HomeMy WebLinkAboutPLANSGENERAL NOTES 1. GENERAL CONTRACTOR AND ALL SUBCONTRACTORS SHALL VISIT THE BUILDING SITE AND VERIFY ALL CONDITIONS PRIOR TO SUBMISSION OF BID. 2. ANY ERRORS, AMBIGUITIES AND OMISSIONS IN THE DRAWINGS AND OR SPECIFICATIONS SHALL BE REPORTED TO A/E FOR CORRECTIONS BEFORE SUBMISSION OF BID. 3. UNLESS EXPRESSLY STIPULATED, NO ADDITIONAL ALLOWANCE WILL BE MADE IN THE CONTRACT AND/OR MANUFACTURES FAVOR OR BY VIRTURE OF ERRORS, AMBIGUITIES AND/OR OMISSIONS WHICH SHOULD HAVE BEEN DISCOVERED DURING THE PREPARATION OF BID ESTIMATE AND DIRECTED TO A/E ATTENTION IN A TIMELY MANNER 4. WRITTEN DIMIENSIONS GOVERN. CONTRACTOR SHALL VERIFY ALL DIMIENSIONS. IN THE EVENT OF CONFLICT, THE A/E SHALL BE NOTIFIED PRIOR TO PROCEEDING WITH ANY WORK. 5. CONTRACTOR AND SUBCONTRACTORS DOING WORK ON THIS PROJECT SHALL BE FURNISHED WITH A DAMAGE INSURANCE AGAINST ACCIDENTS OF ALL KINDS AND THE OWNER SHALL BE FURNISHED WITH A CERTIFICATE OF SAID INSURANCE. CONTRACTOR AND ALL SUBCONTRACTORS SHALL CARRY WORKER'S COMPENSATION INSURANCE ON ALL WORKMEN EMPLOYED ON THIS JOB. 6. ALL WORK PERFORMED SHALL CONFORM TO THE LATEST EDITION OF THE 2004 AND 2006 AMENDMENTS FLORIDA BUILDING CODE AND ALL APPLICABLE COUNTY ORDINANCES, AND SHALL BE COMPLETED TO THE HIGHEST STANDARDS OF CRAFTSMANSHIP BY JOURNEYMEN OF THE REPECTIVE TRADES. 7. CONTRACTOR IS RESPONSIBLE FOR THE PROPER EXECUTION OF ALL WORKS, NOTWITHSTANDING THE APPROVAL OF SHOP DRAWINGS, DESIGN MIZED, LABORATORY INSPECTIONS AND REPORTS, ARCHITECTS AND/OR ENGINEER'S FIELD OBSERVATIONS, THE LIKE OF WHICH ARE INTENDED TO ASSIST BUT IN NO WAY RELIEVE THE CONTRACTOR OF HIS/HER RESPONSIBILITY. 8. INCLUDED 1N THE RESPONSIBILITES OF ITEM 7 ARE THE FOLLOWING: A. EXECUTION OF ALL WORKS IN A PROPER AND SAFE MANNER FOR ALL PERSONS, EQUIPMENT AND PROPERTIES. B. DESIGN, ENGINEERING, CONSTRUCTION AND HANDLING OF AL FORM WORK AND TEMPORARY STRUCTURES. C. SPECIFIED STRENGTH AND PROPER PLACING OF CONCRETE. ALL CONCRETE AND RELATED WORK INPROPERLY PLACED AND/OR TESTING UNDER STRENGTH SHALL BE REPLACED WITHOUT ANY ADDITIONAL EXPENSE TO THE OWNER 9. ROOF TRUSS FABRICATOR TO PROVIDE DESIGN AND SHOP DRAWINGS FOR TRUSSES. 10. SOIL SHALL BE COMPACTED TO A MINIMUM OF 95 % CO]AIPACTION DETERMINED BY A MODIFIED PROCTOR METHOD. 11. SOIL BEARING IS DETERMINED TO BE 2000 PSF. IF SITE CONDITIONS VARY, CONTACT ENGINEER OR RECORD. 12. SOIL SHALL BE PRE-TREATED FOR SUBTERANEAN TERMITES / N 510 32' 38 50.0d -- A --------- r / / / rJ 0 / / / / / / / / EXIST. DRIVEWAY EXIST FIN ., w I I bh�� ryy/ II I I I _J N EXISTING BUILDING ANALYSIS TPIK BUILDING FALLS UNDER TIIE CLASSIFICATION OFAN ADDITION AS PER THE THE FLORIDA BUILDING 2004 EXISTING BUILDIN6 CODE BOOK TIJE ADDITION SHALL APPLY TO THE REQUIREMENTS OFCNAPTER 9 OF THE CODE SECTION 902 C IIE1611T AND AREA) THIS RESIDENCE IS CLASSIFIED AS R-3 , TYPE V CONST. SHALL NOT BE MORE THAN 3 STORIES IN 1467. AS PER FBC. SECTION 101.2. THE ADDITION SHALL FOLLOW THE F.B.C. RES.2004 W/ 2006 / 2007 SUPPLEMENTS SECTION 902 SMOKE DETECTORS FOR NEW AND EXIST. SECTION 903 SEE STRUCT. SECTION 904 SMOKE DETECTORS SHALL BE INSTALIED ACCORDIN6 TO THE FBC. RES 2004 SECTION R913 SMOKE ALARMS SECTION 905 / 71rE EXIST. HOUSE SHALL COMPLY W/ CHAPTER II OF THE F. B. C. 2004 W/ 2006 / 2007, U115 MENTS I I I / I I i / / I / I � Y 1 / FILE a I / I / I ��rl�� NEW ADDITION m % I / I o00 MAIN I6 A4' N6VA — 1 II I I I I I I I I I I J EXIST ELECTRICAL CONDUITTO RUN TNRU FOUNDATION WALL ABOVE NEW FT6. CONTRACTOR TO VERIFY LOCATION BEFOR FORMIN6 UP FOR FOUNDATION WORK J1 49'-91' INEW UNIT EXIST UNIT RELOCATED I NEW 5'-O" lI6T BLK WALL TO SCREEN A/C 01TS 9CATED A/C UNIT ,UCIE COUNTY / BUILDING DIVISION pEV FO O REVIEWED E IT DATE PLANS A P OR MUST BE KEPTW NJOB OBMADE NO INSPECTION DRAWING INDEX ARCHITECTURAL A-2 BUILDING DEPTS. FORMS FA —3--] DEMOLITION FLOOR PLAN A 4 FLOOR PLAN A-5 FRONT, REAR & LEFT ELEVATIONS A-6 TYPICAL WALL SECTION " A- SHT A-6 " STRUCTURAL DRAWINGS S 1 FOUNDATION PLAN S-2 ROOF FRAMING PLAN S-3 ETAILS S 4 SECTION ELECTRICAL E-1 FIRST FLOOR ELECTRICAL PLAN E-2 SCHEDULES & NOTES PLUMBING P-1 PLUMBING FLOOR PLAN MECHANICAL, M-1 MECHANICAL FLOOR PLAN ET-1 M-2 SCHEDULES AND DETAILS SITE CALCULATIONS LOT SQ. FOOTAGE I MAX BU/LDIN6 COVER46F ALLOWED @ 35 X EXIST HOUSE AIC S: F J EXIST 6ARA6E NEW ADDITION AIC S. F. / TOTAL BUILDIN6 COVERA6E / 411N OPEN SPACE REQ'D = 30 X OF 21,453 TOTAL OPEN SPACE PROVIDED / NEW ADDITION EXIST HOUSE & GARAGE POOL AND PATIO CONC. PADS / DRIVEWAY & WALK COVERED ENTRY TOTAL ZONING: E 9,E16NT (TO RIDGE OF ROOF) NET LAND AREA LOT COVERA6E SETBACKS: FRONT R16NT SIDE LEFT SIDE REAR = 7508 S: F. = 2570 fF. = 616 S.F. 512 S: F. 3698 S:F. < 7508 S.F. 6435 S.F. 12,910 = S: F. = TO 67X 512 SF. 3186 S. F. 965 S.F. 