REPORT
Owens Corning Roofing and Asphalt, LLC Evaluation Report 111980.11.08-R8
One Owens Corning Parkway FL11602-R7
Toledo, OH 43659
(740)321-6345
Date of Issuance:11/03/2008
Revision 8: 09/14/2018
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products
described herein have been evaluated for compliance with the 6tb Edition (2017) Florida Building Code sections noted
herein.
DESCRIPTIory: Titamurti'."_ Raof,Underlaym"ents
tr
LABELING: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. of any changes to the
product(s), the Quality Assurance or the production facility location(s). NEMO) etc. requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "NEMOIetc. Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 7.
Prepared by:
Robert 1.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
CERTIFICATION OF INDEPENDENCE:
'e4. ...i'y',d
ion
The facsimile seal appearing was authorized by Robert
Nieminen,P.E. on 09/14/2018. This does not serve as an
electronically signed document.
1. NEMO ETC, LLC does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMO ETC, LLC is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
S. This is a buildingcode evaluation. Neither NEMO l etc. nor Robert Nleminen, P.E.are, in anyway, the Designer of Record forany project
on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically
for that purpose.
ONEMO etc.
ROOFING COMPONENT EVALUATION:
Product Category: Roofing
Sub -Category: Underlayment
Compliance Statement: TitaniumTM Roof Underlayments, as produced by Owens Corning Roofing and Asphalt, LLC,
have demonstrated compliance with the intent of the following sections of the 6" Edition (2017) Florida Building
Code through testing in accordance with applicable sections the following Standards. Compliance is subject to the
Installation Requirements and Limitations / Conditions of Use set forth herein.
'Section
Property
Standard
Year
1507.1.1, R905.1.1 Exception
Unrolling, Breaking Strength, Pliability
ASTM D226
2009
1507.1.1, R905.1.1 Exception
Tear Strength
ASTM D1970
2015
1507.1.1, T1507.1.1, 1507.2.9.2
Physical Properties
ASTM D1970
2015
1507.3.3
Physical Properties
FRSA/TRI April 2012 (04-12)
2012
TAS 110
Accelerated Weathering
ASTM D4798
2011
TAS 110
Pull -through resistance
TAS 117(B)
1995
11Entity__ ___
Examination
Reference
ERD (TST6049)
Physical Properties
115010.04.09
ERD (TST6049)
Physical Properties
115010.05.10
ERD (TST6049)
Physical Properties
135520.06.11
ERD (TST6049)
ASTM D226
138010.08.11
ERD (TST6049)
Wind Uplift
135520.08.11-1
ITS (TST1509)
ASTM D226
311801000Q-003
ITS(TST1509)
ASTM D226
3130639COQ-002A
ITS (TST1509)
Physical Properties
3126617COQ-005
ITS(TST1509)
ASTM D226
101823107COQ-011
Owens Corning
Product equivalency
Declaration
PRI (TST5878)
ASTM D1970
OCF-341-02-01
PRI (TST5878)
ASTM D1970; Tear strength
OCF-331-02-02
PRI (TST5878)
ASTM D1970; Tear strength
OCF-332-02-02
PRI (TST5878)
ASTM D1970; Tear strength
CCF-334-02-02
PRI (TST5878)
FRSA/TRI April 2012 (04-12), partial
OCF-343-02-01
PRI (TST5878)
ASTM D4798
OCF-341-02-01
PRI(TST5878)
TAS 117(B); Pull -through
OCF-422-02-02
PRI (TST5878)
FRSA/TRI April 2012 (04-12), partial
OCF-425-02-01
ITS (QUA1673)
Quality Control
ITS Listings
ITS (QUA1673)
Quality Control
Service Confirmation
Date
04/29/2009
05/14/2010
06/15/2011
08/11/2011
08/12/2011
04/26/2007
08/21/2007
10/31/2007
01/23/2015
06/18/2018
09/20/2017
10/03/2017
10/03/2017
10/03/2017
11/09/2017
11/27/2017
04/03/2018
08/13/2018
Current
09/30/2017
4.1 Self -Adhering Underlayments:
�,11:1, Titarti0m PSU„30 is an unreinforced polymer modified bitumen material adhered to the underside of a polymer-
r� ._. ated, sp the Ic woven sheet. The underside is backed with a release film. Unit weight 24lbs/square. Meets ASTM
D1970 and FRSA/TRI April 2012.
