HomeMy WebLinkAboutENERGY EFFICIENCY CODEFORM R405-2017
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2017 Florida Building Code, Energy Conservation via the residential
Simulated Performance method shall include:
❑ This Checklist
❑ A FORM 405 report that documents that the Proposed Design complies with Section R405.3 of the Florida
Energy Code. This form shall include a summary page indicating home address, a -ratio and the pass or fail
status along with summary areas and types of components, whether the home was simulated as a worst -case
orientation, name and version of the compliance software tool, name of individual completing the compliance
report (one page).
❑ An input summary checklist that can be used for field verification (usually 4 pages/maybe greater).
SCANNED
❑ Energy Performance Level (EPL) Display Card (one page) BY
St. Lucie Coin*
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO for the Performance method:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table 402.4.1.1- one page)
❑ A completed Form 2017 Envelope Leakage Test Report (usually one page). Section R402.4 or R402.4.1.2
exceptions may apply.
❑ If FORM R405 duct leakage type indicates anything other than "default leakage", then a completed FORM R405
Duct Leakage Test Report (usually one page).
yes ���n: �•^, ;)
4wrigh` - 2019.Oct-18 09:47:53
tsoft" Rig htSuBe® U niv ersal 201919.0.13 RSU25344 Right -Energy® Florida 2017 Section 405.4.1 Compliant Software page 1
O Pro 11FlnalslCurtent\Sparks Renovation RE.rup CaIc=M a Front Door aces:
FORM R405-2017
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: Sparks Renovation
Builder Name:
Street: 2358 S Brochsmith Rd
Permit Office:
City, State, Zip: Ft. Pierce, FL 34945
Permit Number:
Owner. Sparks Renovation
Jurisdiction: St. Lucie County
Design Location: FL, St Lucie Co Intl
County: St. Lucie (Florida Climate Zone 1)
-1. New construction or existing New (From Plans)
9. Wall types (3208 ft')
Insulation (R) Area (ft')
2. Single family or multiple family Single -Family
a. Block Wall R-5
b. 2x6 R-20 spray foam
5.0 2868.40
20.0 340.00
3. Number of units, if multiple family 1
c. N/A
4. Number of bedrooms 6
d. N/A
10. Ceiling types (3333 ft')
Insulation (R) Area (ft')
5. Is this a worst case? No
a. metal spray foam R-30
30.0 3332.83
6. Cond dioned floo r area ab ove g rade(W) 3306.50
b. N/A
Conditioned floor area below grade (W) 0
c. NIA
7. Windows 376f1' Description Area W
( ) P ( )
11.DUSu:AHU-1MainAltl,Ret:AHU-1MainAfti,AH:AHU-1MainANc cts
a. p
R A486.5rea ')
6.0
a.U-Factor: DblImpact, 0.450 375.50
baup:AHU-3MazterAt,RetAHLL3Me51erAt,AH:AHU3MaslerANc 6.0 119.15
119.15
SHGC: 0.30
b. U-Factor:
12. Cooling systems
kBlulhr Efficiency
SHGC:
a.Split air conditioner
40.0 SEER: 16.0
c. U-Factor:
b.Split air source heat pump
12.0 SEER: 18.6
SHGC:
13. Healing systems
kBlulhr Efficiency
d. U-Factor.
a.Electric strip
36.9 AFUE: 100.0
SHGC:
b.Split air source heat pump
16.3 HSPF: 10.9
Area Weighted Average Overhang Depth: 7.290 ft
14. Hot water systems
Area Weighted Average SHGC: 0.300
a.Propane instantaneous (0 gal)
Cap: 0 gal
EF: 0.99
8. Floor types (3306.50 ft') Insulation (R) Area (fl')
b.Conservation features
a. slab on grade 0.0 3306.50
(None)
b. NIA
c. N/A
15. Credits None
Glass/Floor area: 0.114 Total Proposed Modified Loads: 85.65
PASS
Total Baseline
Loads: 110.50
I hereby certify that the plans and specifications covered by
Review of the plans and specifications
indicates
?AD
this calculation are in compliance with the Florida Energy
covered by this calculation
0
Code.
compliance with the Florida Energy
�J
Code. Before construction is completed
PREPARED BY: CAV�'
this building will be inspected for
compliance with Section 553.908
o
DATE: 10/18/2019
Florida Statutes.
I hereby certify that this building, as designed, is in
compliance with the Florida Energy Code.
OWNER/AGENT:_�//� !✓--
BUILDING OFFICIAL:
DATE: 101141 It
DATE:
Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with R403.3.2.1.
Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project
requires an envelope leakage test report with envelope leakage no greater than 5.0 ACH50 (R402.4.1.2).