20 S.F. 748 S. F. 78 S. F. 5,509 S. F. = TO 25%OF THE LOT AREA TOTAL OF15, 944 = 74 X OPEN SPACE 22'-111/2" 21, 453 S.F. 359 REQUIRED 25'-0" 30'-0" BETWEEN UNITS 30'-0" BETWEEN UNITS 20'-0" PROVIDED SEE PLAN SEE PLAN SEE PLAN SEE PLAN S 650II' 091, W / 5CH(VNED — BY 186.67 St. Lucie County SITE PLAN 1" = 107-011 LEGAL DESCRIPTION UNIT lO , WEST HAMMOCK HARBOUR R1D6E PLAT NO. 9, PLAT BOOK27, P46E 1-1D, PUBLIC RECORDS ST. LUCIE FLORIDA W M A a �O w 00 M/ ` W 00 O a N N a W a; W o M I�-��1► U W � W � w � N w A z a: o A U GTa P4 A C 44 U Product Review Affidavit St Lucie County, Public 11 orbs Departlraeut code Compliance Division The fDllov. ing. products will be installed in the structure located at Building Penriit,# 1472 SWEET BAY CIRCLE Owners Name DELUCA RESIDENCE sCITY PALM , FL. ----------------------ITY------ contractor Contractor'sAddress PALM CITY 34990 _ Product I *Product Kilted I Nfanufacturer Windows I` Fail nn the rated rind deaiznp, esv4res +4 . PGT I USTRIES lst Choice SIN( XP DATE tss MULLION PGT INDUSTRIES N.O.A- of Attachment k `lute v1af31 V4WY,'tf1ffo4 It 700 L & 14 III" O.C. W / 4" MAX. FROM EACH CORNER / 1 l sl choice + 80 0 PGT INDUSTRIES P `IS 1' NSA 11" O.C. AROUND 7 C NOA#07-041&06 lr&I (other) lit Colas_ Gloss Block ogsph.:it�`PiL,es �'�fe`ai Other MONIER ESPANA GOLD DU T ROOF NOAl 07-1023.06 EXP 0A1E IL-10-IA Choice I have reviewed the above component and cladding, and have approved their use in the Structure to r°oside adequate resistance to the wind loads and forc€s specified b-, current code provisions. P il. P Nil '�,e: Deg, qn l=irirl Signature Cerl. No Date: T SIDES FIXED LITES EMBED. M'.CORNERS AND St. Lucie Count`' Building and Zoning Department 2300 Virginia Avenue Fort Fierce, FL 3982 7 7 62-1553 FILE COPY Design Certification for Wind Load Compliance This Certification is to be, completed by the project design architect or engineer. This C"ertiiication must be submitted with all applications for builduig peerinits involving the construction of tiecv resilience (single or multi family), residential addition, any accessory structure requiring a building permit, and any noureside tial structure. This Certification shall not apply to interior renovations (provided that no structural scans, columns or other similar comip r ent is 1xei ng effected) and certain other minor building permits. For further assistance, please contact the Building Inspection Office at 462-1553 or 4, 62 2172. PsojectNrusie D LUCA RESIDENCE itifi< Use Orila Street Address 1412 SWEET BAY CIRCLE Permit Numbei ALM CITY FL. Occupancy T >e Canstiaaction Ta e Certification Statement: T cel-tit; that, to the hest of try knowledge gird belief, these plans and specification; have been deli red to comply with the applicable structural portion of the Building Codes currently adopted and enforced by St. Lucie Colltlt} . I also certify that struchlt-al elements depicted on these plates provide adequate resistilice to the wind loads and forces specified by cuiTent code provisions. 1 Desi Pa'I1 glee°s and Asstrm Itions L sed: (Please cliecl: or complete the appropriate box,) 1. Flor'idr l3nilclilr C'oMOdition ✓ ASC`E 7-98 & 2006 AMMADMras Enclosed �� Partially Enclosed Open Building 3. Building Height: 22'-11" 4. Wind Speed Used in Building Design: 140 3 second gust 5. Wind Exposure Classification (refer to exposuix tables in Building Code identified in Line 41): C 6. Average Wind Velocity Pressure on Exterior Faces of Structure _ _PSE 7. Peak Wind Velocity Pressure on Exterior, Faces of Structure S. Importance, -Use Factor (obtain from Building Code): 1.0 PSF 9. Loads: Floor N.A. PSF Roof/dead 30 PSF Roof'live 20 PSF 10. Were Shear Walls Considered for Structure (check one): Yes _ No LL (if No, attach explanation) 11. Is a Continuous Load Path Provided (check one): Yes NOTO.'l k- ff, attach explanation) 12. Are C 0111polteut and Cladding Detail Provided (check onie): Yesl��N,o __(if No, attach explanation) 13. Minimum Soil Bearing Pressure: 2500 PSF As witnessed b)- my seal, I hereby certii{' that the information included with this certification is true and correct. to the best of ink- kno-A=ledge and belief. ?arne: Design Finn: Certification #: [Seal Here] Date: SLCCDV Form 020-00 rev. 10%5/05 ding THESE PLANS AND ALL PROPOSED WORK: AND SUBJECT TO ANY CORRECTIONS REQUIRED BY FIELD INSPECTORS THAT MAY BE NECESSARY IN ORDER TO COMPLY WITH ALL APPLICABLE CODES. CODE COMPLIANCE DIVISION RESIDENTIAL PLAN REVIEW F0F,. fI 472 SWEET BAY CIRCLE Job Address _ PALM CITY, FL. Pernift ATTACHNIEN'TS Sigried & Sealed Utawimgs FBC" tC:a l LC Ivaid Load Compliance Cert. FRC1603 Lot Survey t "F shed. Moo €1ev.1 FB(- 106.1 SLC- F4exluet Reiiew Affidavit FBC 1609 Signed Enerov Efficiency Cilcs. FBC 1 v-6 H1', C' L ad Calcniations FBC 13-6 NA FOUNDATION Foundation Plan Hatches Sur eey FBC' 106.I Iiatar or Bearingt4'alls FBC 18051FRC' 4tJ3 A Footing Details FBC'. l 9Q5 FIdC 403 Coluanl Pads FBC 180 �IFR(2 403 Change inEleiatians FBC 1805'FRC 403 I NEj Area'fabulaticn FBC 106,3.5 NA STRI CTITRAL SECTIONS & DETAILS S'tT-all. Section FBC C'h.