DATE: 6/17/19 $ ER #: 19-2996 SCANNED
CLIENT: All Area Roofing BY
ADDRESS: 3921 S. US Highway 1 Fort Pierce, FL 34982 Lucie County
PROJECT: Franklin Residence Flat Wood Non -Insulated Roof Deck
ADDRESS: 400 E. Weatherbee Road Fort Pierce, FL
2017 FBC/ASCE-7 DESIGN PRESSURE CALCULATIONS
Proiect Information:
Height = 8' Exposure: C Basic/Ultimate Wind Speed: V i=163 mph
Length = 37' Category: II Nominal Wind Speed: V.d=V it*40.6
Width = 15' Slope: < 7° (asd = allowable strength design)
Parapet Wall: N/A Residential KZ = 0.85, Kzt = 1.0, Kd = 0.85
Design Calculations:
Velocity Pressure: q = 0.00256*K K tKdV2
Velocity Pressure (u): q=0.00256(0.85)(1.0)(0.85)(163)2 = 49.14 psf
Velocity Pressure (.d): q=0.00256(0.85)(1.0)(0.85)(163*40.6)2 = 29.49 psf
Width of Pressure Coefficient: 0.1(15') = 1.5'
0.4(8') = 3.2' ) use: TO"
Effective Wind Area: <1 Off
For parapet height three feet (3') or larger, zone three (3) shall be treated as zone two (2).
External Pressure Coefficient:
1)
GCP1 =
-1.0
2)
GCP2 =
-1.8
3)
GCP3 =
-2.8
Internal Pressure Coefficient:
1) GCP; = 0.18
REVIEWED FOR
CODE COMPLIANCE
ST. L.UCIE COUNTY
BOCC
re, `:%
v Q ti
Qaawy ��\ t1 &.4ssarance
GL
r4d
Page 2, 6/17/19, Job Order #19-2996
All Area Roofing - Franklin Residence
Flat Wood Non Insulated Roof Deck
400 E. Weatherbee Road; Fort Pierce, FL:
Design Pressures Based on Vasd:
1) Field
2) Perimeter
3) Corners
Attachment Requirements:
P1 = 29.49*[(-1.0) — (0.18)] = -34.8 psf
P2 = 29.49*[(-1.8) — (0.18)] = -58.4 psf
P3 = 29.49* [(-2.8) — (0.18)] = -87.9 psf
The system is acceptable as approved based on the requirements of Florida Product
Approval # FL1654-R23, Appendix 1, page 26 of 65, System No. W-170 with a
maximum design pressure of -90 psf.
Base Ply:
Self adhere one or more plies of Elastoflex SA V Base Ply sheet to the min. 15/32"
plywood deck.
Cap Ply:
Torch apply the Polyflex G Cap Ply sheet to the base ply sheet.
Notes: Corners and perimeter area dimension shall not be less than a = 3'0"
Contractor to verify that the fastening patterns meet manufacturer's
requirements for issuance of a warranty (as applicable).
All work shall be in compliance with the local building code product
control notice of acceptance and manufacturer specifications and Florida
Building Code 2017 Edition.
Wind load calculations based on ASCE-7, FBC 2017, and information
provided by client. Client is responsible for verifying existing/proposed
conditions/decks as it pertains to the above provided product approval.
All work shall be inspected by our field engineer (or authorized
representative) or a building department inspector to verify compliance
with specifications.