NEMO ETC, LLC Evaluation Report 111980.11.08-R8
Certifimte o)Author&otlon#32455 6- EDITION (2017) FBC NON-HVHZ EVALUATION FL11602-117
Titanium Roof Underlayments Revision 8:09/14/2018
Page 2 of 7
ONEMO etc.
4.2 Mechanically Fastened Underlavments:
4.2.1 TitaniumTM UDL-25 is a synthetic sheet -type underlayment comprised of a woven core coated on one side with a
polymer coating. Unit weight 2.5 lbs./square; meets FBC 1507.1.1 & R905.1.1 (Exception).
4.2.2 TitaniumTM UDL-30 is a synthetic sheet -type underlayment comprised of a woven core coated on both sides with a
polymer coating. Unit weight 4.0 lbs./square; meets FBC 1507.1.1 & R905.1.1 (Exception).
4.2.3 TitaniumTM UDL-50 is a synthetic sheet -type underlayment comprised of a woven core coated on both sides with a
polymer coating. Unit weight 4.7 lbs./square; meets FBC 1507.1.1 & R905.1.1 (Exception).
5.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or
design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Fire Classification is not part of this report; refer to current Approved Roofing Materials Directory for fire ratings of
this product.
5.4 TitaniumTM Roof Underlayments may be used with any prepared roof cover where the product is specifically
referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction
for approval based on this evaluation combined with supporting data for the prepared roof covering.
5.5 Allowable Roof Covers:
TABLE
I: ROOF COVEROPTIONS
ASPHALT
WOOD SHAKES
UNDERLAYMENT
SHINGLES
NAIL -ON TILE
FOAM -ON TILE
METAL
&SHINGLES
SLATE
Titanmrim SU3D__
-,
es
_
yes'
Yes
,. Yes
-
fyYes+'^
ubai, UAE _
_
Titanium PSU-30
Yes
Yes
No
Yes
Yes
Yes
(Brentwood, NH)
Titanium UDL-25
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Titanium UDL-30
Yes'
(Base sheet In 2-ply
(Base Sheet in 2-ply
Yes
Yes
Yes
'yZ"
system)
Titanium UDL-50
Yes
No
No
Yes
Yes
Yes
5.5.1 "Foam -On Tile" is limited to use of following Approved tile adhesives / underlayment combinations.
TABLE
1A: ALLOWABLE TILE ADHESIVE/ UNDERLAYMENT
COMBINATIONS'
ADHESIVE
FLORIDA PRODUCFAPPROVAL
UNDERLAYMENTS
Dow TileBonds"
FL22525
Titanium PSU-30 (Dubai, UAE)
ICP Adhesives Polyset® AH-160
FL6332
Titanium PSU-30 (Dubai, UAE)
' Refer to Tile Manufacturers or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
NEMO ETC, LLC Evaluation Report 111980.11.08-R8
Certificate of Authorization#32455 0 EDITION(2017) FBC NON-HVHZ EVALUATION FL11602-R7
Titanium Roof Underlayments Revision 8: 09/14/2018
Page 3 of 7
ONEMOletc.
5.6 Allowable Substrates: Titanium PSU-30:
5.6.1 Direct -Bond to Deck:
➢ New untreated plywood;
➢ Existing untreated plywood, primed as needed with D41 primer to achieve bond.