=1'FRC Ch.6 Framed fall Section. FBC' Ch.23J-RC_' C'h,6 Interior Bearing ii'all FRC 602.4 NA Frame to Black Wall Detail FRC 601 Bay Wiudoaa Detail. FRC 602 NA Window Seat Detail FRC 602 NA Gable End Detail FBC; 2304.3:4 ,' FRC 802.10.3 NA Porch & Front Entry - Exterior Ceiling FBCCh, 16 NA Sheathing '�laes & Nailing FRC 803 knee INTall Detail FRC 602 NA Butt Glass Detail FBC 2404 NA Bearing Wall Header Detail FRC 602 Fue Place & Chimney Derails FRC_ Ch. 10 NA i'Viauiowr & Door Bnck Details FBC 1714 =..4 Tie Beam at Change in Heights FRC 606_ 1 NA Beam Block : Poured Tie Bemn FRC 6t}Cri I A Lintel Schedule FRC 606.9 NAI Glass Block Detail FBC 2110 NA Truss Plan YSi Amavia copie,t FBC l06 3.5rFRC 802- l0 Taus C omiector Chart FBC 106 3_.i NA 'Wind Borne Debris Protection FBC 1609.1.4 ign uini i pressures at openings FBC 1609 NIECHAaNIC AL . ELECTRICAL / PLUMBING Drv. i Vern Exhaust FRC 1501 NA Electrical Pi.i;i, LoadCaks. & Riser NFPA 7OA E,,di us[ Fite S'enting FRC I--06 Phinibulg Ri*cr Diagram FRC [ 1;. 30 AC Duct sit Return Air Plan FBC 13-610.FRC 16014 HVAC -:slake, Model & BTU's EEC 13-6 INTERIOR Egress Windows F3C.10&15tFRC' 310.1 Front Door S'i,-e (36' x 6`8") FRC' 31 L4 2 NA Accessible BathrBecrooni Timor FBC 106.3.5 & I 1-11(1) Smoke Dl resters FBC 106 3 5TRC 31 ATtic Access (22"x 30" main.) FRC 807 NA Stair:'llairciraii.`Cruariirail Dilates FBC 106 3 5rFRC 3l l.5 N 1 st Review Bate Plans Examiner Naule tiEVIsED V31,16 BY CNIL 'Aire Review Date SignatLue Filial Review i i ti a� xN w Q' o Q� C U I X4 AT. WD. BUCK LOCATION OF TAPCON SCREWS BOTT OF CONT T. B. PICTURE WINDOW FLANGE TYPE FRAME MOUNT/AG 2" ,, 4" x 1141' STL REQUIREMENTS AS PER THE NOA IS 81/2' FROM! CORNERS AND MAX OF11" 0.0 MULLION NOA # 03-1105.01 2" x 4" x 114' MULL BAR N.O.A. 06-0125.08 4-1/4" x 12/2' EMBED INTO 3/4" x 2-3/4' WD. BUCK 25 ALUM SINGLE HUNG BY PGT IMPACT GL. ARCH TOP ABOI/E I X 4 AT. WD. BUCK ARCH WINDOW MULL DETAIL 8'-0" ABOVE FIN SLAB CAULKING BEAD ALL AROUND. ALUMINUM SINGLE NGING WINDOW W1TN IMPACT RESISTANCE GLASS NOA CAULKING BEAD ALL AROUND. SLOPEI/2" — 6" RAISED STUCCO BAND ON 3/4" STYROFOAM BACKING 518" STUCCO FINISH. — 8" CONC. BLOCK. SCALE 1 1/2" = 1'-0" 1/2" DRYWALL ON 1" X 2" P. T WOOD FURRINGS AT 16" C/C. CONCRETE LINTEL / BEAM. SEE STRUCTURAL DWa. FOR DETAIL. I X 3 AT. WOOD NAILER 1X4AT. WD. BUCK WITH 114"0TAPCONSA7-I2"O.C., AND 6" FROM EDGES. 2" MIN. EMBEDMENT INTO BLOCK OR COLUMN REQUIRED. WOOD TRIM. VERIFY W/OWNER MARBLE SILL TO MATCNEX/ST -I X 4 AT. WA BUCKWITN 1/4" O X 31/2" TAPCONS SCREWS AT12" O.C., 6" FROM EDGES. 2" MIN. EMBEDMENT INTO BLOCK OR COLUMN REQUIRED. 1 X3 AT. WOOD NAILER. 8" x 8" CONCRETE CAP. W/ 2#5 R-5.0 INSULATION 1/'1" DRYWALL, ON 1" X 2" AT. WOOD FURRINGS AT I6" C/C. TYPICAL WINDOW DETAIL SCALE 11/2" =1 0" SYMBOL LEGEND & NOTES �y CONTRACTOR IN 11/S BASE BID TO PREP FLOOR W/ I/a" PLVWD LN HALL WAYGOING INTO NEW BEDROOD FOR NEW WOOD FLOOR. PROVIDE AN ALLOWANCE FOR NEW FIN WOOD UNDERSTANDING OWNER MAY GET SHOP FOR NIS OWN FIN WOOD FLOORING EXIST HOUSE EXIST. 8" BLKWALL 0 � NEW 8" CONC BLK WALL W/ co FILLED CELLS 0 EXIST. 24 W00D STUDS TO 'm 0 REMAIN ® NEW 2x4 WOOD STUDS @ 16" O.C. NON STRUCTURAL ^o w ~o NEW 2x4 WD STUD WALL ti Q W/ R-111NSUL a o NEW 2x6 WD STUD WALL 271 Q v W/ R-19 INSUL o o Q 80T11 BATHS ARE TO GET GRAINTF COUNTERTOPS GRADE 2 OR BETTER L� M h ti ARCHED WINDOW DETA I SCALEII/2" _ 2 x 4 WD STUDS TURNED SIDEWAYS @ 16" D.C. 22 2 A T BOTT PL PARTITION DETAIL SCALE 11/2" = 1'-O" 0 EXIST. UNIT TO PROPOSED WORK THESE PLANS AND AL CORRECTIONS AND SO IEGI TO A NSPECTORS THAT REQUIRED BY FIE L Y IN ORDER TO MAY BE NECESS pLICABLE CODES. COMPLY WITH ALL EXIST FIN SLAB OF 6AR46E=15.56' N&VP. a A-6 25'-IO" 3'-4112"LO I9'-1 l21 ALUM PROJECTED WINDOWS BY 21 AL M PROJEC to PGT IMPACT GL. PGT l PACT GL. 24, 6, 6" CROWN MOULDING EGRESS —NEW BEDROC M I OEM EGRESS �1� o FIN FLOOR TO BE CAR IFT I WOOD BASF TO MATC EXIST. �_0 NEWS " BTOMATC11 3-0 COFFERED CLG. MAIN 10L1SE = 16.09' NGl/D. 8 314" CROWN TO WRAP AROU PROVIDE?/2' DU-RO 4CKING EGRESS COFFER CLG. FOR FULL A16T. TILE l EGRESS I' -8" 2'-71/2"51/ 3'_6" 111/2" D X g M 2-0 GLAS DOOR'14' TEMP �y R.P. D I CA WINDOWS BY 0. il�i►'1 ,�, � �� � r •� � I�iIIIIIIIIIIIIIIIIIIIYIilllllllllllllllllllllllllllll Dole o TNISSNT � EXISTF/NSLRBOF FLOOR PLAN MAIN HOUSE = 16.09'N6V9. 