zo19-0a-1e 09:47:53
h'Hrry91hQ{},o, Right-Sude0l Universal 201919.0.13 RSU25344 Right-Energy®Flaritla 2017 Section 405.4.1 Compliant Software Page$
... OPmj'TinalslCurrenllSparks Renovation RE.mp Calc=MJe Front Doorfaces: W
FORM R405-2017
Building Input Summary Report
PROJECT
Title:
Sparks Renovation
Bedrooms: 6
Address type:
Street
address
Building
Type: FLAsBuilt
Bathrooms: 5
Lot#:
Owner:
Sparks Renovation
Conditioned Area: 3307
Block/Subdivision:
# of Units: 1
Total Stories: 1
Platbook:
Builder Name:
Worst Case: No
Street:
2358 S Brochsmith
Rd
Permit Office:
Rotate Angle: 0
County:
St. Lucie
Jurisdiction:
St. Lucie County
Cross Ventilation: No
City, State, Zip:
Ft. Pierce,
FL
34945
FamilyV Typpe: Single -Family
Whole House Fan: No
Terrain: Ocean/Lake
New/Exisfing:
New (From
Plans)
Year Construct: 2018
Shielding: Suburban
Comment:
CLIMATE
IECC Design Temp
Int Design Temp
Heating
Design
Daily Temp
Design Location
TMY Site Zone 97.5 % 2.5
% Winter Summer Degree Days
Moisture
Range
FL, St Lucie Cc Intl
FL Foe_Pieme 1 37 91
70 75
486
54
Low
BLOCKS
#
Name
Area Volume
1
AHU-2 Master
697.75 ft' 7085.50 f s
2
AHU-1 Main
2608.75 ft' 27136.30 fP
SPACES
#
Area
Volume Kitchen Occupants Bedrooms Infil ID Finished
Cooled
Heated
1
M Bath
229.75 ft'
2297.50 fP No 0
0 1
Yes
Yes
Yes
2
WIC 2
36.00 ft'
360.00 W No 0
0 1
Yes
Yes
Yes
3
WIC 1
33.00 ft'
330.00 ft' No 0
0 1
Yes
Yes
Yes
4
Master Bedroom
259.00 ft'
2698.00 ft' No 0
1 1
Yes
Yes
Yes
5
Foyer
235.75 fl'
2923.30 fP No 0
0 1
Yes
Yes
Yes
6
Bedroom 6
225.00 ft'
2250.00 ft' No 0
1 1
Yes
Yes
Yes
7
Bath 4
ft
58.50 '
585.00 fl' No 0
0 1
Yes
Yes
Yes
8
Utility
155.50 ft'
1555.00 ft' No 0
0 1
Yes
Yes
Yes
9
Butler
56.25 ft'
562.50 fi' No 0
0 1
Yes
Yes
Yes
10
11
Bedroom 3
Bath 3
174.75 ft-
52.25 fl'
1747.50 fl' No 0
522.50 ft' No 0
1 1
0 1
Yes
Yes
Yes
Yes
Yes
Yes
12
Bedroom
153.63 ft'
1536.25 f' No 0
1 1
Yes
Yes
Yes
13
Bedroom 2
314.25 ft'
3142.50 ft' No 0
1 1
Yes
Yes
Yes
14
Bath
63.00 ft'
630.00 Its No 0
0 1
Yes
Yes
Yes
15
Bath 2
71.50 fl'
715.00 ft' No 0
1
Yes
Yes
Yes
16
Bedroom 5
187.50 ft'
1875.00 fl' No 0
1
Yes
Yes
Yes
17
Office
140.00 fP
1400.00 fl' No 0
0 1
Yes
Yes
Yes
18
Great Room
860.88 ft'
9091.75 ft- Yes 7
0 1
Yes
Yes
Yes
FLOORS
(Total Exposed Area = 3307 sq.fL)
#
Floor Type
Space Perimeter R-Value Area
U-Factor
Tile Wood Carpet
1
slab on grade
M Bath 40
ft
0 229.75 ft'
1.180
1.0
0 0
2
slab on grade
WIC 2 6
it
0 36.00 fl'
1.180
1.0
0 0
3
slab on grade
WIC 1 0
ft
0 33.00 fl'
1.180
1.0
0 0
4
slab on grade
Master Bedroom 17
It
0 259.00 fl'
1.180
1.0
0 0
5
slab on grade
Foyer 20
It
0 235.75 ft'
1.180
1.0
0 0
6
slab on grade
Bedroom 6 39
ft
0 225.00 ft'
1.180
11.0
0 0
7
slab on rade
grade
B th 4 9
ft
0 58.50 If?
ft'
1.180
1.180
1.0
0 0
8
slab on
Utility 11
ft
0 155.50
9
slab on grade
Butler 0
ft
0 56.25 ft'
1.180
1.0
0 0
10
slab on grade
Bedroom 3 15
It
0 174.75 ft'
1.180
1.0
0 0
11
slab on grade
Bath 3 6
It
0 52.25 fP
1.180
1.0
0 0
12
slab on grade
Bedroom 4 14
it
0 153.63 fl'
1.180
1.0
0 0
- 13
slab on grade
Bedroom 2 39
ft
0 314.25 fl'
1.180
1.0
0 0
14
slab on grade
Bath 17
It
0 63.00 ft'
1.180
1.0
0 0
15
slab on grade
Bath 2 6
It
0 71.50 ft'
1.180
1.0
0 0
16
slab on grade
Bedroom 5 27
ft
0 187.50 ft'
1.180
1.0
0 0
17
slab on rade
Office 24
ft
0 140.00 fl'
1.180
1.0
0 0
18
slab on grade
Great Room 10
It
0 860.88 fl'
1.180
1.0
0 0
ROOF
Roof Gable
Roof
Solar SA
Emitl
Emitt
Deck Pitch
#
Type
Materials Area Area
Color
Absor. Tested
Tested
Insul. (deg)
2
RooftIvleta1 29107ftt'
Light
0 75 No
0.90
90
No
0 27
Hip
IT "'_ . ..: 2019-Oct-te 09:4ge3
+4VIIi1C]�'ItiSOt S Right-Su@eals%Cu nt\Sparks Renovation
RE.m44 Right-Energynt Floridaes: Section 405.4.1 Compliant Software pege3
-r ; aw.i•ifn,Y.4i...a,�, ...0 PrglFinalslCurreMlSparks Renovation RE.rup Calc= MJ8 Front Door laces: W
FORM R405-2017
ATTIC
#
Type
Ventilation
Vent Ratio 1 In
Area
RBS
IRCC
1
Full attic
Unvented
0
697.75 ft2 N
N
2
Full attic
Unvented
0
2608.75ft2 N
N
CEILING
(Total Exposed Area = 3333 sq.fL)
J
#
Ceiling TVpe
Space
R-Value
U-Factor
Area
Framing Fraction Truss Type
1
metal spra foam R-30
M Bath
30
0.408
229.75 ft2
0.10
Wood
2
metal spra foam R-30
WIC 2
30
0.408
36.00 ft2
0.10
Wood
3
metal spray foam R-30
WIC 1
30
0.408
33.00 ft2
0.10
Wood
4
metal spray foam R-30
Master Bedroom
30
0.408
259.00 ft2
0.10
Wood
5
metal spray foam R-30
Foyer
30
0.408
262.08 ft2
0.10
Wood
6
7
metal spra foam R-30
foam R-30
Bedroom 6
30
0.408
225.00 ft2
0.10
Wood
8
meta spra
metal spray foam R-30
Bath 4
Utility
30
30
0.408
0.408
58.50 ft2
155.50 ft2
0.10
0.10
Wood
Wood
9
metal spray foam R-30
Butler
30
0.408
56.25 ft2
0.10
Wood
10
metal spray foam R-30
Bedroom 3
30
0.408
174.75 ft2
0.10
Wood
11
metal spra foam R-30
Bath 3
30
0.408
52.25 ft2
0.10
Wood
12
metal spra foam R-30
Bedroom 4
30
0.408
153.63 ft2
0.10
Wood
13
metal spray foam R-30
Bedroom 2
30
0.408
314.25 ft2
0.10
Wood
14
metal spray foam R-30
Bath
30
0.408
63.00 fl2
0.10
Wood
15
metal spray foam R-30
Bath 2
30
0.408
71.50 fl2
0.10
Wood
16
metal spray foam R-30
Bedroom 5
30
0.408
187.50 fl2
0.10
Wood
17
metal s ra foam R-30
Office
30
0.408
140.00 {fl2
0.10
Wood
18
metal spra�r foam R-30
Great Room
30
0.408
860.88 fl2
0.10
Wood
WALLS
(Total Exposed Area = 3208 sq.tL)
Adjacent
Cavity Width
Height
Sheathing
U- Frm.
