acceptable to cut holes in the solid wood
joists at or below the center of the depth of the solid wood joist for support.
Holes must be oversized to allow for movement and must be located
in an area that will not compromise joist integrity. Consult the authority
having jurisdiction for more information regarding structural integrity.
10. When installing Spears® FlameGuard® CPVC Fire Sprinkler Products
parallel (branch lines) to the solid wood joists, the pipe and fittings must
be installed in the cavity below the bottom of the ceiling and above the
bottom of the joist Branch lines must be located at or below the center
of the depth of the solid wood joist. UL Listed support devices must be
used to mount piping directly to nominal in. wood blocking. In addition,
UL Listed support devices can be used that offset the pipe a nominal
distance of 1-1/2 in. from the solid wood joists.
Extended Coverage Quick Response Sprinklers
In accordance with the UL Listing, Spears® FlameGuard® CPVC Fire Sprinkler
Products may be installed without protection (exposed) when subject to the
following additional limitations:
1. Exposed piping is to be installed below a smooth, flat, horizontal ceiling
construction.
2. Listed pendent, light hazard, quick response, extended coverage
sprinklers,155° F maximum temperature rating having deflectors installed
within 8 in. from the ceiling and a maximum distance between sprinklers
not to exceed 20 ft. with an application density of at least 0.10 gpnvsgft.
3. Listed pendent residential sprinklers, 1550 F maximum temperature rating
having deflectors installed within 8 in. from the ceiling and a maximum
distance between sprinklers not to exceed 20 ft. with an application
density of at least 0.10 gpm/sgtt.
4. Listed horizontal sidewall, light hazard, quick response, extended
coverage sprinklers, 165' F maximum temperature rating having
deflectors installed within 6 in. from the ceiling and within 4 in. from the
sidewall and a maximum distance between sprinklers not to exceed 18 ff.
with an application density of at least 0.10 gpm/sqft.
5. Listed horizontal sidewall residential sprinklers, 1650 F maximum
temperature rating having deflectors installed within 6 in. from the ceiling
and within 4 in. from the sidewall and a maximum distance between
sprinklers and not to exceed 18 ft. with an application density of at least
0.10 gpm/sgfL
6. When using fittings in the 1-1/2 in. and greater size only Schedule 80
fittings maybe used.
7. The end use application is limited to unobstructed construction.
8. All solventcemenljointsshall bemadewithSpears®FSSOne Step Solvent
Cement, or any other cements referenced on page 23 of this manual.
Page 14 m 2013 Spears® Manufacturing Company FG-3-1010
Return Air Plenum Installation
Spears® FlameGuard° CPVC Fire Sprinkler Products meet the combustibility
requirements for thermoplastic sprinkler pipe, as described in the Standard
for Installation of Air Conditioning and Ventilating Systems, NFPA 90A.
Spears® FlameGuard® CPVC Fire Sprinkler Products may be installed in
the plenum space adjacent to, but not over, an opening in the ceiling, such as
a ventilation grill.
Garage Installations
Spears® FlameGuard® CPVC Fire Sprinkler Products are suitable for use
in garages requiring sprinklers, as defined in NFPA 13R, with the following
requirements:
Minimum protection consisting of either one layer of 3/8-Inch thick gypsum or
1/2-inch thick plywood must be provided.
Listed pendent or sidewall sprinklers with a maximum temperature rating of
225' F (107' C) must be used.
All sprinklers must be installed per the manufacturer's published installation
instructions.
The system must be installed per the requirements of NFPA 13R and these
installation instructions.
Ambient Temperature Limitations
Spears® FlameGuard® CPVC Fire Sprinkler Products are suitable for use in
areas where ambient temperatures are within the range of 35° F (2° C) to
150' F (65° C). The Loss Prevention Certification Board (LPCB) listing stales
the maximum ambient temperature shall not exceed 120° F (50' C).
High Temperature Areas
Spears® FlameGuard® CPVC Fire Sprinkler Products can be installed in areas,
such as an attic, where the ambient temperature exceeds 150' F (65' C) If
ventilator is provided or if insulation is used around the product to maintain
a cooler environment.
WARNING: DO NOT install Spears' FlameGuard' CPVC Fire Sprinkler
Products in areas where the ambient temperature exceeds 150' F (65° C)
without adequate ventilation or insulation around the product to maintain
a cooler environment.
Cold Temperature Areas
Spears® FlameGuard® CPVC Fire Sprinkler Products can be used In areas
where the ambient temperature remains above 35° F (2' C). These products
can also be used in an area subject to freezing temperatures g the sprinkler
system installation is protected from freezing. Many standard cold weather
piping design and installation practices can be used to protect the system
from freezing, including, but not limited to the use of low pressure dry
pipe and pre -action systems (see tilled section in this manual), the use of
glycerin, insulation installation techniques, and pipe Insulation. Contact the
manufacturers for compatibility of their products with Spears® FlameGuard®
CPVC Fire Sprinkler Products.
FG-3-1010 m 2013 Spears® Manufacturing Company Page 15
NOTE: Attention must be given to local insulating techniques and codes
that require a particular method. Since very cold weather will make Spears®
FlameGuard® CPVC Fire Sprinkler Products more susceptible to damage,
extra care should be taken to avoid rough handling or impact to these products.
WARNING: DO NOT allow a sprinkler system to freeze. A frozen system
will deactivate and the pressures built up can cause the sprinkler heads
to open or damage the pipe and fittings.
Antifreeze solutions of water and USP or CP grade GLYCERIN are acceptable
for use with Spears® FlameGuard® CPVC Fire Sprinkler Products. Refer to
NFPA 13, NFPA 13R, NFPA 13D and consult the local authority having
jurisdiction before using glycerin solutions in fire sprinkler applications.
WARNING: DO NOT use glycol -based antifreeze solutions. Glycol
solutions are not chemically compatible with the CPVC material and can
cause damage to the CPVC Fire Sprinkler System.
The following information can be used to determine the quantity of a glycerin
based antifreeze solution needed to protect the piping system.
Nominal Pipe
Size -inch
Actual mm Size
US Gallons of Water
Per Foot
3/4 (DN20)
26,9
.0311
1 (DN25)
33.7
.0494
1-1/4 (DN32)
42,4
.0792
1-1/2 (DN40)
48.3
.1042
2 (DN50)
60,3
.1636
2-1/2 (DN65)
73,0
.2395
3 (DN80)
88,9
.3555
NOTE: The gallons per foot column can be used for calculations when adding
GLYCERIN to the piping system for freeze protection. All fire protection
systems wintertzed with glycerin solutions must conform to local, state, and
NFPA requirements. Glycerin based solutions are the only antifreeze solutions
recommended for use. Glycol solutions are not chemically compatible with
the CPVC material, and their use may result in damage to the CPVC Fire
Sprinkler System.
Fire Sprinkler System Risers
In accordance with the UL Listing, Spears® FlameGuard® CPVC Fire Sprinkler
Products may be used as system risers in accordance with NFPA 13D and
13R when subject to the following additional limitations:
1. When installed protected (concealed), the minimum protection shall
consist of either one layer of 3/8 in. (9.5 mm) thick gypsum wallboard or
1/2 in. (12.7 mm) thick plywood.
Page 16 02013 Spears® Manufacturing Company FG-3-1010
2. When installed without protection (exposed), the following limitations shall
apply:
a) The riser shall be installed below a smooth, flat, horizontal ceiling
construction. A Listed residential pendent sprinkler is to be installed
with its deflector at the distance from the ceiling specified In the
sprinkler Listing.
OR
The riser shall be installed below a horizontal unfinished basement
ceiling (in accordance with NFPA 13D) constructed utilizing nominal
2 in. x 10 in. or nominal 2 in. x 12 In. exposed solid wood joists on
16 in. centers. A Listed residential pendent sprinkler is to be installed
with its deflector a maximum of 1-3/4 in. below the bottom of the solid
wood joist in anticipation of future installation of a finished ceiling.
• When installing Spears® FlameGuard® CPVC Fire Sprinkler
Products in conjunction with 2 in. x 12 in. solid wood joists, the
maximum system working pressure under flowing conditions
shall not exceed 100 psi and the maximum system working
pressure under static (nonflowing) conditions shall not
exceed 175 psi.
b) The Listed residential pendent sprinkler is to have a maximum
temperature rating of 155° F and a minimum K-factor of 3.0 and is to
be installed at a maximum horizontal distance of 12 inches from the
centedine of the riser. The system Is to be designed based upon the
Listed flows for the sprinkler being used. However, the flow must not
be less than 11 gpm per sprinkler.
c) The riser shall be supported vertically within 2 feet of the ceiling or
bottom of the joist.
d) The minimum riser diameter shall be 1 in. and the maximum riser
diameter shall be 2In.
e) The maximum distance between the wall(s) and the outside surface
of the riser pipe shall be 1-1/2 in.
Q All solvent cement joints shall be made with Spears® FS5, or any of
the solvent cements referenced on page 23 of this manual.
g) These installations require the use of Schedule 80 fittings for riser
sizes 1-W in. and larger.
3. The system shall be installed per the requirements of NFPA 13, Support
of Risers. Sections 9.2.5 (2002 Edition).
4. SpearseFlameGuard°CPVCFire Sprinkler Products shall beinstalled per
the manufacturer's installation and design manual and this addendum.
5. Risers shall be supported by pipe clamps or by hangers located on the
horizontal connection close to the riser. Only Listed hangers and clamps
shall be used.
6. Vertical lines must be supported at intervals, described in 7 & 8 below, to
avoid placing excessive load on a fitting at the lower end. Do this by using
riser clamps or double bolt pipe clamps Listed for this service. The clamps
must not exert compressive stresses on the pipe. If possible, the clamps
should be located just below a fitting so that the shoulder of the fitting rests
against the clamp. If necessary, a coupling can be modified and adhered
to the pipe as a bearing support such that the shoulder of the fitting
rests on the clamp. Follow the manufacturer's recommended cure time.
FG-3-1010 92013 Spears® Manufacturing Company Page 17
7. Recommended method for securing CPVC fire sprinkler pipe vertically.
Place clamp below shoulder of fitting.
WARNING: Modified riser collar shall only be used to provide support to the
riser and shall not be used to join two pieces of pipe.
emdcm
aam.cu.ra-
m.Wreaen...0
m v0
OF
I Cut
{ --Above
I; Seat
Top View CPerpendicular Seat nwkn
Cut
8. Do not use dserclampsthat squeeze the pipe and depend oncompression
of the pipe to support the weight.
9. Hangers and straps shall not compress, distort, cut or abrade the piping
and shall allowforfree movement of the pipe to allowfor thermal expansion
and contraction.
10. Maintain vertical piping in straight alignment with supports at each Itoor
level, or at 10 feet (3.05 m) intervals, whichever is less.
11. CPVC risers in vertical shafts or in buildings with ceilings over 25 feet
(7.62 m), shall be aligned straight and supported at each floor level, or at
10 feet (3.05 m) intervals, whichever is less.
Underground Fire Service
Spears® FlameGuard® CPVC Sprinkler Products are UL Listed for use in
underground water service when installation is in accordance with:
• ASTM D 2774, 'Standard Recommended Practice for Underground
Installation of Thermoplastic Pressure Piping"
• ASTM F 645, 'Standard Guide for Selection, Design and Installation of
Thermoplastic Water Pressure Piping Systems"
• NFPA 24, 'Standard for the Installation of Private Fire Service Mains and
Their Appurtenances"
The installation procedures detailed in this manual apply to CPVC Fire
Sprinkler Products with solvent cemented joints in sizes 314 inch through
3 inches.
C•UL Listing Requirements
Spears® FlameGuard° CPVC Fire Sprinkler Products are C-UL Listed In
accordance with Canadian requirements for use in:
Light Hazard occupancies defined in the Standard for Installation of Sprinkler
Systems, NFPA 13.
Page 18 C 2013 Spears® Manufacturing Company FG-3-1010
Residential occupancies as defined In the Standard for Installation of Sprinkler
Systems in Residential Occupancies up to Four Stories in Height, NFPA 13R.
Residential occupancies as defined in the Standard for Installation of Sprinkler
Systems in One and Two Family Dwelling and Manufactured Homes,
NFPA 13D.
Protected Installations
When used with standard response sprinklers, protection shall be provided
for Spears° CPVC piping products by ceilings, walls or soffits consisting of
the following minimum protection: lath and plaster, 9.5 mm thick gypsum
wallboard, 13 mm thick plywood or a suspended membrane ceiling with lay -
in panels or tiles, classified with respect to surface burning characteristics
having mass of not less than 1.7 kg/sq in and installed in steel suspension
grids. The effectiveness of this protection can be impaired if penetrated by
openings such as ventilation grills, exhaust fans connected to metal ducts
serving washrooms excepted. Where such penetration is present, individual
openings exceeding 0.03 sq in but not exceeding 0.71 sq m in an area must
be located so that the distance from the edge of the opening to the nearest
sprinkler does not exceed 300 mm. This piping shall not be used where such
openings exceed 0.71 sq in in area. The effect of the presence of non -rated
recessed lighting fixtures, public address speakers and other interruptions of
the protective membrane has not been investigated.
Exposed Installations
As an alternative to the protection requirements, Spears® FlameGuard® CPVC
Fire Sprinkler Products may be installed without protection (exposed) when
subject to the following additional limitations:
• Exposed piping is to be installed below a smooth, flat, horizontal, fixed
ceiling construction.
• Listed Quick -Response pendent sprinklers having deflectors installed within
8 inches from ceiling or Listed Residential pendent located in accordance
with their Listing and a maximum distance between sprinklers not to exceed
15 feet
• Listed Quick -Response horizontal sidewall sprinklers having deflectors
installed within 6 inches from the ceiling and within 4 inches of the sidewall
or Listed Residential horizontal sidewall sprinklers located in accordance
with their Listing and a maximum distance between sprinklers notto exceed
14 feet
During remodeling or repair, appropriate precautions shall be implemented to
properly shield the piping from the protected occupancy.
Spears® FlameGuard® CPVC Fire Sprinkler Piping Products are to be installed
in accordance with the requirements specified in NFPA 13, NFPA 13R or
NFPA 13D and the National Building Code of Canada. Spears® FlameGuard°
CPVC Fire Sprinkler Piping Products must be installed in accordance with the
other special installation and design criteria relative to handling, assembly,
pipe hanger spacing, piping and sprinkler restraint, sprinkler temperature
rating, piping location, testing procedures, friction loss characteristics and
other applicable requirements specified in the manual. The use of Spears®
FlameGuard° CPVC Fire Sprinkler Products In ceiling spaces above non-
sprinklered areas has not been investigated.
FG-3-1010 © 2013 Spears® Manufacturing Company Page 19
Spears° FlameGuardO CPVC Fire Sprinkler Piping Products are Listed for use
in wet pipe systems only, and are not Listed for outdoor use.
Spears® FlameGuardO CPVC Fire Sprinkler Products are C-UL Listed in
accordance with Canadian requirements for use in combination with CPVC
sprinkler products Listed in accordance with Canadian requirements and
manufactured by Victaulic (pipe and fittings), Harvel (pipe), Ipex (pipe and
fittings), NCO Fire Products (pipe and fittings), Viking (pipe), or Nibco
(fittings).
NOTICE: While Spears° FlameGuard® CPVC Fire Sprinkler Products are
Listed for use in combination with other listed manufacturers' products, specific
application approvals may not be the same amongst manufacturers. It is the
installer's responsibility to verify suitability of products used in combination
according to each manufacturer's installation instructions. Contact Spears® if
you have questions on any application not addressed. -
Spears® recommends the use of FS-5 One Step Low VOC Solvent Cement.
However, Victaulic 899; Ipex BM-5; Central Sprinkler CSC-500; Nibco FP-1000
and TYCO Fire Products TFP-500 CPVC Solvent Cements can also be used
in place of the FS-5 One Step Low VOC Solvent Cement provided that the
assembly and curing information referenced within this manual is used.
Factory Mutual Approvals FM
APPROVED
Spears® FlameGuardO CPVC Fire Sprinkler Products have been approved by
Factory Mutual for use in exposed environments in Light Hazard Occupancies
as defined in:
NFPA 13, the Standard for "Installation of Sprinkler Systems."
Residential occupancies, as defined in NFPA 13R, the Standard for"Installation
of Sprinkler Systems in Residential Occupancies up to and Including Four
Stories in Height."
Residential occupancies, as defined in NFPA 13D, the Standard for°Installation
of Sprinkler Systems in One and Two Family Dwellings and Manufactured
Homes'
Spears® FlameGuard® CPVC Fire Sprinkler Products are FM Approved for
use with Fire Resistant Barriers for CPVC Pipe and Fittings in Light Hazard
Occupancies under FM Approval of the Soffi-Steelm System manufactured
by Grice Engineering, Inc. Installation is to be made In accordance with the
FM Approval requirements for the Soffi-SteelT1 System.
Loss Prevention Certification Board LPCB iT W
LOBS P&EV¢NTION
Oau,unoNEo+eo
SpearsO FlameGuardO CPVC Fire Sprinkler Products are approved for use
as agreed between plastics suppliers, purchaserfinstaller, authority having
jurisdiction and/or insurer in accordance with documented supplier Installation
Instructions but subject to the following criteria taking precedence:
Page 20 0 2013 Spears° Manufacturing Company FG-3-1010
• Use of plastic pipe and fittings Is subject to water authority agreement for
the territory concerned.
• _PCB Approved quick response sprinklers shall be used with exposed (i.e.,
fire exposure) plastic pipe and filings.
• Plastic pipe and fittings are suitable for use only with wet pipe systems.
• Care should be exercised to ensure that joints are adequately cured,
in accordance with the manufacturer's installation instructions prior to
pressurization.
• Plastic pipe and fittings shall not be installed outdoors.
• Where plastic pipe and fittings are exposed (i.e., fire exposure), the system
shall be installed close to a flat ceiling construction.
• Sprinkler systems which employ plastic pipe and fittings shall be designed
where possible to ensure no 'no flow" sections of pipework in the event of
sprinkleroperation.
In addition, the maximum normal ambient temperature shall not exceed
120° F (50° C). The product shall only be installed in the UK by LPCB
Certificated or Registered installing companies or by firms outside the UK who
can provide evidence of personnel training in the installation of the product.
NSF International NSF
Spears® FlameGuard® CPVC Fire Sprinkler Products have been approved
by NSF® for potable water applications. These products meet all applicable
performance standards for a pressure rated application, as required in ANSI/
NSF@ Standard 14, and they comply with ANSIINSF@ Standard 61 for health
effects. Spears® FlameGuard@ CPVC Fire Sprinkler Products are tested
againstASTM Standards F 438 and F 439.
Penetrating Fire -rated Walls & Partitions
Before beginning, consultthe building codes and authorities having jurisdiction
in your area. Several UL Classified, through -penetration firestop systems are
approved for use with CPVC pipe. Consult the UL Building Materials Directory,
the UL Fire Resistance Directory, and the system manufacturer for proper
selection and application. Two manufacturers of Listed systems for use with
CPVC pipe are Nelson Fire Stop Products (800-331-7325) and Tremco (800-
321-7906). Consult Spears@ Manufacturing Company for further information.
Heal Sources & Open Ceiling Areas
Piping systems using Spears@ FlameGuard@ CPVC Fire Sprinkler Products
must be laid out so that the piping is not closely exposed to heat producing
sources, such as light fixtures, ballasts, and steam lines. Pipe must not be
positioned directly over open ventilation grills. During remodeling or ceiling
repair, appropriate precautions must be implemented to properly protect
the piping.
FG-3-1010 © 2013 Spears° Manufacturing Company Page 21
Use With Other Manufacturers' Pipes, Fittings, & Solvent Cements
Spears° FlameGuard° CPVC Fire Sprinkler Products may be used only
in connection with UL, FM and NSF® certified CPVC products of other
manufacturers. Use of Spears° FlameGuard® CPVC Fire Sprinkler Products
in connection with CPVC products of other manufacturers which are not ILL,
FM and NSFo certified may result in inappropriate product application and
inconsistent determinations in the event of warranty claims.
Spears® FlameGuard® CPVC Fire Sprinkler Products are UL Listed for use
in combination with UL Listed CPVC sprinkler products manufactured by
Victaulic (pipe and fittings), Harvel (pipe), Ipex (pipe and fittings), TYCO Fire
Products (pipe and fittings), Viking (pipe), or Nibco (fittings).
NOTICE: While Spears® FlameGuard® CPVC Fire Sprinkler Products are UL
Listed for use in combination with other listed manufacturers' products, specific
application approvals may not be the same amongst manufacturers. It is the
installer's responsibility to verify suitability of products used in combination
according to each manufacturer's installation Instructions. Contact Spears® if
you have questions on any application not addressed in this manual.
Spears° recommends the use of FSS One Step Low VOC Solvent Cement.
However, Victaulic e99; Ipex BM-5; Central Sprinkler CSC-500; Nibco FP-1000
and TYCO Fire Products TFP-500 CPVC Solvent Cements can also be used
in place of the FSS One Step Low VOC Solvent Cement, provided that the
assembly and curing information referenced within this manual is used.
Installation & Joining
Make sure you follow all assembly and curing information referenced within this
manual when installing Spears® FlameGuard® CPVC Fire Sprinkler Products.
Failure to follow this instruction could cause improper curing, resulting in serious
personal injury, significant property damage, joint leakage, or joint failure.
Before assembling any Spears® FlameGuard° CPVC Fire Sprinkler Products,
you must inspect all components for cuts, scratches, gouges, split ends, or
any other irregularities that have occurred during shipping and handling.
Solvent Cement Welded Joints
Cut Pipe Square.
CPVC pipe can be easily cut with a ratchet cutter,
a wheel -type plastic tubing cutter, a power saw
or a fine toothed saw. Tools used to cut CPVC
must be designed for plastic use and must be
in good condition in accordance with the tool
manufacturer's recommendations. It is important
to cut the pipe square. Asquare cut provides the
surface of the pipe with maximum bonding area.
If any indication of damage or cracking is evident at the pipe end, cut off at
least 2 inches (50 mm) beyond any visible crack.
Notice: Avoid splitting the pipe when using ratchet cutters. Failure to do so
may result in pipe failure or leakage.
• Only use ratchet cutters that contain a sharp blade (blades dull quickly).
• Only use ratchet cutters at temperatures of 50• F If 0° C) or warmer.
• Only use well -maintained, good quality ratchet cutters capable of consistently
cutting the pipe squarely.
Page 22 02013 Spears° Manufacturing Company FG-34010
Deburr & Bevel Pipe
Burrs and filings can prevent proper contact between pipe and fitting during
assembly, and must be removed from the outside and the inside of the pipe.
A chamfering/reaming tool or a file is
suitable for this purpose. A slight bevel
(approximately 10° to 15°) shall be placed
at the end of the pipe to ease entry of the
pipe into the socket. This will minimize
the chance that the edges of the pipe will
wipe solvent cement from the fitting socket
during the insertion of the pipe.