5.6.2 Bond to Mechanically Attached Base Sheet:
➢ ASTM D226, Type 1 or II felt.
➢ Titanium UDL-30 (primed with D41 primer) or UDL-30 (inverted).
5.6.3 Wind Resistance for Underlayment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12) does not
address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment
forms part of the load -path. The following wind uplift limitations apply to underlayment systems that are not
addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile applications. Maximum Design Pressure is
the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing
pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April
2012 (04-12), Appendix A, Table SA or FBC 1609 for determination of design wind loads.
#1 Maximum Design Pressure =-45psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Primer: (Optional) ASTM D41
Underlayment: One or two plies, Titanium PSU-30 (Dubai, UAE), self -adhered and back -nailed max. 12" o.c. in
accordance with Owens Corning Roofing and Asphalt, LLC published installation requirements.
#2 Maximum Design Pressure=-30 psf*:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Base Sheet: Titanium UDL-30 (inverted)
Fasteners: 12 ga. annular ring shank nails having not less than 20 rings per inch, heads.not less than 3/8 inch
diameter and length sufficient to penetrate through the thickness of deck not less than 3/16-inch
with min. 32 ga., 1-5/8" diameter tin caps
Spacing: 6-inch o.c. at 4-inch wide side laps and 12-inch o.c. at three (3), equally spaced center rows.
Primer: ASTM D41 primer required at all tin -caps.
Underlayment: One or two plies, Titanium PSU 30 (Dubai, UAE), self -adhered and back -nailed max. 12" o.c. in
accordance with Owens Corning Roofing and Asphalt, LLC published installation requirements.
#3 Maximum Design Pressure =-30 psf*
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Base Sheet: Titanium UDL-30 (printed side up)
Fasteners: 12 ga. annular ring shank nails having not less than 20 rings per inch, heads not less than 3/8 inch
diameter and length sufficient to penetrate through the thickness of deck not less than 3/16-inch
with min. 32 ga., 1-5/8" diameter tin caps.
Spacing: 6-inch o.c. at 4-inch wide side laps and 12-inch o.c. at three (3), equally spaced center rows.
Primer: ASTM D41 primer required over printed side of UDL-30.
Underlayment: One or two plies, Titanium PSU 30 (Dubai, UAE), self -adhered and back -nailed max. 12" o.c. in
accordance with Owens Corning Roofing and Asphalt, LLC published installation requirements.
NEMO ETC, LLC Evaluation Report 111980.11.08-R8
Certificate of Authorization#32455 6-EDITION (2017) FBC NON-HVHZ EVALUATION FL11602-R7
Titanium Roof Underlayments Revision 8: 09/14/2018
Page 4 of 7
NNEMO etc.
#4 Maximum Design Pressure=-45 psf*:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Base Sheet: Titanium UDL-30 (inverted)
Fasteners: 12 ga. annular ring shank nails having not less than 20 rings per inch, heads not less than 3/8 inch
diameter and length sufficient to penetrate through the thickness of deck not less than 3/16-inch
with min. 32 ga.,1-5/8" diameter tin caps
Spacing: 6-inch o.c. at 4-inch wide side laps and 8-inch o.c. at three (3), equally spaced center rows.
Primer: ASTM D41 primer required at all tin -caps.
Underlayment: One or two plies, Titanium PSU 30 (Dubai, UAE), self -adhered and back -nailed 12" o.c. in
accordance with Owens Corning Roofing and Asphalt, LLC published installation requirements.
#5 Maximum Design Pressure =-45psf':
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority Having
Jurisdiction.
Base Sheet: Titanium UDL-30 (printed side up)
Fasteners: 12 ga. annular ring shank nails having not less than 20 rings per inch, heads not less than 3/8 inch
diameter and length sufficient to penetrate through the thickness of deck not less than 3/16-inch
with min. 32 ga., 1-5/8" diameter tin caps.