4'�=1'-0" FILE 00v SHOWER ELEVAT"ION EXIST 9'-2" CLG. NEW DROPPED 8'-0" CLG. OPEN TO INSIDE OF SHOWER '/4' TEMP. FIXED GLASS IN ALUM FRAME CATT 2 MARBLE OR TILE FIN NEW 6" NGT. CROWN MOULDING W/ CURVED PIECE ON TOP EXIST NOR TO BE REMOVE UP TO THE FIN CLG NGT OF 9'2" + PR0f4(Jf.1t/EW CROWN MOULING ALONG CL EDGE OF WALLS u LiASING BD. Toil Tt TY'P I CVIk•T /1/1l?r OPENING ARCHED HDR4 ELEVATION s W a; W O a M z�u W W z � a; ►! W C r!] NEW AND RELOCATED AIC UNITS 5-0" NGT. BLK. WALL W/ 5/8' STUCCO BOTH SIDES NEW 518" STUCCO BAND ON WIRE NEW ON A P. T. WD BD TO AfATCN EXIST. + 95.2 - 38.2 LEFT SIDE ELEVATION Y4f�=11_011 REAR ELEVATION DESIGNATES EXIST. NOISE ONAP.T. WDBDTONIATCNvEXISTC3� FRONT ELEVATION �4n=1�_Oa FILE COPY rNESF N q/vp s fts'gIV® eyr rOq/v aROPa -oMP V �I �FA C S o�V ecro'� NOR/x APpl'Cl ete 4 7 r C06caS. CRIOR WOOD SHALL RECEIVE TWO FINISH COATS OF N MOORE PAINT OR STAIN. PROVIDE SAMPLE FOR WNERS APPROVAL BEFORE STARTING WORK. COLOR TO MATCH EXIST ATTN PEGGY EVERSON FOR PAINT COLOR OAT OF PRIME WITH MOORWHITE ALKYD PRIMER 100 SERIES. TWO COATS TOPCOAT MOORGLO HOUSE & TRIM LATEX 5 SERIES. ERIOR STUCCO SURFACES SHALL RECEIVE TWO COATS OF .RD OVER ONE COAT OF SEALER. PROVIDE SAMPLE FOR APPROVAL BEFORE STARTING WORK. A. PRIMER: BASE COAT-MOORE S LATEX ALKALI RESISTANT MASONRY JX SERIES. B. FINISH: MOORGARD LATEX LOW LUSTRE HOUSE PAINT 103 ti A O A 0 U W 2 woo H A4 M M N A M O x a e 0 N w a W C, M N AN N 61RDER TRUSS ago. NEW ESPANIA 601D DUST MONIER /LIFE TILE I�i • ROOF TO MATCH EXIST ON 90# SLATE NOT MATCH MOPPED TO 30" SAT FELT TIN CAPPED TO 3/4" EXIST. FOR GRADE PLYWO.W/l0 d NAILS @ 4" O.C. O ALON6 ED6E, &6" 0. C. IN FIELD a 346d No I LS N W WOOD TRUSSES AT 24" C/C. PROVIDE SHOP a ORAWIN6S FOR APPROVAL PRIOR TO FABRICATION PRODEVIDE X BRACING SEE ROOF FRAMING PLAN SNT S-2 3'-0 ANCHOR PLYWD AS 6ALV MTL S AT AND PER ROOF Cf/EATNIN6 NOTE GALV. OIL CLIP MArcN ON P. T. 2r4 WD NAILER EXIST. STRAP @ EA TRUSS R-90 BATT !N ULATION W 2 r WOOD Sll8-FASCIA p EVERY T141RD TRUSS MTL DRIP ON AT. AS co TOP OF TIE BEAM WD NAILER TO MATCH EXIST. '� a en en h iAATca EXIST T B. ABOVE FIN SL48 CIMPSO# HANGER @ EA TRUSS \ ' Z 3'-0" 8 3/a" CROWN MOULDING ° NCNOR VALLEY TRUSSES TO LOWER ROOF W � 518" DRYWALL ON l x 3 AT. W . FURRINGS s W/ NVRT24 AND 5-16d NAILS INTO EA. A Z WD FASCIA TO MATCH EXIST IN DEPTH 8 �4 CROWN MOULDING CA AT I6 C/C MEMBERAT Z' MAX SPACING OF 4 -O" 0. C. AT PANEL POINT 0404 a 112" PLYWD. SOFFIT W/ A 3" .r 16" SCREENED VENT l r 4 CONTT, WOOD F/RE STOP AT 8'-O" C/C EXIST O. N. TO BE REMOVED WHERE POSSIBLE A z g4 ACOOROING TO FBC. 2004 RESIDENTIAL SECTION R806.2 MEASURED VERTICALLY PROVIDE'/2' PLYWD BOTH 5/8 TEXTURED STUCCO ON CONCRETE TIE BEAM. SEE STRUCTURAL EXIST STUCCO TO BE REMOVED SIDE W/ 10-16 d NAIL IN TOP & NEW DRYWALL INSTALLED CHORD & 1516-d NAILS IN BOTT CHORD FELT BACKED RIB LAIN DRAWINGS. Ca 518" DRYWALL ON 1 x 2 AT. WD, FURRIN6S AT 16" C/C W/ R-5.0 RIGID THESE PLANS AND ALL PROPOSED COR ECjIONNSK INSUL AND SUBJECT TO A f1, REQUIRED BY FIELD INSPECTORS THAT TYPICAL WOOD FIRE STOP MAY BE NECESSARY IN ORDER TO 8" CONCRETEMASONRYUNIT. SEE COMPLY WITH ALL APPLICABLE CODlz ES. r l STRUCTURAL DWG. FOR DETAILS 1169T TEXTURE STUCCO FINISH WOOD BASE BOARD. MATCH EXIST. IN DRILL AND EPDXY #5 @ 24 O.C. INTO O T~ EX TO MATCH EXIST. SEE THE N6T. AND STYLE /Sr. SLAB ( THICKENED ED6E)W/ 6 EMBEDMENT USE A R B cop\1 NY-15O EPDXY BYNILTI U A FOR HARBOUR RIDGE (PE6GY FINISH FLOOR. TO BE CARPET EVERSON) FOR PAINT COLOR f Z QW 4" CONC. SLAB W/ 6A'6 - Wt. 4XWL4 W.W.F.ON WELL COMP. q FILL OVER 6 MIL VAPOR BARRIER SOIL COMPACTED TO W EXIST. FIN/KY GRADE 2500 PSF. AND POISONED FOR TERMITES AS PER F.B.C. 2004 W/ EXISr FTG. A 2006 AMENDMENrr R-320 NEW SLAB TO MATCH EXIST. FlN SLAB + 16.09' NGVD. FLOOD ZONE lS " X" • 11=III=III—III=III=III=III—I I—III=III—III=III=IIIIII=III=III=11I=III___— 11=111= III =1 III=II I III=III=III=III=III=III=III III=III= —III—III—III—III=III—III—III—III—III—I III=III=III=III—III=I I I 1 W I I I=1 I I=1 I I=111=LI_I=1 11=1 I =1 11=1 11=1 11=1 11=1 11=1 11=1 11=1 11=1 I I I 1=1 11=1 11=1 11=1 I I 11=1 11=1 11=1 11=1 11=1 I �=1 I I 11=1 11=1 I I 1=1 11=1 11=1 11=1 11=1 11=1 11=1 11=1 11=1 I I _I 11=1 II=1 11=1 11=1 I_I—III—III v III=1 I I=1 I I=1�-1 I1=1I1=1 11=1 I I-1 11=1 11=1 11=1 11=1I I-1I1=1I I-= 11=1 I I-1 11=1 11=1 11= I I I=1 11=1 11=1 11=1 11=1I1=1I =1 I I-1 11= I —I I I_I I I_I I I I I I_I I I_I I I —I I I_I I I_I —_ __—I I I_I I II I I_I I1=1I I_�—IIII � IIIIIIIII=Ill=III=III=III=III=III=III=III=III=III=III=11 =III=III=III=III =III=III=III=III=III=III III=III= 1=III—III=III=III=III=III=III=III=III=III=III=III=IIIIII=III=III=III=III=1 — 111=111=I I =111=III=111=111=1 I I-1 11=1 11=111=III=III=111=1 —_ = 1= — I I I 1=1 11=1 I I—III=1 1=1 11=1 — I_I I I_I I I —I I I_I I I —III —I 11=1 I I —III —III —I 