Fitting Preparation
The pipe should enter the filling socket easily one-third to two-thirds of the
way (full interference fit). Contact between the pipe and fitting is essential in
making a good joint. If the pipe bottoms Full Fit
with little interference (net fit), use extra
solvent cement in making the joint �Q t
This contact allows the solvent cement
(which is applied in the next step) to -f 2
effectivelyjoin the pipe and filfing. Net Fit
Using a clean, dry rag, wipe loose dirt and moisture from the fitting socket
and pipe end. Moisture can slow the cure time and at this stage of assembly,
excessive water can reduce joint strength.
Solvent Cement Application
CAUTION: Prior to using Spears° FS-5 One -Step CPVC solvent cement, or
other approved CPVC fire sprinkler cement, review and follow all precautions
found on the container labels, material safely data sheet, and Standard
Practice for Safe Handling ASTM F 402. Failure to follow precautions may
result in injury.
Special rare shall be exercised when assembling CPVC fire sprinkler systems
in temperatures below 40° F (4' C). In colder temperatures extra time must
be allowed for the solvent cement to set and cure. Extra care should be taken
to prevent damaging the pipe during handling. When solvent welding pipe and
fittings in colder temperatures, make certain that the cement has not become
lumpy or has 'gelled". Gelled cement must be discarded.
At temperatures above 80' F (27° C) make sure both surfaces to be joined
are still wet with cement during assembly. Higher temperatures and/or wind
accelerate the evaporation of the volatile solvents in the cement. Pipe stored
in direct sunlight may have surface temperatures 20° F to 30' F above the air
temperature. If possible store the pipe and fittings, or, at least, the ends to be
solvent welded, out of the direct sunlight prior to cementing. The solvents will
penetrate hot surfaces more deeply. In conditions like this it is very important
to avoid puddling the solvent cement inside the fitting socket.
Use a dauber that is property sized for the pipe, no less than 112 the diameter of
the pipe being assembled.
Only use solvent cements that have been specifically formulated and listed/
approved for use with CPVC fire sprinkler systems and approved by the pipe
and fitting manufacturers.
FG-3-1010 O 2013 Spears° Manufacturing Company Page 23
Vigorously apply a heavy, even coat of cement to the outside pipe end. Apply
a medium coal to the fitting socket. Pipe sizes 1-1A inch (DN32, 32mm)
and above shall always receive a second cement application on the pipe
end. FIRST APPLY CEMENT ON THE PIPE END, THEN IN THE FITTING
SOCKET, AND, FINALLY, ON THE PIPE END AGAIN.
'�*� f W4(J/
Notice: Too much solvent cement can cause clogged waterways or weaken
the wall of the pipe or fitting and result in pipe failure or leakage.
• Do not allow excess cement to puddle in the pipe and fitting assembly. To
prevent this puddling, apply a lighter coating of solvent cement to the inside of
the fitting socket than the outside of the pipe.
• Wipe off excess cement on the outside of the joint. The solvents will
evaporate, but the solvent cement inside the fitting will stay there.
• Take care to prevent cement from running into the threads of Sprinkler
Head Adapters and Adjustable Sprinkler Head Adapters. Where possible, it
is recommended to pre -install head adapters on to pre-cut Drops (section of
pipe) and allow to achieve initial set in the inverted position. The head adapter
and drop combination can then be installed into the system fitting.
Assembly
After applying cement, immediately insert the pipe into the fitting socket, while
rotating the pipe one -quarter turn unfit the pipe bottoms out at the fitting stop.
Rotate the pipe as it is inserted into the fitting not after it has bottomed out
in the fitting. Properly align the fitting for the installation at this time. Pipe
must bottom to the stop. Hold the assembly for 30 seconds to ensure initial
bonding. A bead of solvent cement should be evident around the pipe and
fitting juncture. If this bead is not continuous around the socket shoulder, it
may indicate that insufficient cement was applied. If insufficient cement is
applied, the fitting must be cut out and discarded. Cement in excess of the
bead should be wiped off with a rag.
14:j r Be
�Conlinuous
ad
Notice: Failure to allow sprinkler head adapter fitting joints to cure before
installing sprinklers may result in cement in the sprinkler waterway.
• Install sprinkler heads only after all the CPVC pipe and fittings, including
the sprinkler head adapters, are solvent welded and allowed to cure for a
minimum of 30 minutes.
• Do not install sprinklers in the fiWngs prior to the fittings being cemented
in place.
Page 24 02013 Spears® Manufacturing Company FG-3-1010
- Prior to installing any sprinklers, the entire system including drops must
be thoroughly flushed to remove all pipe shavings, dirt and debris left from
installation. Fill lines slowly and bleed air from the farthest and highest point,
then flush with full flow.
Exercise care when installing sprinklers. Allow sprinkler head fittings and
previoustyjoined fittings to cure for a minimum of 30 minutes prior to installing
the sprinkler. When installing sprinklers, be sure to anchor or hold the pipe
drop securely to avoid rotating the pipe in previously cemented connections.
Notice: Too much solvent cement can cause clogged waterways.
• Usually inspect sprinkler fittings to ensure that the waterway and threads are
clear of any excess cement.
- Once the installation is complete and cured per Table I,11 or III, then test the
system as described in the System Acceptance Testing (Hydrostatic Pressure
Test) section of this manual.
Set and Cure Times
Notice: Inadequate curing of solvent cement joints may cause pipe failure
or leakage. Solvent cement set and cure times are a function of pipe size,
temperature, relative humidity, and tightness of fit.
Cure times should be increased when moisture is present such as during cut -
ins to live sprinkler lines. (NOTE: refer to Recommended Cut -In Procedures
for System Modification or Repair section in this manual.) The assembly must
be allowed to set, without any stress on the joint, for 5 minutes, depending on
pipe size and temperature. Following the initial set period, the assembly can
be handled carefully, avoiding significant stresses to the joint
Refer to Tables I, II, and III for MINIMUM cure times prior to pressure testing.
Table 1: Minimum Cure Time Table for Pressure Test up to 225 psi (15.5 bar)
Ambient Temperature During Cure
Nominal
60' F to 120' F
40' F to 59' F
0' F to 39' F
Pipe Sizes
(16* C to 49° C)
(4' C to 15° C)
(-18° C to Y C)
3/4' (DN20)
1 hour
4 hours
48 hours
1' (DN25)
1-1/2 hours
4 hours
48 hours
1-1/4' & 1-1/2'
(DN32 & DN40)
3 hours
32 hours
10 days
2- (DN50)
8 hours
48 hours
Note 1
2-1/2° &3'
(DN65 & DN80)
24 hours
96 hours
Note 1
FG-3-1010 0 2013 Spears® Manufacturing Company Page 25
Table 2: Minimum Cure Time Table for Pressure Test up to 200 psi (13.8 bar)
Ambient Temperature During Cure
Nominal
60° F to 120° F
40' F to 59° F
0' F to 39' F
Pipe Sizes
(16' C to 49° C)
(4° C to 15' C)
(-18' C to 3° C)
3/4- (DN20)
45 minutes
1.1/2 hours
24 hr.
1' (DN25)
45 minutes
1-1/2 hours
24 hr.
1-1/4' & 1-1/2'
(DN32 & DN40)
1-1/2 hours
16 hours
120 hours
2- (DN50)
6 hours
36 hours
Note 1
2-1/2' & 3'
(DN65 & DN80)
8 hours
72 hours
Note 1
Note 1: For these sizes, the solvent cement can be applied at temperatures below 40' F (4' C).
However, the spdnklersystem temperature must bembed to a temperature of 40' F(4'C)orabove
and allowed to cure per the above recommendations prior to pressure testing.
Table 3: Minimum Cure Time Table for Pressure Test up to 100 psi (6.9 bar)
Ambient Temperature During Cure
Nominal
Pipe Sizes
60' F to 120' F
(16' C to 49° C)
40' F to 59° F
(4° C to 15" C)
0° F to 39° F
(-18' C to 3' C)
3/4' (DN20)
15 minutes
15 minutes
30 minutes
1' (DN25)
15 minutes
30 minutes
30 minutes
1-1/4' (DN32)
15 minutes
30 minutes
2 hours
NOTICE: 1-112-Inch and larger must be tested ONLY in =ordance Wth Table 1 and Table 2.
WARNING: Make sureyou allowthe cement to cum accorc inglo the times listed in the charts forthe
pipe size and ambienitemperature. These cure times have been tested and approved far Spears°
FlameGuard* CPVC Fire Sprinkler products. DO NOT Instal any sprinkler heads until the piping
system has cured far a minimum of 30 minutes.
Page 26 0 2013 Spears- Manufacturing Company FG-3-1010
The following giadeUnes provide an esgmale of the quantities of Spears' FS-5 Low VOC SONent
Cement thatyou W9 need to complete the assembly.
Seli ent Cement Requirements
Solvent Cement
Nominal Fitting Sizes
Number of Joints
Per Quart (estimated)
3/4'
(DN20)
270
1'
(DN25)
180
1-1/4'
(ON32)
130
1-1/2'
(DN40)
100
T
(DN50)
70
2-1/2'
50
(ON65)
3'
(DN80)
40
Threaded Connections
WARNING: Use only thread sealant recommended by Spearse. Otherjoint
compounds or pastes may contain substances that could cause stress
cracks in the CPVC. Cutting oils used in metal pipe threading cause
stress cracking in CPVC materials. All cutting ails must be removed and
the metal pipe thoroughly flushed and degreased prior to assembly with
CPVC systems.
APPLY SEALANT ONLY TO MALE THREAD
DO NOT use a combination of
tape and paste sealants.
DO NOT clog waterway with
excessive sealant.
RECOMMENDED SEALANT.
z
B 1e' I
75
Spears® Manufacturing Company recommends the use of Spears® BLUE
75M thread sealant, which has been tested for compatibility with Spears®
products. Please follow the sealant Manufacturer's Application4nstallation
instructions. Choice of another appropriate thread sealant is at the discretion
of the installer.
ASSEMBLE JOINT BY HAND
Thread Sprinkler Head in 'finger tight" for initial assembly.
FG-3-1010 m 2013 Spears® Manufacturing Company Page 27
WRENCH MAKE-UP
Use an adjustable wrench on the
flats of the Head Adapter and
Wrench recommended by Sprinkler _ --
Manufacturer for Head. Generally,
wrench make-up of 1 to 2 turns ,
beyond finger fight is sufficient. Avoid b
'backing up the wrenched assembly.
For Sprinkler Head Adapter connections:
Metal Thread &
Special Reinforced
Zinc SR Plastic Thread
SR) Plastic Thread
Min. Torque: 15 ft: lbs.
5 ft: lbs.
Max. Torque: 20 ft.lbs.
10 fL-Ibs.
For Female Adapter transitions to metal
pipe, tighten hand -tight plus
1-112 turns.
DO NOT over -tighten.
IF A TAPE SEALANT MUST BE USED:
1. Use TFE tape no less than
2.5 mil thick.
2. initial wrap must fully cover the thread end.
3. Wrap clockwise with standard
pipe threads.
4. For Head Adapters, use ONLY 2 - 3 wraps
of tape
and lighten to specified torque.
5. For Female Adapter transition to metal pipe, use ONLY 5 - 5-112 wraps of
tape and tighten hand -tight plus 1-V2 turns.
WARNING: Always use commercially available strap wrenches. Do not
use conventional pipe wrenches that can damage fitting.
WARNING: DO NOT over -torque any threaded connections. Generally,
one to two turns beyond finger -tight are required to make a threaded
connection. Factory testing has indicated that 15 - 20 ft-Ibs of torque
on Metal Thread Head Adapters and 5 -10 ft4bs on Special Reinforced
(SR) Plastic Thread Head Adapters is adequate to obtain a leak free seal
for Sprinkler Head Installations. Transitions to metal pipe using Female
Adapters should be hand tight plus 1-112 turns.
NOTICE: Sprinkler heads must be installed only after all fire sprinkler pipe
fitfings, including the sprinkler head adapters, are cemented to the piping and
have been allowed to cure for a minimum of 30 minutes. Plastic, threaded
plugs are available for use in pressure testing. Before installing the sprinkler
head, the sprinkler head fittings must be visually inspected or probed with a
wooden dowel to ensure that the waterway and threaded areas are free of any
excess cement that may restrict the flow of water.
Page 28 0 2013 Spears° Manufacturing Company FG3-1010
TorpueSafe- Gasket Sealed Thread Connections
This type of connection can only be made when using the FlameGuard'
TorqueSafe" Gasket Female Sprinkler Head Adapter. This special adapter
has a special thread with gasket for sealing the sprinkler head. The adapter
provides a special thread insert that can be rotated for proper frame alignment
during installation. Warning: DO NOT USE ANY TYPE OF THREAD SEALANT
when installing this adapter. Use of tape or paste sealant may impair
proper sealing and function of the adapter.
ffffFM INSTALL SPRINKLER
HEAD BY HAND
Check that elastomer gasket and
threads are clean, dry and gasket
is seated at the base of the adapter
thread. Install sprinkler head hand
light into adapter. DO NOT use any
thread sealant!
WRENCH ALIGNMENT
With wrench on sprinkler head, rotate
sprinkler head clockwise unfit frame
is properly aligned (Brass insert and
Sprinkler head will rotate together.
This will require approximately 10 to
25 R-lbs torque at final orientation).
Caution: DO NOT use back-up
wrench on brass insert flats.
NEVER Reverse or Back up
Threaded Assembly. If over -
adjusted, continue to rotate
clockwise until properly aligned.
NOTE: Back-up wrench may be
applied to brass insert
removal of sprinkler he
NOTICE: Sprinkler h
installed only after at
pipe fittings, includin!
head adapters, are ce
piping and have been;
for a minimum of 30 m
threaded plugs are av
in pressure testing. Bf
the sprinkler head,
head fittings must bt
ensure that the watery
that may restrict the flow of water.
NO Tape —NO Paste
Align Sprinkler
Headframe
with Pipe
Centedine
Handinstal/
unnlsnug.
Align
Align Sidewall Sprink/er/lead & Frame
HorizonlaW
FG-3-1010 02013 Spears® Manufacturing Company Page 29
Painting Pipe & Fittings
CAUTION: The UL Listing DOES NOT cover painted CPVC fire sprinkler
piping products. Use of certain paints, such as oil -based, ran damage CPVC
fire sprinkler piping products. Before painting any CPVC fire sprinkler piping
products, you must consult with your local authority having jurisdiction for
restrictions.
Cleaning
Spears° FlameGuard® CPVC Fire Sprinkler Products can be cleaned using
a mild soap and water solution. DO NOT use ammonia or other harsh
chemical cleaners.
Transitions to Other Materials
Specifically designed female threaded adapters, grooved coupling adapters,
and flanges are Listed for connecting systems incorporating Spears®
FlameGuard® CPVC Fire Sprinkler Products to other materials, valves, and
accessories. A special, reinforced female threaded adapter Is available for
connection to the sprinkler head.
Flanged Connections
Piping runs joined to the Flanges must be installed in a straight line in relation
to the flange to avoid stress at the flange due to misalignment. In addition,
piping must be secured and supported to prevent lateral movement, which
can create stress and damage the flange. Use only full-faced, Grade E,
EPDM,1/8' thick flange gaskets.
RILIM Attach Flange to Pipe.
The flange must be attached to UL Listed CPVC pipe following procedures for
Solvent Cement Welded Joints in this manual.
NOTICE: When using 'One -Piece" type flanges (fixed flange ring), care
must be taken to align bolt holes with mating flange during solvent welding
installation to pipe, or assure that pipe in system can be adequately rotated
for correct hole alignment.
E11fya Position Gasket & Align Flanges.
With gasket between flanges, align gasket and mating flange bolt holes by
rotating flange ring (see notice above).
Install Bolts, Nuts, & Washers.
Bolts should be lubricated with an acceptable anti -seize lubricant (such as IMS
Copper Flake). Insert required bolts through flange bolt holes being sure to
use two (2) flat washers per bolt, one at head and one below nut. Make sure
that mating flanges are flush against gasket and property aligned. Tighten
nuts by hand until snug.
WARNING: Certain lubricants can cause stress cracking in CPVC
materials.
lIIIUL-■ Tighten Flange Bolts.
Establish uniform pressure over the flange face by lightening bolts in
5-fit. lbs. increments using the sequence shown in Figure 1 and specified
torque values.
Page 30 © 2013 Spears® Manufacturing Company FG-3-1010
CAUTION: DO NOT use bolts to draw together improperly mated flanges.
Care must be taken to avoid 'bending' the flange ring when attached to a
raised -face flange or wafer style valves.
Flange Data & Bolt Torque
The following recommendations are based on the use of two standard flat
washers, standard nuts, and 1/8-inch thick EPDM full -face gasket. Actual field
conditions may require a variation in these recommendations.
FIG.1
3 1
•
2 4
Flange Size
Recommended
Nominal In.
Torque ft-lbs (N-m)
314 to 1-1/2
12
(DN20-DN40)
(16,3)
2 to 3
25
(DN50-DN80)
(33,9)
Flange Size
Nominal in.
Boll
Holes
Bolt Diameter
inches (mm)
Minimum Bolt
Length inches (mm)
314
(DN20)
4
1/2
2
(50,8)
(12,7)
1
(DN25)
4
112
2-1/4
(57,2)
(12,7)
1-1/4
(DN32)
4
1/2
2-1/4
(57,2)
(12,7)
1-1/2
(DN40)
4
1/2
2-1/2
(63,5)
(12,7)
2
(DN50)
4
518
3
(76,2)
(15,9)
2-1/2&3
(DN65 & DN80)
4
618
3-1/4
(85,6)
(15.9)
Grooved Coupling Adapters
Spears® FlameGuard® CPVC Grooved Coupling Adapters are designed for
use with Victaulic Style 75 and Style 77 Flexible Couplings. Other UL Listed
couplings of similar flexible design maybe used.
CAUTION: The use of rigid style couplings will damage the Grooved Coupling
Adapter. Consult coupling manufacturer for proper selection.
Inspect Pipe & Adapter.
Check to ensure that both pipe and Grooved Coupling Adapter are free of
indentations, projections, or roll marks on the gasket seating areas. Pipe end
must be cut square and any loose scale, paint or dirt removed.
FG-3-1010 0 2013 Spears® Manufacturing Company Page 31
NOTICE: Use a -standard grade'E' (EPDM) compound gasket with a green
stripe or a grade'E; type 'A' gasket with a purple stripe that Is suitable for
wet fire sprinkler service.
Inspect & Lubricate Gasket
Be sure the gasket is clean and free of any cracks, cuts, or other defects that
could cause leaks. DO NOTall0wsolventcementto contactthe sealing surface
of the gasket. Lubricate the gasket with a vegetable soap -base lubricant to
prevent pinching and to assist in the seating and alignment process. Apply a
thin layer of lubricant to the gasket lips and exterior surface. Pre -lubricated
gaskets may be used. It is the installer's responsibility to determine both the
gasket suitability and chemical compatibility of any lubricants. Consultgasket
and lubricant manufacturers.
WARNING: Certain lubricants may contain petroleum based or other
chemical that can damage the gasket or adapter. Verify the suitability of
the lubricant with the manufacturer before use.
Align Components & Install Gasket
Place the gasket over the pipe end making sure the gasket lip does not
overhang the end of the pipe. Align the grooved coupling adapter with the
end of the pipe and slide the gasket over the seating surface of the adapter,
centering the gasket between the two grooves. Make sure the gasket is not
pinched between the pipe and the adapter filing. No portion of the gasket
should extend into the grooves.
Install Coupling
Place the coupling housings over the gasket, making sure the housing keys
engage into the grooves of the pipe and the adapter fitting. Insert the bolts
and apply the nuts finger -tight Using a socket wrench or other appropriate
tool, lighten the nuts alternately and equally until you achieve metal -to -metal
contact at the housings' bolt pads.
WARNING: You must tighten the bolts alternately and evenly to achieve
metal -to -metal contact at the housings' bolt pads.
Inspect thejoints before and after pressure testing. Look for gaps between the
bolt pads and for housing keys that are not inside the grooves. Ensure that the
pipe alignment does not place undue stress on the grooved coupling adapters.
The maximum recommended pipe hanger distance from the grooved coupling
adapter fitting is shown in the following table.
Page 32 02013 Spears® Manufacturing Company FG-3-1010
Nominal Pipe Sizes
Maximum Recommended Hanger
Spacing feet (meters)
1-1/4
6-1/2
(DN32)
(2,0)
1-1/2
7
(DN40)
(2,1)
2
8
(DN50)
(2,4)
2-1/2
9
(DN65)
(2,7)
3
10
(DN80)
(3,0)
As an added precaution to enhance the structural design of the system, it is
suggested that a hanger or support be located at or near the grooved coupling
adapter joint This hanger or support can be on either side of the coupling.
However, this is not a requirement, since the hanger spacing shown in the
above table meets the minimum requirements established by UL.
Adjustable Sprinkler Head Adapter Installation
Spears® FlameGuarde CPVC Adjustable Fire Sprinkler Head Adapter comes
pre -assembled. There is no need for lubrication. It is recommended that the
adjustable sprinkler head adapter be adjusted completely "in' by hand before
beginning the installation process.
Install Adapter on Drop.
The Adjustable Sprinkler Head Adapter must be installed in accordance with
the approved procedures for Solvent Cement Welded Joints, as outlined in
this manual. It is recommended that the drop/riser pipe be solvent cemented
into the adjustable sprinkler head adapter first, and then into the drop/riser
tee or elbow.
CAUTION: Care must be taken to prevent solvent cement from coming in
contact with the internal 0-ring seal or sealing surface. All pipe shavings, dirt
and debris must be flushed from the drop prior to adjustment. DO NOT over
extend the adjustment barrel. Extend only to the point that free movement
slops or damage to internal sealing components may result.
Install Sprinkler Head
Sprinklerhead installation must be in accordance with the approved procedures
for Threaded Connections, as outlined in this manual. The Adjustable Sprinkler
Head Adapter has multiple wrench flats provided to hold the adjustment barrel
while installing the sprinkler head. These same wrench flats must be used to
adjust the sprinkler head adapter to its required position.
CAUTION: Never use wrenches, pliers, or any other tool on the threaded
portion of the adjustment barrel. DO NOT over extend the adjustment barrel.
FG-3-1010 ® 2013 Spears® Manufacturing Company Page 33
Adjust Finished Height.
The maximum range of travel is 1-5/8". Always use multiple wrench flats for
making adjustments. Make adjustments slowly if system is pressurized in
order to avoid Inadvertently over extending adjustment barrel.
CAUTION: Cam must be taken not to extend or retract the adjustment barrel
excessively, since this may result in damage to the adapter. Adjust only to the
point that free movement stops.
For the purpose of hydraulic calculations, the adjustable sprinkler head
equivalent length of pipe in feet are as follows: 3/4'x1/2' = 64,1'xl/2' = 9-ft.
Flushing System
Prior to installing any sprinklers and testing, the entire system including drops
must be thoroughly flushed to remove all pipe shavings, dirt and debris left
from installation. Fill lines slowly and bleed air from the farthest and highest
point, then flush with full flow.