Spacing: 6-inch o.c. at 4-inch wide side laps and 8-inch o.c. at three (3), equally spaced center rows.
Primer: ASTM D41 primer required over printed side of UDL-30.
Underlayment: One or two plies, Titanium PSU 30 (Dubai, UAE), self -adhered and back -nailed 12" o.c. in
accordance with Owens Corning Roofing and Asphalt, LLC published installation requirements.
5.6.4.1 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or
exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table 1A.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design
pressure determined in accordance with FBC 1609. In this case, Zones 2 and 3 shall employ an attachment density
designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are
ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies
marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29
(January 2016) for Zone 2/3 enhancements.
5.7 Exposure Limitations:
Titanium UDL-25, Titanium UDL-30 or Titanium UDL-50 shall not be left exposed for longer than 30-days.
Titanium PSU-30 shall not be left exposed for longerthan 180-days.
5.8 Tile Slippage Limitations [per FRSA/TRI April 2012 (04-12)1:
When loading roof tiles on the underlayment in direct -deck tile assemblies, the maximum roof slope shall be as
follows. These slope limitations can only be exceeded by using battens during loading of the roof tiles.
TABLE 2: TILE
SLIPPAGE LIMITATIONS
DIRECT -DECK TILE INSTALLATIONS
UNDERLAYMENT
TILE PROFILE
STAGING METHOD MAXIMUM SLOPE
Titanium PSU-30 (Dubai, UAE)
Flat
Max. 30-tile stack 5:12
Lugged
Max.10-tile stack 6:12
Titanium PSU-30 (Brentwood, NH)
Tiles shall be loaded and staged atop battens, regardless of tile profile or
slope
NEMO ETC, LLC Evaluation Report 111980.11.08-RB
Certificate of Authorization#32455 9-EDMON(2017)FBC NON-HVHZ EVALUATION FL11602-R7
Titanium Roof Underiayments Revision 8: 09/14/2018
Page 5 of 7
ONEMO I etc.
6.1 Titanium Roof Underlayments shall be installed in accordance with Owens Corning Roofing and Asphalt, LLC
published installation requirements subject to the Limitations set forth in Section 5 herein and the specifics noted
below. ,
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to
remove any dust and debris prior to application, and prime the substrate (if applicable).
6.3 TitaniumTM UDL-25, Titanium UDL-30 or Titanium UDL-50:
6.3.1 Shall be installed in compliance with the requirements for ASTM D226, Type I or II underlayment in FBC Table
1507.1.1 or R905.1.1 for the type of prepared roof covering to be installed, considering the wider sheet -width.
6.3.2 Fasteners:
Mechanical attachment of Titanium UDL-25 and Titanium UDL-30 is limited to ring shank roofing nails with
minimum 1-inch diameter plastic caps.
Mechanical attachment of Titanium UDL-50 is limited to ring shank roofing nails with minimum 3/8-inch diameter
heads; ring shank roofing nails with minimum 1-inch diameter plastic caps; screws and plates; or plastic cap staples.
6.3.2.1 Code Reference: The Exception statement in FBC 1507.1.1 and FBC R905.1.1 states: "...except metal cap nails shall
be required where the ultimate design wind speed, Vauw equals or exceeds 150 mph."
Owens Corning Roofing and Asphalt, LLC has furnished data to permit the use of 1-inch diameter plastic cap nails
in lieu of metal cap nails for these applications, when the TitaniumTM UDL-25, Titanium UDL-30 or Titanium UDL-
50 underlayment is installed beneath mechanically fastened prepared roof covers referenced in FBC Table 1507.1.1
or R905.1.1.
6.3.3 Slopes of 4:12 or greater
End (vertical) laps shall be minimum 6-inches and side (horizontal) laps shall be minimum 4-inches.
Minimum attachment shall be in accordance with FBC Table 1507.1.2 or R905.1.1. When batten systems are to
be installed atop the underlayment, the underlayment need only be preliminarily attached pending attachment of
the battens.