11=III—I 11=1 I I —I 11=III=111=111=11— 111=1—=1__ CONCRETE SLA8 ON 6 MIL VAPOR 1 1=1 1=1 1=1 1=1 1=1 1=1 1=1 1=1 1=1—I 1=1 1=1 1=1—I 11=1 I� I I I=1 =I 1-111=III=III=III=1=11=11=11=111=III=11=11=111=III=11=III=111=III= =111=III=1 1=1 1= BARRIER. sEE sneucruRAL Dw6s 1— f=1 I1=1 11=1 1=1 1=1 1=1 1=1-1 1=1 1=1 1=1-1-1—III1 1=1—LI 1=1—I 11=1 I-1 I I =1 I —III —III —I 1=1 I —III —III —III —I I_I—I I_IIII—I 1=1 I I I=1 =1 I1=1 11=1I 1=1I 1=1 1=1 1 1I 1=1I -1 1=1 11 1 1=1 I I I=1 I I I=1 1=1 I=1I 1=1I1=1 1=1 1= 1 I I I I I —I 11— 1 1 I I —III —III —III I I I=1 11=1 1 1 I I III —III— 1=1 1=1 �11=III—I11=III=III=III=III=111=III=III=111=III=111=111=III—_=_=_ III=111=III=1I_f---III=III=111=IIIIII—III=III—III II III=III=III—IIIIII—III=III-11_�III=III I I I=1 =1 1=1 11=1 11=1 11=1 1=1 1=1 11=1 11=1 11=1 1=1 1=1 1=1 1=1 1=1 1=1 1=1 1— 11=1 1__ =1 I I-1 I III 1=1 =1 1=1 I I —I 1=1 1=1 I I=1 —I 11= 11=1 =1 1=1I I —I I1=1 I —III —I 1 1 I —III —I 1=1 —III —III III —III —III —III —I I I =11 I-1 —_= WELL COMPACTED, ccEaNNON-oRGaNic II I 11 I I I I I I I=1 I1=1 —III=III—III=III—III=III=III=III=III=III=III=III—III=III=III=III=IIII III—III==III=1 — = 1=III=III—III=III=IIIIII=III= —11=111=11-111-1 1—I 1-1-111 IIII 1—III—I 11—III-1—I 1 III —� 1= FILL. =1 111II I— — =111=I M 111=11 Ell I I=111-111=111-1 11-111=1 I E I 1=111— II —I1=111—III—III—III—IIII 11=111-111—I 11—I I 1=1 1 — IIII=III—III=III=III=111—III—III=111— —I I I=III—III—III-111=11- - CONCRETE FOOTING. SEE STRUCTURAL DWa.. TYPICAL SECTION " A TYPICAL SECTION " A " o SCALE 3/4"=1'-0" SCALE 3/4"=1'-0" WoF' NOTE: PROVIDE HORIZONTAL JOINT REINFORCEMENT BETWEEN EVERY OTHER COURSE W/MIN. #9 LADDER TYPE. REINF. TO EXTEND INTO TIE COLUMN MIN. 4". TERMINATE COLUMN FILLED CELL STEEL INTO CONC. BE M W/ 900 HOOK • I/ I I I I I . I I I I /l I I I I I I. I . EXIST. BLOCK WALL # 5 BEND BAR x 30" LONG, EACH DIRECTION W/ 443 & 12" O.C. 2 # 5 BEND BARS x 30" LONG,EACH DIRECTION W/ 443 @ 12" O.C. COLUMN BEAM CORNER DETAIL 3/4" = 11-0" EXIST ONE STORY DWELLING ZONE "Y'=12.55' N.G.V.D. FC. O O C FC.I O F.C. SOIL STATEMENT INSPECTION OF THE SITE INDICATES UND/STURB'ED SOIL WITfl A BEARING F C VALUE WNICN WILL EXCEED 2900 PSF. SHOULD OTHER CON017-10NS OR o MATERIALS BE ENCOUNTERED, THE ENGINEER SNALI SE NOTIFIED BEFORE o PROCEEDING W1TN THE WORK AND TILE CONTRACTOR SHALL HIRE ~ GEOTECNNICAL ENGINEER TO CERTIFY THAT EXISTING MATERIAL IS CAPABLE FC. OF 2500 PSF BEARIN6 CAPACITY. (MLN. OF 3 SOIL BORING IS REQUIRED) EXIST ONE STORYOWFWN6 EXIST A/C UNIT REMOVED F.CI� —ICI 8" x 12" STARTER COL W/ 4 # 5 VERT & #3 TIES @ 12" O.C. 0 2 #5 x 3'-0" LON6 DOWELS DRILLED 6" MLN INTO EXIST. BEAM AND SET IN APDXY GROUT NEW MASONRY BLOCK WALL DRILL & EPDXY #5 x Y-0" LONG REMOVE STUCCO TOP AND 80TTINTO EXIST. FOOTING FOR A MIN OF 8" & LAP 36 MIN TOP 7//7 STI 36" LONG PROVIDE WIPEOUT BETWEEN EXIST SLAB AND NEW TNRU OUT NEW 8" x 16" C.M. U.W/ 3/8' MORTAR JNT W/ EXIST. CONC. FOOTING 1 #5 /N FILLED CELL BENT 18" INTO FT6. & BEAM EXIST GRADE LINE APPROXIMATE NS AND All PROPOSED WOR o THESE PLA ANY CORRECTIONS ti AND SUBJECT TO A REQUIRED BY FIELD INS 4 OR ER TO MAY BE NECES`AR PLICABLE CODE COMPLY WITH AL NEW 16" x I6" CONC. FTC, 12" BELOW EXIST GRADE A _ A-6 NEW COL TO EXIST WALL DETAILEXISTELECTRICAL CONDUIT TO RUN TNRU 1 NEW CONC BLK CONTRACTOR TO VERIFY LOCATION TNlSSNT 1 3/4" = 1'-0" 25'-l0" MASONRY REINFORCING ALL CONCRETE 8lOCK TD 8E 8"x8" j6" WITH MIN. COMPREESS/VE F.C. F.C. F.C. FC• F.C. STRENGTH OF Pb = 1400 P.S.1. RESULTING PRISM PROVIDE I-N..51N M4SONRYATAMAXSPACIN6OF48"O.C. (UO.N) O O O O O F.C. F.C. FILL CELLS W/TN CEMENT GROUT WET CELLS BEFORE PLACING GROUT, RE- CONSOLIDATE F. C. � EA. LIFT MAX. OF 4'-0". WITH LOW VELOCITY 3/4' D1A. MECHANICAL 24 -6 I VIBRATOR SEE TYR FILL CELL MASONRY DETAIL . PLACE ADDITIONAL BAR FOR EVERY INCREMENT EXCEEDING 1NDICATE0SPACIN6. REFER TYPICAL FOOTING NOTE: �NF.C, TO TYPICAL CORNER DETAIL FOR ADDITIONAL REINFORCING. PROVIDE HORIZONTAL REINFORCING #9 GAGE LADDER TYPE EVERYOTIIER 6 DEEP CONC � M\����M COURSE TNRU-OUT All MASONRY WALLS DO NOT USE PEAROCK 2 ID 5 CON PUMP MIX CONCRETE FOR MASONRY WALLS 4" CONC. SLAB W/ 6" X 6" - W I.4 W l.4 ON WELL CORP. FILL OVER 6 MILL VAPOR BARRIER i ZONE"X" MY ATCN EXLST. DRILL AND EPDXY #f @ 48" O.C. INTO EXIST. SLAB ( TglCkqVFD EDGE)W/ 4" EMBEDMENT USE NY-150 EPDXY BY NL Tl F P OVIDE WIPEOUT BETWEEN EXIST W B AND NEW TNRU OUT FOUNDATION PLAN 60 / /4„=1'_0" 1 A A-6 8" x 12" STARTER COL W/ 4 # 5 VERT & #3 TIES @ 12" O.C. DRILL AND EPDXY #5 @ 24" O.C. INTO NEW C148 ( THICKENED ED6E)W/ 6" E/ NY-150 EPDXY BYNILTI 7-101/2" 9 o 0 8" x 12" STARTER COL W/ 4 # 5 VERT I V&#3TIES(g12"O.C. OFc. 36l1x3�,axl6//���� 3 5 INTO EXIST USE FOUNDATION NOTES 1) SLAB TO BE 4' THICK W/ 6" x 6"Wl.4x W1.4 W.W.F. SUPPORTED