Solar
Below
#
Ornt
To Wall Type
Space R-Value
Ft
In Ft In
Area R-Value
Factor Frac.
Absor.
Grade%
1
N
Exterior Block Wall R-5
M Bath
5
9
6 10 0
95.0
ft2 0
0.125 0.22
0.75
0
2
S
Exterior Block Wall R-5
M Bath
5
15
0 10 0
150.0
ft2 0
0.125 0.22
0.75
0
3
W
Exterior Block Wall R-5
M Bath
5
15
6 10 0
155.0
ft2 0
0.125 0.22
0.75
0
4
S
Exterior Block Wall R-5
WIC 2
5
6
0 10 0
60.0
ft2 0
0.125 0.22
0.75
0
5
N
Exterior Block Wall R-5
Master Bedroom
5
1
2 10 5
12.0
ft2 0
0.125 0.22
0.75
0
6
E
Exterior Block Wall R-5
Master Bedroom
5
0 10
10 5
9.0
ft2 0
0.125 0.22
0.75
0
7
S
Exterior Block Wall R-5
Master Bedroom
5
17
6 10 5
182.0
ft2 0
0.125 0.22
0.75
0
8
W
Exterior Block Wall R-5
Master Bedroom
5
0 10
10 5
9.0
ft2 0
0.125 0.22
0.75
U
9
E
Exterior Block Wall R-5
Foyer
5
3 12
12 5
49.2
ft2 0
0.125 0.22
0.75
0
10
W
Exterior Block Wall R-5
Foyer
5
19
8 12 5
244.2
ft2 0
0.125 0.22
0.75
0
11
N
Exterior Block Wall R-5
Bedroom 6
5
13
6 10 0
135.0
ft2 0
0.125 0.22
0.75
0
12
S
Exterior Block Wall R-5
Bedroom 6
5
4
6 10 0
45.0
ft2 0
0.125 0.22
0.75
0
13
W
Exterior B ock Wall R-5
Bedroom 6
5
21
0 10 0
210.0
ft2 0
0.125 0.22
0.75
0
14
S
Exterior Block Wall R-5
Bath 4
5
9
0 10 0
90.0
ft2 0
0.125 0.22
0.75
0
15
N
Exterior Block Wall R-5
Utility
5
7
6 10 0
75.0
ft2 0
0.125 0.22
0.75
0
16
S
Exterior Block Wall R-5
utility
5
3
6 10 0
35.0
ft2 0
0.125 0.22
0.75
0
17
N
Exterior Block Wall R-5
Bedroom 3
5
14
6 10 0
145.0
ft2 0
0.125 0.22
0.75
0
18
N
Exterior Block Wall R-5
Bath 3
5
5
6 10 0
55.0
ft2 0
0.125 0.22
0.75
0
19
N
Exterior Block Wall R-5
Bedroom 4
5
14
0 10 0
140.0
ft2 0
0.125 0.22
0.75
0
20
N
Exterior Block Wall R-5
Bedroom 2
5
28
6 10 0
285.0
ft2 0
0.125 0.22
0.75
0
21
E
Exterior Block Wall R-5
Bedroom 2
5
7
6 10 0
75.0
fl2 0
0.125 0.22
0.75
0
22
S
Exterior Block Wall R-5
Bedroom 2
5
3
0 10 0
30.0
ft2 0
0.125 0.22
0.75
0
23
24
E
S
Exterior B ock Wall R-5
Exterior Block Wall R-5
Bath
Bath
5
6
0 10 0
60.0
ft2 0
0.125 0.22
.75
8.75
0
25
E
Exterior Block Wall R-5
Bath 2
5
5
10
6
6 10 0
0 10 0
105.0
60.0
ft2 0
ft2 0
0.125 0.22
0.125 0.22
0.75
0
0
26
E
Exterior Block Wall R-5
Bedroom 5
5
12
6 10 0
125.0
ft2 0
0.125 0.22
0.75
0
27
S
Exterior Block Wall R-5
Bedroom 5
5
14
6 10 0
145.0
ft2 0
0.125 0.22
0.75
0
28
E
Exterior 2x6 R-20 spray fo
Office
20
14
0 10 0
140.0
ft2 0
0.080 0.25
0.75
0
29
S
Exterior 2x6 R-20 spray fo
Office
20
10
0 10 0
100.0
ft2 0
0.080 0.25
0.75
0
30
N
Exterior Block Wall R-5
Great Room
5
1 12
10 7
21.0
ft2 0
0.125 0.22
0.75
0
31
E
Exterior 2x6 R-20 spray fo
Great Room
20
9
6 10 7
100.0
ft2 0
0.080 0.25
0.75
0
32
E
Exterior Block Will R-5
Great Room
5
2
2 10 7
23.0
ft2 0
0.125 0.22
0.75
0
33
S
Exterior Block Wall R-5
Great Room
5
1 12
10 7
21.0
ft2 0
0. 25 0.22
.75
8.75
0
34
W
Exterior Block Wall R-5
Great Room
5
2
2 10 7
23.0
ft2 0
025 0.22
0
DOORS
(Total Exposed Area = 92 sq.ft.)