System Acceptance Testing (Hydrostatic Pressure Test)
Once an installation is completed and joints are properly cured per the above
recommendations, the system should be hydrostatically pressure tested with
water at 200 psi (13.8 bar) for 2 hours. See Table II for curing conditions at
200 psi (13.8 bar).
The system should be pressure tested with water at 50 psi (3.4 bar) In
excess of maximum pressure when the maximum system pressure is to be
maintained in excess of 150 psi (10.3 bar). See Table I for curing conditions
at 225 psi (15.5 bar). This requirement is in accordance with the requirements
established by NFPA Standard 13, Section 24.2.1 (2007 Edition).
Sprinkler systems in one- and two-family dwellings and mobile homes may
be pressure tested with water at line pressure, after following Table III curing
conditions, in accordance with the requirements established by NFPA 13D,
Section 4.3 (2007 Edition).
Prior to testing, be sure that the entire system including drops has been
thoroughly flushed to remove all pipe shavings, did and debris left from
installation as specified in the preceding section.
When pressure testing, the sprinkler system shall be slowly filled with water
and the air bled from the highest and farthest sprinkler heads before pressure
testing is applied. Air must be removed frompiping systems (plastic or metal)
to prevent it from being locked in the system when pressure is applied.
Entrapped air can generate excessive surge pressures that can result in bodily
injury and/or property damage, regardless of the piping materials used.
If a leak is found, the fitting must be cut out and discarded. A new section can
be installed using couplings or a union. Unions should be used in accessible
areas only.
Page 34 © 2013 Spears° Manufacturing Company FG-3-1010
Becommanded Cm -in Procedures for System Modification or Repair
Existing system modifications or repairs can be made using Spears®
FlameGuard® CPVC Fire Sprinkler Products. In order to maintain full system
integrity the following procedure must be followed when making a system
tie-in or repair by cutting into an existing system line. A careful review of all
Joining Procedures must be made prior to making a cut -in on an existing
system and the Minimum Cut -in Cure Times schedule listed below must be
followed. Avariety of fitting combinations can be used to tie into an existing
system or replace a section between fixed cut -in points. These include using
a socket Tee for add-ons or a socket Coupling for repairs in combination
with a mechanical joint such as a union grooved coupling adapter, or flange.
Regardless of the components selected, the following must be adhered to:
System modification cut -ins should be made on the smallest diameter pipe
section, in close proximity to the area of modification, capable of properly
supplying the system change.
Carefully plan and measure prior to cutting into existing system. Be sure to
provide adequate space and insure that full insertion into fitting sockets can
be made during assembly.
Note: Allowance must be made for making a 1/4-turn twist when inserting the
pipe into the fitting during assembly of the tee (or other component), especially
on 1-1/2' and larger pipe sizes. This may require assembly of components in
combination with the cut -In tee to create a short spool piece for final connection
using socket unions, flanges, or grooved coupling adapters.
Review all Installation & Joining procedures prior to commencing cut -in
(including square cutting, deburring & beveling, cleaning, dry fit checks).
Depressurize and drain existing line prior to making the cut -in.
Connect to the existing system prior to proceeding with the modification or
repair.
All pipe shavings, dirt, debris must be removed from the cut -in system and,
water and residual moisture must be removed from all solvent cement areas.
Vacuum lines and wipe dry with a clean dry rag. Moisture and dirt will slow the
curing and can affectjoint strength.
Use only a new can of approved solvent cement when making cut -in
connections. Verity cement expiration date on can prior to use.
Cut -ins for modifications or system repairs are often made under less than
ideal situations as compared to new installations. As a result, the following
specified Minimum Cut -in Cure times must be used.
FG-3-1010 02013 Spears° Manufacturing Company Page 35
Minimum Cut -In Cure Times
Ambient Temperature During Cure
Pipe Size
60' F to 120° F
40' F to 59° F
0' F to 39° F
Nominal In.
(16' C to 49- C)
(4' C to 15' C)
(-18' C to 3- C)
3/4' (DN20)
24 hours
24 hours
48 hours
1- (DN25)
24 hours
24 hours
48 hours
1-1/4' & 1-1/2'
(DN32 - DN40)
24 hours
32 hours
10 days
2' (DN50)
24 hours
48 hours
Note 1
2-1/2' & 3'
(DN65 - DN80)
24 hours
96 hours
Note 1
Note 1: Solvent cement can be applied at temperatures below 40° F (4' C)
in all saes. For the 2-1/2' & larger, the temperature must be raised to 40° F
(4° C) or above and allowed to cure for the recommended times before the
system is filled and pressurized. Cement, pipe or fittings brought in from colder
outside temperatures must be brought up to room temperature before using
the 60° F to 120° F cure schedule.
Following completion and proper cure, inspect for proper alignment and
hanger placement prior to pressure testing.
To pressure test the system, slowly fill the system with water and make sure
that all air is bled from the farthest and highest point before test pressure is
applied. The system MUST be pressure tested in accordance with NFPA 13,
NFPA 24, or any other applicable NFPA standard requirements. The system
must be tested with water. The purpose of the hydrostatic pressure test is
to check for leakage, and it may not identify improperly assembled joints.
This test MUST NOT be considered a substitute for full compliance to these
published installation instructions.
It is recommended that the portion of the sprinkler system containing the cut -
in tee be isolated for pressure test where possible. The applied test pressure
should not exceed 50 psi over the system pressure in order to minimize water
damage in the event that a leak occurs.
WARNING: Spears' FlameGuard• CPVC Fire Sprinkler Products must
never be used in a system for distribution of compressed air or other
gases. Air must be removed from piping systems. Entrapped air can
generate excessive surge pressures, regardless of the piping materials
used. Failure to follow this warning could result in product failure,
property damage and severe personal injury or death.
Page 36 02013 Spears® Manufacturing Company FG-3-1010
Engineering Data
Pipe and Fining Spealgcations
Spears® FlameGuard® CPVC Sprinkler Pipe is produced in SDR 13.5
dimensions, as specified in ASTM F 442. Engineering data on Material
Properties and Expansion & Contraction are provided in this manual for (A)
Spears® FlameGuard® or Victaulic FireLock® and (B) Harvel BlazeMaster®
CPVC Fire Sprinkler Pipe. Consult other manufacturers for applicable
variations
Spears® FlameGuard® CPVC Sprinkler Fittings are produced in Schedule 40
and Schedule 80 dimensions for sizes 3/4'through 1-1/4', and in Schedule 80
for sizes 1-1/2' through 3', in accordance with ASTM F 437, ASTM F 438, and
ASTM F 439 as applicable. These products are UL Listed FWApproved for
a rated working pressure of 175 psi (1200kPa)at 150' F (65° C) for sprinkler
service and LPCB listed for a rated working pressure of 175 psi (1200kPa) at
120' F (49' C).
CPVC Fire Sprinkler Pipe Dimensions
SDR 13.5 (Ref. ASTM F442)
Weight lbs/ft
(kg/m)
Size
Average
Average
Nominal inches
OD inches
ID
(mm)
inches
314
1.050
0.874
0.168
(DN20)
(26,7)
(22,5)
(0,2)
1
1.315
1.101
0.262
(DN25)
(33,4)
(28,2)
(0,4)
1-1/4
1.660
1.394
0.418
(DN32)
(42,2)
(35,6)
(0,6)
1-1/2
1.900
1.598
0.548
(DN40)
(48,3)
(40,7)
(0,7)
2
2.375
2.003
0.859
(DN50)
(60,3)
(50,9)
(1,2)
2-1/2
2.875
2.423
1.257
(DN65)
(73,0)
(61,5)
(1,2)
3
3.500
2.950
1.867
(DN80)
(88,9)
(75,0)
(1,2)
Hydraulic Design
Hydraulic calculations for the sizing of systems incorporating Spears°
FlameGuard® CPVC Fire Sprinkler Products must be calculated using a
Hazen-Wlliams C value of 150. Pipe friction loss calculations must be made
according to NFPA Standard 13. The following table shows the allowance for
friction loss for fittings, expressed as equivalent length of pipe. For additional
information regarding friction loss, contact Spearsa.
FG-3-1010 02013 Spears® Manufacturing Company Page 37
Allowance for Friction Loss In Fillings
Equivalent Feet (meters) of Pipe
3/4'
26,7
RIM
1'
33,7
mm
1-1/4"
42.4
mm
1-1/2'
48,3
mm
2"
60,3
mm
2-1/2"
73,0
mm
3'
88,9
mm
Tee Run
1(0,3)
1(0,3)
1(0.3)
1(0,3)
1(0,3)
2(0,6)
2(0,6)
Tee Branch
3(0,9)
5(1,5)
6(1,8)
8(2,4)
10(3.1)
12(3,7)
15(4.6)
90° Elbow
4(1,2)
5(1,5)
6(1,8)
7(2,1)
9(2.7)
12(3,7)
13(4,0)
45' Elbow
1(0,3)
1(0,3)
2(0,6)
2(0,6)
2 (0,6)
3(0,9)
4(1,2)
Coupling
1(0,3)
1 (0,3)
1(0,3)
1(0,3)
1(0,3)
1 2(0,6)
2(0,6)
Hangers & Suppolls
Since CPVC Fire Sprinkler pipe is rigid, it requires fewersupports than flexible,
plastic systems. Spears° recommends use of hangers that are designed and
listed for supporting the CPVC Fire Sprinkler pipe. However, some hangers
designed for steel pipe may be used if their suitability is clearly established.
These hangers must have a minimum 1/2-inch, load -bearing surface, and
they must be selected to accommodate the specific pipe size. In addition,
they cannot contain rough orsharp edges that contact the pipe, and they must
not bind the pipe from axial movement Vertical runs must be supported so
that the weight of the run is not on a fitting or a joint.
Horizontal runs must be braced so that the stress loads (caused by bending
or snaking pipe) will not be placed on a fitting or a joint. Support spacing is
shown in the following table. See "Snaking/Defiection of Pipe" in this manual
for information regarding bending or snaking CPVC Fire Sprinkler Pipe.
Pipe Size
Nominal inches
Maximum Support
Spacing feet (meters)
Wt. Water Filled
Pipe Ibs/ft (kg/m)
3/4 (DN20)
5-1/2 (1,7)
0.427 (0,635)
1 (DN25)
6(1,8)
0.674 (1,003)
1-1/4 (DN32)
6-1/2 (2,0)
1.078 (1,604)
1-1/2 (DN40)
7(2.1)
1.412 (2,101)
2 (DN50)
8(2,4)
2.223 (3,308)
2-1/2 (DN65)
9(2,7)
3.254 (4,842)
3 (DN80)
10(3.0)
4.831 (7,189)
Page 36 02013 Spears® Manufacturing Company FG-3-10 00
NFPA 13D permits 'support methods comparable to those required by local
plumbing codes.' The above hanger/support requirements must also be
followed on NFPA 13D systems.
CAUTION: DO NOT use hanger items such as plumber's tape or 'nail -on'
devices. Pipe hanger must comply with NFPA 13,13D and 13R.
When a sprinkler head activates, a significant reactive force can be exerted
on the pipe. With a pendent head, this reactive force can cause the pipe to
lit vertically if it is not secured properly, especially if the sprinkler drop is from
small diameter pipe. The pipe must be braced against the vertical lip -up with
the closest hanger. Refer to the following illustration and Table & B.
tA-� B Xa1rS pM y
BracelSuppdrt BracelSupport
Finished Ceiling Ltna
i8
Table A - Maximum Support Spacing Distance
End Line Sprinkler Bead Drop Elbow
Pipe Sae
Nominal inches
Line Pressure
<100 psi
(<689kPa)
Line Pressure
>100 psi
(>689kPa)
3/4 (DN20)
9 inches (228,6 mm)
6 inches (168,3 mm)
1 (DN25)
12 inches (304,8 mm)
9 inches (228,6 mm)
1-1/4 (DN32)
16 inches (406,4 mm)
12 inches (304,8 mm)
1-1/2 - 3 (DN40 - DN80)
24 inches (610,0 mm)
1 12 inches (304,8 mm)
Note: Support spacing can be increased by approximately 50%for lower pressures.
Table B - Maximum Support Spacing Distance
Inline Sprinkler Bead Drop Tee
Pipe Sae
Nominal inches
Line Pressure
<100 psi
(<689kPa)
Line Pressure
>100 psi
(>689kPa)
3/4 (DN20)
4 feel (1,22 meters)
3 feet' (0,91 meters)
1 (DN25)
5 feet (1,52 meters)
4 feet' (1,22 meters)
1-1/4 (DN32)
6 feet (1,83 meters)
5 feet' (1,52 meters)
1-1/2 - 3 (DN40 - DN80)17
feet(2,13 meters)
1 7 feet(2,13 meters)
Note: *Support spacing can be increased by one foot for lower pressures.
FG-3-1010 ©2013 Spears® Manufacturing Company Page 39
Numerous common methods are used to brace Fire Sprinkler Pipe. A few
acceptable methods include: use of a standard band hanger by positioning
the threaded support rod to 1116-inch above the pipe (however, it is important
that the rod does not contact the pipe), a wrap around U-hanger, a special
escutcheon which prevents upward movement of the sprinkler through the
ceiling or band hangers with Surge Restraints to provide surge protection for
the system.
Pipe hangers are available that are tested and UL Listed for fire sprinkler
service. These hangers comply with NFPA 13 requirements for use with
CPVC fire sprinkler piping systems. The following illustrations depict several
of these.
Band Hanger - designed to support CPVC piping systems when used in
conjunction with a hanging steel threaded rod that is suspended from a ceiling
or other flat, horizontal surface. The threaded rod must be leveled property
before installing the hanger and restraint.
Surge Restraint - when installed with the Band Hanger, as shown below,
provides surge protection for the system.
One Hole Wrap -Around Strap - designed to support CPVC piping systems
only when the hanger tab is in the vertical position, and the screw -type
fastener is in the horizontal position. The one -hole strap can be used as a pipe
restrainer when the hanger tab is in the downward position, but it cannot be
used as a hanger to hold any weight of the system. In addition, the one -hole
strap can be used as a piping system guide when the system lies on lop of the
beam, and the beam supports the system's weight. The one -hole strap is not
intended to support the CPVC piping system from under a ceiling or any other
flat, horizontal surface. For this application, install two -hole strap.
Z
e
0
t
Hanger
Page 40 0 2013 Spears® Manufacturing Company FG-3-1010
Two -Hole Strap -designed to support CPVC piping systems when attached to
a flat, horizontal surface with the screw -type fasteners in the vertical position.
In addition, the two -hole strap is designed to support CPVC piping systems
when attached to a flat, vertical surface with one mounting tab in the vertical
position and the screw -type fasteners in the horizontal position. The two -hole
strap can be used as a piping system guide when the system lies on top of a
beam, and the beam supports the system's weight.
Two -Hole 90° Side Mount Strap - designed to support CPVC piping systems
when attached to a horizontal beam with the screw -type fasteners in the
horizontal position and the pipe hanging below the beam. The fastener's
mounting edges are designed to allow the screws to be installed horizontally.
This is a benefit when overhead clearance is limited. In addition, the 90° side
mount strap can be used in a restrainer fashion when it is attached to the top
of a beam, and the system lies on top of the beam.
Riser Supports
Risers must be supported by pipe clamps or by hangers located on the
horizontal connection close to the riser. Only Listed hangers and clamps
can be used. Vertical lines must be supported at intervals to avoid placing
excessive load on a fitting at the lower end. This can be done by using riser
clamps or double -bolt pipe clamps listed for this service.
Hangers and supports must not compress, distort, cut, or abrade the piping,
and they must allow free movement of the pipe for thermal expansion and
contraction. DO NOT use riser clamps that squeeze the pipe and depend on
compression of the pipe to support the weight.
Maintain vertical piping in straight alignmentwith supports at each floor level or
10-foot intervals, whichever is less. CPVC risers in vertical shafts or buildings
with ceilings over 25 feet must be aligned straight and supported at each floor
level or 10-fool intervals, whichever is less.
FG-3-1010 0 2013 Spears® Manufacturing Company Page 41
Clamps must not exert compressive stresses on the pipe. It possible, the
clamps should be located directly below a coupling so that the shoulder of the
coupling rests against the clamp. A coupling can be modified to achieve this
by cutting a CPVC coupling just above the stop at the socket bottom. Then,
cut this piece in half lengthwise to provide two halves that do not contain the
stop. Follow the 'Solvent Cement Welding Instructions' to cement the two
halves to the pipe at the required location, and make sure that the shoulder of
the modified coupling rests on the clamp. Allow the assembly to cure before
placing any stress on the joint
WARNING: CPVC pipe andlor system components must not be used to
provide structural support for the system. Care should be used when
installing, hanging, or bracing to prevent unnecessary stress loads on
the CPVC piping system.
Eltposed Installations
For exposed installations that incorporate pendent or sidewall sprinklers,
UL Listed support devices for thermoplastic sprinkler piping, or other listed
support devices shall be used to mount the piping directly to the ceiling or
sidewall.
Earthquake Bracing
Since CPVC fire sprinkler plastic piping is more ductile than metallic sprinkler
pipe, it has a greater capacity to withstand earthquake damage. In areas
subject to earthquakes, CPVC fire sprinklersystems should be designed and
braced in accordance with local codes and NFPA Standard 13.
Trenching
The trench for underground fire service applications should be of adequate
width to allow convenient installation, while at the same time being as narrow
as possible. Minimum trench widths may be utilized by joining pipe outside
of the trench and lowering it into the trench after adequate joint strength has
been achieved.
CAUTION - Refer to the set and cure times listed in this manual for solvent
cement joints. Failure to follow these cure times before installing piping
systems in trenches could result in joint separation. Trench widths have to
be wider where pipe is joined in the trench or where thermal expansion and
contraction is a factor. Refer to the 'Snaking/Deflection of Pipe" section.
Page 42 © 2013 Spears® Manufacturing Company FG-3-1010
LightTraffic
Heavy
Size
Trench
Ground
Traffic
Width
Cover
Ground
Cover
Nominal
Actual Outside
Minimum
Minimum
Diameter
Diameterinches/
inches
inches
inches
inchesfmm
mm
3 and under
3.500 and under
8
12 to 18
30 to 36
50 and under
60.3 and under
• Water filled pipe should be buried at least 12 inches below the maximum
expected frost line.
• It is recommended thatthermoplastic piping be run within a metal or concrete
casing when it is installed beneath surfaces that are subject to heavy weight
or constant traffic, such as roadways and railroad tracks.
The trench bottom should be continuous, relatively smooth, and free of rocks.
Where ledge rock, hardpan, or boulders are encountered, it is necessary to
pad the trench bottom using a minimum of four inches of tamped earth or sand
beneath the pipe as a cushion and for protection of the pipe from damage.
Sufficient cover must be maintained to keep external stress levels below
acceptable design stress. Reliability and safely of service is of major
importance in determining minimum cover. Local, state, and national codes
may also apply.
Snaking/Deflection of Pipe
NOTICE -
• After CPVC pipe has been solvent cemented, snake the pipe, according
to the following recommendations, beside the trench during its required
drying time.
• Be especially careful not to apply any stress thatwill disturb the undded joint
• Snaking is necessaryto allow for any anticipated thermal contraction thalwill
take place in the newlyjoined pipeline.
Snaking is particularly necessary on the lengths that have been solvent
cemented during the late afternoon or a hot summer's day because their
drying time will extend through the cool of the night when thermal contraction
of the pipe could stress the joints to the point of pull out. This snaking is
especially necessary with pipe that is laid in its trench (necessitating wider
trenches than recommended) and is back -filled with cool earth before the
joints are thoroughly dry. The following information can be used in determining
maximum deflection allowable for various run lengths and pipe sizes.
FG-3-1010 02013 Spears• Manufactunng Company Page 43
Mafdmem Bending Deflections In Inches
For Given Lengths of CPVC, SDR 13.5 (730 F)
Pipe
Size
Length of Run (L) in Feet
2 1 5 7 1 10 1 12 1 15 1 17 1 20 25 1 30 1 35 1 40 1 45 50
SDR
13.5
Pipe Deflection (D) in Inches
314
1.3
7.8
15.4
31.3
45.1
70.5
90.6
124.4
195.9
M1
38M
-
-
1
1.0
6.3
12.3
25.0
36.0
56.3
72.3
100.1
156.5
2252
306.6
400.4
-
I -
1-19
0.8
5.0
9.7
19.8
28.5
44.6
57.3
79.3
123.9
1784
2428
317.2
401A
-
1-12
0.7
4.3
8.5
17.3
24.9
39.0
50.1
69.3
1082
155.9
2122
277.1
350.7
2
0.6
3.5
6.8
13.9
20.0
312
40.0
55A
86.6
124.7
169.7
221.7
2�.6
2-12
0.5
2.1
5.6
11.4
16.5
25.8
33.1
45.8
71.5
103.0
140.2
183.1
231.8
J2862
3
0.4
2.4
4.6
9.4"
21227.2
37.6
58.8
84.6
1152
150.4
190A
D-in.
Maximum Snaking Deflections In Inches
For Given Lengths o1 CPVC, SOB 13.5 (73° F)
Length of Run (L) in Feel
Pipe
Size
2
1 5
1 7
10
12
1 15
1 17
1 20
1 25
1 30
1 35
1 40
1 45
50
SDR
13.5
Pipe Deflection (D) in Inches
3/4
0.3
2.0
3.8
7.8
11.3
17.6
22.6
31.3
49.0
70.5
96.0
125.4
158.7
195.9
1
0.3
1.6
3.1
6.3
9.0
14.1
18.1
25.0
39.1
56.3
76.6
100,1
126.7
156.4
1-1/4
0.2
1.2
2.4
5.0
7.1
11.2
14.3
19.8
31.0
44.5
fi0.7
79.3
100.4
123.9
1-1/2
0.2
1.1
2.1
4.3
6.2
9.7
12.5
17.3
27.1
39.0
53.0
69.3
87.7
108.2
2
0.1
0.9
1.713.515.0
7.8
10.0
13.9
21.6
31.2
42.4
55.4
70.1
86.6
2-12
0.1
0.7
1Al2.914.1
6.4
8.3
11.4
17.9
25.8
35.1
45.8
57.9
71.5
3
0.1
0.6
1.212.413.4
5.3
6.
99.4
14.7
21.2
28.8
37.6
47.6
58.8
r - L-ft. --►�
Page 44 0 2013 Spears® Manufacturing Company FG-3-1010
BACBFILLING
CAUTION - Underground pipe must be thoroughly inspected and tested for
leaks prior to backfilling (refer to section on hydrostatic pressure testing).
Failure to follow this instruction could result in system failure.
During periods of hot weather, backfilling should only be done early in the
morning when the line is fullyoontracted, and there is nochanceof insufficien8y
dried joints being subjected to contraction stresses.
The pipe should be uniformly and continuously supported over its entire length
on a firm, stable material. Blocking should not be used to change pipe grade
or to intermittently support pipe across excavated sections.
Pipe is installed in a wide range of subsoils. These soils must be stable and
applied in such a manner to physically shield the pipe from damage. Attention
should be given to local pipe laying experience, which may indicate particular
pipe bedding problems.