ON SLAB BOOSTER @ 6'-0" O.C. ON 6 MILL VAPOR BARRIER ONCOMPACTED FILL TO A MIN OF 95X OF MAX DRY DENSITY FOR ALL LAYERS FOR ALL LAYERS IN ACCORDANCE WITNASTM D 1567 2) TOP OFSLAB = TO MATCNEXXTSLAB 3) OVERLAP ALL FOOTING STEEL AT ALL CORNERS & INTERSECTIONS FOR 30" (MIN. BEND BARS 4) DISCONT/NOUS EDGES OF ALL SLAB SHALL NAVE 8" x 12" THICKENED EDGE WIT# 2 # 5 CONT. 5, DRILL & EPDXYALL VERT. STEEL INTO EXIST. FOOTING & TB. W/ AN B" MIN. EMBEDMENT. USE /1Y-150 EPDXY BV 141LT1 6) CENTERLINE OF FOOTING AND WALLS, COLUMNS MUST LINE UP U.O. N. 7) DRILL & EPDXY #4 cr 24" O.C. x 3' 0" " LONG.AT CL. WHEN NEW SLAB IS PLACED AGAINST EXISTING W/ 6"MIN EMBED 8) PROVIDE 2#5 UNDER GIRDER TRUSS( U.O.N.) M N A� wz�� O F� hw^N �ccin0 N W W a W °D 0 � a M W M � Z 3 u z W � � Q N z a; we H �� O 518" CDX PLYWD. NAILED TO RMIG W/ 8d NAILS AT 4" 0. C. IJ!" uxv H /Vr I "uN w1 J-!V9 NAILS ON EA. SIDE " X " BRACING DETAIL ANCHOR PLYWD. SNEATNING TO BLOCKIM W110d NAILS AT 6" 0. C, PROVIDE BLOCKING & BRACM EVERY0MER VALLEY TRUSS AT MAX. SPACING OF 4" 0. C. XX 3-16,1 NAILS M 2X4 / X 3-16d N910d NAILS X 2X4 / M 346d NAILS 346d NAILS TOE NAIL VALLEY TRUSSES TO ROOF STRUCTURE W/ 2-16d NAILS @ ALL CONTACT POINTS IN ADDITION TO HURRICANE STRAP SHOWN PIGGY BACK DETAIL %" I,-0n THESE PLANS AND ALL PaCORRECTIONS pOSED WORK AND SUBJECT TO ANY REQUIRED BY FIELD INSN ®� �R THAT MAY BE NECESSARY COMPLY WITH ALL APPLICABLE CODER, ANCHOR PLYWD AS PER ROOF SNEATNING NOTE PROVIDE INV6" MIT OPENING FROM UPPER ROOF TO LOWER ROOF EVERY THIRD TRUSS ANCHOR VALLEY TRUSSES TO LOWER ROOF W1 NVRT24 AND 5-16d NAILS INTO EA. MEMBERAT MAX SPACING OF4'-O" O.C. AT PANEL POINT WHERE POSSIBLE EXIST. TRUSS EXIST. CONC. TIE BEAM TO BOTT 1. f6N TRUSSES TO ALLOW FOR l TNIS SPACE Tic OMIT TNIS NOTE 6-16-08 SPY PIGGY BACK & FLASHING DETAIL ROOF PLAN NOTES w (01) M N N N O W N a ^ � N V1 � Tw O N a a W a n W O a M a W M W W � � N W A kn Z a IN 1• CONTRACTOR TO SUBMIT SHOP DWG. TO ENGINEER Q FOR APPROVAL BEFORE FABRICATION OF TRUSSES. 2. ALL FLASNIN6 TO BE MTL. O w S. GUTTERS AND DOWNSPOUTS TO BE MTL. 4. TYP. ROOFING TO BE A CEMENT TILE TO MATCN EXIST. 5. TYP. ROOF PITCH TO AM MI EXIST. THE STRUCTURAL SYSTEM FOR THE BUILDING NAS BEEN OFS16NFD IN A ACCORDANCE WITH THE FLORIDA BUILDING CODE 2004 RESIDENTIAL EDITION W1 2006AMENDMENTS W coi WIND LOAD 140 MPN AS PER ASCE 7-02 IMPORTANCE FACTOR 1.0 EXPOSURE C WIND DIRECTIONALITY FACTOR Kd = 1.0 0.18 COEFFICIENTS INTERNAL PRESSURE7.66 PSF. W1TN + F� CODES FLORIDA 8UILDIN6 CODE 2004 RESIDENTIAL, LOCAL CODES AND GOVERNING py/ REGUMTON. ACI318-02 U ACI 421.1-R92 u A.L.C. NINTH EDITION a IV. Ds. 2001 ASCE 7-02 ROOF SNEATNING NAILING SCHEDULE (518" CDX. WITH 8d RING SHANK &AtV ) A. PROVIDE 24 BLOCKIN6 AT ALL RIDGE, NIP LINES & VALLEYS W13-8d NAILS FROM EA SIDE B. NAIL PLYWD. WITH 8d NAILS @ 6" 0. C. TNROU611 OUT PROVIDE 24 BLOCKIN6 FOR FIRST FOUR FEET AT THE PLYWD. EDGES W110 d NAILS AT 4" 0. C. C. PROVIDE 2X4 CONT. BOTT. CHORD BRACING @ 8'-O" O.C. MAXWITN 2-16d NABS AT PANEL POINT . BRACING SHALL BE RESTRAINED AT EACH END AND AT 20'-O" INTERVALS D. ALL NAILS MUST BE RIN6 SHANK 6ALV. ALL WOOD CONNECTORS MUST BE NOT DIP 6ALVANIZED. WoW A��� o WOOD TRUSSES AT 24" C/C. PROVIDE SHOP DRAWINGS FOR APPROVAL PRIOR TO FABRICATION PRODEVIDE X BRACING SEE ROOF FRAMING PLAN C[IT S-2 3'-0" MATCH EXIST. 3/4" CDX PLYWD. W/ 8d NAILS @6" O.0 & " @ EDGES PROVIDE 2X4 BLOCKING AT ALL RIDGELINE & NIP LINE W/ 3-16d NAILS TYP. TOP OF TIE BEAM SIMPSON II--5 HURRICANE CLIP @ EA TRUSS 1/2" PLYWD. SOFFIT W/A 3" x 16" SCREENED VENT ACOOkD1N6 TO FBC. 2004 RESIDENTIAL SECTION R806.2 NOTE: PROVIDE HORIZONTAL JOINT REINFORCEMENT BETWEEN EVERY OTHER COURSE W/MIN. # 9 LADDER TYPE. REINF. TO EXTEND INTO T/E COLUMN MIN. 4". NEW SLAB TO MATCH EXIST. FIN SLA8 + 16.09' NGVD. FLOOD ZONE IS " X " EXIST. FINlSN GRADE MATCH EXIST. 0 12 USP TA -16 W/ 840d N1 1 1 x 4 CONT. WOOD FIRE STOP AT 8'-0" C/C MEASURED VERTICALI Y 8" x12" CONC. T.B. W/ 2#5 TOP AND BOTT. #3 @ 48" O.C. (2#5 BEND BARS 30 LONG AT ALL CORNERS 8" CONCRETE MASONRY UNIT. SEE STRUCTURAL DWG. FOR DETAILS #5 40" O.C. W/ NORIZ. REINF #9 GA. LADDER TYPE EVf'Y OTHER COURSE PROVIDE SO" LAP FOR ALL #5 BARS ( TYP. ) GIRDER TRUSS 3-16d Nf r SIMPSO -5 HURRICANE CLIP @ 1 A TRUSS w" FILE CO THESE PLANS AND ALL PROPOSED WORK AND SUBJECT TO ANY CORRECTIONS REQUIREMAY BED NECESSARY INBY FIELD ECTORS ORDER TO T 4 CONC. SLAB W/ 6X6 - WL4XWL4 W.W.F.ON WELL COMP, FILL OVER 6 MIL VAPOR BARRIER S01L COMPACTED TO rpMPLY WITH ALL APPLICABLE CODES. 