6.3.4 Slopes of 2:12 to less than 4:12:
Double layer application; begin by fastening a 25-inch wide strip along the eaves. Place a full -width sheet over the
starter, completely overlapping the starter course. Continue as noted in 6.3.3, but maintaining minimum 25-inch
side (horizontal) laps, resulting in a double -layer application.
6.4 T, itani m^'PSSU, 3`0;�
6.4.1-Tire
Shall be installed in compliance with the codified requirements for ASTM D1970 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed, and Owens Corning published requirements.
TitaniumTM PSU-30 shall be back -nailed max. 12" o.c. in accordance with Owens Corning Roofing and Asphalt, LLC
published installation requirements.
6.4.2 Tile Applications:
Shall be installed in compliance with the requirements for Self -Adhered Membrane underlayment set forth in
FRSA/TRI April2012 (04-12), and Owens Corning published requirements. TitaniumTM PSU-30 shall be back -nailed
max. 12" o.c. in accordance with Owens Corning Roofing and Asphalt, LLC published installation requirements.
Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment. Refer
to Table 2 herein, and Owens Corning Roofing and Asphalt, LLC published requirements for tile staging.
NEMO ETC, LLC Evaluation Report 111980.11.08-R8
Certificate of Authonxatlon#32455 9"'EDI nON(2017)FBC NON-HVHZ EVALUATION FL11602-R7
Titanium Roof Underlayments Revision 8:09/14/2018
Page 6 of 7
ONEMOletc.
6.5 I Titanium 2-Ply System:
6.5.1 The Titanium 2-Ply System consists of a base layer of Titanium UDL-30 (top -surface primed or sheet inverted)
mechanically attached to the wood roof deck followed by Titanium PSU-30, self -adhered.
6.5.2 Non -Tile Applications:
Install Titanium UDL-30 (top surface primed or sheet inverted)in accordance with Section 6.3 followed by Titanium
PSU-30 in accordance with Section 6.4.
6.5.3 Tile Applications:
For nail -on tile installations, install Titanium UDL-30 (top surface primed or sheet inverted) in accordance with
FRSA/TRI April 2012 (04-12), using Section 6.3 as a guide, and considering the wider sheet width relative to ASTM
D226 felt. Then apply Titanium PSU-30 in accordance with Section 6.4.
For adhesive -set tile roofing, refer to Section 5.6.3 herein.
Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment. Refer
to Table 2 herein, and Owens Corning Roofing and Asphalt, LLC published requirements for tile staging.
17. BUILDING PERMIT REQUIREMENTS:
As required bythe Building Official or Authority Having Jurisdiction in orderto properly evaluate the installation of
this product.
8. MANUFACTURING PLANTS:
Contact the noted QA agency for information on product locations covered for F.A.C. 61G20-3 QA requirements.
The following plants have qualified products under their respective physical properties specifications.
Plant
specification
Products
Mission, BC, Canada
FBC 1507.1.1(Exception)
Titanium UDL-30; Titanium UDL-50
Qingdao, China
FBC 1507.1.1(Exception)
Titanium UDL-25; Titanium UDL-30; Titanium UDL-50
Dubai, UAE
FRSA/TRI 04-12 (2-ply system)
Titanium PSU-30 (Dubai, UAE)
Brentwood, NH
ASTM D1970, FRSA/TRI 04-12
Titanium PSU-30 (Brentwood, NH)
9. QUALITY AS57URANCE ENTITY:
IntertekTesting Services NA Inc.—QUA1673; (604) 520-3321
END OF EVALUATION REPORT -
NEMO ETC, LLC Evaluation Report 111980.11.08-RS
Certificate of Authorization 932455 6-EDI nON(2017)FBC NON-HVHZ EVALUATION F1.11602-117
Titanium Roof Undedayments Revision 8: 09/14/2018
Page 7 of 7