Backfill materials that are free of rocks with a particle size of 1/2-inch or less
should be used to surround the pipe with 6 to 8 inches of cover. It should
be placed in layers. Each soil layer should be sufficiently compacted to
uniformly develop lateral passive soil forces during the backfill operation.
It may be advisable to have the pipe under pressure,15 to 25 psi, during
the backfilling.
Vibratory methods are preferred when compacting sand or gravels. Best
results are obtained when the soils are In a nearly saturated condition.
Where water -flooding is used, the initial backfill should be sufficient to ensure
complete coverage of the pipe. Additional material should not be added unfit
the water flooded backfill is firm enough to walk on. Care should be taken to
avoid Floating the pipe.
Sand and gravel containing a significant proportion of fine-grained material,
such as silt and clay should be compacted by hand or, preferably, by
mechanical tamper.
The remainderof the backfill should be spread in uniform layersto fill the trench
completely so that there will be no unfilled spaces around rocks or lumps of
earth In the backfill. Large or sharp rocks, frozen clods, and other debris,
greater than 3 inches in diameter, should be removed. Rolling equipment or
heavy tampers should be used only to consolidate the final backfill.
Maintenanceshall be in accordancewith the Standard for Inspection, Testing and
Maintenance of Water Based Extinguishing Systems, as defined by NFPA25.
FG-3-1010 02013 Spears® Manufacturing Company Page 45
Material Properties
Table I -A
Modulus of Elasticity & Stress vs. Temperature
For Spears® FlameGuar& orVictaullc Firelock" CPIIC Fire Sprinkler Pipe
Property
Temperature ° F
73
80
90
100
110
120
140
150
Modulus of
Elasticity
3.90
3.84
3.78
3.70
3.46
3.21
3.05
2.84
"E" x 105 psi
Working
Stress
1,900
1,785
1,630
1,485
1,345
1,270
950
875
"S" psi
Table 1"B
Modulus of Elasticity & Stress vs. Temperature
For Harvel BlazeMaster® CPVC Fire Sprinider Pipe
Property
Temperature ° F
73
80
90
100
110
120
140
1 150
Modulus of
Elasticity
4.23
4.14
3.99
3.85
3.70
3.55
3.23
3.08
"E" x 105 psi
Working
Stress
2,000
1,815
1,715
1,560
1,415
1,275
1,000
875
"S. psi
Page 46 0 2013 Spears® Manufacturing Company FG-3-1010
Table II
Physical & Thermal Properties
A -Spears®
FlameGuard®
B-Harvel
Property
or Udaulic
BlazeMaster°
ASTM
Fbel-ock"
CPVC Pipe
CPVC Pipe
Specific Gravity
'Sp. Gr.'
1.51
1.55
D 92
IZOD Impact Strength
5.0
3.0
D256A
In. Ibynch of notch
Modulus of Elasticity, psi
'E'
3.9 x I
4.23 x 10'
D 639
Ultimate Tensile Strength, psi
8,000
8,400
D638
Compressive Strength, psi
91000
9,600
D 695
Poisson's Ratio
.35-.38
.35-.38
-
Working Stan @73°F. psi
1,9D0
2,000
D1598
Hazen-Wfifiams'C' Factor
150
150
-
Coefficient ofUnear
'a-
3.2x 104
3.4x 10'
D696
Expansion In./tn.' F)
Thermal Conduarmy
'k'
0.95
0.95
C177
BTU/(hr ° F Win)
Upper Temperature ❑mit
"P
205
210
-
Flammability
Flame Retardant
Flame Retardant
Electrical Conductivily
No Conductor
Non Conductor
Expansion and Contraction
Spearse FlameGuard® CPVC Fire Sprinkler Products, like all piping materials,
expand and contract With changes in temperature. If the coefficient of linear
expansion is 3.2 x10" inchrinch ° F. A 25° F change in temperature will
cause an expansion of 1 inch fora 100-foot straight length. For most operating
and installation conditions, expansion and contraction can be accommodated
at changes of direction.
FG-3-1010 C 2013 Spears° Manufacturing Company Page 47
Table III -A
Thermal Expansion In Inches
ForSpearse FlamellumnP or IActaulic Flydock- CPVC Fire Sprinkler Pipe
Temp.
Length of Run in Feet
Change
5 1 10 15 20 25 30 35 140145 150 170190112OF160
at F
Thermal Expansion AL (in.)
20
0.04
0.08
0.12
0.15
0.19
0.23
0.27
0.31
0.35
0.38
0.54
0.69
0.92
1.23
30
0.06
0.12
0.17
0.23
0.29
0.35
0.40
0.46
0.52
0.58
0.81
1.04
1.38
1.84
40
0.08
0.15
0.23
0.31
0.38
0.46
0.54
0.61
0.69
0.77
1.08
1.38
1.84
2.46
50
0.10
0.19
0.29
0.38
0.48
Us
0.67
0.77
0.86
0.96
1.34
1.73
2.30
3.07
60
0.12
0.23
0.35
0.46
0.58
0.69
0.81
0.92
1.04
1.15
1.61
2.07
2.76
3.69
70
0.13
0.27
0.40
0.54
0.67
0.81
0.94
1.08
1.21
1.34
1.88
2.42
3.23
4.30
80
0.15
0.31
0.4610.611
0.77
0.92
1.08
1.23
1.38
1.54
215
2.76
3.69
4.92
90
0.17
0.35
0.52
0.69
0.86
1.04
1.21
1.38
1.56
1.73
2.42
3.11
4.15
5.53
too
0.19
0.38
0.58
0.77
0.96
1.15
1.34
1.54
1.73
1.92
2.69
3.46
4.61
6.14
Table III-B
Thermal Expansion In Inches
For Harvel BlazeMastere CPVC Fire Sprinbler Pipe
Temp.
Change
Length of Run in Feet
5 10 15 20 25 1 30 1 35 140 145 1 50 1 70 190 1120T160
nT ^ F
Thermal Expansion AL (in.)
20
0.04
0.08
0.12
0.16
0.20
0.24
0.29
0.33
0.37
0.41
0.57
0.73
0.98
1.31
30
0.06
0.12
0.24
0.24
0.31
0.37
0.43
0.49
0.55
0.61
0.86
1.10
1.47
1.96
40
0.08
0.16
0.33
0.41
0.41
0.49
0.57
0.65
0.74
0.82
1.14
11.47
1.96
2.61
50
0.10
0.20
0.41
0.51
0.51
0.61
0.72
0.82
0.92
1.02
1.43
1.84
2.45
3.26
60
0.12
0.24
0.49
0.61
0.61
0.73
0.86
0.98
1.10
1.22
1.71
2.20
2.94
3.92
0.29
0.57
0.71
0.71
0.98
1.00
1.14
1.29
1.43
200
2.
3.43
4.57
E02
0.33
0.65
0.82
0.82
0.98
1.14
1.31
1.47
1.63
2.28
2.94
3.92
5.22
0.37
0.73
0.92
0.92
1.04
1.10
1.29
1.47
1.66
2.84
3.30
4.41
5.88
0.41
0.82
1.02
1.02
1.22
1.43
1.63
1.84
2.04
2.86
3.67
4.90
6.53
AL = 12 ell (AT)
e = 3.4 004 in.(n.' F (Coefficient of Linear Expansion for Harvel
BlazeMaster° CPVC Fire Sprinkler Pipe)
-or-
e = 3.2 x104 in./in. ° F (Coefficient of Linear Expansion for Spears®
FlameGuard° CPVC Fire Sprinkler Pipe)
L = Length of Run in Feet
AT = Temperature Change in' F
Page 48 © 2013 Spearse Manufacturing Company FG-3-1010
Example:
How much will a 40 ft. run of 2' Spears® FlameGuard® CPVC Fire Sprinkler Pipe
expand if the expected ambient temperature will range from 45° F to 85° F?
AL = 12 eL (AT)
AL = 12 (.000032) x 40 x 40
AL = .61'
Expansion Loop & Offset Configurations
Hangers or guides should only be placed in the loop, offset or change of
direction as indicated below. Piping supports should restrict lateral movement
and should direct axial movement into the expansion loop.
Expansion Loop and Offset Configurations
Loop
_�
y 215C
6" Min IS=� �- 6" Min
Offset
!E
Change of Direction
Long Run of Pipe
Hanger or Guide
Restraint
FG-3-1010 02013 Spears° Manufacturing Company Page 49
Table IV -A
Expansion Loop Length In Inches
Far SpearsRameGuardearNctaulicFlreLock—CPIICFireSprinlderPlpe
Naninal
pipe
Size
Avg.
0'D'
Length of Run In Feet
5 1 10 1 15 1 20 1 25 1 30 1 35 1 40 1 45 1 50 70 1 90 120 160
Length of Loop On.)
Temperature=100' F-30' F,AT=70' F
314
1.050
7
10
13
15
16
18
19
21
22
23
27
31
36
41
1
1.315
8
11
14
16
18120
22
23
24
26
30
34
40
46
1-114
1.660
9
13
i6
18
20
22
24
26
27
29
34
39
45
52
1-ir2
1.900
10
14
17
20
22
24
26
28
29
31
37
41
48
55
2
2.375
11
15
19
22
24
27
29
31
33
35
41
46
54
62
2-V2
2.875
12
17
21
24
27
30
32
34
36
38
45
51
59
68
3
3.500
13
19
23
27
30
33
35
38
40
42
50
56
65
75
Table N-B
Expansion Loop Length In Inches
For Harvel BlazeMasterm CPVC Fire Sprinkler Pipe
Norninal
Pipe
Size
Avg
O.D.
Length of Run in Feel
5 ID 15 20 25 30 35 40 45 50 70 90 120 ifi0
Length of Loop On.)
Temperature=10V F- so- F, AT= 70- F
314
1.050
7
11
13
15
17
18
20
8
32
37
42
1
L315
8
12
14
17
19120
22
31
35
41
47
1.114
1.660
9
13
16
19
25
35
40
46
531-112
1.900
10
14
20
22
27
38
M4248
43
49
572
2375
11
16
19
22
J123
30
42
48
55
632-112
2.875
12
18
21
25
33
46
52
60
703
3.500
13
19
24
27
36
51
58
67
77
Note: Table IV -A and IV-B are based on Stress & Modulus Elasticity at 100= F
E = 3EDAL
2S
E = Length of Expansion Loop in Inches
E = Modulus of Elasticity (Table I -A or I-B)
D = Average O.D. of Pipe
AL = Change in Length of Pipe Due to Change in
Temperature (Table III-Aor III-B)
S = Working Stress (Table I -A or 1-13)
Page 50 02013 Spears®Manufacturing Company FG-3-1010
Note: Data in Table I -A must be used with Table III -A and data in Table I-B
with Table III-B
Example: How much expansion can be expected in a 200 ft run of 2' Spears®
FlameGuardm CPVC Fire Sprinkler Pipe and how long should the expansion
loop be to compensate for this expansion? (The expected temperature range
will be from 40' F to 110' F).
First Find:
AT = (Change in Temperature)
AT = T2—T1
AT = 110'F-40'F
AT = 70' F
To Find
AL = (Amount of Expansion in inches from
Table III -A)
AL = AL of 160 ft. with a AT of 70' F + AL of40ft.
with a AT of 70' F
AL = 4.30'+1.08'
AL = 5.38'
-OR-
AL =
12eL(AT)
e =
3.2 x 1V (from Table II, Victaulic
Fhai-ocO CPVC Pipe)
L =
Length of Run in Feet
AT =
Change in Temperature in ' F
AL =
12 x .000032 x 200 x 70
AL =
5.38'
To find the length of the expansion loop or offset in inches:
t = 3EDAL
2S
t = Length of Expansion Loop in Inches
E = Modulus of Elasticity at 110' F (Table I -A)
D = Average O.D. of Pipe
AL = Change in Length of Pipe Due to Change in
Temperature (Table III -A)
S = Working Stress at 110' F (Table I -A)
t = 3EDAL
2S
It= 3 x 346.000 x 2.375 x 5.38
2 x 1345
t = 4931
It = 70.2'
FG-3-1010 02013 Spears® Manufacturing Company Page 51
Review— Do's & Don'ts
Do's
• Read the manufacturer's installation instructions.
• Follow recommended safe work practices.
• Make certain that thread sealants, gasket
lubricants, or fire stop materials are compatible with CPVC.
• Keep pipe and fittings in original packaging unfil
needed.
• Cover pipe and fittings with an opaque tarp if
stored outdoors.
• Follow proper handling procedures.
• Use tools specifically designed for use with plastic pipe
and fittings.
• Use the proper solvent cement and follow
application instructions.
• Use a drop cloth to protect interior finishes.
• Cut the pipe ends square.
• Deburr and bevel the pipe end with a chamfering tool.
• Rotate the pipe 1/4 turn when bottoming pipe in fitting socket
• Avoid puddling of cement in fittings and pipe.
• Make certain no solvent cement is on sprinkler head and adapter
threads.
• Make certain that solvent cement does not run and plug the sprinkler
head orifice.
• Follow the manufacturer's recommended cure times prior to pressure
testing.
• Flush the entire system including drops to remove pipe shavings, dirt
and debris left from installation.
• Fill lines slowly and bleed the air from the system prior to Flushing and
pressure testing.
• Support sprinkler head properly to prevent lift up of the head through the
ceiling when activated.
• Keep threaded rod within 1116' of the pipe or use a surge arrestor.
• Install Spears®FlameGuard® CPVC Fire Sprinkler Products In wet
systems only.
• Use only glycerin and watersolutions forfreeze protection.
• Allow for movement due to expansion and contraction.
• Renew your Spears® FlameGuard® CPVC Fire Sprinkler Products
installation training every two years.
Page 52 02013 Spears° Manufacturing Company FG-3-1010
Don'ts
Do not use edible oils such as Crisco as a gasket lubricant. .
Do not use petroleum or solvent -based sealants, lubricants, or fire stop
materials.
Do not install tape, insulated wire or cable in direct contact with CPVC.
Do not use any glycol -based solutions as an anti -freeze.
Do not mix glycerin and water solutions in contaminated containers.
Do not use solvent cement that exceeds its shelf life or has become
discolored orjellied.
Do not allow solvent cement to plug the sprinkler head orifice.
Do not connect rigid metal couplers to CPVC grooved adapters.
Do not thread, groove, or drill CPVC pipe.
Do not use solvent cement near sources of heat, open flame, or when
smoking.
Do not pressure test with air.
Do not pressure test until recommended cure times are met
Do not use ratchet cutters below 50' F.
Do not use CPVC pipe that has been stored outdoors, unprotected and
is faded in color.
Do not allow threaded rod to come in contact with the pipe.
Do not install Spears® FlameGuard® CPVC Fire Sprinkler Products In
cold weather without allowing for expansion.
Material Safety Data Sheet
IPS WELD -ON
Date Revised: FEB 2000
Supersedes: FEB 1999
Information on this form is furnished solely for the purpose of compliance with
the Occupational Safety and Health Act and shall not be used for any other
purpose. IPS Corporation urges the customers receiving this Material Safety
Data Sheet to study it carefully to become aware of the hazards, if any, of the
product involved. In the interest of safety, you should notify your employees,
agents and contractors of the Information on this sheet.
Section I
Manufacturer's Name: IPS Corporation
Address: 17109 S. Main St., PO Box 379, Gardena, CA 90248
Transportation Emergencies: CHEMTREC: (800) 424-9300 or
3 E COMPANY (800) 451-8346
Medical Emergencies: 3 E (24 Hour No.) (800) 451-8346
Business: (310) 898-3300
CHEMICAL NAME and FAMILY: Solvent Cement for CPVC Plastic Pipe
Mixture of CPVC Resin and Organic
Solvents
Trade Name: SPEARS® FS-5
Formula: Proprietary
FG-3-1010 © 2013 Spears® Manufacturing Company Page 53
Section II - Hazardous Ingredients
None of the ingredients below are listed as carcinogens by IARC, NTP or
OSHA
Ingredient:
Chlorinated Polyvinyl Chloride Resin (CPVC)
Cas#:
NON/HAZ
ACGIH-TLV:
NIA
OSHA-PEL:
NIA
Ingredient:
Tetrahydrofuran (THF)"
CasM
109-99-9
ACGIH-TLV:
200 PPM
ACGIH-STEL:
250 PPM
OSHA-PEL:
200 PPM
OSHA-STEL:
250 PPM
DUPONT (A) AEL:
25 PPM
DUPONT (B) STEL:
75 PPM
Ingredient:
Methyl Ethyl Ketone (MEK)
Cas#:
78-93-3
Approx%: 2•
ACGIH-TLV: 200 PPM
ACGIH-STEL: 300 PPM
OSHA-PEL: 200 PPM
OSHA-STEL: 300 PPM
Ingredient: Cyclohexanone
Cas#: 108-94-1
ACGIH-TLV: 25 PPM Skin
OSHA-PEL: 25 PPM Skin
Ingredient Acetone
Cas#: 67-64-1
ACGIH-TLV: 750 PPM
ACGIH-STEL: 1000 PPM
OSHA-PEL: 750 PPM
OSHA-STEL: 1000 PPM
`Title III Section 313 Supplier Notification: This product contains toxic chemicals
subject to the reporting requirements of Section 313 of the Emergency
Planning and Community Right -to -Know Act of 1986 and of 40CFR372. This
information must be included in all MSDS's that are copied and distributed
for this material.
(A) Dupont's Acceptable Exposure Limit (AEL) guidelines for 8 hour and 12
hour TWA, (B) Dupont's recommended STEL for 15 minute TWA.
Information found in a report from the National Toxicology Program (NTP)
on an Inhalation study in rats and mice suggests that Tetrahydrofuran (THF)
can cause tumors in animals. In the study the rats and mice were exposed to
THF vapor levels up to 1800 PPM for two years (their lifetime), 6 hours/day, 5
days/week. Test results showed evidence of liver tumors in female mice and
kidney tumors in male rats. No evidence of tumors was seen in female rats
and male mice. There is no data linking Tetrahydrofuran exposure with cancer
in humans.
Page 54 0 2013 Spears® Manufacturing Company FG-3-1010
BULK SHIPPING INFORMATION (CONTAINERS GREATER THAN ONE
LITER
DOT Shipping Name:
Adhesive
DOT Hazard Class:
3
Identification Number.
UN 1133
Packaging Group:
II
Label Requirement:
Flammable Liquid
SHIPPING INFORMATION FOR CONTAINERS LESS THAN ONE LITER
DOT Shipping Name: Consumer Commodity
DOT Hazard Class: ORM-D
HMIS
NFPA
HAZARD RATING
HEALTH:
2
2
0-MINIMAL
FLAMMABILITY:
3
3
1-SLIGHT
REACTIVITY:
0
1
2 - MODERATE
PROTECTIVE:
3 - SERIOUS
EQUIPMENT.
H
4-SEVERE
H = Eye, Hand/Skin, Respiratory Protection and ImpemieableApron
Section 111 - Physical Data
Appearance: Red, medium syrupy liquid
Specific Gravity @ 73` F± 3.6` (20° C±2*): Typical 1.0 ± 0.040
Vapor Density (Air =1): 2.49
ODOR: Ethereal
VAPOR PRESSURE (mm Hg.): 143mm Hg. based on first boiling
component, THE @ 68° F (20° C)
EVAPORATION RATE (BUAC =1): >1.0
BOILING POINT (° F1' C):151' F (67° C) Based on first boiling component:
THE
PERCENT VOLATILE BY VOLUME (%): Approx. 70 - 80%
VOC STATEMENT: VOC as manufactured: 720 Grams/Liter. Maximum VOC
emission per SCAOMD Rule 1168, Test Method 316A: 490 Grams/Liter.
Section IV - Fire and Explosion
Hazard Data
FLASH POINT: 4- F (20° C) T.C.C. based on THE
FLAMMABLE LIMITS (Percent by Volume)
LEL:2.O
UEL: 11.8
FG-3-1010 C, 2013 Spears® Manufacturing Company Page 55
FIRE EXTINGUISHING MEDIA: Ansul "Purple K° potassium bicarbonate dry
chemical, carbon dioxide, National Aer-0-Foam universal alcohol resistant
foam, water spray.
SPECIAL FIRE FIGHTING PROCEDURES: Evacuate enclosed areas, stay
upwind. Close or confined quarters require self-contained breathing apparatus,
positive, pressure masks or airline masks. Use water spray to cool containers,
to flush spills from source of ignifion and to disperse vapors.
UNUSUAL FIRE AND EXPLOSION HAZARDS: Fire hazard because of low
flash point and high volatility. Vapors are heavier than air and may travel to
source(s) of Ignition at or near ground or lower levels and flash back.
Section V - Health Hazard Data
PRIMARY ROUTES OF ENTRY: Inhalation, Skin Contact
EFFECT OF OVEREXPOSURE
ACCUTE:
Inhalation: Severe overexposure may result in nausea, dizziness, headache.
Can cause drowsiness, irritation of eyes and nasal passages.
Skin Contact: Skin irritant. Liquid contact may remove natural skin oils resulting
in skin irritation. Dermatitis may occur with prolonged contact.
Skin Absorption: Prolonged or widespread exposure may result in the
absorption of harmful amounts of material.
Eve Contact: Overexposure may result in severe eye injury with corneal
or conjunctival inflammation on contact with the liquid. Vapors slightly
uncomfortable.
Ingestion: Moderately toxic. May cause nausea, vomiting, diarrhea. May
cause mental sluggishness.
CHRONIC: Symptoms of respiratory tract irritation and damage to respiratory
epithelium were reported in rats exposed to 5000 ppm THE for 90 days.
Elevation of SGPT suggests a disturbance in liver function. The NOEL was
reported to be 200 ppm.
REPRODUCTIVE EFFECTS: N. AP.
TERATOGENICITY: N. AP.
MUTAGENICITY: N. AR
EMBROYOTOXICITY: N. AP.
SENSITIZATION TO PRODUCT: N. AP.
SYNERGISTIC PRODUCTS: N. AV.
MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE: Individuals with
pre-existing diseases of the eyes, skin or respiratory system may have
increased susceptibility to the toxicity of excessive exposures.
Page 56 © 2013 Spears® Manufacturing Company FG-3-1010
EMERGENCY AND FIRST AID PROCEDURES
Inhalation7 If overcome by vapors, remove to fresh air and if breathing stopped,
give artificial respiration. If breathing is difficult, give oxygen. Call physician.
Eve Contact: Flush eyes with plenty of water for 15 minutes and call a
physician.
Skin Contact: Remove contaminated clothing and shoes. Wash skin with
plenty of soap and water for at least 15 minutes. If irritation develops, get
medical attention.
Ingestion: Give 1 or 2 glasses of water or milk. Do not Induce vomiting. Call
physician or poison control center immediately.
Section VI - ReaCUvitY
Stability: Stable
Conditions to Avoid: Keep away from heat, sparks, open flame and other
sources of ignition.
Incompatibility: (Materials to avoid) Caustics, ammonia, inorganic acids,
chlorinated compounds, strong oxidizers and isocyanates.