2500 PSF. AND POISONED FOR TERMITESAS PER F.S.C. 200 2006 AMENDMENTS R-920 TYPICAL WALL SECTION SCALE 3/4"=V-0" WELL COMPACTED, CLEAN NON -ORGANIC FILL. TERMITE TREATED TYPICAL FOOTING NOTE: 16" WIDE x 16" DEEP CONC FTG. W/ 2 # 5 CONT ° e e 40 PRO VIDE16"xT6" VENT OPENING FROM UPPER ROOF TO LOWER ROOF EVERY THIRD TRUSS ANCHOR VALLEY TRUSSES TO LOWER ROOF W/ NVRT24 AND 5-16d NAILS INTO EA. MEM8ERAT MAX SPACING OF 4'-O" O.C. AT PANEL POINT WHERE POSSIBLE PROVIDE 314" PLYWD BOTH SIDE W/ 10-16 d NAIL IN TOP CHORD & 1516-d NAILS IN BOTT CHORD DRILL AND EPDXY #5 @ 48" O.C. INTO 24" NEW SLAB ( THICKENED EDGE)W/ 6" EMBEDMENT INTO EXIST USE NY-150 EPDXY 8Y NILTI W M Mai N a�o�T. 00 V1 N W w a 0 a M a M w � z3� O W W W � N � 0 w o A U W � �A U L� l� M Ate, � V1 KITCHEN OR BATHROCEM EXIST HOUSE SCHEDULE WASHER 5000 V.A. COOKTOP 3400 V.A. OVEN DOI. 4500 V.A. WATER NEATER 3500 V.A. DISFIWASWER 1200 V.A. REFRIGERATOR 1500 V.A. GARBAGE DISP 1200 V.A. WASHER 1500 V.A. SMALL APPLIANCES 3000 V.A. P001 PUMP 2800 V.A. GARAGE DOOR OPEN 1500 VA. GENERAL LIGHTING 7710 VA. (2,570 SF. @ 3VA. /S.F. SUB TOTAL 36,81OV.A. ELECTRICAL NOTES 1. CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT FOR COMPLETE ELECTRICAL INSTALLATION IN ACCORDANCE WITH THESE DRAWINGS 2. COMPLYWITO TOE N.E.C. AND THE FLORIDA BUILDING CODE. 3. PROVIDE EMPTY CONDUITS AS REQUIRED FOR TELEPHONE SYSTEM 4. OBTAIN ALL PERMITS FOR WORK UNDER THIS CONTRACT. 5. PROVIDE TEMPORARY POWER AND LIGOT OUTLETS FOR USE BY O MER TRADES. 6. PROVIDE ALL REQUIRED CONNECTIONS FOR OTOFR TRADES. 7. COORDINATE ALL OUTLET LOCATIONS WITO BUILDING ARC91TECTURAI FEATURES. &. CONTRACTOR SHALL VISIT THE SITE TO FAMILIARIZE HIMSELF WITOALL EXISTING CONDITIONS 9. ALL CABLE SOALL BE COPPER EXCEPT WOFN NOTED OTOERWISE. 10. INDOOR CONDUITS SHALL BE EMT 11. OUTDOOR CONDUIT SOACL BE SCOEDULE 40 PVC MINIMUM COVER SOALL BE 24' 12. ALL MOUNTING OARDWAREWALL BE BYCONTRACTOR. 13. CONTRACTOR TO PROVIDE A BASE BID FOR TOE INSTALLATION OF TOE PADDLE FANS AND LI60T FIXTURES, OWNER WILL SUPPLY TOE U60TS AND PADDLE FANS 120 V. LINE SIDE SWITCH ""' SWITCH PHASE CONDUCTOR LEG SMOKE DETECTOR SHALL BE 120 V. WITH BATTERY BACK-UP & ALL SMOKE DETECTORS MUST BE INTERCONNECTED. TOTAL HOUSE CALCULATION EXIST. NOISE LOAD = 36, 810 V.A. NEW ADDITION LOAD = 7536 V.A. TOTAL = 44,346 V.A. FIRST 10, 000 @ 100% =10, 000 REMAINDER @ 40 % = IS,738 V.A. A1C EXIST @100 % =14,705 V.A. NEW A1C @ 100% = 4474 V.A. TOTAL =42, 917 V.A. 42,917 V.A. 240V =178 AMPS L SUB-PNL W/ TWO 2 P. BRKS. NEMA-I IN FAN -COIL CLOSET * SIZE AS PER EQUIP. NAME PLATE 10, 000 AIC 30 BREAKF S 100 AMP NEW PANEL 1201240 V I PW. / 3 W. I PW. / 3 W. C11. BUS LOAD V.A. COND. WIRE TRIP VOLTS DESCRIPTION CKT. NO CKT. NO DESCRIPTION VOLTS TRIP WIRE COND. LOAD V.A. 112" 12 20 120 GEN LTS. AND REC 1 2 GEN ITS. AND REC 120 20 12 112" JJk J� 112" 12 20 120 GEN LTS. AND REC 3 4 GEN ITS. AND REC 120 20 12 112" 1500 I/2" 12 20 120 BATNG.F.L 5 6 SMALL FANS 120 20 12 1/2" 1500 1500 112" 12 20 120 PADDLE FANS 7 8 EXHAUST FANS 120 20 12 1/2" 1500 4,474 3/4" 6 60 240 A.N.U. #1 9 10 A/C CONDENSER UNIT #1 240 40 8 I" 6,450 - - 1.5 TONS 10 KW STRIP 11 12 1.5 TONS SEE A/C PLAN FOR SEER - - - 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 SPARE 3000 VA. TOTAL LOAD NOT INCLUDING A/C TOTAL LOAD NOT INCLUDING A/C 3000 V.A. * 3VA X 512 SF =I536 VA + 3000 V.A. + 3000 V.A. =7,536 V.A. 24 OV. 2 P. FUSE SW SIZE FOR COND. UNIT UNIT SIZE AS PERERA/ ILE NAMEPLATE A/C CONNECTION DETAIL nts EXIST SERVICE ENTRANCE COND TO BE PROTECTED ACCORDING TO NEC 230.43 FROM FPL TRANSFORMER NEW 0 ALL CONDUCTORS ARE TO COMPLYW/NEC. 240.21 3 # 210 TWIN CU IN 2" p CONDUIT TOTAL = 7596 V.A. A/C LOAD @ 10OX = 4,474 V.A. TOTAL = 50 VA. cop"I THESE PLANS AND ALL PROPOSED CORRECT ONSK AND SUBJECT TO ANY REQUIRED BY FIELD INSPECTORS THAT MAY BE NECESSARY IN ORDER TO COMPLY WITH ALL APPLICABLE CODES. EXIST PANEL LOCATED IN GARAGE 2�A fP I100 AMI{ INSIDE PANEIL D.S 1-# 2 TNNN CI. IN 112" CONO #3 TWNN CU. & I TO 2 5189Zf BYIO'-O" LONG GROUND #8 GND WIRE IN 1-112" RODS 6'-0" APART (MIN) COND EXIST GND TO COPPER WATER PIPE FOUNDATION 1- # 4 TNNN CU. IN112" COND TO 2-518" x 10'-0" LONG GROUND RODS MIN. OF 6'-0" APART & I # 210 BARE AWG CU. GROUNDING ELECTRODE CONNECTED TO STEEL AT FOOTING, AND COPPER WATER LINE. ((TEEL 20'-0" LONG MIN.) SEE DIAGRAM TWISSWEET. RISER DIAGRAM NTS NEW 12,010 V.A. DEMAND= = 50AMPS 249 V PROVIDE "AFCI" BREAKERS AT ALL BEDROOM OUTLETS TO COMPLY WITH NEC. 210.12 (B ) ALL RECESS LIGHT FIXTURES THAT ABUT AN ATTIC SPACE SHALL BE "IC" RATED AS PER FLORIDA ENERGY EFFICIENCY CODE PROVIDE "AFCI" BREAKERS AT ALL BEDROOM OUTLETS TO COMPLY WITH CODE. 1- # 8 TNNN CU, IN 112" COND TO FTG. STEEL w 01� rn N AN N �I� N � O x N W W�W E� W n 0 a M a W M � A W P W a z � N w a w U w I 00 owN a4 xw w GALV. EXHAUST ROOF CAP BIRD SCREEN 6" MIN. NEW MTL ROOF 2" X 4" BLK'G. 4"- (25 GA.) SMOOTH MTL. DUCT FROM BATHROOM EXHAUST FAN OR DRYER EXHAUST ROOF CAP DETAIL nts BATHROOM, KITCHEN HOOD AND CLOTHS