f
#
Ornt Door Type
Space
Storms
U-Value Width
Ft In
Height
Ft In
Area
1
W Door, mil fbrgl type
Foyer
None
0.600
3 0
8 0
24.0 ft2
2
N Door, mill fbrgl type
Utility
None
0.600
3 0
6 8
20.1 ft2
3
N Door, mtl fbrgl type
Bedroom 2
one
0.600
3 0
8 0
24.0 ft2
4
E Door, mtl fbrgl
type
Bath 2
None
0.600
3 0
8 0
24.0 ft2
2019-Oct-18 09:47:53
,11'1(LN [�9f1t$O ° Rig htSude®Univ ersa1201919.0.73 RSU25344 Rig ht-Enemy®Florida 2017 Section 405.4.7 Compliant SoBware Pege4
yrY:pfkaiy:.yi�p ... O Prol"FinalslCurrennSparks Renovation RE.rup Calo- MJ8 Front Doorfaces: W
FORM R405-2017
WINDOWS
(Total Exposed Area = 376 sq.fL)
Wall
Overhang
Interior
#
Ornt
ID Frame Panes
NFRC
U-Factor
SHGC Impact
Area
Depth Separation
Shade
Screening
1
S
2 TIM Low-E Double
Yes
0.450
0.30 Yes
6.Oft2
2 ft 0 in 1 it 1 in
None
None
2
W
3 TIM Low-E Double
Yes
0.450
0.30 Yes
10.Of12
2 ft 0 in 1 ft 1 in
None
None
3
W
3 TIM Low-E Double
Yes
0.450
0.30 Yes
12.5ft2
2 ft 0 in 1 ft 1 in
None
None
4
S
7 TIM Low-E Double
Yes
0.450
0.30 Yes
15.02
2 it 0 in 1 ft 1 in
None
None
5
S
7 TIM Low-E Double
Yes
0.450
0.30 Yes
18.Oft2
2 It 0 in 1 it 1 in
None
None
6
W
10 TIM Low-E Double
Yes
0.450
0.30 Yes
36.Oft2
8 It 3 in 2 ft 2 in
None
None
7
8
W
W
10 TIM Low-E Double
10 TIM Low-E Double
Yes
Yes
0.450
0.30 Yes
10.7ft2
8 ft 3 in 2 ft 2 in
one
None
9
W
13 TIM Low-E Double
Yes
0.450
0.450
0.30 Yes
0.30 Yes
11.3ft2
36.Oft2
8 ft 3 in 2 ft 2 in
2 ft 0 in 1 It 1 in
one
None
None
None
10
S
14 TIM Low-E Double
Yes
0.450
0.30 Yes
6.Oft2
2 ft 0 in 2 It 0 in
None
None
11
N
17 TIM Low-E Double
Yes
0.450
0.30 Yes
18.0ft2
2 it 0 in 1 ft 1 in
None
None
12
18 TIM Low-E Double
Yes
0.450
0.30 Yes
6.Oft2
2 ft 0 in 1 ft 1 in
14
NNN
N
20 TIM Low-E Double
Yes
0.450
0.30
30 Yes
36.Oft2
2 ft 0 in 1 ft 1 in
NNone
NNone
15
E
23 TIM Low-E Double
Yes
0.450
0.30 Yes
6.Oft2
2 it 0 in 2 ft 0 in
None
None
None
None
16
E
26 TIM Low-E Double
Yes
0.450
0.30 Yes
18.0ft2
2 ft0 in 2 it 0 in
None
None
17
E
28 TIM Low-E Double
Yes
0.450
0.30 Yes
48.Oft2
x
16 ft 6 in 0 ft 0 in
None
None
GARAGE
` #
Floor Area Ceiling Area
Exposed Wall Perimeter
Avg. Wall Height Exposed Wall Insulation
1
0
INFILTRATION
1
Wholehouse Blower Door 0.000329
2852
156.9
294.6
0.39 5.00
HEATING SYSTEM
#
System Type
Subtype
Efficiency
Capacity
Block
Ducts
1
Split air source heat pump
HSPF: 10.9
16.3
kBtu/hr
1
sys#1
2
Electric s ri
AFUE: 100.0
36.9 B ulhr
2
s s#2
COOLING SYSTEM
#
System Type
Subtype
Efficiency
Capacity Air Flow SHR Block
Ducts
1
Split air source heal pump
SEER: 18.6
12.0 kBtu/hr 382 cfm 0.80
1
sys#1
' 2
Sot air conditioner
SEER: 16.