Hazardous Decomposition Products: When forced to bum, this product gives
out carbon monoxide, carbon dioxide, hydrogen chloride and smoke.
Hazardous Polymerization: Will not occur.
Conditions To Avoid: Keep away from heat, sparks, open flame and other
sources of ignition.
Section NI - Spill Or leak Procedures
Steps To Be Taken In Case Material Is Released Or Spilled: Eliminate all
Ignition sources. Avoid breathing of vapors. Keep liquid out of eyes. Flush with
large amount or water. Contain liquid with sand or earth. Absorb with sand or
nonflammable absorbent material and transfer into steel drums for recovery
or disposal. Prevent liquid from entering drains.
Waste Disposal Method: Follow local, State and Federal regulations. Consult
DISPOSALEXPERT Can be disposed of by incineration. Excessive quantities
should not be permitted to enter drains. Empty containers should be air dried
before disposing. Hazardous Waste Code: 214.
Section Vill - Special Protection Information
Respiratory Protection (Specify type)• Atmospheric levels should be
maintained below established exposure limits contained in Section II. If
airborne concentrations exceed those limits, use of a NIOSH approved
organic vapor cartridge respirator with full face -piece is recommended. The
effectiveness of an air purifying respirator is limited. Use it only for a single
short-term exposure. For emergency and other conditions where short-term
exposure guidelines may be exceeded, use an approved positive pressure
self-contained breathing apparatus.
FG-3-1010 02013 Spears® Manufacturing Company Page 57
Ventilation - Use only with adequate ventilation. Provide sufficient ventilation
in volume and pattern to keep contaminants below applicable exposure limits
set forth in Section II. Use only explosion proof ventilation equipment.
Protective Gloves: PVA coated
Eve Protection: Splash proof chemical goggles
Other Protective Eouioment And Hvaienic Practices: Impervious apron
and a source of running water to flush or wash the eyes and skin in case of
contact.
Section IX • Special Precautions
Precautions To Be Taken In Handling And Storing; Store in the shade between
40° F - 90° F (4° C - 32.5° C). Keep away from heat, sparks, open flame
and other sources of ignition. Avoid prolonged breathing of vapor. Use
with adequate ventilation. Avoid contact with eyes, skin and clothing. Train
employees on all special handling procedures before they work with this
product.
Other Precautions Follow all precautionary information given on container
label, product bullefins and our solvent cementing literature. All material
handling equipment should be electrically grounded.
The Information contained herein is based on data considered accurate.
However, no warranty is expressed or implied regarding the accuracy of this
data or the results to be obtained from the use thereof.
Page 58 © 2013 Spears® Manufacturing Company FG-3-1010
NOTES
FG-3-1010 02013 Spears• Manufacturing Company Page 59
NOTES
Page 60 © 2013 Spears® Manufactunng Company FG-3-1010
NOTES
FG-3-1010 02013 Spears® Manufacturing Company Page et
NOTES
Page 62 © 2013 Spears® Manufacturing Company FG-3-1010
SPEARS* MANUFACTURING COMPANY
CORPORATE OFFICE
15853 Olden St., Sylmar, CA 91342
PO Box 9203, Sylmar, CA 91392
(818) 364-1611 • www.spearsmfg.com
PACIFIC SOUTHWEST
158W Olden St
Sylmar(Los Angeles), CA 91342
(818)364-1611•(800)862.1499
Fax (818) 367-3014
ROCKY MOUNTAIN
4880 Florence St
Denver, CO 80238
(303) 371.9430 • (800) T77-4154
Fax(303) 375.9546
NORTHEAST
5901ndustrial Dr., Suite 100
Lewisberry(Hamsburg), PA
17339 9532
(71193HS44 • (800) 233-0275
Fax (717)938.6547
MIDWEST
1 Gateway CL, Suits
Boringbmok (Chicago), IL 60440
(630)759.7529•(800) 662-6330
Fax(630) 759-7515
NORTHWEST
4103 C SL NE Suite 200
Auburn (Seattle), WA 98002
(2S3) 939A433•(800) 347-7327
Fax(253) 939-7557
UTAH
5395 West 1520 South
Salt lake City, Ur 84104
(303)371-9430•(800) T17-4154
Fax (303)375-9546
SOUTH CENTRAL
10001akeside Parkway
Flower Mound, TX 75028
(469) 52MODO - (800) 441-1437
Fax (469) 5283001
FLORIDA
9563 Parksouth Court
Orlando, FL 32937
(407)843-1960•(800)327-6390
Fax(407)425-3563
SOUTHEAST
4205 NewpoinlPL, Suite 100
Lawrenceville (Atlanta), GA 30043
(678)985-1263•(80D) 662-6326
Fax (678) 985-5642
INTERNATIONAL SALES
1585301den St
Sylmar (Los Angeles), CA 91342
(818) 364-1611 • Fax (818) 8983774
Distdbutor
FG-3-1010 02013 Spears® Manufacturing Company Page 63
... 00 IT CORRECTLY!
Failure to follow instructions can result in thread breaks from too
much tape, difficult assembly from not enough, or leaks due to
exposed starting threads.
DO NOT USE TAPE & PASTE!
• DO NOT USE with Gasket Sealed Head Adapters
• USE a TFE tape with a min. thickness of 2.5 mil.
• Cover male starting threads to prevent seizing.
• Wrap tape in direction of threads.
— For Regular Head Adapters, use 2 to 3 wraps.
Tighten to specified torque (see front cover).
— For Female Adapter Transitions to metal pipe,
use ONLY 5 to 5-1/2 wraps.
• Joint Assembly — tighten 1-2turns beyond finger tight.
DO NOT back up. DO NOT over tighten!
SPEARS® MANUFACTURING COMPANY
15853 Olden Street, Sylmar CA 91342
PO Box 9203, Sylmar, CA 91392
(818)364-1611
www.spearsmfg.com
© Copyright 2013 Spears• Manufacturing Company
All Rights Reserved. Printed in the United States of America 01/13. FG-3-1010
SCANNED
BY
St. Lucie Cow*
FlameGUard°
CPVC FIRE SPRINKLER
PIPING PRODUCTS
TECHNICAL INFORMATION
WEIGHTS & DIMENSIONS
November 20_, 5-
SUPERSEDES ALL PREVIOUSEDITIONS
~
VFACTUR
�p
OLPCB
UKAS
Visit our web site: F
Assessed to ISO 9001>2009=
Cedfficate number`293
e
IameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS
The information contained in this section is based on current information and Product design at the time of publication and is subject to change without notification. Our
ongoing commitment to product improvement may result in some variation. No representations, guarantees or warranties of any kind are made as to its accuracy, suitability
for particular applications or results to be obtained therefrom. For verification of technical data or additional Information not contained herein, please contact Spears® Technical
Services Department Most Coast: (818) 364-1611--East Coast: (678) 985-1263].
General Information
RECOMMENDATIONS FOR INSTALLERS AND USERS:
Plastic piping systems should be ENGINEERED, INSTALLED and OPERATED in accordance with ESTABLISHED DESIGN AND ENGINEERING STANDARDS AND
PROCEDURES for plastic piping systems. Suitability for the intended service application should be determined by the installer and/or user prior to installation of a plastic
piping system. All Installation and maintenance personnel should be trained in the proper handling and installation requirements and precautions of plastic piping systems.
PRIOR TO ASSEMBLY, all piping system components should be inspected for damage or irregularities. Mating components should be checked to assure that
tolerances and engagements are compatible. Do not use any components that appear irregular or do not fit properly. Contact the appropriate manufacturer of
the component product in question to determine usability. Consult all applicable codes and regulations for compliance prior to installation.
Installation must be made in accordance with Spearse Manufacturing Company
FlameGuard® CPVC Fire Sprinkler Piping Products Installation Instructions - FG-3
NOTE — Individual or group Instruction in correct solvent welding procedures is available by contacting your local distributor or your servicing Spears® Regional Distribution
Center.
SOLVENT CEMENT CONNECTIONS — Spears° Manufacturing Company recommends the use of Spearse FS5 One Step solvent cement for joining Spears®
products. Use of solvent cementing products not approved for CPVC fire spdnkler systems, or failure to follow installation instructions will automatically void
the warranty.
THREADED CONNECTION —Spears® Manufacturing Company recommends the use of Spears® BLUE 751e Thread Sealant. This product has been tested by Spears°
and the sealant manufacturer for compatibility with the Spears' CPVC fire sprinkler products. Consult the sprinkler head manufacturer before using this product. WARNING:
OTHER PIPE JOINT COMPOUNDS OR PASTES MAY CONTAIN SUBSTANCES THAT COULD CAUSE STRESS CRACKING IN THE CPVC OR OTHER FITTING
COMPONENTS. Care must betaken to avoid over torquing -generally 1 to 2 tums beyond finger fight is all that is required to make up a threaded connection. Factorytesting
has indicated 10-25 IL lbs. of torque is adequate to obtain a leak free seal.
GASKET SEALED THREAD CONNECTIONS —This type of connection can only be made with Spears® TorqueSaf0, Sofrorqu0 or QuickTorqueTM style Gasket Sealed
Female Sprinkler Adapters. DO NOT USE ANY TYPE OF THREAD SEALANT WHEN INSTALLING THIS TYPE OF ADAPTER. Tape or paste may impair proper sealing
and function. Testing has shown that hand fight until snug for the TorqueSafsT" adapter and finger tight plus 14um is all that is needed to seal this special connection.
Sprinkler heads in these specialty fittings can then be additionally tightened clockwise to bring spdnkler frames into desired alignment without stressing the fdling. See
specific adapter instructions in package for details.
GripLocTM CONNECTIONS— This type of connection can only be made with Spears@GdpLocTM Couplings or Repair Couplings, DO NOT USE ANY TYPE OF SOLVENT
CEMENT OR SEALANT WHEN INSTALLING THIS TYPE OF CONNECTION. Uses an internal stainless steel gripper ring with an internal elastomer gasket seal.
Connection allows immediate system use. See specific instructions in package for details.
Installation Training Available - Contact Spearse Technical Services for Details
FlameGuard® Products must be installed in accordance with Spearse FlameGuard® CPVC Fire Sprinkler Piping Products Installation Instructions, National Fire Protection
Association Standards 13, 13R, 13D, and in accordance with local codes. Code requirements and field conditions may differ. It is the responsibility of the Installing contractor
to insure that the product is suitable to meet these requirements.
Dimension Reference
G = (LAYING LENGTH) Intersection of center lines to bottom of sockeNhread; 90' elbows, tees,
crosses; ± 1/32 inch. M = Outside diameter of sockethhread hub; ± 1/16 inch.
H = Intersection of center lines to face of fitting; 90° elbows lees, crosses; ± 1132 inch. N = Socket bottom to socket bottom; couplings; ± 1116 inch.
J = Intersection of center lines to bottom of sockedthread; 45' elbows; ± 1132 inch 0 = Width of fiats; ±1116 inch.
L = Overall length of fittings; ± 1116 inch. W = Height of cap; ± 1/16 inch.
CPVC FIRE SPRINKLER PIPE SDR 13.5 (ASTM F 442)
Part Number
Nominal Size
Inches (ram)
Average O.D.
Inches (ram)
Average I.D.
Inches (mm)
Approx. Weight LbsJFt.
CP-007
3/4
(19.1)
1.050
(26.7)
.874
(22.5)
0.168
CP-010
1
(25.4)
1.315
(33.4)
1.101
(28.2)
0.262
CP-012
1-1/4
(31.8)
1.660
(42.2)
1.394
(35.6)
0.418
CP-015
1-12
(38.1)
1.900
(48.3)
1.598
(40.7)
0,548
CP.020
2
(50.8)
2,375
(60.3)
2.003
(50.9)
0.859
CP-025
2-12
(63.5)
2.875
(73.0)
2.423
(61.5)
1.257
CP-030
3
(76.2)
3.500
(88.9)
2,950
(75.0)
1.867
"Lead Free° low lead certification — unless other wise spedfied, all Spears® FlameGuard° fittings specified here -in are certified by NSF International to ANSYNSFe Standard 61,
Annex G and is in compliance with California's Health 8 Safety Code Section 116825 (commonly known as ABi953) and VermontAct 193. Weighted average lead content <=0.25"/u.
Spears® PVC and CPVC Pipe, Fittings and Valves have always been lead-free and Certified by NSF International for use in potable water systems. Spears® offers a wide range of
lead-free specialty fittings and transition adapters for plumbing applications. However, certain brass threaded adapter fittings for applications that are not intended to convey water
for human consumption through drinking or cooking are still produced and available.
SPEARS® MANUFACTURING COMPANY
FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS
SPEARS
SOCKET DIMENSIONS
SCH 40 -ASTM F438
Fes-- C --.)
SCH 80 -ASTM F439
A
Size
Socket
Socket
Tolerance
SCH 40 Minimum
SCH 80 Minimum
Entrance A
Bottom B
Socket Length C
Socket Length C
314
1.058
1.046
t.004
.719
1.000
1
1.325
1.130
t.005
.875
1.125
1-114
1.670
1.655
t.005
.938
1.250
1-112
1.912
1.894
1.006
1.094
1.375
2
2.387
2.369
t .005
1.156
1.500
2-112
2.889
2.868
t .007
1.750
1.750
3
3.516
3.492
t .008
1.875
1.875
TEE
Socket x Socket x Socket
P_P
L-
Part Number
Size
G
H
L
M
Approx. Wt. (Lbs.)
4201-007
3/4
9116
1-12
2-3W2
15116
.11
4201-010
1
718
1-13116
3518
15/8
.20
4201-012
1-1/4
102
2-3132
4-7/32
2
.29
4201-015
1-112
1-6132
2-9/16
5J/32
2-IW2
.54
4201-020
2
1-13132
2-15/16
5.7/8
2-718
.86
4201-025
2-112
1-2352
3-12
7
3-15/32
1.62
4201-030
3
2-1/16
3-31132
7-15116
4-5/32
2.53
REDUCING TEE
r--.;M+
Socket x Socket x Socket
t
;-jT�Hl
q�H
Part
Approx.
Size
G
G1
G2
H
H1
H2
L
M
M1
M2
Number
Wt. (Lbs.)
4201-102
3143141
314
3/4
3/4
1-11116
1.25132
1-11116
3-13132
1-5116
1-21132
1-5116
.13
4201-125
1z314314
23/32
718
23/32
1-25/32
1-13116
1-21132
34116
1-19132
1-11132
15116
.16
4201-126
10141
23/32
23132
314
1-27/32
1-27132
1-3/4
3-19132
15/8
15/8
1-5116
.17
4201-131
UU314
11/16
13/16
11116
1-13116
1-13/16
1-13116
3-5/8
1-5/8
15116
15/8
.17
4201-157
1-11UN3/4
11/16
14M2
11116
1-15116
2.1132
1.13116
3-25132
2-3132
1-13132
1-23/32
.32
MADE IN THE U.S.A.
S\ PERRS
FlameGuard° CPVC FIRE SPRINKLER PIPING PRODUCTS
REDUCING TEE (continued) ["MI
Socket x Socket x Socket
M G FH2
Part Number
Size
G
G1
G2
H
H1
H2
L
M
M1
M2
Approx. Wt. (Lbs.)
4201-158
1-1141xl
27132
29/32
25132
2-1116
2-1132
1-29/32
3.15/16
131132
1-518
"18
.24
4201-159
1-1/41A-1/4
31132
31132
31132
2-7132
2-732
23B2
4-11/32
2-118
2-1/8
1-23132
.36
4201-167
1-1/41-11404
21132
1
21132
1-29132
2
1.29B2
3-13116
2
1-5116
2
.22
4201-168
1-1/4x1-114x1
13116
1
13/16
2-1116
2-1/8
2.1116
4-118
131132
1-21132
131132
.24
4201-169
1-1/4x1-1/4A-112
1-118
15116
1-1/8
2-M
2-11132
2-318
4314
23B2
2-11/32
2-3/32
.51
4201-201
142xl-114x3/4
11/16
1
1/4
2-1116
2
1-15116
4
25116
13B
2-1/16
1 .41
4201-202
1-12x1-1141
27132
1-1132
1 1
2-7132
2-5132
1 2-1/4
4.15132
25/16
1 1-11/16
2-1116
.42
4201-210
1-112x1-112x3/4
11/16
1-1132
11116
2-1116
2-1132
2-1116
4-5132
2-11132
1-13B2
2.11132
.39
4201-211
14I2x1-1/2x1
13116
1-3132
13/16
23116
2-1/4
2-3/16
4318
2-11132
13/4
2-11132
.41
4201-212
1-12x1-12x1-1/4
1-iB2
W/32
1-1/32
2-1M2
2-11132
2-13132
4.13116
2-11/32
2-1/8
2-11132
.49
4201-213
1.12x1-I/W
1-9/32
1-5132
1-9B2
2-21132
2-21132
2-21132
5-11132
2-11/32
2-29B2
2.11/32
.64
4201-248
2x2x314
11/16
143132
11/16
2-7B2
2-7116
2-7132
4-7/16
2-27132
13B
2-27132
.52
4201-249
2x2x1
27B2
1-13B2
27132
2-11/32
2-9116
2-1162
4-23B2
2-7/8
13/4
2-7/8
.58
4201-250
2x2x1-114
1-1/32
1-11132
1-1B2
2-17132
2-19132
2-17/32
53132
2-7/8
23132
2-7/8
.65
4201-251
2x2x1-12
1-5B2
1-7/16
15132
2.11116
2-13132
2-11116
5-3/8
2-7/8
2-13132
2-7/8
.79
4201-289
2-124-1/2x1
27/32
1-23132
27B2
2-5/8
2-27132
1 2-5/8
5.1/4
3-17B2
1 1-23132
3-17132
1.01
4201-290
2-1/W-112x14/4
13B2
1-23132
1-1132
2-13116
231132
2-13/16
5-21/32
3-9116
23B2
3-9/16
1.13
4201-291
2-12x2-V2x1-V2
13116
1/2
13/16
2-15116
1-718
2-15/16
&718
3-15/32
2-11B2
3-15132
1.26
4201-292
2-12x2-12x2
1-13132
1-5/8
1-13132
33/16
3-1/8
33116
63B
3-12
2-7/8
3-1/2
1.37
4201-335
3x3xl
7/8
1.15116
718
23/4
3-1/16
23I4
5-15132
4-3/16
1-23/32
43/16
1.26
4201-336'
Wxl-1/4
1318
13/4
13/8
3-5116
3-112
35116
6518
4-1/8
2-718
4-118
1.94
4201-3E
3x3x1-12
1-5B2
2-1/16
1-5132
3-iB2
3-7/16
3-iB2
6-3B2M43/16
2-3/8
4-3116
1.46
4201-338
344
1.7116
1-13/16
1-7116
3-1116
35116
3-5116
6-191322-7/8
43I16
1.69
4201-339
3x3x2-12
1-3/4
131B2
13/4
3-518
3-23132
35/8
7-1/43-17B2
431i6
2.11
' Bmnch Outlet Sized with Bushing
TorqueSafe'" SPRINKLER HEAD TEE
Gasket Sealed Brass
Thread Insert Style
G1
Socket x Socket x Gasket Fipt
H1
With Elastomer Seal - Use NO Thread Sealant
Tn
M2
G
G2
H
H2
L
Part Number
Size
G
G1
G2
H
1-11
H2
L
M
M1
M2
Approx. Wt (Lbs.)
4202-101 G
3143/40/2
7116
13116
7/16
1-7/16
1-7/16
1-17/32
2.29132
1-3/8
1-3/8
1-318
.22
4202-124G
1x314x112
7/16
1-11/32
9116
1-9/16
1-11/16
1-9/16
3-W
1-11/16
13B
1-3/8
.26
4202-130G
1x1x1/2
7116
1-11/32
7/16
1-9/16
1-11/16
1-9116
3-V8
1-23B2
13/8
1-23B2
.28
4202-131 G
ixWA
17132
15116
17/32
1-11116
1-518
1-11/16
3-11B2
1-2362
1-9/16
1-23/32
.31
4202-166G
1-1/41-1/4xl2
7116
1-5/8
7/16
1-11/16
1-15116
1-11116
3318
2.1116
13/8
2-1116
.34
4202-209G
1-1120-1202
1/2
1-13116
12
1-7/8
23B2
1418
33/4
2.11/32
13B
2-11132
.41
4202-247G
I 2x2xl/2
I 12
1 2-1/16
12
1 2
1 2-11132
1 2
1 4.1132
1 2-27132
1 1318
1 2-27132
1 .54
Not intended to convey or dispense water for human consumption through ddnking or cooking
SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
S\ PEAIS
SPRINKLER HEAD TEE
M,
Brass Thread Insert Style
x Socket x Fipt
G,
H1
ISocket
M —_
IM2
S
G
G2
H
L
H2
Part Number
Size
G
G1
G2
H
H1
H2
L
M
M1
M2
Approx. Wt. (Lbs.)
4202-010
1x1x1
21M
1-1/8
1 21/31
1-202
1-29/32
1-25/32
3-19132
1 1-23132
1 1-23/32
1 1-23/32
1 .37
Not Intended to conveyor dispense water for human consumption through drinking or cooking
SofTorque'rm SR REDUCING TEE
Gasket Sealed Special Reinforced Plastic Thread Style
Socket x Socket x SR Fipt
With Elastomer Seal - Use NO Thread Sealant
V
Part Number
Size
G
G1
G2
H
H1
H2
L
I M
M1
M2
Approx. WL (Lbs.)
4202-101GSR
3/4x314x12
1 7/16
1-1/2
7/16
1 W18
1-718
W18
2-314
1 1-5116
1 13/8
1-5116
.16
4202-130GSR
lxlx1/2
1 7/16
15/8
7116
1 1-112
2
1-12
3
1 1-5/8
1 1-3/8
1518
.20
SPRINKLER REDUCING HEAD TEE
Brass Thread Insert Style
Socket x Socket x Fipt
-T x1
M2
G1
HG2
TGHI
Part Number
Size
G
G1
G2
H
H1
H2
L
M
M1
M2
Approx. Wt. (Lbs.)
4202-101
3143MA2
7/16
1.1116
7/16
1-15/32
15/8
1-15/32
2-29132
1-13132
13116
1-13132
.20
4202-124
1414x112
7/16
1-11/32
9/16
1-9116
1-11116
1-9/16
3-118
1.11116
W18
W18
.26
4202-130
lxlxl/2
7116
1-7132
7/16
1-9116
1-25/32
1-9/16
3.1/8
WA
13116
1-314
.26
4202-156
1-1/4z1x1/2
7/16
1-7/16
9116
1-11/16
2-1132
1-11/16
3318
23132
W116
1-23132
.30
4202-166
1-1/4x1-114A/2
7116
1-15132
7/16
1-11116
2-1132
1-11/16
3318
23132
13116
2-M2
.31
4202-199
1-1/2xl-1/4x12
1/2
1-5/8
9/16
1-718
23/16
1-13116
3-11116
2-11132
13116
2-1116
.37
4202-209
1-172xl-11202
12
1-518
12
1-718
23/16
1-7/8
33/4
2-11/32
13116
2-11/32
.38
4202-231
2x1-1I2x1/2
12
1-27132
17/32
2
2-7116
1-29132
3-15/16
2-7I8
13116
2-111,32
.47
4202-247
2x2xl/2
12
1-7/8
12
2
2-7I16
2
4-1l32
2-27/32
1-3116
2-27/32
.50
Not intended to convey or dispense water for human consumption through drinking or cooking
IG101:811GAM7_1
S\ PFARS
Fla; a ivardO CPVC FIRE SPRINKLER PIPING PRODUCTS
SPRINKLER HEAD TEE
Special Reinforced
Plastic Thread Style
Socket x Socket x SR Fipt
Part Number Size G G1 G2 H H1 H2 L M M7 M2 Approx. Wt. (Lbs.)