DRYER EXHAUST FAN 4"- (22 GA.) SMOOTH MTL. DUCT THRU ROOF (SEE DETAIL ABOVE) SCROLL TYPE STEEL, 4" DIAM. OUTLET WITH HOUSING WITH WHITE VINYL BACKDRAFT DA ERIAKED ENAMEL FINISH OR AS PER MANUF. SPE ELECTRICAL JUNCTION BOX • 8" DLAM. 9 BLADED PROPELLER FAN POLYSTYRENE GRILLE DIRECTLY MOUNTED WHITE COLOR, ALIGNED TO 1000 RPM MOTOR AND TIGHTENED BY SINGLE CENTER KNOB TYPICAL CEILING EXHAUST FAN DETAIL nts EXHAUST CEILING F'AN, CFM AS NOTED Jr ON PLANS, 1.5 SONES NOISE CRITERIA UVACDESIGNREQUIRESYES NO Ducr SMOKE DETEC OR X FIRE DAMPERS X SMO ; DAMPERS X F CE RATED ROOF/ F LNG ASSEMBLY OOR X FIRIE STOPPING X SMOKE CONTROL X PROVIDE 2 1/4" DIA. STEINLESS STEEL CABLES AROUND MECHANICAL EQUIPTMENT, BOTH ENDS ANCHORED TO SLAB W Z� UOTDENSING W O rrQ� w CONC. SLAB V PTO � SEESTRUCTURAL 00 DWGS. FOR � w N POWER & CONT. N CONNECTIONS 0* a, v FASTEN C.U. TO CONC. SLAB W/ (4) 2"x 2"x 3/16" STL. ANGLES W/ e N W 3/8"- x 3" SLV. ANCH. TO SLAB & 3/8"- x THRU BOLTS TO 6" - SCH. 40 PVC. PIPE. 45 DEG. (MAX.) ELBOW ALLOWED SEAL ENTRANCE OF REFR. LINES INTO PVC. PIPE W/ IMPERMEABLE, RESILIENT SUCTION LINE W/ 3/4" = MATERI ARMFLEX INSULATION & VAPOR BARRIER a I� CONDENSING UNIT MOUNTING DETAIL nts Ic_-1 M ►a � � w A a W � z O W � FIVE COP ._ A a W z a AIR CONDITIONING SCHEDULE CONDENSER AIR HANDLER COOLING CAPACITY REFRIGERANT LINES WEIGHT DIMENSIONS AC No TONS SEER CFM MODEL NUMBER MODEL NUMBER TOTAL TOTAL COOLINC SENSIBLE LATENT SUCTION LIQUID A.H.0 CONP. A.H.U. H%WxD COND. HxWxD (� 1 1.5 13.0 600 2TTB3018A1000A 2TGB3F18A1000A 17.1 13.4 15.25 5/8" 1/4" 109LBS 163 LBS 46" x 18" x 21" 33 x 28" x 25" O _ w r� THESE PLANS AND ALL PROPOSED AND WORK O W SUBJECT TO ANY CORRECTIONS REQUIRED ^� BY FIELD INSPECTORS W MAY BEECESSARY IN ORDER • HVAC NOTES TO COMPLY WITH ALL APPLICABLE Z � CODES. W 1.0 GENERAL 1.6 GUARANTEE ALL WOR K FREE OF DEFECTS IN MATERIALS 2A PROVIDE AIR CONDITIONING UNITS WITH MATCHING LOW Q AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM VOLTAGE HEAT -COOL THERMOSTATS WITH ON -OFF AUTO 1.1 PROVIDE ( FURNISH AND INSTALL) ALL NECESSARY OPERATIONAL DATE OF ACCEPTANCE. SUB -BASE SWITCH, FURNISHED BY THE EQUIPMENT Gla MATERIALS AND LABOR FOR A COMPLETELY MANUFACTURER. AIR CONDITIONING, HEATING AND VENTILATING SYSTEM AS 2.0 MATERIALS SHOWN ON THE DRAWINGS AND HEREIN SPECIFIED 2.5 ALL AIR CONDITIONING COMPRESSMS SHALL INSTALL IN ACCORDANCE WITH THE FLORIDA 2.1 DUCTWORK WARRANTED FOR A MINIMUM OF FIVE YEARS AFTER DATE BUILDING CODE, ASHRAE, SMACNA, NFPA, AND LOCAL 2,1.1 GENERAL. ALL DUCT SIZES SHOWN ARE CLEARINSIDE OF ACCEPTANCE OF THE PROJECT. ORDINANCES. DIMENSIONS. 2.7 AIR DISTRIBUTION PRODUCTS: 1.2 SCOPE OF WORK: 2.1.2 MATERIMEOUNDS DENSITY 1 1/2 " THICK GLASSFIBER 2.7.1 PROVIDE SUPPLY AND RETURN GRILLES AND DIFFUSERS DESIGNED, CONSTRUCTED AND INSTALLED IN ACCORDANCE AS INDICATED ON THE DRAWINGS. PROVIDE THE FOLLOWING COMPLETE SYSTEMS: WITH SMACNA'S LOW PRESURE DUCT MANUAL. ALL 2.7.2 PROVIDE EXTRUDED ALL ALUMINIUM AIR DISTRIBUTION A. SUPPLY AND RETURN DUCT SYSTEM. DUCT JOINTS SHALL BE SEALED AND TAPED. PRODUCTS. U 2.1.3 PROVIDE DOUBLE THICKNESS TURNING VANES AT ALL 2.7.3 PROVIDE FINISHES AND TYPES OF MOUNT IN COORDINATION B. EXHAUST SYSTEM FOR BATHROOMS AND KITCHEN. SQUARE ELBOWS. WHERE THE ELBOWS ARE RECTANGULAR WITH THE CEILING TYPES AS SHOWN ON ARCHITECTURAL a C. AIR CONDITIONING UNITS WITH REFRIGERANT PIPING INSTALL SINGLE THICKNESS INSTEAD. DRAWINGS. AND CONTROLS. 23A PROVIDE VOLUME EXTRACTORS BEHIND EACH SUPPLY 2.7.4 PROVIDE OPPOSED BLADE, KEY OPERATED DAMPERS OUTLET AND AT EACH DUCT BRANCH. BEHIND ALL AIR SUPPLY OUTLETS. 1.3 PAY FOR ALL FEES, INSPECTIONS AND CONNECTION CHARGES REQUIRED 2.2 REFRIGERANT PIPING. SEAMLESS COPPER TYPE "L" AND 3.0 INSTALLATION f HARD OR SOFT DRAWN ON ACR COPPER TUBING WITH 1.4 VERIFY AT JOB SITE ALL SPACE CONDITIONS, DIMENSIONS WROUGHT COPPER SOLDER JOINT FITTINGS, SOLDER 3.1 INSTALL ALL EQUIPMENT IN,.ACCORDANCE TO THE AND EQUIPMENT SIZES PRIOR TO DUCT RUBRICATION SHALL BE 95/5 APPLIED WITH SUITABLE FLUX. MANUFACTURER'S MANUAL AND RECORIMENDATIONS INSTALLATION. COORDINATE REQUIREMENTS TO AVOID 2.3 INSULATE ALL REFRIGERANT SUCTION PIPING WITH 3/4" PAYING SPECIAL ATTENTION TO REQUIRED CLEARANCES INTERFERENCE WITH OTHER TRADES. CLOSED CELL POLYETHYLENE PREMOLDED PIPE FOR INSTALLATION, OPERATION AND SERVICE. 1.5 SUBMIT SHOP DRAWINGS FOR ARCHITECT / ENGINEER INSULATION, WITH AN APPROVED PIPE AND SMOKE 3.2 BALANCE ALL SYSTEMS TO PROVIDE AIR QUANTITIES AND APPROVAL BEFORE PROCEEDING WITH THE PURCHASE OR JACKET. PAINT ALL EXPOSED INSULATION WITH TWO CAPACITIES. INDICATED ON DRAWINGS. SUBMIT FINAL INSTALLATION OF EQUIPMENT AND MATERIALS. COATS OF WHITE LATEX PAINT. AND BALANCE REPORT TO ARCHITECT / ENGINEER FOR ACCEPTANCE. 4 OWN x � w A� � C