40.0 kBtu/hr 1390 0.80
2
s s#2
HOT WATER SYSTEM
#
System Type Subtype Location EF
Cap
Use
SetPnt
Conservation
1
Propane instantaneous
0.99
0 gal
90 cat
120 °F
None
DUCTS
'
Supply ---- ---- Return ----,
Air
CFM 25 Percent
HVAC #
#
Location R-Value Area
Location
Area
Leakage Type Handler
Out Leakage ON
RLF Heat Cool
1
AHU-2 MasterAt 6.0 119 ft2 AHU-2 Master Al 58 ft2
Default Leakage A11LL2 MasterANc
(Default) 6.00
1 1
2
AHU-1 Main Atli 6.0 487 fl2 AHU-1 Main Atli 95 ft2
Default Leakage AHU.1
Mein Attic
(Default) 6.00
2 2
TEMPERATURES
Programmable Thermostat: Y
Ceiling Fans:
Cooling
[ X ]Jan
X]] Feb [ X]] Mar X]]
E E
Apr [ X]]
May [ X]]
Jun [ X]] Jul [
X]] Aug
X]] Se X]] Oct
X]] Nov
X]] Dec
Healing
[ X ]Jan
X] Feb [ X] Mar X]
Apr [ X]
May [ X]
Jun [ X] Jul [
X] Au[
X] SeP [ X] Oct [
X] Nov
[ X] Dec
Venting
[ X
Jan [ X1l Feb I X1l Mar [[ X1l
Apr [ X11
May [ X1]
Jun [ Xi Jul [
X1l Aug
[ X11 Se [ X11 Oct [
X1l Nov
[ X1l Dec
Thermostat Schedule: Florida Building Code, 6th Edition
Hours
Schedule Type
1 2
3
4
5 6
7
8 9 10
11
12
Cooling
(WD)
AM 75 75
75
75
75 75
75
75 75 75
75
75
PM 75 75
75
75
75 75
75
75 75 75
75
75
Cooling
(WEH)
AM 75 75
75
75
75 75
75
75 75 75
75
75
PM 75 75
75
75
75 75
75
75 75 75
75
75
Heating
(WD)
AM 72 72
72
72
72 72
72
72 72 72
72
72
. PM 72 72
72
72
72 72
72
72 72 72
72
72
Heating
(WEH)
AM 72 72
72
72
72 72
72
72 72 72
72
72
PM 72 72
72
72
72 72
72
72 72 72
72
72
• 2
WrlgfltSOfE° Rig hlSUHe®Universal 201919.0.13RSU25344 Rig ht•Enegy®Florid a2017 Sect on405.4ACompkaMSa019-Oct-18 09:47:53
oxre Page
0 ProlffinalslCurrenl\Sparks Renovation RE.rup Calc-We Front Door faces: W
FORM R405-2017
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX = 78
The lower the EnergyPerformance Index, the more efficient the home.
1. New home or addition
1. New (From
Plans)
12. Ducts, location & insulation level
a. Supply ducts:
R
6.0
2. Single-family or multiple -family
2. Single -Family
b. Return ducts:
R
6.0
c. AHU location:
AHU-1 Main Attic
3. Number of units, if multiple -family
3.
1
13. Cooling systems
Capacity
52.0
4. Number of bedrooms
4.
6
a. Split system:
SEER
18.60
b. Single package:
SEER
5. Is this a worst case? (yes/no)
5.
No
c. Ground/water source: SEER/COP
d. Room unit/PTAC:
EER
6. Conditioned floor area (ft�
6.
3306.50
e. Other:
7. Windows, type and area'
14. Heating systems
Capacity
53.2
a. U-Factor:
7aDb1 Imp
act 0.450
a. Split system heat pump:
HSPF
10.90
b. Solar Heat Gain Coefficient (SHGC):
7b.
0.30
b. Single package heat pump:
HSPF
c. Area (fl
7c.
375.50
c. Electric resistance:
COP
100.00
d. Gas furnace, natural gas:
AFUE
8. Skylights
e. Gas furnace, LPG:
AFUE
a. U-Factor:
8a.
f. Other:
b. Solar Heat Gain Coefficient (SHGC):
8b.
15. Water heating systems
9. Floor type, insulation level
a. Electric resistance:
EF
a. Slab -on -grade (R-value):
9a.
0.0
b. Gas fired, natrual gas:
EF
b. Wood, raised (R-value):
9b.
c. Gas fired, LPG:
EF
0.990
c. Concrete, raised (R-value)
9c.
d. Solar system with tank:
EF
e. Dedicated heat pump with
tank: EF
10 Wall type and insulation:
f. Heat recovery unit:
HeatRec%
a. Exterior:
g. Other:
1. Wood frame (Insulation R-value):
10al.
20
2. Masonry (Insulation R-value):
10a2.
5
16. HVAC credits claimed (Performance
Method)
b. Adjacent: '
a. Ceiling fans:
1. Wood frame (Insulation R-value):
10bl.
b. Cross ventilation:
2. Masonry (Insulation R-value):
10b2.
c. Whole house fan:
d. Multizone cooling credit:
Yes
11. Ceiling type and insulation level
e. Multizone heating credit:
Yes
a. Under attic (R-value):
11 a.
30.0
f. Programmable thermostat:
Yes
b. Single assembly (R-value):
ll b.
c. Knee walls/skylight walls (R-value)
11c.
d. Radiant barrier installed
11d.
*Label required by Section 303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
I certify that this home has complied with the Florida Building Code, Energy Conservation,through the above energy saving features
which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code compliant features.
Builder Signature: /'` 2n-
Address of New Home: 2358 S Brochsmith Rd
Date:
City/FL Zip: Ft. Pierce, FL 34945
r' 2019-Oct-18 09:47:53
swrightsoft° Right-SudeH Universal RSU25344 Right-Enegy® Florida Section CampliaMSo ware Page
a:::yi ...0 ProffinalslCurreninSparks Renovation RE.mp Celc= MJe Front Doorfaces: W
FORM R405-2017
Florida Building Code, Energy Conservation, 6th Edition (2017)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: 2358 S Brochsmith Rd PERMIT #:
Ft. Pierce FL 34945
MANDATORY REQUIREMENTS - See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory). The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
(Section 553.9085, Florida Statues) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. completed and signed by the builder The building gfficial shall verify that the EPL display card accurately reflects the plans
and specifirali0.ns submitted to demonstrate compliance for the building. A copy of the EPL display card can be found in Appendix RD.
❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dvvellingg units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
R402.4.1 Building thermal envelope. The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing
methods between dissimilar materials shall allow for differential expansion and contraction.
R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table 402.4. 1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verdy compliance.
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakagge rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3lhrough 8. Testing shall be conducted in
accordance with ANSI/RESET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(51 or (7), Florida Statutes or individuals licensed as set forth in Section 489.105(3)(0, (g), or (i) or
an approved third party. A written report off the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building the envelope.
1. Ederior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended
weatherstripping or other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond
intended infiltration control measures.
3. Interior doors, if installed at the time of the lest, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, If Installed at the time of the test, shall be fully open.
R402.4.2 Fireplaces. New wood -burning fireplaces shall have light -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeledin accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight-figging doors on masonry fireplaces,lhe doors shall be listed and labeled in accordance with UL 907.
R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per
square fool (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square fool (2.6 Us/m2), when tested according to NFRC 400 or
/W AAMADMA/CSA 101/I3.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
t" h 2019.0ct-18 09:47:53
,�l;tN1±ItJt7150ft' Rig hlSuite®Universal 207979.0A3 RSU25344 Rig ht-Energy®Florida 2017 Section 405.4.1 Compliant Software Page
;;,rYi.4Q4 "t-6�, ...0 Proj\Finals\Current\Sparks Renovation RE.mp Calc= We Front Door faces: W
FORM R405-2017
MANDATORY REQUIREMENTS -(Continued)
El R402.4.4 Rooms containing fuel-buming appliances In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent apliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
❑ R403.1 Controls
R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate healing and cooling system.
R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
rl R403.3.2 Sealing (Mandatory). All ducts, air handlers, filler boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts and plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct lightness criteria below.
Duct tightness shall be verged by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7),
Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design air flow rate when tested in accordance with ASHRAE 193.
R403.3.3 Duct testing. Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the
manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test.
2. Post construction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the
entire system, including the manufacturer's air handler enclosure. All registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct leakage lest shall not be required where the ducts and air handlers are located entirely within the building thermal envelope.
2. Duct testing Is not mandatory for buildings complying by Section 405 of this code.
A written report of the results of the test shall be signed by the party conducting the lest and provided to the code official.
❑ R403.3.5 Building Cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
❑ R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C)
or below 55'F (13"C) shall be insulated to a minimum of R-3.
R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance, and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). Heated water circulation systems shall be in
accordance with Section R403.5.1.1. Heat trace lemmperature maintenance systems shall be in accordance with Section R403.5.1.2.
Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe
shall be dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited.
Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for how water within the
occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and
when there is no demand for hot water.
❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comp)yy with IEEE 515.1 or UL 515. Controls for such systems
shall automatically adjust the energy input to the heal tracing to maintain the desired water temperature in the piping in accordance
with the times when heated water Is used in the occupancy.
2019.Oct-1809:47.63
WvriglNtSoflE° Right -Su He® Universal 201919.0.13 RSU25344 Right-Energy®Florida 2017 Section 405.4.1 Compliant S0lware Page
...0 PrcjTlnals\Current\Sparks Renovation RE.rup Calc-MJ8 Fmnt Door faces: W
FORM R405-2017
MANDATORY REQUIREMENTS -(Continued)
R403.5.5 Heat traps (Mandatory). Storage water healers not equipped with integral heat traps and having vertical pipe risers shall have heat
traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 1/2 inches (89 mm) in the hot water distribution line and cold water line located as close as
possible to the storage tank.
❑ R403.5.6 Water heater efficiencies (Mandatory).
rl R403.5.6.1 Storage water heater temperature controls.
R403.5.6.1.1 Automatic controls. Service water heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be f rom 1007 to 140oF (38oC to 60oC).
R403.5.6.1.2 shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power suppplied
to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s)
of combustion types of service water heating systems to be turned off
El R403.5.6.2 Water heating equipment Water healing equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment
installed. Equipment used to provide heating functions as part of a combination system shall satisfy all staled requirements for the
appropriate water heating category. Solar water heaters shall met the criteria of Section R403.5.6.2.1.
R403.5.6.2.1 Solar water heating system. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9805, Test Methods for Solar Collectors,
and SRCC Standard TMA, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida
Building Code, Residential or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation, including:
Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the
ventilation system is not operating.
❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be powered by
an electronically commutated motor.
R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure of for mechanical
ventilation shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawls aces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air Is drawn from enclosed spaces(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum or R-19, space permitting, or R-10 otherwise.
rl R403.7 Heating and cooling equipment (Mandatory)
R403.7.1 Equipment sizing. Heating and coaling equipment shall be sized in accordance with ACCA Manual S based on the
equipment loads calculated in accordance with ACCA Manual J or other approved methodologies, heating and cooling calculation
based on building loads for the directional orientation of the building The manufacturer and model number of the outdoor and
indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1. This code does not allow designer safety factors, provisions for future expansion or other factors that
affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such
as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency
rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
CFM
MINIMUM EFFICACY (a)
CFM/WATT
AIRFLOW RATE MAXIMUM
CFM
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfri/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
< 90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm - 28.3 Umin.
(a) When tested in accordance HVI Standard 916
! - 2019.0d-1809:47:53
- � Wlrightsoft° Right-SuiteOUniversa1201919.0.13RSU25344 Rig ht-Enemy®Florida 2017 Section 405.4.1 Compliant Saftxare Page
•' ;iu6Nji.a::.r: e:.o:�; ...0 PropFinals\Curront\Sparks Renovation RE.rup Cole -MJ8 Front Door faces: W
MANDATORY REQUIREMENTS -(Continued)
R403.7.1.1 Cooling equipment capacity. Coolingg only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section 403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is
less than the calculated total sensible load but not less than 80 percent of that load.
2. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the
capacity of equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
R403:7.1.2.1 Heat pumps Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
R403.7.1.2.2 Electric resistance furnaces. Electric resistance fumaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1
R403.7.1.2.3 Fossil fuel heating equipment The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
C403 and C404 of the IECC•—Commercial Provisions in lieu of action R403.
R403.9 Snow melt and Ice system controls (Mandatory). Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the systemw hen the ppavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that w ill allow s hutoff w hen the outdoor temperature is above 40°F (4.8°C).
R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the healer thermostat. Such switches shall be in addition to a circuit breaker for the
power to the healer. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
R403.10.2 Time switches. Time switches or other control methods that can automatically turnoff and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operations.
2. Pumps that operate solar- and waste -heal -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor- retardant cover on or at
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
R403.10.4 Gas -and oil -fired pool and spa heaters. All gas -and oil -fired pool and spa heaters shall have a minimum thermal
efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heatersfired by natural or LP gas shall not have continuously burning pilot lights.
2019.0cl-18 09:47:53
=lwFightsoft? Right -Suite® Universal 201919.0.13 RSU25344 Right-Energy®Florida 2017 Section 405.4.1 Compliant So ware Page10
ir4�Yulai+ h+ri ... 0 Pro1lFina1s1CumentlSparks Renovation RE.rup Calc= We Front Odor laces: W
MANDATORY REQUIREMENTS - (Continued)
R403.10.5 Heat pump pool heaters. Heat pump pool healers shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
R403.11 Portable spas (Mandatory). The energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 75 percent of the lamps in permanently installed lighting fixtures shall be
high -efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high -efficacy lamps.
Exception: Low -voltage lighting.
❑ R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
P019-Oct-18 09:47:53
=F�F;rr;yh;pfit° RgM-Sude®UnNersa1201919.0.13RSU25344 Right-Enemy®Floritla2017 Section405.4.1CompliantSoftware pagell
iii44F ...OProflFinalslCumenllSparks Renovation RE.rup Cato =MJa Front Door faces: W
FORM R405-2017
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Sparks Renovation Builder Name
Street: 2358 S Brochsmith Rd Permit Office:
City, Stale, Zip: Ft. Pierce, FL 34945 Permi( Number:
Owner: Spparks Renovation Jurisdiction: St. Lucie County
Design Location: FL, St Lucie Co Intl
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
'0'
General
A continuous air barrier shall be installed in the
requirements
building envelope. The exterior thermal envelope
in
Air- enneable insulation shall not be used as a
seeping material.
❑
contains a continuous barrier. Breaks or joints the
air barrier shall be sealed.
Ceilinglattic
The air barrier in any dropped ceiling/soffit
The insulation in any dropped ceiling/soffit
shall be aligned with the insulation and any
shall be aligned with the air barrier.
gaps in the air barrier shall be sealed.
❑
Access openings, drop down stairs or knee wall doors
to unconditioned attics paces shall be sealed.
Walls
The junction of the foundation and sill plate
Cavities with comers and headers of frame walls
shall be sealed.The junction of the top plate
shall be insulated by completely filling the cavity
and the top of exterior walls shall be sealed.
with a material having a thermal resistance of R-3
❑
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope Insulation for framed
walls shall be installed Pn substantial contact and
continuous alignment with the air barrier
Windows, skylights
The space between window/doorjambs and framing,
❑
and doors
and skylights and framing shall be sealed.
-
Rim joists are Insulated and include an air
Rim joists shall be insulated.
❑
Rim joists
barrier.
Floors (Including
The air barrier shall be installed at any exposed
Floor framing cavity Insulation shall be installed
above -garage and
edge of insulation.
to maintain permanent contact with the underside
cantilevered floors)
of subfloor decking, or floor framing cavity
insulation shall be permitted to be in contact
❑
with the top sideof sheathing, or continuous
insulation installed on the underside of floor
framing and extends from the bottom to the top of
all perimeter floor framing members.
Crawl space
Exposed earth In unvented crawl spaces shall be
Where provided in lieu of floor insulation,
walls
covered with a Class I vapor retarder with
insulation shall be permanently attached
❑
overlapping joints taped.
to the crawlspace walls.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shaft
openings to exterior or unconditioned space shall
❑
be sealed.
Narrow cavities
Batts in narrow cavities shall be cut to fit, or
narrow cavities shall be filled by Insulation that
❑
on Installation readily conforms to the available
cavity spaces.
Garage
separation
Air sealing shall be provided between the garage
and conditioned spaces.
❑
Recessed
Recessed light fixtures installed in the building
Recessed light fixtures installed in the
lighting
thermal envelope shall be sealed to the drywall.
building thermal envelope shall be air tight
❑
and IC rated.
Plumbing and
Batt insulation shall be cut neatly to fit around
wiring
wiring and plumbing in exterior walls, or
Insulation that on installation readily conforms
❑
to available space shall extend behind piping
and wiring.
Shower/tub on
The air barrier shall be Installed behind
Exterior walls adjacent to showers and tubs
exterior wall
electrical or communication boxes or air -sealed
shall be Insulated.
❑
boxes shall be installed.
Electrical/phone
The alr barrier shall be Installed behind
on exterior
electrical or communication boxes or air -sealed
El
walls
boxes shall be installed.
HVAC register
HVAC register boots that penetrate building
boots
thermal envelope shall be sealed to the subfloor.
❑
or drywall.
Concealed
When required to be sealed, concealed fire
sprinklers
sprinklers shall only be sealed in a manner that
Is recommended by the manufacturer.
❑
Caulking or other adhesive sealants shall not be
used to fill voids between fire sprinkler cover
plates and walls or ceilings.
a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400.