4202-010SR ix1x1 21/32 3/4 21/32 1-25/32 1-518 1-25/32 3-19/32 1-23132 1-11/16 1-23132 .26
SPRINKLER REDUCING HEAD TEE
Special Reinforced
Plastic Thread Style
Socket x Socket x SR Fipt
1--M1j
H1
12
M 41 G1
G2
H H2
L
Part Number
Size
G
G1
G2
H
H1
I H2
L
M
M1
M2
Approx. Wt. (Lbs.)
4202-101SR
3/4x3/4x1/2
19132
25/32
19132
1-19132
1-7/16
1-19/32
3-7132
1-13/32
1-3116
1-13/32
.15
4202-124SR
ix3/4x112
7116
29132
9/16
1-19132
15/8
1-9116
3-5/32
1-23/32
1-3116
1-17/32
.19
4202-130SR
1x1x112
7116
29132
7/16
1-9116
1-518
1-9/16
3-1/8
1-23132
W116
1-23/32
.20
4202-156SR
1-1/UW12
15/32
1-5132
19132
1-23132
1-7/8
1-23132
3-13132
23132
1-3116
1-23/32
.26
4202-166SR
1-1/4A-1/4A/2
7/16
1-1/8
7/16
1-11/16
1-27/32
1-11/16
3-318
23/32
1-3116
2-3/32
.26
4202-168SR
1-1/4xl-1/4xl
27/32
1-1132
27132
23/32
1-29132
2-3/32
4-7/32
2-3132
1-11/16
2-3/32
.34
4202-199SR
1-1/2x1-1/41/2
9116
1-9/32
17132
1-15116
2
1-25/32
3-23132
2-11132
1-3116
2-3/32
.33
4202-209SR
1-1/20-1/2x1/2
1/2
1 1-1/4
1 12
1 1-7/8
1 1-31/32 1
1-7/8
1 3-3/4
1 2-11132
1 1-3116
2-11/32
.35
4202-211SR
1-1/20-1/2A
27/32
1-7132
27/32
2-7132
2-1/8
2-7132
4-15132
2-11/32
1-23/32
2-11/32
.44
4202-237SR
2x1-1/2x1/2
23/32
1-9116
318
2-7/32
2-9/32
1-3/4
3-31132
2-7/8
1-3/i6
2-11/32
.45
4202-247SR
2x2x1/2
112
1 31132
1 12
1 2
1-11116
1 19132
1 4
1 2-7/8
1-3/16
2-7/8
.48
4202-287SR
2-11W-112012
17/32
1 1-3/4
1 17132
1 2-9132
2-1/2
1 2-9/32
1 4-19/32
1 3-1/2
1-7/32
3-1/2
.78
SOFIFORQUETM
~
SR SPRINKLER HEAD TEE
j
Gasket Sealed Special
Reinforced Plastic Thread Style
Socket x SR Fipt xSocket
Stainless Steel Collar With Elastomer Seal - Use
NO Thread Sealant
H2
Part Number
i Size
G
G1
G2
H
H7
H2
L
M
M7
M2
Approx. Wt. (Lbs.)
4203-122GSR
ix12x11
13116
1 13116
1 1-1/2
1 1-27132
1 1-27/32
1 1-31132
3-13/16
1 1-5/8
1 15/8
1 1-3/8
1 .22
5 SPEARS® MANUFACTURING COMPANY
FlameGuardO CPVC FIRE SPRINKLER PIPING PRODUCTS J
S\ PFANS
TorqueSafeTM
SPRINKLER HEAD TEE
M7
Gasket Sealed
G1
H1
Brass Thread Insert Style
+ `
Socket x Gasket Fipt x Socket
M _ Mz
With Elastomer Seal - Use NO Thread Sealant
G G2
H L H2
Part Number
Size
I G
I G1
I G2
I H
I H1
I H2
I L
I M
I M1
I M2
I Approx. Wt. Lbs.
4203-122G
I 1xl/2x1
1 19132
1 13116
1-13132
1-19/32
1-27132
1-3/4
3-11/32
1-5/8
1 1-5/8
1 1JI8
1 .25
Not intended to convey or dispense water for human consumption through drinking or cooking
SPRINKLER HEAD TEE
Brass Thread Insert Style
Socket x Fipt x Socket
*JH2
M
�I
L
Part Number
I Size
G
G1
G2
I H
I H1
I H2
L
I M
M1
M2
Approx. Wt. (Lbs.)
4203-122
1 W120
1 23132
1 314
1 1-114
1 1-5/6
1 1-5/8
1 1-15116
1 3-12
1 1-23/32
1 1-23/32
1 13/16
1 .25
Not intended to convey or dispense water for human consumption through ddnking or cooking
SPRINKLER HEAD TEE
Special Reinforced
Plastic Thread Style
Socket x SR Fipt x Socket
Part Number Size G G1 G2 H H1 H2 L M M1 M2 I Approx. Wt. (Lbs.)
4203-122SR 1x12xl 27132 23132 I-M2 1-23132 1-518 1-25132 3-13132 1-314 1314 13116 .21
MADE IN THE U.S.A. 6
FlameGuard° CPVC FIRE SPRINKLER PIPING PRODUCTS
STREET TEE
Spigot x Socket x Socket
Mi
M2
OR
H1
Gi
G
G2
H
�1�— H2
L
Part Number
Size
G
GI
G2
H
H1
H2
L
M1
M2
Approx. Wt. (Lbs.)
4244-007
314
13/16
27132
27132
1.13/16
1-7/8
1-78
3-518
1-13132
1-13132
.16
4244-010
1
15/32
1-1132
1-1132
2-1/8
1-29132
1-29/32
4.3116
13/4
13/4
.27
4244-012
1414
1-1/4
1
1
2.7116
2-9132
2-9132
4-27132
23132
23132
.42
4244-015
1-112
1-13/16
1-118
1-18
2-7/8
2-9116
2-9116
5-11132
2-11/32
2-11/32
.56
4244-020
2
1-23132
1-7/16
1-13132
3-1/4
2-15116
2-15116
6-5/32
2-7/8
2-7/8
.84
900 ELBOW
Socket Socket
G
H
--
�M�
Part Number
Size
G
H
M
Approx. Wt. (Lbs.)
4206007
314
9116
14/2
M116
o7
4206-010
1
314
1-518
1-6B
.11
4206-012
1-1/4
15116
23/16
2
.22
4206-015
1-112
15132
2-17132
23/8
.41
4206-020
2
1-13/32
2-29132
2-7/8
.62
4206.025
2-12
1-15132
3318
3-12
1.15
4206-030
3
1-02
33/32
43116
1.83
SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
3\ PFANS
SIDE OUTLET ELBOW
Socket x Socket x Socket
tHG
Part Number
Size
G
H
M
Approx. Wt. (Lbs.)
4213-007
314
27/32
1-19132
1-5116
.09
4213-010
1
13116
1-7/8
M18
.18
REDUCING 900 ELBOW
Socket x Socket Hi �{
G7
G
r- M1
H
L
I. M
Part Number Size G G1 H H1 M M1 Approx. Wt
Lbs.
4206-131 104 21/32 13/16 1-25132 1-13116 1-19132 1-5116 .11
TorqueSafeTM 900 SPRINKLER HEAD ELBOW
Gasket Sealed Brass Thread Insert Style
Socket x Gasket Fipt
With Elastomer Seal - Use NO Thread Sealant
Hi
Gi
G
_ M1
H
M
Part Number
Size
G
G1
H
H1
M
M1
Approx. Wt (Lbs.)
4207-101 G
3Ida1/2
9/16
1-7132
1-13132
1-17/32
1-13/32
1-318
.19
4207-130 G
1xi/2
7116
1-3/16
1-9116
1-11/16
1-23r32
1-3/8
.23
4207-166 G
1-1I4x1/2
1 15/32
1-19/32
1-15/16
1-11/16
23132
1-3/8
.25
Not Intended to convey or dispense water for human consumption through ddnking or cooking
MADE IN THE U.S.A. 8
SPEARS
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
SPRINKLER HEAD 900 ELBOW
Brass Thread Insert Style
H,
Socket x Fipt
Gi
G
--
41
M7
H I
M —.I
Part Number
Size
G
G1
H
H1
M
M1
Approx. Wt. (Lbs.)
4207-101
314x12
12
1-3132
1-12
1-5/8
1-13132
13116
.17
4207-130
1x12
7/16
1-7132
1-19f32
1-25132
1-2322
1-3116
.21
4207431
1x3/4
17132
1-11/32
1-21132
131132
1-23132
1318
.25
4207-166
1-11402
15132
1-17/32
1 1-11/16
W5116
2.3132
1-17/32
.33
Not Intended to conveyor dispense water for human consumption through drinking or cooking
Sof7orque"m SR 900 ELBOW SPRINKLER HEAD ADAPTER
Gasket Sealed Special Reinforced Plastic Thread Style
Socket x SR Fipt G1
With Elastomer Seal -Use NO Thread Sealant —II
y
fG
Part Number
Size
G
G1
H
H1
M
M1
Approx. Wt (Lbs.)
4207-101GSR
3/402
7/16
1-17132
1316
1-27132
1-11132
1318
.17
4207-130GSR
1x12
7116
1-11116
1-12
2
1-21/32
1318
.19
4207-166GSR
1-114012
7116
1-7/8
1-11116
2732
2
13I8
.22
SPRINKLER HEAD 900 ELBOW
Special Reinforced Plastic Thread Style
HI
Socket x SR Fipt
G1
G
to -T
-
M1G
H
M
Part Number
Size
G
G1
H
H1
M
M1
Approx. Wt. (Lbs.)
4207-101SR
314x112
11132
13116
1-15/32
1-1/2
1-13132
1-3116
.14
4207-130SR
1x112
7116
7/8
1-9116
1-518
1-23132
1-3/8
.20
4207-131SR
1x314
12
718
1-5/8
1-9116
1-23132
1-3/8
.16
4207-166SR
1-1/41/2
13132
1-1/32
1-21132
1-23/32
2-3132
1-7132
.19
SPEARS® MANUFACTURING COMPANY
FlameGuard° CPVC FIRE SPRINKLER PIPING PRODUCTS
900 STREET ELBOW
Spigot x Socket
H
G1
c
Ml
IH
L
PIPEO.D.
Part Number
Size
G
G1
H
H1
M1
Approx. Wt. (Lbs.)
4209-007
314
29132
19132
1-16116
1-11116
113132
.12
4209-010
1
1-9132
23/32
2-13132
1-27132
1-3/4
.21
4209-012
1-1/4
1-9/16
27/32
2-13116
2-3132
2-3132
.32
4209-015
1-1/2
1-15/32
1-3116
2-27/32
2-9/16
2-11/32
.42
4209-020
2
1-23/32
1-3/8
3-7132
2-15116
2-27132
.65
22-1120 ELBOW
Socket x Socket
J
H
M.
Part Number
Size
H
J
M
Approx. Wt. (Lbs.)
4216-007
314
1-3/16
7/32
1-13/32
.09
42W010
1
1-3/8
9132
1-25/32
.14
4216-012
1.1/4
1-1/2
5/16
2-3/32
.20
4216-015
1-1/2
1-7/16
13132
1-3/8
.19
4216-020
2
1-7/8
318
2-27/32
.43
4216-030
1 3
2-3/8
1 112
1 4-5132
1 1.00
22-1120 STREET ELBOW
Spigot x Socket
M1
Hi J,
H J AI /
i
— I PIPE O.D.
Part Number
Size
H
H1
J
J1
M7
Approx. Wt. (Lbs.)
4242-007
3/4
1-1/4
1-1/2
1/4
112
1-318
.08
4242-010
1
1-7116
1-11132
5/16
7132
1-23/32
.14
4242-012
1-1/4
1-9116
1-25/32
17132
11116
2-1116
.21
4242-015
1-1/2
1-13132
1-23132
112
11/32
2-11/32
.28
4242-020
2
1-29/32
2-116
7132
518
2-7/8
.42
4242-025
1 2-1/2
2-1/8
2-1/4
13132
112
3-112
.68
4242-030
3
2-13132
2-13/32
9116
17/32
4-5/32
.99
MADE IN THE U.S.A. 10
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
450 ELBOW
Socket x Socket
H
L
�M--.1
Part Number
Size
H
J
M
Approx. Wt. (Lbs.)
4217-007
A
1-5/16
5/16
1-5/16
.07
4217-010
1
1-13/32
318
1-5/8
.11
4217-012
1-1/4
1-5/8
318
2-5132
.21
4217-015
1-1/2
1-27132
15/32
2-11132
.32
4217-020
2
2-1/8
21132
2-7/8
.48
4217-025
2-112
2-17132
3/4
3.1/2
.88
4217.030
3
2-29132
29/32
4-5132
1.17
CROSS
Socket x Socket x
Socket x Socket
OG
MH1
�H
IL 4
Part Number
Size
G
G1
H
H1
L
L1
M
Approx. Wt. (Lbs.)
4220-007
3/4
5/8
518
1-21132
1-21/32
3-5116
3-5116
1-13/32
.22
4220-010
1
3/4
314
1-5/8
1-518
3-1/4
3-1/4
1-23/32
.20
4220-012
1-1/4
1-1/8
1-1/8
2-3/8
2-3/8
4-3/4
4-3/4
2-3132
.63
4220-015
1-112
1-7132
1-7132
2-5/8
2-5/8
5-7132
5-7132
2-3/8
.80
4220-020
2
1-1/2
1-1/2
3
3
6
6
3
1.43
4220.025
2-1/2
i-11116
1-11111
3-7111
3-7116
6-7/8
6-718
3-17132
2.16
42MO30
3
2-3/32
2.3132
3-31132
3-31132
7-15116
7-15/i6
4.7116
3.37
11 SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
450 STREET ELBOW
Spigot x Socket
H1J1
Mi
tmp
H j I
I .I PIPE O.D.
Part Number
Size
H
Hl
J
Jl
Ml
App—romW(Lbs.)
4227-010
1
1-1/2
1-5116
112
1/4
1-5/8
.10
4227-012
1-1/4
1-25132
1-9116
9116
11132
1-31132
.15
4227-015
1-1/2
2-1/32
2-1/8
19132
25132
2-11132
.29
4227-020
2
2-5/16
1-15116
25/32
13132
2-7/8
.44
r +rMl
Socket x Socket
x Socket x Socket
i H7
M — --- Li
L i G1
Li
H
L
Part Number
Size
G
G1
H
H1
L
L1
M
M1
Approx. Wt. (Lbs.)
4220-131
IX3/4
23132
518
1-5/8
1-5/8
3-1/4
3-1/4
1-7/8
1-112
.31
4220-167
1-1143/4
1-1/16
23132
2-1116
1-31132
4-3132
3.31132
2-1116
1-13/32
.35
4220.210
1-1/2z3/4
11116
1-5132
2-3132
2-3116
4-3116
4-11132
2-3/8
1-13/32
A2
4220-248
2x314
11116
1-7116
2-7/32
2-7116
4-13/32
4-718
2-29132
1-13132
.56
4220-289
2-112A
29132
1-314
2-11116
2-7/8
5-11132
5314
3-1/2
1-314
.98
COUPLING
Socket Socket
M
I
:Nl
I
Part Number
Size
L
M
N
Approx. Wt. (Lbs.)
4229-007
314
2-1/8
1-5116
3/16
.05
4229-010
1
2-3116
1-518
3/32
.08
4229-012
1-1/4
2-19/32
2
3132
.13
4229-015
1-112
2-7/8
2-11132
3132
.22
4229-020
2
3-1/8
2-7/8
118
.33
4229-025
2-1/2
3-i1/16
3-15132
3/16
.48
4229-030
3
4
4-3116
114
.89
MADE IN THE U.S.A. 12
SPERRS
FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS
REDUCER COUPLING
Socket x Socket
M I—_— --_ M1
F N L
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4229-131
104
2-3/8
1-23132
1-13132
7132
.10
4229-167
1-1/4314
2-19/32
2-3132
1S/8
11132
.17
4229-168
1-1141
2-11116
2-3132
1-23132
5116
.18
4229-210
1-11204
2-13116
2-11132
1-13132
15132
.19
4229-211
1-112x1
2-718
2-11132
1-15116
318
.24
4229-212
1-1/2xi-114
2-13116
2-13/32
2-1/8
5/32
.23
4229.248
2x3/4
3-3I16
2-7/8
1-7116
23132
.32 1
4229-249
2x1
3-1/8
2-7/8
1-23132
112
.31
4229-250
2x1-114
3-3116
12-7/8
2-1/8
17132
.33
4229-251
2x1-1/2
3-3/16
2-27132
2-11/32
9132
.31
4229-291
2-112xl-112
3-23/32
3-15/32
2-11132
21132
.51
4229-292
2-1/2K2
3-202
3-1/2
2-7/8
13132
.52
4229-337
3x1-1/2
3-12
4-3/16
2-3/8
7132
A
4229339
3x2-12
3.27132
4-3116
3-12
3/16
.80
GripLoCTM COUPLING - LEAD FREE
wIEPDM 0-Ring Seals
L
175 psi Maximum
Internal Pressure @ 150T
_-
----- -----
------ M
LI
WARNING:
DO NOT INSERT FINGERS.
Part Number
Size
L
M1
N
Approx. Wt. (Lbs.)
GL4229-007
314
4
1-15/16
1-29/32
.25
GL4229-010
1
4-5132
2
2-1/4
.34
13 SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
GROOVED COUPLING ADAPTER
Groove x Socket
PIPE M1
O.D.
N
L
Part Number
Size
L
M1
N
Approx. Wt. (Lbs.)
4233-012
1-1/4
3-5/8
2-3/32
2-11132
.72
4233-015
1-1/2
3-3/4
2-11132
2-11132
.83
4233-020
2
3-27132
2-27132
2-11/32
1.27
4233-025
2-1/2
4-3116
3-15132
2-7116
2.02
4233.030
3
4-5/16
4-1/8
2-7/16
2.76
Not Intended to convey or dispense water for human consumption through drinking or cooking
FEMALE ADAPTER
Brass Thread Insert Style
Socket x Fipt
IM
L
1
-- -
L
M7
Part Number
Size
L
M
M7
N
Approx. Wt. (Lbs.)
4235-007
3/4
2
1-13132
1-318
5116
.23
4235-010
1
2-3116
1-3/4
1-11/16
11/32
.25
4235.012
1-1/4
2-3/8
2-3/32
2-1/16
318
.36
4235-015
1-1/2
2-17/32
2-3/8
2-7/16
318
.47
4235-020
2
2-25132
2-27132
3-3116
7116
1.05
Not intended to convey or dispense water for human consumption through drinking or cooking
FEMALE ADAPTER
Special Reinforced Plastic Thread Style
Socket x SR Fipt
1
MI
--- M1
L
NJ
L�
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4235.007SR
314
1-7/8
1-13132
1-318
3132
.08
4235-010SR
1
2-5/32
1-23132
1-7/8
3132
.22
4235-012SR
1-1/4
2-5115
2-1/8
2-1116
3116
.20
MADE IN THE U.S.A. 14
FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS
FEMALE SPRINKLER HEAD ADAPTER
Special Reinforced Plastic Thread Style
Socket x SR Fipt
M _._._ _ ^Q'' M1
F N L�
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4235-101SR
314x1/2
1-29/32
1-13132
1-3116
1/8
.08
4235.130SR
1x1/2
1-31/32
1-23132
1-3/8
3/32
.16
4235-131SR
104
2-3132
1-3/4
1-3/8
1/4
.13
FEMALE SPRINKLER HEAD ADAPTER
Special Reinforced Plastic Thread Style with Socket Wrench Flats
Socket x SR Fipt
M------- ---
- Mi
M = Flat -to -Flat Dimension
N
L
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
W4235401SR
314x1/2
2-9/32
1-13132
1-3/16
17/32
.09
W4235-130SR
102
2-9/32
1-314
1-3/16
13/32
.12
15 SPEARS® MANUFACTURING COMPANY
FlameGuard° CPVC FIRE SPRINKLER PIPING PRODUCTS
S\ PERRS
SPIGOT FEMALE ADAPTER
Brass Thread Insert Style
Spigot x Fipt
I
PIPE O.D. M7
L
L
Part Number
Size
L
M1
N
Approx. Wt. (Lbs.)
4278-007
314
2-5132
1-3/8
17/32
1 .15
4278-010
1
2-9/32
1-11116
7116
1 .22
Not intended to convey or dispense water for human consumption through drinking or cooking
SPIGOT FEMALE ADAPTER
Special Reinforced Plastic Thread Style
Spigot x SR Fipt
PIPE —-
O.D.
�L
Part Number
Size
L
M1
N
Approx. Wt. (Lbs.)
4278-007SR
3/4
1-15116
1-318
11132
.08
4278-010SR
1
2-1/4
1-23/32
13/32
.13
TorqueSafeT14 FEMALE SPRINKLER HEAD ADAPTER
Gasket Sealed Brass Thread Insert Style
Socket x Gasket Fipt
With Elastomer Seal - Use NO Thread Sealant
M - — - — --tall
Mt
N
L
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4235-101 G
3141/2
1-718
1-13/32
1-318
9116
.15
LS130GS
1x112
2-1/32
1-11/16
1-318
17132
.17
35-131 G
1x3/4
2
1-11/16
1-9116
9116
.18
Not Intended to convey or dispense water for human consumption through drinking or cooking
MADE IN THE U.S.A. 16
FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS
FEMALE SPRINKLER HEAD ADAPTER
Brass Thread Insert Style
Socket x Fipt
M ----
M1
N
L
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4235-101
3141/2
1-7/8
1-13132
1-17/32
15/32
.19
4235-130
lx1/2
2-11132
1-11/16
1-3/16
518
.16
4235-131
ix314
2-5116
1-11116
1-3/8
17/32
.18
Not Intended to convey or dispense water for human consumption through drinking or cooking
SofTorqueTM SR FEMALE SPRINKLER HEAD ADAPTER
Gasket Sealed Special Reinforced Plastic Thread Style
Socket SIR Fipt
With Elastotomer Seal -Use NO Thread Sealant L
M --_
N
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4235-101GSR
3/4112
25116
1-5/16
1-3/8
31132
.11
4235-130GSR
1x1/2
2-13132
1-19132
1-3/8
31132
.13
4235-131GSR
1414
2.13132
15/8
1-23132
1
.16
QuickTorqueTM
SR FEMALE SPRINKLER HEAD ADAPTER
Gasket Sealed Special
Reinforced Plastic Thread Style
Socket x SR Metal Fipt
With Elastomer Seal - Use NO Thread Sealant t
1M ____ _ _M1
L
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
4235-101GMR
314x112
1-15/16
1-5116
1-9116
13/16
.17
4235-73OGMR
1x1/2
23116
1-19132
1-9116
15/16
.19
17 SPEARS® MANUFACTURING COMPANY
FlameGuard° CPVC FIRE SPRINKLER PIPING PRODUCTS
S\ PFARS
FEMALE SPRINKLER
HEAD ADAPTER
Brass Thread Insert Style M
with Long Body
Socket x Fipt
M1
— —
N
L
Part Number
Size
I L
M
M1
N
Approx. Wt. (Lbs.)
L4235-130
1x1/2
1 2-3116
1 1-23/32
1-7132
1/2
.19
Not Intended to convey or dispense water for human consumption through drinking or cooking
FEMALE SPRINKLER HEAD ADAPTER
Brass Thread Insert Style
with Positioning Ring M
Socket x Fipt �I
4.—
—•-- M,
L
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
R4235-101
3/4112
2-1/32
1-7116
1-3116
1 15/32
.15
Not intended to convey or dispense water for human consumption through drinking or cooking
FEMALE SPRINKLER HEAD ADAPTER
Special Reinforced Plastic Thread
Style with Positioning Ring M
Socket x SR Rpt
____,
NL�
Part Number
Size
L
M
M1
N
Approx. Wt. (Lbs.)
R4235-101SR
3/41/2
1 1-16116 1
1-7/16
1-7132
1 7132
.09
TorqueSafeT" FEMALE SPIGOT SPRINKLER HEAD ADAPTER
Gasket Sealed Brass Thread Insert Style
Spigot x Gasket Fipt
With Elastomer Seal - Use NO Thread Sealant
PIPE —_—_—_ +• M1
O.D.
N
L
Part Number
Size
L
M
N
Approx. Wt. (Lbs.)
4238-101 G
314Al2
1-15/16
1-3/8
21132
.14
4238-130G
1x112
2-1116
1-3/8
19132
.15
Not intended to convey or dispense water for human consumption through drinking or cooking
MADE IN THE U.S.A. 18
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
SPIGOT FEMALE SPRINKLER HEAD ADAPTER
Brass Thread Insert Style
Spigot x Fipt
PIPE ____ _ M1
O.D.
�I
F L
'—
Part Number
Size
L
M1
N
Approx. Wt. (Lbs.)
4238-101
314x112
1-15116'
1-17132
17132
.18
4238_139
1x112
2-114
1-3/16
11/32
.19
Not intended to conveyor dispense water for human consumption through drinking or cooking
TorqueSafeTm BUSHING - GASKET SEALED
Brass Thread Insert Style
Spigot x Gasket FIPT
With Elastomer Seal - Use NO Thread Sealant
L
Part Number
Size
L
Approx. Wt. (Lbs.)
4238-130BR G
1x112
1-7132
.10
Not intended to conveyor dispense water for human consumption through drinking or cooking
BUSHING with BRASS THREAD INSERT
Spigot x Fipt
_ PIP
0. .
Part Number
Size
L
Approx. Wt. (Lbs.)
4238-130BR
1 142
1
.13
Not Intended to convey or dispense water for human consumption through drinking or cooking
SPIGOT FEMALE SPRINKLER HEAD ADAPTER
Special Reinforced Plastic Thread Style
Spigot x SR Fipt
PIPE
.L--
N
L
Part Number
Size
L
M1
N
Approx. Wt. (Lbs.)
4238-101SR
1 314112
1-29132 1
1-7132
1 118
.07
4238-130SR
I 1x112
2-1132 1
1-7132
1 7132
1 .09
19 SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
SPEARS
MALE ADAPTER
With CPVC Lined Thread Brass Insert
Mipt x Socket
M1
______
—_—_
N
L
Part Number
Size
L
M1
N
Approx. Wt. (Lbs.)
4236-007
314
2-17/32
1-13132
13116
.26
4236-010
1
2-15/16
1-23132
29132
.43
4236-012
1-1/4
3-1/8
2-3/32
31/32
.66
4236-015
1-1/2
3-9132
2-11132
31/32
.80
4236-020
2
3-7115
2-27132
31/32
1.00
ADJUSTABLE SPRINKLER HEAD ADAPTER
Special Reinforced Plastic Thread Style
Socket x SR Fipt
Lt
N Body
L Width
Part Number
Size
L
N
Q
Body Width
Approx. Wt. (Lbs.)
Min
Max
Min
Max
42001SR
3/4112
6-9132
8
4-7/16
6-1/4
1-7116
2-3/16
.66
42011SR
W/2
6-13132
8
4-1/2
6-1/8
1-7116
2-118
.68
ADJUSTABLE SPRINKLER HEAD ADAPTER
Special Reinforced Plastic Thread Style
Spigot x SR Fipt
PIPE
I�—L ld
Widh
L
N
Part Number
Size
Q
Body Width
Approx. Wt. (Lbs.)
Min
Max
Min
Max
42004SR
3/4112
5-1132
6-5/16
3-3116
4-15132
1-5/16
2-1/8
.36
42014SR
1x112
6-7/16
8-1/8
1 4-7/16
6-1/4
1-7/16
2.3116
.67
MADE IN THE U.S.A. 20
SPEARS
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
REDUCER BUSHING
Flush Style
Spigot x Socket PIPE
O.D.
]-
N
-
L
Part Number
Size
L
N
Approx. Wt (Lbs.)
4237-131
1414
1-1/4
1/4
.D4
4237-167
1-114314
1-7116
7/16
.10
4237-168
1-1/41
1.13/32
9132
.06
4237-210
1-1/2x3/4
15/8
518
.19
4237-211
1-1 /2z1
1-17132
13132
.13
4237-212
1-12xl-1/4
1-9/16
5/16
.07
4237-248
2414
1-29132
AM
.28
4237-249
2x1
1-23132
9116
.23
4237-250
2A-1/4
1-11/16
7116
.21
4237-251
20-1/2
1-11116
5116
.15
4237-990
2-12x1-114
25132
718
.41
4237-291
2-112XI-12
25/32
314
.39
4237-292
2-11W
2-9/32
39
.28
4237-338
3x2
2-7/32
11116
.63
4237-339
3x2412
2-5116
114
.42
TRANSITION BUSHING
IPS Spigot x CTS Socket
PIPE
O.ID.
LEE
L
L-
Part Number
Size
L
N
Approx. Wt. (Lbs.)
4240-101
314x112
1-1/8
518
.03
4240-130
W/2 -
1-114
23132
.05
CAP
Socket
--
W
M
Part Number
Size
M
W
Approx. Wt (Lbs.)
4247-007
314
15/16
1-5/16
.04
4247-010
1
1-518
1-9/16
.06
4247-012
1-114
2-3/32
1-27/32
.13
4247-015
1.112
2-11/32
2
.17
4247-020
2
2-27132
2-9132
.39
ISM
2-12
3-1722
2518
.50
4247-030
3
43I8
3
.92
21 SPEARS® MANUFACTURING COMPANY
FlameGuardO CPVC FIRE SPRINKLER PIPING PRODUCTS
TEST PLUG - 0-ring Sealed
Mipt - For Pressure Testing Only,
Not For use with Z4235 Series Adapters
L ,
_.
M1 — M
In-14NPr �
Part Number Size L M M1 Approx. Wt. (Lbs.)
FTP-005 1/2 1-27/32 1-15116 1-7132 .03
TEST PLUG for TorqueSafeTM
Gasket Sealed Head Adapters
Mipt- For Pressure Testing Only.
Use ONLY with Gasket Sealed Head Adapters
M1Tcur �_....,I -..zid1.
1/2-14NPT
Part Number Size L M M1 Approx. Wt. (Lbs.)
FTP-005GS 1/2 1-25/32 2-1/32 1-1/4 .05
TEST PLUG
(PVC White) Not UL Listed; For Pressure Testing Only,
Mipt
Part Number Size L Approx. Wt. (Lbs.)
4250-005 112 27132 .02
MADE IN THE U.S.A. 22
S\ PFAR3
FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS
FLANGE - ONE PIECE
4 Bolt Holes,175 psi
Socket
L
R
I
N I If BOLT CIRCLE DIA .:1
I.--. MO.D.
Ax
No. of
Bolt
Min.
Bolt
Max.
Approx. Wt.
Part Number
Size
L
M
N
R
Bolt
Circle
Bolt
Size
O.D.
(Lbs.)
Holes
Dia.
Length
4251-007
3/4
1,5132
1-1/2
1/8
17132
4
M/4
12
2
3-29132
.31
4251-010
1
1-5116
1-13116
1/8
11/16
4
3-1/8
1/2
2-1/4
4-9/32
.35
4251-012
1-1/4
1-13132
2-7132
5132
11/16
4
3-1/2
112
2-1/4
4-5/8
.44
4251-015
1-1/2
1-19/32
2-112
3116
23/32
4
3-27/32
112
2-1/2
5-1/16
.61
4251-020
2
1-27132
3
5116
27132
4
4-3/4
518
3
5-31/32
.95
4251-025
2-1/2
1 2-7132
3-1/2
7116
1-1132
4
5-1/2
5/8
3-1/4
17
1.50
BLIND FLANGE
4 Bolt Holes, 175 psi
�R
{�- BOLTCIRCLE DIA
MAX O.D.
Bolt
No. of Bolt
Min. Bolt
Part Number
Size
R
Bolt Size
Max. O.D.
Approx. Wt. (Lbs.)
Circle Dia.
Holes
Length
4253-007
314
17/32
2-3/4
4
112
2
3-27/32
.30
4253-010
1
23132
3-1/8
4
112
2-1/4
4-1/4
.35
4253-012
1-114
21132
3-1/2
4
112
2-1/4
4-5/8
.40
4253-015
1-1/2
23132
3-27/32
4
112
2-1/2
5-IM6
.52
4253-022
2
27132
4-314
4
5/8
3
5-31/32
.86
4253-025
2-112
1-1/32
5-1/2
4
518
3-1/4
6-15/16
1.70
4253-030
3
1-5/16
6
4
W
3-1/4
7-5/8
1 1.72
FLANGE - TWO PIECE
Van Stone Style, 4 Bolt Holes,175 psi
Socket
M
L R
i I i
N-+ CLE DIA.�
MAX O.D.
Bolt Circle I No, of Bolt I Min. Bolt
Part Number Size L M N R Dia. Holes Bolt Size Length Max. O.D. Approx. Wt. (Lbs.)
4254-030 1 3 2-1/8 4-1/4 9132 1-1/32 6 4 1 5/8 1 3-1/4 7-15132 1.75
23 SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
El
FLANGE - TWO PIECE
Van Stone Style, 4 Boll Holes, 175 psi
PIPEOD.
Spigot
N
L
I
R I BOLTCIRQE DtA--I
MNXOD.
Bolt
No. of Bolt
Min. Bolt
Approx. WL
Part Number
Size
L
N
R
Bolt Size
Max. O.D.
Circle Dia.
Holes
Length
(Lbs.)
4256-007
314
1-15116
13116
17132
2-3/4
4
112
2
3.27132
.30
4256-010
1
2-7132
Vr32
11116
3.1/8
4
W
2-114
4-114
.41
4256-012
1.1/4
2-318
1
11116
3-10
4
1/2
2-114
4-58
.50
4256-015
1-12
2-7116
1-3132
23132
3.718
4
W
2-12
43182
.65
4256020
2
2-314
1-5132
2582
4314
4
1
3
rA5116
1.00
4256-025
2-12
3-1116
1-982
1-182
5-12
4
5B
3.1/4
6-15116
1.62
4256-030
3
3-38
1-13/32
1-1132
6
4
518
}1I4
7-9/16
1.76
TRANSITION UNION
Brass Thread Insert Style
Socket x Fipt
175 psi
NUT M _
O.D.
14—P
=ri
L
Part Number
Size
L
M
N
Nut O.D.
Approx. Wt. (Lbs.)
• 4259-010BR
1
2-13116
1-7/8
1-1132
2-7/8
.52
4259-012BR
1-1/4
3
2-3/16
1-1/8
3-9/32
.98
4259-01513R
1-112
3-3/4
2-112
1-9116
3-17/32
.93
4259-020BR
2
3-5/8
2-7/8
1-1/4
4-5116
1.64
Not intended to convey or dispense water for human consumption through drinking or cooking
UNION
Socket x Socket
175 psi
NUT M
O.D.
N I
Part Number
Size
L
M
N
Nut O.D.
Approx. WL (Lbs.)
4257-007
314
2-38
1-17132
38
2-W
.38
4257-010
1
2.9116
1-2782
3/8
2-78
.41
4257-012
1-1/4
2.2782
2-7132
11132
3-5116
.52
4257-015
1-112
3.18
2-1/2
3/8
3-17/32
.63
4257-020
2
3-58
3-1W
9/16
4-3/16
1.09
MADE IN THE U.S.A. 24
FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS
SofTorqueT" SR FEMALE SPIGOT SPRINKLER HEAD ADAPTER
Gasket Sealed Special Reinforced Plastic Thread Style
Spigot x SR Fipl
With Elastomer Seal - Use NO Thread Sealant
PIPE M7
L M �..
Part Number Size L M7 N Approx. Wt. (Lbs.)
4278-101GSR 314x112 2-114 1318 1 .11
SHORT REPAIR COUPLING
Spigot x Socket
175 psi
L2
L1
L3
S
Part Number
Size
L1
L2
1-3
M
S
Approx. Wt. (Lbs.)
SH118-07CO
3/4
4-13/16
5-17132
1 3/4
1-3/4
2-3/16
.31
SH118-1000
1
4-3/4
5.5/8
1 31132
1 2-1116
2-5/32.
.40
GripLoc'm REPAIR COUPLING — LEAD FREE
w/EPDM 0-Ring Seals
WARNING: DO NOT INSERT FINGERS.
175 psi Maximum
Pressure @ 150°F
Part Number I Size I L I L1 I L2 I M I S I Approx. Wt
SG118-1000 I 1 1-17132 7-17132 4-1/4 2-1/4 2-27132 .73
25 SPEARS® MANUFACTURING COMPANY
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
FlameGuard® CPVC Drain & Swing Check Valves for NFPA 13D Applications Only
Application: FlameGuard® CPVC Orange Swing Check Valves and PVC/CPVC True Union Drain Valves are for use in configuring CPVC Fire
Sprinkler System connection to water supply (riser/drain assembly) in NFPA 13D installations only. These valves are not UL Listed and NOT for
use in any other locations within the fire sprinkler system.
TRUE UNION INDUSTRIAL DRAIN VALVES
CPVC Gray Valve with CPVC Orange End Connector
Socket x Socket
'
E
D
i
A
B
C
Part Number
Size
A
B
C
D
E
1822-007CFG
314
2-1/4
2-3/4
4314
2-78
3318
1822-010CFG
1
2.112
2-7/8
5-118
3.1/8
3.7116
1822-012CFG
1-1/4
3-1/16
3-1/4
53/4
3-5/8
3.7/8
1822-015CFG
1-112
3.172
3-1/2
6-114
4
43116
1822-020CFG
2
4-1/4
43/4
7314
4-12
5.1/8
Not UL Listed
TRUE UNION DRAIN VALVES
PVC Valve with CPVC End Connector
Socket x Socket
D I
4E
_l _
8
C
Part Number
Size
A
B
C
D
E
622-007FG
314
2-1/4
2-3/4
43/4
2
3
622-010FG
FN,—tUL
1
2-1/2
2-7/8
5-1/8
2-5116
3-7116
isted
MADE IN THE U.S.A. 26
FlameGuar& CPVC FIRE SPRINKLER PIPING PRODUCTS
COMPACT 2000 DRAIN VALVE E
Socket x Socket
D
s�c
Part Number
Size
A
B
C
D
E
6622-0117CO
314
1-13/16
1.12
3-9116
2
3
6622-01000
1
2.1116
13/4
4
25116
3-7116
Not UL Listed
CPVC SWING CHECK VALVES
Socket x Socket T
A
�B
C
Part Number
Size
A
B
C
D
Approx. WL (Lbs)
S1520-1000
1
1-11/16
25/16
4-9116
2518
.33
S1520.12CO
1-1/4
2-1/16
2-15116
5-12
33/8
.42
S1520-15C0
1-1/2
2-7116
3
5518
M18
.89
Not UL Listed
CPVC SPECIAL REINFORCED
THREAD INLET SWING CHECK VALVES
SR Fipt x Socket
A — —.— D
B
C
Part Number
Size
A
B
C
D
Approx. Wt. (Lbs)
S1520-ICFSRSCO
1
1-11116
2-15116
4-9116
2.58
.33
S1520-12FSRSCO
1-1/4
2-1116
M18
5-1/2
3-318
.42
S1520-15FSRSCO
1-1/2
2-7116
3-11116
5518
33/8
.89
Not UL Listed
27 SPEARS® MANUFACTURING COMPANY
NOTES
PRODUCT LIMITED LIFETIME WARRANTY
Except as otherwise specified for certain products, mandated by law or herein provided, Spears® Manufacturing Company ("Company) warrants
Standard Catalog Products ('Products") which have been directly manufactured by them to be free from defects in material and workmanship for as long
as the original intended end user of the Products (°End User) retains ownership and possession of the Products and complies with this Warranty
('Warranty Period'). Each other person or entity acquiring or employing the Products, including buyers, contractors and installers ('Buyer) and End Users
(°Buyer/End User) agrees that this Warranty shall be effective only during the Warranty Period so long as the Products are used solely for the normal purposes
for which they are intended and in conformance with industry established standards, engineering, installation, operating, and maintenance specifications,
recommendations and instructions including explicit instructions by the Company; the Products are properly installed, operated and used, and have not been
modified; and all the other terms of this Warranty are complied with. Any violation thereof shall void this Warranty and relieve Company from all obligations arising
from this Warranty and the Products.
Upon receipt or discovery of any Products that appear questionable or defective each Buyer/End User shall promptly inspect and return any such Prod-
uct to the Company at 15853 Olden Street, Sylmar, California 91342, accompanied by a letter stating the nature of any problems. If the Prod-
ucts are determined by Company to be defective in materials or workmanship directly provided by Company, Company, at its sole option, may ei-
ther repair or replace the defective Products, or reimburse applicable Buyer/End User for the cost of such Products. The applicable Buyer/End
User shall bear all applicable shipping costs. THIS SHALL BE BUYERS/END USERS' SOLE REMEDY. EACH BUYERIEND USER AGREES
THAT COMPANY WILL NOT BE RESPONSIBLE FOR ANY OTHER OBLIGATIONS RELATING TO THE PRODUCTS, INCLUDING ANY OTH-
ER MATERIALS OR LABOR COSTS, LOSS OF USE OR ANY OTHER ITEM OR FOR ANY DELAYS IN COMPLYING WITH THIS WARRANTY
BEYOND COMPANY'S REASONABLE CONTROL.
COMPANY SHALL NOT BE LIABLE FOR, DOES NOT ASSUME, AND EXPRESSLY DISCLAIMS, ANY LIABILITY, RESPONSIBILITY AND
DAMAGES: DUE TO ANY BUYERIEND USER'S FAILURE TO COMPLY WITH THIS WARRANTY, INCLUDING IMPROPER INSTALLATION,
USE OR OPERATION; USE WITH PRODUCTS FROM OTHER MANUFACTURERS THAT DO NOT MEET ASTM OR OTHER APPLICABLE PRODUCT
STANDARDS; IMPROPER CONTROL OF SYSTEM HYDRAULICS, IMPROPER WINTERIZATION PROCEDURES, IMPROPER VOLTAGE SUPPLY, CON-
TACT WITH INCOMPATIBLE MATERIALS OR CHEMICALS, EXCAVATION/DIGGING, EXCESSIVE WEIGHT, AND VANDALISM; DUE TO REASONABLE
WEARAND TEAR AND DUE TO ANY ACTS OF NATURE, INCLUDING LIGHTNING, EARTHQUAKES, GROUND MOVEMENT, FROST HEAVE, OR FLOODS.
COMPANY EXTENDS ONLYTHIS WARRANTYAND EXPLICITLY DISCLAIMSALL OTHER WARRANTIES, WHETHER IMPLIED OR OTHERWISE EXPRESSED,
WHETHER ORAL, STATUTORY OR OTHERWISE, INCLUDING ANY IMPLIED WARRANTIES OR AFFIRMATIONS FOR SUITABILITY, MERCHANTABILITY OR
FITNESS FORA PARTICULAR PURPOSE. NO AFFIRMATION BY COMPANY ORANY OF ITS REPRESENTATIVES, BY WORDS, CONDUCT OR OTHERWISE,
SHALL CONSTITUTEA WARRANTY. THIS WARRANTY MAY NOT BE TRANSFERRED, EXTENDED, ALTERED OR OTHERWISE MODIFIED IN ANY MANNER,
EXCEPT BY WRITTEN AGREEMENT SIGNED BY COMPANY.
BY ITS ACCEPTANCE OF THE PRODUCTS, EACH BUYERIEND USER EXPRESSLY WAIVES ALL OTHER LIABILITY OR OBLIGATION OF
ANY KIND OR CHARACTER OF COMPANY, INCLUDING LIABILITY PREDICATED UPON CONTRACT, TORT, STRICT LIABILITY OR OTHER
LEGAL OR EQUITABLE GROUNDS, AND ALL, IF ANY, DAMAGES AND LOSSES AS A RESULT THEREOF, INCLUDING ALL, IF ANY,
COMPENSATORY, GENERAL, SPECIAL, CONSEQUENTIAL, INCIDENTAL, OR PUNITIVE DAMAGES. WITH RESPECT TO SUCH WAIVERS,
EACH BUYERIEND USER EXPLICITLY WAIVES CALIFORNIA CIVIL CODE §1542 WHICH STATES "A GENERAL RELEASE DOES NOT
EXTEND TO CLAIMS WHICH THE CREDITOR DOES NOT KNOW OR SUSPECT TO EXIST IN HIS FAVOR AT THE TIME OF EXECUTING THIS RELEASE,
WHICH IF KNOWN BY HIM MUST HAVE MATERIALLY ADVERSELY AFFECTED HIS SETTLEMENT WITH DEBTOR" AND ALL OTHER SIMILAR STATU-
TORY, COMMON AND CASE LAW RIGHTS, DEFENSES AND LIMITATIONS.
Having previously independently inspected the Products, or a sample, as fully as desired, or having the opportunity to and having not done so,
upon acceptance of delivery of the Products, and except as otherwise herein explicitly provided, each Buyer/End User by acceptance or use of the Products
accepts them in theirAS IS" and "WITH ALL FAULTS" condition without any otherwarranty, expressed, implied or otherwise, and accepts and assumes the entire
risk and cost of all servicing, remediation and consequences thereof. This Warranty shall be governed by California law and any unenforceable provisions severed
without affecting the remaining provisions. As used herein, 'including' includes 'without limitation."