2019-Oct-18 09:47:53
wrightsoft° Rig htSu e®Unverse1201919.0.13 RSU25344 Rig ht-Ene gy®Florida 2017 Section 405.4A Compriant Softxare Page 12
1aLYieeG'.8y'Ona.jr ... 0 PralFinals\Current\Sparks Renovation RE.rup Cale =MJ8 Front Door faces: W
FORM R405-2017
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction: St. Lucie County
Permit Number:
Job Information
Builder: Community: Lot:
Address: 2358 S Brochsmith Rd Unit:
City: Ft. Pierce State: FL Zip: 34945
Air Leakage Test Results Passing results must meet either the Performance; Prescriptive, or ERI Method.
❑. PRESCRIPTIVE METHOD The building or dwelling unit shall be tested and verifiad as having an aieleakage rate of not exceeding
- 7air changes per hour ate pressure of 0.2 inch w.g. (507 pascals) in Climate Zones l and 2.
❑, _ The building or dwelling unitshall be tested and verified as having an air leakage rate of not
PERFORMANCE oriERl METHOD exceeding the selected ACH(50) value, as shown on FORM R405-2017 (Performance).or
,., R406-2017 (ERI); section labeled as Infiltration,: sub -section ACH50.
ACH(50) specified on Form R405.2017-Energy Cale (Performance) or R406-2017 (ERI); 5.000
x60 + 34222 - Method for calculating building volume:
CFM(50) Building Volume ACH(50) ❑ Retrieved from architectural plans
❑ PASS 0 Code software calculated
❑ When ACH(50) is less than 3, Mechanical Ventilation installation ❑ Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSURESNET/ICC 380 and reported at a pressure of 0.2 inch w.g.
(50 Pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues, or individuals
licensed as set forth in Section 489.105(3)(1), (g), or (i) or and approved third party. A written report of the results of the lest shall be
signed by the party conducting the test and provided to the code official. Testing shall be performed at any lime after creation of all
penetrations of the building thermal envelope.
During testing:
1. Exteriorwindows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2017 6th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
2019-Oct-1e 09:47:53
,.r;Y{RIgt71;SOftQ Right-Suite®Universal201919.0.13RSU25344 Right-Energy®Fienda2017 Section405.4.1CompliantSoftware Page13
...0 ProtffinalslCurrent\Sparks Renovation RE.mp Cale= MJe Front Door faces: W
FORM R405-2017
Duct Leakage Test Report
Residential Perscriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Jurisdiction: St. Lucie County Permit Number:
Job InfoimatonJ
Builder: Community: Lot:
Address: 2358 S Brochsmith Rd Unit:
City: Ft. Pierce State: FL Zip: 34945
buctLeakage Test Results
System 1
cfm25
System 2
cfm25
System 3
cfm25
Sum of any
additional systems
cfm25
systet s0 a
cfm25
3307
Total of all T Total Conditioned
systems Square Footage
M1
❑ PASS ❑ FAIL
[] •Prescriptive Methodefmz5 (Total] „.
T.o.qualify as "sub stantially,leakfree" Qo,Totsl must be less' -
than or equal to 0.04 if air handier uhitris installed. If air handler
unit is not installed, Qn Total` must be less than or equal to
0.03, This testing method meets the requirements n .
accordance wiihdSection R403.3.3..
Is the, air'handler Unit installed, ![� YES r<=0,04on)
during testing? Np t b"o3 0"1
❑i "Performs_ nce /ERI Method cfm25 (Qut or Total},.;
To qualify using this method; Qri must be'not greater than the
proposed duct,leakage Qn specified on Form R41[t5;2017 or
R406-2017.`
Leakage Type "selected on Farm Qn specfied onForm R40S2017'.
R405-2017 (Energy Calc) or R40§-2011 • , (Energy,,Caic) or R406-20f7T '
Default Leakage
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set
forth in Section 489.105(3)(f), (g) or (1), Florida Statues.
Testing Company
Company Name: Phone:
I hereby verify that the above duct leakage test results are in accordance with the 2017 6th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
2019-OIX-18 09:47:53
m- ghtsoft' Right-SidleO Universal 201919.0.13 RSU25344 Right-EnergyO Florida 2017 Section 405.4.1 compliant Software Page 14
...0 PropFinals%Cunent\Sparks Renovation RE.rup Calc= MJ8 Front Doorfaces: W
Reference Home Characteristics
Sparks Renovation
2p58 S Brochsmith Rd
Ft. Pierce, FL 34945
Above -grade Walls (Uo)
Above -grade Wall Solar Absorptance
Above -grade Wall Infared Emittance
Basement Walls (Uo)
Above -grade Floors (Uo)
Slab Insulation R-Value
Ceilings (Uo)
Roof Solar Absorptance
Roof Infared Emittance
Attic VentArea (ft2)
Crawls pace Vent Area (ft�
Expose d Mason ry Fl oor Area (ft�
Carpet & Pad R-Value
Door Area (ft2)
Door U-Factor
North Window Area (fl:2)
South Window'Area (ft�
East Window Area (ft�
West Window Area (f12)
Window U-Factor
Window SHGC (Heating)
Window SHGC (Cooling)
ACH50
Internal Gains ` (Btu/day)
Water heater gallons per day
Water Heater set point temperature
Water heater efficiency rating
Labeled Heating System Rating and Efficiency
Labeled Cooling System Rating and Efficiency
Air Distribution System Efficiency
Thermostat Type
Heating Thermostat Settings
Title: Sparks Renovation RE
FLBase2017
0.084
0.75
0.90
n/a
n/a
0.0
0.035
0.75
0.90
2.33
n/a
661.30
2.0
40.00
0.500
92.67
92.67
92.67
92.67
0.500
0.2169
0.2169
7.00
139119
180.00
120.00
0.47
HSPF = 8.2
SEER = 14.0
0.88
Manual
72.0 (All hours)
TMY City: FL -Fort -Pierce