Spears° Quality Policy
It is the policy and objective of Spears® Manufacturing Company to produce a superior quality product suitable for its intended use, with
regard to functionality, structural integrity and conformance to established industry standards and practices. It is the commitment of this
Company to do so in a manner which provides consistency of product quality, optimum availability, and superior customer service, while
maintaining efficiency of operations and profitability necessary to perpetuate product improvement and customer satisfaction. Furthermore,
it is recognized that the attainment of these objectives is the responsibility of all Company operations and personnel according to their
respective functions.
The information contained in this publication is based on cuff ant information and product design at the time of publication and is subject to change vdthout notricaton. Our ongoing
commitment to product improvement may result in some variations. No representations, guarantees or waffanties of any kind are made as to its accuracy, suitability for particular
application or results to be obtained therefrom. For information not contained herein, please contact Spears®Technical Services Department ]Nest Coast:(818) 364-1611 — East Coast:
(676) 985-1263]. Reproduction of this publication in whole or in part is prohibited without the authorized consent of Spears° Manufacturing Company, Sylmar, California.
0 Copyright 2014 Spears® Manufacturing Company. All Rights Reserved. Printed in the United States of America.
SPEARS® MANUFACTURING COMPANY
Corporate Office
SPEAKS 15853 Olden Street • Sylmar, CA 91342
PO Box 9203 • Sylmar, CA 91392
(818) 364-1611 - hftp://www.spearsmfg.com
B Copyright 2015 Spears® Manufacturing Company. All Rights Reserved. Printed in the United States of America 11115
Fig. 22 - Hanger for CPVC Plastic Pipe
Single Fastener Strap Type
Size Range — 3/4" thru 2" CPVC pipe
Material — Pre -Galvanized Steel
Function — Intended to perform as a hanger to support CPVC piping used
in automatic fire sprinkler systems. The product acts as a hanger when tab
is upward and the fastener screw is in the horizontal position. Figure 22 can
be installed on the top of a beam, but in this situation acts as a guide to
the piping which is supported by the beam itself. It is not intended to sup-
port CPVC pipe from under a flat horizontal surface, such as a ceiling. For
this type of installation, use the TOLCOO Fig. 23, Double Fastener Strap for
CPVC Piping. Fig. 22, when inverted, with the hanger tab downward, can
function as a restrainer to prevent the upward movement of the sprinkler
head during activation.
Approvals — Underwriters' Laboratories Listed in the USA (UL) and Canada
(cUL) to support fire sprinkler piping. May be installed in wood using
fasteners supplied with product, or into minimum 20 gauge steel using (1)
1/4" x 1" tek type screw. Meets and exceeds the requirements of NFPA 13,
13R and 13D.
C @US USTEO
SG NWD
BY
Features — Fig. 22 incorporates features which protect the pipe and ease installation. The flared edge design pro-
tects CPVC pipe from any rough surface. It is easily attached to the building structure using the special UL Listed
hex head self threading screw' furnished with the product. It is recommended that rechargeable electric drills fit-
ted with a hex socket attachment to be used as installation tools. No impact tools (such as a hammer) are allowed.
Damage has been known to result from installations using impact type tools. No pre -drilling of a pilot hole in wood is
required.
Finish — Pre -Galvanized
Order By — Figure number and CPVC pipe size.
' Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
Dimensions -Weights
CPVC
Max. Hanger
Fastener Hex
Approx.
Pipe Size
A
B
C
Spacing (Ft.)
Head Size
WtJ100
3/4
27/16
15/16
1 V116
51A
5/16
9
1
211/16
17/16
1V6
6
5/16
9
11/4
31/16
18/8
13/16
61/2
5/16
11
11/2
35/16
1Y74
1Y116
7
5116
12
2
33/4
21A
13/16
8
5/16
15
OFFICF/MANUFACTURING FACILITY- 1375 SAMPSON AVE.- CORONA, CA 92879-PH. 951.737.5599- FAX: 951.737.0330
CUSTOMER SERVICE - 800.786.5266
w ..fokoxom
Fig. 23 - Hanger for CPVC Plastic Pipe
n, Double Fastener Strap Type
SizelRange — 3/4" thru 3" CPVC pipe
, ._,
yj1 , , l eta al bByre-Galvanized Steel
Function — Intended to perform as a hanger/restrainer to support
CPVC piping used in automatic fire sprinkler systems. Fig. 23 can
be installed on the top, bottom or side of a beam. The Fig. 23 also
functions as a restrainer to prevent the upward movement of the
sprinkler head during activation.
Approvals — Underwriters' Laboratories Listed in the USA (UL)
and Canada (WL) sizes 3/4" thru 2" to support fire sprinkler piping.
May be installed in wood using fasteners supplied with product,
or into minimum 20 gauge steel using (2) 1/4" x 1" tek type screw.
Meets and exceeds the requirements of NFPA 13, 13R and 13D.
Features — Fig. 23 incorporates features which protect the pipe
and ease installation. The flared edge design protects the CPVC
pipe from any rough surface. It also incorporates snap restrain-
ers allowing easier and faster installation. Easily attaches to the
building structure using the two UL Listed hex head self thread-
ing screws` furnished with the product. It is recommended that
rechargeable electric drills fitted with a hex socket attachment be
used as installation tools. No impact tools (such as a hammer) are
allowed. Damage has been known to result from installations using
impact type tools. No pre -drilling of a pilot hole in wood is required.
Finish — Pre -Galvanized
Order By — Figure number and pipe size
' Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
C @Us u5TE0
Dimensions -Weights
CPVC
Max. Hanger
Fastener Hex
Approx.
Pipe Size
A
B
C
Spacing (Ft.)
Head Size
WtJtoo
3/4
31h
19/16
1Vi6
51h
5/16
9
1
33A
111/16
13/16
6
5/16
9
11/4
43he
2%2
13/16
61h
5/16
11
11h
47/is
21h2
13/16
7
5/16
12
2
47A
27/16
13/i6
8
5/16
15
21/2
109/32
211/16
13/18
Consult Factory
5/16
22
3
117/S
3
13/16
Consult Factory
5/16
25
OFFICE/MANUFACTURING FACILITY -1375 SAMPSON AVE. - CORONA, CA 92879 - PH: 951.737.5599 - FAX: 951.737.0330
CUSTOMER SERVICE - 800.766.5266
38
Fig. 28M - Offset Hanger and Restrainer for
CPVC Plastic Pipe and IPS Pipe
Size Range — 3/4" thru 1-1/4"
Material — Carbon Steel, Pre -Galvanized
Function — Designed to be used as a hanger and restrainer for CPVC piping or
steel piping where the "stand-off' design will ease installation by eliminating the
need for wood blocking.
Features —
• Flared edge design protects CPVC pipe from any rough or abrasive
surfaces
• Unique snap -on design holds pipe firmly in place and allows retrofit
type of installation
• The "Stand -Off' design eliminates the need for wood block extension
• Can be installed on horizontal or vertical piping regardless of mounting
surface orientation
• Attaches easily to wood structure with two hex head self -threading
screws furnished with product
• Installs easily using rechargeable electrical driver with 5/16" extension
socket eliminating impact tool damage to pipe
• Attaches easily to steel, minimum 18 gauge with (2) 1/4" x 1" tek type
self drilling tapping screws
• cULus Listed as a hanger and a restrainer for fire sprinkler piping
Installation Note — When installed in wood structural member and threads
from the #10 x 1" screws are exposed, use FIG. 27B speed nut to secure
Approvals — Underwriters' Laboratory Listed in the USA (UL) and Canada (cUL)
to support automatic fire sprinkler systems. May be installed into wood using fas-
teners screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D.
Fig. 28M satisfies the UL vertical restraint requirements where needed.
Order By — Figure number and pipe size
Patent #7,744,042
iTRAINT
RESTRAINT
Dimensions • Weights
Max.
Spacing
Pipe
required per
Approx
Size
A
B
C
NFPA 13 for
WtJ100
CPVC plastic pipe
3/4
2
3/16
3-5/16
5'-6"
9
1
2-1/8
3/16
3-1/2
6'-0"
12
1-1/4
2-5/16
3/16
3-1/2
6'-6"
13
C @US LISTED
TOLCO FIG. 27B
(2) REQUIRED
5B
HANGER AND RESTRAINT
APPLICATION
TOLCO FIG. 27B--- " II `�,W
(1) REQUIRED "
n �
HIGH SIDE Lj
OF HANGER
DETAIL A
HANGER APPLICATION
mOFFICF7MANUFACTURING FACILITY •1375 SAMPSON AVE. •CORONA, CA 92879• PH: 95IJ37.5599• FAX. 951.737.0330
' CUSTOMER SERVICE • 800.786.5265
W .fokv.wm
High-performance intumescent firestop
sealant FS-ONE MAX
Applications
■ For effectively sealing most common through penetrations in a variety
of base materials
■ For use on concrete, masonry and drywall
■ Mixed and multiple penetrations
■ Metal pipe penetrations: copper, steel and EMT
■ Insulated metal pipe penetrations: steel and copper
■ Plastic pipe penetrations: closed or vented
Advantages
■ US -produced: "Buy American" compliant
■ One product for a variety of common through penetrations
■ Cost-effective, easy -to -use solution
■ Water -based and paintable
■ Industry -leading VOC results
■ Ethylene glycol -free
FBG
ratpid
Chemical Mold and milder
assistant resistant
FlLI, VOID OR CFVRY MA"'
*ug,
J ♦e FOR USE IN THROUGH PENElR4TONEMS �YPaYm C UL US SEE IILFlRE RESISTANCE DIRMTCPY
Intertek
data
Chemical basis
Water -based acrylic dispersion
Approx. Density
84.31b/IP
Color
Red
Application temperature range
41 - 104 "F
Approx. cure time')
4 mm/3 days
Temperature resistance range
-4 to 212 -F
Mold and mildew performance
Class 0(ASTM G21-96)
Mold and mildew resistance
Yes
Surface burning characteristics
UL 723(ASTM E84)
Flame spread:0
Smoke development; 10
Tested in accordance with
UL 1479, ASTM H14, ASTM E84,
CAN/ ULC-S115, ASTM G21, ASTM E90
California State fire marshal approval
CSFM Using 4485-1200:0108 for
FS-ONE MAX Intumescent Firestop
Sealant
Expansion ratto (unrestricted, up to)
1:5
') at 75-F/24°C, 50% relative humidity
{�' R1616t1
order Designation i
Padkage Content
Item number
FS-ONE MAX 20oz foil (3 case + disp)
1x Foil pack dispenser manual CS 270-P1, 75x Firestop sealant FS-ONE MAX 20 oz foil
3WO252
Fs -ONE MAX 10oz tube (1 case)
12x Firestop sealant FS-ONE MAX 10 oz cartridge
3WO249
FS-ONE MAX 5 gallon (18 pails)
tax F'isestap sealant FS-ONE MAX 5 gallon pail
SWO263
FS-ONE MAX 20oz foil (1 case)
25x Firestop sealant IFS -ONE MAX 20 or foil
=0250
FS-0NE MAX 20oz foil (3 cases)
75x Fireatop sealant FS-ONE MAX 20 oz foil
3530251
FS-ONE MAX 20ozFoll-Pallet
600x SONE-MAX 20 cz foil, 290x Bulk Sh_ipping.Condition
_ 35 44713
FS-ONE MAX 10 oz cartridge
TFS+ONE MAX 5 gallon pail - �_—
2101531
Hilti. Outperform. Outlast. U ©LOU El
Hilt!, Inc. (USA) 1.800-879-80001 wwmus.hi0l.com I an espanol 1-800-879-50001 Hill (Canada) Corp. 1-800-363-44581 wwmhilti.ca
ZURN® Model 700XLFP
W� High Capacity Dual Check Valve
Application
Ideal for use where Lead -Free* valves are required. Designed
for Installation on potable water lines to protect against both
backsiphonage and backpressure of polluted water into the
potable water supply. The Model 700XLFP shall provide pro-
tection where a potential health hazard does not exist.
Standards Compliance
• ULB Classified
• ASSEB Listed 1024
• CSAB Certified B64.6
• Certified to NSF/ANSI 372" by IAPMO R&T
(0.25% MAX. WEIGHTED AVERAGE LEAD CONTENT)
Materials
Main valve body
Low Lead Cast Bronze ASTM B 584
Elastomers
Buna Nitrile (FDA approved)
Silicone (FDA approved)
EPDM (FDA approved)
Polymers
Delrin 0, NSF Listed
Springs
Stainless Steel, 300 Series
Connections Legend
U
= Indicates location of "union" connection
FNPT
= Female National Pipe Tapered Thread
FC
= Female Copper Sweat
FMTC
= Female Meter Thread Connection
Features
Sizes: 1", 1 1/4",
1 1/2"
Max. pressure:
175 PSI
Max. temp:
180"F
Connections:
Threaded ANSI B 1.20.1
Copper sweat ANSI B 16.22
(1-1/2" only)
Dimensions & Weights (do not include pkg.)
MODEL
SIZE
in. mm
DIMENSIONS
WEIGHT
lbs. kg
A
in. mm
B
in. mm
1
25
6 5/16
160
3 3/8
86
3.6
1.6
1 114
32
6 5/16
160
3 3/8
86
3.4
1.5
1 112
40
6 5/16
160
3 3/8
86
3.3
1.5
Accessories
❑ Repair kit (RK1-700FP)
❑ Thermal expansion tank (Model XT)
Configurations
SCANNED
BY�
St. LuaeCoulft
0
CIAIVI
FEMALE UNION INLET X FEMALE OUTLET
INLET (UNION)
OUTLET
PART NUMBER
1" FNPT
1" FNPT
1UFX1F-700XLFP
1-1/4" FNPT
1-1/4" FNPT
114UFX114F-700XLFP
1-1/2" FNPT
1-1/2" FNPT
112UFX112F-700XLFP
1-1/4" FMTC'
1-1/4" FMPT
114UFMX114F-700XLFP
1-1/4" FMTC'
1" FNPT
114UFMX1F-700XLFP
1-1/2" FC
1-1/2" FNPT
112UFCX112F-700XLFP
'1-1/4" NPSH threads are used on 1" water meters
Zurn Industries, LLC 11Klklns
1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766
In Canada I Zurn Industries Limited
3544 Nashua Drive, Mississauga, Ontario L4V 1 L2 Ph. 905-405-8272, Fax 905-405-1292
Rev. A
Date: 1/14
Document No. BF-700XLFP
Product No. Model 700XLFP
w .zum.com ) Page 1 of 2
Flovr;Characteristics
_nFha:nl teri
0.00 0.63
0 25 _
Vl
W 20
O 15
WW 10
N
W 5
z 0
O Racd Flow(established by appm dagencies)
MODEL 700XLFP,1 ",14/4" & 1.1/2" (STANDARD & METRIC)
FLOW RATES (Its)
1.26 1.89 2.52 3.15 3.79 4.42 5.05 5.68 6.31
a 0 10 20 30 40 5o
FLOW RATES(GPM)
Typical Installation
Local codes shall govern installation requirements. Unless
otherwise specified, the installation shall be in accordance
with the manufacturer's instructions and the latest edition of
the Uniform Plumbing Code. The installation shall be made
so that no part of the unit can be submerged.
VERTICAL INSTALLATION
60
138 N
W
103 0
313S�f�l�t�C� "
M ,
I :I •I rt
Capacity thru Schedule 40 Pipe (GPM)
Pipe size
5 ft/sec
7.5 ft/sec
10 ft/sec
15 fUsec
1"
13
20
27
40
11/4"
23
35
47
70
1 1/2"
32
48
63
95
2"
52
78
105
167
DIRECTION OF FLOW -D
INDOOR INSTALLATION
MODEL 700XLFP
Specifications
The Dual Check Valve Backflow Preventer shall be certified to NSF/ANSI 372 and ASSEO Listed 1024. The main body shall
be low lead cast bronze (ASTM B 584), the check assemblies shall be DELRIN O. The seal ring and o-rings shall be Buna
Nitrile or Silicone. The Dual Check Valve shall be a ZURN WILKINS Model 700XLFR
Zurn Industries, LLC I Wilkins
1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766
In Canada I Zurn Industries Limited
3544 Nashua Drive, Mississauga, Ontario L4V 1L2 Ph. 905-405-8272, Fax 905-405-1292
Page 2 of 2
FlameGuardTM CPVC Drain & Check Valves
For NFPA 13D Applications Only
Application: FlameGuardTM' CPVC Orange Drain Valves and Check Valves are for use in configuring CPVC Fire
Sprinkler System connection to water supply (riser/drain assembly) in NFPA 13D installations only. These valves
are NOT for use in any other locations within the fire sprinkler system.
Drain Valve
Check Valve
Special Reinforced (SR) Threaded Inlet Check Valve
CPVC Drain Valves
Disc
Price
Part Number
Size
Code
Each
Socket x Socket
6622-007C0
3/4
004
22.68
6622-01000
1
0041
28.36
CPVC Check Valves
Disc Pri
Part Number Size I Code Each
Socket x Socket
S1520-1000
1
004
22.56
S1520-12C0
1-114
004
25.22
51520-15C0
1-1/2
064
28.36
CPVC Special Reinforced Thread Inlet Check
Valves
Disc Price
Part Number Size Code Each
SR Fipt x Socket
51520-10FSRK0
1
004
- 24.44
51520-12FSRSCO
1-1/4
004
28.22
51520-15FSRSCO
1-112
004
33.47
General Installation Information: Socket end
connections should be installed using Spears@ FS-5
One -Step Cement for use with Spears@ CPVC Fire
Sprinkler Products. Threaded connections should be
made using Spears@ BLUE 75TM' Thread Sealant
tested for compatibility with CPVC materials. Swing
check valves are designed for horizontal installations,
but may be installed in up -flow only vertical position.
Check valves MUST be installed with the valve's FLOW
arrow pointing in the direction of the flow. Do not install
valve upside down.
NOT FOR USE WITH COMPRESSED AIR OR GAS
Page 1 Spears® Manufacturing Company
Progressive Products from Spears® Innovation and Technology
FlameGuardTM CPVC Drain & Check Valves
For NFPA 13D Applications Only
Drain Valve:
Nominal Size Range
Type
Material
Seats
Seals
Handle
End Connections
Check Valve:
Nominal Size Range
Type
Material
Seat
End Connections
Specifications
3/4" 1-
1/4-Turn Ball Valve, Maintenance -free Sealed Unit
CPVC, Orange
PTFE/HDPE
EPDM
Polypropylene, Red
Socket x Socket
Socket x Socket
Part Number
Nominal
Size
1 Dimension Reference
Inches, t 1116
A B
C
D
E
6622-007C0
1 314
1 1-13116 1-1/2
1 3-9116
1 2
2
6622-01000
1 1
1 2-1116 1-3/4
1 4
1 2-5116
2-5/16
1",1-1/4°,1-1/2°
Swing Check, Maintenance -free Sealed Unit
CPVC, Orange
EPDM
Socket x Socket
Socket x Special Reinforced (SR) Female Plastic Thread
Socket x Socket
Part Number
SR Thread x Socket
Part Number
Nominal
Size
Dimension Reference inches,* 116
C,
(GPM)
A
B
C
D
Socket
SR Thread
S1520-1000
S1520-10FSRSCO
1
1-11116
2-5/16
2-15116
4-9/16
2-5/8
33
S1520-12CO
S1520-12FSRSCO
1-1/4
2-1/i6
2-15116
3-5/S
5-1/2
3_38
42
S1520-15CO
S1520-15FSRSCO
1 1-1/2
1 2-7/16
1 3
1 3-11116
15-5/8
33/8
89
Made in the U.S.A.
NOT FOR USE WITH COMPRESSED AIR OR GAS
Progressive Products from Spears® Innovation and Technology
Page 2
-L
O
O
O
CA
.P
00
N
N
:r.
C7
O
FPPI"
28
Pressure Gauges
Pressure Gauges and Accessories
Each gauge features an impact and corrosion resistant case made from
ABS (plastic).
Features a phosphor bronze bourdon tube movement with
white enameled brass dial face with large numbers for easy reading. Dual
scale to 300 PSI/2000Kpa. UL/ULc Listed and FM Approved.
Part No.
Description Box City.
11-550
Water Gauge 0-300 UUFM 60
11-551
Air Gauge 0-300 UUFM 60
11-552
Air Gauge w/Retard 60
11-553
Air/Water Gauge 0-300 UUFM 60
11-555
Resid. 2" Spr. Gauge 0-300 100
11-560
Liquid Filled, 0-300 100
Pressure Gauge Kits
Each kit contains a pressure gauge', 1/4" 3-way valve', 1/4" x 4" black pipe
nipple, 1/2" and 1/4" bushing and a 1/4" IPS pipe plug, blister packed to
make sure all components get to the job.
Part No. Description Box City.
11-565 Gauge Kit, Water 8
11-566 Gauge Kit, Air -Water 8
11-567 Gauge Kit, Air 8
11-568 Gauge Kit, Air w/Retard 8
Components are UUULc or FM approved or both.
ARGCO
n7CC THREAD SEAL TAPE
(INDUSTRIAL]
Meets MIL Spec T-27730A
-For all industrial applications.
*Made from 100% virgin PTFE.
•No pigments, no additives.
-Exceeds MILSpec T-27730A.
•Temperature range of -450F to +550F.
*Available in a variety of sizes and densities.
-May be used on all applicationsincluding water, oil, chemical, medical, and food processing
where non -contamination standards are high.
60-10-260
1/2" x 260" STANDARD 0.4 DENSITY INDUSTRIAL GRADE
60-10-262
112" x 520" STANDARD 0.4 DENSITY INDUSTRIAL GRADE
60-10-264
1/2" x 1296" STANDARD 0.4 DENSITY INDUSTRIAL GRADE
60-10-262
3/4" x 260" STANDARD 0.4 DENSITY INDUSTRIAL GRADE
60-10-267
3/4" x 520" STANDARD 0.4 DENSITY INDUSTRIAL GRADE
60-10-269
3/4" x 1296" STANDARD 0.4 DENSITY INDUSTRIAL GRADE
60-10-270
1" x 260" STANDARD 0.4 DENSITY INDUSTRIAL GRADE
60-10-271
1" x 520" STANDARD 0.4 DENSITY INDUSTRIAL GRADE
60-10-272
1" x 1296" STANDARD 0.4 DENSITY INDUSTRIAL GRADE
The information contained herein is produced in good faith and is believed to be reliablebut is for. guidance only. ARGCO and its agents cannot
assume liability or responsibility for results obtained in the use of its product by persons whose methods are outside or beyond our control. It is the
user's responsibility to determine the suitability of any of the products, methods of use, or preparation prior to use, mentioned in our literature. It is
the user's responsibility to observe and adapt such precautions as may be advisable for the protection of personnel and property in the handling and
use of any of our products.
FOR MORE INFORMATION CALL ARGCO AT 1-800-854-1015
OR LOG ONTO WWW.ARGCO.COM